Goodman Mfg A-GPG13 M User Manual

INST ALLA TION & OPERA TING
INSTRUCTIONS for
A/GPG13 M SERIES W/R410A
SINGLE P ACKAGE GAS-ELECTRIC
HEA TING & COOLING UNIT
Affix this manual and Users Information Manual adjacent to the unit.
®
C
This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National S tandard of Canada Shown Below .
ANSI Z21.47•CSA-2.3 Central Furnaces
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor installation of single package gas electric heating and cooling units. See the Specification Sheet or Technical Manual applicable to your model* for information regarding accessories.
Goodman Manufacturing Company , L.P. IO-357A 5151 San Felipe, Suite 500, Houston, TX 77056 3/10 www.goodmanmfg.com
© 2009 - 2010 Goodman Manufacturing Company, L.P.
*NOTE: Please contact your distributor or
our website for the applicable
Specification Sheet or Technical Manual
referred to in this manual.
Index
Replacement Parts ...................................................................................................................................................................... 3
ORDERING PARTS ....................................................................................................................................................................... 3
Safety Instructions ....................................................................................................................................................................... 3
I
MPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY .................................................................................................. 3
Unit location ................................................................................................................................................................................. 4
A
LL INST ALLATIONS: .................................................................................................................................................................... 4
G
ROUND LEVEL INSTALLATIONS ONLY: ...........................................................................................................................................4
ROOFTOP INSTALLATIONS ONLY:..................................................................................................................................................... 5
R
OOF CURB INST ALLA TIONS ONLY: ................................................................................................................................................ 5
General Information .................................................................................................................................................................... 5
T
RANSPORTATION DAMAGE ............................................................................................................................................................. 6
Rigging Details ............................................................................................................................................................................. 6
Gas Piping .....................................................................................................................................................................................6
H
IGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) ..................................................................................................................... 6
P
IPING ....................................................................................................................................................................................... 6
G
AS PIPING CHECKS .................................................................................................................................................................. 7
Propane Gas Installations .......................................................................................................................................................... 8
TANKS AND PIPING...................................................................................................................................................................... 8
Electrical Wiring ..........................................................................................................................................................................8
T
HERMOSTAT LOCATION ................................................................................................................................................................8
U
NIT VOLT AGE ............................................................................................................................................................................ 9
H
EAT ANTICIPATOR SETTING .......................................................................................................................................................... 9
Circulating Air and Filters ........................................................................................................................................................ 10
A
IRFLOW CONVERSION .............................................................................................................................................................. 10
D
UCTWORK ..............................................................................................................................................................................10
FILTERS ................................................................................................................................................................................... 10
Venting......................................................................................................................................................................................... 11
F
LUE HOOD INSTALLATION ..........................................................................................................................................................11
Condensate Drain ...................................................................................................................................................................... 11
C
ONDENSATE DRAIN CONNECTION ............................................................................................................................................... 11
Normal Sequences of Operation ............................................................................................................................................. 11
H
EATING ................................................................................................................................................................................... 11
C
OOLING ................................................................................................................................................................................. 11
F
AN ONLY ................................................................................................................................................................................ 11
Startup, Adjustments, and Checks .......................................................................................................................................... 11
HEATING STARTUP......................................................................................................................................................................11
G
AS SUPPLY PRESSURE MEASUREMENT ...................................................................................................................................... 12
G
AS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT ......................................................................................................... 13
C
OOLING STARTUP .................................................................................................................................................................... 15
Troubleshooting .........................................................................................................................................................................15
I
GNITION CONTROL ERROR CODES ............................................................................................................................................. 15
ABNORMAL OPERATION - HEATING ..........................................................................................................................................15
ABNORMAL OPERATION - COOLING ......................................................................................................................................... 16
Maintenance............................................................................................................................................................................... 16
F
ILTER REPLACEMENT OR CLEANING ............................................................................................................................................ 16
CABINET FINISH MAINTENANCE ................................................................................................................................................... 17
C
LEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) ................................................................................................................... 17
C
ONDENSER, EVAPORA TOR, AND INDUCED DRAFT MOTORS ........................................................................................................... 17
F
LAME SENSOR (QUALIFIED SERVICER ONLY).............................................................................................................................. 17
F
LUE PASSAGES (QUALIFIED SERVICER ONLY)............................................................................................................................. 17
C
LEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY).............................................................................................................. 17
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) .....................................................................................................................17
C
LEANING BURNERS .................................................................................................................................................................17
Accessories and Functional Parts ...........................................................................................................................................18
S
HEET METAL ACCESSORIES ...................................................................................................................................................... 18
F
UNCTIONAL PARTS ...................................................................................................................................................................18
G
ENERAL INFORMATION ..............................................................................................................................................................18
APPENDIX ...................................................................................................................................................................................26
Unit Dimensions ......................................................................................................................................................................... 26
Minimum Clearances ................................................................................................................................................................ 35
Recommended Filter Sizes ......................................................................................................................................................35
2
REPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
SERVICE P ARTS DEP ARTMENT
GOODMAN MANUFACTURING COMP ANY, L.P .
5151 SAN FELIPE, SUITE 500
HOUSTON, TEXAS 77056
(713) 861 – 2500
SAFETY INSTRUCTIONS
TO THE INST ALLER
Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
WARNING
DO NOT CONNECT TO OR USE ANY DE VICE THAT IS NOT DESIGN CERTIFIED
BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/ CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.
WARNING
OR HAZARDOUS
IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty cer­tificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please contact your installing contractor or contact customer service (877-254-4729) to obtain a copy.
IMPORT ANT NOTICE TO GOODMAN
the 10 Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Full warranty details available at www.goodmanmfg.com.
IMPORT ANT NOTICE TO AMANA® BRAND OWNERS: T o receive the Lifetime Heat Exchanger Limited Warranty and the 10 Years Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Full warranty details available at www.amana-hac.com.
T o register your Goodman
®
brand unit, go to www.goodmanmfg.com. Click on the word “Warranty” located on the left side of the home page. Next, click on the word “Product Registration” located on the left side of the Warranty page and complete the forms in the man­ner indicated on the Product Registration page.
To register your Amana
®
brand unit, go to www.amana-hac.com. Click on the word “Warranty” located on the top right of the home page. Next, click on the word “Product Registration” located on the left side of the Warranty page and complete the forms in the man­ner indicated on the Product Registration page.
Product limited warranty certificates can be viewed at www.goodmanmfg.com or www.amana-hac.com. Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that spe­cific product. To view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online Product Registration pages are located in this same section.
Keep this literature in a safe place for future reference.
®
BRAND OWNERS: T o receive
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN
OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY.
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
WARNING
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE
T
I
THIS UNIT IF ANY PART HAS BEEN UNDER WATER. QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER.
MMEDIATELY CALL A
3
WARNING
CARBON MONOXIDE POISONING HAZARD
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUI DS OR VAPORS I N THE V ICINIT Y OF THI S APPL IANCE.
Special Warning for Installation of Furnaces or A ir Handling Units i n Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is oper ated therein, there must be adequate, direct outside ventilation.
UNIT LOCATION
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
ALL INSTALLATIONS:
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted level.
The flue outlet hood must be at least 12 inches from any
opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds.
T o avoid possible illness or death of the building occup ants,
do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see appendix). These clearances must be permanently maintained.
The combustion air inlet and flue outlet hoods on the unit
must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems.
When the unit is heating, the temperature of the return air
entering the unit must be between 50° F and 100° F.
GROUND LEVEL INSTALLATIONS ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runoff of water
from higher ground can collect in the unit.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclose d area. Carbon monox ide emissions can be (re)circulated throughout t he structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
B10259-216
4
Outside Slab Installation
ROOFTOP INSTALLATIONS ONLY:
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
To avoid possible property damage or personal injury, the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
ROOF CURB INSTALLATIONS ONLY:
Sufficient structural support must be determined prior to
locating and mounting the curb and package unit.
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before mounting the package unit.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor.
Rooftop Installation
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
Roof Curb Installation
GENERAL INFORMATION
WARNING
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE,
T
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED, AND MAINTAINED.
This unit is approved for outdoor installation ONLY. To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
5
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J ­Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
TRANSPORTATION DAMAGE
Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately.
Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be retightened. In the event of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging ma­terial according to local codes.
RIGGING DETAILS
Rigging
GAS PIPING
IMPORTANT NOTE: This unit is factory set to operate on natural gas at the altitudes shown on the rating plate.
WARNING
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER
T
USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL THE PROPER CONVERSIO N KIT(S). UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. KITS ARE FOR IN
ANADA.
C
U.S
. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPT-03. (LPT-00A may
be used on models with AA revisions. LPT-03 is compatible with both the White Rodgers and the Honeywell gas valves.)
AILURE TO DO SO CAN RESULT IN
F
IGH ALTITUDE
H
WARNING
O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
T
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.
Important: If using bottom discharge with roof curb, ductwork should
be attached to the curb prior to installing the unit. Ductwork dimen­sions are shown in roof curb installation instructions.
Refer to the Roof Curb Installation Instructions for proper curb in­stallation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.
T
O FACILITATE
Inlet Gas Pressure
Natural Min. 5.0" W.C., Max. 10.0" W.C.
Propane Min. 11.0" W.C., Max. 13.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.
The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)
IMPORT ANT NOTE: The gas/electric units naturally derate with al-
titude. Do not attempt to increase the firing rate by changing ori­fices or increasing the manifold pressure. This can cause poor com­bustion and equipment failure. At all altitudes, the manifold pres­sure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air tempera­ture rise must be within the range listed on the unit nameplate. Refer to the Installation Manual provided with the LP kit for conver­sion from natural gas to propane gas and for altitude adjustments. NOTE: Up to 7,000 feet, no changes are required; above 7,000 feet, refer to High Altitude Kit HA-02.
6
PIPING
p
)
g
)
IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not un­dersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously. The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Natural Gas Connection
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based
CFH =
Heatin
Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:
1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.
2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
5. Use two pipe wrenches when making connection to the gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8. The unit must be connected to the building piping by one of the following methods:
Rigid metallic pipe and fittings
Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)
Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment
In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage)
Nominal Black Pipe Size (inches)
1/2 3/4
on 0.60 S
1
ecific Gravity Gas
1 1/4 1 1/2
BTUH Furnace Input
Value of Gas (BTU/Cubic Foot
MANUAL SHUT-OFF VALVE
DRIP LEG
GROUND JO INT UNION (INSTALLED AHEAD OF GAS VALVE)
GROMMET
Proper Piping Practice
NOTE: The unit gas supply entrance is factory sealed with plugs.
Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommet s and install gas supply line.
GAS PIPING CHECKS
CAUTION
T
O PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING:
HE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE
T
PLACING IN OPERATION. FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. EXCEED SPECI FIED PRES SURES FOR TESTI NG. DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE.
HIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM
T
THE GAS S UPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSUR E S IN EX CES S OF 1/2
HIS UNI T MU ST BE I SOLAT ED FRO M THE GAS SUPPL Y SYS TEM BY
T
CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PI PING SYSTEM AT TEST PRESSURE S EQUAL TO OR LESS THAN 1/2
BECAUSE OF THE DANGER OF EXPLOSION OR
N
IGHER PRESSURE MAY
H
(3.48 KPA).
PSIG
(3.48 KPA).
PSIG
EVER
WARNING
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY
T
NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.
, BE SURE THERE IS
7
PROPANE GAS INSTALLATIONS
WARNING
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
T
OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DE VICE. OF ODORANT IN PROPANE GAS, A GAS DETECTING W ARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK.
ONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A
C
GAS DETECTING WARNING DEVICE.
INCE RUST CAN REDUCE THE LEVEL
S
IMPORTANT NOTE: Propane gas conversion kits must be
installed to convert units to propane gas. All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See NBFU Manual 58).
For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:
1. V aporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.
TANKS AND PIPING
Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
See below for typical propane gas piping.
First Stage Regulator
5 to 15 PSIG (20 PSIG Max.)
Continuous
11" W.C.
Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING
LENGTH,
FEET
30 309 700 1,303 2,205 3,394 1,843 3,854 40 265 599 1,115 1,887 2,904 1,577 3,298 50 235 531 988 1,672 2,574 1,398 2,923 60 213 481 896 1,515 2,332 1,267 2,649 70 196 446 824 1,394 2,146 1,165 2,437 80 182 412 767 1,297 1,996 1,084 2,267
90 171 386 719 1,217 1,873 1,017 2,127 100 161 365 679 1,149 1,769 961 2,009 150 130 293 546 923 1,421 772 1,613 200 111 251 467 790 1,216 660 1,381 250 90 222 414 700 1,078 585 1,224 300 89 201 378 634 976 530 1,109 350 82 185 345 584 898 488 1,020 400 76 172 321 543 836 454 949
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130 To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance* Maximum Propane Capacities Lis ted are Based on 1/2" W.C. Pressure Drop at 11" W.C. Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING
LENGTH,
FEET
10 49 110 206 348 539 291 608 1,146 2,353 3,525 20 34 76 141 239 368 200 418 788 1,617 2,423 30 27 61 114 192 296 161 336 632 1,299 1,946 40 23 52 97 164 253 137 284 541 1,111 1,665 50 20 46 86 146 224 122 255 480 985 1,476 60 19 42 78 132 203 110 231 436 892 1,337
80 16 36 67 113 174 94 198 372 764 1,144 100 14 32 59 100 154 84 175 330 677 1,014 125 12 28 52 89 137 74 155 292 600 899 150 11 26 48 80 124 67 141 265 544 815 200 10 22 41 69 106 58 120 227 465 697 250 9 19 36 61 94 51 107 201 412 618 300 8 18 33 55 85 46 97 182 374 560 350 7 16 30 51 78 43 89 167 344 515 400 7 15 28 47 73 40 83 156 320 479
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
NOMINAL PIPE SIZE,
NOMINAL PIPE SIZE,
SCHEDULE 40
SCHEDULE 40
Table 3 - Propane Gas Pipe Sizing
WARNING
200 PSIG Maximum
Second Stage Regulator
Typical Propane Gas Piping
T
O PREVENT PROPERTY DAMAGE OR SERIOUS PERSONAL INJURY DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE.
F THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A
I
CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE TO:
ROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN
P
SETTLE IN ANY LOW AREAS OR CONFINED SPACES.
ROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE
P
EXCEPT WITH A WARNING DEVICE.
ELECTRICAL WIRING
THERMOSTAT LOCATION
Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation.
8
Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air duct s in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions.
All units have one stage of heating and one stage of mechanical cooling. Units which will have economizers may use thermostats with one or two stages of cooling.
The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. 24 volt wiring must be connected between the unit control panel and the room thermostat.
CAUTION
O PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRORS,
T
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
ERIFY PROPER OPERATION AFTER SERVICING.
V
For unit protection, use a time delay fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DA T A PLA TE.
All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring.
Note:Junction box location shown is optional and is for illustration purposes only.
JUNCTION BOX
1068-83-400A
B18099-18
K4
K3
WYR
C
G
LOW VOLTAGE
CONNECTOR
MODEL
1068-400
24VAC 50/60Hz 400mA MAX.
ANSI Z21.20 AUTO M A TIC IGN IT ION S Y STEM
COMPRE SSOR
BREAK FOR T W O S TA G E
T2
K2
K1
R
12
12
12
11
Y
W G
11
11
10
10
10
F1
FUSE 3 AMP MAX
T1
C22
Low Voltage Wiring
Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof.
COOL
L2L2L2L2
L1 HEATUNUSED
L1DI
9FS6
3
3
659
9
6
3
2
2
8
8
5
7
4
1
1
7
4
12
7
4
P1
ECON 120 135
P3
150
P2
SPEED-UP
Electrical Power Directly To Junction Box
Electrical Power Ro uted Th roug h Botto m of Unit
Typical Electrical Wiring Unit Voltage
UNIT VOLTAGE
The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram.
WARNING
O AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE
T
POLARIZED AND GROUNDED.
CAUTION
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
T
ONLY COPPER CONDUCTORS.
HEAT ANTICIPATOR SETTING
The heat anticipator is to be set by measuring the load (amperage) at the “R” circuit. Follow the instructions provided by the thermostat for more details.
9
G
Y
R
W
R
From
Unit
W Y G
Typical Thermostat and Unit 24 V Wiring Hookup
CIRCULATING AIR AND FILTERS
AIRFLOW CONVERSION
Units can easily be converted from horizontal to down­discharge airflow delivery. In down-discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow.
Horizontal Air Flow (Applies to 3 phase models)
Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman’s Service Parts department.
Remove supply and return duct covers which are attached to the unit as shown below.
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis).
DUCTWORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix.
For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
Remove these covers for horizontal duct applications
FILTERS
CAUTION
T
O PREVENT PRO PERTY DAMAG E DUE TO FIRE AND LOSS O F EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. All units may be externally filtered.
Refer to the unit filter size chart in the appendix for filter size information.
Filters installed external to the unit should be sized in accordance with their manufacturer recommendations. A throwaway filter must be sized for a maximum face velocity of 300 feet per minute.
Filter Installation
Important: When installing a filter, the air flow arrows on the
filter must point toward the circulator blower.
Duct Cover Installation
10
VENTING
NOTE: Venting is self-cont ained. Do not modify or block.
FLUE HOOD INSTALLATION
Install the exhaust flue hood and combustion air intake hood prior to operation of the unit.
To install the flue hood cover, please refer to IO-653*, included in the flue hood assembly box located in the blower compartment.
2. The spark igniter and gas valve energizes for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas.
3. The 30-second HEAT FAN ON delay time begins.
4. The unit delivers heat to the conditioned space until the thermostat is satisfied.
5. The gas valve deenergizes. The induced draft blower continues operation for a 29-second post-purge.
6. Ignition control begins timing the HEAT FAN OFF delay. There is an adjustable HEAT FAN OFF delay of approximately 120/135/150 seconds (factory set at 150). After the HEA T F AN OFF delay time has elapsed, the blower will deenergize. This allows any additional heat in the heat exchanger to be transferred to the conditioned space.
COOLING
1. Thermostat calls for cooling. The compressor and outdoor fan are energized.
2. Approximately seven seconds later, the indoor fan starts.
3. The unit will deliver cooling to the conditioned space until the thermostat is satisfied.
4. The compressor and outdoor fan will be de-energized when the thermostat opens.
5. The indoor fan continues to run for approximately 60 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor fan stops.
Flue Hood and Bug Screen Installation
CONDENSATE DRAIN
CONDENSATE DRAIN CONNECTION
A 3/4” NPT drain connection is supplied for condensate piping. An external trap must be installed for proper condensate drainage. NOTE: Maximum torque is 10 in-lbs.
DRAIN CONNECTION
UNIT 2" MIN IMUM
FLEXIBLE TUBING-HOSE OR PIPE
A POSIT IVE L I QUID SEAL IS REQU IRE D
3" MIN IMUM
Drain Connection
NORMAL SEQUENCES OF OPERATION
HEATING
This unit is equipped with an ignition control that automatically lights the main burner. DO NOT attempt to light the main burners by any other method.
1. Thermostat calls for heat. The induced draft blower energizes for a 15-second pre-purge.
NOTE: A 180-second anti-short cycle is integral to the control and prevents recycling of the compressor.
FAN ONLY
1. Thermostat calls for FAN ONLY by energizing “G”.
2. Approximately seven seconds later, the indoor fan starts.
3. The indoor fan continues to run for approximately 60 seconds after “G” is de-energized.
STARTUP, ADJUSTMENTS, AND CHECKS
HEATING STARTUP
This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower to exhaust combustion products.
On new installations, or if a major component has been replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct covers must
be removed before operating unit.
Heat Anticipator Setting
Set the heat anticipator on the room thermostat to 0.4 amps to obtain the proper number of heating cycles per hour and to prevent the room temperature from overshooting the room thermostat setting.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control.
11
WARNING
T
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
T
OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE.
Rollout Protection
8. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 3 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position.
9. Replace the heat exchanger door on the side of the unit.
10. Open the manual gas valve external to the unit.
11. Turn on the electrical power supply to the unit.
12. Set the thermostat to desired setting.
Rollout Protection on Burner Bracket
Secondary Limit Control
The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting.
If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset.
Secondary
Control Lim it
IN L E T
Inlet Pressure Tap
OUTLE
Gas Valve
On/Off
Selector
Switch
White-Rodgers 36G22
Pressu re Regulator (under cap screw)
Outlet Pressure Tap
Gas Valve On/Off Selector Switch
Honeywell Model VR8215 (Single-Stage)
Back of Unit
Secondary Limit Control
Pre-Operation Checks
1. Close the manual gas valve external to the unit.
2. Turn off the electrical power supply to the unit.
3. Set the room thermostat to its lowest possible setting.
4. Remove the heat exchanger door on the side of the unit by removing screws.
5. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method.
6. Move the gas control valve switch to the OFF position. Do not force.
7. Wait five minutes to clear out any gas.
Gas Supply And Manifold Check
Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.
GAS SUPPLY PRESSURE MEASUREMENT
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE
I
NLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING
.
12
The line pressure supplied to the gas valve must be within the range specified in the chart on the next page. The supply pressure can be measured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must be measured with the unit OFF. To measure inlet pressure, use the following procedure.
Gas Valve
On/Off
OUTLET
Pressure Regulator
Adjustment
(Under Cap Screw)
White-Rodgers Model 36G22
Selector
Switch
Outlet Pressure
Inlet Pres s ur e
Tap
INLET
Tap
Pressu re Regulator
Inlet Pressure Tap
(under cap screw)
Outlet Pressure Tap
8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below. If supply pressure reading differs from the table, make necessary adjustments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.
Inlet Gas Supply Pressure
Natural Gas
Propane Gas
9.Turn OFF all electrical power and gas supply to the system.
10. Remove the manometer hose from the hose barb fitting or inlet pressure boss.
11. Replace inlet pressure tap:
a. Honeywell VR8215 valve:
Remove the 1/8” NPT hose barb fitting from the inlet pressure tap. Replace the inlet pressure boss plug and seal with a high quality thread sealer.
b. White-Rodgers 36G22 valve:
Turn inlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).
12.Retest for leaks. If bubbles form, SHUT DOWN GAS AND REPAIR LEAKS IMMEDIA TEL Y .
13. Turn ON electrical power and gas supply to the system.
14.Turn valve switch ON.
Minimum:5.0" W.C. Maximum :10.0" W.C. Minimum:11.0" W.C. Maximum :13.0" W.C.
GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT
Gas Valve On/Off Selector Switch
Honeywell Model VR8215 (Single-Stage)
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2. Turn OFF all electrical power to the system.
3. Inlet pressure tap connections:
a. Honeywell VR8215 Valve:
Remove the inlet pressure boss plug. Install an 1/8” NPT hose barb fitting into the outlet pressure tap.
b. White-Rodgers 36G22 valve:
Back inlet pressure test screw (inlet pressure boss) out one turn (counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or inlet pressure boss (White­Rodgers valve).
5. Turn ON the gas supply.
6. Turn On power and close thermostat “R” and “W” contacts to provide a call for heat.
7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY!
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE
I
NLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING
This valve is shipped from the factory with the regulator preset (see control label). Consult the appliance rating plate to ensure burner manifold pres­sure is as specified. If another outlet pressure is required, follow these steps.
1. Turn OFF gas to furnace at the manual gas shutoff valve
2. Turn OFF all electrical power to the system.
3. Outlet pressure tap connections: a. Honeywell VR8215 valve:
b. White-Rodgers 36G22 valve:
4. Attach a hose and manometer to the outlet pressure barb
5. Turn ON the gas supply.
.
external to the furnace.
Remove the outlet pressure boss plug. Install an 1/8” NPT hose barb fitting into the outlet pressure tap.
Back outlet pressure test screw (outlet pressure boss) out one turn (counterclockwise, not more than one turn).
fitting (Honeywell valve) or outlet pressure boss (White­Rodgers valve).
13
6. Turn ON power and close thermostat “R” and “W” contacts to provide a call for heat.
7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIA TELY!
8. Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.
Manifold Gas Pressure
Natural Gas 3.5" w.c.
Propane Gas 10.0" w.c.
9. Remove regulator cover screw from the outlet pressure regulator and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.
10.Turn OFF all electrical power and gas supply to the system.
11. Remove the manometer hose from the hose barb fitting or outlet pressure boss.
12. Replace outlet pressure tap:
a. Honeywell VR8215 valve:
Remove the 1/8” NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure boss plug and seal with a high quality thread sealer.
b. White-Rodgers 36G22 valve: Turn outlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb minimum).
13. Turn ON electrical power and gas supply to the system.
14. Close thermostat contacts to provide a call for heat.
15. Retest for leaks. If bubbles form, SHUT OFF GAS AND REP AIR ALL LEAKS IMMEDIA TELY!
Gas Input (Natural Gas Only) Check
To measure the gas input use a gas meter and proceed as follows:
1. Turn off gas supply to all other appliances except the unit.
2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.
4. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating.
Main Burner Flame Check
Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off.
Temperature Rise Check
Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained.
1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking readings.
2. The temperature rise must be within the range specified on the rating plate.
NOTE: Air temperature rise is the temperature difference between supply and return air.
With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise.
NOTE: Blower speed MUST be set to give the correct air tempera­ture rise through the unit as marked on the rating plate.
External Static Pressure Check
The total external static pressure must be checked on this unit to determine if the airflow is proper.
Blower Speed Adjustments
WARNING
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE
ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE BLOWER MOTOR.
Refer to the wiring diagram in the appendix to verify speed tap settings.
For models equipped with PSC type motors, blower speeds are to be changed at the ignition control board. Both heat speed and cool speed terminals are supplied on the board along with two unused motor lead terminals.
Some models are equipped with X-13 motors. X-13 motors are constant torque motors with very low power consumption. This motor is energized by 24V . Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor.
Heating-White Lead Cooling-Yellow Lead T1 - Low Speed T4 - Low Speed T2 - Medium Speed T5 - High Speed T3 - High Speed
NOTE: Heating airflow must be adjusted to provide the tempera­ture rise shown on rating plate.
Limit Check
Check limit control operation after 15 minutes of operation by blocking the return air grille(s).
1. After several minutes the main burners must go OFF. Blower will continue to run.
2. Remove air restrictions and main burners will relight after a cool down period of a few minutes.
14
Adjust the thermostat setting below room temperature.
1
2
3
10
11
12
9
6
23
6
5
8
9
11
12
L2
L2L2
L2
D1
L1
L1 UNUSED
HEAT
COOL
FS
K2
K1
R8
R10
R3
K4
K3
R31
LED
1
0
6
8
-
8
3
-
4
0
0
A
C27
D3 R38
D9 D10
R34
R35
R4
R11 R42
D12
R36
D11
D14
C20
Z
1
R29
R22
C13
R25
D5
D7
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for 120, 135 or 150 seconds, depending on the setting.
Control Board (Top)
NOTE: If necessary, adjust fan OFF delay settings to obtain satis-
factory comfort level.
To ensure the unit is properly charged for the intended application, check the unit refrigerant superheat at the compressor. The refrigerant superheat is a function of outdoor ambient temperature and return air temperature of the conditioned space. It is the installing contractors responsibility to ensure the proper refrigerant superheat at the compressor is adjusted for each application. For example, 10 degree refrigerant superheat level is adequate for a 95 degree outdoor ambient temperature and a 78 - 80 degree for indoor return air temperature. As the outdoor ambient temperature rises the superheat decreases and as the outdoor ambient temperature lowers the superheat increases. Proper superheat adjustment optimizes cooling performance.
Cooling Operation
NOTE: Mechanical cooling cannot be reliably provided at ambient
temperatures below 50° F.
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired).
3. Set the room thermostat to the desired temperature.
TROUBLESHOOTING
IGNITION CONTROL ERROR CODES
The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.
Unit Shutdown
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the unit.
3. Remove the heat exchanger door on the side of the unit by removing screws.
4. Move the gas control valve switch to the OFF position. Do not force.
5. Close manual gas shutoff valve external to the unit.
6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be desired, turn ON the electrical power.
COOLING STARTUP
NOTE: Check all manual reset limit controls in heating circuit if
cooling mode does not operate.
Compressor Protection Devices
The compressor includes components which are designed to protect the compressor against abnormal operating conditions.
WARNING
O PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL
T
POWER BEFORE INSPECTING OR S ERVICING T HE UNIT. PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR AND OUTDOOR FAN.
Cooling Refrigerant Charging
Check unit charge before putting the cooling section into full operation. The unit is factory charged with R-410A for nominal air flow and static pressure conditions. The unit has a piston flowrator expansion device.
ALL COMPRESSOR
Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.
ABNORMAL OPERATION - HEATING
Internal Control Failure
If the integrated ignition control in this unit encounters an internal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control.
External Lockout
An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is de-energized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state.
If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle for four (4) consecutive ignition attempts (five attempts total) before locking out.
15
The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perform the following checks:
Check the supply and manifold pressures
Check the gas orifices for debris
Check gas valve for proper operation
Check secondary limit
A dirty filter, excessive duct static, insufficient air flow , a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly.
Check rollout limit
If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit.
Check flame sensor
A drop in flame signal can be caused by nearly invisible coating on the sensor. Remove the sensor and carefully clean with steel wool.
Check wiring
Check wiring for opens/shorts and miswiring. Important: If you have to frequently reset your gas/electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information.
Pressure Switch Stuck Open
A pressure switch stuck open can be caused by a faulty pressure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower.
If the control senses an open pressure switch during the pre­purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is de-energized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic fault code is two flashes.
Pressure Switch Stuck Closed
A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower remains off. The diagnostic LED code for this fault is three (3) flashes.
Open Thermal Protection Device
If the primary limit switch opens, the gas valve is immediately de-energized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diagnostic fault code for an open limit is four (4) flashes.
A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.
Flame Detected with Gas Valve Closed
If flame is detected with the gas valve de-energized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault.
ABNORMAL OPERATION - COOLING
Short Cycle Compressor Delay
The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the compressor contactor output is being delayed.
NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time.
MAINTENANCE
Have the gas heating section of the unit checked at least once a year before the heating season begins, to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a properly operating vent system.
FILTER REPLACEMENT OR CLEANING
A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), or return air filter grille(s). Consult with your installing dealer for the actual location of the return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent filters should last several years. However, should one become torn or uncleanable, it should be replaced.
16
CABINET FINISH MAINTENANCE
Use a fine grade automotive wax on the cabinet finish to maintain the finish’s original high luster. This is especially important in installations with extended periods of direct sunlight.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris.
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS
Bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated. No additional oiling is required.
5. When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed.
6. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in “Startup, Adjustments, and Checks”.
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)
Flames should be stable, soft and blue (dust may cause orange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
A drop in the flame current can be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool.
NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC.
Flame Sensor
Flame Sensor
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and, if necessary , clean the unit flue passage.
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)
1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line and removing the manifold bracket from the partition panel.
3. Remove the flue from the induced draft blower and the collector box cover from the partition panel.
4. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube.
Check the burner flames for:
1. Good adjustment
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
Burner Flame
WARNING
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,
T
DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. FLAME SHOULD DEVELOP.
ONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL
C
At least once a year, prior to or during the heating season, make a visual check of the burner flames.
NOTE: This will involve removing and reinstalling the heat exchanger door on the unit, which is held by two screws. If you are uncertain about your ability to do this, contact a qualified servicer. If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not pos­sible.
CLEANING BURNERS
1. Shut off electric power and gas supply to the unit.
2. Remove the screws securing the manifold to the burner retention bracket. Remove the manifold and rotate each burner counterclockwise to remove.
Burner
Burner Bracket
Manifold
Manifold Assembly
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the burners.
17
5. Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots.
6. Reconnect electrical power and gas supply.
CAUTION
ABEL ALL WIRES PRIOR TO DI SCONNECTI ON WHEN S ERVICING CONTRO LS.
L
IRING ERRORS CAN CAUSE IMPRO PER AND DANG EROUS OPERAT ION.
W
CAUTION
LWAYS VERIFY PROPER OPERATI ON AFTER S ERVICIN G.
A
For further information on the yearly inspection, consult the User Manual. It is recommended that a qualified servicer inspect and service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.
ACCESSORIES AND FUNCTIONAL PARTS
SHEET METAL ACCESSORIES
Additional accessories can be purchased to fit specific application needs. Parts and instructions are available from your distributor.
FUNCTIONAL PARTS
FUNCTI ONAL P ARTS
Aux iliary Lim it S wit c h Flam e Roll-out S witc h Blower Hous ing Flam e S ens or Circulator B lower Mot or G as O rific e Blower Wheel G as V alve Burner Heat E x c hanger Capacit or High Limit S witch Compres sor Igniter Condenser Coil Ignition Control Condenser Fan B lade Induced Draft Blower Condenser Fan M ot or Pres s ure Swit c h Contactor Pressure Switch Hose Gas Manifold Transformer Evaporator Coil
Functional Parts List
GENERAL INFORMATION
1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the unit model and serial numbers with the order.
2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description.
3. Parts are available from your distributor.
18
5259
6
9403
5
BLOWER PERFORMANCE DA T A - SINGLE PHASE
R
*PG1324045M 41A * - Rise Ra nge: 30° - 60°
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 600 150 0.67 57 850 230 1.02 40 1,190 380 1.67 NR
0.2 570 140 0.65 60 830 220 1.00 41 1,140 360 1.62 NR
0.3 510 130 0.63 NR 765 215 0.97 45 1,080 350 1.58 32
0.4
0.5
0.6 -------- -------- -------- NR 610 195 0.88 56 920 310 1.37 37
0.7 -------- -------- -------- NR -------- -------- -------- NR 830 300 1.35 4 1
0.8
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 600 150 0.67 NR 850 230 1.02 NR 1,190 380 1.67 43
0.2 570 140 0.65 NR 830 220 1.00 NR 1,140 360 1.62 45
0.3 510 130 0.63 NR 765 215 0.97 NR 1,080 350 1.58 47
0.4
0.5
0.6 -------- -------- -------- NR 610 195 0.88 NR 920 310 1.37 56
0.7 -------- -------- -------- NR -------- -------- -------- NR 830 300 1.35 6 2
0.8
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RI SE
0.1 1,056 350 1.51 33 1,261 452 1.95 NR 1,370 509 2.23 NR
0.2 1,010 339 1.43 34 1,221 442 1.90 NR 1,310 492 2.13 NR
0.3 971 343 1.45 36 1,174 428 1.84 NR 1,262 489 2.09 NR
0.4
0.5
0.6 811 306 1.29 43 1,004 380 1.66 34 1, 081 440 1.90 32
0.7 723 291 1.21 48 919 368 1.59 38 1,006 425 1.88 34
0.8
450 125 0.61 NR 715 210 0 .94 48 1,025 340 1.54 33 380 120 0.58 NR 660 205 0 .90 52 975 330 1.38 35
-------- -------- -------- NR -------- -------- -------- NR 730 290 1.32 47
450 125 0.61 NR 715 210 0.94 NR 1,025 340 1.54 50 380 120 0.58 NR 660 205 0.90 NR 975 330 1.38 52
-------- -------- -------- NR -------- -------- -------- NR 730 290 1.32 N
937 329 1.41 37 1,125 414 1.80 878 318 1.27 39 1,063 398 1.70
54
LOW MEDIUM HIGH
*PG1324070M 41A * - Rise Ra nge: 35° - 65°
LOW MEDIUM HIGH
*P G1330045 M4 1A* - Ri se Range: 30° - 60°
LOW MED IUM HIGH
1.10 NR 796 371 1.4
31 32
43
1,208 475 2.06 NR 1,140 453 1.93 30
87
1.74 39
*PG133070M41A* - Rise Range: 35° -65°
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RI SE
0.1 1,056 350 1.51 49 1,261 452 1.95 41 1,370 509 2.23 38
0.2
0.3
0.4 937 329 1.41 55 1,125 414 1.80 46 1,208 475 2.06 43
0.5 878 318 1.27 59 1,063 398 1.70 49 1,140 453 1.93 45
0.6 811 306 1.29 64 1,004 380 1.66 52 1,081 440 1.90 48
0.7 723 291 1.21 NR 919 368 1.59 56 1,006 425 1.88 NR
0.8
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
1,010 339 1.43 51 1,221 442 1.90
971 343 1.45 53 1,174 428 1.84
545 259 1.10 NR 796 371 1.46
LOW MED IUM HIGH
42 44
6
1,310 492 2.13 40 1,262 489 2.09 41
879 403 1.74 NR
19
BLOWER PERFORMANCE DA T A - SINGLE PHASE
8
945852
8
9
2
*PG 1336045M41A * - Rise Range: 30 -6 0°
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,029 346 1.51 34 1,337 471 2.08 NR 1,462 596 2.64 NR
0.2 982 334 1.46 35 1,265 452 2.01 NR 1,398 563 2.58 NR
0.3 946 329 1.40 36 1,227 448 1.97 NR 1,326 550 2.50 NR
0.4
0.5
0.6 750 287 1.23 46 1,008 393 1.71 34 1,090 496 2.22 32
0.7 668 271 1.16 52 895 371 1.61 39 997 478 2.18 35
0.8
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,029 346 1.51 50 1,337 471 2.08 39 1,462 596 2.64 35
0.2 982 334 1.46 53 1,265 452 2.01 41 1,398 563 2.58 37
0.3 946 329 1.40 55 1,227 448 1.97 42 1,326 550 2.50 39
0.4 888 313 1.38 58 1,159 429 1.87 45 1,260 534 2.42 41
0.5 823 304 1.29 63 1,073 405 1.73 48 1,188 513 2.34 44
0.6 750 287 1.23 NR 1,008 393 1.71 51 1,090 496 2.22 47
0.7
0.8
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,029 346 1.51 50 1,337 471 2.08 NR 1,462 596 2.64 NR
0.2 982 334 1.46 53 1,265 452 2.01 NR 1,398 563 2.58 NR
0.3 946 329 1.40 55 1,227 448 1.97 NR 1,326 550 2.50 NR
0.4
0.5
0.6 750 287 1.23 69 1,008 393 1.71 51 1,090 496 2.22 47
0.7 668 271 1.16 NR 895 371 1.61 58 997 478 2.18 52
0.8
888 313 1.38 823 304 1.29
454 23
668 271 1.16 NR 895 371 1.61 454 238 1.00 NR 760 346 1.49
888 313 1.38 58 1,159 429 1.87 823 304 1.29 63 1,073 405 1.73
454 23
LOW MEDIUM HIGH
39 42
1.00 NR 760 346 1.4
LOW MEDIUM HIGH
LOW MEDIUM HIGH
1.00 NR 760 346 1.4
1,159 429 1.87 30 1,260 534 2.42 NR 1,073 405 1.73 32 1,188 513 2.34 NR
454 2.12 40
*P G133 6070M41A* - Rise Range: 35° - 65°
REMOVED AA & USED A*
*P G133 6090M41A* - Rise Range: 45° - 75°
58 68
45 48
68
997 478 2.18 52 852 454 2.12 61
1,260 534 2.42 1,188 513 2.34
85
454 2.12
NR NR
61
*PG1342070 M4 1A* - Rise Range: 35° - 65°
Unit
Static CFM WATT S AMPS R ISE C FM WATTS AMPS RISE CFM W ATT S AMPS R ISE
0.1 1,100 340 1.55 46 1,450 480 2.15 35 1,575 585 2.64 NR
0.2 1,040 325 1.49 49 1,390 460 2.06 37 1,515 565 2.58 NR
0.3 1,000 320 1.44 51 1,300 445 1.98 39 1,430 550 2.50 36
0.4
0.5
0.6 800 275 1.22 64 1,030 375 1.71 50 1,130 465 2.22 45
0.7 690 255 1.16 NR 945 350 1.60 54 1,010 450 2.18 51
0.8
Unit
Static CFM WATT S AMPS R ISE C FM WATTS AMPS RISE CFM W ATT S AMPS R ISE
0.1 1,100 340 1.55 62 1,450 480 2.15 47 1,575 585 2.64 NR
0.2 1,040 325 1.49 66 1,390 460 2.06 49 1,515 565 2.58 45
0.3 1,000 320 1.44 68 1,300 445 1.98 52 1,430 550 2.50 48
0.4
0.5
0.6 800 275 1.22 NR 1,030 375 1.71 66 1,130 465 2.22 60
0.7 690 255 1.16 NR 945 350 1.60 72 1,010 450 2.18 67
0.8
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
925 305 1.38 55 1,215 425 1.89 860 290 1.32 59 1,115 395 1.79
-------- -------- -------- NR 860 335 1.54
925 305 1.38 74 1,215 425 1.89 860 290 1.32 NR 1,115 395 1.79
-------- -------- -------- NR 860 335 1.54
LOW MEDIU M HIGH
42 46
59
*PG1342090 M4 1A* - Rise Range: 45° - 75°
LOW MEDIU M HIGH
56 61
NR
1,340 525 2.42 1,240 505 2.34
910 430 2.12
1,340 525 2.42 1,240 505 2.34
910 430 2.12
20
38 41
56
51 55
75
9
9
BLOWER PERFORMANCE DA T A - SINGLE PHASE
* P G134 8070M41A* - Rise Ra nge: 35° - 65°
Unit
Static C FM W ATTS AMPS R ISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- --------
0.2 914 125 1.07 56 1,105 186 1.56 46 1,397 323 2.57 NR
0.3 822 134 1.14 62 1,024 193 1.60 50 1,346 331 2.67 NR
0.4
0.5
0.6 606 154 1.28 NR 816 220 1.75 62 1,178 359 2.88 NR
0.7 584 162 1.32 NR 769 230 1.85 66 1,120 369 2.97 45
0.8
733 140 1.20 69 967 202 1.65 664 150 1.26 NR 884 214 1.76
551 164 1.34 NR 698 236 1.8
T1 HEAT ING SPEED T2 HEATING SPEED T3 HEATING SPEED
53 58
73
1,288 342 2.76 1,273 352 2.82
1,057 381 3.09
NR NR
48
Unit
Static CFM WATTS AMPS C FM WATT S AMPS
0.1 -------- -------- -------- -------- -------- --------
0.2 1,593 449 3.55 1,669 532 4.22
0.3 1,545 463 3.69 1,654 239 4.25
0.4 1,506 476 3.82 1,610 551 4.30
0.5
0.6
0.7 1,341 502 4.00 1,433 578 4.59
0.8
Unit
Static C FM W ATTS AMPS R ISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- --------
0.2 914 125 1.07 75 1,105 186 1.56 62 1,397 323 2.57 49
0.3 822 134 1.14 NR 1,024 193 1.60 67 1,346 331 2.67 51
0.4 733 140 1.20 NR 967 202 1.65 71 1,288 342 2.76 53
0.5
0.6
0.7 584 162 1.32 NR 769 230 1.85 NR 1,120 369 2.97 61
0.8
Unit
Static CFM WATTS AMPS C FM WATT S AMPS
0.1 -------- -------- -------- -------- -------- --------
0.2 1,593 449 3.55 1,669 532 4.22
0.3 1,545 463 3.69 1,654 239 4.25
0.4 1,506 476 3.82 1,610 551 4.30
0.5 1,448 481 3.87 1,545 557 4.36
0.6
0.7
0.8
T4 COOL IN G SPEED T 5 COOLI NG SPEE D
1,448 481 3.87 1,545 557 4.36 1,400 493 3.95 1,512 566 4.41
1289 511 4.11 1,392 591 4.65
* P G134 8090M41A* - Rise Ra nge: 45° - 75°
T1 HEAT ING SPEED T2 HEATING SPEED T3 HEATING SPEED
664 150 1.26 NR 884 214 1.76 606 154 1.28 NR 816 220 1.75
551 164 1.34 NR 698 236 1.8
T4 COOL IN G SPEED T 5 COOLI NG SPEE D
1,400 493 3.95 1,512 566 4.41 1,341 502 4.00 1,433 578 4.59
1289 511 4.11 1,392 591 4.65
NR NR
NR
1,273 352 2.82 1,178 359 2.88
1,057 381 3.09
54 58
65
*PG1 3480115M4 1A* - Ri se Range: 45° - 75°
Unit
Static C FM W ATTS AMPS R ISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- --------
0.2 914 125 1.07 NR 1,105 186 1.56 77 1,397 323 2.57 61
0.3 822 134 1.14 NR 1,024 193 1.60 N R 1,346 331 2.67 63
0.4 733 140 1.20 NR 967 202 1.65 NR 1,288 342 2.76 66
0.5 664 150 1.26 NR 884 214 1.76 NR 1,273 352 2.82 67
0.6
0.7
0.8
Unit
Static CFM WATTS AMPS C FM WATT S AMPS
0.1 -------- -------- -------- -------- -------- --------
0.2 1,593 449 3.55 1,669 532 4.22
0.3 1,545 463 3.69 1,654 239 4.25
0.4 1,506 476 3.82 1,610 551 4.30
0.5 1,448 481 3.87 1,545 557 4.36
0.6 1,400 493 3.95 1,512 566 4.41
0.7
0.8
606 154 1.28 NR 816 220 1.75 584 162 1.32 NR 769 230 1.85 551 164 1.34 NR 698 236 1.89
1,341 502 4.00 1,433 578 4.59
1289 511 4.11 1,392 591 4.65
T1 HEAT ING SPEED T2 HEATING SPEED T3 HEATING SPEED
NR NR NR
T4 COOL IN G SPEED T 5 COOLI NG SPEE D
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
1,178 359 2.88 1,120 369 2.97 1,057 381 3.09
72 NR NR
21
BLOWER PERFORMANCE DA T A - SINGLE PHASE
2562
2562
*PG136090M41A* - Rise Range: 45° - 75°
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,125 162 1. 44 61 1,466 315 2.67 47 1,780 496 3.33 NR
0.2 1,049 168 1. 53 65 1,384 322 2.74 50 1,730 506 3.89 NR
0.3 1,000 178 1. 60 69 1,347 329 2.78 51 1,664 520 4.01 NR
0.4
0.5
0.6 809 201 1.83 NR 1,185 362 3.05 58 1,515 546 4.14 45
0.7 739 207 1.86 NR 1,134 369 3.09 60 1,477 552 4.18 46
0.8
T1 HEATIN G SPEED T2 HEATIN G SPEED T3 HEATING SPEED
910 18 4 1.64 75 1,291 341 2.83 857 197 1.75 NR 1,237 350 2.90
703 218 1.96 NR 1,087 382 3.21
53 55
63
1,608 526 4.03 1,568 532 4.12
1,42
4.23
NR NR
48
Unit
Static CFM WATTS AMPS CFM WATTS AMPS
0.1 1,942 649 4. 83 2,067 792 5.81
0.2 1,883 657 4. 87 2,030 811 5.85
0.3 1,859 670 4. 96 1,982 814 5.88
0.4 1,827 675 4. 97 1,909 808 5.86
0.5
0.6
0.7 1,655 703 5. 12 1,703 763 5.58
0.8
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,125 162 1. 44 NR 1,466 315 2.67 58 1,780 496 3.33 48
0.2 1,049 168 1. 53 NR 1,384 322 2.74 62 1,730 506 3.89 49
0.3 1,000 178 1. 60 NR 1,347 329 2.78 63 1,664 520 4.01 51
0.4 910 184 1.64 NR 1,291 341 2.83 66 1,608 526 4.03 53
0.5
0.6
0.7 739 207 1.86 NR 1,134 369 3.09 NR 1,477 552 4.18 58
0.8
Unit
Static CFM WATTS AMPS CFM WATTS AMPS
0.1 1,942 649 4. 83 2,067 792 5.81
0.2 1,883 657 4. 87 2,030 811 5.85
0.3 1,859 670 4. 96 1,982 814 5.88
0.4 1,827 675 4. 97 1,909 808 5.86
0.5 1,749 683 4. 99 1,842 798 5.85
0.6
0.7
0.8
T4 COOLING SPEED T5 COOLING SPEED
1,749 683 4.99 1,842 798 5.85 1,706 693 5.10 1,789 772 5.65
1,588 705 5.11 1,618 732 5.29
*PG1360115M41A* - Rise Range: 45° - 75°
T2 HEATING SPEEDT1 HEATIN G SPEED
857 197 1.75 NR 1,237 350 2.90 809 201 1.83 NR 1,185 362 3.05
703 218 1.96 NR 1,087 382 3.21
T4 COOLING SPEED T5 COOLING SPEED
1,706 693 5.10 1,789 772 5.65 1,655 703 5.12 1,703 763 5.58 1,588 705 5.11 1,618 732 5.29
69 72
NR
T3 HEATING SPEED
1,568 532 4.12 1,515 546 4.14
1,42
4.23
54 56
60
*PG1360140M41A* - Rise Range: 45° - 75°
Unit
Static CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1,125 162 1. 44 NR 1,466 315 2.67 71 1,780 496 3.33 59
0.2 1,049 168 1. 53 NR 1,384 322 2.74 NR 1,730 506 3.89 60
0.3 1,000 178 1. 60 NR 1,347 329 2.78 NR 1,664 520 4.01 63
0.4 910 184 1.64 NR 1,291 341 2.83 NR 1,608 526 4.03 65
0.5 857 197 1.75 NR 1,237 350 2.90 NR 1,568 532 4.12 67
0.6
0.7
0.8
Unit
Static CFM WATTS AMPS CFM WATTS AMPS
0.1 1,942 649 4. 83 2,067 792 5.81
0.2 1,883 657 4. 87 2,030 811 5.85
0.3 1,859 670 4. 96 1,982 814 5.88
0.4 1,827 675 4. 97 1,909 808 5.86
0.5 1,749 683 4. 99 1,842 798 5.85
0.6 1,706 693 5. 10 1,789 772 5.65
0.7
0.8
1,655 703 5.12 1,703 763 5.58 1,588 705 5.11 1,618 732 5.29
T1 HEATIN G SPEED
809 201 1.83 NR 1,185 362 3.05 NR 1,515 546 4.14 739 207 1.86 NR 1,134 369 3.09 NR 1,477 552 4.18 703 218 1.96 NR 1,087 382 3.21 NR 1,422 562 4.23
T4 COOLING SPEED T5 COOLING SPEED
T2 HEATING SPEED
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
T3 HEATING SPEED
69 71 74
22
BLOWER PERFORMANCE DA T A - HEA TING SPEEDS THREE PHASE
R
GPG133 6090M 43A* - Rise Range: 45° - 75°
Unit
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1100 342 1.57 62 1469 494 2.24 47 1655 604 2.67 NR
0.2 1037 335 1.52 66 1409 480 2.15 49 1579 587 2.68 NR
0.3 991 320 1.45 69 1327 459 2.08 52 1483 567 2.62 46
0.4 926 308 1.39
0.5 831 290 1.32
0.6 773 279 1.25 NR 1094 398 1.80 63 1210 498 2.35 57
0.7 669 260 1.17 NR 942 363 1.65 73 1036 464 2.24 66
0.8------------
Unit
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1
0.2
0.3 822 134 1.14 NR 1,024 193 1.60 67 1,346 331 2.67 51
0.4 733 140 1.20 NR 967 202 1.65 71 1,288 342 2.76 53
0.5 664 150 1.26 NR 884 214 1.76 NR 1,273 352 2.82 54
0.6 606 154 1.28 NR 816 220 1.75 NR 1,178 359 2.88 58
0.7 584 162 1.32 NR 769 230 1.85 NR 1,120 369 2.97 61
0.8
Unit
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1125 162 1.44 61 1466 315 2.67 47 1780 496 3.33 NR
0.2 1049 168 1.53 65 1384 322 2.74 50 1730 506 3.89 NR
0.3 1000 178 1.60 69 1347 329 2.78 51 1664 520 4.01 NR
0.4 910 184 1.64 75 1291 341 2.83 53 1608 526 4.03 NR
0.5 857 197 1.75
0.6 809 201 1.83
0.7 739 207 1.86 93 1134 369 3.09 60 1477 552 4.18 46
0.8 703 218 1.96
-------- -------- -------- -------- -------- -------- -------- -------- -------- -------- -------- --------
T1 HEATING SPEED T2 HEATING SPEED T3 HEATING SPEED
914 125 1.07 75 1,105 186 1.56
551 164 1.34 NR 698 236 1.89
LOW MEDIUM HIGH
74
NR
GPG1348090M43A* - Rise Range: 45° - 75°
GPG136 0090M 43A* - Rise Range: 45° - 75°
L OW - T1 MEDI U M - T2 HI GH - T3
80 85
97
1257 442 2.00 1163 419 1.89
1237 350 2.9 1185 362 3.05
1087 382 3.21
55 59
62
NR
55 58
63
1407 547 2.53 1329 522 2.44
1,397 323 2.57
1,057 381 3.09
1568 532 4.12 1515 546 4.14
1422 562 4.23
49 52
49
65
NR
45
48
GPG136 0140M 43A* - Rise Range: 45° - 75°
Unit
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS RISE
0.1 1125 162 1.44 NR 1466 315 2.67 NR 1780 496 3.33 59
0.2 1049 168 1.53 NR 1384 322 2.74 NR 1730 506 3.89 60
0.3 1000 178 1.6 NR 1347 329 2.78 NR 1664 520 4.01 63
0.4 910 184 1.64
0.5 857 197 1.75
0.6 809 201 1.83 NR 1185 362 3.05 N R 1515 546 4.14 69
0.7 739 207 1.86 NR 1134 369 3.09 N R 1477 552 4.18 71
0.8 703 218 1.96
L OW - T1 MEDI U M - T2 HI GH - T3
NR NR
NR
1291 341 2.83 1237 350 2.9
1087 382 3.21
NR NR
N
1608 526 4.03 1568 532 4.12
1422 562 4.23
65 67
72
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
23
BLOWER PERFORMANCE DA T A - COOLING SPEEDS THREE PHASE
S
GPG1336* * * M4 3A * - COOLI N G SPEEDS
Unit
Static CFM Watts RPM Amps CFM Watts RPM Amps CFM Watts RPM Amps
0.1 1,655 604 878 2.67 1,469 494 804 2.24 1,100 342 665 1.57
0.2 1,579 587 903 2.68 1,409 480 833 2.15 1,037 335 697 1.52
0.3 1,483 567 925 2.62 1,327 459 866 2.08 991 320 760 1.45
0.4 1,407 547 953 2.53 1,257 442 903 2 926 308 818 1.39
0.5 1,329 522 980 2.44 1,163 419 942 1.89 831 290 872 1.32
0.6 1,210 498 1,004 2.35 1,094 398 968 1.8 773 279 902 1.25
0.7 1,036 464 1,033 2.24 942 363 1,002 1.65 669 260 945 1.17
0.8------------
Unit
Static CFM WATT S AMPS CFM WATTS AMPS
0.1 -------- -------- -------- -------- -------- --------
0.2 1,593 449 3.55 1,669 532 4.22
0.3
0.4
0.5 1,448 481 3.87 1,545 557 4.36
0.6 1,400 493 3.95 1,512 566 4.41
0.7 1,341 502 4.00 1,433 578 4.59
0.8
HIGH (Cooling Speed) MEDIUM (Cooling Speed) LOW (Cooling Speed)
GP G1348* **M43A* - Ris e Range: 45° - 7 5°
T 4 COOL ING SPEED T5 CO OLING SPEED
1,545 463 3.69 1,654 239 4.25 1,506 476 3.82 1,610 551 4.30
1289 511 4.11 1,392 591 4.65
GP G1 36 0** *M 43 A* - COOLIN G SPE ED S
Unit
Static CFM WATTS RPM AMPS C FM W ATTS RPM AMP
0.1 1942 649 993 4.83 2067 792 1054 5.81
0.2 1883 657 1010 4.87 2030 811 1077 5.85
0.3 1859 670 1029 4.96 1982 814 1088 5.88
0.4 1827 675 1047 4.97 1909 808 1101 5.86
0.5 1749 683 1069 4.99 1842 798 1110 5.85
0.6 1706 693 1083 5.10 1789 772 1117 5.65
0.7 1655 703 1104 5.12 1703 763 1129 5.58
0.8 1588 705 1120 5.11 1618 732 1135 5.29
T4 (Cooling Speed) T5 (Cooling Speed)
NR = Heating T emperature Rise Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
24
Circulator Blower
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART
Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Off Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch Stuck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay (Cooling Only)
HEA TING TIMING CHART
100 %
OFF
Gas Valve
Igniter
Induced Draft Blower
Thermostat
Seconds
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0 15 22 45 52 0 29 120, 135,150
COOLING TIMING CHAR T
Circulator Blower
Outdoor Fan
and
Compressor
Thermostat
ON
OFF
ON
OFF
ON
OFF
100%
25
APPENDIX
A
UNIT DIMENSIONS
FLUE EXHAUST
HOOD
FLUE EXHAUST
B
HEA T E XCHANGE ACCESS PANEL
B
POWER WIRE ENTRANC E
CONTROL WIRE ENTRANCE
EXHAUST FLUE HOOD
BLOWER ACCESS PAN EL
26
*PG13(24,30,36,42)1** WIRING DIAGRAM
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
P
Y
B
B
CH OPTIONAL
CONNECTED AT L1, L2
NOTE 3
BR
R
PU(L2)
BL
MEDI UM
B
HIGH
PU
BR
CAP.2
ALT. 3 SPEED MOTOR
ALS
SCR
COMP
CM
NOTE 4
LOW
EM
3SPEED
OPTIONA L
PU
B
1
CAP2
BR BR
EM
32
B
4SPEED MOTOR
R
B
PU
B
BL
BL
LS
BL
BL
R
R
T1
T2
R
L1
L2
GR
CC
1C2
TRANS
BL
208
24V
B
PU
PU
240
R
GRD
Y
B
CH OPTIONAL
B
POW ER SUPPLY 208-230/1/60
3
R
SEENOTE6
B
NOTE 2
HPS
Y
BL/ PK
BL/PK
54
R
Y
BL
PU
BL
Y
R
Y
Y
Y
PU
PU
BL
PS
NOTE 5
RS
SEE NOT E 5
W. R.
GAS VALVE
GV
VM
PU
Y
Y
3
2 5
1 4
PL
(ALT.) HONEYWELL
GAS VALV E
PU
BL
R
PU
B
B
G
Y
Y
6
BL
PU
Y
R
PU
W
MV
GV
MV
IGN
FS
BL
Y
Y1
Y/Y2
TO THC
(SEE THC FIELD WIRING BELOW)
PU
CR
O
R
G
WG
O
R
R
PU
PU
BR
Y
1
2
3
L2
NOTE 4
ECON
7
4
89
56
DI
L1
UNUSE D
HEAT
COOL
10
11
12
FS
IIC
BL
Y
R
B
CAP
F CH
R
0140G01233 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
27
*PG13(24,30,36,42)1** WIRING DIAGRAM
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
L1
CC
L1
L1
T1
C
COMP
C
L1 L1
H
L1
D1
SUPPLY VOLT AGE
R
S H
208-230/1/60
CH
T2
C
CAP1
F
(HIGH)
(LOW)
TRANS
NOTE 3
CM
NOTE 4
VM
CC
CAP 2
EM
NOTE 2
1
4
5
9
FUSE
IIC
FS
3
6
8
ECON
7
10
12
11
LS
ALS
PS
IGN
FS
RS
HPS
GV
CC
NOTE 5
PL
RG
TO THC
Y/Y2WY1
C
INSTALLER/SERVICEMAN
THE STATUS L IGHT ON THE F URNACE CONTROL MAY BE USED AS AGUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHTCODES ARE AS FOLLOWS:
STATUS LIGHT
ON
OFF
1BLINK
2BLINKS
3BLINKS
4BLINKS
5BLINKS 6BLINKS
EQUIP. STATUS
NORMAL OPERATION
NO POWER OR
INTERNA L CO NTROL
FAULT
IGNITION FAILURE
OR
OPEN ROLLOUT
SWIT CH
OR
OPEN AUX. LIMI T
SWIT CH
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITH OUT INDUCER ON
OPEN LIMIT SWIT CH
FALSE FLAME SEN SED
COMPRES SOR
OUTPUT DELAY
CHECK
-
CHECK INPU TPOWER CHECK FUSE ON CONTROL REPLACE CONTROL
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. L IMIT OPEN
CHECK
PRESSU RE SWIT CH
CHECK
PRESSU RE SWIT CH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
3MIN.COMP.
ANTI-CYCLE TIMER
L2
L2
L2
L2
L2
65
23
MPONENT LEGEND
CO
ALS AUXILIARY L IMIT SWITCH CAP C AP ACITOR COMP C OMPRESSO R CM CONDENSER MOTOR CC CONTACT OR CH CRANKC ASE HEA TER EM EVAPORATOR MOTOR
FS FL AME SEN SOR GV GAS VALVE IIC INTEGRATED IGNITION CONTROL IGN IG NITOR LS LIMIT SWITCH PL PLU G PS PRESSU RE SWITCH
RS ROLLOUT SW ITCH THC THERMOSTAT HEAT & COOL TRANS TRANSFORMER
2
VM VENT MOTOR
HPS HIGH PRESSURE SWITCH
NOTES
1. REPLAC EMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(U SE COPPER CONDUCTOR ON L Y ).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE
FROM TERMINAL 3 TO TERMIN AL 2 ON TRANSFORMER.
3. CRANKCA SE H EA TER ( OPTIONAL).
4. F OR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING
SPEED A T COOL TERM INAL (IIC). CHANG E HEATIN G SPE ED AT H EAT TERMINAL (IIC)
4SPE
ED MOTOR B - HIGH SPEED BL - MED IUM H IGH SPEED Y - MEDIUM LOW SPEED
4
1
R - LOW SPE ED
5. A CCESSORY ECONOMI ZER PLUG AD JACENT TO BLOWER HOU SING IN RETURN AIR COMPARMENT.
6. USE C OPPER W IRE
WIRE SPLICE MARKED TERMINAL UNMARKED TERMINAL
WIRIN
LINE VOLTAGE LOW VOLTAGE
FIELD INSTALLED POWER FIELD INSTALLED CONTROL
BBLACK BL BLUE BR BROW N GGREEN OORANGE PK PINK PU PURPLE RRED WWHITE
Y YELLOW
BL/PK BLUE/PIN K
ED MOTOR
3SPE B - HIGH SPEE D BL - ME DIUM SPEED
R - LO W S PEED
THC-FIELD W IRING
THC-N O ECONOMIZER
W W
G
R
Y
BL C
G
R
Y
2 STAGE COOLING WITH ECONOMIZER
0140G01233 REV. A
G
WIRE CO
W
G
BL
DE
208-230/1/60
W
G
RR
Y1PU
Y2Y
C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
28
BK
(
BK
CH OPTIONAL
CONNECTED AT L1, L2
NOTE 3
BR
BL
RS
COMP
CM
*PG13(48,60)1** WIRING DIAGRAM
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEA TH.
YL BK
RD PU
C
BK BL
BL
T2T1
YL
L2L1
C
PU
PU
3
1
2
POWER SUPPL Y 208-230/1/60 SEE NOTE 6
HPS
BK
BK
GR
PU
LS
RD
BK
208
TR
24V
3
2
240
4
VMR
1
C
RD
GND
CH OPTIONAL
BL/PK BL/PK
BL
YL
YL
RD
BR
BL
WH
YL
WH YL
PU
PU
GAS VALVE
VM
ALS
PS
RS
W. R.
C
EM
PLF
ALT.) HONEYWELL
PU
GV
BL
BL
RD PU BL
BR
NGL
NOTE 4
PU
YL
YL
Y
3
YL
GAS VALVE
GR
6 5412
MV
MV
GV
FS
IGN
YL
PU
YL WH
BL
YL
SEE NOTE 5
Y/Y2
Y1
OR
RD
BL
RD
BL
BL
RD
RD
RD
WH
RD
OR
YL
YL
BL
BL
WGCR
SEE NOTE 7
IIC
RD
WH
YL
BR
PU
RCCF
HCF
RD
YL
0140G01234 REV A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
29
*PG13(48,60)1** WIRING DIAGRAM
A
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
L1
C
T1
L
N
EM
NOTE 7 NOTE 7
L1
F
4
5
9
TO THERMOSTAT
IIC
C H
3 6 8
7
10
C
FS
D1
12 11
SUPPLY VOLTAGE
208-230/1/60
CH
R S
NOTE 2
2
3
LS
ALS
PS
Y/Y2
Y1WGR
NOTE 3
HFC
1
TR
IGN
VMR
RS
HPS
T2
CM
VMR
4
FS
GV
C
C
2
EM31C
C
NOTE
5
PLF
VM
L2
IIC
56
4
321
FA
OMPONENT LEGEND
C
AUXILIARY LIMIT SWITCH
LS
COMP
COMPRESSOR CONDENSER MOTOR
CM
CONTACTOR
C
CRANKCASE HEATER
CH
EM
EVAPORATOR MOTOR FUSEF
FS
FLAME SENSOR
GND
EQUIPMENT GROUND GAS VALVE
GV
IIC
INTEGRATED IGNITION CONTROL IGNITOR
IGN LS
LIMIT SWITCH
PLF
FEMALE PLUG/CONNECTOR
PS
PRESSURE SWITCH RUN CAPACITOR FOR COMPRESSOR/FANRCCF
RS
ROLLOUT SWITCH
TR TRANSFORMER VM
VENT MOTOR
VMR
VENT MOTOR REL AY
HPS
HIGH PRESSURE SWITCH
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE B L ACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING
SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING SPEED A T MOTOR T1, T2 AND T3 TERMINALS.
C
OOLING SPEED (YELLOW WIRE) T4 - LOW SPEED T5 - HIGH SPEED
5. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOW ER HOUSING IN RETURN AIR COMPARMENT .
6. USE COOPER CONDUCTORS ONLY .
USE NEC CLASS 2 WIRE.
H
EATING SPEED (WHIT E W IRE) T1 - LOW SPEED T2 - MED. SPEED T3 - HIGH SPEED
CTORY WIRING
LINE VOLTAGE LOW VOL TAGE OPTIONAL HIGH VOLTAGE
D WIRING
FIEL
H IGH VOLT AGE LOW VOL TAGE
WI
RE CODE BK BLACK BL BLUE
BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE RD RED WH WHITE
YL YELLOW
BL/PK BLUE/PINK
208-230/1/60
STATUS LIGHT
ON
OFF
1 BLINK
2 BLINKS
3 BLINKS
4 BLINKS
5 BLINKS
6 BLINKS
INST ALLER /SERVICEMAN
EQUIP. STATUS CHECK
NORMAL OPERATION
NO POWER OR
INTERNAL CONTROL
FAULT
IGNITION FAILURE
OR
OPEN ROLLOUT
SWITCH
OR
OPEN AUX. LIMIT
SWITCH
PRESSURE SWITCH
OPEN
WITHOUT INDUCER ON
OPEN LIMIT SWITCH
FALSE FL A ME SE NSED
COMPRESSOR
OUTPUT DELAY
-
GAS FLOW
GA S PR E SSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
3 MIN. COMP.
NO ECONOMIZER
THERMOSTAT FIEL D WIRING
WH GR RD YL BL
W G R Y C
2 STAGE COOLING WITH ECONOMIZER
GR RD
YL BL
0140G01234 REV A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
30
WWH G R
Y1PU
Y2
C
BK
BK
CH OPTIONAL
CONNECTED AT L1, L2
NOTE 3
BR
PU
FC
PU
COMP
CM
NOTE 4
BR
T2 T1T3
PU
BK
EM
3 SPEED
MOTOR
GPG13(36)3** WIRING DIAGRAM
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL
RD
PU
BL BL
LS
RD BK BL
BK
BK
BL
BL
BK
PU
R D
R D
PU
T2T1
T3
L2
L1
C
1
C
208
L3
3
2
240
TR
24V
BL
RD
BK BK
NOTE 2
HPS
GND
CH OPTIONAL SEE NOTE 3
POWER SUPPLY 208-230/3/60 SEE NOTE 6
BK
BL/PK
BL/PK
RD
YL
BR BL PU
PU
BL
ALS
PS
RS
NOTE 5
W. R.
GAS VALVE
GV
VM
PU
YL
YL
PLF
(ALT.) HONEYWELL
GAS VALVE
PU
BL
RD PU
BK
RD
YL
GR
YL
YL
6523
41
YL
MV
MV
IGN
GV
FS
PU
BL
PU
RD
WH
BL
YL
RC
PU
GR
PU
W
Y1Y/Y2
RD
OR
G
O R
RD
RD
PU
PU
BR
NOTE 4
ECON
FS
IIC
BK RD
BK
FC
BL
BL
CF
YL
BK
RD
0140G01001 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
31
GPG13(36)3** WIRING DIAGRAM
A
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
L1
C
IIC
L1
1
F
4 5
IIC
9
R G
SUPPLY VO LTAG E
208-230/3/60
NOTE 3
T2T1
T1
T3
C H
FS
3
6
8
7
10
12 11
CH
C
NOTE 4
C
FC
E
M
G V
C
T3
T2
C
F
CM
(MED)
V M
2
3
LS
AL
S
PS
1
NOTE 2
T R
IG
N
FS
RS
HPS
NOTE 5
Y/Y2W Y1
C
PLF
L3L2
56
32
COMPONE
COMP CM C CH EM F FC FS
GND GV
IIC IGN LS PLF PS RS
2
TR TRANSFORMER VM
HPS
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING
4
5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT
1
6. USE COOPER CONDUCTORS ONLY.
NT LEGEND
AUXILIARY LIMIT SWITCH
LS
COMPRESSOR CONDENSER MOT OR CONTACTOR CRANKCASE HEATER EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE
INTEGRATED IGNITION CONTROL IGNITOR LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH
VENT MOTOR HIGH PRESSURE SWITCH
SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT TERMINAL (IIC)
3 SPEED MOTOR BK - HIGH SPEED BL - MEDIUM SPEED RD - LOW SPEED
TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.
USE NEC CLASS 2 WIRE.
FACTOR
LINE VOLTAGE
LOW VOLTAGE OPTIONAL HIGH VOLT AGE
Y WIRING
FIELD
WIRING
HIGH VOLTAGE LOW VOLTAGE
W
IRE CODE
BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE RD RED
WH WHITE
YL YELLOW
BL/PK BLUE/PINK
208-230/3/60
STATUS LIGHT
ON
OFF
1 BLINK
2 BLINKS 3 BLINKS 4 BLINKS 5 BLINKS
6 BLINKS
INSTALLER/SERVICEMAN
EQUIP. STATUS
NORMAL OPERATION
NO POWE R OR
INTERNAL CONTROL
FAULT
IGNITION FAILURE
OR
OPEN ROLLOUT
SWITCH
OR
OPEN AUX. LIMIT
SWITCH
PRESSURE SWITCH
OPEN
WITHOUT INDUCER ON
FALSE FLAME SENSED
COMPRESSOR
OUTPUT DEL AY
CHECK
-
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPENOPEN LIMIT SWITCH
BAD SWITCH
3 MIN. COMP.
NO ECONOMIZER
THERMOSTAT FIELD WIRING
WH GR RD YL BL
W G R Y
C
2 STAGE COOLING WITH ECONOMIZER OPTION
WH GR RD PU
BL
0140G01001 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
32
W G R
Y1
Y2
C
BK
BK
CH OPTIONAL
CONNECTED AT L1, L2
NOTE 3
BR
COMP
PU
BK
GPG13(48,60)3** WIRING DIAGRAM
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL
RD
BK
PU
BK
BL
BL
BL
T2 T3
T1
GND
YL
L2
L1
C
L3
BK
CH OPTIONAL
POWER SUPPLY
208-230/3/60
SEE NOTE 6
RD
BR WH
BL
YL
BL
WH YL
PU
PU
GAS VALV E
VM
ALS
PS
RS
NOTE 5
W. R.
CM
C LEMG
PU
YL YL
PLF
(ALT.) HONEYWELL
PU
GV
BL
BL
RD
PU BL
BR
BK
GR
N
NOTE 4
GR
YL
3 6 2
5
1 4
YL
GAS VALVE
MV
GV
MV
FS
IGN
PU
YL
PU
YL WH
BL
Y/Y2
C
LS
RD
RD
BL
BL
RG
W
Y1
RD
OR
1 23 C
BL
BLTRBL
208
24V
240
RD
SEE NOTE 7
RD
YL WH
OR
VMR
YL
BR
BK
3
4
1
2
RD
WH
BL
YL RD
RD
HPS
BL/PK
BL/PK
IIC
RD
FC
RD
0140G01002 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
33
GPG13(48,60)3** WIRING DIAGRAM
A
HIGH VOLTA GE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
T1
T1
L
EM
7
SUPPLY VOLTAGE
208-230/3/60
CH
T2 T3
FC
N
FS
C H
D1
3 6 8
10
12 11
3
NOTE 3
T2
CM
2
LS
ALS
PS
C
T3
C
VMR
VM
1
TR
RS
IGN
1
FS
3
VMR
HPS
GV
C
NOTE 7
EM
C
L1
C
NOTE 7
1 2
F
4 5
IIC
9
5
R G
TO THERMOSTAT
WY1
Y/Y2
NOTE
C
PLF
65
L3L2
COMPONEN
LS COMP CM C CH
L3
EM FFUSE FC FS
GND
GV
IIC
4
IIC
IGN
PLF PS RS
TR VM
VMR
NO
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF
INSULATION AS ORIGINAL .(USE COPPER CONDUCTOR ONLY).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIR E
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING
4
5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT
123
6. USE COOPER CONDUCTORS ONLY.
7. L1 AND L2 ON ICC CONTROL IS 24V INPUT.
T LEGEND
AUXILIARY LIMIT SWITCH COMPRESSOR CONDENSER MOTOR CONTACTOR CRANKCASE HEATER EVAPORATOR MOTOR
FAN CAPACITOR FLAME SENSOR
EQUIPMENT GROUND GAS VALVE INTEGRATED IGNITION CONTROL IGNITOR LIMIT SWITCHLS FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH
TRANSFORMER VENT MOTOR
VENT MOTOR RELAY
HIGH PRESS U RE SWITCHHPS
TES
SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING SPEED AT MOTOR T1, T2 AND T3 TERMINALS.
COOLING
SPEED (YELLOW WIRE) T4 - LOW SPEED T5 - HIGH SPEED
TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.
USE NEC CLASS 2 WIRE.
HEA T1 - LOW SPEED T2 - MED. SPEED T3 - HIGH SPEED
FACTORY WIRING
LINE VOLTAGE LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIE
LD WIRING
HIGH VOLTAGE LOW VOLTAGE
W
IRE CODE
BK BLACK
BL BLUE BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE RD RE D
WH WHITE
YL YELLOW
BL/PK BLUE/PINK
TING SPEED (WHITE WIRE)
208-230/3/60
STATUS LIGHT
ON
OFF
1 BLINK
2 BLINKS 3 BLINKS 4 BLINKS 5 BLINKS
6 BLINKS
INSTALLER/SERVICEMAN
EQUIP. STAT US
NORMAL OPERATION
NO POWER OR
INTERNAL CO NTRO L
FAULT
IGNITION FAILURE
OR
OPEN ROLLOUT
SWITCH
OR
OPEN AUX. LIMIT
SWITCH
PRESSURE SWITCH
OPEN
WITHOUT INDUCER ON
OPEN LIMIT SWITCH
FALSE FLAME SENSED
COMPRESSOR
OUTPUT DELAY
CHECK
-
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
3 MIN. COMP.
NO ECONOMIZER
THERMOSTAT FIELD W IRING
WH GR RD YL BL
W
G R Y
C
2 STAGE COOLING WITH ECONOMIZER OPTION
WH GR RD PU YL BL
0140G01002 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
34
W G R
Y1
Y2
C
48" MIN
MINIMUM CLEARANCES
12" MIN
3"
.
12" MIN
NOTE: Roof overhang should be no more than 36".
UNIT 2 Ton 2 1/2 Ton 3 Ton 3 1/2 / 4 Ton 5 Ton
Min. Filter Size (1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1
MIN
36" MIN
(FOR SERVICE)
-
RECOMMENDED FILTER SIZES
35
NOTE: SPECIFICATIONS AND PERFORMANCE DA TA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
Quality Makes the Difference!
All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have designed these units to significantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit is run tested before it leaves the factory.
That’s why we know . . .There’ s No Better Quality.
• Products • Parts
• Warranties • Contractor Programs and Training
• Customer Services • Financing Options
Visit our website at www.goodmanmfg.com for information on:
© 2009 - 2010 Goodman Manufacturing Company, L.P.
36
Loading...