Goodman SSZ160601A, SSZ160481A, SSZ160361A, SSZ160241A User Manual

TECHNICAL INFORMATION MANUAL
Models listed
SSZ 16 SEER Split System Heat Pumps
Refer to Service Manual RS6200005 for installation, op-
eration, and troubleshooting information.
All safety information must be followed as provided in the
Service Manual.
Refer to the appropriate Parts Catalog for part number
information.
on page 3
®
This manual is to be used by qualified, professionally trained HVAC techni­cians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
Copyright © 2006-2007 Goodman Manufacturing Company, L.P.
September 2007
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
S S Z 16 036 1 A A
Brand Name
G: Goodman
(Standard Feature Set Models)
S: Goodman
(High Feature Set Models)
Product Family
S: Split System
Product Type
C: Condenser R-22 X: Condenser R-410A H: Heat Pump R-22 Z: Heat Pump R-410A
SEER
SEER Rating
Minor Revision
A: Initial Release
Major Revision
A: Initial Release
Electrical
1: 208/230V/60Hz/1ph
3: 208/230V/60Hz/3ph 4: 460V/60Hz/3ph
Nominal Capacity
024: 2 tons 036: 3 tons 048: 4 tons 060: 5 tons
HIGH VOLTAGE!
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
2
Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Installation and repair of this unit should be performed ONLY by individu­als meeting the requirements of an "entry level technician" as specified by the Air Conditioning and Refrigeration Institute (ARI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death.
Goodman will not be responsible for any injury or property damage arising from improper service or service procedures. If you install or perform service on this unit, you assume responsibility for any personal injury or property damage which may result. Many jurisdictions require a license to install or service heating and air conditioning equipment.
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
SSZ160241A* SSZ160361A* SSZ160481A* SSZ160601A*
* Indicates minor revision & is not used for order entry or inventory management
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
The United States Environmental Protection Agency (“EPA”) has issued vari­ous regulations regarding the introduction and disposal of refrigerants intro­duced into this unit. Failure to follow these regulations may harm the envi­ronment and can lead to the imposition of substantial fines. These regula­tions may vary by jurisdiction. Should questions arise, contact your local EPA office.
To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance.
Do not connect or use any device that is not design certified by Goodman for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
3
PRODUCT DESIGN
SSZ16 models are available in 2, 3, 4 and 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications.
The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis­charged out of the top of the cabinet.
These units are designed for free air discharge, so no addi­tional resistance like duct work shall be attached.
The suction and liquid line connections on present models are of the sweat type for field piping with refrigerant type cop­per. Front seating valves are factory installed to accept the field run copper. The total refrigerant charge for a normal in­stallation is factory installed in the condensing unit. SSZ units are charged for the matching evaporator coil and a 15 foot refrigerant line set.
Systems should be properly sized by heat gain and loss calculations made according to methods of the Air Condi­tioning Contractors Association (ACCA) or equivalent. It is the contractors responsibility to ensure the system has ad­equate capacity to heat or cool the conditioned space.
SSZ16 models use high-efficiency Copeland® Scroll "Ultratech" compressors which are specifically designed for R-410A refrigerant. There are a number of design character­istics which are different from the scroll compared to the tra­ditional reciprocating compressor.
"Ultratech" Series scroll compressors will not have a dis­charge thermostat, some of the early model scroll compres­sors required discharge thermostats.
Due to their design Scroll compressors are inherently more tolerant of small quantities of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll com­pressor is more tolerant of liquid refrigerant, continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure.
"Ultratech" Series scroll compressors use "POE" or
polyolester oil which is NOT compatible with mineral oil based
lubricants like 3GS. "POE" oil must be used if additional oil is required.
These clearances will help avoid air recirculation. If installing two or more units at the same location, allow at least 24 inches between units. If only one side is restricted (for ex­ample, against the outside wall of a house), the unit may be placed as close as 8" to that one wall.
DO NOT locate the unit:
* Directly under a vent termination for a gas appliance.
* Within 3 feet of a clothes drier vent
* Where the refreezing of defrost water would create
a hazard
* Where water may rise into the unit.
NOT
RECOMMENDED
B B B
AA AAA
C
AA
A
Model Type A B C AA
Residential
AA
10" 10" 18" 20"
AA
C
AA
CC
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
WARNING
To avoid possible injury, explosion or death, practice safe handling of refrigerants.
Operating pressures and amp draws may differ from stan­dard reciprocating and/or scroll compressors. This informa­tion may be found in the "Cooling Performance Data" sec­tion.
This unit is for outdoor installation only. Refer to minimum figure for clearances from the sides of the unit to full walls and other objects.
NOTE: This unit cannot be completely enclosed. At least
one side must be unrestricted.
4
Light Commercial
12' 12" 18" 24"
Model Dimensions - W x D x H
SSZ160241A* 29 x 29 x 38¼
SSZ160361A* 35½ x 35½ x 38¼
SSZ160481A* 35½ x 35½ x 38¼
SSZ160601A* 35½ x 35½ x 38¼
HEAT PUMP SPECIFICATIONS
SSZ160241A*
SSZ160361A*
SSZ160481A*
SSZ160601A*
Cooling Capacity, BTUH
24,000 36,000 48,000 60,000
Compressor
R.L. Amps
13.4 14.1 19.8 25.6
L.R. Amps
58.3 77.0 109.0 118.0
Low Pressure Switch
Open
22 PSIG 22 PSIG 22 PSIG 22 PSIG
Close
50 PSIG 50 PSIG 50 PSIG 50 PSIG
High Pressure Switch
Open
610 PSIG 610 PSIG 610 PSIG 610 PSIG
Close
420 PSIG 420 PSIG 420 PSIG 420 PSIG
Condenser Fan Motor
Horsepower
1/6 1/6 1/6 1/6
F.L. Amps
1.1 1.1 1.1 1.0
Liquid Line, Inches O.D.*
3/8" 3/8" 3/8" 3/8"
Suction Line, Inches O.D.*
3/4" 7/8" 1-1/8" 1-1/8"
Refrigerant Charge
160.0 190.0 285.0 280.0
Power Supply
208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
Minimum Circuit Ampacity
(1)
17.9 18.7 25.7 33.0
Maximum Overcurrent Device
(2)
30 30 40 50
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4
Approximate Shipping Weight
282 282 282 296
SSZ160241A* -SSZ160601A*
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
Always check the S & R plate for electrical data on the unit being installed.
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general and electrical information.
5
COOLING PERFORMANCE DATA
COOLING OPERATION
SSZ160241A*
EXPANDED PERFORMANCE DATA
356 371 352 379 400 418 389 419 442 461
24.1 25.8 20.5 21.1 22.9 24.5 19.0 19.6 21.2 22.7
337
22.2
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
149 159 135 143 157 167 139 148 162 173
137
1.78 1.84 1.76 1.80 1.85 1.92 1.82 1.86 1.92 1.98
1.72
65 75 85 95 105 115
S/T 0.78 0.65 0.45 - 0.81 0.68 0.47 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.89 0.74 0.52 - 0.90 0.75 0.52 -
MBh 23.5 24.4 26.7 - 23.0 23.8 26.1 - 22.4 23.2 25.5 - 21.9 22.7 24.8 - 20.8 21.5 23.6 - 19.3 20.0 21.9 -
MODEL: SSZ160241A* / CA*F3636*6A* + TXV / MBE1600**-1 Design Subcooling 7 ± 2 °F @ t he liquid service valv e, ARI 95 test conditions
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
HI PR 213 230 242 - 239 258 272 - 272 293 309 - 310 334 352 - 349 375 396 - 385 415 438 -
AMPS 5.6 5.7 5.9 - 6.0 6.2 6.3 - 6.5 6.7 6.9 - 6.9 7.1 7.3 - 7.4 7.5 7.8 - 7.8 8.0 8.2 -
Delta T 17 15 11 - 17 15 11 - 17 15 11 - 18 15 12 - 17 15 11 - 16 14 11 -
984 KW 1.44 1.47 1.51 - 1.55 1.58 1.63 - 1.64 1.68 1.73 - 1.73 1.77 1.82 - 1.80 1.84 1.90 - 1.86 1.91 1.97 -
S/T 0.75 0.62 0.43 - 0.77 0.65 0.45 - 0.79 0.66 0.46 - 0.82 0.68 0.47 - 0.85 0.71 0.49 - 0.86 0.72 0.50 -
MBh 22.8 23.7 25.9 - 22.3 23.1 25.3 - 21.8 22.6 24.7 - 21.2 22.0 24.1 - 20.2 20.9 22.9 - 18.7 19.4 21.2 -
LO PR 112 119 130 - 118 125 137 - 122 130 142 - 129 137 149 - 135 143 157 - 139 148 162 -
HI PR 211 227 240 - 237 255 269 - 270 290 306 - 307 330 349 - 345 372 392 - 382 411 434 -
AMPS 5.5 5.7 5.8 - 6.0 6.1 6.3 - 6.5 6.6 6.8 - 6.9 7.0 7.3 - 7.3 7.5 7.7 - 7.7 7.9 8.2 -
Delta T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
70 875 KW 1.43 1.46 1.50 - 1.54 1.57 1.62 - 1.63 1.67 1.72 - 1.72 1.75 1.81 - 1.79 1.83 1.89 - 1.85 1.89 1.95 -
S/T 0.72 0.60 0.42 - 0.75 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.68 0.47 - 0.83 0.69 0.48 -
MBh 21.1 21.8 23.9 - 20.6 21.3 23.4 - 20.1 20.8 22.8 - 19.6 20.3 22.3 - 18.6 19.3 21.1 - 17.3 17.9 19.6 -
LO PR 110 117 128 - 117 124 136 - 121 129 141 - 127 136 148 - 133 142 155 - 138 147 160 -
HI PR 205 220 233 - 230 247 261 - 261 281 297 - 298 320 338 - 335 360 381 - 370 398 421 -
AMPS 5.4 5.5 5.7 - 5.8 5.9 6.1 - 6.3 6.4 6.6 - 6.7 6.9 7.1 - 7.1 7.3 7.5 - 7.5 7.7 7.9 -
Delta T 18 16 12 - 18 16 12 - 18 16 12 - 19 16 12 - 18 16 12 - 17 15 11 -
LO PR 107 114 124 - 113 120 131 - 118 125 137 - 124 131 143 - 129 138 150 - 134 142 156 -
766 KW 1.39 1.42 1.47 - 1.50 1.53 1.58 - 1.59 1.63 1.68 - 1.67 1.71 1.76 - 1.74 1.78 1.84 - 1.80 1.84 1.90 -
S/T 0.890.800.600.390.920.820.620.400.940.850.640.410.98 0.87 0.66 0.42 1.00 0.91 0.69 0.44 1.00 0.91 0.69 0.44
MBh 23.9 24.6 26.7 28.6 23.4 24.1 26.0 27.9 22.8 23.5 25.4 27.3 22.2 22.9 24.8 26.6 21.1 21.8 23.6 25.3 19.6 20.2 21.8 23.4
HI PR 215 232 245 255 242 260 275 287 275 296 312 326 313
AMPS 5.6 5.8 5.9 6.2 6.1 6.2 6.4 6.6 6.6 6.7 6.9 7.2 7.0 7.2 7.4 7.7 7.4 7.6 7.9 8.1 7.9 8.0 8.3 8.6
Delta T20181510201915102019151020 19 15 11 20 18 15 10 18 17 14 10
984 KW 1.45 1.48 1.53 1.58 1.56 1.59 1.64 1.70 1.66 1.69 1.75 1.81 1.74 1.78 1.84 1.90 1.82 1.86 1.92 1.98 1.88 1.92 1.99 2.05
LO PR 113 120 131 139 119 127 138 147 124 132 144 153 130 138 151 161 136 145 158 168 141 150 164 174
S/T 0.850.760.570.370.880.790.590.380.900.810.610.390.93 0.83 0.63 0.41 0.97 0.86 0.65 0.42 0.97 0.87 0.66 0.42
MBh 23.2 23.9 25.9 27.8 22.7 23.4 25.3 27.1 22.1 22.8 24.7 26.5 21.6
HI PR 213 230 242 253 239 258 272 284 272 293 309 323 310 334 352 368 349 375 396 413 385 415 438 457
AMPS 5.6 5.7 5.9 6.1 6.0 6.2 6.3 6.6 6.5 6.7 6.9 7.1 6.9 7.1 7.3 7.6 7.4 7.5 7.8 8.1 7.8 8.0 8.2 8.5
Delta T21191611211916112119161121 19 16 11 21 19 16 11 19 18 15 10
75 875 KW 1.44 1.47 1.51 1.56 1.55 1.58 1.63 1.68 1.64 1.68 1.73 1.79 1.73 1.77 1.83 1.89 1.80 1.84 1.90 1.97 1.86 1.91 1.97 2.04
LO PR 112 119 130 138 118 125 137 146 122 130 142 152 129
S/T 0.820.730.550.360.850.760.570.370.870.780.590.380.90 0.80 0.61 0.39 0.93 0.83 0.63 0.41 0.94 0.84 0.64 0.41
MBh 21.4 22.1 23.9 25.6 20.9 21.6 23.3 25.0 20.4 21.0 22.8 24.4 19.9 20.5 22.2 23.8 18.9 19.5 21.1 22.7 17.5 18.1 19.6 21.0
HI PR 207 223 235 245 232 250 264 275 264 284 300 313 301 324 342 357 338 364 385 401 374 402 425 443
AMPS 5.4 5.6 5.7 5.9 5.9 6.0 6.2 6.4 6.3 6.5 6.7 6.9 6.8 6.9 7.1 7.4 7.2 7.3 7.6 7.9 7.6 7.8 8.0 8.3
Delta T21191611212016112120161121 20 16 11 21 19 16 11 20 18 15 10
LO PR 108 115 126 134 114 122 133 141 119 126 138 147 125 133 145 154 131 139 152 162 135 144 157 167
766 KW 1.40 1.43 1.48 1.53 1.51 1.54 1.59 1.64 1.60 1.64 1.69 1.75 1.69
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.
6