Goodman GSZ130362A User Manual

Page 1
NomiNal CooliNg CapaCity: 22,000 to 52,000 BtU/h
GSZ13
EnErgy-EfficiEnt 50 Hz Split SyStEm HEat pump
2 to 5 tonS
NomiNal heatiNg CapaCity: 22,000 to 52,000 BtU/h
Nomenclature .........................................2
Product Specifications ..............................3
Expanded Cooling Data ........................... 4
Expanded Heating Data ......................... 14
Dimensions ........................................... 16
Wiring Diagrams....................................17
Accessories ...........................................19
Standard Features
• R-410A chlorine-free refrigerant
• High-efficiency scroll compressor
• SmartShift® technology to ensure quiet reliable defrost
• Factory-installed bi-flow liquid-line filter drier
• Factory-installed suction-line accumulator
• Factory-installed compressor crankcase heater
• Factory-installed high-capacity muffler
• High- and low-pressure switches
• Service valves with sweat connections and easy access to gauge ports
• Copper tube/enhanced aluminum fin coil
• Fully charged for 15’ of tubing length
• Contactor with lug connection
• Ground lug connection
SS-iGSZ13 www.goodmanmfg.com 9/14
Cabinet Features
• Goodman® brand sound control top design
• Steel louver coil guard
• Heavy-gauge galvanized-steel cabinet
• Attractive Architectural Gray powder-paint finish with 500-hour salt-spray approval
• Top and side maintenance access
• Service ports and controls are accessible while unit is operating
Page 2
Product SPecificationS Product SPecificationS
Brand Engineering *
G
Goodman
®
(
Standard
Minor Revision
Feature Set Models)
S
Goodman
®
(Hig
h
Feature Set Models) Engineering *
Major Revision
Product Category
S Split System Electrical 1 208/230 V, 1 Phase, 60 Hz Unit Type 2 220/240 V, 1 Phase, 50 Hz C Condenser R-22 3 208/230 V, 3 Phase, 60 Hz X Condenser R-410A 4 460 V, 3 Phase, 60 Hz H Heat Pump R-22 5 380/415 V, 3 Phase, 50 Hz Z Heat Pump R-410A
Nominal Capacity
Efficiency 018 1½ Tons 048 4 Tons
13 13 SEER 024 2 Tons 060 5 Tons 14 14 SEER 030 2½ Tons 090 7½ tons 16 16 SEER 036 3 Tons 120 10 Tons
042 3½ Tons
* Neither used for order entry
or inventory management.
A
11
AS
21
GZ3036
6,7,8
13
4,5 9
1
10

NomeNClatUre

2 www.goodmanmfg.com SS-iGSZ13
Page 3
SpeCifiCatioNS
GSZ13
0242A*
Nominal Capacities
Cooling (BTU/h) 22,000 32,000 31,500 43,500 52,000
Heang (BTU/h) 22,000 32,000 31,500 43,500 52,000
Decibels
Compressor
RLA 11.2 16.0 6.0 6.8 8.5
LRA 60 87.0 46.0 51.5 67.1
Type Scroll Scroll Scroll Scroll Scroll
Condenser Fan Motor
Horsepower 1/4 1/4 1/4 1/4 1/3
FLA 0.90 0.90 0.80 0.80 1.20
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ⅞" ⅞" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ¾" ¾" ⅞" ⅞"
Valve Connecon Type Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge 99 128 149 204 231
Shipped with Orice Size 0.057 0.071 0.071 0.078 0.088
Electrical Data
Volts-Hz/Phase 216-253/50/1 216-253/50/1 216-253/50/3 216-253/50/3 216-253/50/3
Minimum Circuit Ampacity ² 14.9 20.9 8.3 9.3 11.8
Max. Overcurrent Protecon ³ 25 35 15 15 20
Min / Max Volts 198 / 264 198 / 264 198 / 264 198 / 264 198 / 264
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Ship Weight (lbs) 198 202 232 240 266
¹ Tested and rated in accordance with ARI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes ³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
GSZ13
0362A*
GSZ13
0365A*
GSZ13
0485A*
GSZ13
0605A*
SS-iGSZ13 www.goodmanmfg.com 3
Page 4
expaNDeD Data expaNDeD Data
CooliNg Data — gSZ130242a*/a24-00-2rC
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 20.2 20.9 22.9 - 19.1 19.8 21.7 - 17.7 18.4 20.1 -
21 20 16 11 21 20 16 11 21 19 16 11 20 18 15 10
∆T 21 19 16 11 21 20 16 11
kW 1.62 1.65 1.70 1.75 1.73 1.77 1.82 1.88 1.84 1.87 1.93 1.99 1.93 1.97 2.03 2.10 2.01 2.05 2.11 2.18 2.07 2.12 2.18 2.26
6.3 6.5 6.7 6.6 6.8 7.0 7.3 7.2 7.4 7.6 7.9 7.7 7.9 8.1 8.5 8.2 8.4 8.7 9.0 8.7 8.9 9.2 9.5
Amps 6.1
Hi PR 232 250 264 275 260 280 296 309 296 319 337 351 337 363 383 400 380 408 431 450 419 451 477 497
Lo PR 100 107 117 124 106 113 123 131 110 117 128 136 116 123 135 143 121 129 141 150 126 134 146 155
MBh 22.0 22.7 24.6 26.3 21.5 22.2 24.0 25.7 21.0 21.6 23.4 25.1 20.5 21.1 22.8 24.5 19.5 20.0 21.7 23.3 18.0 18.6 20.1 21.6
S/T 0.86 0.77 0.58 0.37 0.89 0.79 0.60 0.39 0.91 0.81 0.62 0.40 0.94 0.84 0.64 0.41 0.97 0.87 0.66 0.42 0.98 0.88 0.67 0.43
∆T 19 18 15 10 20 18 15 10 20 18 15 10 20 18 15 10 19 18 15 10 18 17 14 9
kW 1.64 1.67 1.72 1.78 1.76 1.80 1.85 1.91 1.86 1.90 1.96 2.03 1.96 2.00 2.06 2.13 2.04 2.08 2.15 2.22 2.11 2.15 2.22 2.29
Hi PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 417 440 459 428 460 486 507
Lo PR 102 109 119 127 108 115 126 134 112 120 131 139 118 126 137 146 124 132 144 153 128 136 149 158
Amps 6.3 6.4 6.6 6.9 6.8 6.9 7.1 7.4 7.3 7.5 7.8 8.1 7.8 8.0 8.3 8.6 8.3 8.5 8.8 9.2 8.8 9.1 9.4 9.7
6.3 6.6 - 6.7 6.9 7.1 - 7.3 7.4 7.7 - 7.8 8.0 8.2 - 8.3 8.5 8.7 - 8.8 9.0 9.3 -
∆T 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 17 15 11 -
S/T 0.68 0.57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.78 0.65 0.45 - 0.78 0.66 0.45 -
MBh 20.6 21.4 23.4 - 20.1 20.9 22.9 - 19.7 20.4 22.3 - 19.2 19.9 21.8 - 18.2 18.9 20.7 - 16.9 17.5 19.2 -
kW 1.58 1.61 1.66 - 1.70 1.73 1.78 - 1.80 1.83 1.89 - 1.89 1.93 1.99 - 1.96 2.00 2.07 - 2.03 2.07 2.14 -
Hi PR 226 243 257 - 253 273 288 - 288 310 328 - 328 353 373 - 369 397 420 - 408 439 464 -
Lo PR 98 104 114 - 103 110 120 - 107 114 125 - 113 120 131 - 118 126 137 - 122 130 142 -
Amps 6.0 6.1 6.3 - 6.5 6.6 6.8 - 7.0 7.2 7.4 - 7.5 7.7 7.9 - 8.0 8.2 8.5 - 8.5 8.7 9.0 -
∆T 18 16 12 - 18 16 12 - 18 16 12 - 19 16 12 - 18 16 12 - 17 15 11 -
S/T 0.71 0.59 0.41 - 0.73 0.61 0.43 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.81 0.68 0.47 -
MBh 20.9 21.7 23.8 - 20.4 21.2 23.2 - 20.0 20.7 22.7 - 19.5 20.2 22.1 - 18.5 19.2 21.0 - 17.1 17.8 19.5 -
kW 1.60 1.64 1.68 - 1.72 1.75 1.81 - 1.82 1.86 1.92 - 1.91 1.95 2.01 - 1.99 2.03 2.10 - 2.06 2.10 2.17 -
Hi PR 230 247 261 - 258 277 293 - 293 316 333 - 334 359 380 - 376 404 427 - 415 447 472 -
Lo PR 99 106 115 - 105 112 122 - 109 116 127 - 115 122 133 - 120 128 140 - 124 132 144 -
Amps 6.1 6.2 6.4 - 6.6 6.7 7.0 - 7.1 7.3 7.6 - 7.6 7.8 8.1 - 8.1 8.3 8.6 - 8.6 8.8 9.1 -
MBh 21.7 22.5 24.6 - 21.2 21.9 24.0 - 20.7 21.4 23.5
∆T 17 14 11 - 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 16 14 10 -
S/T 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.86 0.72 0.50 -
kW 1.63 1.66 1.71 - 1.75 1.78 1.84 - 1.85 1.89 1.95 - 1.94 1.98 2.05 - 2.02 2.06 2.13 - 2.09 2.13 2.20 -
Hi PR 234 252 266 - 263 283 299 - 299 322 340 - 341 367 387 - 383 412 436 - 423 456 481 -
Lo PR 101 108 118 - 107 114 124 - 111 118 129 - 117 124 136 - 123 130 142 - 127 135 147 -
Amps 6.2
MBh 21.0 21.6 23.4 25.1 20.5 21.1 22.8 24.5 20.0 20.6 22.3 23.9 19.5 20.1 21.7 23.3 18.5 19.1 20.6 22.2 17.2 17.7 19.1 20.5
S/T 0.78 0.70 0.53 0.34 0.81 0.72 0.55 0.35 0.83 0.74 0.56 0.36 0.85 0.76 0.58 0.37 0.88 0.79 0.60 0.39 0.89 0.80 0.60 0.39
∆T 21 20 16 11 22 20 16 11 22 20 16 11 22 20 16 11 22 20 16 11 20 19 15 10
kW 1.59 1.63 1.67 1.73 1.71 1.75 1.80 1.85 1.81 1.85 1.91 1.97 1.90 1.94 2.00 2.07 1.98 2.02 2.08 2.15 2.04 2.09 2.15 2.22
Amps 6.1 6.2 6.4 6.6 6.5 6.7 6.9 7.2 7.1 7.3 7.5 7.8 7.6 7.8 8.0 8.3 8.1 8.3 8.5 8.9 8.5 8.7 9.0 9.4
Hi PR 228 246 259 270 256 276 291 303 291 313 331 345 332 357 377 393 373 402 424 442 412 444 468 489
Lo PR 99 105 115 122 104 111 121 129 108 115 126 134 114 121 132 141 119 127 139 148 123 131 143 153
MBh 21.3 21.9 23.7 25.5 20.8 21.4 23.2 24.9 20.3 20.9 22.6 24.3 19.8 20.4 22.1 23.7 18.8 19.4 21.0 22.5 17.4 17.9 19.4 20.8
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.37 0.88 0.79 0.60 0.38 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
750
75
900
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) Rang Condions kW = Total system power
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
700
750
70
900
700
4 www.goodmanmfg.com SS-iGSZ13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 5
CooliNg Data — gSZ130242a*/a24-00-2rC (CoNt.)
142 121 128 140 149 125 133 145 154
23.5 19.1 19.6 20.9 22.3 17.7 18.1 19.4 20.7
134
22.0
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
MBh 21.3 21.8 23.3 24.9 20.8 21.3 22.8 24.3 20.3 20.8 22.2 23.7 19.8 20.3 21.7 23.2 18.9 19.3 20.6 22.0 17.5 17.8 19.1 20.4
S/T 0.85 0.80 0.65 0.49 0.88 0.83 0.67 0.50 0.91 0.85 0.69 0.52 0.93 0.88 0.71 0.53 0.97 0.91 0.74 0.55 0.98 0.92 0.75 0.56
∆T 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 22 22 19 15
kW 1.61 1.64 1.69 1.74 1.72 1.76 1.81 1.87 1.83 1.86 1.92 1.98 1.92 1.96 2.02 2.08 1.99 2.04 2.10 2.17 2.06 2.10 2.17 2.24
Amps 6.1 6.3 6.5 6.7 6.6 6.8 7.0 7.2 7.2 7.3 7.6 7.9 7.6 7.8 8.1 8.4 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.5
Hi PR 231 248 262 273 259 278 294 307 294 317 334 349 335 361 381 397 377 406 428 447 416 448 473 494
Lo PR 100 106 116 123 105 112 122 130 109 116 127 135 115 122
MBh 21.7 22.1 23.7 25.3 21.2 21.6 23.1 24.7 20.7 21.1 22.6 24.1 20.2 20.6
S/T 0.88 0.83 0.67 0.50 0.92 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 0.95 0.77 0.58
∆T 23 22 20 16 24 23 20 16 24 23 20 16 24 23 20 16 23 23 20 16 22 21 18 15
kW 1.63 1.66 1.71 1.76 1.75 1.78 1.84 1.89 1.85 1.89 1.95 2.01 1.94 1.98 2.05 2.11 2.02 2.06 2.13 2.20 2.09 2.13 2.20 2.27
Amps 6.2 6.3 6.6 6.8 6.7 6.9 7.1 7.3 7.3 7.4 7.7 8.0 7.8 8.0 8.2 8.5 8.3 8.5 8.8 9.1 8.8 9.0 9.3 9.6
Hi PR 234 252 266 278 263 283 299 312 299 322 340 355 341 367 387 404 383 413 436 454 424 456 481 502
Lo PR 101 108 118 125 107 114 124 133 111 119 129 138 117 124 136 145 123 130 142 152 127 135 147 157
24.9 20.9 21.3 22.8 24.3 19.8 20.2 21.6 23.1 18.4 18.8 20.0 21.4
MBh 22.4 22.9 24.5 26.2 21.9 22.4 23.9 25.6 21.4 21.8 23.3
S/T 0.94 0.88 0.72 0.54 1.00 0.91 0.74 0.56 1.00 0.94 0.76 0.57 1.00 1.00 0.79 0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.82 0.62
∆T 22 21 18 14 22 21 18 14 22 21 18 15 21 22 18 15 20 21 18 14 19 19 17 13
kW 1.65 1.69 1.74 1.79 1.77 1.81 1.87 1.92 1.88 1.92 1.98 2.04 1.97 2.02 2.08 2.15 2.05 2.10 2.16 2.24 2.12 2.17 2.24 2.31
6.5 6.7 6.9 6.8 7.0 7.2 7.5 7.4 7.6 7.8 8.1 7.9 8.1 8.4 8.7 8.4 8.6 8.9 9.2 8.9 9.1 9.4 9.8
Amps 6.3
Hi PR 239 257 272 283 268 289 305 318 305 328 347 362 348 374 395 412 391 421 444 464 432 465 491 512
Lo PR 103 110 120 128 109 116 127 135 114 121 132 141 119 127 139 148 125 133 145 155 129 138 150 160
MBh 21.7 22.1 23.2 24.7 21.2 21.6 22.6 24.2 20.7 21.1 22.1 23.6 20.2 20.6 21.6 23.0 19.2 19.6 20.5 21.9 17.8 18.1 19.0 20.2
S/T 0.89 0.86 0.78 0.63 0.93 0.89 0.81 0.65 0.95 0.92 0.83 0.67 0.98 0.95 0.85 0.69 1.00 0.98 0.89 0.72 1.00 0.99 0.89 0.72
∆T 25 25 24 21 26 25 24 21 26 25 24 21 26 26 24 21 25 25 24 21 23 24 22 19
kW 1.62 1.65 1.70 1.75 1.74 1.77 1.83 1.88 1.84 1.88 1.94 2.00 1.93 1.97 2.03 2.10 2.01 2.05 2.12 2.19 2.08 2.12 2.19 2.26
Amps 6.2 6.3 6.5 6.8 6.7 6.8 7.0 7.3 7.2 7.4 7.6 7.9 7.7 7.9 8.2 8.5 8.2 8.4 8.7 9.0 8.7 8.9 9.2 9.6
Hi PR 233 251 265 276 261 281 297 310 297 320 338 352 338 364 385 401 381 410 433 451 421 453 478 499
Lo PR 101 107 117 125 106 113 124 132 111 118 128 137 116 124 135 144 122 130 141 151 126 134 146 156
MBh 22.0 22.5 23.5 25.1 21.5 21.9 23.0 24.5 21.0 21.4 22.4 23.9 20.5 20.9 21.9 23.4 19.5 19.9 20.8 22.2 18.0 18.4 19.3 20.6
S/T 0.93 0.89 0.81 0.65 0.96 0.93 0.84 0.68 0.98 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.75
25 25 24 20 25 25 24 21 24 24 23 20 22 23 22 19
∆T 25 25 23 20 25 25 24 20
kW 1.64 1.67 1.72 1.78 1.76 1.80 1.85 1.91 1.87 1.90 1.96 2.03 1.96 2.00 2.06 2.13 2.04 2.08 2.15 2.22 2.11 2.15 2.22 2.29
6.4 6.6 6.9 6.8 6.9 7.1 7.4 7.3 7.5 7.8 8.1 7.8 8.0 8.3 8.6 8.3 8.5 8.8 9.2 8.8 9.1 9.4 9.7
Amps 6.3
Hi PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 417 440 459 428 460 486 507
Lo PR 102 109 119 127 108 115 126 134 113 120 131 139 118 126 137 146 124 132 144 153 128 136 149 158
MBh 22.8 23.3 24.4 26.0 22.3 22.7 23.8 25.4 21.8 22.2 23.2 24.8 21.2 21.6 22.7 24.2 20.2 20.6 21.5 23.0 18.7 19.0 19.9 21.3
S/T 0.98 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.98 0.79 1.00 1.00 0.98 0.80
∆T 23 23 21 18 23 23 22 19 22 23 22 19 22 22 22 19 21 21 21 19 19 19 20 17
kW 1.66 1.70 1.75 1.80 1.79 1.82 1.88 1.94 1.89 1.93 1.99 2.06 1.99 2.03 2.10 2.16 2.07 2.11 2.18 2.25 2.14 2.19 2.26 2.33
Amps 6.4 6.5 6.7 7.0 6.9 7.0 7.3 7.5 7.5 7.7 7.9 8.2 8.0 8.2 8.4 8.8 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.9
Hi PR 242 260 275 286 271 292 308 321 308 332 350 365 351 378 399 416 395 425 449 468 436 470 496 517
Lo PR 105 111 121 129 110 117 128 137 115 122 133 142 121 128 140 149 126 134 147 156 131 139 152 162
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
700
750
80
900
700
750
85
900
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) Rang Condions kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 5
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 6
expaNDeD Data expaNDeD Data
CooliNg Data — gSZ130362a*/a36-00-2rC
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 29.2 30.2 33.1 - 27.7 28.7 31.5 - 25.7 26.6 29.1 -
21 19 16 11 21 20 16 11 21 19 16 11 20 18 15 10
∆T 21 19 16 11 21 19 16 11
kW 2.53 2.58 2.66 2.74 2.71 2.77 2.85 2.94 2.87 2.93 3.02 3.12 3.02 3.08 3.17 3.28 3.14 3.20 3.30 3.41 3.24 3.31 3.41 3.52
9.9 10.2 10.6 10.5 10.7 11.1 11.5 11.4 11.6 12.0 12.4 12.1 12.4 12.8 13.3 12.9 13.2 13.6 14.1 13.6 14.0 14.4 15.0
Amps 9.7
Hi PR 242 260 275 287 271 292 308 322 309 332 351 366 351 378 399 417 395 425 449 469 437 470 496 518
Lo PR 102 108 118 126 108 114 125 133 112 119 130 138 117 125 136 145 123 131 143 152 127 135 148 157
MBh 31.9 32.8 35.5 38.1 31.1 32.1 34.7 37.3 30.4 31.3 33.9 36.4 29.7 30.5 33.1 35.5 28.2 29.0 31.4 33.7 26.1 26.9 29.1 31.2
S/T 0.88 0.78 0.59 0.38 0.91 0.81 0.62 0.40 0.93 0.83 0.63 0.41 0.96 0.86 0.65 0.42 1.00 0.89 0.68 0.43 1.00 0.90 0.68 0.44
∆T 19 18 14 10 19 18 15 10 19 18 15 10 19 18 15 10 19 18 14 10 18 16 14 9
kW 2.55 2.60 2.68 2.76 2.73 2.79 2.87 2.96 2.90 2.96 3.05 3.14 3.04 3.10 3.20 3.30 3.16 3.23 3.33 3.44 3.27 3.34 3.44 3.55
Hi PR 244 263 278 289 274 295 311 325 312 335 354 369 355 382 403 421 399 430 454 473 441 475 501 523
Lo PR 103 109 119 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159
Amps 9.8 10.0 10.3 10.7 10.6 10.8 11.2 11.6 11.5 11.7 12.1 12.6 12.2 12.5 12.9 13.4 13.0 13.3 13.7 14.3 13.8 14.1 14.6 15.1
9.9 10.2 - 10.5 10.7 11.1 - 11.3 11.6 12.0 - 12.1 12.4 12.8 - 12.9 13.2 13.6 - 13.6 14.0 14.4 -
∆T 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 18 15 12 -
S/T 0.71 0.59 0.41 - 0.74 0.61 0.43 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.81 0.68 0.47 -
MBh 30.0 31.1 34.1 - 29.3 30.4 33.3 - 28.6 29.6 32.5 - 27.9 28.9 31.7 - 26.5 27.5 30.1 - 24.5 25.4 27.9 -
kW 2.48 2.53 2.60 - 2.66 2.71 2.79 - 2.81 2.87 2.96 - 2.95 3.01 3.11 - 3.07 3.13 3.23 - 3.17 3.24 3.34 -
Hi PR 235 253 267 - 264 284 300 - 300 323 341 - 342 368 389 - 385 414 437 - 425 457 483 -
Lo PR 99 105 115 - 105 111 122 - 109 116 126 - 114 122 133 - 120 127 139 - 124 132 144 -
Amps 9.5 9.7 10.0 - 10.2 10.5 10.8 - 11.1 11.3 11.7 - 11.8 12.1 12.5 - 12.6 12.9 13.3 - 13.3 13.6 14.1 -
∆T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
S/T 0.74 0.61 0.43 - 0.76 0.64 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.84 0.70 0.48 - 0.84 0.71 0.49 -
MBh 30.4 31.6 34.6 - 29.7 30.8 33.8 - 29.0 30.1 33.0 - 28.3 29.4 32.2 - 26.9 27.9 30.6 - 24.9 25.8 28.3 -
kW 2.51 2.56 2.64 - 2.69 2.75 2.83 - 2.85 2.91 3.00 - 2.99 3.05 3.15 - 3.11 3.18 3.28 - 3.21 3.28 3.39 -
Hi PR 239 258 272 - 269 289 305 - 305 329 347 - 348 374 395 - 391 421 445 - 432 465 491 -
Lo PR 101 107 117 - 106 113 124 - 111 118 128 - 116 124 135 - 122 130 141 - 126 134 146 -
Amps 9.6 9.8 10.2 - 10.4 10.6 11.0 - 11.2 11.5 11.9 - 12.0 12.3 12.7 - 12.8 13.1 13.5 - 13.5 13.8 14.3 -
MBh 31.4 32.5 35.6 - 30.6 31.7 34.8 - 29.9 31.0 34.0
∆T 16 14 11 - 17 14 11 - 17 14 11 - 17 15 11 - 17 14 11 - 15 13 10 -
S/T 0.77 0.64 0.45 - 0.80 0.67 0.46 - 0.82 0.68 0.47 - 0.85 0.71 0.49 - 0.88 0.73 0.51 - 0.89 0.74 0.51 -
kW 2.53 2.58 2.66 - 2.71 2.77 2.85 - 2.87 2.93 3.02 - 3.01 3.08 3.17 - 3.14 3.20 3.30 - 3.24 3.31 3.41 -
Hi PR 242 260 275 - 271 292 308 - 309 332 351 - 351 378 399 - 395 425 449 - 437 470 496 -
Lo PR 102 108 118 - 107 114 125 - 112 119 130 - 117 125 136 - 123 131 143 - 127 135 148 -
Amps 9.7
MBh 30.5 31.4 34.0 36.5 29.8 30.7 33.2 35.6 29.1 29.9 32.4 34.8 28.4 29.2 31.6 33.9 26.9 27.7 30.0 32.2 25.0 25.7 27.8 29.9
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.37 0.88 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
∆T 22 20 16 11 22 20 16 11 22 20 16 11 22 20 17 11 22 20 16 11 20 19 15 11
kW 2.50 2.55 2.62 2.70 2.68 2.73 2.81 2.90 2.84 2.89 2.98 3.08 2.98 3.04 3.13 3.23 3.09 3.16 3.26 3.36 3.20 3.26 3.37 3.48
Amps 9.6 9.8 10.1 10.5 10.3 10.6 10.9 11.3 11.2 11.4 11.8 12.3 11.9 12.2 12.6 13.1 12.7 13.0 13.4 13.9 13.4 13.7 14.2 14.7
Hi PR 238 256 270 282 267 287 303 316 303 326 345 360 345 372 393 409 389 418 442 461 429 462 488 509
Lo PR 100 106 116 124 106 112 123 131 110 117 128 136 115 123 134 143 121 129 140 150 125 133 145 155
MBh 31.0 31.9 34.5 37.0 30.2 31.1 33.7 36.2 29.5 30.4 32.9 35.3 28.8 29.7 32.1 34.4 27.4 28.2 30.5 32.7 25.3 26.1 28.2 30.3
S/T 0.84 0.75 0.57 0.36 0.87 0.78 0.59 0.38 0.89 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.95 0.85 0.64 0.41 0.96 0.86 0.65 0.42
1140
75
1350
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) Rang Condions kW = Total system power
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1050
1140
70
1350
1050
6 www.goodmanmfg.com SS-iGSZ13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 7
CooliNg Data — gSZ130362a*/a36-00-2rC (CoNt.)
144 122 130 142 151 126 134 147 156
34.2 27.8 28.5 30.4 32.5 25.8 26.4 28.2 30.1
135
32.0
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
MBh 31.0 31.7 33.9 36.2 30.3 31.0 33.1 35.4 29.6 30.2 32.3 34.5 28.9 29.5 31.5 33.7 27.4 28.0 29.9 32.0 25.4 26.0 27.7 29.7
S/T 0.88 0.83 0.68 0.50 0.92 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.55 1.01 0.94 0.77 0.57 1.00 0.95 0.78 0.58
∆T 24 23 20 16 24 23 20 16 24 23 20 16 25 24 20 16 24 23 20 16 22 22 19 15
kW 2.52 2.57 2.64 2.72 2.70 2.75 2.84 2.92 2.86 2.92 3.01 3.10 3.00 3.06 3.16 3.26 3.12 3.18 3.28 3.39 3.22 3.29 3.39 3.50
Amps 9.6 9.9 10.2 10.5 10.4 10.6 11.0 11.4 11.3 11.5 11.9 12.4 12.0 12.3 12.7 13.2 12.8 13.1 13.5 14.0 13.5 13.9 14.3 14.9
Hi PR 240 258 273 285 269 290 306 319 306 330 348 363 349 376 397 414 393 422 446 465 434 467 493 514
Lo PR 101 107 117 125 107 114 124 132 111 118 129 137 117 124
MBh 31.5 32.2 34.4 36.8 30.8 31.4 33.6 35.9 30.0 30.7 32.8 35.1 29.3 30.0
S/T 0.92 0.86 0.70 0.52 0.95 0.89 0.73 0.54 0.97 0.91 0.74 0.56 1.00 0.94 0.77 0.57 1.00 0.98 0.80 0.60 1.00 0.99 0.80 0.60
∆T 23 22 19 16 24 23 20 16 24 23 20 16 24 23 20 16 22 22 20 16 21 21 18 15
kW 2.55 2.60 2.68 2.76 2.73 2.79 2.87 2.96 2.90 2.96 3.05 3.14 3.04 3.10 3.20 3.30 3.16 3.23 3.33 3.44 3.27 3.34 3.44 3.55
Amps 9.8 10.0 10.3 10.7 10.6 10.8 11.2 11.6 11.5 11.7 12.1 12.6 12.2 12.5 12.9 13.4 13.0 13.3 13.8 14.3 13.8 14.1 14.6 15.1
Hi PR 244 263 278 289 274 295 311 325 312 335 354 369 355 382 403 421 399 430 454 473 441 475 501 523
Lo PR 103 109 119 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159
36.1 30.2 30.9 33.0 35.2 28.7 29.3 31.3 33.5 26.6 27.1 29.0 31.0
MBh 32.5 33.2 35.4 37.9 31.7 32.4 34.6 37.0 30.9 31.6 33.8
S/T 0.96 0.90 0.73 0.55 1.00 0.93 0.76 0.57 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.84 0.62 1.00 1.00 0.84 0.63
∆T 21 20 18 14 22 21 18 14 21 21 18 14 21 21 18 14 20 20 18 14 18 18 17 13
kW 2.57 2.62 2.70 2.78 2.75 2.81 2.90 2.99 2.92 2.98 3.07 3.17 3.06 3.13 3.23 3.33 3.19 3.25 3.36 3.47 3.29 3.36 3.47 3.58
10.1 10.4 10.8 10.7 10.9 11.3 11.7 11.6 11.8 12.2 12.7 12.3 12.6 13.0 13.5 13.1 13.4 13.9 14.4 13.9 14.2 14.7 15.2
Amps 9.9
Hi PR 247 265 280 292 277 298 315 328 315 339 358 373 359 386 407 425 403 434 458 478 446 480 506 528
Lo PR 104 110 121 128 110 117 127 136 114 121 132 141 120 127 139 148 125 134 146 155 130 138 151 161
MBh 31.6 32.2 33.7 36.0 30.8 31.4 32.9 35.1 30.1 30.7 32.1 34.3 29.4 29.9 31.4 33.5 27.9 28.4 29.8 31.8 25.9 26.4 27.6 29.4
S/T 0.93 0.89 0.81 0.66 0.96 0.93 0.84 0.68 0.99 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.75
∆T 26 25 24 21 26 26 24 21 26 26 24 21 26 26 24 21 24 25 24 21 23 23 22 19
kW 2.54 2.59 2.66 2.74 2.72 2.77 2.86 2.95 2.88 2.94 3.03 3.13 3.02 3.09 3.18 3.28 3.14 3.21 3.31 3.42 3.25 3.32 3.42 3.53
Amps 9.7 10.0 10.3 10.6 10.5 10.7 11.1 11.5 11.4 11.7 12.0 12.5 12.1 12.4 12.8 13.3 12.9 13.2 13.7 14.2 13.7 14.0 14.5 15.0
Hi PR 242 261 276 287 272 293 309 322 309 333 352 367 352 379 401 418 397 427 451 470 438 471 498 519
Lo PR 102 109 119 126 108 115 125 133 112 119 130 139 118 125 137 146 123 131 143 153 128 136 148 158
MBh 32.1 32.7 34.2 36.5 31.3 31.9 33.4 35.7 30.6 31.2 32.6 34.8 29.8 30.4 31.8 34.0 28.3 28.9 30.2 32.3 26.2 26.8 28.0 29.9
S/T 0.96 0.93 0.84 0.68 1.00 0.96 0.87 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.95 0.77 1.00 1.00 0.96 0.78
25 25 23 20 24 25 24 20 23 23 23 20 21 22 22 19
∆T 25 24 23 20 25 25 23 20
kW 2.57 2.62 2.70 2.78 2.75 2.81 2.90 2.99 2.92 2.98 3.07 3.17 3.06 3.13 3.23 3.33 3.19 3.25 3.36 3.47 3.29 3.36 3.47 3.58
10.1 10.4 10.8 10.7 10.9 11.3 11.7 11.6 11.8 12.2 12.7 12.3 12.6 13.0 13.5 13.1 13.4 13.9 14.4 13.9 14.2 14.7 15.2
Amps 9.9
Hi PR 247 265 280 292 277 298 315 328 315 339 358 373 359 386 407 425 403 434 458 478 446 480 506 528
Lo PR 104 110 121 128 110 117 127 136 114 121 132 141 120 127 139 148 125 134 146 155 130 138 151 161
MBh 33.0 33.7 35.3 37.6 32.3 32.9 34.4 36.7 31.5 32.1 33.6 35.9 30.7 31.3 32.8 35.0 29.2 29.7 31.2 33.2 27.0 27.6 28.9 30.8
S/T 1.00 0.97 0.88 0.71 1.00 1.00 0.91 0.74 1.00 1.00 0.93 0.76 1.00 1.00 0.96 0.78 1.00 1.00 1.00 0.81 1.00 1.00 1.00 0.82
∆T 22 22 21 18 22 22 21 18 21 22 21 18 21 21 22 19 20 20 21 18 18 19 20 17
kW 2.59 2.64 2.72 2.80 2.78 2.83 2.92 3.01 2.94 3.00 3.10 3.19 3.09 3.15 3.25 3.36 3.21 3.28 3.38 3.49 3.32 3.39 3.50 3.61
Amps 10.0 10.2 10.5 10.9 10.7 11.0 11.4 11.8 11.7 11.9 12.3 12.8 12.4 12.7 13.2 13.7 13.2 13.6 14.0 14.5 14.0 14.4 14.8 15.4
Hi PR 249 268 283 295 280 301 318 331 318 342 361 377 362 390 412 429 407 438 463 483 450 484 512 533
Lo PR 105 112 122 130 111 118 129 137 115 122 134 142 121 129 140 150 127 135 147 157 131 139 152 162
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1050
1140
80
1350
1050
1140
85
1350
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) Rang Condions kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 7
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 8
expaNDeD Data expaNDeD Data
CooliNg Data — gSZ130365a*/a36-00-2rC
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 28.7 29.8 32.6 - 27.3 28.3 31.0 - 25.3 26.2 28.7 -
21 19 16 11 21 19 16 11 21 19 16 11 19 18 15 10
∆T 21 19 16 11 21 19 16 11
kW 2.40 2.45 2.52 2.60 2.57 2.63 2.70 2.79 2.72 2.78 2.86 2.95 2.86 2.92 3.01 3.10 2.97 3.03 3.13 3.22 3.07 3.13 3.23 3.33
9.3 9.6 10.0 9.8 10.1 10.4 10.8 10.7 10.9 11.3 11.7 11.4 11.7 12.0 12.5 12.1 12.4 12.8 13.3 12.8 13.1 13.5 14.0
Amps 9.1
Hi PR 240 259 273 285 270 290 306 320 307 330 349 364 349 376 397 414 393 423 447 466 434 467 493 515
Lo PR 102 109 119 126 108 115 125 133 112 119 130 139 118 125 137 146 123 131 143 153 128 136 148 158
MBh 31.4 32.3 35.0 37.5 30.7 31.6 34.2 36.7 29.9 30.8 33.4 35.8 29.2 30.1 32.5 34.9 27.7 28.6 30.9 33.2 25.7 26.5 28.6 30.7
S/T 0.88 0.79 0.60 0.38 0.91 0.82 0.62 0.40 0.94 0.84 0.63 0.41 0.97 0.86 0.65 0.42 1.00 0.90 0.68 0.44 1.00 0.90 0.68 0.44
∆T 19 17 14 10 19 18 14 10 19 18 14 10 19 18 14 10 19 17 14 10 17 16 13 9
kW 2.42 2.47 2.54 2.62 2.59 2.65 2.72 2.81 2.75 2.80 2.89 2.98 2.88 2.94 3.03 3.12 2.99 3.05 3.15 3.25 3.09 3.16 3.25 3.36
Hi PR 243 261 276 288 272 293 310 323 310 333 352 367 353 380 401 418 397 427 451 470 439 472 498 520
Lo PR 103 110 120 128 109 116 127 135 113 121 132 140 119 127 138 147 125 133 145 154 129 137 150 160
Amps 9.2 9.4 9.7 10.1 9.9 10.2 10.5 10.9 10.8 11.0 11.4 11.8 11.5 11.8 12.1 12.6 12.2 12.5 12.9 13.4 12.9 13.2 13.7 14.2
9.3 9.6 - 9.8 10.1 10.4 - 10.7 10.9 11.3 - 11.4 11.7 12.0 - 12.1 12.4 12.8 - 12.8 13.1 13.5 -
∆T 18 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 17 15 11 -
S/T 0.71 0.59 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.68 0.47 - 0.82 0.68 0.47 -
MBh 29.5 30.6 33.5 - 28.8 29.9 32.7 - 28.1 29.2 32.0 - 27.5 28.5 31.2 - 26.1 27.0 29.6 - 24.2 25.0 27.4 -
kW 2.36 2.40 2.47 - 2.52 2.57 2.65 - 2.67 2.72 2.80 - 2.80 2.85 2.94 - 2.91 2.97 3.06 - 3.00 3.06 3.16 -
Hi PR 234 252 266 - 262 282 298 - 298 321 339 - 340 366 386 - 382 412 435 - 423 455 480 -
Lo PR 99 106 115 - 105 112 122 - 109 116 127 - 115 122 133 - 120 128 140 - 124 132 144 -
Amps 8.9 9.1 9.4 - 9.6 9.8 10.2 - 10.4 10.7 11.0 - 11.1 11.4 11.7 - 11.8 12.1 12.5 - 12.5 12.8 13.2 -
∆T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
S/T 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.78 0.66 0.45 - 0.81 0.68 0.47 - 0.84 0.70 0.49 - 0.85 0.71 0.49 -
MBh 30.0 31.1 34.0 - 29.3 30.3 33.2 - 28.6 29.6 32.4 - 27.9 28.9 31.7 - 26.5 27.4 30.1 - 24.5 25.4 27.9 -
kW 2.39 2.43 2.50 - 2.55 2.61 2.68 - 2.70 2.76 2.84 - 2.83 2.89 2.98 - 2.95 3.01 3.10 - 3.04 3.11 3.20 -
Hi PR 238 256 270 - 267 287 303 - 304 327 345 - 346 372 393 - 389 419 442 - 430 463 488 -
Lo PR 101 108 117 - 107 114 124 - 111 118 129 - 117 124 135 - 122 130 142 - 126 134 147 -
Amps 9.1 9.3 9.6 - 9.8 10.0 10.3 - 10.6 10.8 11.2 - 11.3 11.6 11.9 - 12.0 12.3 12.7 - 12.7 13.0 13.4 -
MBh 30.9 32.0 35.1 - 30.1 31.2 34.2 - 29.4 30.5 33.4
∆T 16 14 11 - 16 14 11 - 16 14 11 - 17 14 11 - 16 14 11 - 15 13 10 -
S/T 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.82 0.69 0.48 - 0.85 0.71 0.49 - 0.88 0.74 0.51 - 0.89 0.74 0.51 -
kW 2.40 2.45 2.52 - 2.57 2.63 2.70 - 2.72 2.78 2.86 - 2.86 2.92 3.00 - 2.97 3.03 3.12 - 3.07 3.13 3.23 -
Hi PR 240 259 273 - 270 290 306 - 307 330 348 - 349 376 397 - 393 423 447 - 434 467 493 -
Lo PR 102 109 119 - 108 115 125 - 112 119 130 - 118 125 137 - 123 131 143 - 128 136 148 -
Amps 9.1
MBh 30.0 30.9 33.5 35.9 29.3 30.2 32.7 35.1 28.6 29.5 31.9 34.2 27.9 28.8 31.1 33.4 26.5 27.3 29.6 31.7 24.6 25.3 27.4 29.4
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.37 0.86 0.77 0.58 0.37 0.89 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
∆T 21 20 16 11 22 20 16 11 22 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10
kW 2.37 2.42 2.49 2.56 2.54 2.59 2.67 2.75 2.69 2.74 2.83 2.91 2.82 2.88 2.97 3.06 2.93 2.99 3.08 3.18 3.03 3.09 3.18 3.29
Amps 9.0 9.2 9.5 9.8 9.7 9.9 10.2 10.6 10.5 10.8 11.1 11.5 11.2 11.5 11.9 12.3 11.9 12.2 12.6 13.1 12.6 12.9 13.3 13.8
Hi PR 236 254 268 280 265 285 301 314 302 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
Lo PR 100 107 117 124 106 113 123 131 110 117 128 136 116 123 134 143 121 129 141 150 126 134 146 155
MBh 30.5 31.4 34.0 36.5 29.8 30.6 33.2 35.6 29.1 29.9 32.4 34.8 28.4 29.2 31.6 33.9 26.9 27.7 30.0 32.2 24.9 25.7 27.8 29.8
S/T 0.84 0.75 0.57 0.37 0.87 0.78 0.59 0.38 0.89 0.80 0.60 0.39 0.92 0.82 0.62 0.40 0.96 0.85 0.65 0.42 0.96 0.86 0.65 0.42
1140
75
1350
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) Rang Condions kW = Total system power
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1050
1140
70
1350
1050
8 www.goodmanmfg.com SS-iGSZ13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 9
CooliNg Data — gSZ130365a*/a36-00-2rC (CoNt.)
145 123 130 142 152 127 135 147 157
33.7 27.4 28.0 29.9 32.0 25.4 25.9 27.7 29.6
136
31.5
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
MBh 30.6 31.2 33.4 35.7 29.8 30.5 32.6 34.8 29.1 29.8 31.8 34.0 28.4 29.0 31.0 33.2 27.0 27.6 29.5 31.5 25.0 25.6 27.3 29.2
S/T 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0.53 0.94 0.89 0.72 0.54 0.97 0.91 0.74 0.56 1.01 0.95 0.77 0.58 1.00 0.96 0.78 0.58
∆T 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 22 21 19 15
kW 2.39 2.44 2.51 2.58 2.56 2.61 2.69 2.77 2.71 2.76 2.85 2.94 2.84 2.90 2.99 3.08 2.95 3.01 3.11 3.21 3.05 3.11 3.21 3.31
Amps 9.1 9.3 9.6 9.9 9.8 10.0 10.3 10.7 10.6 10.9 11.2 11.6 11.3 11.6 12.0 12.4 12.0 12.3 12.7 13.2 12.7 13.0 13.5 14.0
Hi PR 239 257 271 283 268 288 304 317 305 328 346 361 347 373 394 411 390 420 443 463 431 464 490 511
Lo PR 101 108 118 125 107 114 124 133 111 118 129 138 117 124
MBh 31.0 31.7 33.9 36.2 30.3 31.0 33.1 35.4 29.6 30.2 32.3 34.5 28.9 29.5
S/T 0.92 0.86 0.70 0.53 0.95 0.89 0.73 0.54 0.98 0.92 0.75 0.56 1.00 0.95 0.77 0.58 1.00 0.98 0.80 0.60 1.00 0.99 0.81 0.60
∆T 23 22 19 15 23 22 19 16 23 22 19 16 23 23 20 16 22 22 19 15 20 21 18 14
kW 2.42 2.47 2.54 2.62 2.59 2.65 2.72 2.81 2.75 2.80 2.89 2.98 2.88 2.94 3.03 3.12 2.99 3.06 3.15 3.25 3.09 3.16 3.25 3.36
Amps 9.2 9.4 9.7 10.1 9.9 10.2 10.5 10.9 10.8 11.0 11.4 11.8 11.5 11.8 12.1 12.6 12.2 12.5 12.9 13.4 12.9 13.2 13.7 14.2
Hi PR 243 261 276 288 272 293 310 323 310 333 352 367 353 380 401 418 397 427 451 471 439 472 498 520
Lo PR 103 110 120 128 109 116 127 135 113 121 132 140 119 127 138 147 125 133 145 154 129 137 150 160
35.6 29.7 30.4 32.4 34.7 28.2 28.9 30.8 32.9 26.2 26.7 28.6 30.5
MBh 31.9 32.6 34.9 37.3 31.2 31.9 34.1 36.4 30.5 31.1 33.3
S/T 0.97 0.91 0.74 0.55 1.00 0.94 0.76 0.57 1.00 0.96 0.78 0.59 1.00 1.00 0.81 0.60 1.00 1.00 0.84 0.63 1.00 1.00 0.85 0.63
∆T 21 20 18 14 21 20 18 14 21 20 18 14 20 21 18 14 19 20 18 14 18 18 16 13
kW 2.44 2.49 2.56 2.64 2.61 2.67 2.75 2.83 2.77 2.82 2.91 3.00 2.90 2.96 3.05 3.15 3.02 3.08 3.18 3.28 3.12 3.18 3.28 3.39
9.5 9.8 10.2 10.0 10.3 10.6 11.0 10.9 11.1 11.5 11.9 11.6 11.9 12.3 12.7 12.3 12.6 13.0 13.5 13.0 13.4 13.8 14.3
Amps 9.3
Hi PR 245 264 279 291 275 296 313 326 313 337 356 371 356 384 405 422 401 431 456 475 443 477 503 525
Lo PR 104 111 121 129 110 117 128 136 114 122 133 142 120 128 140 149 126 134 146 156 130 139 151 161
MBh 31.1 31.7 33.2 35.4 30.4 31.0 32.4 34.6 29.6 30.2 31.6 33.8 28.9 29.5 30.9 32.9 27.5 28.0 29.3 31.3 25.4 25.9 27.2 29.0
S/T 0.93 0.90 0.81 0.66 0.96 0.93 0.84 0.68 0.99 0.95 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.76
∆T 25 25 24 20 26 25 24 21 26 25 24 21 25 25 24 21 24 25 24 21 22 23 22 19
kW 2.41 2.46 2.53 2.60 2.58 2.63 2.71 2.79 2.73 2.79 2.87 2.96 2.86 2.92 3.01 3.11 2.98 3.04 3.13 3.23 3.07 3.14 3.24 3.34
Amps 9.2 9.4 9.7 10.0 9.9 10.1 10.4 10.8 10.7 11.0 11.3 11.7 11.4 11.7 12.1 12.5 12.1 12.4 12.8 13.3 12.8 13.1 13.6 14.1
Hi PR 241 259 274 286 270 291 307 321 308 331 350 365 350 377 398 415 394 424 448 467 435 469 495 516
Lo PR 102 109 119 127 108 115 126 134 112 120 131 139 118 126 137 146 124 132 144 153 128 136 149 158
MBh 31.6 32.2 33.7 35.9 30.8 31.4 32.9 35.1 30.1 30.7 32.1 34.3 29.4 29.9 31.3 33.4 27.9 28.4 29.8 31.8 25.8 26.3 27.6 29.4
S/T 0.97 0.93 0.84 0.68 1.00 0.97 0.87 0.71 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.96 0.78 1.00 1.00 0.97 0.78
24 24 23 20 24 24 23 20 22 23 23 20 21 21 21 19
∆T 25 24 23 20 25 24 23 20
kW 2.44 2.49 2.56 2.64 2.61 2.67 2.75 2.83 2.77 2.82 2.91 3.00 2.90 2.96 3.05 3.15 3.02 3.08 3.18 3.28 3.12 3.18 3.28 3.39
9.5 9.8 10.2 10.0 10.3 10.6 11.0 10.9 11.1 11.5 11.9 11.6 11.9 12.3 12.7 12.3 12.6 13.0 13.5 13.0 13.4 13.8 14.3
Amps 9.3
Hi PR 245 264 279 291 275 296 313 326 313 337 356 371 356 384 405 422 401 431 456 475 443 477 503 525
Lo PR 104 111 121 129 110 117 128 136 114 122 133 142 120 128 140 149 126 134 146 156 130 139 151 161
MBh 32.5 33.1 34.7 37.0 31.8 32.4 33.9 36.2 31.0 31.6 33.1 35.3 30.2 30.8 32.3 34.4 28.7 29.3 30.7 32.7 26.6 27.1 28.4 30.3
S/T 1.00 0.98 0.88 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.78 1.00 1.00 1.00 0.81 1.00 1.00 1.00 0.82
∆T 22 22 21 18 22 22 21 18 21 22 21 18 21 21 21 18 20 20 21 18 18 18 19 17
kW 2.46 2.51 2.58 2.66 2.63 2.69 2.77 2.85 2.79 2.84 2.93 3.02 2.92 2.98 3.08 3.17 3.04 3.10 3.20 3.30 3.14 3.21 3.31 3.41
Amps 9.4 9.6 9.9 10.3 10.1 10.3 10.7 11.1 11.0 11.2 11.6 12.0 11.7 12.0 12.4 12.8 12.4 12.7 13.1 13.6 13.2 13.5 13.9 14.4
Hi PR 248 267 281 294 278 299 316 329 316 340 359 375 360 387 409 427 405 436 460 480 447 482 508 530
Lo PR 105 112 122 130 111 118 129 138 116 123 134 143 121 129 141 150 127 135 148 157 132 140 153 163
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1050
1140
80
1350
1050
1140
85
1350
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) Rang Condions kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 9
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 10
expaNDeD Data expaNDeD Data
CooliNg Data — gSZ130485a*/a48-00-2rC
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 39.8 41.3 45.2 - 37.9 39.2 43.0 - 35.1 36.3 39.8 -
24 22 18 13 24 23 18 13 24 22 18 13 23 21 17 12
∆T 24 22 18 12 24 22 18 13
kW 3.17 3.23 3.32 3.42 3.39 3.46 3.56 3.67 3.59 3.66 3.77 3.89 3.76 3.84 3.96 4.08 3.91 3.99 4.12 4.25 4.04 4.13 4.25 4.39
12.3 12.7 13.1 12.9 13.2 13.7 14.2 14.0 14.4 14.8 15.4 15.0 15.3 15.8 16.4 15.9 16.3 16.8 17.5 16.8 17.3 17.8 18.5
Amps 12.0
Hi PR 234 251 266 277 262 282 298 311 298 321 339 353 340 366 386 403 382 411 434 453 422 454 480 500
Lo PR 101 107 117 125 107 113 124 132 111 118 129 137 116 124 135 144 122 130 142 151 126 134 146 156
MBh 43.6 44.8 48.5 52.1 42.5 43.8 47.4 50.9 41.5 42.8 46.3 49.7 40.5 41.7 45.2 48.5 38.5 39.6 42.9 46.0 35.7 36.7 39.7 42.7
S/T 0.86 0.77 0.58 0.37 0.89 0.79 0.60 0.39 0.91 0.81 0.62 0.40 0.94 0.84 0.64 0.41 0.97 0.87 0.66 0.42 0.98 0.88 0.67 0.43
∆T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 17 11 20 19 15 11
kW 3.21 3.28 3.37 3.47 3.44 3.51 3.62 3.73 3.64 3.72 3.83 3.95 3.82 3.90 4.02 4.15 3.97 4.06 4.18 4.32 4.10 4.19 4.32 4.46
Amps 12.2 12.5 12.9 13.4 13.2 13.5 13.9 14.4 14.3 14.6 15.1 15.7 15.2 15.6 16.1 16.7 16.2 16.6 17.1 17.8 17.1 17.6 18.1 18.8
Hi PR 238 257 271 283 267 288 304 317 304 327 346 361 346 373 394 411 390 419 443 462 431 463 489 510
Lo PR 103 109 120 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159
12.4 12.8 - 13.1 13.4 13.8 - 14.2 14.5 15.0 - 15.1 15.5 16.0 - 16.1 16.4 17.0 - 17.0 17.4 18.0 -
∆T 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 20 17 13 -
S/T 0.68 0.57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.78 0.65 0.45 - 0.78 0.66 0.45 -
MBh 40.8 42.3 46.3 - 39.8 41.3 45.2 - 38.9 40.3 44.1 - 37.9 39.3 43.1 - 36.0 37.3 40.9 - 33.4 34.6 37.9 -
kW 3.10 3.16 3.26 - 3.32 3.39 3.49 - 3.51 3.59 3.69 - 3.69 3.76 3.88 - 3.83 3.91 4.03 - 3.95 4.04 4.16 -
Hi PR 227 245 258 - 255 275 290 - 290 312 330 - 331 356 376 - 372 400 423 - 411 442 467 -
Lo PR 98 104 114 - 104 110 120 - 108 115 125 - 113 120 131 - 119 126 138 - 123 131 143 -
Amps 11.7 12.0 12.4 - 12.6 12.9 13.3 - 13.7 14.0 14.5 - 14.6 15.0 15.4 - 15.5 15.9 16.4 - 16.4 16.8 17.4 -
∆T 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 19 17 13 -
S/T 0.71 0.59 0.41 - 0.73 0.61 0.43 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.81 0.68 0.47 -
MBh 41.4 42.9 47.0 - 40.4 41.9 45.9 - 39.5 40.9 44.8 - 38.5 39.9 43.7 - 36.6 37.9 41.5 - 33.9 35.1 38.5 -
kW 3.14 3.20 3.30 - 3.36 3.43 3.53 - 3.56 3.63 3.74 - 3.73 3.81 3.93 - 3.88 3.96 4.08 - 4.01 4.09 4.22 -
Hi PR 231 249 263 - 260 279 295 - 295 318 335 - 336 362 382 - 378 407 430 - 418 450 475 -
Lo PR 100 106 116 - 106 112 123 - 110 117 127 - 115 123 134 - 121 128 140 - 125 133 145 -
Amps 11.9 12.2 12.6 - 12.8 13.1 13.5 - 13.9 14.2 14.7 - 14.8 15.2 15.7 - 15.8 16.1 16.7 - 16.7 17.1 17.7 -
MBh 42.8 44.4 48.6 - 41.8 43.4 47.5 - 40.8 42.3 46.4
∆T 19 16 12 - 19 17 13 - 19 17 13 - 19 17 13 - 19 16 12 - 18 15 12 -
S/T 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.86 0.72 0.50 -
kW 3.19 3.25 3.35 - 3.42 3.48 3.59 - 3.62 3.69 3.80 - 3.79 3.87 3.99 - 3.94 4.02 4.15 - 4.07 4.16 4.29 -
Hi PR 236 254 268 - 265 285 301 - 301 324 342 - 343 369 390 - 386 415 438 - 426 459 484 -
Lo PR 102 108 118 - 108 114 125 - 112 119 130 - 117 125 136 - 123 131 143 - 127 135 148 -
Amps 12.1
MBh 41.5 42.7 46.2 49.6 40.5 41.7 45.1 48.4 39.5 40.7 44.1 47.3 38.6 39.7 43.0 46.1 36.6 37.7 40.8 43.8 33.9 34.9 37.8 40.6
S/T 0.78 0.70 0.53 0.34 0.81 0.72 0.55 0.35 0.83 0.74 0.56 0.36 0.85 0.76 0.58 0.37 0.88 0.79 0.60 0.39 0.89 0.80 0.60 0.39
∆T 24 22 18 13 24 23 18 13 24 23 18 13 25 23 19 13 24 22 18 13 23 21 17 12
kW 3.13 3.19 3.28 3.38 3.35 3.41 3.52 3.62 3.54 3.61 3.72 3.84 3.71 3.79 3.91 4.03 3.86 3.94 4.06 4.19 3.99 4.07 4.20 4.33
Amps 11.8 12.1 12.5 12.9 12.7 13.0 13.5 14.0 13.8 14.1 14.6 15.1 14.7 15.1 15.6 16.2 15.7 16.0 16.6 17.2 16.6 17.0 17.5 18.2
Hi PR 230 247 261 272 258 277 293 306 293 315 333 347 334 359 379 396 376 404 427 445 415 447 472 492
Lo PR 99 105 115 123 105 111 122 130 109 116 126 135 114 122 133 141 120 128 139 148 124 132 144 153
MBh 42.1 43.3 46.9 50.3 41.1 42.3 45.8 49.2 40.1 41.3 44.7 48.0 39.2 40.3 43.6 46.8 37.2 38.3 41.4 44.5 34.5 35.5 38.4 41.2
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.37 0.88 0.79 0.60 0.38 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1225
1300
70
1575
1225
1300
75
1575
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) Rang Condions kW = Total system power
10 www.goodmanmfg.com SS-iGSZ13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 11
CooliNg Data — gSZ130485a*/a48-00-2rC (CoNt.)
143 121 129 141 150 125 133 145 155
46.5 37.9 38.7 41.3 44.2 35.1 35.8 38.3 40.9
134
43.5
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
MBh 42.2 43.1 46.1 49.2 41.2 42.1 45.0 48.1 40.2 41.1 43.9 46.9 39.2 40.1 42.8 45.8 37.3 38.1 40.7 43.5 34.5 35.3 37.7 40.3
S/T 0.85 0.80 0.65 0.49 0.88 0.83 0.67 0.50 0.91 0.85 0.69 0.52 0.93 0.88 0.71 0.53 0.97 0.91 0.74 0.55 0.98 0.92 0.75 0.56
∆T 27 26 22 18 27 26 23 18 27 26 23 18 28 26 23 18 27 26 23 18 25 24 21 17
kW 3.15 3.21 3.30 3.40 3.37 3.44 3.54 3.65 3.57 3.64 3.75 3.87 3.74 3.82 3.94 4.06 3.89 3.97 4.09 4.22 4.02 4.10 4.23 4.37
Amps 11.9 12.2 12.6 13.0 12.9 13.2 13.6 14.1 13.9 14.3 14.7 15.3 14.9 15.2 15.7 16.3 15.8 16.2 16.7 17.3 16.7 17.1 17.7 18.4
Hi PR 232 250 264 275 260 280 296 309 296 319 337 351 337 363 383 400 379 408 431 450 419 451 476 497
Lo PR 100 107 116 124 106 113 123 131 110 117 128 136 116 123
MBh 42.8 43.8 46.8 50.0 41.8 42.8 45.7 48.8 40.8 41.7 44.6 47.7 39.8 40.7
S/T 0.88 0.83 0.67 0.50 0.92 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 0.95 0.77 0.58
∆T 27 26 22 18 27 26 23 18 27 26 23 18 27 26 23 18 27 26 22 18 25 24 21 17
kW 3.19 3.25 3.35 3.45 3.42 3.48 3.59 3.70 3.62 3.69 3.80 3.92 3.79 3.87 3.99 4.12 3.94 4.03 4.15 4.28 4.07 4.16 4.29 4.43
Amps 12.1 12.4 12.8 13.2 13.1 13.4 13.8 14.3 14.2 14.5 15.0 15.5 15.1 15.5 16.0 16.6 16.1 16.4 17.0 17.6 17.0 17.4 18.0 18.7
Hi PR 236 254 268 280 265 285 301 314 301 324 342 357 343 369 390 407 386 415 439 457 426 459 485 505
Lo PR 102 108 118 126 108 115 125 133 112 119 130 138 118 125 137 145 123 131 143 152 127 136 148 158
49.3 41.2 42.1 45.0 48.1 39.2 40.0 42.8 45.7 36.3 37.1 39.6 42.4
MBh 44.3 45.3 48.4 51.7 43.3 44.2 47.3 50.5 42.3 43.2 46.1
S/T 0.94 0.88 0.72 0.54 1.00 0.91 0.74 0.56 1.00 0.94 0.76 0.57 1.00 1.00 0.79 0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.82 0.62
∆T 24 23 20 16 25 24 21 16 25 24 21 16 24 25 21 17 23 23 20 16 21 22 19 15
kW 3.24 3.30 3.40 3.50 3.47 3.54 3.64 3.76 3.67 3.75 3.86 3.98 3.85 3.93 4.05 4.18 4.00 4.09 4.22 4.35 4.14 4.22 4.36 4.50
12.6 13.0 13.5 13.3 13.6 14.0 14.6 14.4 14.8 15.2 15.8 15.4 15.7 16.3 16.9 16.4 16.7 17.3 17.9 17.3 17.7 18.3 19.0
Amps 12.3
Hi PR 241 259 274 285 270 291 307 320 307 331 349 364 350 377 398 415 394 424 447 467 435 468 494 516
Lo PR 104 111 121 129 110 117 128 136 114 121 133 141 120 128 139 148 126 134 146 155 130 138 151 161
MBh 42.9 43.8 45.8 48.9 41.9 42.7 44.8 47.8 40.9 41.7 43.7 46.6 39.9 40.7 42.6 45.5 37.9 38.7 40.5 43.2 35.1 35.8 37.5 40.0
S/T 0.89 0.86 0.78 0.63 0.93 0.89 0.81 0.65 0.95 0.92 0.83 0.67 0.98 0.95 0.85 0.69 1.00 0.98 0.89 0.72 1.00 0.99 0.89 0.72
∆T 29 28 27 23 29 29 27 23 29 29 27 23 29 29 27 24 28 28 27 23 26 27 25 22
kW 3.17 3.23 3.33 3.43 3.40 3.47 3.57 3.68 3.60 3.67 3.78 3.90 3.77 3.85 3.97 4.09 3.92 4.00 4.13 4.26 4.05 4.13 4.26 4.40
Amps 12.0 12.3 12.7 13.2 13.0 13.3 13.7 14.2 14.1 14.4 14.9 15.4 15.0 15.4 15.9 16.5 16.0 16.3 16.9 17.5 16.9 17.3 17.9 18.5
Hi PR 234 252 266 278 263 283 299 312 299 322 340 354 341 367 387 404 383 412 435 454 423 456 481 502
Lo PR 101 108 117 125 107 114 124 132 111 118 129 137 117 124 136 144 122 130 142 151 126 135 147 156
MBh 43.6 44.4 46.5 49.6 42.6 43.4 45.4 48.5 41.6 42.4 44.4 47.3 40.5 41.3 43.3 46.2 38.5 39.3 41.1 43.9 35.7 36.4 38.1 40.6
S/T 0.93 0.89 0.81 0.65 0.96 0.93 0.84 0.68 0.98 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.75
29 28 27 23 29 29 27 23 27 28 27 23 25 26 25 22
∆T 29 28 27 23 29 28 27 23
kW 3.21 3.28 3.37 3.47 3.44 3.51 3.62 3.73 3.64 3.72 3.83 3.95 3.82 3.90 4.02 4.15 3.97 4.06 4.18 4.32 4.10 4.19 4.32 4.46
12.5 12.9 13.4 13.2 13.5 13.9 14.4 14.3 14.6 15.1 15.7 15.2 15.6 16.1 16.7 16.2 16.6 17.1 17.8 17.2 17.6 18.2 18.8
Amps 12.2
Hi PR 238 257 271 283 268 288 304 317 304 327 346 361 347 373 394 411 390 420 443 462 431 464 489 511
Lo PR 103 109 120 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159
MBh 45.1 46.0 48.2 51.4 44.1 44.9 47.0 50.2 43.0 43.8 45.9 49.0 42.0 42.8 44.8 47.8 39.9 40.6 42.6 45.4 36.9 37.6 39.4 42.1
S/T 0.98 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.98 0.79 1.00 1.00 0.98 0.80
∆T 26 26 24 21 26 26 24 21 25 26 24 21 24 25 25 21 23 24 24 21 22 22 23 20
kW 3.26 3.32 3.42 3.53 3.49 3.56 3.67 3.78 3.70 3.78 3.89 4.01 3.88 3.96 4.09 4.22 4.04 4.12 4.25 4.39 4.17 4.26 4.39 4.53
Amps 12.4 12.7 13.1 13.6 13.4 13.7 14.2 14.7 14.5 14.9 15.4 15.9 15.5 15.9 16.4 17.0 16.5 16.9 17.5 18.1 17.5 17.9 18.5 19.2
Hi PR 243 262 276 288 273 294 310 323 310 334 353 368 353 380 402 419 398 428 452 471 439 473 499 521
Lo PR 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1225
1300
80
1575
1225
1300
85
1575
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) Rang Condions kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 11
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 12
expaNDeD Data expaNDeD Data
CooliNg Data — gSZ130605a*/a60-00-2rC
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 47.6 49.4 54.1 - 45.2 46.9 51.4 - 41.9 43.4 47.6 -
23 21 17 12 23 21 17 12 23 21 17 12 21 20 16 11
∆T 23 21 17 12 23 21 17 12
kW 3.60 3.67 3.77 3.88 3.85 3.92 4.04 4.16 4.07 4.15 4.28 4.41 4.27 4.35 4.49 4.63 4.43 4.53 4.66 4.81 4.58 4.67 4.82 4.97
13.8 14.2 14.8 14.5 14.9 15.4 15.9 15.8 16.1 16.7 17.3 16.8 17.2 17.8 18.4 17.9 18.3 18.9 19.6 18.9 19.4 20.0 20.8
Amps 13.5
Hi PR 232 249 263 275 260 280 295 308 296 318 336 350 337 362 383 399 379 408 430 449 418 450 475 496
Lo PR 103 110 120 128 109 116 127 135 114 121 132 140 119 127 139 148 125 133 145 155 129 138 150 160
MBh 52.1 53.6 58.0 62.3 50.9 52.4 56.7 60.8 49.6 51.1 55.3 59.4 48.4 49.9 54.0 57.9 46.0 47.4 51.3 55.0 42.6 43.9 47.5 51.0
S/T 0.88 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.94 0.84 0.64 0.41 0.97 0.87 0.66 0.42 1.00 0.90 0.68 0.44 1.00 0.91 0.69 0.44
∆T 19 17 14 10 19 18 14 10 19 18 14 10 19 18 14 10 19 17 14 10 17 16 13 9
kW 3.65 3.72 3.83 3.94 3.91 3.98 4.10 4.23 4.13 4.22 4.34 4.48 4.33 4.42 4.56 4.70 4.50 4.60 4.74 4.89 4.65 4.75 4.89 5.05
Hi PR 236 254 268 280 265 285 301 314 301 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
Lo PR 105 112 122 130 111 119 129 138 116 123 134 143 122 129 141 150 127 136 148 158 132 140 153 163
Amps 13.7 14.0 14.5 15.0 14.8 15.1 15.6 16.2 16.0 16.4 17.0 17.6 17.1 17.5 18.1 18.8 18.2 18.6 19.3 20.0 19.3 19.7 20.4 21.1
13.9 14.4 - 14.7 15.0 15.5 - 15.9 16.3 16.8 - 17.0 17.4 17.9 - 18.0 18.5 19.1 - 19.1 19.5 20.2 -
∆T 19 16 12 - 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 18 15 12 -
S/T 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.70 0.48 - 0.84 0.70 0.49 -
MBh 49.5 51.3 56.2 - 48.3 50.1 54.9 - 47.2 48.9 53.6 - 46.0 47.7 52.3 - 43.7 45.3 49.6 - 40.5 42.0 46.0 -
kW 3.57 3.64 3.74 - 3.82 3.90 4.01 - 4.04 4.12 4.24 - 4.23 4.32 4.45 - 4.40 4.49 4.63 - 4.54 4.64 4.78 -
Hi PR 229 247 261 - 257 277 292 - 293 315 332 - 333 359 379 - 375 403 426 - 414 446 471 -
Lo PR 102 109 119 - 108 115 126 - 112 120 131 - 118 126 137 - 124 132 144 - 128 136 149 -
Amps 13.4 13.7 14.1 - 14.4 14.8 15.2 - 15.6 16.0 16.5 - 16.7 17.1 17.6 - 17.7 18.1 18.7 - 18.7 19.2 19.8 -
∆T 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 18 16 12 -
S/T 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.70 0.48 - 0.84 0.70 0.49 -
MBh 49.5 51.3 56.2 - 48.3 50.1 54.9 - 47.2 48.9 53.6 - 46.0 47.7 52.3 - 43.7 45.3 49.6 - 40.5 42.0 46.0 -
kW 3.57 3.64 3.74 - 3.82 3.90 4.01 - 4.04 4.12 4.24 - 4.23 4.32 4.45 - 4.40 4.49 4.63 - 4.54 4.64 4.78 -
Hi PR 229 247 261 - 257 277 292 - 293 315 332 - 333 359 379 - 375 403 426 - 414 446 471 -
Lo PR 102 109 119 - 108 115 126 - 112 120 131 - 118 126 137 - 124 132 144 - 128 136 149 -
Amps 13.4 13.7 14.1 - 14.4 14.8 15.2 - 15.6 16.0 16.5 - 16.7 17.1 17.6 - 17.7 18.1 18.7 - 18.7 19.2 19.8 -
MBh 51.2 53.1 58.1 - 50.0 51.8 56.8 - 48.8 50.6 55.4
∆T 16 14 11 - 16 14 11 - 16 14 11 - 17 14 11 - 16 14 11 - 15 13 10 -
S/T 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.83 0.69 0.48 - 0.85 0.71 0.49 - 0.89 0.74 0.51 - 0.89 0.75 0.52 -
kW 3.62 3.69 3.80 - 3.88 3.95 4.07 - 4.10 4.18 4.31 - 4.30 4.39 4.52 - 4.47 4.56 4.70 - 4.61 4.71 4.85 -
Hi PR 234 252 266 - 262 282 298 - 298 321 339 - 340 366 386 - 382 411 435 - 422 455 480 -
Lo PR 104 111 121 - 110 117 128 - 115 122 133 - 120 128 140 - 126 134 147 - 131 139 152 -
Amps 13.6
MBh 50.3 51.8 56.1 60.2 49.1 50.6 54.8 58.8 48.0 49.4 53.5 57.4 46.8 48.2 52.2 56.0 44.5 45.8 49.5 53.2 41.2 42.4 45.9 49.3
S/T 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.38 0.88 0.79 0.60 0.39 0.91 0.82 0.62 0.40 0.95 0.85 0.64 0.41 0.96 0.85 0.65 0.42
∆T 22 20 17 11 22 20 17 12 22 21 17 12 22 21 17 12 22 20 17 12 21 19 16 11
kW 3.60 3.67 3.77 3.88 3.85 3.92 4.04 4.16 4.07 4.15 4.28 4.41 4.27 4.35 4.49 4.63 4.43 4.53 4.66 4.81 4.58 4.67 4.82 4.97
Amps 13.5 13.8 14.2 14.8 14.5 14.9 15.4 15.9 15.8 16.1 16.7 17.3 16.8 17.2 17.8 18.4 17.9 18.3 18.9 19.6 18.9 19.4 20.0 20.8
Hi PR 232 249 263 275 260 280 295 308 296 318 336 350 337 362 383 399 379 408 430 449 418 450 475 496
Lo PR 103 110 120 128 109 116 127 135 114 121 132 140 119 127 139 148 125 133 145 155 129 138 150 160
MBh 50.3 51.8 56.1 60.2 49.1 50.6 54.8 58.8 48.0 49.4 53.5 57.4 46.8 48.2 52.2 56.0 44.5 45.8 49.5 53.2 41.2 42.4 45.9 49.3
S/T 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.38 0.88 0.79 0.60 0.39 0.91 0.82 0.62 0.40 0.95 0.85 0.64 0.41 0.96 0.85 0.65 0.42
1700
75
2250
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) Rang Condions kW = Total system power
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1750
1700
70
2250
1750
12 www.goodmanmfg.com SS-iGSZ13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 13
CooliNg Data — gSZ130605a*/a60-00-2rC (CoNt.)
149 126 134 147 156 131 139 152 162
55.6 45.3 46.2 49.4 52.8 41.9 42.8 45.8 48.9
140
52.0
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
MBh 51.2 52.3 55.9 59.8 50.0 51.1 54.6 58.4 48.8 49.9 53.3 57.0 47.6 48.7 52.0 55.6 45.3 46.2 49.4 52.8 41.9 42.8 45.8 48.9
S/T 0.91 0.86 0.70 0.52 0.95 0.89 0.72 0.54 0.97 0.91 0.74 0.55 1.00 0.94 0.76 0.57 1.00 0.97 0.79 0.59 1.00 0.98 0.80 0.60
∆T 25 24 20 16 25 24 21 17 25 24 21 17 25 24 21 17 24 24 21 16 22 22 19 15
kW 3.62 3.69 3.80 3.91 3.88 3.95 4.07 4.19 4.10 4.18 4.31 4.44 4.30 4.39 4.52 4.66 4.47 4.56 4.70 4.85 4.61 4.71 4.86 5.01
Amps 13.6 13.9 14.4 14.9 14.7 15.0 15.5 16.1 15.9 16.3 16.8 17.4 17.0 17.4 17.9 18.6 18.0 18.5 19.1 19.8 19.1 19.6 20.2 21.0
Hi PR 234 252 266 277 263 282 298 311 299 321 339 354 340 366 386 403 383 412 435 453 423 455 480 501
Lo PR 104 111 121 129 110 117 128 136 115 122 133 142 120 128
MBh 51.2 52.3 55.9 59.8 50.0 51.1 54.6 58.4 48.8 49.9 53.3 57.0 47.6 48.7
S/T 0.91 0.86 0.70 0.52 0.95 0.89 0.72 0.54 0.97 0.91 0.74 0.55 1.00 0.94 0.76 0.57 1.00 0.97 0.79 0.59 1.00 0.98 0.80 0.60
∆T 25 24 21 17 26 25 21 17 26 25 21 17 26 25 21 17 24 24 21 17 23 23 20 16
kW 3.62 3.69 3.80 3.91 3.88 3.95 4.07 4.19 4.10 4.18 4.31 4.44 4.30 4.39 4.52 4.66 4.47 4.56 4.70 4.85 4.61 4.71 4.86 5.01
Amps 13.6 13.9 14.4 14.9 14.7 15.0 15.5 16.1 15.9 16.3 16.8 17.4 17.0 17.4 17.9 18.6 18.0 18.5 19.1 19.8 19.1 19.6 20.2 21.0
Hi PR 234 252 266 277 263 282 298 311 299 321 339 354 340 366 386 403 383 412 435 453 423 455 480 501
Lo PR 104 111 121 129 110 117 128 136 115 122 133 142 120 128 140 149 126 134 147 156 131 139 152 162
59.0 49.3 50.4 53.8 57.5 46.8 47.9 51.1 54.7 43.4 44.3 47.4 50.6
MBh 53.0 54.2 57.9 61.8 51.8 52.9 56.5 60.4 50.5 51.6 55.2
S/T 1.00 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 1.00 0.79 0.59 1.00 1.00 0.81 0.61 1.00 1.00 0.84 0.63 1.00 1.00 0.85 0.64
∆T 22 20 17 14 21 20 18 14 21 21 18 14 20 21 18 14 19 20 18 14 18 18 16 13
kW 3.68 3.75 3.86 3.97 3.94 4.01 4.13 4.26 4.16 4.25 4.38 4.51 4.37 4.46 4.59 4.74 4.54 4.63 4.78 4.93 4.69 4.78 4.93 5.09
14.2 14.6 15.1 14.9 15.3 15.8 16.4 16.2 16.6 17.1 17.7 17.3 17.7 18.3 19.0 18.4 18.8 19.4 20.2 19.4 19.9 20.6 21.3
Amps 13.8
Hi PR 239 257 271 283 268 288 304 317 305 328 346 361 347 373 394 411 390 420 443 462 431 464 490 511
Lo PR 107 113 124 132 113 120 131 139 117 124 136 145 123 131 143 152 129 137 150 159 133 142 155 165
MBh 52.1 53.1 55.6 59.3 50.9 51.9 54.3 58.0 49.7 50.6 53.0 56.6 48.5 49.4 51.7 55.2 46.0 46.9 49.2 52.4 42.6 43.5 45.5 48.6
S/T 0.96 0.92 0.83 0.68 0.99 0.96 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.95 0.77 1.00 1.00 0.96 0.78
∆T 26 26 24 21 27 26 25 21 26 26 25 21 25 26 25 21 24 25 24 21 22 23 23 20
kW 3.65 3.72 3.83 3.94 3.91 3.98 4.10 4.23 4.13 4.22 4.34 4.48 4.33 4.42 4.56 4.70 4.50 4.60 4.74 4.89 4.65 4.75 4.89 5.05
Amps 13.7 14.0 14.5 15.0 14.8 15.2 15.6 16.2 16.1 16.4 17.0 17.6 17.1 17.5 18.1 18.8 18.2 18.6 19.3 20.0 19.3 19.7 20.4 21.2
Hi PR 236 254 269 280 265 285 301 314 302 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
Lo PR 105 112 123 130 111 119 129 138 116 123 135 143 122 129 141 150 127 136 148 158 132 140 153 163
MBh 52.1 53.1 55.6 59.3 50.9 51.9 54.3 58.0 49.7 50.6 53.0 56.6 48.5 49.4 51.7 55.2 46.0 46.9 49.2 52.4 42.6 43.5 45.5 48.6
S/T 0.96 0.92 0.83 0.68 0.99 0.96 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.95 0.77 1.00 1.00 0.96 0.78
27 27 25 22 26 27 26 22 25 25 25 22 23 24 24 20
∆T 27 27 25 22 27 27 25 22
kW 3.65 3.72 3.83 3.94 3.91 3.98 4.10 4.23 4.13 4.22 4.34 4.48 4.33 4.42 4.56 4.70 4.50 4.60 4.74 4.89 4.65 4.75 4.89 5.05
14.0 14.5 15.0 14.8 15.2 15.6 16.2 16.1 16.4 17.0 17.6 17.1 17.5 18.1 18.8 18.2 18.6 19.3 20.0 19.3 19.7 20.4 21.2
Amps 13.7
Hi PR 236 254 269 280 265 285 301 314 302 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
Lo PR 105 112 123 130 111 119 129 138 116 123 135 143 122 129 141 150 127 136 148 158 132 140 153 163
MBh 53.9 55.0 57.6 61.4 52.7 53.7 56.2 60.0 51.4 52.4 54.9 58.6 50.2 51.1 53.6 57.1 47.7 48.6 50.9 54.3 44.1 45.0 47.1 50.3
S/T 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.79 1.00 1.00 1.00 0.82 1.00 1.00 1.00 0.82
∆T 22 22 21 18 22 22 21 18 21 21 21 18 20 21 21 18 19 20 21 18 18 18 19 17
kW 3.70 3.77 3.88 4.00 3.96 4.04 4.16 4.29 4.20 4.28 4.41 4.55 4.40 4.49 4.63 4.77 4.57 4.67 4.81 4.97 4.72 4.82 4.97 5.13
Amps 14.0 14.3 14.7 15.3 15.1 15.4 15.9 16.5 16.3 16.7 17.3 17.9 17.4 17.9 18.4 19.1 18.5 19.0 19.6 20.3 19.6 20.1 20.8 21.5
Hi PR 241 259 274 286 270 291 307 321 308 331 350 365 350 377 398 415 394 424 448 467 435 469 495 516
Lo PR 108 114 125 133 114 121 132 141 118 126 137 146 124 132 144 153 130 138 151 161 135 143 156 166
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
1750
1700
80
2250
1750
1700
85
2250
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) Rang Condions kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 13
High and low pressures are measured at the liquid and sucon service valves. Amps = Outdoor unit amps (compressor + fan)
Page 14
expaNDeD Data expaNDeD Data
heatiNg Data
GSZ130242A*/A24-00-2RC
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 28.3 26.8 25.2 23.6 22.5 21.8 20.3 18.7 16.2 15.0 13.8 13.0 12.5 11.2 10.0 8.7 7.4 6.1
∆T 34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1 20.0 18.5 17.0 16.0 15.5 13.9 12.3 10.7 9.1 7.5
kW 1.94 1.90 1.87 1.83 1.8 1.80 1.76 1.72 1.53 1.49 1.46 1.44 1.43 1.40 1.37 1.34 1.30 1.27
Amps 10.6 9.8 9.1 8.6 8.3 8.1 7.7 7.3 7.0 6.6 6.3 6.2 6.1 5.8 5.4 5.1 4.7 4.2
COP 3.78 3.64 3.49 3.32 3.20 3.12 2.95 2.77 2.67 2.51 2.36 2.25 2.18 2.00 1.80 1.60 1.40 1.17
Hi PR 433.0 415.1 399.1 381.5 372.6 365.5 351.4 337.2 323.0 308.5 296.2 289.1 283.9 273.1 262.7 251.9 242.9 234.4
Lo PR 133 124 116 106 100 97 89 79 71 64 56 52 50 42 37 31 27 21
GSZ130362A*/A36-00-2RC
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 38.3 36.3 34.2 31.9 30.5 29.6 27.5 25.3 19.9 18.4 16.9 16.0 15.4 13.8 12.3 10.7 9.1 7.5
∆T 31.1 29.5 27.7 25.9 24.8 24.0 22.3 20.6 16.2 14.9 13.8 13.0 12.5 11.2 10.0 8.7 7.4 6.1
kW 2.60 2.56 2.51 2.46 2.4 2.42 2.37 2.33 2.13 2.08 2.04 2.02 2.00 1.96 1.92 1.88 1.83 1.79
Amps 14.1 13.1 12.3 11.6 11.1 10.9 10.3 9.8 9.4 9.0 8.6 8.4 8.3 7.9 7.4 6.9 6.4 5.8
COP 3.77 3.63 3.47 3.30 3.18 3.10 2.93 2.75 2.34 2.19 2.05 1.96 1.90 1.74 1.57 1.39 1.21 1.01
Hi PR 390.1 374.0 359.5 343.8 335.7 329.3 316.6 303.8 291.1 278.0 266.9 260.5 255.8 246.1 236.7 226.9 218.9 211.2
Lo PR 125 116 109 100 94 91 83 74 67 60 53 49 47 40 34 29 25 20
GSZ130365A*/A36-00-2RC
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 39.0 36.9 34.7 32.5 31.0 30.0 27.9 25.7 21.2 19.6 18.0 17.0 16.4 14.7 13.0 11.4 9.7 7.9
∆T 31.6 30.0 28.2 26.4 25.2 24.4 22.7 20.9 17.2 15.9 14.6 13.8 13.3 11.9 10.6 9.2 7.9 6.4
kW 2.54 2.49 2.45 2.40 2.4 2.36 2.32 2.27 2.06 2.02 1.98 1.95 1.94 1.90 1.86 1.82 1.78 1.74
Amps 13.8 12.8 12.0 11.3 10.9 10.7 10.1 9.6 9.2 8.8 8.4 8.2 8.1 7.7 7.2 6.8 6.3 5.7
COP 3.92 3.77 3.60 3.42 3.30 3.22 3.04 2.85 2.55 2.40 2.24 2.14 2.07 1.89 1.71 1.52 1.32 1.10
Hi PR 394.8 378.5 363.9 348.0 339.8 333.3 320.4 307.5 294.6 281.4 270.1 263.7 258.9 249.1 239.6 229.7 221.5 213.7
Lo PR 125 116 109 100 94 91 83 74 67 60 53 49 47 40 34 29 25 20
High pressure is measured at the sucon service valve ( the larger valve). Low pressure is measured at the gauge port connecon. Calculaons are based on nominal CFM and 70 °F indoor dry bulb.
Amps = Outdoor unit amps (comp.+fan)
kW = Total system power
14 www.goodmanmfg.com SS-iGSZ13
Page 15
heatiNg Data
GSZ130485A*/A48-00-2RC
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 59.7 56.5 53.2 49.7 47.5 46.0 42.8 39.4 39.9 36.8 33.9 32.0 30.8 27.6 24.5 21.4 18.2 14.9
∆T 42.5 40.3 37.9 35.4 33.8 32.8 30.4 28.1 28.4 26.2 24.1 22.8 21.9 19.7 17.5 15.2 13.0 10.6
kW 3.78 3.72 3.65 3.58 3.5 3.51 3.44 3.37 3.14 3.08 3.01 2.97 2.95 2.88 2.82 2.75 2.69 2.63
Amps 20.6 19.1 17.8 16.8 16.2 15.9 15.0 14.2 13.6 13.0 12.4 12.1 11.9 11.3 10.6 10.0 9.2 8.3
COP 4.08 3.93 3.76 3.58 3.45 3.37 3.18 2.99 3.21 3.02 2.83 2.70 2.62 2.40 2.16 1.92 1.68 1.40
Hi PR 455.7 436.9 420.0 401.6 392.2 384.7 369.8 354.9 340.0 324.7 311.8 304.3 298.9 287.5 276.5 265.1 255.7 246.7
Lo PR 137 128 120 110 104 100 92 82 74 66 58 54 52 44 38 32 28 22
GSZ130605A*/A60-00-2RC
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 69.1 65.5 61.6 57.6 55.0 53.3 49.5 45.7 44.2 40.8 37.6 35.5 34.2 30.7 27.2 23.7 20.2 16.6
∆T 37.7 35.6 33.6 31.4 30.0 29.0 27.0 24.9 24.1 22.2 20.5 19.3 18.6 16.7 14.8 12.9 11.0 9.0
kW 4.15 4.07 4.00 3.92 3.9 3.85 3.77 3.70 3.36 3.29 3.22 3.18 3.16 3.09 3.02 2.96 2.89 2.83
Amps 22.5 20.9 19.6 18.4 17.7 17.4 16.4 15.6 14.9 14.3 13.6 13.3 13.1 12.5 11.6 11.0 10.2 9.2
COP 4.27 4.11 3.93 3.73 3.60 3.51 3.32 3.11 3.28 3.08 2.88 2.75 2.67 2.44 2.20 1.95 1.70 1.42
Hi PR 428.2 410.5 394.7 377.3 368.5 361.5 347.5 333.5 319.5 305.1 293.0 286.0 280.8 270.1 259.8 249.1 240.3 231.8
Lo PR 137 128 120 110 104 100 92 82 74 66 58 54 52 44 38 32 28 22
High pressure is measured at the sucon service valve ( the larger valve). Low pressure is measured at the gauge port connecon. Calculaons are based on nominal CFM and 70 °F indoor dry bulb.
Amps = Outdoor unit amps (comp.+fan)
kW = Total system power
SS-iGSZ13 www.goodmanmfg.com 15
Page 16
Product SPecificationS Product SPecificationS
DimeNSioNS
W
D
H
Model
W” D” H”
GSZ130242A* 26 26 32¼
GSZ130362A* 29 29 32¼
GSZ130365A* 29 29 32¼
GSZ130485A* 29 29 34¼
GSZ130605A* 35½ 35½ 34¼

Dimensions

16 www.goodmanmfg.com SS-iGSZ13
Page 17
WiriNg Diagram gSZ130(24-36)2**
INDOOR POWER SUPPLY
NOTES:
1. TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK & INDOOR THERMOSTAT.
2. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
3. USE COPPER CONDUCTOR ONLY.
4. CRANKCASE HEATER & CRANKCASE HEATER SWITCH ARE FACTORY INSTALLED OPTION.
CRANKCASE HEATER MAY NOT HAVE ADDITIONAL GROUND WIRE
5. 40VA MINIMUM TRANSFORMER IS REQUIRED.
6. COMMON SIDE OF TRANSFORMER MUST BE GROUNDED.
COMP
ALTERNATE DOUBLE
POLE CONTACTOR ONLY
IO
T1
C
M
A
IN
R
A
U
X
5
S
SR
SA
2
1
RCCF
SC
T2
C
L1
L2
(IF USED)
NOTE 2
CH
C
F
M
A
I
N
A
U
X
IO
CM
0140R00171 - D
OR
BL/PK
BL
RD
O
Y
C
R
COLOR CODE
BK --------------- BLACK
BL/PK ---------- BLUE/PINK STRIPE
BR --------------- BROWN
GR---------------- GREEN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
YL/PK----------- YELLOW/PINK STRIPE
COMPONENT CODE
C --------------- CONTACTOR
CADM -------- COMFORT ALERT DIAGNOSTIC MODULE
CCR ----------- COMPRESSOR CONTACTOR RELAY
CH ------------- CRANKCASE HEATER
CHS ----------- CRANKCASE HEATER SWITCH
CM ------------ OUTDOOR FAN MOTOR
CMR ---------- CONDENSER MOTOR RELAY
COMP -------- COMPRESSOR
CS ------------- COMPRESSOR SOLENOID
DC ------------- DEFROST CONTROL
DFT ----------- DEFROST THERMOSTAT
DT ------------- DISCHARGE THERMOSTAT
HPS ----------- HIGH PRESSURE SWITCH
HVDR -------- HIGH VOLTAGE DEFROST RELAY
IO -------------- INTERNAL OVERLOAD
LPS --------
-- LOW PRESSURE SWITCH
LVDR --------- LOW VOLTAGE DEFROST RELAY
LVJB --------- LOW VOLTAGE JUNCTION BOX
RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN
RVC ----------- REVERSING VALVE COIL
SA ------------- START ASSIST
SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL)
SR ------------- START RELAY FOR COMPRESSOR (OPTIONAL)
CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
OUTDOOR POWER SUPPLY
SEE RATING PLATE
LVJB
CONTROL BOX
SC
RD
BL
L2
T2
L1
T1
C
BK
BK
BK
RD
RD
BL
RD
RCCF
YL
BR
PU
RD
SR
5
2
1
BK
YL
BL
IO
CM
AUX
MAIN
BR
PU
YL
RD
BK
YL/PK
LPS
DF1
DF2
CH
LVDR
R
CNT
DFT
C
Y
DC
DFT
WH
W2
DC
BL/PK
HPS
O
C
RVC
W2
R
HVDR
YL/PK
BK
BK
BL
BL
CHS
R-DFT
C-RV
LPS
PS2
O
W
C
HPS
CCR
}
FIELD LOW
VOLTAGE
CONNECTIONS
RD
BK
CH
SA
(IF USED)
NOTE 2
DFT
RVC
RD
BK
BL/PK
BK
Y
T1
L1
T2
L2
R
DF1
DF2
0
0-RV
C-RV
W
LVDR
HVDR
CCR
CNT
0
DFT
R-DFT
R-PS1
Y
Y
C
R
C
C
PS2
RD
RD
BK
BK
SEE NOTE 4
SEE NOTE 5 & 6
BK
BK
RD
SEE NOTE 1
EQUIPMENT GROUND
SEE NOTE 3
ALTERNATE
DOUBLE POLE
CONTACTOR
WH BK
BL/PK
YL/PK
YL/PK
OR
PU
PU
CHS
C
R
S
AUX
MAIN
COMP
H
FC
RD
RD
YL
YL
GR
USE N.E.C. CLASS 2 WIRE
SEE NOTE 4
RD
R-PS1
O-RV
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD
WIRING
HIGH VOLTAGE
LOW VOLTAGE
SEE NOTE 1
SS-iGSZ13 www.goodmanmfg.com 17
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
Warning
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
Page 18
Product SPecificationS Product SPecificationS
USE N. E.C. CLASS 2 W IRE
0140R00289-A
OR
BL
RD
O
BL/PK
C
R
NOTE 1
COLOR CODE
BK --------------- BLACK
BL/PK ---------- BLUE/ PINK STRIPE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
YL/PK------------YELLOW/PINK STRIPE
BL ---------------- BLUE
WIR
ING COD
E
FACTORY WIRING
HIGH VOLTAGE
LOW V OLTAGE
OPTIONAL HIGH VOLTAGE
F
IELD W
I
RING
HIGH VOLTAGE
LVJB
CONTROL BOX
IO
CM
AUX
MAIN
BK
BR
PU
BK
YL/PKYL/PK
LPS
CH
RVC
BK
RD
RD
BK
SEE NOTE 2
WH
W2
COMP
T1
C
T3
T2
FC
T3
C
L1
L3
M
A
I
N
A
U
X
IO
CM
BK
T1
L2
C
T2
OUTDOOR POW ER SUPPLY
SEE RATING PLATE
RD
RD
BK
BK
C
T1
L1
T2
L2
T3
L3
YL
RD
YL
FC
PU
BR
RD
DF1
DF2
HVDR
YL/PK
BL
BK
RD
HPS
BL/PK
BL/PK
Y
NOTES:
1. TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK & INDOOR
THERMOSTAT.
2. CRANKCASE HEATER & CRANKCASE HEATER SWITCH ARE
FACTORY INSTALLED OPTION. CRANKCASE HEATER MAY NOT
HAVE ADDITIONAL GROUND WIRE.
3. USE COPPER CONDUCTOR ONLY.
SEE NOTE 2
EQUIPMENTGROUND
SEE NOTE 3
T1
COMP
T3
T2
YL
BK
DFT
COMPONENT COD
E
C --------------- CONTACTOR
CH ------------- CRANKCASE HEATER
CHS ------------ CRANKCASE HEATER SWITCH
CM ------------ OUTDOOR FAN MOTOR
COMP -------- COMPRESSOR
DC ------------- DEFROST CONTROL
DFT ----------- DEFROST THERMOSTAT
HPS-------------HIGH PRESSURE SWITCH
FC ------------- FAN CAPACITOR
HVDR -------- HIGH VOLTAGE DEFROST RELAY
IO -------------- INTERNAL OVERLOAD
LPS ------------ LOW PRESSURE SWITCH
LVDR --------- LOW VOLTAGE DEFROST RELAY
LVJB ---------- LOW VOLTAGE JUNCTION BOX
RVC ----------- REVERSING VALVE COIL
CONTROLS SHOWN WITH THERMOSTAT
IN 'OFF' POSITION.
CH
INDOOR POWER SUPPLY
LVDR
R
CNT
DFT
C
Y
DC
DFT
DC
O
C
RVC
W2
R
R-DFT
C-RV
LPS
PS2
O
W
C
HPS
CCR
}
FIELD LOW
VOLTAGE
CONNECTIONS
Y
R
DF1
DF2
0
0-RV
C-RV
W
LVDR
HVDR
CCR
CNT
0
DFT
R-DFT
R-PS1
Y
Y
C
R
C
C
PS2
SEE NOTE 5 & 6
R-PS1
RD
BK
BK
RD
RD
YL/PK
BL/PK
YL
OR
BK
WH
RD
RD
CHS
SEE NOTE 2
BK
WiriNg Diagram gSZ130(36-60)5**
18 www.goodmanmfg.com SS-iGSZ13
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
Wiring is subject to change. Always
sources may be present. Failure to do so may cause property damage, personal injury, or death.
Warning
refer to the wiring diagram or the
unit for the most up-to-date wiring.
Page 19

aCCeSSorieS

Model # Description
GSZ13
024
GSZ13
036
GSZ13
048
GSZ13
060
0130R00000S Low-pressure Switch Kit X X X X
ABK-20 Anchor Bracket Kit
X X X X
ASC-01 An-Short Cycle Kit X X X X
AFE18-60A All-fuel Kit X X X X
CSR-U-1 Hard-start Kit X X X X
FSK01A¹ Freeze Protecon Kit X X X X
OT18-60A² Outdoor Thermostat X X X X
OT/EHR18-60 Emergency Heat Relay kit X X X X
TX2N4 ³ TXV Kit
TX2N4A ³ TXV Kit X
TX3N4 ³ TXV Kit X
TX5N4 ³ TXV Kit X X
Contains 20 brackets; four brackets needed to anchor unit to pad
¹ Installed on indoor coil
² Required for heat pump applicaons where ambient temperatures fall below 0°F with 50% or higher relave humidity. ³ Condensing units and heat pumps with reciprocang compressors require the use of start-assist components when used in
conjuncon with an indoor coil using a non-bleed thermal expansion valve refrigerant metering device or liquid line solenoid kit. The TXV should always be sized based on the tonnage of the outdoor unit.
SS-iGSZ13 www.goodmanmfg.com 19
Page 20
Product SPecificationS Product SPecificationS
NoteS
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2014 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
20 www.goodmanmfg.com SS-iGSZ13
Loading...