Goodman GSXC180361BA, GSXC180481BA, GSXC180241BA Installation Manual

CONDENSING UNIT
AIR CONDITIONING INSTALLATION & SERVICE REFERENCE
I
MPORTANT SAFETY INSTRUCTIONS
© 2014, 2016-2018 Goodman Manufacturing Compan y , L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-449F Date: February 2018
S
HIPPING INSPECTION
The following symbols and labels are used throughout this manual to indicate immediat e or potential safety haz ards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Fail­ure to heed safety information increases the risk of personal in­jury, property damage, and/or product damage.
WARNING
HIGH VOLTAGE !
D
ISCONNECT
ULTIPLE POWER SOURCES MAY BE PRESENT
M
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR (HEREINAFTER MANUAL SHOULD SERVICE THE EQUIPMENT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
ALL
POWER BEFORE SERVICING
.
. F
AILURE
.
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS
. THE
MANUFACTURER WILL NOT
. IF
YOU SERVICE THIS UNIT, YOU
. IN
ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE
. I
.
CAUTION
MPROPER
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subsequent in­vestigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
C
ODES
& R
EGULATIONS
This product is designed and manufactured to comply with na­tional codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the in­staller. The manufacturer assumes no responsibility for equip­ment installed in violation of any codes or regulations. Rated performance is achieved after 72 hours of operation. Rated per­formance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specifica­tion sheet for packaged and light commercial models. Specifica­tion sheets can be found at www.goodmanmfg.com f or Goodman brand products or www.amana-hac.com for Amana® brand prod­ucts. Within either website, please select the residential or com­mercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
The United St at es Envir onment al Prot ection Agency (EPA) has is­sued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
Should you have any questions please contact the local office of the EPA.
®
S
CROLL EQUIPPE D UNITS SHOULD NEVER BE USED TO EVACUATE THE AIR CONDITIONING SYSTEM ELECTRICAL ARCING RESU LTIN G IN A DAMAGED OR FAILED COMPRESSOR
.
. V
ACUUMS THIS LOW CAN CAUSE INTERNAL
“IMPORT ANT - This pr oduct has been designe d and manufacture d to meet ENERGY STAR® criteria for energy efficiency when ma tched with appropriate c oil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency . Inst allation of this product should f ollow the manufacturer’ s refrig erant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.
is a registered trademark of Maytag Corporation or its related companies and is used under
license to Goodman Company, L.P., Houston, TX. All rights reserved.
If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning, Heating and Refrig­eration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged.
Minimum Airflow Clearance
Model Type A B C AA
Residential
Light Commercial
10" 10" 18" 20" 12" 12" 18" 24"
Outdoor units are approved for operation above 55°F in cooling mode. Operation below 55°F requires the use of an approved low ambient kit.
Damage to the unit caused by operating the unit in a structure that is not complete (either as part of new construction or renovation) is not covered by the warranty.
F
EA TURES
This air conditioner is a part of the ComfortNet™ family of prod­ucts. It may be installed as part of a “legacy” system using a standard 24 VAC thermostat. However, with the CTK0* ComfortNet thermostat kit, this air conditioner may be installed as part of a digitally communicating system. The ComfortNet system provides enhanced setup features, and enhanced diag­nostics. It also reduces the number of thermostat wires to a maxi­mum of four and a minimum of two.
I
NST ALLATION CLEARANCES
Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/ all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an ob­struction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. Consult all appropri­ate regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. Corner in­stallations are strongly discouraged.
NOT
RECOMMENDED
B B B
AA AAA
C
AA
A
AA
AA
C
AA
CC
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foun­dation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.
R
OOFTOP INSTALLATIONS
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper con­sideration is given to the weather-tight integrity of the roof . Since the unit can vibrate during operation, sound vibration transmis­sion should be considered when installing the unit. Vibration ab­sorbing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration.
S
AFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
TO
AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
HANDLING OF REFRIGERANTS
.
WARNING
R
EFRIGERANTS ARE HEAVIER THAN AIR OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE POSSIBLE DIFFICULTY IN BREATHING OR DEATH
EVER PURGE REFRIGERANT INTO AN ENCLOSED ROOM OR SPACE
• N
LAW, ALL REFRIGERANTS MUST BE RECLAIMED
F AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE AREA
• I
BEFORE BEGINNING WORK
IQUID REFRIGERANT CAN BE VERY COLD
• L
OR BLINDNESS, AVOID CONTACT AND WEAR GLOVES AND GOGGLES
LIQUID REFRIGERANT DOES CONTACT YOUR SKIN OR EYES, SEEK MEDICAL
HELP IMMEDIATELY
LWAYS FOLLOW
• A
OISONOUS GAS WILL BE PRODUCED
P
EP A
.
.
REGULATIONS
. T
HEY CAN “PUSH OUT” THE
. TO
AVOID
:
.
. TO
AVOID POSSIBLE FROSTBITE
. N
EVER BURN REFRIGERANT, AS
.
. BY
. IF
WARNING
TO
AVOID POSSIBLE EXPLOSION, USE ONLY RETU RNABLE (NOT DISPOSABLE) SERVICE CYLINDERS WHEN REMOVING REFRIGERANT FROM A SYSTEM
• E
• E
• E W
.
NSURE THE CYLINDER IS FREE OF DAMAGE WHICH COUL D LEAD TO A
LEAK OR EXPLOSION
NSURE THE HYDROSTATI C TEST DATE DOES NOT EXCEED NSURE THE PRESSURE RATING MEETS OR EXCEEDS
HEN IN DOUBT, DO NOT USE CYLINDER
.
400
.
5
PSIG
YEARS
.
.
2
WARN ING
TO
AVOID POSSIBLE EXPLOSION EVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER
• N
MUST HEAT A CYLINDER FOR FASTER CHARGING, PARTIALLY IMMERSE IT IN WARM WATER
EVER FILL A CYLINDER MORE THAN
• N
EVER ADD ANYTHING OTHER THAN
• N 410A
TO AN
BE LISTED OR CERTIFIED FOR THE TYPE OF REFRIG ERANT USED
TORE CYLINDERS IN A COOL, DRY PLACE
• S
LATFORM OR A ROLLER
P
R
EFRIGERANT LINES
.
R-410A
CYLINDER
.
:
80%
FULL OF LIQUID REFRIG ERANT
R-22 TO AN R-22
. THE
SERVICE EQUIPM EN T USED MUST
. N
EVER USE A CYLINDER AS A
. IF
YOU
CYLINDER OR
.
.
R-
CAUTION
THE
COMPRESSOR SUSCEPTIBLE TO MOISTURE ABSORPTION AND COUL D CAUSE COMPRESSOR FAILURE ANY LONGER THAN NECESSARY FOR INSTALLATION
POE
. DO
OIL FOR
R-410A
UNITS IS EXTREMELY
NOT LEAVE SYSTEM OPEN TO ATMOSPHERE
.
Use only refrigerant grade (dehydrated and sealed) copper tub­ing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. Clean the tubing to prevent contamination.
Do NOT let refrigerant lines come in direct contact with plumb­ing, ductwork, floor joists, wall studs, floors, and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap be­tween foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line.
These sizes are suitable for line lengths of 79 feet or less. If a run of more than 79, refer to TP-107 Long Line Set Application Guide­line or contact your distributor for assistance.
Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8” min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2” insulation may be required. Insulation must be installed in a manner which pro­tects tubing from damage and contamination.
Where possible, drain as much residual compressor oil from ex­isting systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, en­sure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.
RECOMMENDED IN TERCONNE CTING TUBING (Ft )
Cond
Unit
Tons Suct Liq Suct Liq Suct Liq
0-24 25-49 50-79*
Lin e Diameter (In. OD)
1 1/2 5/8 1/4 3/4 3/8 3/4 3/8
2 5/8 1/4 3/4 3/8 3/4 3/8
2 1/2 5/8 1/4 3/4 3/8 7/8 3/8
3 3/4 3/8 7/8 3/8 1 1/8 3/8
3 1/2 7/8 3/8 1 1/8 3/8 1 1/8 3/8
4 7/8 3/8 1 1/8 3/8 1 1/8 3/8 5 7/8 3/8 1 1/8 3/8 1 1/8 3/8
* Lines great er than 79 feet in l engt h refer to TP-107 Long Line Set
Application Gui deline or contact your distributor for assi stance. NOTE: The maximum vertic al difference between the outdoor unit and
indoor unit is 25 feet for two s tage units .
B
URYING REFRIGERANT LINES
If burying refrigerant lines can not be avoided, use the following checklist.
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.
3
R
EFRIGERANT LINE CONNECTIONS
IMPORTANT
To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturer’s instruction when using the heat trap compound. Note: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux.
Torch heat required to braze tubes of various sizes is proportional to the size of the tube. T ube s of smaller size requir e less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. NOTE: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit.
1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak.
2. “Sweep” the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device.
3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve.
4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet when the unit is operating.
NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage.
Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing.
NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit.
L
EAK TESTING
TO
AVOID THE RISK OF FIRE OR EXPLOSION, NEVER USE OXYGEN, HIGH PRESSURE AIR OR FLAMMABLE GASES FOR LEAK TESTING OF A REFRIGERATION SYSTEM
(N
ITROGEN OR NITROGEN-TRACED
WARNING
.
)
WARNING
TO
AVOID POSSIBLE EXPLOSION, THE LINE FROM THE NITROGEN CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE RELIEF VALVE NO MORE THAN
. THE
PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT
150
PSIG
.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the sys­tem to 10 psi using the appropriate refrigerant then use nitro­gen to finish charging the system to working pressure then ap­ply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
S
YSTEM EVACUATION
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the
system is evacuated.
WARNING
REFRIGERANT UNDER PRESSURE!
F
AILURE TO FOLLOW PROPER PROCEDURES MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH
.
NOTE: Scroll compressors should never be used to evacuate or
pump down a heat pump or air conditioning system.
CAUTION
P
ROLONGED OPERATION AT SUCTION PRESSURES LESS THAN FOR MORE THAN SCROLLS AND PERMANENT DAMAGE TO THE SCROLL TIPS, DRIVE BEARINGS AND INTERNAL SEAL
5
SECONDS WILL RESU LT IN OVERHEAT ING OF THE
.
1. Connect the vacuum pump with 250 micron capability to the service valves.
2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period.
If the pressure rises to 1000 microns or less and remains steady the system is considered leak-free; proceed to startup.
If pressure rises above 1000 microns but holds steady below 2000 microns, moisture and/or noncondensibles may be present or the system may have a small leak. Return to step 2: If the same result is encountered check for leaks as previously indicated and repair as necessary then repeat evacuation.
If pressure rises above 2000 microns, a leak is present. Check for leaks as previously indicated and repair as necessary then repeat evacuation.
20
PSIG
4
5000
A
4500 4000 3500
MICRONS
3000
IN
2500
ACUUM
2000
V
1500 1000
500
0 1 2 3 4 5 6 7 8 9
E
LECTRICAL CONNECTIONS
CONDENSIBLES OR SMALL LEAK PRESENT
NO LEAKS NO CONDENSIBLES
MINUTES
WARN ING
HIGH VOLTAGE!
D
ISCONNECT
M
ULTIPLE POWER SOURCES MAY BE PRESENT TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK MUST CONFO RM WITH CODES EQUIPM EN T PERFORMANCE, EQUIPM EN T DAMAGE OR FIRE
.
ALL
POWER BEFORE SERVICING
NEC OR CEC
. U
NDERSIZED WIRES COUL D CAUSE POOR
AND ALL LOCAL
. W
.
. F
IRING
AILURE
LEAK(S) PRESENT
These devices have sufficient time delay to permit the motor­compressor to start and accelerate its load.
H
IGH VOLTAGE CONNECTIONS
Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro­vided inside the control panel cover.
LOW V
OLTAGE CONNECTIONS
Condensing unit control wiring requires a nominal 24 VAC (+/- 6 VAC), 60 Hz, minimum 25 VA service from either the indoor or optional outdoor transformer. Low voltage wiring for the con­densing units depends on the thermostat used. The unit is de-
10
signed to work as part of a fully communicating HVAC system utilizing the ComfortNet™, CTK0* thermostat, ComfortNet compat­ible indoor unit, and up to four wires. The unit also has legacy 24 VAC inputs to support non-communicating systems. Route con­trol wires through the low voltage port and terminate in accor­dance with the wiring diagram provided inside the control panel cover.
HIGH VOLTAGE PORT
WARN ING
TO
AVOID THE RISK OF FIRE OR EQUIPMEN T DAMAGE, USE COPPER
CONDUCTORS
.
NOTICE
U
NITS WITH RECIPROCATING COMPRESSORS AND NON-BLEED
REQUIRE A HARD START KIT
.
The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protec­tion. Wires should be sized to limit voltage drop to 2% (max.) from the main breaker or fuse panel to the condensing unit. Consult the NEC, CEC, and all local codes to determine the cor­rect wire gauge and length.
Local codes often require a disconnect switch located near the unit; do not install the switch on the unit. Refer to the installa­tion instructions supplied with the indoor furnace/air handler for specific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostat for mounting and location information.
O
VERCURRENT PROTECTION
The following overcurrent protection devices are approved for use.
Time delay fuses
HACR type circuit breakers
TXV’S
LOW VOLTAGE PORT
Voltage Ports
NOTE: If the condensing unit is wired in the communicating mode
together with the compatible communicating indoor unit and thermostat, then the communicating thermostat is able to search and identify the condensing unit when power is applied to the system. Refer to the Installation Manual of the communicating thermostat for more information.
Thermostat
Y2
Y2
Y2
OD UNIT
Two-Stage Non-Communicating Thermostat Low Voltage Wire Connection (legacy mode)
Two-Stage Heating
with
Two-Sta g e Co oling
FURNACE OR
IR HANDLER
5
S
YSTEM START UP
C
HARGE VERIFICATION
CAUTION
POSSIBLE REFRIGERANT LEAK!
TO
AVOID A POSSIBLE REFRIG ERANT LEAK, OPEN THE SERVICE VALVES
UNTIL THE TOP OF THE STEM IS
1/8”
FROM THE RETAINER
.
NOTE: Power must be supplied to the 18 SEER outdoor units
containing ECM motors before the power is applied to the in­door unit. Sending a low voltage signal without high voltage power present at the outdoor unit can cause malfunction of the control module on the ECM motor.
Adequate refrigerant charge for the matching HSVTC evapora­tor coil and 15 feet of lineset is supplied with the condensing unit. If using evaporator coils other than HSVTC coil it maybe necessary to add or remove refrigerant to attain proper charge. If line set exceeds 15 feet in length, refrigerant should be added at .6 ounces per foot of liquid line.
NOTE: Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge.
Open the suction service valve first! If the liquid service valve is opened first, oil from the compressor may be drawn into the in­door coil TXV, restricting refrigerant flow and affecting operation of the system.
When opening valves with retainers, open each valve only until the top of the stem is 1/8” from the retainer. To avoid loss of refrigerant, DO NO T apply pre ssure to the r etainer. When opening valves without a retainer remove service valve cap and insert a hex wrench into the valve stem and back out the stem by turning the hex wrench counterclockwise. Open the valve until it contacts the rolled lip of the valve body.
NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip.
WARNING
REFRIGERANT UNDER PRESSURE!
• DO
NOT OVERCHARGE SYSTEM WITH REFRIG ERANT
O NOT OPERATE UNIT IN A VACUUM OR AT NEGATIVE PRESSURE
• D
AILURE TO FOLLOW PROPER PROCEDURES MAY CAUSE PROPERTY
F
DAMAGE, PERSONAL INJURY OR DEATH
.
.
.
CAUTION
USE
REFRIG ERANT CERTIFIED TO MAY CAUSE COMPRESSOR DAMAGE, AND WARRANTY REFRIG ERANT TO MEET
. M
OST PORTABLE MACHINES CANNOT CLEAN USED
AHRI
AHRI
STANDARDS
STANDARDS
. U
SED REFRIG ERANT
IS NOT COVERED UNDER
THE
.
NOTICE
V
IOLATION OF
PENALTIES
DAMAGE TO THE UNIT CAUSED BY OPERATING THE COMPRESSOR WITH THE SUCTION VALVE CLOSED IS NOT COVERED UNDER THE WARRANTY AND MAY CAUSE SERIOUS COMPRESSOR DAMAGE
F
INAL CHARGE ADJUSTMENT
The outdoor temperature must be 60°F or higher. Set the room thermostat to COOL, fan switch to AUTO, and set the tempera­ture control well below room temperature.
After system has stabilized per startup instructions, check sub­cooling and superheat as detailed in the following section.
EPA
REGULATIONS MAY RESU LT IN FINES OR OTHER
.
CAUTION
.
After the refrigerant charge has bled into the system, open the liquid service valve. The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap. Tighten cap finger-tight and then tighten additional 1/6 of a turn (1 wrench flat) to properly sea t the sealing surfaces.
Do not introduce liquid refrigerant from the cylinder into the crankcase of the compre ssor as this may damage the compre ssor .
1. Break vacuum by fully opening liquid and suction base valves.
2. Set thermostat to call for cooling. Check indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 minutes for expansion valves.
CAUTION
TO
PREVENT PERSONAL INJURY, CAREFULLY CONNECT AND DISCONNECT MANIFOLD GAUGE HOSES BURNS
. DO
NOT VENT REFRIG ERANT INTO THE ATMOSPHERE ALL REFRIG ERANT DURING SYSTEM REPAIR AND BEFORE FINAL UNIT DISPOSAL
E
XPANSION VALVE SYSTEM
.
. E
SCAPING LIQUID REFRIGERANT CAN CAUSE
. R
ECOVER
NOTE: Units matched with indoor coils equipped with non-ad­justable TXV should be charged by subcooling only.
Run the remote on low stage cooling for 10 minutes until refriger­ant pressures stabilize. Use the following guidelines and methods to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
6
1. Purge gauge lines. Connect service gauge manifold to base­valve service ports.
2. Temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6" from the compressor on the suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line temperature to determine sub-cooling and vapor temperature to determine superheat.
3. Check subcooling and superheat. Systems with TXV application should have a subcooling of 6°F +/- 1°F and superheat of 8°F +/- 1°F.
a. If subcooling and superheat are low, adjust TXV to
8°F +/- 1°F to 9 ºF superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clock-
wise to increase and counter clockwise to decrease.
b. If subcooling is low and superheat is high, add charge
to raise subcooling to 6°F +/- 1°F then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
to 8°F +/- 1°F superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve to 8°F +/- 1°F superheat and remove charge to lower the subcooling to 6°F +/- 1°F.
NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set, installation is complete.
NOTE: Check the Schrader ports for leaks and tighten valve cores if necessary. Install caps finger-tight.
SUPERHEAT FORMULA =
SUCT. LINE TEMP. - SAT. SUCT. TEMP.
SAT URATED SUCTION PRESSURE
TEMPERATURE CHART
SUCTION
PRESSUR E
PS I G R-22 R-410A
50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21
85 50 24 90 53 26
95 56 29 100 59 31 110 64 36 120 69 41 130 73 45 140 78 49 150 83 53 160 86 56 170 90 60
SATURATED SUCTION
TEMPERATURE ºF
SATURATED LIQUID PRESSURE
TEMPERA TURE CHART
LIQUID PRESSURE
PSIG R-22 R-410A
200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 90 285 127 92 295 130 95 305 133 97 325 137 101 355 144 108 375 148 112 405 155 118 415 157 119 425 n/a 121 435 n/a 123 445 n/a 125 475 n/a 130 500 n/a 134 525 n/a 138 550 n/a 142 575 n/a 145 600 n/a 149 625 n/a 152
SATURATED LIQUID
TEMPERATURE ºF
7
ADDITIONAL NOTES:
1. There are (3) 7-segment LED displays on the PCB. See the Troubleshooting Tables at the end of this manual fo r definitions of the LED status.
2. When system is at Standby mode, press “TEST” push button to turn on both compressor and outdoor fan for five (5) seconds.
3. Press “RECALL” push-button t o retrie ve the six most r ecent faults. The control must be in Standby Mode (no thermostat inputs) to use the feature. Depress the push­button for approximately two seconds and less than five seconds. The (3) 7-segment LED displays will then display the six most recent faults beginning with the most recent fault and decrementing to the least recent fault. The faults may be cleared by depressing the button for greater than five seconds. Consecutively repeated faults are displayed a maximum of three times. Refer to the fault code definitions at the end of this manual for more details.
4. “TERM” dipswitch is used for communications bus configuration. Leave the settings to the factory default position.
5. “LEARN” push button is used to reset the communications
between the equipment. Used only for troubleshooting purposes.
C
OMFORTNET
™ S
YSTEM
OVERVIEW
The ComfortNet system (or CT system) is a system that includes a ComfortNet compatible air handler/furnace/modular blower and air conditioner or heat pump with a CTK0* thermostat. Any other system configurations are considered invalid ComfortNet systems and must be connected as a tradition (or legacy) system. The table below compares the valid CT systems.
two-way digital communications between the thermostat and subsystems (indoor/outdoor unit) and between subsystems is the key to unlocking the benefits and features of the ComfortNet system.
Two-way digital communications is accomplished using only two wires. The thermostat and subsystem controls are powered with 24 VAC Thus, a maximum of 4 wires between the equipment and thermostat is all that is required to operate the system.
AIRFLOW CONSIDERATIONS
Airflow demands are managed differently in a fully communicat­ing system than they are in a legacy wired system. The system operating mode (as determined by the thermostat) determines which unit calculates the system airflow demand. If the indoor unit is responsible for determining the airflow demand, it calcu­lates the demand and sends it to the ECM motor. If the outdoor unit or thermostat is responsible for determining the demand, it calculates the demand and transmits the demand along with a fan request to the indoor unit. The indoor unit then sends the demand to the ECM motor. The following table lists the various ComfortNet™ systems, the operating mode, and airflow demand source.
System
Air Conditione r +
Air Handler
Air Conditione r +
Furnace
System
Operating Mod e
Cooling Air Conditioner
Heating Air Handler
Continuous Fan Thermostat
Cooling Air Conditioner
Heating Furnace
Airflow Dem and
Sou rce
CT com patible
Air Handler/Furnace/Modular
Blower
CT com patible
Air Handler/Furnace/Modular
Blower
CT compatible
Air Conditioner
CT compatible
Heat Pump
Full CT system
benefits & features
Full CT system
benefits & features
A ComfortNet heating/air conditioning system differs from a legacy/traditional system in the manner in which the indoor unit, outdoor unit and thermostat interact with one another. In a tra­ditional system, the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals. It is a one-way communication path in that the indoor and outdoor units typi­cally do not return information to the thermostat.
Continuous Fan Thermostat
For example, assume the system is an air conditioner matched with an air handler. With a call for low stage cooling, the air conditioner will calculate the system’s low stage cooling airflow demand. The air conditioner will then send a fan request along with the low stage cooling airflow demand to the air handler. Once received, the air handler will send the low stage cooling airflow demand to the ECM motor. The ECM motor then delivers the low stage cooling airflow. The table below lists the nominal high and low stage airflow for the ComfortNet heat pumps.
Model
*SXC160241 *SXC160361 *SXC160481 *SXC160601
*SXC180241 *SXC180361 *SXC180481 *SXC180601
High Low
800 600 1200 800 1550 1100 1800 1400
800 600 1250 850 1550 1070 1750 1210
8
Loading...
+ 16 hidden pages