•Refer to Service Manual RS6200009 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians
only. Goodman does not assume any responsibility for property damage or
personal injury due to improper service procedures or services performed by an
unqualified person.
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
GSX130242AA
ELECTRICAL:
PRODUCT
FA MILY:
S: Split System
2: 216-253v
1ph/50Hz
5: 376-440v
3ph/50Hz
SEER:
SEER Rating
MINOR REVISION:
A: Initial Release
BRA ND:
®
G: Goodman
(Standard Feature Set M od el)
Brand
S: Goodman®Deluxe
V: Value
PRODUCT TYPE:
C: Condenser R-22
X: Condenser R-410A
H: He at Pump R- 22
Z: Heat Pump R-410A
MAJOR REVISION:
A: Initial Release
NOMINAL
CAPA CITY
024: 2 Tons
036: 3 Tons
048: 4 Tons
060: 5 Tons
WARNING
WARNING
WARNING
service procedures. If you install or perform service on
this unit, you assume responsibility for any personal
injury or property damage which may result. Many jurisdictions require a license to install or service heating and
air conditioning equipment.
2
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
arising from improper service or
WARNING
HIGH VOLTAGE!
WARNING
WARNING
the requirements of an "entry level technician", as specified by the Air Conditioning, Heating, and Refrigeration
Institute (AHRI). Attempting to install or repair this unit
without such background may result in product damage,
personal injury or death.
Installation and repair of this unit
should be performed
dividuals meeting (at a minimum)
ONLY by in-
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
GSX130242A*
GSX130362A*
GSX130365A*
GSX130485A*
GSX130605A*
* Indicates minor revision & is not used for order entry or inventory management
WARNING
WARNING
WARNING
WARNING
property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the
use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by Goodman for use with this unit. Serious
WARNING
WARNING
als or use gasoline or other flammable liquids or vapors
in the vicinity of this appliance.
To prevent the risk of property
damage, personal injury, or death,
do not store combustible materi-
3
PRODUCT DESIGN
GSX13 use R-410A refrigerant and are available in single and
3-phase models. The single phase models are available in 2
and 3 ton sizes and are designed for 216-253 volt. The 3phase models are available in 3, 4 and 5 ton sizes and are
designed for 376-440 volt applications.
The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then discharged out of the top of the cabinet.
These units are designed for free air discharge, so no additional resistance like duct work shall be attached.
The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type copper. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal installation is factory installed in the condensing unit. GSX units
are charged for the matching evaporator coil and a 15 foot
(4.57m) refrigerant line set.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has adequate capacity to heat or cool the conditioned space.
GSX models use the Copeland Scroll "Ultratech" Series compressors which are specifically designed for R-410A refrigerant. There are a number of design characteristics which are
different from the traditional reciprocating and/or scroll compressors.
"Ultratech" Series scroll compressors will not have a discharge thermostat, some of the early model scroll compressors required discharge thermostats.
Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
"Ultratech" Series scroll compressors use "POE" or
polyolester oil which is NOT compatible with mineral oil based
lubricants like 3GS. "POE" oil must be used if additional oil
is required.
Operating pressures and amp draws may differ from standard reciprocating and/or scroll compressors. This information may be found in the "Cooling Performance Data" section.
IMPORTANT NOTE: Because of the potential damage to
compressors, do not allow suction pressure at service valve
to drop below 20 PSIG when pumping unit system down for
repair. Outdoor section, depending on line set length and
amount of charge in system, may not be able to hold the
entire system charge.
4
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other
units, and any/all other factors that may interfere with air
circulation. Where possible, the top of the unit should be
completely unobstructed; however, if vertical conditions re-
quire placement beneath an obstruction there should be a
minimum of 60 inches (1.52m) between the top of the
unit and the obstruction(s). The specified dimensions meet
requirements for air circulation only. Consult all appropriate
regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for
the unit(s) is the angle to obstructions. Either side adjacent
the valves can be placed toward the structure provided the
side away from the structure maintains minimum service clearance. Corner installations are strongly discouraged.
DO NOT locate the unit:
–Directly under a vent termination for a gas appliance.
–Within 3 feet (91.44cm) of a clothes dryer vent.
–Where the refreezing of defrost water would create a
hazard.
–Where water may rise into the unit.
NOT
RECOMMENDED
BBB
AAAAA
C
AA
A
Model TypeABCAA
Residential
Light
Commercial
AA
Minimum Airflow Clearance
10"
254mm
12"
304.8
254mm
304.8
AA
10"
12"
C
AA
CC
18"
457.2mm
18"
457.2mm
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
20"
508mm
24"
609.6mm
PRODUCT DESIGN
DIMENSIONS
H
D
W
Model
GSX130242A*23" x 23" x 25¾"584.2 x 584.2 x 654.0
GSX130362A*29" x 29" x 28¾"736.6 x 736.6 x 730.2
GSX130365A*29" x 29" x 28¾"736.6 x 736.6 x 730.2
GSX130485A*29" x 29" x 36¼"736.6 x 736.6 x 920.7
GSX130605A*35½" x 35½" x 36¼"901.7 x 901.7 x 920.7
Electrical Conduit Size½" or ¾"½" or ¾"½" or ¾"½" or ¾"½" or ¾"
E q ui p ment Weight (lb s) (kg)
Ship Weight (lbs) (kg)
1
Line sizes denoted for 25' (7.62m) line sets, tested and rated in accordance with AHRI Standard 210/240.
For other line-set lengths or sizes, refer to the Installation & operating instructions and/or the long line-set guidelines.
2
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
3
Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
4
Installer will need to supply 3/4" to 7/8" adapters for suction line connections.
5
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections.
6
Energy Efficienty Ratio @ 80°F (26.6°C) / 67°F (19.4°C) / 118.4°F (48°C)
NOTES:
Always check the S&R plate for electrical data on the unit being installed.
Unit is charged with refrigerant for 15' (4.57m) of 3/8" liquid line. System charge must adjusted per Installation Instructions Final Charge
Procedure.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
6