Goodman GPH1424H41C, GPH1424H41D, GPH1430H41C, GPH1430H41D, GPH1436H41C User Manual

...
Service Instructions
*PH 14 PACKAGE HEAT PUMPS
*PC 14 PACKAGE COOLING
HORIZONTAL MODELS
WITH R-410A
©2008 - 2014 Goodman Manufacturing Company, L.P.
RS6300014
September 2014
1
INDEX
IMPORTANT INFORMATION ......................................................................................................... 4 - 5
PRODUCT IDENTIFICATION - *PC/*PH14**H41** ...................................................................... 6 - 8
ACCESSORIES ................................................................................................................................... 9
PCCP101-103 ROOF CURB ........................................................................................................................................ 10
PCP101-103 DOWNFLOW PLENUM .......................................................................................................................... 10
PCEF101-103 ELBOW AND FLASHING KIT ................................................................................................................11
PCE101-103 ECONOMIZER .......................................................................................................................................... 11
PCMD101-103 DOWNFLOW MANUAL DAMPER ....................................................................................................... 12
GPHMD101-103 HORIZONTAL MOTORIZED DAMPER WITH DUCT FLANGE ........................................................... 12
SQRPC SQUARE TO ROUND CONVERTER ............................................................................................................... 13
SQRPCH SQUARE TO ROUND CONVERTER ............................................................................................................ 13
PCFR101-103 EXTERNAL FILTER KIT ....................................................................................................................... 14
PRODUCT DESIGN .......................................................................................................................... 15
ELECTRICAL WIRING ................................................................................................................................................. 16
LINE VOLTAGE WIRING .............................................................................................................................................. 17
SYSTEM OPERATION ...................................................................................................................... 18
*PC/*PH14**H41**
COOLING .................................................................................................................................................................... 18
COOLING CYCLE ........................................................................................................................................................ 18
HEATING CYCLE ......................................................................................................................................................... 18
DEFROST CYCLE ....................................................................................................................................................... 19
FAN OPERATION ........................................................................................................................................................ 19
SCHEDULED MAINTENANCE......................................................................................................... 22
ONCE A MONTH ......................................................................................................................................................... 22
ONCE A YEAR ............................................................................................................................................................. 22
TEST EQUIPMENT ...................................................................................................................................................... 22
SERVICING ....................................................................................................................................... 23
COOLING/HEAT PUMP- SERVICE ANALYSIS GUIDE ................................................................................................ 23
S-1 CHECKING VOLTAGE ........................................................................................................................................... 24
S-2 CHECKING WIRING .............................................................................................................................................. 24
S-3 CHECKING THERMOSTAT, WIRING, AND ANTICIPATOR .................................................................................... 24
S-3A Thermostat and Wiring ..................................................................................................................................... 24
S-3B Cooling Anticipator ........................................................................................................................................... 25
S-3C Heating Anticipator ........................................................................................................................................... 25
S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT ....................................................................................... 25
S-7 CHECKING CONTACTOR AND/OR RELAYS ........................................................................................................ 25
S-8 CHECKING CONTACTOR CONTACTS .................................................................................................................. 26
S-11 CHECKING LOSS OF CHARGE PROTECTOR ................................................................................................... 27
S-15 CHECKING CAPACITOR ..................................................................................................................................... 27
S-15A RESISTANCE CHECK ....................................................................................................................................... 28
S-15B CAPACITANCE CHECK ..................................................................................................................................... 28
S-16 CHECKING MOTORS .......................................................................................................................................... 29
S-16A CHECKING FAN AND BLOWER MOTOR WINDINGS (PSC MOTORS) ............................................................ 29
S-16D CHECKING EEM MOTORS ............................................................................................................................... 29
S-17 CHECKING COMPRESSOR WINDINGS ............................................................................................................. 30
S-17A RESISTANCE TEST .......................................................................................................................................... 30
S-17B GROUND TEST ................................................................................................................................................. 30
S-17D Operation Test ................................................................................................................................................. 31
2
INDEX
S-18 TESTING CRANKCASE HEATER ........................................................................................................................ 31
S-18A CHECKING CRANKCASE HEATER THERMOSTAT ........................................................................................... 31
S-21 CHECKING REVERSING VALVE AND SOLENOID .............................................................................................. 31
S-24 TESTING DEFROST CONTROL .......................................................................................................................... 32
S-25 TESTING DEFROST THERMOSTAT .................................................................................................................... 32
S-50 CHECKING HEATER LIMIT CONTROL(S) ........................................................................................................... 32
S-52 CHECKING HEATER ELEMENTS ........................................................................................................................ 32
S-100 REFRIGERATION REPAIR PRACTICE ............................................................................................................... 33
S-101 LEAK TESTING ................................................................................................................................................. 33
S-102 EVACUATION ..................................................................................................................................................... 33
S-103 CHARGING ........................................................................................................................................................ 34
S-104 CHECKING COMPRESSOR EFFICIENCY ......................................................................................................... 35
S-108 SUPERHEAT ...................................................................................................................................................... 35
S-109 CHECKING SUBCOOLING ................................................................................................................................36
S-111 FIXED ORIFICE RESTRICTION DEVICES ......................................................................................................... 36
S-112 CHECKING RESTRICTED LIQUID LINE ............................................................................................................ 37
S-113 REFRIGERANT OVERCHARGE ......................................................................................................................... 37
S-114 NON-CONDENSABLES ...................................................................................................................................... 37
S-115 COMPRESSOR BURNOUT ................................................................................................................................40
S-122 REVERSING VALVE REPLACEMENT ................................................................................................................ 40
S-200 CHECKING EXTERNAL STATIC PRESSURE .................................................................................................... 41
S-201 CHECKING TEMPERATURE RISE ..................................................................................................................... 41
WIRING DIAGRAMS .......................................................................................................................... 42
OT18-60A OUTDOOR THERMOSTAT ......................................................................................................................... 42
OT18-60A OUTDOOR THERMOSTAT ......................................................................................................................... 43
SINGLE PHASE HKR/P** HEAT KITS......................................................................................................................... 44
PCE* ECONOMIZER .................................................................................................................................................... 45
SPK* - SINGLE POINT WIRING KIT ......................................................................................................................... 46
3
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
THI S UNIT SHOULD NOT BE CONNECTED TO. OR USED IN CONJUNCTION WITH, ANY DEVICES THAT ARE NOT DESIGN CERTIFI ED FOR USE WITH THIS UNIT OR HAVE NOT BEEN
TESTED AND APPROVED BY
FROM THE USE OF DEVICES THAT HAVE NOT BEEN APPROVED OR CERTIF ED BY
OODMAN. SERIOUS PROPERTY DAMAGE OR PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT
G
OODMAN.
G
WARNING
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
T
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
OODMA N WILL NO T BE R ESPONSIBLE FOR AN Y INJURY O R PROPERTY DAM AGE ARI SING FROM IMPROPER SERVICE OR SERVIC E PROCED URES.
G IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RE SPONSIBILITY FOR A NY PERSONA L INJURY OR P ROPERTY DAM AGE WHICH
MAY RESULT.
ANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQUIPMENT.
M
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE 1-877-254-4729 (U.S. only)
email us at: customerservice@goodmanmfg.com
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500
(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
4
IMPORTANT INFORMATION
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
EFRIGERANTS ARE HEAVIER THAN AIR. THEY CAN "PUSH OUT" THE
R
OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE.
POSSIBL E DIFF ICULTY IN BREAT HING O R DEATH:
EVER PURGE REFR IGERANT INTO AN ENCLOSED ROO M OR SPACE . BY
N
LAW, ALL REF RIGERANTS MUST BE RECLAIMED.
F AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE AREA
I
BEFORE BEGINNING WORK.
IQUID REFRIGERANT CAN BE VE RY COLD. TO AVOID POSSIBLE FROST-
L
BITE OR BLINDNESS, AVOID CONTACT WITH REFRIGERANT AND WEAR
GLOVES AND GOGGLES.
SKIN OR E YES, SEEK M EDICAL HELP IMMEDI ATELY.
ALWAYS FOLLOW EPA REG ULATIO NS. NEVER BURN REFRIGE RANT,
AS POISON OUS GAS WI LL BE PRODUC ED.
F LIQUID REFRIGERANT DOES CONTACT YOUR
I
O AVO ID
T
WARNING
TO AVOID POSSIBLE EXPLOSION:
• NEVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER. IF YOU
MUST HEAT A CYLINDE R FOR FASTER CHARGING, PARTI ALLY IMMERSE
IT IN WARM WATER.
NEVER FILL A CYLINDER MORE THAN 80% FULL OF LIQUID REFRIGERANT.
NEVER ADD ANYTHING OTHER T HAN R-22 TO AN R-22 CYLINDER OR R-410A TO AN R-410A CYLINDER. THE SERVICE EQUIPMENT USED MUST
BE LISTED OR CERTIF IED FOR THE TYPE OF REFRIGERANT US ED.
• STORE CYLINDERS IN A CO OL, DRY PLACE. NEVER USE A CYLIND ER
AS A PLATFORM OR A ROLLER.
WARNING
O AVOI D POSSI BLE EX PLOSION, USE ONLY RETURNABLE (NOT DISPOSABL E)
T
SERVICE CYLINDERS WHEN REMOVING REFRIGERANT FROM A SYSTEM.
NSURE THE CYLIND ER IS FREE O F DAMAGE WHICH COULD LEAD TO A
E
LEAK OR EXPLOSION.
NSURE THE HYDROSTA TIC TEST DATE DOES NOT EXCEE D 5 YEARS .
E
NSURE THE PRESSURE RATING MEETS OR EXCEEDS 400 LBS.
E
HEN IN DOUBT, DO NOT USE CYLIND ER.
W
WARNING
WARNING
YSTEM CONTAMINANTS, IMPROPER SERVICE PROCEDURE AND/OR PHYSICAL
S
ABUSE AFFECTING HE RMETIC COMPRESSOR ELECTRICAL TERMI NALS MAY
CAUSE DANGEROUS SYSTEM VENTING.
The successful development of hermetically sealed refrig­eration compressors has completely sealed the compressor's moving parts and electric motor inside a common housing, minimizing refrigerant leaks and the hazards sometimes as­sociated with moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is a method whereby electrical current is transmitted to the com­pressor motor through terminal conductors which pass through the compressor housing wall. These terminals are sealed in a dielectric material which insulates them from the housing and maintains the pressure tight integrity of the her­metic compressor. The terminals and their dielectric em­bedment are strongly constructed, but are vulnerable to care­less compressor installation or maintenance procedures and equally vulnerable to internal electrical short circuits caused by excessive system contaminants.
T
O AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
HANDLING OF REFRIGERANTS.
In either of these instances, an electrical short between the terminal and the compressor housing may result in the loss of integrity between the terminal and its dielectric embed­ment. This loss may cause the terminals to be expelled, thereby venting the vaporous and liquid contents of the com­pressor housing and system.
A venting compressor terminal normally presents no danger to anyone, providing the terminal protective cover is properly in place.
If, however, the terminal protective cover is not properly in place, a venting terminal may discharge a combination of
(a) hot lubricating oil and refrigerant
(b) flammable mixture (if system is contaminated
with air)
in a stream of spray which may be dangerous to anyone in the vicinity. Death or serious bodily injury could occur.
Under no circumstances is a hermetic compressor to be elec­trically energized and/or operated without having the terminal protective cover properly in place.
See Service Section S-17 for proper servicing.
5
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
PC1424 H 4 1 * *G / A
BRAND:
G: Goodman
Brand or Distinctions
A: Amana
®
Brand
®
PRODUCT
TYPE:
Package
Cooling/Heating
PRODUCT
14: 14 SEER
PRODUCT
FAMILY:
C: Cooling H: Heat Pump
SERIES:
Rating
CONFIGURATION:
H: Horizontal
NOMINAL
CAPACITY:
24: 24,000 BTUH 30: 30,000 BTUH 36: 36,000 BTUH 42: 42,000 BTUH 48: 48,000 BTUH 49: 48,000 BTUH 60: 60,000 BTUH
MINOR
REVISION:
MAJOR
REVIS ION:
REFRIGERANT:
4: R-410A
VOLTAGE:
1: 208-230V/1ph/60Hz 3: 208-230v/3ph/ 60Hz 4: 460v/3ph/60Hz
Chassis Model A B
*PC1424 22 30
Small
Medium
Dimensions in inches
*PC1430 22 30
*PC1436 22 30
*PC1442 22 30
*PC1448 24 35
*PC1460 24 35
is a registered trademark of Maytag Corporation or its related entities and is used under license. All rights reserved.
6
Chassis Model A B
Small
Medium
Large
Dimensions in inches
*PH142441** 22.000 29.932
*PH143041** 22.000 29.932
*PH143641** 24.000 34.932
*PH144241** 24.000 34.932
*PH144841B* 24.000 34.932
*PH144841A* 24.000 38.682
*PH146041** 24.000 38.682
PRODUCT IDENTIFICATION
®
MODEL # PACKAGE COOLING DESCRIPTION
oodman® Brand or Distinctions Package Cooling -
GPC1424-48H41AA
GPC1424-48H41AB
GPC1424-48H41BA
GPC1460H41BA
GPC1424-48H41AC
GPC1460H41AB
GPC1424H41CA
GPC1430-60H41CA
A/GPC1424-60H41DA
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A.
oodman® Brand or Distinctions Package Cooling -
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Models with 5 mm condenser coils.
oodman® Brand or Distinctions Package Cooling -
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Models with aluminum evaporator coils.
oodman® Brand or Distinctions Package Cooling -
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Models with 5 mm condenser coils and aluminum evaporator coils.
oodman
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Adds "T" to liquid line and re-locates the pressure switch on "H" series cooling models.
oodman
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Two ton models with a Rechi compressor.
oodman
G
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Models with Broad Ocean Digi motor.
mana® Brand/Goodman
A
14 Seer 208-230/1/60 Single-Phase Electric Cooling Unit with R-410A. Models that change static ratings to be max 0.88 on all E-Heat kits besides 20 kW.
Brand or Distinctions
®
Brand or Distinctions
®
Brand or Distinctions
ackage Cooling -
P
ackage Cooling -
P
ackage Cooling -
P
®
Brand or Distinctions
ackage Cooling -
P
7
PRODUCT IDENTIFICATION
-
MODEL # PACKAGE HEAT PUMP DESCRIPTION
®
Brand or Distinctions
GPH1424-60H41AB
GPH1424-60H41AA
GPH1424-60H41AC
GPH1424-60H41BA
GPH1424-60H41CA
oodman
G
14 Seer 208-230/1/60 Single-Phase Heat Pump with R-410A. Models are changing to the PCBDM133 defrost control and with the addition of the crankcase heaters where necessary.
oodman® Brand or Distinctions Package Heat Pum p -
G
14 Seer 208-230/1/60 Single-Phase Heat Pump with R-410A.
oodman® Brand or Distinctions Package Heat Pum p - 14 Seer 208-
G
230/1/60 Single-Phase Heat Pump with R-410A. Adds "T" to liquid line and re locates the pressure switch on "H" series heat pumps.
oodman® Brand or Distinctions Package Heat Pum p - 14 Seer 208-
G
230/1/60 Single-Phase Heat Pump with R-410A. Models with Aluminum Evaporator Coils.
oodman® Brand or Distinctions Package Heat Pum p - 14 Seer 208-
G
230/1/60 Single-Phase Heat Pump with R-410A. Models with Broad Ocean Digi m otor.
ackage Heat Pum p -
P
A/GPH1424-42H41DA
A/GPH1448H41DA
GPH1460H41DA
mana® Brand/Goodman
A
14 Seer 208-230/1/60 Single-Phase Heat Pump with R-410A. Models that change static ratings to be max 0.88 on all E-Heat kits besides 20 kW.
®
Brand or Distinctions
ackage Heat Pum p -
P
8
ACCESSORIES
Part Number Description
OT18-60A
OT/HER-60A Outdoor Thermostat with Emergency Heat Relay
HKR05A, 08, 10, CA Heater Kit for all *PC/*PH (H) Series
HKP05C, 10C Heater Kit for all *PC/*PH (H) Series
HKP15* Heater kit for *PC/*PH13/14 (30-60) (H) Series
HKP20* Heater Kit for *PC/*PH13/14 (42-60) (H) Series
PCCP101-103 Roof Curb
PCP101-103 Downflow Plenum Kit
PCP101-103R8 Downflow Plenum Kit w/ R-8 Insulation
GPCED101-103 Downflow Economizer for H Series Package Units (A/C) - To Be Used With PCP101-103
GPHED101-103 Downflow Economizer for H Series Package Units (Heat Pump) - To Be Used With PCP101-103
GPCEH101-103 Horizontal Economizer for H Series Package Units (A/C)
GPHEH101-103 Horizontal Economizer for H Series Package Units (Heat Pump)
PCMD101-103 Manual Damper - To Be Used With PCP101-103
PCMDM101-103 Motorized Damper - To Be Used With PCP101-103
GPHMD101-103 Manual Damper for Horizontal Applications
SPK* Single Point Wiring Kit
SQRPCH101 Square to Round Adapters 16"&14"
SQRPCH102-103 Square to Round Adapters 18"&14"
SQRPC101 Square to Round Adapter - For Use With PCCP101-103 Curb 16" Rounds
SQRPC102-103 Square to Round Adapter For Use With PCCP101-103 Curb 18" Rounds
PCFR101-103 External Horizontal Filter Rack
PCEF101-103 Elbow & Flashing w/ R-8 Liner
CDK36 Flush Mount Concentric Duct Kit
CDK36515 Flush Mount Concentric Duct Kit w/ Filter
CDK36530 Step Down Concentric Duct Kit
CDK36535 Step Down Concentric Duct Kit w/ Filter
CDK4872 Flush Mount Concentric Duct Kit
CDK4872515 Flush Mount Concentric Duct Kit w/ Filter
CDK4872530 Step Down Concentric Duct Kit
CDK4872535 Step Down Concentric Duct Kit w/ Filter
*PC/*PH14**H41*
ACCESSORIES *PC/*PH H SERIES
Outdoor Thermostat (Required for heat pumps with 0° outdoor ambient and 50% or higher relative humidity.
GOODMAN® BRAND THERMOSTATS
CH70TG Manual Changeover
CHSATG Manual Changeover
CHT18-60 Manual Changeover
CHT90-120 Manual Changeover Mechanical, Nonprogrammable 2 Heat - 2 Cool
CHTP18-60HD Manual Changeover Digital, Nonprogrammable 2 Heat - 1 Cool
CT18-60 Manual Changeover
Digital, Nonprogrammable 1 Heat - 1 Cool Mechanical, Nonprogrammable 1 Heat - 1 Cool Mechanical, Nonprogrammable 1 Heat - 1 Cool
Mechanical, Nonprogrammable Cool Only
AMANA® BRAND THERMOSTATS
1213401 White Manual Changeover 1213402 White Manual Changeover 1213403 White Manual Changeover 7 Day Programming Digital 2 Heat - 1 Cool 1213404 White Manual Changeover 1213406 1213407 1213408 1213410 1213411 1213412 1213431
Beige White
White White White White
White
Manual/Auto Ch angeover 5 + 2 Programming Digital 3 Heat - 2 Cool
Manual Changeover
Manual/Auto Changeover
Manual Changeover 5 + 2 Programming Digital 2 Heat - 1 Cool
Manual Changeover Manual/Auto Changeover 7 Day Programming Digital 3 Heat - 2 Cool Manual/Auto Changeover
5 + 2 Programming Digital 1 Heat - 1 Cool
Nonprogrammable Digital 1 Heat - 1 Cool
Nonprogrammable Digital 2 Heat - 1 Cool
5 + 2 Programming Digital 2 Heat - 2 Cool
7 Day Programming Digital 1 Heat - 1 Cool
Nonprogrammable Digital 2 Heat - 2 Cool
7 Day Programming Digital 3 Heat - 2 Cool
9
ACCESSORIES
33"
*PC/*PH14H41*
PCCP101-103 ROOF CURB
64"
59"
29 3/8"
29 3/4"
33"
26"
28 3/4"
31"
PCP101-103 DOWNFLOW PLENUM
(Use with PCCP Roof Curb)
14"
1" Flange
Roof Curb
10
37"
13"
25 1/2"
33"
13"
ACCESSORIES
*PC/*PH14H41*
PCEF101-103 ELBOW AND FLASHING KIT
28"
35"
25"
33"
3"
4"
20 3/8"
17 3/4"
4"
25"
8"
PCE*101-103 ECONOMIZER*
(DOWNFLOW APPLICATIONS)
5"
27 3/4"
16 1/2"
17 3/4"
20" x 17 1/2"
Filter
3"
31 1/4"
Model Used With
PCEC101-103* *PC HORIZONTAL A/C
PCEH101-103* *PH HORIZONTAL HP
*Must be used with PCP101-103
11
ACCESSORIES
PCMDM101-103 DOWNFLOW MOTORIZED DAMPER*
2
1
PCMD101-103 DOWNFLOW MANUAL DAMPER*
*USED WITH PCP101-103 DOWNFLOW PLENUM
"
8
/
1
*PC/*PH14H41*
6"
10"
29 3/4"
MODEL DESCRIPTION
PCMDH101-103 Manual Damper
PCMDM101-103 Motorzied Damper
GPHMD101-103 HORIZONTAL MANUAL DAMPER WITH DUCT FLANGE
18"
8
1
/
4
"
18"
12
12"
6"
2"
17"
25 1/4"
17 1/4"
ACCESSORIES
"
A
*PC/*PH14H41*
SQRPC SQUARE TO ROUND CONVERTER
(DOWNFLOW APPLICATIONS)
1" FLANGES
1 1/2
SA
RA
OUTER FLANGE
29 1/2"
29 1/4"
SA 16" 18" RA 16" 18"
SQRPCH SQUARE TO ROUND CONVERTER
(HORIZONTAL APPLICATIONS)
SQUARE TO ROUND DUCT CONVERTER PANEL
BEAD
A
SQRPC101 SQRP102-103
C
2"
RETURN
2"
SUPPLY
B
STARTER FLANGE
SQRPCH-101 SQRPCH-102 SQRPCH-103 SQRPCH102-14 SQRPCH103-14
15" 17" 17" 15" 15"
B C 17" 17" 19" 15" 15" D
SUPPLY 14" 16" 16" 14" 14"
RETURN
15" 17" 17" 15" 15"
22 1/2" 24 1/2" 24 1/2" 24 1/2" 24 1/2"
16" 16" 18" 14" 14"
D
13
ACCESSORIES
*PC/*PH14H41*
PCFR101-103 EXTERNAL FILTER KIT
(HORIZONTAL APPLICATIONS)
14" x 25" x 2" FILTER
14