Goodman DTC036 Installation Manual

Page 1
DTC/DTH SERIES
LIGHT COMMERCIAL PACKAGED HEATING AND COOLING UNIT
3 TO 6 TON
ATTENTION INSTALLING PERSONNEL:
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. Dur­ing installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
Index
Replacement Parts................................................................ 2
Safety Instructions................................................................ 2
General Information ............................................................. 2
Unit Location ........................................................................ 3
Clearances ............................................................................ 4
Roof Curb Post-Installation Checks ....................................... 5
Roof Top Duct Connections ................................................... 5
Rigging Details ...................................................................... 5
Electrical Wiring.................................................................... 6
Circulating Air and Filters...................................................... 8
Condensate Drain Connection ..............................................8
Startup, Adjustments, and Checks ........................................ 9
Air Flow Adjustments .........................................................10
Heat Pump Operation......................................................... 11
Maintenance ......................................................................12
Troubleshooting.................................................................. 12
Appendix A Blower Performance Tables ............................. 14
Direct Drive ....................................................................1 4
Standard Down Shot and Horizontal .......................... 14
Standard DTC/DTH060 Down Shot ............................. 16
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of single package heating and cooling units. See the Specification Sheet applicable to your model for information regarding accessories.
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
IOD-1016 3/2015
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2015
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
Appendix B Electrical Data.................................................. 18
Appendix C Unit Dimensions............................................... 19
WIRING DIAGRAMS ............................................................ 20
DTC0[36-60]XXX1DXXX...............................................20
DTH0[36-60]XXX1DXXX .............................................. 21
START-UP CHECKLIST........................................................... 22
Page 2
REPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
DAIKIN NORTH AMERICA LLC
7401 SECURITY WAY
HOUSTON, TEXAS 77040
855-770-5678
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
Keep this literature in a safe place for future reference.
CAUTION
WA RNING
T
HIS UNIT MUST NOT BE USED AS A “CONSTRUCTION HEATER DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERE S
. T
HIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE
.
WARNING
HIGH VOL TAGE! D
ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARNING
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARN ING
HIGH VOLTAGE!
INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE PERFORMED MINIMUM) THE REQUIREMENTS OF AN
T
ECHNICIAN” AS SPECIFIED BY THE AIR CONDITIONING
HEATING AND REFRIGERATION INSTITUTE
TTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT
A
SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH
ONLY BY
INDIVIDUALS MEETING(AT A
“E
NTRY LEVEL
(AHRI).
.
,
,
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION
.
W ARNING
T
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM
.
WARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO
NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER
I
MMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER
.
.
GENERAL INFORMA TION
W ARNING
TO
PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH, DUE TO FIRE, EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED, AND MAINTAINED
.
This unit is approved for outdoor installation ONLY . Rated perf or ­mance is achieved after 72 hour s of operation. Rated performance is delivered at the specified airflow. See product specification sheet for light commercial models. Specification sheets can be found at www.daikincomfort.com for Daikin brand products. Within the website, please select the commercial products menu and then select the submenu for the type of product to be in­stalled, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specifica­tion sheet.
To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these in­stallation and operating instructions, all local building codes and ordinances.
2
Page 3
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA)
HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND DISPOSAL OF
REFRIGERANTS IN THIS UNIT. F AILURE TO FOLLOW THESE REGULATIONS MAY HARM
THE ENVIRONMENT AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL FINES.
ECAUSE REGULATIONS MAY VARY DUE TO PASSAGE OF NEW LAWS, WE SUGGEST A
B
CERTIFIED
TECHNICIAN PERFORM ANY WORK DONE ON THIS UNIT. SHOULD YOU
HAVE ANY QUESTIONS PLEASE CONTACT THE LOCAL OFFICE OF THE EPA.
NATIONAL CODES
This product is designed and manufactur ed to permit installation in accordance with National Codes. It is the inst aller’ s r e sponsibil­ity to install the product in accordance with National Codes and/ or prevailing local codes and regulations.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calcula te d b y an appr ov e d method or in accordance with ASHRAE Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. R ecycle or dispose of the packaging material according to local codes.
PRE-INSTALLATION CHECKS
Carefully rea d all instructions f or the installation prior t o inst alling unit. Ensure each step or proce dur e is under stood and an y special considerations are taken into account before starting installation. Assemble all tools, hardware and supplie s needed to complet e the installation. Some items may need to be purchased locally.
UNIT LOCATION
WARN ING
American National Standards Institute
1430 Broadway
New York, NY 10018
System design and installation should also, where applicable, fol­low information pre sented in accept ed industry guides such as the ASHRAE Handbooks. The manufacturer assumes no r esponsibility for equipment installed in viola tion of an y c ode or r egula tion. The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services; supply and return duct connections; and drain connections (if re­quired). The internal systems of the unit are completely factory­installed and tested prior to shipment.
Units are g ener ally ins t alled on a steel roof mounting curb assem­bly which has been shipped to the job site for installation on the roof structure prior to the arrival of the unit. The model number shown on the unit’s identification plate iden tifies the various com­ponents of the unit such as refrigeration tonnage, heating input and voltage.
Carefully inspect the unit for damage including damage to the cabinetry . Any bolt s or screws which ma y have loosened in tr ansit must be re-tightened. In the even t of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, c arrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy , or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
TO
PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
IMPORTANT NOTE: Remove wood shipping rails prior to installa­tion of the unit.
ALL INSTALLATIONS: I
MPORTANT NOTE: Unit should be energized 24 hours prior to
compressor start up to ensure crankcase heater has suffi­ciently warmed the compressors. Compressor damage may occur is this step is not followed.
NOTE: Appliance is shipped from factory for vertical duct application.
Proper installation of the unit ensur es tr ouble-free operation. Im­proper installation can result in problems ranging from noisy operation to property or equipment damages, dangerous condi­tions that could result in injury or personal property damag e. Give this booklet to the user and explain it’s provisions. The user should retain these instructions for future reference.
For proper operation and condensate drainage, the unit
must be mounted level.
Do not locate the unit in an area where the outdoor air
will be frequently contaminate d by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishe s, sealers, w ax es (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/ fluorine compounds.
T o avoid possible illness or death of the building occupants,
3
Page 4
do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper opera tion, and service access (see Unit Clearances). These clearances must be permanently maintained.
When the unit is heating, the temperature of the return
air entering the unit must be a minimum of 55°F.
GROUND LEVEL INSTALLATIONS ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended . Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runoff of w at er
from higher ground can collect in the unit.
ROOF TOP INSTALLATIONS ONLY:
T o a v oid possible property damage or per sonal injury, the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structur al engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
Adequate clearances fr om the unit to any adjacent public
walkways, adjacent buildings, building openings or openable windows must be maintaine d in accordance with National Codes.
UNIT PRECAUTIONS
Do not stand or walk on the unit.
Do not drill holes anywhere in panels or in the base frame of the unit (except where indicated). Unit access panels provide structural support.
Do not remove any access panels until unit has been installed on roof curb or field supplied structure.
Do not roll unit across finished roof without prior approval of owner or architect.
Do not skid or slide on any surface as this may damage unit base. The unit must be store d on a flat, level surf ace. Protect the condenser coil because it is easily damaged.
ROOF CURB INSTALLATIONS ONLY:
Curb installations must c omply with local codes and should be done in accordance with the est ablished guidelines of the National R oof­ing Contractors Association.
shipped unassembled. Field assembly, squaring, leveling and mounting on the roof structure are the responsibility of the in­stalling contractor. All required hardware necessary for the as­sembly of the sheet metal curb is included in the curb accessory.
WARN ING
TO
PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
Sufficient structural support must be det ermined prior to
locating and mounting the curb and package unit.
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be a ssembled with the curb. Cantilevered type curbs are not available from the factory.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor. The curbs must be supported on parallel sides by roof members. The roof members must not penetrate supply and return duct opening areas as damage to the unit might occur.
NOTE: The unit and curb accessories are de signed to allow v ertical duct installation before unit placement. Duct inst allation after unit placement is not recommended.
CAUTION
ALL
CURBS LOOK SIMILAR
POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY SUPERSEDES INFORMATION SHOWN
See the manual shipped with the roof curb for assembly and in­stallation instructions.
24”* Min.
. TO
AVOID INCORRECT CURB
. I
NSTRUCTIONS MAY VARY IN CURB STYLES AND
.
CLEARANCES
24”* Min.
36”
Min.
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are
UNIT CLEARANCES
*In situations that have multiple units, a 48” minimum clearance is required between the condenser coils.
Adequate clearance around the unit should be k ept f or safety, ser-
4
Page 5
vice, maintenance, and proper unit operation. A total clearance of 75” on the main control panel side of the unit is r ecommende d to facilitate possible f an shaft, coil, and electric heat. A clearance of 48” is recommended on all other sides of the unit to facilitate possible compressor removal, to allow service access and to in­sure proper ventilation and condenser airflow. The unit must not be installed beneath an y obs truction. The unit should be installe d remote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.
Refer t o IOD-7006 included in the litera ture pack for inst alling hori­zontal duct covers.
Flexible duct connectors between the unit and ducts are recom­mended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes.
11 ” 4 7/8””
REMOVE
COVERS
17” 7 3/8”
INSULATED PANELS
ROOF CURB INSTALLATION
ROOF CURB POST -INSTALLA TION CHECKS
After installation, check the top of the curb, duct connection fr ame and duct flanges to make sure gasket has been applied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct connection frame. If gasket is loose, re-apply using strong weather resistant adhesive.
PROTRUSION
Inspect curb to ensure that none of the utility services (electric) routed through the curb protrude above the curb.
CAUTION
IF
PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB
.
ROOF TOP DUCT CONNECTIONS
RETURN
12”
SUPPLY
6 3/16”
HORIZONTAL DISCHARGE DUCT CONNECTIONS
25”
RIGGING DET AILS
WARNING
O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
T
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.
T
O FACILITATE
CAUTION
IF
UNITS ARE LIFTED TWO AT A TIME, THE FORK HOLES ON THE CONDENSER END OF THE UNIT MUST NOT BE USED LENGTH IS IS RECOMMENDED
42” TO
PREVENT DAMAGE TO THE UNIT; HOWEVER
.
. M
INIMUM FORK
, 48”
Provisions for fork s have been include d in the unit base frame. No other fork locations are approved.
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEAT H, THE FOL LOWING BU LLET POINTS MUST BE OB SERVED WHEN INSTALLING THE UNIT.
• Unit must be lifted by the four lifting holes located at the base frame corners.
• Lifting cables should be att ached to the unit with shackles.
• The distance between the crane hook and the top of the unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent
Install all duct connections on the unit before placing the unit on rooftop.
HORIZONTAL DISCHARGE
5
Page 6
damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. Removal is accomplished by extracting the sheet met al r etainer s and pulling the struts through the base of the unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior t o installing the unit. Ductwork dimensions are shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the Na­tional Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end t o be lower than supply air end.
A*
Model
DTC 036* 35 27 571 546 122 165 111 146
D T C 04 8 * 3 5 2 7 5 9 0 5 6 4 13 1 16 7 118 14 8
DT C060* 35 2 7 635 610 14 3 178 126 163
DTH 036* 34 28 581 556 130 175 105 146
D T H 04 8 * 3 4 2 8 6 0 0 5 7 4 13 1 18 1 111 15 1
DTH 060* 34 28 645 620 141 193 121 165
X (in) Y (in)
Shipping
Weight
(lbs)
Operating
Weight
(lbs)
Co rner Weights ( lbs )
ABCD
CAUTION
TO
PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper align­ment and orientation of supply and return openings with duct.
To assist in determining rigging requirements, unit weights are
shown as follows:
A
Y
B
CONDENSER
COIL
COMPRESSOR
CG
X
RETURN
EVAPO RATOR COIL
CORNER & CENTER OF GRAVITY LOCATIONS
SUPPLY
C
D
RIGGING REMOVAL
CAUTION
TO
PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT
.
Remove sprea der bars, lifting cable s and other rigging equipment.
ELECTRICAL WIRING
WARN ING
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARNING
HIGH VOLTAGE! T
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY WIRING
. THE
OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT
C
ONTACT YOUR LOCAL REPRESENTATIVE IF
ASSISTANCE IS REQUIRED
INTERNAL POWER AND CONTROL WIRING
.
.
CAUTION
TO
PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES LOCAL CODES AND ORDINANCES REMOVABLE ACCESS PANELS
6
. F
OLLOW NATIONAL ELECTRICAL CODE AND ALL
. DO
NOT ROUTE WIRES THROUGH
.
Page 7
CAUTION
C
ONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT
WATER ENTRY INTO THE BUILDING
.
For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maxi­mum overcurrent protection device. DO NOT EXCEED THE MAXI­MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these in­structions, the latest edition of the Na tional Electrical Code (ANSI/ NFP A 7 0), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/ 35°C rise).
The unit is factory wired for the voltage shown on the unit’s data plate. Refer to model nomenclature in Appendix B for voltage re­quirement for your unit.
NOTE: If supply voltage is 208V, lead on primary of transformer must be moved from the 230V to the 208V tap. Refer to wiring diagram on unit for details.
conductor in accordance with T able 250-95 of the National Electrical Code. Do not use the ground lug for connecting a neutral conductor.
• Remove plug in panel located at the condenser end of unit and route conduit to control box. Remove plug in control box and connect power wiring to the contactor closest to the entrance. If Single Point kit is used, refer to Installation Instructions supplied with kit.
MAIN POWER
LOW VOLTAGE BLOCK
LOW VOLTAGE ENTRANCE
POWER THRU THE CURB
CONTROL BOX
Main power wiring should be sized f or the minimum wire ampacity shown on the unit’s data plate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase the wire size to prevent e xce ssive volt age drop. Wires should be sized f or a maximum of 3% voltage drop.
CAUTION
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
T
ONLY COPPER CONDUCTORS.
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS DANGEROUS OPERATION SERVICING
. W
IRING ERRORS CAN CAUSE IMPROPER AND
.
. V
ERIFY PROPER OPERATION AFTER
NOTE: A weather-tight disconnect switch, properly sized for the unit total load, must be field or f actory inst alled. An e xternal field supplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied disconnect switch.
• Some disconnect switches are not fused. Protect the power leads at the point of dis tribution in accordance with the unit’s data plate.
• The unit must be electrically grounded in accordance with local codes or , in the ab sence of local codes, with the lat est edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding
LOW VOLTAGE/THERMOSTAT CONNECTIONS
NOTE:
Some models may vary from illustration. Models with electric heat are equipped with a power block for field connections.
CONTROL BOX CONNECTIONS
GROUND
LUG
WARN ING
F
AILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS
.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable lights and tools used by the service mechanic.
NOTE: Refer to local codes for requirements. These outlets can also be factory installed.
UNITS INSTALLED ON ROOF TOPS
Main power and low voltage wiring may enter the unit through the condenser end or through the roof curb. Install conduit con­nectors at the desired en trance locations. External connector s must be weatherproof. All holes in the unit base must be sealed (in­cluding those around conduit nuts) to prevent water leakage into building. All required conduit and fittings ar e t o be field supplie d.
7
Page 8
Supply voltage to roof top unit mus t not vary by more than 10% of the value indicated on the unit’s data plate. Pha se voltage unbal­ance must not exceed 2%. Contact your local power company for correction of improper voltage or phase unbalance.
HIGH VOLTAGE ENTRANCE
(REMOVE PLUG)
NOTE: Field-supplied conduit may nee d t o be ins t alled depending on unit/curb configuration. Use #18 AWG solid conductor wire whenever connecting thermostat wire s to terminals on sub-ba se. DO NOT use larger than #18 AWG wire. A transition to #18 AWG wire may be required before entering thermostat sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
* (6 Ton - 34 1/4”)
RETURN
SUPPLY
1:4
POWER THRU THE CURB
12 3/8”
30 1/4”*
LOW VOLTAGE ENTRANCE
3.5 DIA.
4 1/2”
CIRCULATING AIR AND FILTERS
DUCTWORK
The supply duct from the unit through a wall may be inst alled with­out clearance. However, minimum unit clearances must be main­tained (see “Clearance s” section). The supply duct should be pro­vided with an access panel large enough to inspect the air cham­ber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
CONDENSA TE DRAIN CONNE CTION
CONDENSATE DRAIN CONNECTION
A 3/4” female NPT drain connection is supplied on the end of the unit and bottom of the drain pan f or condensat e piping. An ext er­nal trap must be installed for proper condensate drainage.
DRAIN CONNECTION
47 1/2”
ELECTRICAL ENTRANCE AND THRU CURB
7 1/2”
LOW VOLTAGE CONTROL WIRING
1. A 24V thermostat must be installed for unit operation. It may be purchased with the unit or field -supplied. Thermostats may be progr ammable or electromechanical as required.
2. Locate thermostat or remote sensor in the conditioned space where it will sense average temperature. Do not locate the device where it may be directly exposed to supply air, sunlight or other sources of heat. Follow installation instructions packaged with the thermostat.
3. Use #18 AWG wire for 24V control wiring runs not exceeding 75 f eet. Use #16 A WG wire f or 24V control wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 wher e permitted by local codes.
4. Route thermostat wires from sub-base terminals to the unit. Control wiring should enter through the condenser panel opening indicated in “Electrical Entrance” figure. Connect thermostat and any accessory wiring to low voltage terminal block TB1 in the main control box.
UNIT 2" MINIMUM
FLEXIBLE TUBING-HOSE OR PIPE
A POSITIVE LIQUID SEAL IS REQUIRED
Drain Connection
3" MIN IMUM
Install condensate drain trap as shown. Use 3/4” drain line and fittings or larger. Do not operate without trap.
HORIZONTAL DRAIN
Drainage of condensate directly on to the r oof ma y be accept able; refer to local code. It is recommended that a small drip pad of either stone, mortar, wood or metal be provided to prevent any possible damage to the roof.
CLEANING
Due to the fact that drain pans in any air conditioning unit will have some moisture in them, algae and fungus will grow due to airborne bacteria and spores. Periodic clean­ing is necessary to prevent this build-up from plugging the drain.
8
Page 9
ST ARTUP, ADJUSTMENTS, AND CHECKS
WARN ING
HIGH VOLTAGE!
O AVOID PERSONAL INJURY OR DEATH DUE TO
T
ELECTRICAL SHOCK, B THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL PROVIDED OR OTHER ACCEPTABLE MEANS SERVICING OR INSTALLING THIS UNIT
OND THE FRAME OF THIS UNIT TO
. D
ISCONNECT ALL POWER BEFORE
.
PRE-STARTUP INSTRUCTIONS
CONTRACTOR RESPONSIBILITY
The installing contractor must be certain that:
All supply and return air ductwork is in place, properly sealed, and corresponds with installation instructions.
All thermostats are mounted and wired in accordance with installation instructions.
All electric power, all gas, hot water or steam line connections, and the condensate drain installation have been made to each unit on the job. These main supply lines must be functional and capable of operating all unit s simultaneously.
All filters are in place.
CAUTION
TO
PREVENT PROPERTY DAMAGE OR PERSONAL INJURY START THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TESTS HAVE BEEN PERFORMED
.
, DO
NOT
Prior to the beginning of Startup, Adjustments, and Checks pr oce­dures, the following steps should be completed in the building.
WARN ING
MOVING MACHINERY HAZARD!
O PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT
T
POWER TO THE UNIT AND PADLOCK IN THE SERVICNG FANS
.
“OFF”
POSITION BEFORE
HEATING STARTUP
On new installations, or if a major component has been replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct cov er s must be removed before
operating unit.
The Startup, Adjustments, and Checks procedure provides a step­by-step sequence which, if follow ed, will assure the proper st artup of the equipment in the minimum amount of time. Air balancing of duct system is not considered part of this procedure. However, it is an important phase of any air c onditioning sys tem st artup and should be performed upon completion of the Startup, Adjustment s, and Checks procedure. The St artup, Adjustment s, and Checks pro­cedure at outside ambients below 55°F should be limit ed to a readi­ness check of the refrigera tion system with the requir ed final check and calibration left to be completed when the outside ambient rises above 55°F.
TEMPORARY HEATING OR COOLING
If the unit is to be used for tempor ary heating or cooling, a “Startup, Adjustments, and Checks” must first be performed in accordance with this manual. Failure to comply with this requir ement will void the warranty. After the machines are used for temporary heating or cooling, inspect the coils, fans, and motors for unacceptable levels of construction dust and dirt and install new filters.
ROOF CURB INSTALLATION CHECK
Inspect the roof curb for correct installation. The unit and curb assembly should be level. Inspect the flashing of the roof mount­ing curb to the roof, especially at the corners, for good workman­ship. Also check for leaks around g a s kets. Note any deficiencies in a separate report and for ward to the contractor.
OBSTRUCTIONS, FAN CLEARANCE AND WIRING
Remove any extraneous construction and shipping materials that may be found during this procedure. Rotate all fans manually to check for proper clearances and that they rotate freely. Check for bolts and screws that may have jarred loose during shipment to the job site. Retighten if necessary. Re-tighten all electrical con­nections.
FIELD DUCT CONNECTIONS
Verify that all duct connections are tight and that there is no air bypass between supply and return.
FILTER SECTION CHECK
Remove filter section access panels and check that filter s are prop­erly installed. Note airflow arrows on filter frames.
PRE-STARTUP PRECAUTIONS
It is important to your safety that the unit has been properly grounded during installation. Check gr ound lug connection in main control box for tightness prior to closing circuit breaker or discon­nect switch. Verify that supply voltage on line side of disconnect agrees with voltage on unit identification plate and is within the utilization voltage rang e as indicat ed in Appendix B Electrical Data.
System Voltage - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage class.
Nameplate Voltage - That voltage assigned to a piece of equip­ment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
Utilization Voltage - The voltag e of the line terminals of the equip­ment at which the equipment must give fully satisfactory perfor­mance. Once it is established that supply voltage will be main­tained within the utilization range under all system conditions, check and calculate if an unbalanced condition exists between phases. Calculate percent voltage unbalance as follows:
9
Page 10
AIR FLOW ADJUSTMENTS
EEM MOTOR
Adjust the CFM for the unit by changing the position of the low voltage leads on the motor terminal block. Green is for Fan Only. Y ello w is for Cooling and Heat Pump Heating. R efer to Appendix A for blower performance at each speed tap. NOTE: If more than one lead is energized simultaneously, the motor will run at the higher speed.
REFRIGERATION SYSTEM CHECKS
Ensure the hold-down bolts on the compressor are secur e and have not vibrated loose during shipment. Check that vibration grom­mets have been installe d. Visually check all piping and clamps. The entire refrigeration system has been factory charged and tested, making it unnecessary to field charge. Factory charges are shown on the unit nameplate.
START-UP PROCEDURE AND CHECKLIST
Begin with power turned off at all disconnects.
AIR CONDITIONING START-UP PROCEDURE
1. Turn thermostat system switch to “Cool,” and fan switch to “Auto” and turn temperature setting as high as it will go.
2. Inspect all registers and set them to the normal open position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blower should operate after a 7 second delay.
5. Turn the f an s witch t o “Auto” position. The blower should stop after a 65 second delay.
6. Slowly lower the cooling temperatur e until the unit starts. The compressor , blo wer and fan should now be oper ating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.
7. Turn the temperature setting to the highest position, stopping the unit. The indoor blower will continue to run for 65 seconds.
8. Turn the thermostat system switch to “OFF” and disconnect all power when servicing the unit.
WARN ING
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
HEAT PUMP START-UP PROCEDURE
9. Check the cooling mode for the heat pump in the same manner as above. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking
sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contractor is energized. The compressor, blower and fan should then be running. After the cooling mode is checke d out, turn the thermostat system switch to “OFF”.
10. Turn the thermostat system switch to “HEAT” and fan switch to “AUTO”.
11. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor, blower and fan should now be running with the reversing v alve in the de­energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.
12. If the outdoor ambien t is abov e 80°F, the unit may trip on its high pressure cut out when on hea ting. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable but-DO NOT FAIL TO TEST.
If the outdoor ambient is low and the unit operates properly on the heating cycle, you ma y check the pressur e cutout operation by blocking off the indoor re turn air until the unit trips.
13. If unit operates properly in the heating cycle, raise the temperature se tting until the hea ting second stag e make s contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly.
NOTE: If outdoor thermostats are installed the outdoor ambient must be below the set poin t of these thermostats for the heaters t o operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.
14. For thermostats with emergency heat switch, return to step 11. The emergency heat switch is located at the bottom of the thermosta t. Move the swit ch to emergency heat. The heat pump will stop, the blower will continue t o run, all heaters will come on and the thermostat emergency heat light will come on.
15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defro st con trol, observe at least one defrost cycle to make sure the unit defrosts completely.
FINAL SYSTEM CHECKS
16. Check to see if all supply and r eturn air grilles ar e adjuste d and the air distribution system is balanced for the best compromise between heating and cooling.
17. Check for air leaks in the ductwork. See Sections on Air
Flow Adjustments.
18. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing ag ainst e ach other or sheet metal surfaces or edges. If so, correct the trouble.
19. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.
10
Page 11
20. Be sure the Owner is instructed on the unit oper ation, filter , servicing, correct thermostat operation, etc.
REFRIGERATION PERFORMANCE CHECK
Check that compressor RLA corresponds to values shown in Ap­pendix B. RLA draw can be much lower than values listed at low load conditions and low ambient condensing temperatures. Val­ues in Appendix B can slightly exceed at high load conditions and high ambient condensing temperatures.
HEAT PUMP OPERATION
COOLING CYCLE
When the heat pump is in the cooling cycle, it operat es exactly as a Summer Air Conditioner unit. In this mode, all the charts and data for service that apply to summer air conditioning apply to the heat pump. Most apply on the heating cy cle e xcept that “ con­denser” becomes “evaporator”, “evaporator” becomes “con­denser”, “cooling” becomes “heating”.
HEATING CYCLE
The heat pump operat es in the heating cycle by redirecting refrig­erant flow through the r efriger ant circuit e xternal to the compre s­sor . This is accomplishe d with through the re versing valv e. Hot dis­charge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes thr ough the expansion device to the outdoor coil (condenser on the cooling cycle) wher e the liquid is evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve.
The following figures show a schematic of a heat pump on the cooling cycle and the heating cycle. In a ddition to a rever sing valve, a heat pump is equipped with an expansion device and check v alve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system.
The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the re­verse of refrigerant flow.
When the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperatur e of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil tem­perature, the gr ea t er the he a ting c ap acity of the he at pump. This phenomenon is a characteristic of a heat pump. It is a good pr ac­tice to provide supplementary heat f or all he a t pump inst allations in areas where the temperature drops below 45° F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requiremen t should ther e be a c omponent f ail­ure of the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the r efrigeran t in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the out­door coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the out­door coil and lessen the time required for defrosting. The indoor blower continues to run and the supplemen t ary heat ers ar e ener­gized.
DEFROST CONTROL
During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30,60 and 90 minutes may be selected by connecting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 31° F), and when the wall thermostat calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sen­sor remains closed. When the sensor opens (appro ximately 75° F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor tempera­ture, a ten minute override interrupts the unit’s defrost period.
11
Page 12
MAINTENANCE
WARN ING
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
CABINET FINISH MAINTENANCE
Use a fine gra de automotiv e wax on the c abinet finish t o maintain the finish’s original high luster. This is especially important in in­stallations with extended periods of direct sunlight.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently a s necessary to keep the finne d areas free of lint, hair and debris.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER
. FOR
.
ADDITIONAL
,
CAUTION
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION
.
The Self Contained Packaged Air Conditioner and He at Pump should operate for man y year s without exce ssive service calls if the unit is installed properly. However it is recommended that the home­owner inspect the unit before a sea sonal start up. The coils should be free of debris so adequate airflow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced. These few steps will help to keep the product up time to a maximum. The Service section that fol­lows should help in identifying problems if the unit does not oper ­ate properly.
FILTERS
CAUTION
T
O PREVENT PRO PERTY DAMAG E DUE TO FIRE AND LOSS O F EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Every application may require a different frequency of replace­ment of dirty filters. Filters must be replaced at least every three (3) months during operating seasons.
Dirty filters are the most common cause of inadequat e he a ting or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local condi­tions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean filter.
Disposable return air filters are supplied with this unit. See the unit Specification Sheet or Technical Manual for the correct size and part number. To remove the filters, remove the filter access panel on return side of the unit.
LUBRICATION
The fan shaft bearings , the 1 to 2 HP supply fan motors, the con­denser fan motors and compressors are permanently lubricated.
FUNCTIONAL PARTS
Refer to the unit Parts Catalog for a list of functional parts. Parts are available from your distributor.
TROUBLESHOOTING
THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SER­VICE AGENCY ONLY: OTHERS SHOULD NOT AT TEMPT TO SERVICE THIS EQUIPMENT.
Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle.
INADEQUATE AIR VOLUME THROUGH INDOOR COIL
When a heat pump is in the heating cycle, the indoor coil is func­tioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass thr ough the indoor coil to pre­vent excessive discharge pressure, and high pressure cut out.
OUTSIDE AIR INTO RETURN DUCT
Do not introduce cold outside air into the return duct of a heat pump installation. For units with 2-speed motor s, do not allow air entering the indoor coil to drop below 65° F. Air below this tem­perature will cause low discharg e pr essur e, thus low suction pr e s­sure, and excessive de frost cycling r esulting in lo w heating output. It may also cause false defrosting.
UNDERCHARGE
An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost ac­cumulation on the outdoor coil.
POOR “TERMINATING” SENSOR CONTACT
The unit’s defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor cont act may not termi­nate the unit’s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure.
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO:
1. Solenoid not energized - In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.
12
Page 13
2. No voltage at unit’s solenoid - Check unit voltage. If no voltage, check wiring circuit.
3. Valve will not shift:
a. Undercharged - check for leaks; b. Valve Body Damaged - Replace valve; c. Unit Properly Charg e d - If it is on the hea ting cycle, r aise
the discharge pressur e by re stricting airflow thr ough the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. DO NOT TAP THE VALVE BODY. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off and wait until the discharge and suction pressure equalize, and repea t above st eps. If the valve does not shift, replace it.
13
Page 14
APPENDIX A BLOWER PERFORMANCE TABLES
L
DIRECT DRIVE
STANDARD DOWN SHOT AND HORIZONTAL
STANDARD DTC/DTH036
SPEED
TAP
T1
T2
T3
T4
T5
Notes: Table represent dry coil without filter, to compensate f o r f ilter add 0.08" to measured E.S.P.. S CF M correction f or wet coil = 4%. 5 Ton models are shipped from the f actory with speed tap set on T4.
EXTERNAL
STATIC
PRESSURE (E SP )
0.1 966 0.5 108 657 T1 0.1 1018 0.47 101 615
0.2 850 0.52 115 710 0.2 969 0.49 109 653
0.3 773 0.55 122 763 0.3 881 0.53 117 712
0.4 678 0.59 130 819 0.4 818 0.55 125 768
0.5 593 0.62 141 875 0.5 732 0.59 135 833
0.6 0.6 658 0.63 142 890
0.7 0.7 616 0.65 148 938
0.8 0.8
0.9 0.9
0.1 1057 0.6 134 693 T2 0.1 1128 0.56 126 645
0.2 956 0.62 140 740 0.2 1070 0.59 132 692
0.3 868 0.66 144 787 0.3 994 0.62 138 727
0.4 788 0.69 156 839 0.4 915 0.66 149 791
0.5 700 0.73 166 898 0.5 839 0.69 156 838
0.6 618 0.76 174 946 0.6 776 0.73 169 909
0.7 0.7 698 0.77 179 963
0.8 0.8 649 0.8 183 1003
0.9 0.9
0.1 1234 0.86 199 784 T3 0.1 1293 0.81 186 733
0.2 1146 0.89 206 822 0.2 1252 0.84 193 765
0.3 1068 0.92 213 863 0.3 1198 0.87 204 803
0.4 977 0.96 221 910 0.4 1130 0.91 212 844
0.5 911 1 232 949 0.5 1075 0.94 218 886
0.6 842 1.04 245 998 0.6 1015 0.98 230 930
0.7 776 1.08 253 1031 0.7 941 1.02 242 984
0.8 703 1.11 263 1082 0.8 870 1.08 253 1045
0.9 682 1.13 266 1107 0.9 817 1.11 262 1080
0.1 1363 1.03 242 822 0.1 1404 0.99 232 789
0.2 1253 1.09 251 874 0.2 1367 1.02 240 817
0.3 1176 1.12 260 910 0.3 1334 1.05 244 845
0.4 1110 1.15 270 940 0.4 1265 1.09 257 882
0.5 1034 1.19 279 981 0.5 1207 1.13 265 922
0.6 966 1.23 290 1028 0.6 1153 1.17 272 958
0.7 899 1.27 301 1074 0.7 1090 1.21 283 1005
0.8 836 1.33 312 1117 0.8 1029 1.25 299 1052
0.9 778 1.35 319 1146 0.9 947 1.31 312 1111
0.1 1413 1.14 268 849 T5 0.1 1457 1.08 254 805
0.2 1299 1.18 275 899 0.2 1413 1.12 266 839
0.3 1233 1.23 259 933 0.3 1359 1.16 273 870
0.4 1166 1.26 296 963 0.4 1307 1.2 285 911
0.5 1096 1.3 307 1000 0.5 1253 1.23 291 940
0.6 1026 1.34 318 1040 0.6 1197 1.28 304 978
0.7 960 1.39 330 1052 0.7 1138 1.31 310 1017
0.8 889 1.44 340 1132 0.8 1082 1.36 322 1059
0.9 835 1.47 347 1169 0.9 1029 1.41 335 1105
STANDARD
CFM
AMPS WATTS RPM
SPEED
TAP
T4
EXTERNAL
STATIC
PRESS URE (ESP)
DOWNSHOT HORIZONTA
STAN DARD
CFM
AMPS WATTS RPM
14
Page 15
APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
STANDARD HORIZONTAL
STANDARD DTC/DTH048
DOWNSHOT HORIZONTAL
EXTERNAL
SPEED
TAP
T1 32%
T2 39%
T3 55%
T4 63%
T5
66.5%
Notes: Table represent dry coil without filter, to compensat e for filter add 0.08" to measured E.S .P.. SC F M correction f or wet coil = 4%. 5 Ton models are ship ped f r om th e f actory with speed tap set on T4.
STATIC
PRESSURE (ESP)
in w.c.
0.1 1286 0.82 187 667
0.2 1205 0.86 198 704 0.2 1286 0.8 186 657
0.3 1139 0.8 205 731 0.3 1 211 0.84 198 698
0.4 1052 0.92 212 764 0.4 1144 0.88 204 730
0.5 982 0.95 215 790 0.5 1068 0.92 214 768
0.6 911 0.97 224 814 0.6 996 0.95 222 798
0.7 840 1 230 837 0.7 923 0.98 229 829
0.8 779 1.02 235 855 0.8 839 1.01 235 857
0.9 717 1.04 242 879 0.9 777 1.04 242 881
0.1 1470 1.09 251 726
0.2 1399 1.12 260 758 0.2 1482 1.05 246 710
0.3 1315 1.16 271 790 0.3 1412 1.09 256 745
0.4 1253 1.19 281 814 0.4 1352 1.13 263 774
0.5 1180 1.22 287 842 0.5 1286 1.17 272 806
0.6 1110 1.26 292 867 0.6 1216 1.19 281 839
0.7 1042 1.29 300 891 0.7 1147 1.24 289 868
0.8 973 1.32 308 914 0.8 1077 1.27 299 892
0.9 916 1.34 314 933 0.9 1002 1.31 309 922
0.1 1747 1.75 413 855
0.2 1668 1.8 414 884 0.2 1 762 1.65 392 809
0.3 1609 1.84 436 908 0.3 1697 1.69 399 835
0.4 1557 1.88 442 931 0.4 1651 1.74 416 863
0.5 1489 1.92 453 957 0.5 1598 1.79 423 892
0.6 1419 1.97 476 984 0.6 1533 1.85 438 922
0.7 1377 2 472 1002 0.7 1464 1.89 447 951
0.8 1311 2.03 479 1022 0.8 1417 1.94 458 975
0.9 1256 2.07 488 1044 0.9 1361 1.97 475 999
0.1 1879 2.11 504 908
0.2 1799 2.16 512 935 0.2 1888 1.99 471 853
0.3 1730 2.2 525 955 0.3 1 847 2.04 491 876
0.4 1677 2.26 539 981 0.4 1790 2.09 502 906
0.5 1630 2.31 547 1006 0.5 1742 2.14 509 928
0.6 1558 2.35 557 1032 0.6 1682 2.19 537 957
0.7 1508 2.38 553 1049 0.7 1620 2.26 5337 987
0.8 1443 2.43 588 1072 0.8 1576 2.28 547 1010
0.9 1389 2.48 585 1091 0.9 1521 2.33 556 1034
0.1 1903 2.28 542 931
0.2 1838 2.31 561 952 0.2 1946 2.16 511 876
0.3 1785 2.38 571 977 0.3 1893 2.15 518 896
0.4 1723 2.41 574 1002 0.4 1865 2.28 536 923
0.5 1666 2.46 585 1020 0.5 1795 2.26 548 351
0.6 1612 2.51 596 1048 0.6 1741 2.39 555 376
0.7 1547 2.56 611 1067 0.7 1681 2.38 572 999
0.8 1505 2.59 607 1083 0.8 1630 2.47 597 1023
0.9 1445 2.63 613 1109 0.9 1576 2.47 595 1046
STANDARD
CFM
AMPS WATTS RPM
SPEED
TAP
T1 32%
T2 39%
T3 55%
T4 63%
T5
EXTERNAL
STATIC
PRESSURE (ESP)
in w.c.
STANDARD
CFM
0.1 1346 0.77 176 622
0.1 1534 1.01 234 681
0.1 1515 1.61 382 787
0.1 1941 1.96 464 834
0.1 1994 2.09 497 845
AMPS WATTS RPM
15
Page 16
APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
STANDARD DTC/DTH060 DOWN SHOT
SPEED
TAP
T1
T2
T3
T4
T5
NOTES: Tables represent dry coil without filter, to compensate for filter add 0. 08 " to measured E.S.P. SCFM correction for wet coil = 4
%. 5 Ton models are shipped from the factory wit h speed tap set on T4.
EXTERNAL STATIC
PRESSURE (ESP)
in w.c.
0.10 1334 1.65 180 627
0.20 1286 1.75 192 665
0.30 1212 1.83 202 715
0.40 1144 1.94 216 759
0.50 1077 1.99 222 792
0.60 1039 2.10 238 830
0.70 953 2.17 248 874
0.80 904 2.27 258 913
0.90 825 2.30 266 940
0.10 1512 2.12 240 682
0.20 1469 2.24 254 720
0.30 1397 2.31 264 759
0.40 1333 2.44 282 803
0.50 1285 2.54 296 836
0.60 1221 2.59 304 874
0.70 1173 2.72 322 913
0.80 1118 2.77 328 946
0.90 1049 2.90 344 984
0.10 2053 4.27 540 869
0.20 2014 4.39 558 896
0.30 1999 4.60 576 929
0.40 1947 4.68 588 957
0.50 1897 4.79 608 989
0.60 1857 4.87 620 1012
0.70 1763 4.99 640 1050
0.80 1741 5.06 650 1072
0.90 1669 5.19 668 1105
0.10 2137 4.95 634 913
0.20 2093 5.07 652 940
0.30 2095 5.19 670 962
0.40 2026 5.28 682 990
0.50 1980 5.40 698 1018
0.60 1961 5.49 720 1039
0.70 1914 5.58 732 1072
0.80 1845 5.70 742 1100
0.90 1766 5.69 740 1127
0.10 2299 5.70 742 942
0.20 2233 5.80 748 969
0.30 2217 5.90 768 990
0.40 2157 6.07 786 1018
0.50 2131 6.12 804 1045
0.60 2060 6.21 816 1073
0.70 2015 6.30 820 1095
0.80 1940 6.27 816 1111
0.90 1862 6.13 790 1128
STANDARD
CFM
16
AMPS WATTS RPM
Page 17
APPENDIX A BLOWER PERFORMANCE TABLES
/
DIRECT DRIVE
STANDARD DTC/DTH060 HORIZONTAL
SPEED
TAP
T1
T2
T3
T4
T5
NOTES: Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.
5 Ton models are shipped from the factory with speed tap set on T4.
EXTERNAL STATIC
PRESSURE (ESP)
in w.c.
0.10 1355 1.57 174 599
0.20 1281 1.66 182 651
0.30 1235 1.76 196 693
0.40 1168 1.81 202 726
0.50 1118 1.94 218 775
0.60 1049 2.03 232 819
0.70 982 2.10 240 858
0.80 922 2.14 246 885
0.90 871 2.25 260 927
0.10 1544 2.04 234 660
0.20 1490 2.17 250 704
0.30 1427 2.25 260 742
0.40 1370 2.35 276 781
0.50 1319 2.42 282 809
0.60 1274 2.52 296 849
0.70 1210 2.62 316 891
0.80 1137 2.73 326 935
0.90 1106 2.77 336 957
0.10 2099 4.13 516 825
0.20 2068 4.25 536 852
0.30 2029 4.37 552 885
0.40 1971 4.48 568 913
0.50 1911 4.61 586 950
0.60 1876 4.73 604 973
0.70 1821 4.86 622 1012
0.80 1792 4.91 630 1028
0.90 1740 5.03 648 1067
0.10 2233 4.76 608 863
0.20 2168 4.91 628 896
0.30 2125 5.02 640 924
0.40 2070 5.14 660 951
0.50 2050 5.27 678 979
0.60 1980 5.41 696 1012
0.70 1954 5.47 704 1034
0.80 1893 5.60 724 1067
0.90 1852 5.70 736 1089
0.10 2322 5.44 710 904
0.20 2294 5.55 726 934
0.30 2254 5.68 742 958
0.40 2201 5.80 766 990
0.50 2147 5.93 782 1017
0.60 2117 6.01 788 1039
0.70 2081 6.12 808 1060
0.80 2017 6.22 822 1094
0.90 1932 6.10 804 1111
STANDARD
CFM
17
AMPS WATTS RPM
Page 18
APPENDIX B ELECTRICAL DATA
MODELS
3 TON 208/230-60-1 187 253 1 14.1 77 1 1/4 1.4 DD STD STATIC 1/2 3.9
4 TON 208/230-60-1 187 253 1 19.9 109 1 1/4 1.4 DD STD STATIC 1 6.9
5 TON 208/230-60-1 187 253 1 25.0 134 1 1/3 2.0 DD STD STATIC 1 6.9
VOLTAGE
(NAM EPLATE)
VOLTAGE
LIMITATION MIN MAX QTY RLA LRA QTY HP RLA HP FLA
COMPR ESSOR
OUTDOOR
FAN MOTOR
INDOOR MOTOR
APPLICATION
INDOOR FAN
MOTOR
MINIMUM AIR F LOW FOR ELECTRIC HEAT
UNIT
3 TON
HEATER KIT
MODEL N UMBE R
EHK*-10 1250 EHK*-15 1250
MIN I MUM CFM
EHK*-10 1300
4 TON
EHK*-15 1400 EHK*-18 1400 EHK*-10 1700
5 TON
EHK*-15 1700 EHK*-20 1800
AT TENTION INSTALLING PERSONNEL
Use only the heater kit specified for each model as dictated by the table above.
18
Page 19
APPENDIX C UNIT DIMENSIONS
47 1/2”
38 13/16”*
74 1/16”
5 Ton “T” model
73 1/4”
48 3/16”
12”
6 1/4”
17” 7 3/8”
SUPPLY
HORIZONTAL DISCHARGE
11”
RETURN
4 7/8”
25”
19 7/16”
RETURN
5 7/8”
SUPPLY
8 3/16”
DRAIN THRU CURB LOCATION
27 3/8”
47 1/2”
BOTTOM VIEW OF UNIT
VERTICAL DISCHARGE
EMBOSS FOR THRU THE BASE UTILITIES
4 1/2”
7 1/2”
19
Page 20
WIRING DIAGRAMS
DTC0[36-60]XXX1DXXX
NOTE 3
RD
BK
3
2
1
C
BL
208
240
TR
24V
BL
PK
BL
BL
L2
T2
RD
RD
BK
BK
YL
L1
T1
C
YL/PK
BK
RD
BR
RD
YL
WH
GR
TB1
H
1
OR
BR
YL
WH
PU
5
3
4
1
2
EM
GLC
N
BL
L1
C
T1
C
BK
RD
SUPPLY VOLTAGE
208-240/1/60
R
COMP
5
SEE NOTE 2
GR
C
T2
RCCF
PU
C
F
L2
S
C
RCCF
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
EM
N
H
F
CM
L
G
3
208-240V NOTE 3
2
1
TR
24V
SEE NOTE #2
1 2 3 C
EM
4 5
C
PLF2
89
7
5
6
4
3
1
2
PLF
4
5
6
TB1
LPS
HPS
WH
6
9
3
5
2
8
BR
1
4
7
GR
WH
BL BL
PLF 1
RD
BK
YL
PU
CM
BK
BR
T3
COMP
T1
T2
COMPONENT LEGEND
C
CONTACTOR
CM
CONDENSER MOTOR
COMP
COMPRESSOR
EM
EVAPORATOR MOTOR
GND
EQUPIMENT GROUND
LVJB
LOW VOLTAGE JUNCTION BOX
PLF
FEMALE PLUG / CONNECTOR
RCCF
RUN CAPACITOR FOR COMPRESSOR AND FAN
TB1
TERMINAL BLOCK (24V SIGNAL)
TR
TRANSFORMER
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM "3" AND "4" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. USE COPPER CONDUCTORS ONLY
++
USE N.E.C. CLASS 2 WIRE.
5. ECONOMIZER PLUG LOCATED IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO ECONOMIZER ACCESSORY.
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
YL
YL/PK
NOTE 5
GCY1
Y2
W1
W1
R
W2
R
W2
O
O
S2
S2
S1
S1
THERMOSTAT
TB1
GCY1
++
208-240/1/60 0140L02910-B
RD
RD
BK
BK
NOTE 4
GND
RD
GR
PLF 2
36 2
PU
5 4
1
BL
YL
LVJB
YL PU RD GR
WH
BR
BL
OR
RD
PK
TB1
CONTROL BOX
HPS
SMOKE/FIRE DETECTOR
LPS
REPLACES JUMPER
FACTORY WIRING
LINE VOLTAGE LOW VOLTAGE
OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE
FIEL
HIGH VOLTAGE LOW VOLTAGE
W
BK BLACK BL BLUE BR BROWN GR GREEN
OR ORANGE
PK PINK PU PURPLE RD RED WH WHITE
YL YELLOW BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
THERMOSTAT FIELD WIRING
NO
ECONOMIZER
W
G
R
Y1
Y2
Y2
C
O
TB1
ITH ECONOMIZER OPTION
W
W
G
R
Y1
Y2
C
O
TB1
2 STA
W
G
R
Y1
Y2
C
O
TB1
OR
9
8 7
BL/PK
D WIRING
IRE CODE
WH
GR
RD
YL
BL
OR
WH
GR
RD
YL
BL
OR
GE COOLING
WH
GR
RD
YL
PK
BL
OR
NOTE 5
Y1 Y2
R G W1
W2
C O S2 S1
++
STAT
W
G
R
Y
C
O
STAT
STAT
2 0 8
­2 4 0
/ 1 /
6 0
T H E R
M
O S T A T
++
W
G
R
Y
C
O
W
G
R
Y1
Y2
C
O
20
Page 21
WIRING DIAGRAMS
DTH0[36-60]XXX1DXXX
SEE
NOTE 7
WH
YL/PK
S
P
L
YL/PK
YL
YL
YL
WH
GR
TB1
1
5
BR
OR
YL
WH
PU
4
3
5
1
2
EM
C
N
L
G
BL
BK
RD
L1
C
T1
C
SEE
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
NOTE 7
R
HVDR
DF1
SEE NOTE 2
GR
SUPPLY VOLTAGE
R
COMP
S
H
CHS
BR
C
C
R
CCR
LVDR
D2
DFT
208-240/1/60
T2
C
RCCF
F
SEE NOTE 6
BL
PU
DC
C
CNT
0
OR
0
0-RV
BK
C-RV
W
Y
Y
PU
PS2
R-PS1
R-DFT
RD
PU
BK
RD
RD
BK
DFT
BK
H
RCCF
BR
RD
WH
C
F
RD
1
RVC
L2
C
DF2
DF1
HVDR
CM
CH
N
EM
G
R
RVC
LPS
P
P
4
L
L F
F
5
1
1
6
L
208-240V
N
O
S
E
3
E
E
T
2
24V
C-RV
Y
HPS
1
TR
R-DFT
DC R-PS1
1 2 3 4 5
DFT
DFT
PS2
SEE NOTE 2
C
EM
87
9
5
4
6 3
2
1
C
C
N
T
C
3
O-RV
R
O
W
PLF2
SEE NOTE 5
GCY1W1
W2
W2
R
R
O
O
S2
S2
S1
S1
THERMOSTAT
GCY1W1
Y2
++
BK
RD
3
1
2
C
PK
BL
240
208
TR
24V
BL
BL
BL
BL
RD
PU
PU
WH
WH
PLF 1
3
6
9
8
2
5
4
BR
7
BL
BK
PU
BR
YL
CM
COMPONENT LEGEND
CONTACTOR
C
COMPRESSOR CONTACTOR RELAY
CCR
CRANKCASE HEATER
CH
CRANKCASE HEATER SWITCH
CHS
CONDENSER MOTOR
CM
COMPRESSOR
COMP
DEFROST CONTROL
DC
DEFROST THERMOSTAT
DFT
ECONOMIZER
ECON
EVAPORATOR MOTOR
EM
EQUIPMENT GROUND
GND
HIGH PRESSURE SWITCH
HPS
HIGH VOLTAGE DEFROST RELAY
HVDR
LOW PRESSURE SWITCH
LPS
LOW VOLTAGE DEFROST RELAY
LVDR
LOW VOLTAGE JUNCTION BOX
LVJB
FEMALE PLUG / CONNECTOR
PLF
REVERSING VALVE COIL
RVC
RUN CAPACITOR FOR
RCCF
COMPRESSOR AND FAN TERMINAL BLOCK (24V SIGNAL)
TB1
TRANSFORMER
TR
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM "3" AND "4" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. USE COPPER CONDUCTORS ONLY
USE N.E.C. CLASS 2 WIRE
++
5. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO ECONOMIZER ACCESSORY.
6. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY EQUIPPED WHEN REQUIRED.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
2
BL
T2
RD
BK
T1
BK
PU
YL
RD
BK
T3
T1
COMP
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
/
1
0
2
/
4
-
8
0
RD
RD
L2
C
L1
BK
YL PU RD
GR
GR
WH
WH
WH
BR
OR
OR
BL
BL
BL
RD
RD
BR
PK
PU
YL
BL/PK
T2
HPS
9
7
-
2
0
0
0
4
L
1
0
0
6
BK
K
B
SEE NOTE 4
GND
OR
RD
GR
PU
YL
PLF 2
9
36 2
8
5
7
4
YL
1
BL
LVJB
TB1
BK
BL/PK
BK
CH
GR
WIRE CODE
BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PK PINK RD RED PU PURPLE YL YELLOW WH WHITE BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
THERMOSTAT FIELD WIRING
N
O ECONOMIZER
W
G
R
Y1
Y2
Y2
C
O
TB1
WITH ECONOMIZER OPTION
W
G
R
Y1
Y2
Y2
C
O
TB1
2 STAGE COOLING
W
G
R
Y1
Y2
C
O
TB1
B
NOTE 5
Y1 Y2 R G W1
W2
O C
S2 S1
CONTROL BOX
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR
SEE NOTE 6
CTORY WIRING
FA
LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WH GR
RD
YL
BL
OR
WH
GR
RD
YL
BL
OR
WH
GR
RD
YL
PK
BL
OR
1
6 0
++
2 0 8
­2 4 0 /
/
STAT
STAT
STAT
R
D
NOTE 6
R
T
B
H E R M O S T A T
++
W
G
R
Y
C
O
W
G
R
Y
C
O
W
G
R
Y1
Y2
C
O
R
D
C
H
S
D
K
21
Page 22
Start-up Checklist
*Store in job file
Date: ___________________________________
Model Number: ___________________________________
Serial Number: ___________________________________
Technician: ___________________________________
Pre Start-Up
(Check each item as completed)
Verify all pack aging ma t erial ha s been r emov ed. Remove all shipping brackets per installation instructions.
Verify the job site voltage agrees with the unit serial plate. Verify condensate c onnection is ins t alle d per ins tallation ins tructions. Verify pr oper cle arance around the unit for safety, service, maintenance and proper unit operation. Verify pr oper weatherproofing of all ductwork, roof curbs and electric al c onnections.
Location: __________________________________________
__________________________________________ __________________________________________
Unit #: __________________________________________
Check that the flue screen is in place. Check gas piping f or leaks. Verify gas pressure to the unit is within the range specified on the serial plate. Check to ensure that all fans, pulleys and wheels ar e secure. Check for proper belt tension and alignment per inst alla tion instructions. Check refriger ant piping for rubbing and leaks. Repair if necessary. Check unit wiring to ensure it is not in contact with refrigerant piping or sharp met al edges. Check all electrical connections and terminals. Tighten as needed. Verify that the crankcase heaters hav e been energized for 24 hours. Verify the scr oll compressor(s) are r ot a ting in the right dir ection. Verify all accessories are installed and oper ating correctly. Check filters and replace if necessary. Verify the inst allation of the thermost at.
22
9/2014
Page 23
ELECTRICA
L
Start-up Checklist
Start-Up
(Insert the values as each item is completed.)
Supply Voltage Circuit 1 Compressor Amps Circuit 2 Compressor Amps
Blower Amps
Condenser Fan Amps
BLOWER EXTERNAL STATIC PRESSURE
Return Air Static Pressure Supply Air Static Pressure
Total External Static Pressure
Blower Wheel RPM
TEMPERATURES
Outdoor Air Temperature
Return Air Temperature Co oling S u pply Air Tem p erat ure He ating Supply Air Temperat u re
L1 - L2 L2 - L3 L3 - L1
L1 L2 L3 L1 L2 L3 L1 L2 L3
Fan 1Fan 2Fan 3
IN. W.C. IN. W.C. IN. W.C. RPM
DB WB DB WB DB WB DB
PRESSURES
Ga s Inlet Pressure
Ga s Manifold Pressure
Superh ea t (O rific e Sys tem)
Superh ea t (O rific e Sys tem)
Discharge Circuit 1
Subcooling (TXV Syst em)
Discharge Circuit 2
Subcooling (TXV Syst em)
(HEAT P UM P O N LY)
Discharge Circuit 1 Discharge Circuit 2
Suction Circuit 1
Suction Circuit 2
Suction Circuit 1 Suction Circuit 2
IN. W.C. IN. W.C. (Low Fire) IN. W.C. (High Fire) PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F PSIG °F PSIG °F PSIG °F
23
Page 24
NOTE: Refer to IOD-7006 included in the literature pack for installing horizontal duct covers.
© 2015
• Products • Contractor Programs and Training
• Parts • Customer Services
• Warranties • Finance Options Visit our website at www.daikincomfort.com
24
Loading...