Page 1
DP14DM
Cooling Capacity: 23,200 – 45,500 BTU/h
Heating Capacity: 60,000 – 115,000 BTU/h
Packaged Dual-Fuel Units
Up to 14.5 SEER
81% AFUE / 8.0 HSPF
■ Contents
Nomenclature ........................................ 2
Product Specicaons ........................... 3
Expanded Cooling Data ......................... 5
Expanded Heang Data ...................... 17
Airow Data ......................................... 18
Dimensions .......................................... 21
Wiring Diagrams ................................. 22
Accessories ..........................................24
■ Standard Features
• Combines cooling with heat pump and gas
heang for opmal year-long performance
• High-eciency scroll compressor
• Heavy-duty stainless-steel tubular heat exchanger
• Mul-Speed ECM indoor blower motor
• All-aluminum evaporator coil
• Copper tube / aluminum n coil
• Two-stage gas valve; natural gas with easy
conversion to propane with accessory kit
• Power-assisted combuson
• Direct spark ignion system with a microprocessor-
based control for the enre ignion sequence
• All blower operaon and all safety circuits
complete with self-diagnoscs
• Loss-of-charge protecon
• All models comply with California
Low NOx emission standards
• AHRI Cered; ETL Listed
* Complete warranty details available from your local dealer or at www.daikincomfort.com. To receive the Lifeme Heat Exchanger Limited Warranty (good for as
long as you own your home), the 6-Year Unit Replacement Limited Warranty and 12-Year Parts Limited Warranty, online registraon must be completed within 60
days of installaon. Addional requirements for annual maintenance are required for the Unit Replacement Limited Warranty. Online registraon and some of the
addional requirements are not required in California or Quebec.
■ Cabinet Features
• Fully insulated heavy-gauge, zinc-coated steel
cabinet with UV-resistant powder-paint nish
• Compressor sound blanket
• Louvered metal panel condenser coil protecon
• Horizontal or downow applicaon
• Convenient access panels
• One roof curb ts all units
• Boom, 2” high base rails for easy handling
• All models t a standard-size pick-up truck
• When properly anchored, meets the 2001 Florida
Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)
SS-DP14DM www.daikincomfort.com 1/16
Supersedes 11/15
Page 2
Nomenclature
D P 14 D M 24 060 4 1 A A
1 2 3,4 5 6 7,8 9,10,11 12 13 14 15
Brand Engineering
DDaikin Minorrevision
ProductType Engineering
SEER Voltage
14Upto14SEER 1208/230Vsinglephase,60Hz
15Upto15SEER 3208/230V,3phase,60Hz
16Upto16SEER
UnitType 4R410A
GGas/Electric
DDualFuel NominalHeatInput
100 100MBTU/H
Configuration
MMultiposition
80MBTU/H
TonnageNominal
242tons 423½tons
484tons
363tons 605tons
120 120MBTU/H
Majorrevision
Refrigerant
2 www.daikincomfort.com SS-DP14DM SS -DP14DM w w w .daikinc om f ort.c om 3
Page 3
Product Specifications
DP14DM
2406041A*
Cooling
Cooling Capacity, BTU/hr 23,800 23,800 28,000 28,000 35,200 35,200
Sensible Capacity, BTU/hr 19,200 19,200 23,000 23,000 25,300 25,300
SEER / EER 14.5 / 12.0 14.5 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0
Decibels 76 76 76 76 76 76
AHRI #'S 8032971 7456905 8032972 7456906 8032973 8032973
Heating
Heang Capacity, BTU/hr (47°F / 17°F) 23,800 / 13,000 23,800 / 13,000 28,000 / 16,000 28,000 / 16,000 32,600 / 19,600 32,600 / 19,600
C.O.P. (47°F / 17°F) 3.6 / 2.3 3.6 / 2.3 3.6 / 2.3 3.6 / 2.3 3.6 / 2.4 3.6 / 2.4
HSPF 8.0 8.0 8.0 8.0 8.0 8.0
Gas Heating
High-Fire Input/Output (BTU/hr) 60,000 69,000 / 55,000 80,000 92,000 / 72,900 80,000 80,000
Low-Fire Input/Output (BTU/hr) 45,000 51,500 / 40,500 60,000 69,000 / 55,000 60,000 60,000
AFUE (%) 81 80 81 80 81 81
Temperature Rise Range (°F) 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65
# of Burners 3 3 4 4 4 4
Orice Size (Natural / LP) 43 / 55 43 / 55 43 / 55 43 / 55 43 / 55 43 / 55
Primary/Auxiliary Limit Seng (°F) 160/150 160/150 150/150 160/150 150/150 150/150
Roll-out Limit Seng (°F) 300 300 350 300 350 350
Evaporator Coil
Face Area (²) 4.3 4.3 4.3 4.3 4.3 4.3
# Rows / Fins per Inch 3 / 16 3 / 14 3 / 16 3 /14 4 / 14 4 / 14
Expansion Device (Orice Diameter in.) 0.06 0.06 0.07 0.07 0.07 0.07
Filter Size (²) / Drain Size (NPT) 2.7 / ¾ 2.7 / ¾ 4.2 / ¾ 4.2 / ¾ 4.2 / ¾ 4.2 / ¾
Refrigerant Charge - R-410A (oz) 120 120 108 108 124 124
Evaporator Motor
Wheel (D x W) 10” x 8” 10” x 8” 10” x 9” 10” x 9” 10” x 9” 10” x 9”
Type / # of Speeds EEM / 5 EEM / 5 EEM / 5 EEM / 5 EEM / 5 EEM / 5
Motor Horsepower / FLA ½ / 4.1 ½ / 4.1 ½ / 1.86 ½ / 1.86 ½ / 1.86 ½ / 1.86
Motor Speed Tap (Cooling and Heat Pump) T4 T4 T4 T4 T4 T4
RPM (Cooling and Heat Pump) 755 755 810 810 880 880
Nominal CFM (Cooling and Heat Pump) 850 850 1,030 1,030 1,050 1,050
Condenser Coil
Face Area (²) 12.2 12.2 12.2 12.2 12.2 12.2
# Rows / Fins per Inch 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16
Expansion Device (Orice Diameter in.) 0.05 0.05 0.05 0.05 0.06 0.06
Condenser Motor / Fan
Fan Diameter / # of Blades 22” / 3 22” / 3 22” / 3 22” / 3 22” / 3 22” / 3
Outdoor Nominal CFM 2,100 2,100 2,500 2,500 2,500 2,500
Motor Horsepower - RPM 1/6 - 815 1/6 - 815 1/4 - 837 1/4 - 837 1/4 - 837 1/4 - 837
Motor FLA 1.1 1.1 1.5 1.5 1.5 1.5
Compressor
Type / Stage Scroll / Single Scroll / Single Scroll / Single Scroll / Single Scroll / Single Scroll / Single
Run Load Amps / Locked Rotor Amps 12.8 / 58.3 12.8 / 58.3 14.1 / 73.0 14.1 / 73.0 16.6 / 79.0 15.4 / 83.9
Electrical Specifications
Voltage / Phase (60 Hz) 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1
Total Unit Amps 18.0 18.0 17.5 17.5 20.0 18.8
Minimum Circuit Ampacity 21.2 21.2 21 21 24.2 22.6
Maximum Overcurrent Protecon 30 30 35 35 40 40
Entrance Size Power Supply 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Entrance Size Control Voltage 7/8 7/8 7/8 7/8 7/8 7/8
Operating / Shipping Weight (lbs) 420 / 440 420 / 440 420 / 440 420 / 440 440 / 460 440 / 460
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
DP14DM
2407041C*
DP14DM
3008041A*
DP14DM
3009041C*
DP14DM
3608041AA
DP14DM
3608041AB
Page 4
Product SPecificatioNS
DP14DM
3609041C*
Cooling
Cooling Capacity, BTU/hr 34,000 41,500 41,500 45,500 45,500
Sensible Capacity, BTU/hr 27,200 32,000 32,000 34,600 34,600
SEER / EER 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0
Decibels 76 76 76 76 76
AHRI #'S 7456907 8032974 7456908 8032975 7456909
Heating
Heang Capacity, BTU/hr (47°F / 17°F) 34,000 / 19,800 40.000 / 24,000 40.000 / 24,000 44,000 / 24,600 44,000 / 24,600
C.O.P. (47°F / 17°F) 3.4 / 2.4 3.6 / 2.4 3.6 / 2.4 3.6 / 2.4 3.6 / 2.4
HSPF 8.0 8.0 8.0 8.0 8.0
Gas Heating
High-Fire Input/Output (BTU/hr) 92,000 / 72,900 100,000 115,000 / 92,200 100,000 115,000 / 92,200
Low-Fire Input/Output (BTU/hr) 69,000 / 55,000 75,000 86,000 / 69,000 75,000 86,000 / 69,000
AFUE (%) 80 81 80 81 80
Temperature Rise Range (°F) 45 - 75 35 - 65 45 - 75 35 - 65 45 - 75
# of Burners 4 5 5 5 5
Orice Size (Natural / LP) 43 / 55 43 / 55 43 / 55 43 / 55 43 / 55
Primary/Auxiliary Limit Seng (°F) 160/150 170/150 170/150 170/150 170/150
Roll-out Limit Seng (°F) 300 350 300 350 300
Evaporator Coil
Face Area (²) 4.3 5.7 5.7 5.7 5.7
# Rows / Fins per Inch 3 / 14 4 / 14 4 / 14 4 / 14 4 / 14
Expansion Device (Orice Diameter in.) 0.07 0.07 0.07 0.08 0.08
Filter Size (²) / Drain Size (NPT) 4.2 / ¾ 5.1 / ¾ 5.1 / ¾ 5.1 / ¾ 5.1 / ¾
Refrigerant Charge - R-410A (oz) 113 206 206 185 185
Evaporator Motor
Wheel (D x W) 10” x 9” 11” x 10” 11” x 10” 11” x 10” 11” x 10”
Type / # of Speeds EEM / 5 EEM / 5 EEM / 5 EEM / 5 EEM / 5
Motor Horsepower / FLA ½ / 1.86 ¾ / 2.87 ¾ / 2.87 ¾ / 2.87 ¾ / 2.87
Motor Speed Tap (Cooling and Heat Pump) T4 T4 T4 T4 T4
RPM (Cooling and Heat Pump) 880 880 880 950 950
Nominal CFM (Cooling and Heat Pump) 1,200 1,370 1,370 1,550 1,300
Condenser Coil
Face Area (²) 12.2 15.3 15.3 15.3 15.3
# Rows / Fins per Inch 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16
Expansion Device (Orice Diameter in.) 0.05 0.06 0.06 0.06 0.06
Condenser Motor / Fan
Fan Diameter / # of Blades 22” / 3 22” / 3 22” / 3 22” / 3 22” / 3
Outdoor Nominal CFM 2,500 3,150 3,150 3,200 3,200
Motor Horsepower - RPM 1/4 - 837 1/4 - 1094 1/4 - 1094 1/4 - 1094 1/4 - 1094
Motor FLA 1.5 1.4 1.4 1.4 1.4
Compressor
Type / Stage Scroll / Single Scroll / Single Scroll / Single Scroll / Single Scroll / Single
Run Load Amps / Locked Rotor Amps 14.1 / 77.0 17.9 / 112.0 17.9 / 112.0 19.8 / 109.0 19.8 / 109.0
Electrical Specifications
Voltage / Phase (60 Hz) 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1
Total Unit Amps 17.5 22.2 22.2 24.1 24.1
Minimum Circuit Ampacity 21 26.7 26.7 29.1 29.1
Maximum Overcurrent Protecon 35 40 40 45 45
Entrance Size Power Supply 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Entrance Size Control Voltage 7/8 7/8 7/8 7/8 7/8
Operating / Shipping Weight (lbs) 420/ 440 525 / 545 525 / 545 525 / 545 525 / 545
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
DP14DM
4210041A*
DP14DM
4211541C*
DP14DM
4810041A*
DP14DM
4811541C*
4 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 5
Page 5
exPaNded cooliNg data — dP14dm24***41**
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 20.1 20.8 22.8 - 19.1 19.8 21.7 - 17.7 18.3 20.1 -
23 21 17 12 23 21 18 12 23 21 17 12 21 20 16 11
6.4 6.6 - 6.7 6.9 7.1 - 7.2 7.4 7.6 - 7.7 7.9 8.1 - 8.2 8.4 8.6 - 8.6 8.8 9.1 -
6.6 6.8 7.0 6.9 7.1 7.3 7.6 7.5 7.7 7.9 8.2 8.0 8.2 8.4 8.7 8.5 8.7 8.9 9.3 8.9 9.2 9.4 9.8
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 19 16 12 - 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 18 15 12 -
S/T 0.82 0.68 0.47 - 0.85 0.71 0.49 - 0.87 0.73 0.50 - 0.90 0.75 0.52 - 0.93 0.78 0.54 - 0.94 0.78 0.54 -
MBh 24.1 25.0 27.4 - 23.5 24.4 26.7 - 23.0 23.8 26.1 - 22.4 23.2 25.5 - 21.3 22.1 24.2 - 19.7 20.5 22.4 -
kW 1.56 1.59 1.64 - 1.68 1.72 1.78 - 1.79 1.83 1.89 - 1.89 1.93 2.00 - 1.97 2.02 2.08 - 2.04 2.09 2.16 -
955
HI PR 232 250 264 - 260 280 296 - 296 319 336 - 337 363 383 - 379 408 431 - 419 451 476 -
Amps 6.5 6.6 6.8 - 6.9 7.1 7.3 - 7.5 7.7 7.9 - 8.0 8.2 8.4 - 8.5 8.7 8.9 - 8.9 9.2 9.4 -
LO PR 111 118 129 - 117 125 136 - 122 130 141 - 128 136 149 - 134 143 156 - 139 148 161 -
∆T 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 19 16 12 -
S/T 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.83 0.69 0.48 - 0.86 0.71 0.49 - 0.89 0.74 0.51 - 0.90 0.75 0.52 -
MBh 23.4 24.3 26.6 - 22.9 23.7 26.0 - 22.3 23.1 25.3 - 21.8 22.6 24.7 - 20.7 21.4 23.5 - 19.2 19.9 21.8 -
kW 1.54 1.58 1.63 - 1.67 1.71 1.76 - 1.78 1.82 1.88 - 1.87 1.91 1.98 - 1.95 2.00 2.07 - 2.02 2.07 2.14 -
850
70
HI PR 230 247 261 - 258 277 293 - 293 315 333 - 334 359 379 - 376 404 427 - 415 446 471 -
Amps 6.4 6.5 6.7 - 6.9 7.0 7.3 - 7.4 7.6 7.8 - 7.9 8.1 8.4 - 8.4 8.6 8.9 - 8.9 9.1 9.4 -
LO PR 110 117 128 - 116 123 135 - 121 128 140 - 127 135 147 - 133 141 154 - 137 146 159 -
MBh 21.6 22.4 24.5 - 21.1 21.9 24.0 - 20.6 21.3 23.4
∆T 20 17 13 - 20 18 13 - 20 18 13 - 20 18 13 - 20 17 13 - 19 16 12 -
S/T 0.75 0.63 0.43 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.82 0.69 0.48 - 0.86 0.71 0.50 - 0.86 0.72 0.50 -
kW 1.51 1.54 1.59 - 1.63 1.66 1.72 - 1.73 1.77 1.83 - 1.82 1.87 1.93 - 1.90 1.95 2.01 - 1.97 2.02 2.09 -
HI PR 223 240 253 - 250 269 284 - 284 306 323 - 324 348 368 - 364 392 414 - 402 433 457 -
Amps 6.2
LO PR 107 113 124 - 113 120 131 - 117 124 136 - 123 131 143 - 129 137 150 - 133 142 155 -
745
MBh 24.5 25.2 27.3 29.3 23.9 24.7 26.7 28.6 23.4 24.1 26.1 28.0 22.8 23.5 25.4 27.3 21.7 22.3 24.1 25.9 20.1 20.7 22.4 24.0
S/T 0.93 0.83 0.63 0.40 0.96 0.86 0.65 0.42 0.99 0.88 0.67 0.43 1.00 0.91 0.69 0.44 1.00 0.95 0.72 0.46 1.00 0.95 0.72 0.46
∆T 22 20 17 11 22 20 17 12 22 20 17 12 22 21 17 12 21 20 17 11 19 19 16 11
kW 1.57 1.61 1.66 1.71 1.70 1.73 1.79 1.85 1.81 1.85 1.91 1.98 1.90 1.95 2.01 2.08 1.99 2.03 2.10 2.18 2.06 2.11 2.18 2.26
955
Amps 6.5 6.7 6.9 7.1 7.0 7.2 7.4 7.6 7.6 7.7 8.0 8.3 8.1 8.2 8.5 8.8 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.9
HI PR 234 252 266 278 263 283 299 312 299 322 340 354 341 366 387 404 383 412 435 454 423 456 481 502
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 168 140 149 163 173
MBh 23.8 24.5 26.5 28.5 23.2 23.9 25.9 27.8 22.7 23.4 25.3 27.1 22.1 22.8 24.7 26.5 21.0 21.7 23.4 25.2 19.5 20.1 21.7 23.3
S/T 0.89 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.94 0.84 0.64 0.41 0.97 0.87 0.66 0.42 1.00 0.90 0.68 0.44 1.00 0.91 0.69 0.44
∆T 23 21 17 12 23 21 17 12
kW 1.56 1.59 1.64 1.70 1.68 1.72 1.78 1.84 1.79 1.83 1.89 1.96 1.89 1.93 2.00 2.07 1.97 2.02 2.08 2.16 2.04 2.09 2.16 2.24
850
75
Amps 6.5
HI PR 232 250 264 275 260 280 296 309 296 319 336 351 337 363 383 400 379 408 431 450 419 451 476 497
LO PR 111 118 129 137 117 125 136 145 122 130 141 151 128 136 149 158 134 143 156 166 139 148 161 172
MBh 22.0 22.6 24.5 26.3 21.5 22.1 23.9 25.7 20.9 21.6 23.3 25.1 20.4 21.0 22.8 24.4 19.4 20.0 21.6 23.2 18.0 18.5 20.0 21.5
S/T 0.85 0.76 0.58 0.37 0.89 0.79 0.60 0.39 0.91 0.81 0.61 0.40 0.94 0.84 0.63 0.41 0.97 0.87 0.66 0.42 0.98 0.88 0.66 0.43
∆T 23 21 17 12 23 22 18 12 23 22 18 12 24 22 18 12 23 21 18 12 22 20 16 11
kW 1.52 1.55 1.60 1.66 1.64 1.68 1.73 1.79 1.75 1.79 1.85 1.91 1.84 1.88 1.95 2.01 1.92 1.96 2.03 2.10 1.99 2.03 2.10 2.18
745
Amps 6.3 6.4 6.6 6.9 6.8 6.9 7.1 7.4 7.3 7.5 7.7 8.0 7.8 8.0 8.2 8.5 8.2 8.4 8.7 9.0 8.7 8.9 9.2 9.5
HI PR 225 242 256 267 253 272 287 299 287 309 326 340 327 352 372 388 368 396 418 436 407 438 462 482
LO PR 108 114 125 133 114 121 132 141 118 126 137 146 124 132 144 154 130 138 151 161 135 143 156 166
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 6
exPaNded cooliNg data — dP14dm24***41** (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
24.9 20.8 21.3 22.7 24.3 19.8 20.2 21.6 23.1 18.3 18.7 20.0 21.4
6.5 6.7 6.9 6.8 7.0 7.2 7.4 7.4 7.5 7.8 8.0 7.8 8.0 8.3 8.6 8.3 8.5 8.8 9.1 8.8 9.0 9.3 9.6
25 26 26 22 25 25 26 22 24 24 25 22 22 22 23 21
6.7 6.9 7.2 7.1 7.2 7.4 7.7 7.6 7.8 8.0 8.3 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.4 9.1 9.3 9.6 10.0
MBh 22.4 22.8 24.4 26.1 21.8 22.3 23.8 25.5 21.3 21.8 23.3
S/T 0.94 0.88 0.72 0.53 0.97 0.91 0.74 0.55 1.00 0.93 0.76 0.57 1.03 0.96 0.78 0.59 1.07 1.00 0.81 0.61 1.08 1.01 0.82 0.61
∆T 26 25 22 17 26 25 22 17 26 25 22 17 26 25 22 18 26 25 22 17 24 23 20 16
kW 1.53 1.57 1.62 1.67 1.65 1.69 1.75 1.81 1.76 1.80 1.86 1.92 1.86 1.90 1.96 2.03 1.94 1.98 2.05 2.12 2.01 2.05 2.12 2.20
745
Amps 6.3
HI PR 227 245 258 269 255 274 290 302 290 312 330 344 330 356 375 392 372 400 422 441 411 442 467 487
LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 163 136 145 158 168
MBh 25.4 25.9 27.1 28.9 24.8 25.3 26.5 28.2 24.2 24.7 25.8 27.6 23.6 24.1 25.2 26.9 22.4 22.9 24.0 25.6 20.8 21.2 22.2 23.7
S/T 1.00 1.00 0.93 0.75 1.00 1.00 0.96 0.78 1.00 1.00 0.99 0.80 1.00 1.00 1.00 0.83 1.00 1.00 1.00 0.86 1.00 1.00 1.00 0.87
∆T 24 25 24 21 24 24 25 21 23 24 25 21 23 23 24 21 22 22 23 21 20 20 21 20
kW 1.60 1.63 1.69 1.74 1.72 1.76 1.82 1.88 1.84 1.88 1.94 2.01 1.94 1.98 2.05 2.12 2.02 2.07 2.14 2.21 2.10 2.14 2.22 2.30
955
Amps 6.6 6.8 7.0 7.2 7.1 7.3 7.5 7.8 7.7 7.9 8.1 8.4 8.2 8.4 8.6 9.0 8.7 8.9 9.2 9.5 9.2 9.4 9.7 10.1
HI PR 239 257 272 283 268 289 305 318 305 328 347 362 347 374 395 412 391 421 444 463 432 465 491 512
LO PR 114 122 133 141 121 128 140 149 126 134 146 155 132 140 153 163 138 147 160 171 143 152 166 177
MBh 24.6 25.1 26.3 28.1 24.1 24.5 25.7 27.4 23.5 24.0 25.1 26.8 22.9 23.4 24.5 26.1 21.8 22.2 23.3 24.8 20.2 20.6 21.5 23.0
S/T 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.94 0.77 1.00 1.00 0.97 0.79 1.00 1.00 1.00 0.82 1.00 1.00 1.00 0.83
∆T 27 27 25 22 26 27 26 22
kW 1.58 1.62 1.67 1.73 1.71 1.75 1.81 1.87 1.82 1.86 1.93 1.99 1.92 1.97 2.03 2.10 2.01 2.05 2.12 2.20 2.08 2.13 2.20 2.28
850
85
Amps 6.6
HI PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 416 440 459 428 460 486 507
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 131 139 152 161 137 146 159 169 141 151 164 175
MBh 22.8 23.2 24.3 25.9 22.2 22.7 23.7 25.3 21.7 22.1 23.2 24.7 21.2 21.6 22.6 24.1 20.1 20.5 21.5 22.9 18.6 19.0 19.9 21.2
S/T 0.98 0.95 0.86 0.69 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.79 1.00 1.00 0.98 0.80
∆T 28 27 26 22 27 27 26 22 27 27 26 22 26 27 26 23 25 25 26 22 23 23 24 21
kW 1.54 1.58 1.63 1.68 1.67 1.70 1.76 1.82 1.78 1.82 1.88 1.94 1.87 1.91 1.98 2.05 1.95 2.00 2.07 2.14 2.02 2.07 2.14 2.22
745
Amps 6.4 6.5 6.7 7.0 6.9 7.0 7.3 7.5 7.4 7.6 7.8 8.1 7.9 8.1 8.3 8.6 8.4 8.6 8.9 9.2 8.9 9.1 9.4 9.7
HI PR 230 247 261 272 258 277 293 305 293 315 333 347 334 359 379 395 375 404 427 445 415 446 471 492
LO PR 110 117 127 136 116 123 135 143 121 128 140 149 127 135 147 157 133 141 154 164 137 146 159 170
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 25.0 25.5 27.2 29.1 24.4 24.9 26.6 28.4 23.8 24.3 26.0 27.8 23.2 23.7 25.3 27.1 22.1 22.5 24.1 25.7 20.4 20.9 22.3 23.8
S/T 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.83 0.62 1.00 1.00 0.85 0.64 1.00 1.00 0.89 0.66 1.00 1.00 0.89 0.67
∆T 24 23 20 16 23 24 21 16 23 23 21 17 22 23 21 17 21 22 21 16 20 20 19 15
kW 1.58 1.62 1.67 1.73 1.71 1.75 1.81 1.87 1.82 1.86 1.93 1.99 1.92 1.97 2.03 2.10 2.01 2.05 2.12 2.20 2.08 2.13 2.20 2.28
955
Amps 6.6 6.7 6.9 7.2 7.1 7.2 7.4 7.7 7.6 7.8 8.0 8.3 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.4 9.1 9.3 9.6 10.0
HI PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 416 440 459 428 460 486 507
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 131 139 152 161 137 146 159 169 141 151 164 175
MBh 24.2 24.8 26.4 28.3 23.7 24.2 25.8 27.6 23.1 23.6 25.2 27.0 22.5 23.0 24.6 26.3 21.4 21.9 23.4 25.0 19.8 20.3 21.6 23.1
S/T 0.97 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 0.97 0.79 0.59 1.00 1.00 0.81 0.61 1.00 1.00 0.84 0.63 1.00 1.00 0.85 0.64
∆T 25 24 21 17 26 25 21 17 25 25 22 17 24 25 22 17 23 24 21 17 21 22 20 16
kW 1.57 1.61 1.66 1.71 1.70 1.73 1.79 1.85 1.81 1.85 1.91 1.98 1.90 1.95 2.01 2.08 1.99 2.03 2.10 2.18 2.06 2.11 2.18 2.26
850
80
Amps 6.5 6.7 6.9 7.1 7.0 7.2 7.4 7.6 7.6 7.7 8.0 8.3 8.1 8.2 8.5 8.8 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.9
HI PR 234 252 266 278 263 283 299 312 299 322 340 354 341 367 387 404 383 412 435 454 423 456 481 502
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 168 140 149 163 173
6 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 7
Page 7
exPaNded cooliNg data — dP14dm30***41**
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 23.3 24.2 26.5 - 22.2 23.0 25.2 - 20.5 21.3 23.3 -
22 20 17 12 22 20 17 12 22 20 17 11 20 19 15 11
8.1 8.4 - 8.5 8.7 8.9 - 9.1 9.3 9.6 - 9.6 9.8 10.1 - 10.2 10.4 10.7 - 10.7 10.9 11.2 -
8.4 8.6 8.9 8.8 8.9 9.2 9.5 9.4 9.6 9.9 10.2 10.0 10.2 10.5 10.8 10.5 10.7 11.0 11.4 11.0 11.3 11.6 12.0
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
S/T 0.82 0.69 0.48 - 0.85 0.71 0.49 - 0.88 0.73 0.51 - 0.90 0.76 0.52 - 0.94 0.78 0.54 - 0.95 0.79 0.55 -
MBh 28.0 29.0 31.8 - 27.3 28.3 31.0 - 26.7 27.6 30.3 - 26.0 27.0 29.6 - 24.7 25.6 28.1 - 22.9 23.7 26.0 -
kW 1.87 1.90 1.96 - 2.01 2.05 2.11 - 2.13 2.18 2.25 - 2.24 2.29 2.37 - 2.34 2.39 2.47 - 2.42 2.47 2.55 -
1170
HI PR 225 242 256 - 253 272 287 - 287 309 326 - 327 352 372 - 368 396 418 - 407 438 462 -
Amps 8.2 8.4 8.6 - 8.8 8.9 9.2 - 9.4 9.6 9.9 - 10.0 10.2 10.5 - 10.5 10.7 11.0 - 11.0 11.3 11.6 -
LO PR 111 118 129 - 117 124 136 - 122 129 141 - 128 136 148 - 134 142 155 - 138 147 161 -
∆T 19 16 12 - 19 17 13 - 19 17 13 - 19 17 13 - 19 16 12 - 18 15 12 -
S/T 0.79 0.66 0.45 - 0.81 0.68 0.47 - 0.84 0.70 0.48 - 0.86 0.72 0.50 - 0.89 0.75 0.52 - 0.90 0.75 0.52 -
MBh 27.2 28.2 30.8 - 26.5 27.5 30.1 - 25.9 26.8 29.4 - 25.3 26.2 28.7 - 24.0 24.9 27.3 - 22.2 23.0 25.2 -
kW 1.85 1.89 1.95 - 1.99 2.03 2.10 - 2.12 2.16 2.23 - 2.22 2.27 2.35 - 2.32 2.37 2.45 - 2.40 2.45 2.53 -
1040
70
HI PR 223 240 253 - 250 269 284 - 284 306 323 - 324 349 368 - 365 392 414 - 403 433 458 -
Amps 8.2 8.3 8.5 - 8.7 8.9 9.1 - 9.3 9.5 9.8 - 9.9 10.1 10.4 - 10.4 10.6 10.9 - 11.0 11.2 11.5 -
LO PR 110 117 127 - 116 123 135 - 120 128 140 - 126 135 147 - 133 141 154 - 137 146 159 -
MBh 25.1 26.0 28.5 - 24.5 25.4 27.8 - 23.9 24.8 27.1
∆T 19 17 13 - 19 17 13 - 19 17 13 - 20 17 13 - 19 17 13 - 18 16 12 -
S/T 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.81 0.67 0.47 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -
kW 1.81 1.85 1.90 - 1.94 1.98 2.05 - 2.06 2.11 2.18 - 2.17 2.22 2.29 - 2.26 2.31 2.38 - 2.34 2.39 2.47 -
HI PR 216 233 246 - 243 261 276 - 276 297 314 - 314 338 357 - 354 380 402 - 391 420 444 -
Amps 8.0
LO PR 106 113 124 - 112 120 131 - 117 124 136 - 123 131 142 - 129 137 149 - 133 141 154 -
910
MBh 28.4 29.3 31.7 34.0 27.8 28.6 31.0 33.2 27.1 27.9 30.2 32.4 26.5 27.2 29.5 31.7 25.1 25.9 28.0 30.1 23.3 24.0 26.0 27.9
S/T 0.94 0.84 0.63 0.41 0.97 0.87 0.66 0.42 1.00 0.89 0.67 0.43 1.00 0.92 0.70 0.45 1.00 0.95 0.72 0.46 1.00 0.96 0.73 0.47
∆T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 20 19 16 11 18 18 15 10
kW 1.88 1.92 1.98 2.04 2.02 2.07 2.13 2.20 2.15 2.20 2.27 2.34 2.26 2.31 2.39 2.47 2.36 2.41 2.49 2.57 2.44 2.49 2.57 2.66
1170
Amps 8.3 8.4 8.7 8.9 8.8 9.0 9.3 9.6 9.5 9.7 9.9 10.3 10.0 10.2 10.5 10.9 10.6 10.8 11.1 11.5 11.1 11.4 11.7 12.1
HI PR 227 245 258 270 255 275 290 302 290 312 330 344 331 356 376 392 372 400 423 441 411 442 467 487
LO PR 112 119 130 138 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 167 140 149 162 173
MBh 27.6 28.4 30.8 33.0 27.0 27.8 30.1 32.3 26.3 27.1 29.3 31.5 25.7 26.5 28.6 30.7 24.4 25.1 27.2 29.2 22.6 23.3 25.2 27.0
S/T 0.89 0.80 0.60 0.39 0.93 0.83 0.63 0.40 0.95 0.85 0.64 0.41 0.98 0.88 0.66 0.43 1.00 0.91 0.69 0.44 1.00 0.92 0.69 0.45
∆T 22 20 16 11 22 20 17 12
kW 1.87 1.90 1.96 2.03 2.01 2.05 2.12 2.18 2.13 2.18 2.25 2.32 2.24 2.29 2.37 2.44 2.34 2.39 2.47 2.55 2.42 2.47 2.55 2.64
1040
75
Amps 8.2
HI PR 225 242 256 267 253 272 287 299 287 309 327 341 327 352 372 388 368 396 418 436 407 438 462 482
LO PR 111 118 129 137 117 125 136 145 122 129 141 150 128 136 148 158 134 142 156 166 139 147 161 171
MBh 25.5 26.2 28.4 30.5 24.9 25.6 27.8 29.8 24.3 25.0 27.1 29.1 23.7 24.4 26.4 28.4 22.5 23.2 25.1 26.9 20.9 21.5 23.3 25.0
S/T 0.86 0.77 0.58 0.38 0.89 0.80 0.60 0.39 0.92 0.82 0.62 0.40 0.94 0.85 0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.88 0.67 0.43
∆T 22 20 17 12 22 21 17 12 22 21 17 12 23 21 17 12 22 21 17 12 21 19 16 11
kW 1.82 1.86 1.92 1.98 1.96 2.00 2.06 2.13 2.08 2.13 2.19 2.26 2.19 2.24 2.31 2.38 2.28 2.33 2.40 2.48 2.36 2.41 2.49 2.57
910
Amps 8.0 8.2 8.4 8.7 8.6 8.7 9.0 9.3 9.2 9.4 9.6 9.9 9.7 9.9 10.2 10.5 10.3 10.5 10.8 11.1 10.8 11.0 11.3 11.7
HI PR 218 235 248 259 245 264 279 291 279 300 317 330 317 342 361 376 357 384 406 423 395 425 448 468
LO PR 107 114 125 133 114 121 132 140 118 126 137 146 124 132 144 153 130 138 151 161 134 143 156 166
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 8
exPaNded cooliNg data — dP14dm30***41** (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
28.9 24.1 24.7 26.4 28.2 22.9 23.4 25.0 26.8 21.2 21.7 23.2 24.8
8.3 8.5 8.7 8.6 8.8 9.1 9.3 9.3 9.4 9.7 10.0 9.8 10.0 10.3 10.6 10.3 10.6 10.9 11.2 10.9 11.1 11.4 11.8
24 25 24 21 24 24 25 21 22 23 24 21 21 21 22 20
8.5 8.7 9.0 8.9 9.1 9.3 9.6 9.6 9.7 10.0 10.4 10.1 10.3 10.6 11.0 10.7 10.9 11.2 11.6 11.2 11.5 11.8 12.2
MBh 25.9 26.5 28.3 30.3 25.3 25.9 27.7 29.6 24.7 25.3 27.0
S/T 0.94 0.89 0.72 0.54 0.98 0.92 0.75 0.56 1.00 0.94 0.77 0.57 1.04 0.97 0.79 0.59 1.08 1.01 0.82 0.61 1.00 1.02 0.83 0.62
∆T 25 24 21 16 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 21 22 19 15
kW 1.84 1.87 1.93 1.99 1.98 2.02 2.08 2.15 2.10 2.14 2.21 2.28 2.21 2.25 2.33 2.40 2.30 2.35 2.42 2.51 2.38 2.43 2.51 2.59
910
Amps 8.1
HI PR 221 237 251 262 248 266 281 293 282 303 320 334 321 345 364 380 361 388 410 428 399 429 453 472
LO PR 109 115 126 134 115 122 133 142 119 127 138 147 125 133 145 155 131 140 152 162 136 144 158 168
MBh 29.5 30.0 31.5 33.6 28.8 29.3 30.7 32.8 28.1 28.6 30.0 32.0 27.4 27.9 29.3 31.2 26.0 26.5 27.8 29.7 24.1 24.6 25.7 27.5
S/T 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.79 1.00 1.00 1.00 0.81 1.00 1.00 1.00 0.83 1.00 1.00 1.00 0.87 1.00 1.00 1.00 0.87
∆T 23 24 23 20 23 23 23 20 22 23 23 20 22 22 23 20 20 21 22 20 19 19 20 19
kW 1.91 1.95 2.01 2.08 2.06 2.10 2.17 2.24 2.19 2.23 2.30 2.38 2.30 2.35 2.43 2.51 2.40 2.45 2.53 2.61 2.48 2.53 2.62 2.71
1170
Amps 8.4 8.6 8.8 9.1 9.0 9.2 9.4 9.7 9.6 9.8 10.1 10.4 10.2 10.4 10.7 11.1 10.8 11.0 11.3 11.7 11.3 11.6 11.9 12.3
HI PR 232 250 264 275 260 280 296 309 296 319 336 351 337 363 383 400 379 408 431 450 419 451 476 497
LO PR 114 121 133 141 121 128 140 149 125 133 146 155 132 140 153 163 138 147 160 171 143 152 166 177
MBh 28.6 29.2 30.5 32.6 27.9 28.5 29.8 31.8 27.3 27.8 29.1 31.1 26.6 27.1 28.4 30.3 25.3 25.8 27.0 28.8 23.4 23.9 25.0 26.7
S/T 1.00 0.99 0.89 0.73 1.00 1.00 0.93 0.75 1.00 1.00 0.95 0.77 1.00 1.00 0.98 0.80 1.00 1.00 1.00 0.83 1.00 1.00 1.00 0.83
∆T 25 26 24 21 25 25 24 21
kW 1.90 1.94 2.00 2.06 2.04 2.08 2.15 2.22 2.17 2.21 2.29 2.36 2.28 2.33 2.41 2.49 2.38 2.43 2.51 2.59 2.46 2.51 2.60 2.68
1040
85
Amps 8.3
HI PR 230 247 261 272 258 277 293 306 293 316 333 347 334 359 379 396 376 404 427 445 415 447 472 492
LO PR 113 120 131 140 119 127 139 148 124 132 144 154 130 139 151 161 137 145 159 169 141 150 164 175
MBh 26.4 26.9 28.2 30.1 25.8 26.3 27.5 29.4 25.2 25.7 26.9 28.7 24.6 25.0 26.2 28.0 23.3 23.8 24.9 26.6 21.6 22.0 23.1 24.6
S/T 0.99 0.96 0.86 0.70 1.00 0.99 0.89 0.73 1.00 1.00 0.92 0.74 1.00 1.00 0.95 0.77 1.00 1.00 0.98 0.80 1.00 1.00 0.99 0.80
∆T 26 26 25 21 26 26 25 22 25 26 25 22 25 25 25 22 24 24 25 21 22 22 23 20
kW 1.85 1.89 1.95 2.01 1.99 2.03 2.10 2.17 2.11 2.16 2.23 2.30 2.22 2.27 2.35 2.42 2.32 2.37 2.45 2.53 2.40 2.45 2.53 2.62
910
Amps 8.2 8.3 8.5 8.8 8.7 8.9 9.1 9.4 9.3 9.5 9.8 10.1 9.9 10.1 10.4 10.7 10.4 10.6 10.9 11.3 10.9 11.2 11.5 11.9
HI PR 223 240 253 264 250 269 284 296 284 306 323 337 324 349 368 384 364 392 414 432 403 433 458 477
LO PR 110 117 127 136 116 123 135 143 120 128 140 149 126 135 147 156 133 141 154 164 137 146 159 170
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 29.0 29.6 31.6 33.8 28.3 28.9 30.9 33.0 27.6 28.2 30.1 32.2 26.9 27.5 29.4 31.4 25.6 26.1 27.9 29.9 23.7 24.2 25.9 27.7
S/T 1.00 0.96 0.78 0.59 1.00 1.00 0.81 0.61 1.00 1.00 0.83 0.62 1.00 1.00 0.86 0.64 1.00 1.00 0.89 0.67 1.00 1.00 0.90 0.67
∆T 23 22 19 16 22 23 20 16 22 22 20 16 21 22 20 16 20 21 20 16 19 19 18 15
kW 1.90 1.94 2.00 2.06 2.04 2.08 2.15 2.22 2.17 2.21 2.29 2.36 2.28 2.33 2.41 2.49 2.38 2.43 2.51 2.59 2.46 2.51 2.60 2.68
1170
Amps 8.3 8.5 8.7 9.0 8.9 9.1 9.3 9.6 9.6 9.7 10.0 10.4 10.1 10.3 10.6 11.0 10.7 10.9 11.2 11.6 11.2 11.5 11.8 12.2
HI PR 230 247 261 272 258 277 293 306 293 316 333 347 334 359 379 396 376 404 427 445 415 447 472 492
LO PR 113 120 131 140 119 127 139 148 124 132 144 154 130 139 151 161 137 145 159 169 141 150 164 175
MBh 28.1 28.7 30.7 32.8 27.5 28.1 30.0 32.0 26.8 27.4 29.3 31.3 26.2 26.7 28.5 30.5 24.8 25.4 27.1 29.0 23.0 23.5 25.1 26.9
S/T 0.98 0.92 0.75 0.56 1.00 0.95 0.78 0.58 1.00 0.98 0.79 0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.85 0.64 1.00 1.00 0.86 0.64
∆T 24 23 20 16 24 24 21 16 24 24 21 16 23 24 21 17 22 22 20 16 20 21 19 15
kW 1.88 1.92 1.98 2.04 2.02 2.07 2.13 2.20 2.15 2.20 2.27 2.34 2.26 2.31 2.39 2.47 2.36 2.41 2.49 2.57 2.44 2.49 2.57 2.66
1040
80
Amps 8.3 8.4 8.7 8.9 8.8 9.0 9.3 9.6 9.5 9.7 9.9 10.3 10.0 10.2 10.5 10.9 10.6 10.8 11.1 11.5 11.1 11.4 11.7 12.1
HI PR 227 245 258 270 255 275 290 303 290 312 330 344 331 356 376 392 372 400 423 441 411 442 467 487
LO PR 112 119 130 138 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 167 140 149 162 173
8 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 9
Page 9
exPaNded cooliNg data — dP14dm36***41**
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 29.0 30.0 32.9 - 27.5 28.5 31.3 - 25.5 26.4 29.0 -
24 22 18 13 24 22 18 13 24 22 18 13 22 21 17 12
10.2 10.5 - 10.7 10.9 11.2 - 11.5 11.7 12.1 - 12.2 12.4 12.8 - 12.9 13.1 13.5 - 13.5 13.8 14.3 -
10.5 10.8 11.2 11.0 11.3 11.6 12.0 11.9 12.1 12.5 12.9 12.6 12.9 13.2 13.7 13.3 13.6 14.0 14.5 14.0 14.3 14.7 15.3
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 20 17 13 - 20 17 13 - 20 17 13 - 20 18 13 - 20 17 13 - 19 16 12 -
S/T 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.77 0.64 0.45 - 0.80 0.66 0.46 - 0.83 0.69 0.48 - 0.83 0.70 0.48 -
MBh 34.8 36.0 39.5 - 34.0 35.2 38.6 - 33.1 34.4 37.6 - 32.3 33.5 36.7 - 30.7 31.8 34.9 - 28.5 29.5 32.3 -
kW 2.32 2.37 2.45 - 2.51 2.56 2.65 - 2.67 2.73 2.82 - 2.81 2.88 2.97 - 2.93 3.00 3.10 - 3.04 3.11 3.21 -
1170
HI PR 240 258 272 - 269 289 305 - 306 329 347 - 348 375 396 - 392 422 445 - 433 466 492 -
Amps 10.3 10.5 10.8 - 11.0 11.3 11.6 - 11.9 12.1 12.5 - 12.6 12.8 13.2 - 13.3 13.6 14.0 - 14.0 14.3 14.7 -
LO PR 108 115 126 - 115 122 133 - 119 127 138 - 125 133 145 - 131 139 152 - 136 144 157 -
∆T 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 21 18 14 - 19 17 13 -
S/T 0.69 0.58 0.40 - 0.72 0.60 0.41 - 0.74 0.61 0.43 - 0.76 0.63 0.44 - 0.79 0.66 0.46 - 0.79 0.66 0.46 -
MBh 33.8 35.0 38.3 - 33.0 34.2 37.4 - 32.2 33.4 36.5 - 31.4 32.5 35.7 - 29.8 30.9 33.9 - 27.6 28.6 31.4 -
kW 2.30 2.35 2.43 - 2.49 2.54 2.62 - 2.65 2.71 2.80 - 2.79 2.85 2.95 - 2.91 2.97 3.08 - 3.01 3.08 3.19 -
1040
70
HI PR 237 255 270 - 266 286 302 - 303 326 344 - 345 371 392 - 388 417 441 - 429 461 487 -
Amps 10.2 10.4 10.7 - 10.9 11.2 11.5 - 11.8 12.0 12.4 - 12.5 12.7 13.1 - 13.2 13.5 13.9 - 13.9 14.2 14.6 -
LO PR 107 114 125 - 113 121 132 - 118 125 137 - 124 132 144 - 130 138 151 - 134 143 156 -
MBh 31.2 32.3 35.4 - 30.4 31.5 34.6 - 29.7 30.8 33.7
∆T 21 18 14 - 21 18 14 - 21 18 14 - 21 19 14 - 21 18 14 - 20 17 13 -
S/T 0.67 0.56 0.39 - 0.69 0.58 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.77 0.64 0.44 -
kW 2.25 2.30 2.37 - 2.42 2.48 2.56 - 2.58 2.64 2.72 - 2.72 2.78 2.87 - 2.83 2.90 3.00 - 2.93 3.00 3.10 -
HI PR 230 248 261 - 258 278 293 - 294 316 334 - 334 360 380 - 376 405 428 - 416 447 472 -
Amps 10.0
LO PR 104 111 121 - 110 117 128 - 114 122 133 - 120 128 139 - 126 134 146 - 130 138 151 -
910
MBh 35.4 36.4 39.4 42.3 34.5 35.6 38.5 41.3 33.7 34.7 37.6 40.3 32.9 33.9 36.7 39.3 31.2 32.2 34.8 37.4 28.9 29.8 32.3 34.6
S/T 0.82 0.74 0.56 0.36 0.85 0.76 0.58 0.37 0.88 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.94 0.84 0.64 0.41 0.95 0.85 0.64 0.41
∆T 23 21 17 12 23 21 18 12 23 21 18 12 23 22 18 12 23 21 17 12 22 20 16 11
kW 2.34 2.39 2.47 2.55 2.53 2.58 2.67 2.76 2.69 2.75 2.84 2.94 2.84 2.90 3.00 3.10 2.96 3.03 3.13 3.24 3.06 3.14 3.24 3.35
1170
Amps 10.4 10.6 10.9 11.3 11.1 11.4 11.7 12.1 12.0 12.2 12.6 13.0 12.7 13.0 13.3 13.8 13.4 13.7 14.1 14.6 14.1 14.4 14.9 15.4
HI PR 242 260 275 287 272 292 309 322 309 332 351 366 352 379 400 417 396 426 450 469 437 471 497 518
LO PR 109 116 127 135 116 123 134 143 120 128 140 149 126 134 147 156 132 141 154 164 137 146 159 169
MBh 34.3 35.3 38.3 41.1 33.5 34.5 37.4 40.1 32.7 33.7 36.5 39.1 31.9 32.9 35.6 38.2 30.3 31.2 33.8 36.3 28.1 28.9 31.3 33.6
S/T 0.79 0.70 0.53 0.34 0.82 0.73 0.55 0.36 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.38 0.90 0.80 0.61 0.39 0.90 0.81 0.61 0.39
∆T 24 22 18 12 24 22 18 13
kW 2.32 2.37 2.45 2.53 2.51 2.56 2.65 2.74 2.67 2.73 2.82 2.92 2.81 2.88 2.97 3.07 2.93 3.00 3.10 3.21 3.04 3.11 3.21 3.33
1040
75
Amps 10.3
HI PR 240 258 272 284 269 289 306 319 306 329 348 362 348 375 396 413 392 422 445 464 433 466 492 513
LO PR 108 115 126 134 115 122 133 142 119 127 138 147 125 133 145 155 131 139 152 162 136 144 157 168
MBh 31.7 32.6 35.3 37.9 30.9 31.9 34.5 37.0 30.2 31.1 33.7 36.1 29.5 30.3 32.8 35.3 28.0 28.8 31.2 33.5 25.9 26.7 28.9 31.0
S/T 0.76 0.68 0.51 0.33 0.79 0.70 0.53 0.34 0.81 0.72 0.55 0.35 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.38 0.87 0.78 0.59 0.38
∆T 24 22 18 13 25 23 19 13 25 23 19 13 25 23 19 13 24 22 18 13 23 21 17 12
kW 2.27 2.32 2.39 2.47 2.44 2.50 2.58 2.67 2.60 2.66 2.75 2.84 2.74 2.80 2.90 2.99 2.86 2.92 3.02 3.13 2.96 3.03 3.13 3.24
910
Amps 10.1 10.3 10.6 10.9 10.8 11.0 11.3 11.7 11.6 11.8 12.2 12.6 12.3 12.5 12.9 13.3 13.0 13.2 13.6 14.1 13.7 14.0 14.4 14.9
HI PR 232 250 264 276 261 281 296 309 297 319 337 352 338 364 384 400 380 409 432 450 420 452 477 498
LO PR 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 148 157 131 140 153 163
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 10
exPaNded cooliNg data — dP14dm36**41** (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
35.9 30.0 30.7 32.7 35.0 28.5 29.1 31.1 33.3 26.4 27.0 28.8 30.8
10.4 10.7 11.0 10.9 11.1 11.4 11.8 11.7 11.9 12.3 12.7 12.4 12.6 13.0 13.5 13.1 13.4 13.8 14.2 13.8 14.1 14.5 15.0
29 28 27 23 29 29 27 23 28 28 27 23 26 26 25 21
10.7 11.0 11.4 11.2 11.4 11.8 12.2 12.1 12.3 12.7 13.1 12.8 13.1 13.5 13.9 13.5 13.8 14.2 14.7 14.2 14.6 15.0 15.5
MBh 32.2 33.0 35.2 37.6 31.5 32.2 34.4 36.8 30.7 31.4 33.6
S/T 0.83 0.78 0.64 0.47 0.86 0.81 0.66 0.49 0.88 0.83 0.67 0.50 0.91 0.86 0.70 0.52 0.95 0.89 0.72 0.54 0.96 0.90 0.73 0.54
∆T 27 26 23 18 27 26 23 18 27 26 23 18 28 27 23 18 27 26 23 18 25 24 21 17
kW 2.28 2.33 2.41 2.49 2.46 2.52 2.60 2.69 2.62 2.68 2.77 2.87 2.76 2.83 2.92 3.02 2.88 2.95 3.05 3.15 2.99 3.05 3.16 3.27
910
Amps 10.2
HI PR 235 253 267 278 263 284 299 312 300 322 340 355 341 367 388 404 384 413 436 455 424 456 482 503
LO PR 106 113 123 131 112 119 130 139 117 124 135 144 123 130 142 152 128 137 149 159 133 141 154 164
MBh 36.6 37.3 39.1 41.7 35.8 36.5 38.2 40.7 34.9 35.6 37.3 39.8 34.1 34.7 36.4 38.8 32.4 33.0 34.5 36.9 30.0 30.6 32.0 34.1
S/T 0.95 0.92 0.83 0.67 0.98 0.95 0.86 0.69 1.00 0.97 0.88 0.71 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.95 0.77
∆T 27 27 25 22 28 27 26 22 27 27 26 22 27 27 26 22 25 26 26 22 24 24 24 21
kW 2.38 2.43 2.51 2.60 2.57 2.63 2.71 2.81 2.74 2.80 2.89 2.99 2.88 2.95 3.05 3.15 3.01 3.08 3.18 3.29 3.12 3.19 3.30 3.41
1170
Amps 10.6 10.8 11.1 11.4 11.3 11.5 11.9 12.3 12.2 12.4 12.8 13.2 12.9 13.2 13.6 14.0 13.6 13.9 14.3 14.8 14.4 14.7 15.1 15.6
HI PR 247 266 281 293 277 298 315 328 315 339 358 373 359 386 408 425 404 434 459 479 446 480 507 529
LO PR 112 119 130 138 118 126 137 146 123 130 142 152 129 137 150 159 135 144 157 167 140 149 162 173
MBh 35.5 36.2 37.9 40.5 34.7 35.4 37.1 39.5 33.9 34.5 36.2 38.6 33.1 33.7 35.3 37.7 31.4 32.0 33.5 35.8 29.1 29.7 31.1 33.1
S/T 0.90 0.87 0.79 0.64 0.94 0.90 0.82 0.66 0.96 0.93 0.84 0.68 0.99 0.96 0.86 0.70 1.00 0.99 0.90 0.73 1.00 1.00 0.90 0.73
∆T 28 28 26 23 29 28 27 23
kW 2.36 2.41 2.49 2.57 2.55 2.61 2.69 2.78 2.71 2.78 2.87 2.97 2.86 2.93 3.02 3.13 2.98 3.05 3.16 3.27 3.09 3.16 3.27 3.38
1040
85
Amps 10.5
HI PR 244 263 278 290 274 295 312 325 312 336 355 370 355 382 404 421 400 430 454 474 442 475 502 524
LO PR 111 118 128 137 117 124 136 145 121 129 141 150 128 136 148 158 134 142 155 165 138 147 161 171
MBh 32.8 33.4 35.0 37.4 32.0 32.7 34.2 36.5 31.3 31.9 33.4 35.6 30.5 31.1 32.6 34.8 29.0 29.6 31.0 33.0 26.9 27.4 28.7 30.6
S/T 0.87 0.84 0.76 0.62 0.90 0.87 0.79 0.64 0.93 0.89 0.81 0.65 0.96 0.92 0.83 0.68 0.99 0.96 0.86 0.70 1.00 0.97 0.87 0.71
∆T 29 28 27 23 29 29 27 24 29 29 27 24 30 29 27 24 29 29 27 23 27 27 25 22
kW 2.30 2.35 2.43 2.51 2.49 2.54 2.62 2.71 2.65 2.70 2.79 2.89 2.79 2.85 2.95 3.05 2.91 2.97 3.07 3.18 3.01 3.08 3.19 3.30
910
Amps 10.2 10.4 10.7 11.1 10.9 11.2 11.5 11.9 11.8 12.0 12.4 12.8 12.5 12.7 13.1 13.6 13.2 13.5 13.9 14.3 13.9 14.2 14.6 15.1
HI PR 237 255 269 281 266 286 302 315 303 326 344 359 345 371 392 409 388 417 441 460 428 461 487 508
LO PR 107 114 125 133 113 121 132 140 118 125 137 146 124 132 144 153 130 138 151 160 134 143 156 166
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 36.0 36.8 39.3 42.0 35.1 35.9 38.4 41.0 34.3 35.1 37.5 40.0 33.5 34.2 36.5 39.1 31.8 32.5 34.7 37.1 29.5 30.1 32.2 34.4
S/T 0.90 0.85 0.69 0.52 0.94 0.88 0.72 0.53 0.96 0.90 0.73 0.55 1.00 0.93 0.76 0.57 1.00 0.97 0.79 0.59 1.00 1.00 0.79 0.59
∆T 26 25 21 17 26 25 22 17 26 25 22 17 26 25 22 17 25 25 21 17 23 24 20 16
kW 2.36 2.41 2.49 2.57 2.55 2.61 2.69 2.78 2.71 2.78 2.87 2.97 2.86 2.93 3.02 3.13 2.98 3.05 3.16 3.27 3.09 3.16 3.27 3.38
1170
Amps 10.5 10.7 11.0 11.4 11.2 11.4 11.8 12.2 12.1 12.3 12.7 13.1 12.8 13.1 13.5 13.9 13.5 13.8 14.2 14.7 14.2 14.6 15.0 15.5
HI PR 244 263 278 290 274 295 312 325 312 336 355 370 355 382 404 421 400 430 454 474 442 475 502 524
LO PR 111 118 128 137 117 124 136 145 121 129 141 150 128 136 148 158 134 142 155 165 138 147 161 171
MBh 34.9 35.7 38.1 40.8 34.1 34.9 37.3 39.8 33.3 34.0 36.4 38.9 32.5 33.2 35.5 37.9 30.9 31.5 33.7 36.0 28.6 29.2 31.2 33.4
S/T 0.86 0.81 0.66 0.49 0.89 0.84 0.68 0.51 0.92 0.86 0.70 0.52 0.95 0.89 0.72 0.54 0.98 0.92 0.75 0.56 0.99 0.93 0.76 0.57
∆T 27 26 22 18 27 26 22 18 27 26 23 18 27 26 23 18 27 26 22 18 25 24 21 17
kW 2.34 2.39 2.47 2.55 2.53 2.58 2.67 2.76 2.69 2.75 2.84 2.94 2.84 2.90 3.00 3.10 2.96 3.03 3.13 3.24 3.07 3.14 3.24 3.36
1040
80
Amps 10.4 10.6 10.9 11.3 11.1 11.4 11.7 12.1 12.0 12.2 12.6 13.0 12.7 13.0 13.3 13.8 13.4 13.7 14.1 14.6 14.1 14.4 14.9 15.4
HI PR 242 260 275 287 272 292 309 322 309 332 351 366 352 379 400 417 396 426 450 469 437 471 497 518
LO PR 110 117 127 135 116 123 134 143 120 128 140 149 126 134 147 156 132 141 154 164 137 146 159 169
10 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 11
Page 11
exPaNded cooliNg data — dP14dm42***41**
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 35.3 36.6 40.1 - 33.5 34.7 38.1 - 31.0 32.2 35.3 -
23 21 18 12 23 22 18 12 23 21 17 12 22 20 16 11
11.5 11.8 - 12.1 12.3 12.7 - 13.0 13.2 13.6 - 13.7 14.0 14.5 - 14.5 14.8 15.3 - 15.3 15.6 16.1 -
11.9 12.2 12.6 12.5 12.7 13.1 13.5 13.4 13.7 14.1 14.6 14.2 14.5 14.9 15.5 15.0 15.3 15.8 16.3 15.8 16.2 16.7 17.2
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 18 16 12 -
S/T 0.77 0.64 0.45 - 0.80 0.67 0.46 - 0.82 0.69 0.47 - 0.85 0.71 0.49 - 0.88 0.73 0.51 - 0.89 0.74 0.51 -
MBh 42.3 43.9 48.1 - 41.3 42.8 46.9 - 40.4 41.8 45.8 - 39.4 40.8 44.7 - 37.4 38.8 42.5 - 34.6 35.9 39.3 -
kW 2.74 2.79 2.88 - 2.94 3.00 3.09 - 3.12 3.18 3.28 - 3.27 3.34 3.45 - 3.41 3.48 3.59 - 3.52 3.60 3.71 -
1575
HI PR 236 254 268 - 265 285 301 - 301 324 342 - 343 369 390 - 386 415 438 - 426 459 484 -
Amps 11.6 11.9 12.2 - 12.5 12.7 13.1 - 13.4 13.7 14.1 - 14.2 14.5 14.9 - 15.0 15.3 15.8 - 15.8 16.2 16.7 -
LO PR 113 120 131 - 119 127 138 - 124 132 144 - 130 138 151 - 136 145 158 - 141 150 163 -
∆T 20 17 13 - 20 17 13 - 20 17 13 - 20 18 13 - 20 17 13 - 19 16 12 -
S/T 0.74 0.61 0.43 - 0.76 0.64 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.84 0.70 0.48 - 0.85 0.71 0.49 -
MBh 41.1 42.6 46.7 - 40.1 41.6 45.6 - 39.2 40.6 44.5 - 38.2 39.6 43.4 - 36.3 37.6 41.2 - 33.6 34.9 38.2 -
kW 2.72 2.77 2.86 - 2.92 2.98 3.07 - 3.09 3.16 3.26 - 3.25 3.32 3.42 - 3.38 3.45 3.56 - 3.49 3.57 3.68 -
1400
70
HI PR 233 251 265 - 262 282 298 - 298 321 339 - 339 365 386 - 382 411 434 - 422 454 479 -
Amps 11.6 11.8 12.1 - 12.4 12.6 13.0 - 13.3 13.6 14.0 - 14.1 14.4 14.8 - 14.9 15.2 15.7 - 15.7 16.0 16.5 -
LO PR 111 119 129 - 118 125 137 - 122 130 142 - 129 137 149 - 135 143 156 - 139 148 162 -
MBh 37.9 39.3 43.1 - 37.0 38.4 42.1 - 36.2 37.5 41.1
∆T 20 17 13 - 20 18 13 - 20 18 13 - 21 18 14 - 20 18 13 - 19 16 12 -
S/T 0.71 0.59 0.41 - 0.74 0.61 0.43 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.68 0.47 - 0.82 0.68 0.47 -
kW 2.66 2.71 2.79 - 2.85 2.91 3.00 - 3.02 3.08 3.18 - 3.17 3.24 3.34 - 3.30 3.37 3.47 - 3.41 3.48 3.59 -
HI PR 226 244 257 - 254 273 289 - 289 311 328 - 329 354 374 - 370 399 421 - 409 440 465 -
Amps 11.3
LO PR 108 115 126 - 114 122 133 - 119 126 138 - 125 133 145 - 131 139 152 - 135 144 157 -
1225
MBh 43.0 44.3 48.0 51.5 42.0 43.3 46.9 50.3 41.0 42.3 45.7 49.1 40.0 41.2 44.6 47.9 38.0 39.2 42.4 45.5 35.2 36.3 39.3 42.1
S/T 0.88 0.78 0.59 0.38 0.91 0.81 0.62 0.40 0.93 0.83 0.63 0.41 0.96 0.86 0.65 0.42 1.00 0.89 0.68 0.44 1.00 0.90 0.68 0.44
∆T 22 20 17 11 22 21 17 12 22 21 17 12 22 21 17 12 22 20 17 12 21 19 16 11
kW 2.76 2.82 2.90 2.99 2.96 3.02 3.12 3.21 3.14 3.21 3.31 3.41 3.30 3.37 3.48 3.59 3.43 3.51 3.62 3.74 3.55 3.63 3.74 3.87
1575
Amps 11.7 12.0 12.3 12.7 12.6 12.8 13.2 13.6 13.5 13.8 14.2 14.7 14.3 14.6 15.1 15.6 15.1 15.5 15.9 16.5 15.9 16.3 16.8 17.4
HI PR 238 256 271 282 267 288 304 317 304 327 345 360 346 373 393 410 390 419 443 462 430 463 489 510
LO PR 114 121 132 141 120 128 140 149 125 133 145 154 131 140 152 162 137 146 160 170 142 151 165 176
MBh 41.8 43.0 46.6 50.0 40.8 42.0 45.5 48.8 39.8 41.0 44.4 47.7 38.9 40.0 43.3 46.5 36.9 38.0 41.2 44.2 34.2 35.2 38.1 40.9
S/T 0.84 0.75 0.57 0.36 0.87 0.78 0.59 0.38 0.89 0.80 0.60 0.39 0.92 0.82 0.62 0.40 0.95 0.85 0.65 0.41 0.96 0.86 0.65 0.42
∆T 23 21 17 12 23 21 18 12
kW 2.74 2.79 2.88 2.97 2.94 3.00 3.09 3.19 3.12 3.18 3.28 3.39 3.27 3.34 3.45 3.56 3.41 3.48 3.59 3.71 3.52 3.60 3.71 3.83
1400
75
Amps 11.7
HI PR 236 254 268 280 265 285 301 314 301 324 342 357 343 369 390 406 386 415 438 457 426 459 484 505
LO PR 113 120 131 139 119 127 138 147 124 132 144 153 130 138 151 161 136 145 158 168 141 150 164 174
MBh 38.6 39.7 43.0 46.1 37.7 38.8 42.0 45.1 36.8 37.9 41.0 44.0 35.9 36.9 40.0 42.9 34.1 35.1 38.0 40.8 31.6 32.5 35.2 37.8
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.36 0.86 0.77 0.58 0.37 0.89 0.79 0.60 0.39 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
∆T 23 22 18 12 24 22 18 12 24 22 18 12 24 22 18 12 23 22 18 12 22 20 17 11
kW 2.68 2.73 2.81 2.90 2.87 2.93 3.02 3.11 3.04 3.11 3.20 3.30 3.20 3.26 3.36 3.47 3.32 3.39 3.50 3.62 3.44 3.51 3.62 3.74
1225
Amps 11.4 11.6 11.9 12.3 12.2 12.4 12.8 13.2 13.1 13.4 13.7 14.2 13.9 14.2 14.6 15.1 14.6 15.0 15.4 15.9 15.4 15.8 16.2 16.8
HI PR 229 246 260 271 257 276 292 304 292 314 332 346 333 358 378 394 374 403 425 443 413 445 470 490
LO PR 109 116 127 135 115 123 134 143 120 128 139 148 126 134 146 156 132 140 153 163 137 145 159 169
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 12
exPaNded cooliNg data — dP14dm42***41** (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
43.7 36.5 37.3 39.9 42.6 34.7 35.4 37.9 40.5 32.1 32.8 35.1 37.5
11.7 12.0 12.4 12.3 12.5 12.9 13.3 13.2 13.5 13.9 14.3 14.0 14.3 14.7 15.2 14.8 15.1 15.5 16.1 15.5 15.9 16.4 16.9
27 27 26 22 26 27 26 22 25 26 26 22 23 24 24 21
12.1 12.4 12.8 12.7 12.9 13.3 13.7 13.6 13.9 14.3 14.8 14.4 14.8 15.2 15.7 15.3 15.6 16.1 16.6 16.1 16.4 16.9 17.5
MBh 39.3 40.1 42.9 45.8 38.3 39.2 41.9 44.7 37.4 38.2 40.9
S/T 0.89 0.83 0.68 0.50 0.92 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.55 1.01 0.95 0.77 0.57 1.02 0.95 0.78 0.58
∆T 26 25 22 17 26 25 22 18 26 25 22 18 27 25 22 18 26 25 22 17 25 23 20 16
kW 2.70 2.75 2.83 2.92 2.89 2.95 3.04 3.14 3.07 3.13 3.23 3.33 3.22 3.29 3.39 3.50 3.35 3.42 3.53 3.65 3.46 3.54 3.65 3.77
1225
Amps 11.5
HI PR 231 249 263 274 259 279 295 307 295 317 335 350 336 361 382 398 378 407 429 448 418 449 474 495
LO PR 110 117 128 136 117 124 135 144 121 129 141 150 127 135 148 157 133 142 155 165 138 147 160 171
MBh 44.6 45.4 47.6 50.8 43.5 44.4 46.5 49.6 42.5 43.3 45.4 48.4 41.5 42.3 44.3 47.2 39.4 40.2 42.1 44.9 36.5 37.2 39.0 41.6
S/T 1.00 0.97 0.88 0.71 1.00 1.00 0.91 0.74 1.00 1.00 0.93 0.76 1.00 1.00 0.96 0.78 1.00 1.00 1.00 0.81 1.00 1.00 1.00 0.82
∆T 26 26 24 21 25 26 25 21 25 25 25 21 24 25 25 22 23 23 25 21 21 22 23 20
kW 2.80 2.86 2.95 3.04 3.01 3.07 3.17 3.27 3.19 3.26 3.36 3.47 3.35 3.42 3.53 3.65 3.49 3.56 3.68 3.80 3.61 3.69 3.80 3.93
1575
Amps 11.9 12.2 12.5 12.9 12.8 13.0 13.4 13.8 13.7 14.0 14.4 14.9 14.6 14.9 15.3 15.8 15.4 15.7 16.2 16.8 16.2 16.6 17.1 17.7
HI PR 243 262 276 288 273 293 310 323 310 334 352 368 353 380 401 419 397 428 452 471 439 473 499 520
LO PR 116 123 135 144 123 130 142 152 127 136 148 158 134 142 155 166 140 149 163 173 145 154 168 179
MBh 43.3 44.1 46.2 49.3 42.3 43.1 45.1 48.1 41.3 42.1 44.1 47.0 40.3 41.0 43.0 45.8 38.2 39.0 40.8 43.6 35.4 36.1 37.8 40.3
S/T 0.96 0.93 0.84 0.68 1.00 0.96 0.87 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.95 0.77 1.00 1.00 0.96 0.78
∆T 27 27 25 22 28 27 26 22
kW 2.78 2.84 2.92 3.01 2.99 3.05 3.14 3.24 3.17 3.23 3.33 3.44 3.33 3.40 3.50 3.62 3.46 3.54 3.65 3.77 3.58 3.66 3.77 3.90
1400
85
Amps 11.8
HI PR 241 259 273 285 270 291 307 320 307 330 349 364 350 376 397 415 393 423 447 466 435 468 494 515
LO PR 115 122 133 142 121 129 141 150 126 134 147 156 132 141 154 164 139 148 161 172 144 153 167 178
MBh 39.9 40.7 42.6 45.5 39.0 39.8 41.6 44.4 38.1 38.8 40.7 43.4 37.2 37.9 39.7 42.3 35.3 36.0 37.7 40.2 32.7 33.3 34.9 37.2
S/T 0.93 0.90 0.81 0.66 0.96 0.93 0.84 0.68 0.99 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.75
∆T 28 27 26 22 28 28 26 23 28 28 26 23 28 28 26 23 26 27 26 23 25 25 24 21
kW 2.72 2.77 2.86 2.94 2.92 2.98 3.07 3.16 3.09 3.16 3.25 3.36 3.25 3.31 3.42 3.53 3.38 3.45 3.56 3.68 3.49 3.57 3.68 3.80
1225
Amps 11.6 11.8 12.1 12.5 12.4 12.6 13.0 13.4 13.3 13.6 14.0 14.4 14.1 14.4 14.8 15.3 14.9 15.2 15.7 16.2 15.7 16.0 16.5 17.1
HI PR 233 251 265 277 262 282 298 310 298 321 339 353 339 365 386 402 382 411 434 452 422 454 479 500
LO PR 111 119 129 138 118 125 137 146 122 130 142 151 129 137 149 159 135 143 156 167 139 148 162 172
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 43.8 44.8 47.8 51.1 42.8 43.7 46.7 49.9 41.8 42.7 45.6 48.7 40.8 41.6 44.5 47.6 38.7 39.6 42.3 45.2 35.9 36.6 39.1 41.9
S/T 0.96 0.90 0.73 0.55 1.00 0.94 0.76 0.57 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.84 0.63 1.00 1.00 0.84 0.63
∆T 25 24 21 16 25 24 21 17 24 24 21 17 24 24 21 17 23 23 21 16 21 21 19 15
kW 2.78 2.84 2.92 3.01 2.99 3.05 3.14 3.24 3.17 3.23 3.33 3.44 3.33 3.40 3.50 3.62 3.46 3.54 3.65 3.77 3.58 3.66 3.77 3.90
1575
Amps 11.8 12.1 12.4 12.8 12.7 12.9 13.3 13.7 13.6 13.9 14.3 14.8 14.4 14.8 15.2 15.7 15.3 15.6 16.1 16.6 16.1 16.4 16.9 17.5
HI PR 241 259 273 285 270 291 307 320 307 330 349 364 350 376 397 415 393 423 447 466 435 468 494 515
LO PR 115 122 133 142 121 129 141 150 126 134 147 156 132 141 154 164 139 148 161 172 144 153 167 178
MBh 42.5 43.5 46.4 49.6 41.5 42.4 45.4 48.5 40.6 41.4 44.3 47.3 39.6 40.4 43.2 46.2 37.6 38.4 41.0 43.9 34.8 35.6 38.0 40.6
S/T 0.92 0.86 0.70 0.52 0.95 0.89 0.73 0.54 0.98 0.91 0.74 0.56 1.00 0.94 0.77 0.57 1.00 0.98 0.80 0.60 1.00 0.99 0.80 0.60
∆T 26 25 21 17 26 25 22 17 26 25 22 17 26 25 22 17 25 25 21 17 23 23 20 16
kW 2.76 2.82 2.90 2.99 2.96 3.02 3.12 3.21 3.14 3.21 3.31 3.41 3.30 3.37 3.48 3.59 3.43 3.51 3.62 3.74 3.55 3.63 3.74 3.87
1400
80
Amps 11.7 12.0 12.3 12.7 12.6 12.8 13.2 13.6 13.5 13.8 14.2 14.7 14.3 14.6 15.1 15.6 15.1 15.5 15.9 16.5 15.9 16.3 16.8 17.4
HI PR 238 256 271 282 267 288 304 317 304 327 346 360 346 373 394 410 390 419 443 462 430 463 489 510
LO PR 114 121 132 141 120 128 140 149 125 133 145 154 131 140 152 162 137 146 160 170 142 151 165 176
12 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 13
Page 13
exPaNded cooliNg data — dP14dm48***41a*
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 38.2 39.6 43.4 - 36.3 37.6 41.2 - 33.6 34.8 38.2 -
22 21 17 12 23 21 17 12 22 20 17 12 21 19 16 11
12.9 13.2 - 13.5 13.8 14.1 - 14.5 14.8 15.2 - 15.3 15.7 16.1 - 16.2 16.5 17.0 - 17.0 17.4 17.9 -
13.3 13.6 14.1 13.9 14.2 14.6 15.1 14.9 15.3 15.7 16.2 15.8 16.2 16.7 17.2 16.7 17.1 17.6 18.2 17.6 18.0 18.5 19.2
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 18 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 18 16 12 - 17 15 11 -
S/T 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.81 0.67 0.47 - 0.83 0.70 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -
MBh 45.8 47.5 52.0 - 44.7 46.4 50.8 - 43.7 45.3 49.6 - 42.6 44.2 48.4 - 40.5 41.9 46.0 - 37.5 38.9 42.6 -
kW 3.10 3.16 3.26 - 3.33 3.39 3.50 - 3.52 3.60 3.71 - 3.70 3.78 3.90 - 3.85 3.93 4.05 - 3.98 4.06 4.19 -
1740
HI PR 237 255 270 - 266 287 303 - 303 326 344 - 345 371 392 - 388 418 441 - 429 461 487 -
Amps 13.0 13.3 13.6 - 13.9 14.2 14.6 - 14.9 15.3 15.7 - 15.8 16.2 16.6 - 16.7 17.1 17.6 - 17.6 18.0 18.5 -
LO PR 111 118 129 - 117 125 136 - 122 129 141 - 128 136 149 - 134 143 156 - 139 147 161 -
∆T 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 19 17 13 - 18 16 12 -
S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -
MBh 44.5 46.1 50.5 - 43.4 45.0 49.3 - 42.4 43.9 48.1 - 41.4 42.9 47.0 - 39.3 40.7 44.6 - 36.4 37.7 41.3 -
kW 3.08 3.14 3.23 - 3.30 3.37 3.47 - 3.50 3.57 3.68 - 3.67 3.75 3.86 - 3.82 3.90 4.02 - 3.94 4.03 4.16 -
1550
70
HI PR 235 253 267 - 264 284 300 - 300 323 341 - 341 367 388 - 384 413 437 - 424 457 482 -
Amps 12.9 13.2 13.5 - 13.8 14.1 14.5 - 14.8 15.1 15.6 - 15.7 16.0 16.5 - 16.6 17.0 17.5 - 17.5 17.8 18.4 -
LO PR 110 117 127 - 116 123 135 - 121 128 140 - 127 135 147 - 133 141 154 - 137 146 159 -
MBh 41.0 42.5 46.6 - 40.1 41.5 45.5 - 39.1 40.6 44.4
∆T 19 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 19 17 13 - 18 16 12 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
kW 3.01 3.07 3.16 - 3.23 3.29 3.39 - 3.42 3.49 3.59 - 3.58 3.66 3.77 - 3.73 3.81 3.92 - 3.85 3.93 4.06 -
HI PR 228 245 259 - 256 275 291 - 291 313 330 - 331 356 376 - 373 401 423 - 412 443 468 -
Amps 12.6
LO PR 106 113 124 - 112 120 131 - 117 124 136 - 123 131 143 - 129 137 149 - 133 142 155 -
1360
MBh 46.6 48.0 51.9 55.7 45.5 46.8 50.7 54.4 44.4 45.7 49.5 53.1 43.3 44.6 48.3 51.8 41.2 42.4 45.9 49.2 38.1 39.3 42.5 45.6
S/T 0.86 0.77 0.58 0.38 0.89 0.80 0.61 0.39 0.92 0.82 0.62 0.40 0.95 0.85 0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.89 0.67 0.43
∆T 21 20 16 11 21 20 16 11 22 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10
kW 3.13 3.19 3.28 3.38 3.35 3.42 3.53 3.63 3.55 3.63 3.74 3.86 3.73 3.81 3.93 4.05 3.88 3.96 4.09 4.22 4.01 4.09 4.23 4.36
1740
Amps 13.1 13.4 13.8 14.2 14.0 14.3 14.7 15.2 15.1 15.4 15.8 16.4 16.0 16.3 16.8 17.4 16.9 17.2 17.7 18.4 17.8 18.1 18.7 19.3
HI PR 240 258 272 284 269 289 306 319 306 329 348 363 348 375 396 413 392 422 445 465 433 466 492 513
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 167 140 149 163 173
MBh 45.2 46.6 50.4 54.1 44.2 45.5 49.2 52.8 43.1 44.4 48.0 51.6 42.1 43.3 46.9 50.3 40.0 41.1 44.5 47.8 37.0 38.1 41.3 44.3
S/T 0.82 0.74 0.56 0.36 0.85 0.76 0.58 0.37 0.87 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.94 0.84 0.63 0.41 0.94 0.84 0.64 0.41
∆T 22 20 17 11 22 21 17 12
kW 3.10 3.16 3.26 3.36 3.33 3.39 3.50 3.61 3.53 3.60 3.71 3.83 3.70 3.78 3.90 4.02 3.85 3.93 4.05 4.19 3.98 4.06 4.19 4.33
1550
75
Amps 13.0
HI PR 237 255 270 281 266 287 303 316 303 326 344 359 345 371 392 409 388 418 441 460 429 461 487 508
LO PR 111 118 129 137 117 125 136 145 122 130 141 151 128 136 149 158 134 143 156 166 139 147 161 171
MBh 41.7 43.0 46.5 49.9 40.8 42.0 45.4 48.8 39.8 41.0 44.3 47.6 38.8 40.0 43.3 46.4 36.9 38.0 41.1 44.1 34.2 35.2 38.1 40.9
S/T 0.79 0.71 0.54 0.35 0.82 0.74 0.56 0.36 0.84 0.75 0.57 0.37 0.87 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.91 0.81 0.62 0.40
∆T 22 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 21 19 16 11
kW 3.03 3.09 3.18 3.28 3.25 3.32 3.42 3.52 3.44 3.51 3.62 3.74 3.61 3.69 3.80 3.92 3.76 3.84 3.96 4.08 3.88 3.96 4.09 4.22
1360
Amps 12.7 13.0 13.3 13.8 13.6 13.9 14.3 14.7 14.6 14.9 15.3 15.8 15.5 15.8 16.2 16.8 16.3 16.7 17.2 17.7 17.2 17.6 18.1 18.7
HI PR 230 248 262 273 258 278 294 306 294 316 334 348 335 360 380 397 376 405 428 446 416 448 473 493
LO PR 108 114 125 133 114 121 132 141 118 126 137 146 124 132 144 153 130 138 151 161 134 143 156 166
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 14
exPaNded cooliNg data — dP14dm48***41a* (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
47.3 39.5 40.4 43.1 46.1 37.5 38.4 41.0 43.8 34.8 35.5 38.0 40.6
13.1 13.4 13.9 13.7 14.0 14.4 14.8 14.7 15.0 15.4 16.0 15.6 15.9 16.4 16.9 16.5 16.8 17.3 17.9 17.3 17.7 18.2 18.9
26 26 25 21 26 26 25 22 25 25 25 21 23 23 23 20
13.5 13.9 14.3 14.1 14.4 14.8 15.3 15.2 15.5 16.0 16.5 16.1 16.4 16.9 17.5 17.0 17.4 17.9 18.5 17.9 18.3 18.9 19.5
MBh 42.5 43.4 46.4 49.6 41.5 42.4 45.3 48.4 40.5 41.4 44.2
S/T 0.87 0.82 0.66 0.50 0.90 0.85 0.69 0.51 0.92 0.87 0.71 0.53 0.95 0.89 0.73 0.54 0.99 0.93 0.76 0.56 1.00 0.94 0.76 0.57
∆T 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 23 23 20 16
kW 3.06 3.12 3.21 3.31 3.28 3.34 3.44 3.55 3.47 3.54 3.65 3.76 3.64 3.72 3.83 3.95 3.79 3.87 3.99 4.12 3.91 4.00 4.12 4.26
1360
Amps 12.8
HI PR 233 250 264 276 261 281 297 309 297 319 337 352 338 364 384 401 380 409 432 451 420 452 477 498
LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 162 136 145 158 168
MBh 48.2 49.2 51.5 54.9 47.1 48.0 50.3 53.7 46.0 46.9 49.1 52.4 44.9 45.7 47.9 51.1 42.6 43.4 45.5 48.5 39.5 40.2 42.1 45.0
S/T 0.99 0.96 0.86 0.70 1.00 0.99 0.89 0.73 1.00 1.00 0.92 0.74 1.00 1.00 0.95 0.77 1.00 1.00 0.98 0.80 1.00 1.00 0.99 0.80
∆T 25 25 23 20 25 25 24 21 24 25 24 21 24 24 24 21 23 23 24 20 21 21 22 19
kW 3.17 3.24 3.33 3.44 3.40 3.47 3.58 3.69 3.61 3.68 3.80 3.92 3.79 3.87 3.99 4.12 3.94 4.03 4.15 4.29 4.07 4.16 4.29 4.44
1740
Amps 13.3 13.6 14.0 14.4 14.2 14.5 15.0 15.4 15.3 15.6 16.1 16.6 16.2 16.6 17.1 17.6 17.1 17.5 18.0 18.7 18.1 18.5 19.0 19.7
HI PR 245 263 278 290 274 295 312 325 312 336 355 370 355 383 404 421 400 430 454 474 442 475 502 524
LO PR 114 122 133 141 121 128 140 149 125 133 146 155 132 140 153 163 138 147 160 171 143 152 166 177
MBh 46.8 47.7 50.0 53.3 45.7 46.6 48.8 52.1 44.6 45.5 47.7 50.9 43.6 44.4 46.5 49.6 41.4 42.2 44.2 47.1 38.3 39.1 40.9 43.7
S/T 0.95 0.91 0.82 0.67 0.98 0.95 0.85 0.69 1.00 0.97 0.88 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.94 0.76 1.00 1.00 0.95 0.77
∆T 26 26 24 21 27 26 25 21
kW 3.15 3.21 3.31 3.41 3.38 3.45 3.55 3.66 3.58 3.66 3.77 3.89 3.76 3.84 3.96 4.09 3.91 3.99 4.12 4.25 4.04 4.13 4.26 4.40
1550
85
Amps 13.2
HI PR 242 261 275 287 272 292 309 322 309 333 351 366 352 379 400 417 396 426 450 469 437 471 497 518
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 130 139 152 161 137 145 159 169 141 150 164 175
MBh 43.2 44.1 46.1 49.2 42.2 43.0 45.1 48.1 41.2 42.0 44.0 46.9 40.2 41.0 42.9 45.8 38.2 38.9 40.8 43.5 35.4 36.1 37.8 40.3
S/T 0.91 0.88 0.79 0.64 0.95 0.91 0.82 0.67 0.97 0.94 0.84 0.68 1.00 0.97 0.87 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.91 0.74
∆T 27 26 25 21 27 27 25 22 27 27 25 22 27 27 25 22 26 26 25 22 24 24 23 20
kW 3.08 3.14 3.23 3.33 3.30 3.37 3.47 3.58 3.50 3.57 3.68 3.79 3.67 3.75 3.86 3.99 3.82 3.90 4.02 4.15 3.94 4.03 4.16 4.29
1360
Amps 12.9 13.2 13.5 14.0 13.8 14.1 14.5 14.9 14.8 15.1 15.6 16.1 15.7 16.0 16.5 17.1 16.6 16.9 17.5 18.0 17.5 17.8 18.4 19.0
HI PR 235 253 267 278 264 284 299 312 300 323 341 355 341 367 388 405 384 413 436 455 424 457 482 503
LO PR 110 117 127 136 116 123 135 143 120 128 140 149 127 135 147 157 133 141 154 164 137 146 159 170
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 47.4 48.4 51.7 55.3 46.3 47.3 50.5 54.0 45.2 46.2 49.3 52.7 44.1 45.1 48.1 51.5 41.9 42.8 45.7 48.9 38.8 39.7 42.4 45.3
S/T 0.95 0.89 0.72 0.54 1.00 0.92 0.75 0.56 1.00 0.94 0.77 0.57 1.00 1.00 0.79 0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.83 0.62
∆T 24 23 20 16 24 23 20 16 24 23 20 16 23 24 20 16 22 23 20 16 21 21 19 15
kW 3.15 3.21 3.31 3.41 3.38 3.45 3.55 3.66 3.58 3.66 3.77 3.89 3.76 3.84 3.96 4.09 3.91 3.99 4.12 4.25 4.04 4.13 4.26 4.40
1740
Amps 13.2 13.5 13.9 14.3 14.1 14.4 14.8 15.3 15.2 15.5 16.0 16.5 16.1 16.4 16.9 17.5 17.0 17.4 17.9 18.5 17.9 18.3 18.9 19.5
HI PR 242 261 275 287 272 292 309 322 309 333 351 366 352 379 400 417 396 426 450 469 437 471 497 518
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 130 139 152 161 137 145 159 169 141 150 164 175
MBh 46.0 47.0 50.2 53.7 45.0 45.9 49.1 52.5 43.9 44.8 47.9 51.2 42.8 43.7 46.7 50.0 40.7 41.6 44.4 47.5 37.7 38.5 41.1 44.0
S/T 0.90 0.85 0.69 0.51 0.93 0.88 0.71 0.53 0.96 0.90 0.73 0.55 0.99 0.93 0.76 0.56 1.00 0.96 0.78 0.59 1.00 0.97 0.79 0.59
∆T 25 24 21 16 25 24 21 17 25 24 21 17 25 24 21 17 24 24 21 16 22 22 19 15
kW 3.13 3.19 3.28 3.38 3.35 3.42 3.53 3.63 3.55 3.63 3.74 3.86 3.73 3.81 3.93 4.05 3.88 3.96 4.09 4.22 4.01 4.10 4.23 4.36
1550
80
Amps 13.1 13.4 13.8 14.2 14.0 14.3 14.7 15.2 15.1 15.4 15.8 16.4 16.0 16.3 16.8 17.4 16.9 17.2 17.8 18.4 17.8 18.2 18.7 19.3
HI PR 240 258 272 284 269 289 306 319 306 329 348 363 348 375 396 413 392 422 445 465 433 466 492 513
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 167 140 149 163 173
14 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 15
Page 15
exPaNded cooliNg data — dP14dm48***41**
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
- 37.2 38.5 42.2 - 35.3 36.6 40.1 - 32.7 33.9 37.1 -
26 24 20 14 26 24 20 14 26 24 20 14 24 22 18 13
12.7 13.1 - 13.3 13.6 14.0 - 14.3 14.6 15.0 - 15.2 15.5 15.9 - 16.0 16.4 16.8 - 16.8 17.2 17.7 -
109 116 126 - 115 122 133 - 119 127 139 - 125 133 146 - 131 140 152 - 136 144 158 -
43.3 44.9 49.2 - 42.3 43.8 48.0 - 41.3 42.8 46.9 - 40.3 41.7 45.7 - 38.3 39.6 43.4 - 35.4 36.7 40.2 -
108 114 125 - 114 121 132 - 118 126 137 - 124 132 144 - 130 138 151 - 134 143 156 -
40.0 41.4 45.4 - 39.0 40.4 44.3 - 38.1 39.5 43.3
104 111 121 - 110 117 128 - 115 122 133 - 120 128 140 - 126 134 146 - 130 139 151 -
45.3 46.7 50.5 54.2 44.3 45.6 49.4 53.0 43.2 44.5 48.2 51.7 42.2 43.4 47.0 50.4 40.1 41.3 44.7 47.9 37.1 38.2 41.4 44.4
110 117 127 136 116 123 135 143 120 128 140 149 127 135 147 157 133 141 154 164 137 146 159 170
44.0 45.3 49.1 52.7 43.0 44.3 47.9 51.4 42.0 43.2 46.8 50.2 41.0 42.2 45.6 49.0 38.9 40.1 43.4 46.5 36.0 37.1 40.2 43.1
13.1 13.5 13.9 13.8 14.0 14.4 14.9 14.8 15.1 15.5 16.0 15.7 16.0 16.5 17.0 16.5 16.9 17.4 18.0 17.4 17.8 18.3 18.9
109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 162 136 145 158 168
40.6 41.8 45.3 48.6 39.7 40.9 44.2 47.5 38.7 39.9 43.2 46.3 37.8 38.9 42.1 45.2 35.9 37.0 40.0 42.9 33.3 34.2 37.1 39.8
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
∆T 21 19 14 - 22 19 14 - 22 19 14 - 22 19 14 - 22 19 14 - 20 17 13 -
S/T 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.81 0.68 0.47 - 0.84 0.70 0.48 - 0.87 0.73 0.50 - 0.88 0.73 0.51 -
MBh 44.6 46.2 50.6 - 43.5 45.1 49.5 - 42.5 44.1 48.3 - 41.5 43.0 47.1 - 39.4 40.8 44.7 - 36.5 37.8 41.4 -
kW 2.93 2.99 3.09 - 3.16 3.22 3.33 - 3.35 3.43 3.54 - 3.53 3.61 3.73 - 3.68 3.76 3.89 - 3.81 3.89 4.02 -
1461
HI PR 237 255 270 - 266 287 303 - 303 326 344 - 345 371 392 - 388 418 441 - 429 461 487 -
Amps 12.9 13.1 13.5 - 13.8 14.0 14.4 - 14.8 15.1 15.5 - 15.7 16.0 16.5 - 16.5 16.9 17.4 - 17.4 17.8 18.3 -
LO PR
MBh
∆T 22 19 15 - 23 20 15 - 23 20 15 - 23 20 15 - 22 19 15 - 21 18 14 -
S/T 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.84 0.70 0.48 -
kW 2.91 2.97 3.06 - 3.13 3.20 3.30 - 3.33 3.40 3.51 - 3.50 3.58 3.70 - 3.65 3.73 3.85 - 3.78 3.86 3.99 -
HI PR 235 253 267 - 264 284 300 - 300 323 341 - 342 368 388 - 384 413 437 - 424 457 482 -
Amps 12.8 13.0 13.4 - 13.7 13.9 14.3 - 14.7 15.0 15.4 - 15.5 15.9 16.3 - 16.4 16.8 17.3 - 17.3 17.6 18.2 -
LO PR
1300
70
MBh
∆T 23 20 15 - 23 20 15 - 23 20 15 - 23 20 15 - 23 20 15 - 21 18 14 -
S/T 0.70 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.62 0.43 - 0.77 0.64 0.45 - 0.80 0.67 0.46 - 0.81 0.67 0.47 -
kW 2.84 2.90 2.99 - 3.05 3.12 3.22 - 3.25 3.32 3.42 - 3.41 3.49 3.60 - 3.56 3.64 3.76 - 3.68 3.76 3.89 -
HI PR 228 245 259 - 256 275 291 - 291 313 331 - 331 356 376 - 373 401 423 - 412 443 468 -
Amps 12.5
LO PR
1139
MBh
S/T 0.87 0.78 0.59 0.38 0.90 0.80 0.61 0.39 0.92 0.82 0.62 0.40 0.95 0.85 0.64 0.41 0.99 0.88 0.67 0.43 1.00 0.89 0.67 0.43
∆T 25 23 19 13 25 23 19 13 25 23 19 13 25 23 19 13 25 23 19 13 23 21 18 12
kW 2.95 3.02 3.11 3.21 3.18 3.25 3.36 3.47 3.38 3.46 3.57 3.69 3.56 3.64 3.76 3.89 3.71 3.79 3.92 4.05 3.84 3.93 4.06 4.20
1461
Amps 13.0 13.2 13.6 14.0 13.9 14.2 14.6 15.0 14.9 15.2 15.7 16.2 15.8 16.1 16.6 17.2 16.7 17.0 17.5 18.1 17.6 17.9 18.5 19.1
HI PR 240 258 272 284 269 289 306 319 306 329 348 363 348 375 396 413 392 422 445 465 433 466 492 513
LO PR
MBh
S/T 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.37 0.88 0.79 0.60 0.38 0.91 0.81 0.61 0.40 0.94 0.84 0.64 0.41 0.95 0.85 0.64 0.41
∆T 26 24 19 13 26 24 20 14
kW 2.93 2.99 3.09 3.19 3.16 3.22 3.33 3.44 3.36 3.43 3.54 3.66 3.53 3.61 3.73 3.85 3.68 3.76 3.89 4.02 3.81 3.90 4.03 4.16
1300
75
Amps 12.9
HI PR 237 255 270 281 266 287 303 316 303 326 344 359 345 371 392 409 388 418 441 460 429 461 487 508
LO PR
MBh
S/T 0.80 0.71 0.54 0.35 0.83 0.74 0.56 0.36 0.85 0.76 0.57 0.37 0.88 0.78 0.59 0.38 0.91 0.81 0.62 0.40 0.92 0.82 0.62 0.40
∆T 26 24 20 14 26 24 20 14 27 24 20 14 27 25 20 14 26 24 20 14 25 23 19 13
kW 2.86 2.92 3.01 3.11 3.08 3.15 3.25 3.35 3.27 3.34 3.45 3.57 3.44 3.52 3.63 3.76 3.59 3.67 3.79 3.92 3.71 3.80 3.92 4.06
1139
Amps 12.6 12.8 13.2 13.6 13.4 13.7 14.1 14.6 14.4 14.7 15.2 15.7 15.3 15.6 16.1 16.6 16.1 16.5 17.0 17.5 17.0 17.3 17.9 18.5
HI PR 230 248 262 273 258 278 294 306 294 316 334 348 335 360 380 397 376 405 428 446 416 448 473 493
LO PR 105 112 122 130 111 118 129 138 116 123 134 143 122 129 141 150 127 136 148 158 132 140 153 163
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
Page 16
exPaNded cooliNg data — dP14dm48***41** (coNt.)
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
24.9 20.8 21.3 22.7 24.3 19.8 20.2 21.6 23.1 18.3 18.7 20.0 21.4
6.5 6.7 6.9 6.8 7.0 7.2 7.4 7.4 7.5 7.8 8.0 7.8 8.0 8.3 8.6 8.3 8.5 8.8 9.1 8.8 9.0 9.3 9.6
25 26 26 22 25 25 26 22 24 24 25 22 22 22 23 21
6.7 6.9 7.2 7.1 7.2 7.4 7.7 7.6 7.8 8.0 8.3 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.4 9.1 9.3 9.6 10.0
MBh 24.6 25.1 26.3 28.1 24.1 24.5 25.7 27.4 23.5 24.0 25.1 26.8 22.9 23.4 24.5 26.1 21.8 22.2 23.3 24.8 20.2 20.6 21.5 23.0
S/T 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.94 0.77 1.00 1.00 0.97 0.79 1.00 1.00 1.00 0.82 1.00 1.00 1.00 0.83
∆T 27 27 25 22 26 27 26 22
kW 1.58 1.62 1.67 1.73 1.71 1.75 1.81 1.87 1.82 1.86 1.93 1.99 1.92 1.97 2.03 2.10 2.01 2.05 2.12 2.20 2.08 2.13 2.20 2.28
1300
85
Amps 6.6
HI PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 416 440 459 428 460 486 507
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 131 139 152 161 137 146 159 169 141 151 164 175
MBh 22.8 23.2 24.3 25.9 22.2 22.7 23.7 25.3 21.7 22.1 23.2 24.7 21.2 21.6 22.6 24.1 20.1 20.5 21.5 22.9 18.6 19.0 19.9 21.2
S/T 0.98 0.95 0.86 0.69 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.79 1.00 1.00 0.98 0.80
∆T 28 27 26 22 27 27 26 22 27 27 26 22 26 27 26 23 25 25 26 22 23 23 24 21
kW 1.54 1.58 1.63 1.68 1.67 1.70 1.76 1.82 1.78 1.82 1.88 1.94 1.87 1.91 1.98 2.05 1.95 2.00 2.07 2.14 2.02 2.07 2.14 2.22
1139
Amps 6.4 6.5 6.7 7.0 6.9 7.0 7.3 7.5 7.4 7.6 7.8 8.1 7.9 8.1 8.3 8.6 8.4 8.6 8.9 9.2 8.9 9.1 9.4 9.7
HI PR 230 247 261 272 258 277 293 305 293 315 333 347 334 359 379 395 375 404 427 445 415 446 471 492
LO PR 110 117 127 136 116 123 135 143 121 128 140 149 127 135 147 157 133 141 154 164 137 146 159 170
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI condions kW = Total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps = outdoor unit amps (comp.+fan)
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 25.0 25.5 27.2 29.1 24.4 24.9 26.6 28.4 23.8 24.3 26.0 27.8 23.2 23.7 25.3 27.1 22.1 22.5 24.1 25.7 20.4 20.9 22.3 23.8
S/T 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.83 0.62 1.00 1.00 0.85 0.64 1.00 1.00 0.89 0.66 1.00 1.00 0.89 0.67
∆T 24 23 20 16 23 24 21 16 23 23 21 17 22 23 21 17 21 22 21 16 20 20 19 15
kW 1.58 1.62 1.67 1.73 1.71 1.75 1.81 1.87 1.82 1.86 1.93 1.99 1.92 1.97 2.03 2.10 2.01 2.05 2.12 2.20 2.08 2.13 2.20 2.28
1461
Amps 6.6 6.7 6.9 7.2 7.1 7.2 7.4 7.7 7.6 7.8 8.0 8.3 8.1 8.3 8.6 8.9 8.6 8.8 9.1 9.4 9.1 9.3 9.6 10.0
HI PR 237 255 269 281 266 286 302 315 302 325 343 358 344 370 391 408 387 416 440 459 428 460 486 507
LO PR 113 120 131 140 120 127 139 148 124 132 144 154 131 139 152 161 137 146 159 169 141 151 164 175
MBh 24.2 24.8 26.4 28.3 23.7 24.2 25.8 27.6 23.1 23.6 25.2 27.0 22.5 23.0 24.6 26.3 21.4 21.9 23.4 25.0 19.8 20.3 21.6 23.1
S/T 0.97 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 0.97 0.79 0.59 1.00 1.00 0.81 0.61 1.00 1.00 0.84 0.63 1.00 1.00 0.85 0.64
∆T 25 24 21 17 26 25 21 17 25 25 22 17 24 25 22 17 23 24 21 17 21 22 20 16
kW 1.57 1.61 1.66 1.71 1.70 1.73 1.79 1.85 1.81 1.85 1.91 1.98 1.90 1.95 2.01 2.08 1.99 2.03 2.10 2.18 2.06 2.11 2.18 2.26
1300
80
Amps 6.5 6.7 6.9 7.1 7.0 7.2 7.4 7.6 7.6 7.7 8.0 8.3 8.1 8.2 8.5 8.8 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.9
HI PR 234 252 266 278 263 283 299 312 299 322 340 354 341 367 387 404 383 412 435 454 423 456 481 502
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137 150 160 135 144 157 168 140 149 163 173
MBh 22.4 22.8 24.4 26.1 21.8 22.3 23.8 25.5 21.3 21.8 23.3
S/T 0.94 0.88 0.72 0.53 0.97 0.91 0.74 0.55 1.00 0.93 0.76 0.57 1.03 0.96 0.78 0.59 1.07 1.00 0.81 0.61 1.08 1.01 0.82 0.61
∆T 26 25 22 17 26 25 22 17 26 25 22 17 26 25 22 18 26 25 22 17 24 23 20 16
kW 1.53 1.57 1.62 1.67 1.65 1.69 1.75 1.81 1.76 1.80 1.86 1.92 1.86 1.90 1.96 2.03 1.94 1.98 2.05 2.12 2.01 2.05 2.12 2.20
1139
Amps 6.3
HI PR 227 245 258 269 255 274 290 302 290 312 330 344 330 356 375 392 372 400 422 441 411 442 467 487
LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 163 136 145 158 168
MBh 25.4 25.9 27.1 28.9 24.8 25.3 26.5 28.2 24.2 24.7 25.8 27.6 23.6 24.1 25.2 26.9 22.4 22.9 24.0 25.6 20.8 21.2 22.2 23.7
S/T 1.00 1.00 0.93 0.75 1.00 1.00 0.96 0.78 1.00 1.00 0.99 0.80 1.00 1.00 1.00 0.83 1.00 1.00 1.00 0.86 1.00 1.00 1.00 0.87
∆T 24 25 24 21 24 24 25 21 23 24 25 21 23 23 24 21 22 22 23 21 20 20 21 20
kW 1.60 1.63 1.69 1.74 1.72 1.76 1.82 1.88 1.84 1.88 1.94 2.01 1.94 1.98 2.05 2.12 2.02 2.07 2.14 2.21 2.10 2.14 2.22 2.30
1461
Amps 6.6 6.8 7.0 7.2 7.1 7.3 7.5 7.8 7.7 7.9 8.1 8.4 8.2 8.4 8.6 9.0 8.7 8.9 9.2 9.5 9.2 9.4 9.7 10.1
HI PR 239 257 272 283 268 289 305 318 305 328 347 362 347 374 395 412 391 421 444 463 432 465 491 512
LO PR 114 122 133 141 121 128 140 149 126 134 146 155 132 140 153 163 138 147 160 171 143 152 166 177
16 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 17
Page 17
exPaNded HeatiNg data
DP14DM24***41**
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 30.5 28.9 27.2 25.4 24.3 23.5 21.8 20.1 17.1 15.7 14.5 13.7 13.2 11.8 10.5 9.1 7.8 6.4
T/R 33.2 31.5 29.6 27.7 26.4 25.6 23.8 21.9 18.6 17.1 15.8 14.9 14.4 12.9 11.4 10.0 8.5 7.0
kW 2.07 2.02 1.98 1.94 1.91 1.90 1.86 1.81 2.04 1.99 1.94 1.91 1.89 1.84 1.79 1.75 1.69 1.65
Amps 10.2 9.5 8.9 8.4 8.1 7.9 7.5 7.1 6.9 6.6 6.3 6.1 6.1 5.8 5.4 5.1 4.8 4.3
COP 4.32 4.18 4.02 3.84 3.71 3.63 3.45 3.25 2.44 2.31 2.18 2.09 2.04 1.88 1.71 1.53 1.35 1.14
EER 14.8 14.3 13.7 13.1 12.7 12.4 11.8 11.1 8.3 7.9 7.5 7.2 7.0 6.4 5.8 5.2 4.6 3.9
HI PR 411 394 379 362 354 347 334 320 307 293 281 275 270 259 249 239 231 223
LO PR 141 130 122 112 106 102 94 83 75 67 59 55 53 45 39 33 28 22
DP14DM30***41**
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 36.3 34.4 32.3 30.2 28.9 28.0 26.0 24.0 20.6 19.1 17.5 16.6 16.0 14.3 12.7 11.1 9.4 7.7
T/R 32.3 30.6 28.8 26.9 25.7 24.9 23.1 21.3 18.4 17.0 15.6 14.7 14.2 12.7 11.3 9.9 8.4 6.9
kW 2.54 2.49 2.44 2.39 2.36 2.34 2.29 2.24 2.12 2.07 2.02 1.99 1.97 1.92 1.88 1.83 1.78 1.73
Amps 13.0 12.1 11.4 10.8 10.5 10.3 9.8 9.3 9.0 8.7 8.3 8.1 8.1 7.7 7.3 6.9 6.5 6.0
COP 4.18 4.03 3.88 3.70 3.58 3.50 3.32 3.13 2.85 2.70 2.54 2.43 2.37 2.18 1.98 1.77 1.55 1.31
EER 14.3 13.8 13.2 12.6 12.2 12.0 11.3 10.7 9.8 9.2 8.7 8.3 8.1 7.4 6.8 6.1 5.3 4.5
HI PR 415 398 382 366 357 350 337 323 310 296 284 277 272 262 252 241 233 225
LO PR 142 132 124 113 107 103 95 84 76 68 60 56 54 45 39 33 29 23
DP14DM36***41**
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 43.4 41.0 38.6 36.1 34.5 33.4 31.0 28.6 24.6 22.7 20.9 19.8 19.0 17.1 15.2 13.2 11.3 9.2
T/R 33.5 31.7 29.8 27.9 26.6 25.8 24.0 22.1 19.0 17.6 16.2 15.3 14.7 13.2 11.7 10.2 8.7 7.1
kW 3.20 3.14 3.07 3.01 2.97 2.94 2.88 2.82 2.49 2.43 2.37 2.34 2.32 2.26 2.20 2.15 2.09 2.04
Amps 16.1 15.1 14.2 13.4 13.0 12.8 12.1 11.6 11.1 10.7 10.3 10.1 9.9 9.5 9.0 8.5 8.0 7.3
COP 3.96 3.83 3.68 3.52 3.40 3.32 3.15 2.98 2.90 2.74 2.58 2.47 2.41 2.21 2.01 1.80 1.58 1.33
EER 13.5 13.1 12.6 12.0 11.6 11.4 10.8 10.2 9.9 9.4 8.8 8.5 8.2 7.6 6.9 6.1 5.4 4.5
HI PR 464 445 428 409 399 392 376 361 346 331 317 310 304 293 281 270 260 251
LO PR 139 129 121 111 105 101 92 82 74 66 58 54 52 44 38 32 28 22
DP14DM42***41**
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 52.9 50.0 47.1 44.0 42.1 40.7 37.8 34.9 30.1 27.8 25.6 24.2 23.3 20.9 18.5 16.1 13.8 11.3
T/R 35.0 33.1 31.1 29.1 27.8 27.0 25.0 23.1 19.9 18.4 16.9 16.0 15.4 13.8 12.2 10.7 9.1 7.5
kW 3.58 3.51 3.44 3.37 3.33 3.30 3.23 3.16 3.01 2.95 2.88 2.84 2.82 2.75 2.68 2.62 2.55 2.49
Amps 18.1 16.8 15.9 15.0 14.5 14.3 13.5 12.9 12.4 12.0 11.5 11.2 11.1 10.6 10.0 9.5 8.9 8.2
COP 4.33 4.18 4.01 3.82 3.70 3.61 3.43 3.23 2.92 2.76 2.60 2.49 2.42 2.22 2.02 1.80 1.58 1.33
EER 14.8 14.3 13.7 13.1 12.6 12.3 11.7 11.0 10.0 9.4 8.9 8.5 8.3 7.6 6.9 6.2 5.4 4.5
HI PR 414 397 382 365 357 350 336 323 309 295 283 277 272 261 251 241 232 224
LO PR 142 132 123 113 107 103 95 84 76 68 60 55 53 45 39 33 29 23
DP14DM48***41**
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 56.7 53.7 50.5 47.2 45.1 43.7 40.6 37.4 32.8 30.3 27.9 26.3 25.3 22.7 20.2 17.6 15.0 12.3
T/R 33.9 32.1 30.2 28.2 26.9 26.1 24.2 22.4 19.6 18.1 16.6 15.7 15.1 13.6 12.0 10.5 9.0 7.3
kW 3.92 3.85 3.77 3.70 3.65 3.62 3.55 3.48 3.31 3.24 3.17 3.12 3.10 3.02 2.95 2.88 2.81 2.74
Amps 19.4 18.1 17.1 16.2 15.7 15.4 14.6 14.0 13.5 12.9 12.4 12.2 12.0 11.5 10.9 10.3 9.7 8.9
COP 4.23 4.08 3.92 3.74 3.61 3.53 3.35 3.15 2.90 2.74 2.58 2.46 2.39 2.20 2.00 1.78 1.56 1.31
EER 14.5 14.0 13.4 12.8 12.3 12.1 11.4 10.8 9.9 9.3 8.8 8.4 8.2 7.5 6.8 6.1 5.3 4.5
HI PR 406 389 374 358 349 343 329 316 303 289 278 271 266 256 246 236 228 220
LO PR 132 122 115 105 99 96 88 78 71 63 55 52 50 42 36 31 27 21
Above informaon is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed. KW = Total system power
High pressure is measured at the liquid line access ng. AMPS: Unit amps (comp.+ evaporator motor + condenser fan motor)
Low pressure is measured at the compressor sucon access ng.
Page 18
airflow data
DP14DM24060M41A* - Rise Range: 35° - 65°
Unit
Static
0.1 616 51 55 845 105 53 859 94 885 103 1048 140
0.2 581 60 58 809 116 56 810 102 836 111 999 148
0.3 535 69 63 774 124 58 761 109 788 118 950 155
0.4 476 79 X 736 134 61 713 117 740 126 901 163
0.5 422 87 X 695 140 65 664 125 692 134 852 171
0.6 365 95 X 646 148 X 615 133 643 142 803 179
0.7 334 101 X 580 161 X --- --- --- --- --- ---
0.8 300 103 X 532 167 X --- --- --- --- --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM2407041** - Rise Range: 35° - 65°
Unit
Static
0.1 708 57 50 1004 129 52 859 94 885 103 1048 140
0.2 659 65 57 955 137 54 810 102 836 111 999 148
0.3 610 72 63 906 145 56 761 109 788 118 950 155
0.4 561 80 X 857 153 59 713 117 740 126 901 163
0.5 512 88 X 808 160 63 664 125 692 134 852 171
0.6 --- --- --- 760 168 X 615 133 643 142 803 179
0.7 --- --- --- --- --- --- --- --- --- --- --- ---
0.8 --- --- --- --- --- --- --- --- --- --- --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM3080M41A* - Rise Range: 35° - 65°
Unit
Static
0.1 997 147 45 1276 284 47 1059 137 1071 142 1333 234
0.2 965 155 47 1238 284 48 1008 144 1023 149 1285 242
0.3 922 165 49 1206 289 50 956 151 976 157 1237 250
0.4 886 173 51 1164 302 52 908 158 928 164 1189 257
0.5 835 182 54 1131 314 53 857 166 880 172 1141 265
0.6 781 188 58 1086 319 55 784 175 832 180 1094 273
0.7 731 200 62 1038 319 58 732 180 784 187 --- ---
0.8 677 202 X 984 322 61 673 188 736 195 --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM3090941** - Rise Range: 45° - 75°
Unit
Static
0.1 1059 137 49
0.2 1008 144 52 1212 221 57 1008 144 1023 149 1285 242
0.3 956 151 54 1165 229 59 956 151 976 157 1237 250
0.4 908 158 57 1117 236 62 908 158 928 164 1189 257
0.5 857 166 60 1069 244 64 857 166 880 172 1141 265
0.6 784 175 63 1021 252 68 784 175 832 180 1094 273
0.7 732 180 69 973 259 70 732 180 784 187 --- ---
0.8 673 188 72 --- --- --- 673 188 736 195 --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
1260 213 55 1059 137 1071 142 1333 234
18 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 19
Page 19
DP14DM36080M41A* - Rise Range: 35° - 65°
airflow data (coNt.)
Unit
Static
0.1 997 147 45 1276 284 47 1317 230 1317 230 1453 269
0.2 965 155 47 1238 284 48 1269 237 1269 237 1405 277
0.3 922 165 49 1206 289 50 1221 245 1221 245 1357 284
0.4 886 173 51 1164 302 52 1174 253 1174 253 1309 292
0.5 835 182 54 1131 314 53 1126 260 1126 260 1261 300
0.6 781 188 58 1086 319 55 1078 268 1078 268 1213 307
0.7 731 200 62 1038 319 58 1030 276 1030 276 --- ---
0.8 677 202 X 984 322 61 982 283 982 283 --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM3609041** - Rise Range: 45° - 75°
Unit
Static
0.1 1053 143 49 1257 236 55 1136 181 1136 181 1408 304
0.2 1007 151 52 1211 243 57 1090 188 1090 188 1362 311
0.3 961 158 54 1165 250 59 1044 195 1044 195 1315 319
0.4 915 165 57 1119 258 62 997 203 997 203 1269 326
0.5 869 173 60 1073 265 64 951 210 951 210 1223 334
0.6 823 180 63 1027 273 68 905 218 905 218 1177 341
0.7 777 188 69 980 280 70 859 225 859 225 --- ---
0.8 731 195 72 --- --- --- 813 233 813 233 --- ---
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM42100M41A* - Rise Range: 35° - 65°
Unit
Static
0.1 1098 167 51 1423 324 53 1354 260 1501 320 1609 365
0.2 1038 178 54 1375 335 55 1296 267 1446 328 1556 373
0.3 991 184 57 1322 347 57 1237 275 1391 336 1504 381
0.4 932 192 60 1275 347 59 1178 283 1336 344 1451 388
0.5 871 204 65 1224 357 61 1120 291 1281 352 1399 396
0.6 811 213 X 1172 364 64 1061 299 1226 359 1347 404
0.7 753 210 X 1130 379 X 1002 306 1171 367 1294 412
0.8 704 221 X 1075 384 X 944 314 1116 375 1242 420
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM4211541** - Rise Range: 45° - 75°
Unit
Static
0.1 1090 150 52
0.2 1025 158 57 1225 239 61 1296 267 1446 328 1556 373
0.3 960 166 62 1165 247 64 1237 275 1391 336 1504 381
0.4 895 174 X 1105 255 X 1178 283 1336 344 1451 388
0.5 830 181 X 1045 262 X 1120 291 1281 352 1399 396
0.6 765 189 --- 984 270 X 1061 299 1226 359 1347 404
0.7 699 197 --- 924 278 --- 1002 306 1171 367 1294 412
0.8 634 205 --- --- --- --- 944 314 1116 375 1242 420
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
1286 231 57 1354 260 1501 320 1609 365
Page 20
airflow data (coNt.)
DP14DM48100M41A* - Rise Range: 35° - 65°
Unit
Static
0.1 1098 167 51 1423 324 53 1164 180 1397 315 1758 427
0.2 1038 178 54 1375 335 55 1100 188 1354 320 1709 435
0.3 991 184 57 1322 347 57 1037 196 1306 329 1660 443
0.4 932 192 60 1275 347 59 974 204 1261 338 1612 450
0.5 871 204 65 1224 357 61 910 212 1211 343 1563 458
0.6 811 213 X 1172 364 64 847 220 1168 356 1514 466
0.7 753 210 X 1130 379 X 784 227 1111 373 1466 474
0.8 704 221 X 1075 384 X 720 235 1066 373 1417 482
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM4811541B* - Rise Range: 45° - 75°
Unit
Static
0.1 1164 180 56 1435 293 61 1164 180 1675 392 1758 427
0.2 1100 188 59 1378 301 63 1100 188 1624 400 1709 435
0.3 1037 196 62 1322 309 65 1037 196 1573 408 1660 443
0.4 974 204 65 1265 316 68 974 204 1522 416 1612 450
0.5 910 212 70 1208 324 70 910 212 1472 424 1563 458
0.6 847 220 75 1152 332 73 847 220 1421 431 1514 466
0.7 784 227 X 1095 340 X 784 227 1370 439 1466 474
0.8 720 235 X 1038 348 X 720 235 1319 447 1417 482
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
DP14DM4811541C* - Rise Range: 45° - 75°
Unit
Static
0.1 1164 180 56 1435 293 61 1164 180 1397 315 1758 427
0.2 1100 188 59 1378 301 63 1100 188 1354 320 1709 435
0.3 1037 196 62 1322 309 65 1037 196 1306 329 1660 443
0.4 974 204 65 1265 316 68 974 204 1261 338 1612 450
0.5 910 212 70 1208 324 70 910 212 1211 343 1563 458
0.6 847 220 75 1152 332 73 847 220 1168 356 1514 466
0.7 784 227 X 1095 340 X 784 227 1111 373 1466 474
0.8 720 235 X 1038 348 X 720 235 1066 373 1417 482
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Speed T5 - Cooling Speed
CFM Watts Rise CFM Watt s Rise CFM Watt s CFM Wat ts CFM Wat ts
20 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 21
Page 21
COMBUSTI ON
AIR INTAKE
EXHAUST FLU E HOOD
CONTROL WIRE ENTRANC E
POWER WI RE ENTRANC E
7 7/8
7 5/16
SUCTION/ LIQUID PRESS URE PORTS
BEHIND C OMPRESSOR ACCESS PANE L
HEAT EXCHANGE ACCESS PANEL
GAS SUPPLY ENTRANCE
CONDENSATE DRAIN C ONNECTION
3/4" NPT FEMALE
16 1/8
19 1/8
EVAPORATO R/CONTROL PANEL ACCESS P ANEL
4 3/4
B
7 15/16
16
B
5 1/2
1 3/8
16
2 3/4
A
18 7/16
FLUE EXHAUST
51
47
BLOWER A CCESS PA NEL
22
22
11
11
3
SUPPLY
RETURN
SUPPLY
RETURN
5 3/4
5 1/4
C
20
24
C
E
N
T
E
R
O
F
G
RA
V
I
T
Y
COMBUSTI ON AIR INTAKE
FLUE EXHAUST
HOOD
dimeNSioNS
Model
W" D" H"
Dimensions
Chassis
Size
DP14DM2406041A* 47 51 34¾ Med.
DP14DM2407041** 47 51 34¾ Med.
DP14DM3008041A* 47 51 34¾ Med.
DP14DM3009041** 47 51 34¾ Med.
DP14DM3608041A* 47 51 34¾ Med.
DP14DM3609041** 47 51 34¾ Med.
DP14DM3709041** 47 51 34¾ Med.
DP14DM4210041A* 47 51 42¾ Large
DP14DM4211541** 47 51 42¾ Large
DP14DM4810041A* 47 51 42¾ Large
DP14DM4811541** 47 51 42¾ Large
7”
Page 22
3
CONTROL
BOX
240
2
24V
208
TR
C
3
COMP
CM
PU
S RC
OR
BL BR
ROCW2W1
GY
T2
T1
L1
GND
C
L2
6
0
/
/
1
0
4
2
-
8
0
2
0140G01780-A
RD
DFT
RVC
RCCF
321
HPS
LPS
DF1 DF2
R-DFT
R
C
C
PS2
R-PS1
CCR
CNT
C-RV
O-RV
W
DFT
C
Y
DC
R
LVDR
HVDR
O
Y
CH
GR
BK
BK
RD
CHS
BL/PK
F
OL I H
ODF
L1
HI
Y2
Y1
G
W2
W1
C
R
ECON
LO COOL
HI HEAT
HI COOL
THERMOSTAT
FS
T1
LO
INDUCER
L2
PARK
24VAC COM
5
4
3
2
1
6
3
1
245
1
2
3
5
6
7
8
9
EM
N GL
T5 T4 T3 T2
T1
C
1
2
6 4
1
FS
LS
C
H
M
RS
VM
ALS
PS
GV
IGN
HC
F
LO HEAT
6
3
1
2
4
5
OR
BL
BL
YL
OR
BR
OR
P1 - PIN # 3
P1 - PIN # 7
P1 - PIN # 5
P1 - PIN # 2
PU
YL
P1 - PIN # 6
P1 - PIN # 9
YL
P1 - PIN # 8
RD
P1 - PIN # 1
BL
P1 - PIN # 5
BK
BL/PK
BL
OR
OR
OR
OR
RD
RD
RD
BL
BK
BK
RD
RD
PU
PU
RD
BL
BL
BL
BK
BK
BK
PU
BR
YL
WH
BR
YL
OR
OR
RD
RD
RD
PK
RD
PK
PU PU
PU
PU
YL
PU
YL
RD
BK
BK
BK
BK
PU
PU
P
U
R
D
B
K
R
D
R
D
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
B
L
Y
L
O
R
P
U
P
U
O
R
O
R
O
R
W
H
W
H
W
H
W
H
E
C
O
N
W
H
W
H
W
H
W
H
W
H
R
D
R
D
P
U
P
U
P
U
P
U
P
U
B
L
B
L
B
L
B
K
B
K
B
K
P
U
P
U
P
U
B
K
B
K
B
K
B
L
B
K
B
K
B
K
B
K
B
K
YL
YL
YL
P
U
R
D
B
L
W
H
B
R
G
R
Y
L
Y
L
P
U
Y
L
G
R
G
R
G
R
O
R
O
R
O
R
O
R
O
R
O
R
O
R
P
U
P
U
R
D
B
K
B
R
B
K
P
U
Y
L
W
H
IIC
D
R
O
T
P
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
SEE NOTE 5
SEE NOTE 6
SEE NOTE 7
SEE NOTE 8
SEE NOTE 9
B
K
R
D
Y
L
R
D
R
D
P
U
W
H
B
R
P
U
R
D
P
U
B
K
P
U
P
U
P
U
YL
YL
G
R
G
R
P
U
B
K
B
L
G
R
R
D
Y
L
/P
K
Y
L
/P
K
SEE NOTE 4
P2
P1
wiriNg diagram
⚡
High Voltage: Disconnect all power before servicing or installing this unit. Mulple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚠ Warning
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
22 www.daikincomfort.com SS-DP14DM SS-DP14DM www .daikincomfort.com 23
Page 23
0140G02004-A
G
ECON
ECON
6
5
1
COMPONENT LEGEND
ALS AUXI LLARY LIMIT SWITCH
C CO NTACTOR
CH CRANKCASE HEATER
CHS CRANKCASE HEATER SWITCH
CM CONDENSER MOTOR
COMP COMPRESSOR
DC DEFROST CONTROL BOARD
DFT DEFROST THERMOSTAT
DR DEFROST RELAY
ECON ECONOMIZER PLUG
EM EVAPORATOR MOTOR
F FUSE
FS FLAME SENSOR
GND EQUIPMENT GROUND
GV GAS VALVE
HPS HIGH PRESSURE SWITCH
IIC INTEGRATED IGNITION CONTROL
IGN
IGNITOR
LPS LOW PRESSURE SW ITCH
LS LIMIT SWITCH
OTP OUTDOOR THERMOSTAT PLUG
P1 9 PIN CONNECTO R PLUG
P2 6 PIN CONNECTO R PLUG
PS PRESSURE SWITCH
RCCF RUN CAPACITOR COMPRESSOR / FAN
RS ROLLOUT SW ITCH
RVC REVERSING VALVE COIL
TR TRANSFORMER
VM VENT MOTOR
FACTOR
Y WIRING
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF
INSULATION AS ORIGINAL (AT LEAST 1 0 5°C ) . USE CO PPER
CONDUCTOR ONLY.
2. FOR 208V TRANSFORMER OPERATION M OVE BLACK WIRE FROM
TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. FOR 208V VENT MOTOR OPERATION, REMOVE BLUE LEAD FROM
INDUCER LOW TERMINAL. MOVE BLACK LEAD FROM PARK TERMINAL
TO INDUCER LOW TERMINAL, AND PLACE BLUE LEAD ON PARK.
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WI RE.
5
. FOR ECONOMIZER, REMOVE PLUG FROM ECONOMIZER HARNESS.
CONNECT PLUG FROM ECONOMIZER TO HARNESS.
6. FOR OUTDOOR THERMOSTAT, R EMOVE PLUG FROM HARNESS AND
CONNECT PLUG FROM OUTDOOR THERMOSTAT T O HARNESS.
7. TO CHANGE AIRFLOW MOVE YELLOW WIRE (COOLING / HEAT PUMP),
WHITE WIRE (LOW STAGE GAS), O R BROWN WIRE (HI GH-STAGE GAS)
TO SPEED TAP T1, T2, T3, T4, OR T5 AT EVAPORATOR MOTOR.
REFER TO UNIT AIRFLOW TABLES FOR TO DETERMINE THE
APPROP
RIATE SPEED TAP FOR APPLICAT ION. UNITS SHIPPED WITH
YELLOW, WHITE, AND BROW N ON T4, T1, AND T2 RESPECTIVELY.
8. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY
EQUIPPED W HEN REQUIRED.
9. DOUBLE POLE CONTACTOR SHOW N. SINGLE POLE CONTACTOR
COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
LINE VOLTAGE
OPTIONAL HIGH
VOLTAGE
HIGH VOLTAGE
FIELD
WIRING
LOW VOLTAGE
LOW VOLTAGE
BK BLACK
W
IRE CODE
PK PINK
OR ORANGE
GR GREEN
BR BROW N
BL BLUE
RD RED
WH WHITE
YL YELLOW
PU PURPLE
COOL
HI HEAT
LO HEAT
P2
2
6
3
1
2
8
6
3
1
2
L1
L1
HI
LO
HI
DR
C
R
W
Y
O
C
HI
M
RS
PS
LS
ALS
TR
EM
VM
H
F
RCCF
C
L2
T2
208-230/1/60
CM
L1
R
T1
S
COMP
C
SUPPLY VOLTAGE
P1
-
REPLACE CONTROL
CHECK
CHECK FOR SHORTS IN
FLAME SENSOR WIRING
-
NORMAL FLAME PRESENT
DIAGNOSTIC
LED - AMBER
-
GAS PRESSURE
FLAME SENSOR
GAS VALVE
GAS FLOW
CHECK GAS VALVE
ON
OFF
1 FLASH
2 FLASHES
FALSE FLAME DETECTED
LOW FLAME SI GNAL
NO FLAME PRESENT
STATUS
CHECK
PSW/LOC OPEN
9 FLASHES
CHECK JUMPER BETWEEN
1 AND 4 ON 6-CIRCUIT
CONNECTOR IDT/ODT OPEN
8 FLASHES
CHECK AUXILIARY LIMIT SW.
CHECK MAIN LIMIT SWITCH
LIMIT OPEN 5 TIMES IN
SAME CALL FOR HEAT
3 MIN COMP. SHORT
CYCLE DELAY
COMPR. SHORT CYCLE DELAY
6 FLASHES
DIAGNOSTIC
LED - RED
7 FLASHES
STATUS
CHECK
DIAGNOSTIC
LED - RED
CHECK FOR SHORTS IN
FLAME SENSOR WIRING
CHECK GAS VALVE
CHECK ROLLOUT LIMIT SW.
CHECK AUXILIARY LIMIT SW.
CHECK MAIN LIMIT SWITCH
CHECK WIRING FOR SHO RTS
CHECK PRESSURE SWI TCH PRESSURE SWITC H CLOSED
CHECK VENT MOTOR
CHECK TUBING
CHECK FUSE(S)
CHECK INPUT POWER
-
GAS PRESSURE
FLAME SENSOR
GAS VALVE
GAS FLOW
CHECK PRESSURE SWITCH
OFF
ON
1 FLASH
3 FLASHES
2 FLASHES
4 FLASHES
5 FLASHES
FALSE FLAME DETECTED
OPEN LIMIT SW ITCH
WITHOUT INDUCER ON
PRESSURE SWITCH O PEN
IGNITION FAILURE
NORMAL OPERATION
NO POWER OR
INTERNAL CONTROL
FAULT
STATUS
CHECK
C
C
F
Y1
RC
W2
W1
TO
MICRO
TO
MICRO
L1
L2
CHECK OPTIONAL
REFRIGERANT SWITCHES
CHECK REFRIGERANT
SWITCHES FOR LOSS OF
CHARGE OR HIGH HEAD
PRESSURE
HPS
LPS
DF1
HVDR
DC
DF2
ODF
CHS
INDUCER
IIC
PARK
3
4
1
2
5
1
2
3
5
4
1
6
G
Y1
R
C
Y2
W2
O
OTP
3
2
1
2 3
4
T5
T1
T3
T2
EM
C
O-RV
CNT
C-RV
R-DFT
PS2
DC
R-PS1
RVC
DFT
C
DFT
LO
L2
L2
L2
L2
CH
GV
W1
R
C
W1 G Y1
Y2
W2
IIC
T4
+
+
THERMOSTAT
5
7
9
SEE NOTE 2
SEE NOTE 3
SEE NOTE 5
SEE NOTE 6
SEE NOTE 7
SEE NOTE 8
SEE NOTE 9
SEE NOTE 4
P9
wiriNg diagram (coNt.)
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
⚠ Warning
High Voltage: Disconnect all power before servicing or installing this unit. Mulple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Page 24
Accessories
Accessory
Description
Medium Chassis Large Chassis
Item Number
Concentric Kit CDK36 CDK4872
Downow Economizer DDNECNJPGMM DDNECNJPGML
Downow Internal Filter Rack DDNIFRPGA DDNIFRPGA
Downow Manual Damper DDN25FDPGCHMM DDN25FDPGCHML
Downow Motorized Damper DDN25MFDPGCHMM DDN25MFDPGCHML
Downow Square to Round SQRPG101/102 SQRPG103
External Horizontal Filter Rack DPHFRA DPHFRA
High-Altude Kit HA-03 HA-03
Horizontal Duct Cover 20464501NGK 20464502NGK
Horizontal Economizer DHZECNJPGCHM DHZECNJPGCHL
Horizontal Manual Damper DHZ25FDPGCHMM DHZ25FDPGCHML
Horizontal Motorized Damper DHZ25MFDPGCHMM DHZ25MFDPGCHML
Horizontal Square to Round SQRPGH101/102 SQRPGH103
Outdoor Thermostat with Housing OTDFPKG-01 OTDFPKG-01
LP Conversion Kit LPM-08 LPM-08
Roof Curb D14CRBPGCHMA D14CRBPGCHMA
Our connuing commitment to quality products may mean a change in specicaons without noce.
©2016 • Houston, Texas • Printed in the USA.
24 www.daikincomfort.com SS-DP14DM SS -DP14DM w w w .daikinc om f ort.c om PB