Goodman DP13CM3641A Installation Manual

Page 1
INSTALLATION INSTRUCTIONS
DP13C/DP13H 13 SEER “M” SERIES WITH R-410A
SELF -CONT AINED PACKAGE AIR CONDITIONERS AND HEA T PUMP UNITS
Index
TO THE INSTALLER............................................................................ 2
SHIPPING INSPECTION ................................................................... 2
REPLACEMENT PARTS .................................................................... 2
ORDERING PARTS ............................................................................ 2
SAFETY INSTRUCTIONS .................................................................. 2
CODES AND REGULATIONS ............................................................ 3
EPA REGULATIONS ........................................................................... 3
ATIONAL CODES ............................................................................. 3
N
MAJOR COMPONENTS ................................................................... 3
PRE-INSTALLATION CHECKS ............................................................ 3
CLEARANCES AND ACCESSIBILITY ............................................................. 3
UNIT LOCA TION................................................................................ 4
GROUND LEVEL PRE-INSTALLATION DETAILS................................................ 4
ROOF TOP PRE-INSTALLATION DETAILS ..................................................... 4
ROOF CURB INSTALLATIONS ONLY ........................................................... 4
IGGING DETAILS ............................................................................. 4
R
CIRCULATING AIR AND FILTERS ...................................................... 5
AIRFLOW CONVERSION ....................................................................... 5
DUCT WORK ................................................................................... 5
FILTERS ........................................................................................ 5
PIPING ........................................................................................... 6
CONDENSATE DRAIN ......................................................................... 6
WIRING.......................................................................................... 6
HIGH VOLTAGE WIRING ..................................................................... 7
OW VOLTAGE WIRING ...................................................................... 7
ATTENTION INSTALLING PERSONNEL:
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During in­stallation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of self contained package air conditioners and heating units. See the Specification Sheets applicable to your model for information regarding accessories.
*NOTE: Please contact your distributor or our website for the ap­plicable Specification Sheets referred to in this manual.
L
INTERNAL WIRING ............................................................................ 7
STARTUP, ADJUSTMENTS, AND CHECKS ......................................... 7
START-UP PROCEDURE AND CHECKLIST..................................................... 7
HEAT PUMP START-UP PROCEDURE ....................................................... 7
FINAL SYSTEM CHECKS ....................................................................... 8
COMPONENTS................................................................................ 8
CRANKCASE HEATER ......................................................................... 8
ONDENSER MOTOR ......................................................................... 8
C
COMPRESSOR ................................................................................. 8
CONTACT OR RELAY............................................................................ 8
DEFROST CONTROL ........................................................................... 8
OUTDOOR THERMOSTAT ..................................................................... 8
REVERSING VALVE COIL ...................................................................... 8
NDOOR BLOWER MOTOR ................................................................... 8
I
BLOWER INTERLOCK RELAY ................................................................... 9
IOD-3004 6/2013
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2013
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
Page 2
HEA T PUMP OPERATION................................................................. 9
C
OOLING CYCLE ............................................................................... 9
HEA TING CYCLE ............................................................................... 9
DEFROST CONTROL ........................................................................... 9
SUGGESTED FIELD TESTING/TROUBLE SHOOTING .......................................... 9
IRFLOW MEASUREMENT AND ADJUSTMENT ............................................ 10
A S
PEED TAP ADJUSTMENTS FOR INDOOR BLOWER MOTOR ............................ 12
REFRIGERANT CHARGE CHECKS ........................................................... 12
ELECTRICAL ADJUSTMENTS .......................................................... 11
MAINTENANCE............................................................................. 13
ERVICE ..................................................................................... 13
S
NADEQUAT E AIR VOLUME THROUGH INDOOR COIL ................................. 13
I
OUTSIDE AIR INTO RETURN DUCT .................................................... 13
UNDERCHARGE .......................................................................... 13
OOR “TERMINATING” SENSOR CONTACT ............................................ 13
P
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO: ..................... 13
TROUBLESHOOTING CHART ......................................................... 14
APPENDIX .................................................................................... 15
UNIT DIMENSIONS....................................................................... 15
MINIMUM CLEARANCES ............................................................... 16
RECOMMENDED FILTER SIZES ...................................................... 16
W ARNING
I
NSTALLATION AND REPAI R OF THIS UNIT SHOULD BE PERFORMED THE REQUIREMENTS OF AN SPECIFIED
R
EFRIGERATION INSTITUTE INSTALL RESULT
ONLY BY
BY
THE AIR-CONDITIONING
OR
REPAIR THIS UNIT WITHOUT SUCH BACKGROUND MAY
IN
PRODUCT DAMAGE, PERSONAL INJURY OR DEATH
INDIVIDUALS MEETING
“E
NTRY LEVEL TECHNICIAN” AS
, H
(AHRI). A
EATING, AND
TTEMPTING TO
AT A MINIMUM
(
)
.
REPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIR S
DAIKIN NORTH AMERICA LLC
7401 SECURITY W A Y
HOUSTON, TEXAS 77040
855-770-5678
SAFETY INSTRUCTIONS
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Fail­ure to heed safety information increases the risk of personal in­jury, property damage, and/or product damage.
W ARNING
TO THE INSTALLER
Carefully read all instructions for the installation prior to install­ing unit. Make sure each step or procedure is understood and any special considerations are taken into account before starting in­stallation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. After deciding where to install unit, closely look the loca­tion over - both the inside and outside of home. Note any poten­tial obstacles or problems that might be encountered as noted in this manual. Choose a more suitable location if necessary.
IMPORTANT NOTE: If a crankcase heater is used, the unit should be energized 24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor. Com­pressor damage may occur if this step is not followed.
Before using this manual, check the serial plate for proper model identification.
The installation and servicing of this equipment must be performed by qualified, experienced technicians only.
SHIPPING INSPECTION
Upon receiving the unit, inspect it for damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, specifications, electrical characteristics and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer assumes no responsibility for instal­lation of incorrectly shipped units.
WARNING
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING
THIS UNIT. TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
WARNING
CONNECTING UNIT DUCT WORK TO UNAUTHORIZED HEAT PRODUCING DEVICES
SUCH AS A FIREPLACE INSERT, STOVE, ETC. MAY RESULT IN PROPERTY DAMAGE, FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR DEATH.
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
2
Page 3
WARNING
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE
T
I
THIS UNIT IF ANY PART HAS BEEN UNDER WATER. QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER.
MMEDIATELY CALL A
WARNING
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUI DS OR VA PORS I N THE V ICINITY OF THIS APPLI ANCE.
CODES AND REGULATIONS
EPA REGULATIONS
IMPORT A NT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EP A) HAS
ISSUED
VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND DISPOSAL OF
REFRIGERANTS ENVIRONMENT REGULATIONS TECHNICIAN QUESTIONS
IN THIS UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY HARM THE
AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL FINES. BECAUSE
MAY VARY DUE TO PASSA GE OF NEW LAWS, WE SUGGEST A CERTIFIED
PERFORM ANY WORK DONE ON THIS UNIT. SHOULD YOU HAVE ANY
PLEASE CONTACT THE LOCAL OFFICE OF THE EP A.
NATIONAL CODES
This product is designed and manufactured to permit installation in accordance with National Codes. It is the installer’s responsi­bility to install the product in accordance with National Codes and/or prevailing local codes and regulations.
MAJOR COMPONENTS
The unit includes a hermetically sealed refrigerating system (con­sisting of a compressor, condenser coil, evaporator coil with flow­rator), an indoor blower, a condenser fan and all necessary inter­nal electrical wiring. The heat pump also includes a reversing valve, solenoid, defrost thermostat and control and loss of charge protection. The system is factory-evacuated, charged and perfor­mance tested. Refrigerant amount and type are indicated on rat­ing plate.
The DP13CM/DP13HM M-series air conditioners and heat pumps are designed for OUTDOOR USE ONLY. DP13HM M-Series is avail­able in cooling capacities of 2, 2-1/2, 3, 3-1/2, 4 and 5 nominal tons of cooling. DP13CM M-Series is available in cooling capacities of 3, 4 and 5 nominal tons of cooling. Optional field installed heat kits are available in 5,8,10,15 and 20 kW. 3 phase heat kits are available only in 15 and 20 kW. The units can be easily installed in manufactured or modular homes with existing high-static duct work. The units can also be easily converted to accommodate a plenum for normal or low-static applications. The DP13CM/DP13HM M-series are self contained packaged units so the only connec­tions needed for installation are the supply and return ducts, the line and low voltage wiring and drain connection. Rated perfor­mance is achieved after 72 hours of operation. Rated perfor­mance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specifica­tion sheet for packaged and light commercial models. Specifica­tion sheets can be found at
www.daikincomfort.com for Daikin
brand products. Within the website, please select the residential or commercial
products menu and then select the submenu for the type of prod­uct to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
The information on the rating plate is in compliance with the FTC & DOE rating for single phase units. The three phase units in this series are not covered under the DOE certified program. The effi­ciency ratings of these units are a product of thermal efficiency determined under continuous operating conditions independent of any installed system.
PRE-INSTALLATION CHECKS
Before attempting any installation, the following points should be considered:
• Structural strength of supporting members
• Clearances and provision for servicing
• Power supply and wiring
• Air duct connections
• Drain facilities and connections
• Location may be on any four sides of a home, manufactured or modular, to minimize noise
CLEARANCES AND ACCESSIBILITY
The unit is designed to be located outside the building with un­obstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for service and installa­tion. Condenser air enters from three sides. Air discharges up­ward from the top of the unit. Refrigerant gauge connections are made on the right side of the unit as you face the compressor compartment. Electrical connections can be made either on the right, bottom or duct panel side of the unit. The best and most common application is for the unit to be located 10” from wall (4” minimum) with the connection side facing the wall. This “close to the wall” application minimizes exposed wiring.
Close to the wall application assures free, unobstructed air to the other two sides. In more confined application spaces, such as corners provide a minimum 12” clearance on all air inlet sides. Allow 36” minimum for service access to the compressor compart­ment and controls. The top of the unit should be completely unob­structed. If units are to be located under an overhang, there should be a minimum of 48” clearance and provisions made to deflect the warm discharge air out from the overhang.
3
Page 4
UNIT LOCATION
Consider the affect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away. Consideration should also be given to shade and unit appearance.
Heat pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continu­ous subfreezing temperatures. Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accu­mulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum 2" clearance under the outdoor coil is required in the milder climates.
GROUND LEVEL PRE-INSTALLATION DETAILS
The unit should be set on a solid, level foundation - preferably a concrete slab at least 4 inches thick. The slab should be above ground level and surrounded by a graveled area for good drain­age. Any slab used as a unit’s foundation should not adjoin the building as it is possible that sound and vibration may be trans­mitted to the structure.
Rooftop Installation
ROOF CURB INSTALLATIONS ONLY
NOTE: Sufficient structural support must be determined prior to
locating and mounting the curb and package unit.
Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor.
Curbing must be installed in compliance with the National Roof­ing Contractors Association Manual. Construct duct work using cur­rent industry guidelines. The duct work must be placed into the roof curb before mounting the package unit.
Ground Level Installation
ROOF TOP PRE-INSTALLATION DETAILS
Ensure that the roof is weather tight and allows proper drainage of condensation. Use steel or treated wood beams as unit sup­port for load distribution.
NOTE: To ensure proper condensate drainage, unit must be in­stalled in a level position.
To avoid possible property damage or personal injur y, the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
Roof Curb Installation
RIGGING DETAILS
WARNING
O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
T
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.
T
O FACILITATE
WARNING
O AVOID POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH,
T
ENSURE THE ROOF HAS SUFFICIENT STRUCTURAL STRENGTH TO CARRY THE WEIGHT OF THE UNIT(S), ROOF CURB, SNOW LOADS, AND WATER LOADS AS REQUIRED BY LOCAL CODES. DETERMINE THE WEIGHT CAPABILITIES OF THE ROOF.
CONSULT A STRUCTURAL ENGINEER TO
4
Page 5
CAUTION
O AVOID POSSIBLE PERSONAL INJURY, A SAFE, FLAT SURFACE FOR SERVICE
T
PERSONNEL SHOULD BE PROVIDED.
IMPORTANT: If using bottom discharge with roof curb, duct work should be attached to the curb prior to installing the unit.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.
Return
Supply
Remove these panels for downflow duct applications
Duct Cover Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit #20464501NGK (medium chassis) and #20464502NGK (large chassis).
Rigging
CIRCULATING AIR AND FILTERS
AIRFLOW CONVERSION
Units can easily be converted from horizontal to down-discharge airflow delivery. In down-discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installa­tion. In some installations it will be necessary to change the blower speed to provide proper air flow.
Horizontal Air Flow (Applies to 3 phase models)
Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Daikin’s Service Parts department.
DUCT WORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Duct work should be designed in accordance with the recommended meth­ods of Air Conditioning Contractors of America Manual D (Resi­dential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate in­sulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pam­phlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimen­sion illustration in the appendix.
For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Duct work dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
Remove these covers for horizontal duct applications
FILTERS
CAUTION
T
O PREVENT PRO PERTY DAMAG E DUE TO FIRE AND LOSS O F EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.
5
Page 6
Filters are not provided with unit and must be supplied and exter­nally installed in the return duct system by the installer. An op­tional factory approved internal filter rack may also be used. A field-installed filter grille is recommended for easy and conve­nient access to the filters for periodic inspection and cleaning. When installing filters, ensure the air flow arrows on the filter are pointing toward the circulator blower.
Refer to the unit filter size chart below for filter size information.
MINIMUM FILTER SIZ E
NOMINAL SIZE
(INCHES)
10x20 1.4 14x20 1.9 14x25 2.4 15x20 2.1 16x20 2.2 16x25 2.8 20x20 2.8 20x25 3.5 25x25 4.3
NOTE: Filters must have adequate face area for the rated quantity of the unit. See the air delivery table below for recommended filter size. Size the filters in accordance with their manufacturer recommendations. Throwaway filters must be sized for a maxi­mum face velocity of 300 feet per minute.
NOMINAL AREA
(SQ. FT.)
Consult your local Power Company to determine the availability of sufficient power to operate the unit. Check the voltage, frequency, and phase at the power supply to ensure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT.
In accordance with the N.E.C. or local codes, install a branch circuit fused disconnect near the unit. Determine wire sizes and overcur­rent protection from the unit nameplate ampacity and in accor­dance with the Branch Circuit Ampacity table on the next page or the N.E.C. The wiring should never be sized smaller than is recom­mended by either of these two sources.
Fuses smaller than that recommended on the rating plate could result in unnecessary fuse failure or service calls. The use of protective devices of larger size than indicated could result in extensive damage to the equipment. The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for ship­ment. This equipment has been started at minimum rated voltage and checked for satisfactory operation. Do not attempt to operate this unit if the voltage is not within the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit. The unit must be permanently grounded in accordance with local codes, or in absence of local codes, with N.E.C ANSI/ NFPA NO. 70­1984 or latest edition by using ground lug in the control box.
7
a e
r
6
t
A
e
r
e
e
t
F
l
5
i
e
F
r
l
a
a
u
n
4
q
i
S
m o N
3
B
A
S
O
P
S
I
D
R
E
T
L
I
F
E
L
P
N
E
N
A
M
R
E
R
E
T
L
I
F
T
2
500 1000 1500 2000 2500 3000 3500
Airflow - SCFM
PIPING
CONDENSATE DRAIN
The condensate drain connection of the evaporator is a half cou­pling of ¾” N.P.T. A trap must be provided to have Proper conden­sate drainage.
Unit
Drain Connection
Flexible Tubing-Hose Or Pipe
A Positive Liquid Seal Is Required
2" Minimum
3" Minimum
Fuses or HACR type circuit breakers may be used where codes permit.
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
RW
G
CONTACTOR
24 VOLT CONTR OL WIRING
L3 CONNECTION - 3 PHASE ONLY
*NOTE:
LOW VOLTAGE CONNECTORS do not apply to heat pumps with
See *NOTE
W
R
G
electric heat. LOW VOLTAGE CONNECTORS apply ONLY to DP13C units with electric heat.
IMPORTANT NOTE: Some single phase units are equipped with a
single-pole contactor. Exercise caution when servicing as only one leg of the power supply is broken with the contactor.
To wire the unit, make the following high and low voltage connec­tions.
Install condensate drain trap as shown. Use ¾ “ drain connection size or larger. Do not operate without trap. Unit must be level or slightly inclined toward drain.
WIRING
NOTE: All wiring should be made in accordance with the National Electrical Code.
6
Page 7
BRANCH
CIRCUIT AMPACI TY
SUPPLY WIRE LENGTH
(FEET)
200 64443322 150 86644433 100 108866644
50 14 12 10 10 8 8 6 6
15 20 25 30 35 40 45 50
HIGH VOLTAGE WIRING
• Single Phase- Two leads should be connected to terminals L1 & L2 in the electrical control section, using wire sizes specified in wiring table.
• Three Phase- Three leads should be connected to terminals L1, L2 and L3 in the electrical control section, using wire sizes specified in wiring table.
LOW VOLTAGE WIRING
• Air Conditioners- Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18 AWG as follows:
LEAD THERMOSTAT
Red R (24V)
Green G (Fan)
Yellow Y (Cool)
White W1 (Heat)*
Brown W2 ( Heat)*
• Heat Pumps- Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18 AWG as follows:
TERMINAL THERMOSTAT
Red R (24V)
Green G (Fan)
Orange O (Rev. Valve)
White W1 (Heat, 2nd)*
Brown W2 (Heat, 3rd)*
Yellow Y (Cool)
C (Blue) C (C ommon)
*Optional field installed heat connections
INTERNAL WIRING
A diagram detailing the internal wiring of this unit is located on the electrical box cover. If any of the original wire supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models. See wir­ing diagram for 208 volt wiring.
1. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined using the circuit ampacity found on the unit rating plate and the table below. From the unit disconnect to unit, the smallest wire size allowable may be used for the ampacity, as the Disconnect must be in sight
of the unit.
2. Wire size based on 60° C rated wire insulation and 30° C Ambient Temperature (86° F).
3. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.
STARTUP, ADJUSTMENTS, AND CHECKS
WARNING
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING
THIS UNIT. TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
START-UP PROCEDURE AND CHECKLIST
With power turned off at all disconnects:
1. Turn thermostat system switch to “COOL” and fan switch to
2. Inspect all registers and set them to the normal open
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blower should
5. Turn the fan switch to “AUTO” position. The blower should
6. Slowly lower the cooling temperature until the unit starts.
7. Turn the temperature setting to the highest position,
8. Turn the thermostat system switch to “OFF” and disconnect
HEAT PUMP START-UP PROCEDURE
1. Check the cooling mode for the heat pump in the same
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
“AUTO”. Next, turn the temperature setting as high as it will go.
position.
operate after a 7-second delay.
stop after a 65-second delay.
The compressor, blower and fan should now be operating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.
stopping the unit. The indoor blower will continue to run for 65-seconds.
all power when servicing the unit.
manner as above. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contactor is energized. The compressor, blower and fan should then be running. After the cooling mode is checked out, turn the thermostat system switch to “OFF”.
7
Page 8
2. Turn the thermostat system switch to “HEAT” and fan switch to “AUTO”.
3. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting. The compressor, blower and fan should now be running with the reversing valve in the de­energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.
4. If the outdoor ambient is above 80°F, the unit may trip on its high pressure cut out when in heating. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable. DO NOT FAIL TO TEST.
5. If the outdoor ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation by blocking off the indoor return air until the unit trips.
6. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly.
NOTE: If outdoor thermostats are installed, the outdoor ambient must be below the set point of these thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.
7. For thermostats with emergency heat switch, return to step
6. The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on. 3-phase models are single stage heat only.
8. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely.
FINAL SYSTEM CHECKS
1. Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling.
2. Check for air leaks in the ductwork.
3. See Sections on Air Flow Measurement and Adjustment and
Checking Charge.
4. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges. If so, correct the trouble.
5. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.
6. Be sure the Owner is instructed on the unit operation, filter, ser vicing, correct thermostat operation, etc.
The foregoing “Start-up Procedure and Check List” is recommended to serve as an indication that the unit will operate normally.
COMPONENTS
CRANKCASE HEATER
This item is “ON” whenever power is supplied to the unit and the crankcase heater thermostat is closed. Crankcase heater thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage. The insert type heater is self regulating. It is connected electrically to the contactor L1 and L2 terminals.
CONDENSER MOTOR
This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation.
COMPRESSOR
This item is activated by the contactor for heating and cooling, except during emergency heat. It is protected by an internal over­load.
CONTACTOR RELAY
This control is activated by the thermostat (24V coil) and supplies power to the compressor and condenser fan motor.
DEFROST CONTROL
The Defrost control provides time/temperature initiation and ter­mination of the defrost cycle. When a Defrost cycle is initiated, the defrost control shifts the reversing valve to “COOLING” mode, stops the outdoor fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on charge or outdoor conditions are severe. (windy and cold). The defrost control also provides for a 3 minute off cycle compressor delay.
OUTDOOR THERMOSTAT
These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0° F-to 45° F). They are nor­mally open above their set points and closed below to permit staging of indoor supplement heater operation. If the outdoor ambient temperature is below 0° F (-18° C) with 50% or higher RH, an outdoor thermostat (OT) must be installed and set at (0°) on the dial. Failure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer’s warranty.
REVERSING VALVE COIL
This coil is activated by the thermostat, in the cooling mode and during defrost. It positions the reversing valve pilot valve for cool­ing operation.
INDOOR BLOWER MOTOR
This is activated by the room thermostat by COOLING or FAN ON position. The motor is energized through the EBTDR for PSC motors and directly by the room thermostat for EEM motors (4 or 5 Ton units). EEM motors are constant torque motors with very low power consumption. This motor is energized by a 24V signal from the thermostat. (See Air Flow Measurement and Adjustment for speed adjustment instructions).
8
Page 9
BLOWER INTERLOCK RELAY (SINGLE PHASE PSC MODELS ONLY)
This relay is used to energize the blower during the electric heat operation. Some room thermostats do not energize the motor dur­ing electric heat. This relay insures blower operation when the room thermostat energizes heat. This relay has a 240 volt coil and an 8 amp contact relay. This relay is energized by the electric heat kit sequencer.
HEAT PUMP OPERATION
COOLING CYCLE
When the heat pump is in the cooling cycle, it operates exactly as a Summer Air Conditioner unit. In this mode, all the charts and data for service that apply to summer air conditioning apply to the heat pump. Most apply on the heating cycle except that “condenser” becomes “evaporator”, “evaporator” becomes “condenser”, “cool­ing” becomes “heating”.
HEATING CYCLE
The heat pump operates in the heating cycle by redirecting refrig­erant flow through the refrigerant circuit external to the compres­sor. This is accomplished with the reversing valve. Hot discharge vapor from the compressor is directed to the indoor coil (evapora­tor on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve.
The following figures show a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system.
The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow.
When the heat pump is in the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil tem­perature, the greater the heating capacity of the heat pump. This phenomenon is a characteristic of a heat pump. It is a good practice to provide supplementary heat for all heat pump instal­lations in areas where the temperature drops below 45° F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a compo­nent failure of the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the refrigerant in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the out­door coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run and the supplementary heaters are energized.
DEFROST CONTROL
During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30, 60 and 90 minutes may be selected by setting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 31° F), and when the wall thermostat calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 75° F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor temperature, a twelve minute override interrupts the unit’s defrost period.
SUGGESTED FIELD TESTING/TROUBLE SHOOTING
1. Run unit in the heating mode (room thermostat calling for heat).
2. Check unit for proper charge. Note: Bands of frost on the
condenser coil indicate low refrigerant charge.
3. Shut off power to unit.
4. Disconnect outdoor fan by removing the outdoor fan motor wire from “DF2” on defrost control.
5. Restart unit and allow frost to accumulate.
9
Page 10
6. After a few minutes of operation, the unit’s defrost thermostat should close. To verify this, check for 24 volts between “DFT” and “C” on board. If the temperature at the thermostat is less than 28° F and the thermostat is open, replace the unit’s defrost thermostat, as it is defective.
7. When the unit ’s defrost thermostat has closed, short the test pins on the defrost board until the reversing valve shifts, indicating defrost. This should take up to 22 seconds depending on what timing period the control is set on. After defrost initiation, the short must instantly be removed or the unit’s defrost period will only last 3 seconds.
8. The control is shipped from the factory with the compressor delay option selected. This will de-energize the compressor contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to Normal, the compressor will continue to run during defrost initiation and defrost termination. The control will also ignore the low pressure switch connected to R-PS1 and PS2 for 5 minutes upon defrost initiation and 5 minutes after defrost termination.
9. After the unit ’s defrost thermostat has terminated, check the defrost thermostat for 24 volts between “DFT” and “C”. The reading should indicate 0 volts (open sensor).
10. Shut off power to unit.
11. Replace outdoor fan motor lead to terminal “DF2” on defrost board and turn on power.
AIRFLOW MEASUREMENT AND ADJUSTMENT
After reviewing Duct Work section, proceed with airflow measure­ments and adjustments. The unit blower curves (see Specifica­tion Sheets) are based on external static pressure (ESP per in/wc). The duct openings on the unit are considered internal static pres­sure. As long as ESP is maintained, the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application (i.e. home, building, etc.)
Generally, 400 CFM per ton of cooling capacity is a rule of thumb. Some applications depending on the sensible and latent capacity requirements may need only 350 CFM or up to 425 CFM per ton. Check condition space load requirements (from load calculations) and equipment expanded ratings data to match CFM and capacity.
After unit is set and duct work completed, verify the ESP with a 1-inch inclined manometer with pitot tubes or a Magnahelic gauge and confirm CFM to blower curves in the Specification Sheets. All units have three-speed blower motors. If low speed is not uti­lized, the speed tap can be changed to medium or high speed.
NOTE: Never run CFM below 350 CFM per ton, evaporator freezing or poor unit performance is possible.
10
Page 11
Model Speed Volts
230
230
230
230
230
230
230
230
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
DP13CM3641*
DP13CM4841*
DP13CM6041*
DP13CM3643*
DP13CM4843*
DP13CM6043*
LOW
MED
HIGH 230
T1
T2/T3
T4/T5
T1
T2/T3
T4/T5
E.S.P (In. of H
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1122 1078 1032 972 915 804 687 558
338 330 321 310 300 283 264 250
1387 1331 1264 1209 1119 1041 935 748
456 440 428 412 399 382 363 330
1521 1454 1388 1311 1230 1144 1055 939
534 521 510 490 477 461 442 420
1451 1404 1356 1309 1262 1215 1168 1121
255 264 273 282 291 299 308 317
1809 1762 1715 1667 1620 1573 1526 1479
444 453 462 471 479 488 497 506
1885 1838 1790 1743 1696 1649 1602 1555
484 493 502 510 519 528 537 546
1774 1731 1688 1645 1602 1559 1515 1472
444 453 463 473 483 493 503 512
1891 1848 1804 1761 1718 1675 1632 1589
515 525 535 544 554 564 574 584
2105 2062 2018 1975 1932 1889 1846 1803
646 656 666 676 686 696 705 715
O)
2
NOTES:
Data shown is dry coil.
Wet coil pressure drop is approximately:
0.1” H
0, for two-row indoor
2
coil;
0.2” H2O, for three-row indoor coil;
and 0.3” H20, for four-row indoor coil.
• Data shown does not include filter pressure drop, approx.
0.08” H20.
• Reduce airflow by 2% for 208­volt operation.
Model Speed Volts
Low 230
Med 230
DP13HM2441*
High 230
Low 230
Med 230
DP13HM3041*
High 230
T1 230
T2/T3 230
DP13HM3641*
DP13HM3643*
T4/T5 230
Low 230
Med 230
DP13HM4241*
High 230
T1 230
T2/T3 230
DP13HM4841*
DP13HM4843*
T4/T5 230
T1 230
T2/T3 230
DP13HM6041*
DP13HM6043*
T4/T5 230
E.S.P (In. of H
O)
2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 667 596 -------- -------- -------- -------- -------- --------
WATTS 153 150 --- ----- -------- -------- -------- -------- --------
CFM 897 841 784 713 610 -------- -------- --------
WATTS 233 229 224 217 207 -------- -------- --------
CFM 1242 1181 1122 1057 982 883 719 617
WATTS 373 364 354 344 333 318 298 284
CFM 1097 1059 1016 959 901 818 648 562
WATTS 337 330 324 315 305 290 271 257
CFM 1253 1204 1148 1097 1033 952 777 670
WATTS 397 388 379 369 356 342 313 297
CFM 1448 1380 1323 1258 1194 1106 1008 864
WATTS 499 483 472 459 446 427 410 382
CFM 867 789 711 632 554 --- --- ---
WATTS 77 84 90 97 103 --- --- ---
CFM 1272 1222 1173 1123 1074 1024 974 925
WATTS 233 230 236 243 249 256 262 269
CFM 1446 1396 1347 1297 1248 1198 1148 1099
WATTS 287 293 300 306 313 319 326 332
CFM 1122 1078 1032 972 915 804 687 558
WATTS 338 330 321 310 300 283 264 250
CFM 1387 1331 1264 1209 1119 1041 935 748
WATTS 456 440 428 412 399 382 363 330
CFM 1521 1454 1388 1311 1230 1144 1055 939
WATTS 534 521 510 490 477 461 442 420
CFM 1451 140 4 1356 1309 1262 1 215 1168 1121
WATTS 255 264 273 282 291 299 308 317
CFM 1809 176 2 1715 1667 1620 1 573 1526 1479
WATTS 444 453 462 471 479 488 497 506
CFM 1885 183 8 1790 1743 1696 1 649 1602 1555
WATTS 484 493 502 510 519 528 537 546
CFM 1774 173 1 1688 1645 1602 1 559 1515 1472
WATTS 444 453 463 473 483 493 503 512
CFM 1891 184 8 1804 1761 1718 1 675 1632 1589
WATTS 515 525 535 544 554 564 574 584
CFM 2105 206 2 2018 1975 1932 1 889 1846 1803
WATTS 646 656 666 676 686 696 705 715
11
Page 12
SPEED TAP ADJUSTMENTS FOR INDOOR BLOWER MOTOR
PSC Motor
Adjust the CFM by changing the speed tap of the indoor blower motor at the EBTDR “COM” connection with one of the speed taps on “M1” or “M2”. (Black-High Speed, Blue-Medium Speed, Red-Low Speed.)
EEM Motor
Adjust the CFM by changing the 24V low voltage lead at the speed terminal block on the motor. (T1-Low Speed, T2 and T3-Medium Speed, T4 and T5-High Speed).
REFRIGERANT CHARGE CHECKS
After completing airflow measurements and adjustments, the unit’s refrigerant charge must be checked. All package units are charged to the superheat method at the compressor suction line (these are fixed orifice devices). After superheat is adjusted it is recom­mended to check unit sub-cooling at the condenser coil liquid line out. For charge adjustments, see superheat and subcooling charts shown for each model.
SUPERHEAT CAN BE DETERMINED AS FOLLOWS:
1. Read suction pressure. Determine Saturated Suction Temperature from tables or pressure gauge saturated temperature scale (R-410A).
2. Read suction line temperature.
3. Use the following formula:
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
SATURATED
SUCTION
PRESSURE
SUCTION
TEMPERATURE
SUCTION
PRESSURE
ºF
PSIG R-410A PSIG R-410A
50 1 78 20 52 3 80 21 54 4 56 6 58 7 60 8 62 10 64 11 66 13 68 14 70 15 72 16 74 17
85 24 90 26
95 29 100 31 110 36 120 41 130 45 140 49 150 53 160 56 170 60
76 19
Suction Pressure Temperature (R-410A)
SUBCOOLING = SAT. LIQUID TEMP. - LIQUID LINE TEMP.
SATURATED
SUCTION
TEMPERATURE
ºF
SATURATED LIQUID PRESSURE
TEMPERATURE C HART
SATURATED
LIQUID
PRESSURE
PSIG R-410A PSIG R-410A
200 70 375 112 210 73 405 118 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108
Liquid Pressure Temperature (R-410A)
LIQUID
TEMPERATURE
ºF
LIQUID
PRESSURE
415 119 425 121 435 123 445 125 475 130 500 134 525 138 550 142 575 145 600 149 625 152
SATURATED
LIQUID
TEMPERATURE
ºF
DESIGN SUPERHEAT @ 95 °F
OUTDOOR AMBIENT TEMPERATURE
Model # SUPERHEAT ± 2°F DP13CM3641/43 9 DP13CM4841/43 13 DP13CM6041/43 11 DP13HM2441 13 DP13HM3041 10 DP13HM3641/43 6 DP13HM4241 13 DP13HM4841/43 13 DP13HM6041/43 10
ELECTRICAL ADJUSTMENTS
This series of electric cooling and, heat pump package equipment is designed to accept a field installed electric heat kit. The unit is equipped to easily install the HKP or HKR Series single phase and HKR3 Series 208-230 volt three phase Electric Heat Kits. Full Instal­lation Instructions are included in this kit. Please use this docu­ment for guidance in field equipping the package unit with elec­tric heat.
Choose the heat kit that fits the application for the specific instal­lation. Permanently mark the unit’s nameplate with the model being installed. High and low voltage connections are detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be modi­fied to accommodate normal continuous operation to prevent a nuisance trip. See following table.
12
Page 13
ELECTRIC HEAT KW
UNIT MODEL # 5 8 10 15 20
DP13HM2441** DP13HM3041** DP13[H or C]M3641** DP13HM4241** DP13[H or C]M4841** DP13[H or C]M6041**
M M
M
(F) (F)
(F)
M
(F)
MM MM
3
(F)
3
(F)
3
(F)
3
(F)
M M
H
(F)
H
(F)
3
(F)
3
(F)
(F) (F)
H H 3 3
HNA HNA
NA
(F)
NA
(F)
3
(F) (F)
(F)
3
(F)
ELECTRIC HEAT KW
DP13CM3643** DP13CM4843** DP13CM6043** DP13HM3643** DP13HM4843** DP13HM6043**
*(F) - Factory Setting Speed Taps Description: H / 4, 5 - High; M / 2, 3 - Medium; L / 1 - Low 3 speed (H)igh/(M)edi u m /( L )ow : P SC motor 4 speed (H)igh/(ML)Medium Low/ (MH) Medium High/(L)ow: PSC motor 1/2/3/4/5: EEM motor
--- --- ---
--- --- ---
--- --- --­MM
3
(F)
3
(F)
3
(F)
3
(F)
H
3 3
H 3 3 H
(F)
3
(F)
3
(F)
NA
(F)
3
(F) (F) (F) (F) (F)
3 NA 3 3
(F) (F)
(F) (F)
MAINTENANCE
WARNING
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING
THIS UNIT. TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
The Self Contained Package Air Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly. However it is recommended that the home­owner inspect the unit before a seasonal start up. The coils should be free of debris so adequate airflow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced. These few steps will help to keep the product up time to a maximum. The Troubleshooting Chart (on page 14) should help in identifying problems if the unit does not operate properly.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
OUTSIDE AIR INTO RETURN DUCT
Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop below 65° F. Air below this temperature will cause low dis­charge pressure, thus low suction pressure, and excessive defrost cycling resulting in low heating output. It may also cause false defrosting.
UNDERCHARGE
An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil.
POOR “TERMINATING” SENSOR CONTACT
The unit’s defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor contact may not termi­nate the unit’s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure.
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO:
1. Solenoid not energized - In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.
2. No voltage at unit’s solenoid - Check unit voltage. If no voltage, check wiring circuit.
3. Valve will not shift:
a. Undercharged - check for leaks; b. Valve Body Damaged - Replace valve; c. Unit Properly Charged - If it is on the heating cycle, raise
the discharge pressure by restricting airflow through the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. DO NOT TAP THE VALVE BODY. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off and wait until the discharge and suction pressure equalize, and repeat above steps. If the valve does not shift, replace it.
SERVICE
THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIP­MENT.
Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle.
INADEQUATE AIR VOLUME THROUGH INDOOR COIL
When a heat pump is in the heating cycle, the indoor coil is func­tioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cut out.
13
Page 14
TROUBLESHOOTING CHART
g
g
p
p
g
p
p
p
p
g
prop
SYMPTOM
High head - low suction a. Restriction in liquid line or flowrator a. Remove or replace with proper size flowrator. High head - high or normal suction a. Dirt y condenser coil a. Clean coil.
Low head - high suction
Unit will not run
Condenser fan runs, compressor doesn't
b. Overchar c. Condenser fan not runnin a. Incorrect flowrator a. Re b. Defective com c. Flowrator not seating properly c. Check for debris under flowrator or deformed
d. Defective reversing valve d. Replace reversing valve. a. Power off or loose electrical connection a. Check for unit voltage at contactor in unit.
b. Thermostat out of calibration set too hi c. Defective contactor c. Check for 24 volts at contactor coil replace if
d. Blow n fuses or tripped breaker d. Replace fuse or reset breaker.
e. Transformer defective e.
f. High or low pressure control open
(Optional)
g. Compressor overload contacts open g. Replace compressor.
a. Loose connection a. Check for unit voltage at compressor check &
b. Compressor stuck, grounded or open
winding open internal overload
c. Low voltage connection c. At compressor terminals, voltage must be within
ed b. Correct System charge.
c. Repair or Replace.
lace with correct flowrator.
ressor valves b. Repla ce compressor.
flowrator. Remove debris or replace flowrator.
h b. Reset.
contacts are open.
Check wiring - replace transformer.
f. Reset high pressure control or check unit charge.
High pressure control opens at 610 psig. Low
ressure control opens at 22 psig.
NOTE: Wait at least 2 hours for overload to reset.
tight en all connections.
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
10 % of nameplate volts when unit is operating.
REMEDYPOSSIBLE CAUSE
d. Capacitor weak, open, or shorted d. Check capacitor. If defective, replace.
Low suction - cool compressor a. a. Iced evaporator coil Compressor short cycles
Registers sweat Low airflow
High suction pressure
Insufficient cooling
Low indoor airflow
a. Defective overload protector a. Replace - check for correct voltage. b. Unit cycling on low pressure control b. Check refrigerant charge and / or airflow.
a. a. Increase s
a. Excessive load a. Recheck load calculation. b. Defective com c. Reversin a. Im b. Improper airflow b. Check - should be approximately 400 CFM per
c. Incorrect refrigerant charge. c. Charge per procedure attached to unit service
d. Incorrect voltage d. At compressor terminals, voltage must be within
erly sized unit a. Recalculate load.
ressor b. Replace.
valve not seating properly.c.Replace.
14
Increase speed of blower or reduce restriction ­replace air filters.
eed of blower or reduce restriction
re
lace air filters.
ton.
panel.
10% of nameplate volts when unit is operating.
Page 15
47
47
APPENDIX
UNIT DIMENSIONS
POWER
POWER WIRE
WIRE ENTRANCE
ENTRANCE
4 1/8
4 1/8
2 1/8
2 1/8
6 ½
6 ½
1 3/8
1 3/8
16
16
8
8
51
51
5 ½
5 ½
?
?
A
16
16
B
B
A
2 34
2 34
SUCTION/LIQUID
SUCTION/LIQUID PRESSURE PORT
PRESSURE PORT
CONDENSATE
CONDENSATE DRAIN
DRAIN CONNECTION
CONNECTION 3/4” NPT FEMALE
3/4” NPT FEMALE
MEDIUM CHASSIS
DP13*M244** DP13*M304** DP13*M364** DP13*M424**
LARGE CHASSIS
DP13*M484** DP13*M604**
18 7/8
18 7/8
?
?
B
B
3
3
CONTROL
CONTROL WIRE
WIRE ENTRANCE
ENTRANCE
SUPPLY
SUPPLY
RETURN
RETURN
BLOWER
BLOWER ACCESS PANEL
ACCESS PANEL
15
Page 16
12” MIN
36” MIN (F OR SERVICE)
MINIMUM CLEARANCES
48” MIN
.
4”
MIN
12” MIN
36” MIN
(FOR SERVICE)
NOTE: Roof overhang should be no m or e than 36”
RECOMMENDED FILTER SIZES
UNIT 2 ton 2-1/2 ton 3 ton 3-1/2 ton 4 ton 5 ton
Min. Filter Size (1) 25x25x 1 (1) 25x25x1 (1) 25x25x1 (1) 25x25x1 (2) 20x20x1 (2) 20x2 0x 1
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2013
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
16
Loading...