Goodman DCG090 Installation Manual

DCG SERIES
LIGHT COMMERCIAL PACKAGED GAS UNIT
7.5 to 12.5 TON
Index
Replacement Parts................................................................ 2
Safety Instructions................................................................ 2
General Information ............................................................. 3
Unit Location ........................................................................ 4
Clearances ............................................................................ 5
Roof Curb Post-Installation Checks ....................................... 6
Roof Top Duct Connections................................................... 6
Rigging Details ...................................................................... 6
Electrical Wiring.................................................................... 8
Gas Supply Piping ............................................................... 10
Propane Gas Installations ................................................... 11
Circulating Air and Filters.................................................... 12
Venting ............................................................................... 12
Condensate Drain Connection ............................................ 12
A TTENTION INSTALLING PERSONNEL: Prior to installation, thoroughly f amiliarize yourself with this
Installation Manual. Observe all safety warnings. During in­stallation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of single package heating and cooling units. See the Specification Sheet applicable to your model for information regarding acces­sories.
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
This Forced Air Central Unit Design Complies With Requirements Embodied In The American National Standard / National Stan­dard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Centr al Furnaces
Startup, Adjustments, and Checks ...................................... 13
Air flow Adjustments.......................................................... 14
Motor Sheave Adjustments ................................................ 15
Gas System Check ............................................................... 15
Normal Sequence Of Operation.......................................... 18
Maintenance ...................................................................... 20
Troubleshooting.................................................................. 22
Appendix A Blower Performance Data
Belt Drive - Standard Horizontal..................................... 24
Appendix A Blower Performance Data
Belt Drive - Standard Down Shot.................................... 25
Appendix A Blower Performance Data
Belt Drive - Horizontal High Static .................................. 26
Belt Drive - Down Shot High Static ................................. 27
Appendix B Electrical Data.................................................. 28
Appendix C Unit Dimensions............................................... 29
Appendix D Wiring Diagrams .............................................. 30
Start-Up Checklist ............................................................... 43
INSTALLATION INSTRUCTIONS
IOD-1005E 2/2015
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2013 - 2015
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
REPLACEMENT PARTS
WARNING
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
DAIKIN NORTH AMERICA LLC
7401 SECURITY WAY
HOUSTON, TEXAS 77040
855-770-5678
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
Keep this literature in a safe place for future reference.
WARNING
DO
NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY DAIKIN FOR USE WITH THIS UNIT DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESU LT FROM THE USE OF SUCH NON APPROVED DEVICES
.
. S
ERIOUS PROPERTY
-
WARNING
T
HIS PRODUCT CONTAI NS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRO DUCTI VE HARM
.
WARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNAC E AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER
.
. I
MMEDIATELY
WARNING
T
HIS UNIT MUST NOT BE USED AS A “CONSTRUCTION HEATER” DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES
.
. T
HIS
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESU LT CAUSING PROPERTY DAMAGE
,
PERSONAL INJURY OR LOSS OF LIFE
DO
NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
WHAT TO DO IF YOU SMELL GAS:
D
O NOT TRY TO LIGHT ANY APPLIANCE
D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE
IN YOUR BUILDING
I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
PHONE
. F
I
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE
DEPART MENT
I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
.
OLLOW THE GAS SUPPLIER’S INSTRUCTIONS
.
.
.
.
WARNING
S
HOULD OVERHEAT ING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
CAUTION
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTI O N
.
WARNING
HIGH VOLTAGE !
D
ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
ULTIPLE POWER SOURCES MAY
AILURE TO DO SO MAY CAUSE PROPERTY
.
WARNING
TO
PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPO RS IN THE VICINITY OF THIS APPLIANCE
.
WARNING
ONLY
INDIVIDUALS MEETING (AT A MINIMUM) THE REQUIREMENTS
,
OF AN
“E
NTRY LEVEL TECHNICIA N” AS SPECIFIED BY THE AIR
C
ONDITIONING
MAY USE THIS INFORMATION THIS UNIT WITHOUT SUCH BACKGROUND MAY RESU LT IN PRODUCT DAMAGE, PERSONAL INJURY OR DEATH
, H
EATING, AND REFRIGERATION INSTITUTE
. A
TTEMPTING TO INSTALL OR REPAIR
(AHRI)
.
2
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA)
HAS ISSUED VARIOUS REGULATIONS RE GARDING THE INTRODUCTION AND DISPOSAL
REFRIGERANTS IN THIS UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY
OF
THE ENVIRONMENT AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL
HARM
. BECAUSE REGULATIONS MAY VARY DUE TO PASSAGE OF NEW LAWS, WE
FINES
A CERTIFIED TECHNICIAN PERFORM ANY WORK DONE ON THIS UNIT.
SUGGEST
SHOULD YOU HAVE ANY QUESTIONS PLEASE CONTACT THE LOCAL OFFICE OF THE EPA.
NATIONAL CODES
This product is designed and manufactur ed to permit installation in accordance with National Codes. It is the inst aller’ s r e sponsibil­ity to install the product in accordance with National Codes and/ or prevailing local codes and regulations.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be c alculat ed b y an appr o ve d method or in accordance with ASHRAE Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
GENERAL INFORMA TION
WARNING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, EXPLOSION S, SMOKE, SOOT, COND E NSATION, ELECTRIC SHOCK OR CARBON MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED REPAIRED, OPERATED AND MAINTAINED
.
This unit is approved for outdoor inst allation ONLY . Rated perf or­mance is achieved aft er 72 hours of opera tion. Rated performance is delivered at the specified airflow. See outdoor unit specifica­tion sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.daikinc omfort.com for Daikin brand prod­ucts. Within the website, please select the residential or com­mercial products menu and then select the submenu for the type of product to be installed, such as air conditioner s or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these in­stallation and operating instructions, all local bui lding codes and ordinances, or in their absence, with the latest edition of the Na­tional Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
,
American National Standards Institute
1430 Broadway
New York, NY 10018
System design and installation should also, where applicable, fol­low information pre sented in accept ed industry guides such as the ASHRAE Handbooks. The manufacturer assumes no r esponsibility for equipment installed in viola tion of an y c ode or r egula tion. The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services; supply and return duct connections; and drain connections (if re­quired). The internal systems of the unit are completely factory­installed and tested prior to shipment.
Units are g ener ally ins t alled on a steel roof mounting curb assem­bly which has been shipped to the job site for installation on the roof structure prior to the arrival of the unit. The model number shown on the unit’s identification plate iden tifies the various com­ponents of the unit such as refrigeration tonnage, heating input and voltage.
Carefully inspect the unit for damage including damage to the cabinetry . Any bolt s or screws which ma y have loosened in tr ansit must be re-tightened. In the even t of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, c arrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy , or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof.
3
c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage. NOTE: When inspecting the unit for transportation damage, re­move all packaging materials. R ecycle or dispose of the pack aging material according to local codes.
PRE-INSTALLATION CHECKS
Carefully rea d all instructions for the ins tallation prior t o installing unit. Ensure each step or proce dur e is under stood and an y special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies nee ded to complet e the installation. Some items may need to be purchased locally.
UNIT LOCA TION
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
IMPORTANT NOTE: Remove wood shipping rails and metal ship-
ping brace (if applicable) prior to installation of the unit on a roof curb.
.
,
To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper , adhesives, p aints, varnishe s, sealers, wax es (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds.
T o avoid possible illness or death of the building occupant s,
do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper opera tion, and service access (see unit clearances). These clearances must be permanently maintained.
The combustion air inlet and flue outlet on the unit must
never be obstructe d. If used, do not allow the economizer/ manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elev at e the unit to avoid these problems.
When the unit is heating, the temperature of the return
air entering the unit must be between 50° F and 100° F.
ALL INSTALLATIONS:
IMPORTANT NOTE: Unit should be energized 24 hours prior to
compressor start up to ensure crankcase heater has suffi­ciently warmed the compressors. Compressor damage may occur if this step is not followed.
NOTE: Appliance is shipped from factory for vertical duct application.
Proper installation of the unit ensure s tr ouble-free operation. Im­proper installation can result in problems ranging from noisy operation to property or equipment damages, dangerous condi­tions that could result in injury or personal property damage and could void the warranty. Give this booklet to the user and explain it’s provisions. The user should r etain these ins tructions for futur e reference.
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted level.
The flue outlet must be at least 12 inches fr om any opening
through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
GROUND LEVEL INSTALLATIONS ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended . Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runof f of wa ter
from higher ground can collect in the unit.
ROOF TOP INSTALLATIONS ONLY:
To avoid possible property damage or personal injury , the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structur al engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
As indicated on the unit data plate, a minimum clearance
of 36” to any combusti ble material is required on the furnace access side of the unit. All combustible materials must be kept out of this area.
This 36” clearance must also be maintained to insure
proper combustion air and flue gas flo w. The combustion air intake and furnace flue dischar ge mus t not be block ed for any reason, including blockage by snow.
4
Adequate clearances from the furnace flue discharge to
any adjacent public walkwa ys, adjacent buildings, building openings or openable windows must be maintained in accordance with the latest edition of the Na tional Fuel Gas Code (ANSI Z223.1)
Minimum horizontal clearance of 48” from the furnace
flue discharge to any electric met ers, gas meter s, regulators and relief equipment is required.
UNIT PRECAUTIONS
Do not stand or walk on the unit.
Do not drill holes anywhere in panels or in the base fr ame of the unit except where indicated. Unit access panels provide structural support.
Do not remove any access panels until unit has been installed on roof curb or field supplied structure.
Do not roll unit across finished roof without prior approval of owner or architect.
Do not skid or slide on any surface as this may damage unit base. The unit must be store d on a flat, level surf ace. Protect the condenser coil because it is easily damaged.
ROOF CURB INSTALLATIONS ONLY:
Curb installations must c omply with local codes and should be done in accordance with the est ablished guidelines of the National R oof­ing Contractors Association.
NOTE: The unit and curb accessories ar e designed to allow v ertical duct installation before unit placement. Duct inst allation after unit placement is not recommended.
CAUTION
ALL
CURBS LOOK SIMILAR CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY INFORMATIO N SHOWN
. I
NSTRUCTIONS MAY VARY IN CURB STYLES AND SUPERCEDE
. TO
AVOID INCORRECT CURB POSITIONING
.
,
See the manual shipped with the roof curb for assembly and in­stallation instructions.
CLEARANCES
36”
Min.*
36”* Min.
36” Min.*
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped unassembled. Field assembly, squaring, leveling and mounting on the roof structure are the responsibility of the in­stalling contractor. All required hardware necessary for the as­sembly of the sheet metal curb is included in the curb accessory.
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
Sufficient structural support mus t be determined prior to
locating and mounting the curb and package unit.
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb befo re mounting the package unit. Our full perimeter curbs include duct connection frames to be assemble d with the curb. Cantilevered type curbs are not available from the factory.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor. The curbs must be supported on parallel sides by roof members. The roof members must not penetrate supply and return duct opening areas as damage to the unit might occur.
*In situations that have multiple units, a 48” minimum clearance is required between the condenser coils.
UNIT CLEARANCES
Adequate clearance around the unit should be k ept f or safe ty , ser ­vice, maintenance, and proper unit operation. A total clearance of 75” on the main control panel side of the unit is r ecommende d to facilitate possible fan shaft, coil, electric heat and gas furnace removal. A clear ance of 48” is rec ommended on all other side s of the unit to facilitate possible compressor removal, to allow ser­vice access and to insure proper ventilation and condenser air­flow. The unit must not be installe d beneath an y obstruction. The unit should be installed remote from all building exhausts to in­hibit ingestion of exhaust air into the unit fresh air intake.
NOTE: If the 48” minimum is used on the control panel side of a DCG unit, a flue extension (MF# 220-GX-02) needs be to installed to prevent flue gas recirculation.
5
REMOVE COVERS
17” 7 3/8”
11” 4 7/8””
25”
INSULATED PANELS
ROOF CURB INSTALLATION
ROOF CURB POST -INSTALLA TION CHECKS
After installation, check the top of the curb, duct connection fr ame and duct flanges to make sure gasket has been applied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct connection frame. If gasket is loose, re-apply using strong weather resistant adhesive.
PROTRUSION
Inspect curb to ensure that none of the utility services (electric) routed through the curb protrude above the curb.
CAUTION
IF
PROTRUSIONS EXIST, DO NOT ATTEM PT TO SET UNIT ON CURB
NFORMATION SHOWN
I
.
.
ROOF TOP DUCT CONNECTIONS
Install all duct connections on the unit before placing the unit on rooftop.
HORIZONTAL DISCHARGE
Refer t o IOD-7006 included in the litera ture pack for inst alling hori­zontal duct covers.
Flexible duct connectors between the unit and ducts are recom­mended. Insulate and weatherproof all ex ternal ductwork and joints as required and in accordance with local codes.
12”
SUPPL Y
6 3/16”
HORIZONTAL DISCHARGE DUCT CONNECTIONS
RIGGING DET AILS
WARNING
TO
PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMA IN IN AN
UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS
T
O FACILITATE LIFTING AND MOVING WHEN A CRANE IS USED, PLACE
THE UNIT IN AN ADEQU ATE CABLE SLING
.
.
CAUTION
DO
NOT LIFT UNITS TWO AT A TIME INCLUDED IN THE UNIT BASE FRAME PREVENT DAMAGE TO THE UNIT
. P
ROVISIONS FOR FORKS HAVE BEEN
. M
INIMUM FORK LENGTH IS
.
48” TO
Provisions for fork s have been include d in the unit base frame. No other fork locations are approved.
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
• Unit must be lifted by the four lifting holes located at the base frame corners.
• Lifting cables should be at tached to the unit with shackle s.
• The distance between the crane hook and the top of the unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. Removal is accomplished by extracting the sheet met al r etainer s and pulling the struts through the base of the unit. Refer to rigging label on the unit.
6
• Your unit may be equipped with a steel shipping brace located underneath the unit (under compressors). If installing on a roof curb, the brace MUST be removed. Follow the following instructions for removal.
CAUTION
W
HEN UNIT IS SUSPENDED, BOARDS AND SHIPPING BRACE WILL DROP WHEN
SCREWS ARE REMOVED
EMOVE FORK HOLE BRACKETS, BOARDS AND SHIPPING BRACE FROM BOTTOM
R
UNIT BEFORE PLACING UNIT ONTO CURB
OF
Before installing this unit on a roof curb:
1. Remove wooden strut s per installation instructions. These are the struts that are located in the fork holes and are used to protect the unit from damage while lifting with forks.
2. Locate and remove the twelve (12) scr ews tha t at t ach the shipping brace to the side rails. There will be six (6) screws on each side of the unit and they are in a diagonal pattern.
See following figure.
. TO
PREVENT PERSONAL INJURY
, STAND CLEAR.
.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end t o be lower than supply air end.
To assist in determining rigging requirements, unit weights are shown as follows:
3. Lift unit per the “Rigging Details” section of the installation instructions, observing all warnings and cautions. Lift the unit high enough off the ground to reach under and gra sp the shipping brace.
4. Rotate the brace by tapping the ends until the brace falls free from the unit.
5. Dispose of the brace appropriately.
Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior t o installing the unit. Ductwork dimensions are shown in Roof Curb Installation Instructions.
A
Y
RETURN
C
EVAPORATOR COIL
COMPRESSOR 1
CG
COMPRESSOR 2
SUPPLY
BD
DATA
Corner Weight - A 269 255 255 335 Corner Weight - B 297 321 321 390 Corner Weight - C 254 250 250 295 Corner Weight - D 280 314 314 345 Unit Shipping Weight 1175 1215 1215 1390 Unit Operating Weight 1100 1140 1140 1365
X (Inches) 48 49 49 Y (Inches) 32 34 34
X
CORNER & CENTER OF GRAVITY LOCATIONS
DCG Weights (lbs)
090 102 120 150
47
33.5
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the Na­tional Roofing Contractors Association Manual.
CAUTION
TO
PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
7
.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper align­ment and orientation of supply and return openings with duct.
The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these in­structions, the latest edition of the Na tional Electrical Code (ANSI/ NFP A 7 0), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/ 35°C rise).
RIGGING REMOVAL
CAUTION
TO
PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS AND
SPREADER BARS TO REST ON THE ROOF OF THE UNIT
.
Remove sprea der bars, lifting cable s and other rigging equipment.
ELECTRICAL WIRING
WARNING
HIGH VOLTAGE !
D
ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
ULTIPLE POWER SOURCES MAY
AILURE TO DO SO MAY CAUSE PROPERTY
.
WARNING
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY WIRING INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THOROUGHLY TEST PRIOR TO SHIPMENT REPRESENTATIVE IF ASSISTANCE IS REQUIRED
. C
ONTACT YOUR LOCAL
. THE
.
CAUTION
TO
PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES
. F
OLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES ACCESS PANELS
. DO
NOT ROUT E WIRES THROUGH REMOVABLE
.
CAUTION
C
ONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT WATER
ENTRY INTO THE BUILDING
.
For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maxi­mum overcurrent protection device. DO NOT EXCEED THE MAXI­MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
The main power supply shall be three-phase, three wir e. The unit is factory wired for the voltage shown on the unit’s data plate.
NOTE: If supply voltage is 208V, all leads on primary of transformer TRANS1 must be moved from the 230V to the 208V tap.
Main power wiring should be sized f or the minimum wire ampacity shown on the unit’s database. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase the wire size to prevent e xce ssive volt age drop. Wires should be sized f or a maximum of 3% voltage drop.
CAUTION
TO
AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
ONLY COPPER CONDUCTORS
.
CAUTION
TO
PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRO RS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS
. V
ERIFY PROPER OPERATION AFTER SERVICING
.
NOTE: A weather-tight disconnect switch, properly sized for the
unit total load, must be field or f actory inst alled. An e xt ernal field supplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied disconnect switch.
• Some disconnect switches are not fused. Protect the power leads a t the point of distribution in accordance with the unit data plate.
• The unit must be electrically grounded in accor dance with local codes or, in the absence of local codes, with the lates t edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding conductor in accordance with T able 250-95 of the National Electrical Code. Do not use the ground lug for c onnecting a neutral conductor.
• Connect power wiring to the middle contactor within the main control box or to electric al power block if equipped.
All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.
8
10 3/16”
DIMPLES MARK DRILL LOCATIONS
HIGH VOLTAGE ENTRANCE
Power Wiring
Thermostat Wiring
POWER AND LOW VOLTAGE BLOCK LOCATIONS
WARNING
F
AILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAG E OR WITH EXCESSIVE PHASE UNBALANCE CONST I TUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS
.
AREAS WITHOUT CONVENIENCE OUTLET
It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable lights and tools used by the service mechanic.
NOTE: Refer to local codes for requirements. These outlets can also be factory installed.
UNITS INSTALLED ON ROOF TOPS
Main power and low voltage wiring may enter the unit through the side or through the roof curb. Install conduit connectors at the desired entrance locations. External connectors must be weatherproof. All holes in the unit base must be sealed (including those around conduit nuts) to prevent water leakage into build­ing. All required conduit and fittings are to be field supplied.
Supply voltage to roof top unit mus t not vary by more than 10% of the value indicated on the unit data plate. Phase voltage unbal­ance must not exceed 2%. Contact your local power company for correction of improper voltage or phase unbalance.
LOW VOLTAGE ENTRANCE
26 ½”
ELECTRICAL ENTRANCE LOCATIONS
Unit is equipped with a Low Voltage T erminal Block and has Single Point wiring to the contactor.
LOW VOLTAGE CONTROL WIRING
1. A 24V thermostat must be installed for unit operation. It may be purchased with the unit or field -supplied. Thermostats may be programmable or electromechanical as required.
2. Locate thermostat or remote sensor in the conditioned space where it will sense average temperature. Do not locate the device where it may be directly exposed to supply air, sunlight or other sources of heat. Follow installation instructions packaged with the thermostat.
3. Use #18 AWG wire for 24V control wiring runs not exceeding 75 feet. U se #16 A WG wire for 24V con trol wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 wher e permitted by local codes.
4. Route thermostat wires from sub-base terminals to the unit. Control wiring should enter through the duct panel (dimple marks entrance location) or thr ough the roof curb. Connect thermostat and any accessory wiring to low voltage terminal block TB1 in the main control box.
NOTE: Field-supplied conduit may need to be installed depending on unit/curb configuration. Use #18 AWG solid conductor wire whenever connecting thermostat wire s to t erminals on sub-base. DO NOT use larger than #18 AWG wire. A transition to #18 AWG wire may be requir e d be fore entering thermostat sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
9
GAS SUPPLY PIPING
Natural Gas Connection
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERA TI ON, SERVICE OR MAINTENANCE REFER TO THIS MANUAL INFORMATIO N, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
,
IMPORTANT NOTE: This unit is factory set to operate on natural
gas at the altitudes shown on the rating plate.
WARNING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL THE PROPER CONVERSION KIT(S RESU LT IN UNSATISFACTORY OPERATION AND/OR EQUIPMEN T DAMAGE
IGH ALTITUDE KITS ARE FOR
H
APPROVED FOR USE IN CANADA
U.S. I
.
). F
AILURE TO DO SO CAN
NSTALLATIONS ONLY AND ARE NOT
.
The rating plate is stamped with the model number, type of gas and gas input rating. Mak e sure the unit is equippe d to oper ate on the type of gas available. Conver sion to propane (LP) g as is permit­ted with the use of the factory authorized conversion kit (see the unit Technical Manual for the appropriate kit). For High Altitude derates, refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
INLE T GAS PRESSURE
NATURAL M i n. 5.0" W .C ., Ma x . 10.0" W.C.
PROPANE Min. 1 1.0 " W. C., M ax . 14.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.
The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.
PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not un­dersize the natur al/propane gas piping fr om the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas and gas input rating. Mak e sure the unit is equippe d to oper ate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Pressure= .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based on 0.60 Specific Gravity Gas)
CFH =
Nominal Black Pipe Size (inches)
1/2 3/4 1 1 1/4 1 1 /2
BTUH Furnace Input
Heatin g Valu e of Gas (BTU/Cubic Foot)
Refer to the Proper Piping Practice drawing for the gener al layout at the unit. The following rules apply:
1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.
2. Use pipe joint compound on male thre a ds only. Pipe joint compound must be resis tant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
5. Use two pipe wrenches when making connection to the gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8. The unit must be connected to the building piping by one of the following methods:
• Rigid metallic pipe and fittings
• Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)
• Listed ga s appliance c onnector s used in acc or dance with the terms of their listing that are complet ely in the same room as the equipment
• In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect agains t external corrosion when in cont act with masonry, pla st er or insula tion or are subject t o r epe ate d wettings by liquids (wat er - not rain w at er, detergents or sewage).
10
DOOR
PROVIDE CLEARANCE FOR REMOVAL OF ACCESS PANELS
MANUAL SHUTOFF VALVE
GROUND JOINT UNION
DRIP LEG
PROP ANE GAS INSTALLA TIONS
WARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A GAS DETECTING WARNING DEVICE
.
. S
INCE RUST CAN REDUCE THE LEVEL OF
. C
ONTACT A
IMPORTANT NOTE: Propane gas conversion kit s must be installed
to convert units to propane gas.
PROPER PIPING PRACTICE
NOTE: The unit gas supply entrance is factory sealed with plugs.
Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.
GAS PIPING CHECKS
CAUTION
TO
PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING
• T
HE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS
H
OVERFIRING WHICH MAY RESU LT IN PREMATURE HEAT EXCHANGE FAILURE
• T
HIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF
HIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY
• T
CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN
. N
EVER EXCEED SPECIFIED PRESSURES FOR TESTING
IGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE
.
1/2 P SIG (3.48 KPA).
:
. B
ECAUSE OF THE DANGER OF
1/2 P SIG (3.48 KPA).
WARNING
TO
AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS
NO OPEN FLAME
IN THE VICINITY DURING AIR BLEEDING
.
,
.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriter s (See NBFU Manual 58). Line pressure 11.3 - 14” w.c.
For satisfactory operation, propane gas manifold pressure must be within 9.7 - 10.3 inches w.c. for high fire and within 6.7 - 7.3 inches w.c. low fire at the manifold with all gas appliances in op­eration. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface ar ea of the co ntainer or containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.
TANKS AND PIPING
Complete information re garding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulat or manufacturers and pr opane gas suppliers .
Since propane gas will quickly dissolve white lead or most standard commer cial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum ga ses such as Gasolac®, Stalactic®, Clyde’ s or John Crane® are satisfactory.
See the following figure for typical propane gas piping.
First Stage Regulator
5 to 15 PSIG (20 PSIG Max.)
Continuous
11" W.C.
®
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure ga s is expelled. Tighten union and wait for five minutes until all ga s ha s been dissipa t ed in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.
11
200 PSIG Maximum
TYPICAL PROPANE GAS PIPING
Second Stage Regulator
ROOF TOP LOCATION AND INSTALLATION
The gas supply piping location and installation for roof top units must be in accordance with local codes or, in the absence of locals codes, with ordinances of the latest edition of the National Fuel Gas Code (ANSI Z223.1).
A manual gas shut off valve must be field installed external to the roof top unit. In addition, a drip leg must be installed near the inlet connection. A ground joint union connection is required be­tween the external shut off valve and the unit connection to the gas valve to permit removal of the burner assembly for servicing.
1. Route gas piping to unit so that it does not interfere with the removal of access panels. Support and align piping to prevent strains or misalignmen t of the manifold assembly .
2. All units are furnished with standard female NPT pipe connections. Connection pipe sizes for DCG090 through 300 units is 3/4" NPT The size of the gas supply piping to the unit must be based on length of run, number of units on the system, gas characteristics, BTU requirement and available supply pressure. All piping must be done in accordance with local codes or, in the absence of local codes, with the lates t edition of the National Fuel Gas Code (ANSI Z223.1).
NOTE: The gas connection size at the unit does NOT establish the size of the supply line.
3. These units are designed for either natural or propane (LP) gas and are specifically cons tructed at the factory for only one of these fuels. The fuels are NO T interchangeable. However, the furnace can be converted in the field from natural gas to LP gas with the appropriate factory kit (see unit Technical Manual for the appropriate kit). Only a qualified contractor, experienced with natural and prop ane gas systems, should attempt conversion. Kit instructions must be followed closely to assure safe and reliable unit operation.
4. With all units on a common line operating under full fire, natural gas main supply pressure should be adjusted to approximat ely 7.0" w.c., measured at the unit gas valv e. If the gas pressur e at the unit is greater than 10.5" w.c., the contractor must furnish and install an external type positive shut off service pressure regulator. The unit will not function satisfactorily if supply gas pr essure is less than
5.5" w.c. or greater than 10.5" w.c.. NOTE: A minimum horizontal dist ance of 48" between the
regulator and the furnace flue discharge is required.
5. With all units on a common line operating under full LP gas main supply pressur e should be at lea st 11.0" w.c. and must be no greater than 14.0" w.c., measured at the unit gas valve. Unit will not function satisfactorily if supply gas pressure is less than 11.0" w.c. or greater than 14.0" w .c..
6. All pipe connections should be sealed with a pipe thread compound, which is resistant to the fuel used with the furnace. A soapy water solution should be used to check all joints for leaks. A 1/8" NPT plugged tap is located on the entering side of the gas v alve for test g auge connection to measure supply (main) gas pressure. Another 1/8" tap is provided on the side of the manifold for checking manifold pressure.
WARNING
T
HIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE
DISCONNECTED
PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF
1/2 PSIG (13.8”
FROM THE GAS SUPPLY SYSTEM DURING ANY
W.C
.).
CAUTION
T
HIS UNIT MUST BE BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN
ISOLATED
FROM THE GAS SUPPLY PIPING SYSTEM
1/2 P SIG.
7. There must be no obstruction to prevent the flow of combustion and ventilating air. A vent stack is not requir ed and must never be used. The power venter will supply an adequate amount of combustion air as long as the air passageways are kept free of any obstructions and the recommended external unit clearances are maintained.
CIRCULA TING AIR AND FIL TERS
DUCTWORK
The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat ex­changer. A cover should be tightly attached to prevent air leaks.
Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
VENTING
NOTE: V enting is self-contained.
The inductor motor on DCG units is a dual voltage motor. It is factory wired for 230 volt s. If field supply power is 208V , the ins taller must swap the connections of the black and red leads (located in the blower compartment) to ensure c orrect inductor mot or operation.
CONDENSA TE DRAIN CONNE CTION
CONDENSATE DRAIN CONNECTION
A 3/4” female NPT drain connection is supplied on the end of the unit and bottom of the drain pan f or condensat e piping. An ext er­nal trap must be installed for proper condensate drainage.
DRAIN CONNECTION
UNIT 2" MINIMUM
FLEXIBLE TUBING-HOSE OR PIPE
A POSITIVE LIQUID SEAL IS REQUIRED
DRAIN CONNECTION
Install condensate dr ain trap as shown. Use 3/4" drain line and fit­tings or larger. Do not operate without trap.
3" MIN IMUM
12
HORIZONTAL DRAIN
Drainage of condensate directly on to the r oof ma y be accept able; refer to local code. It is recommended that a small drip pad of either stone, mortar, wood or metal be provided to prevent any possible damage to the roof.
and Checks procedure. The St artup, Adjustment s, and Checks pro­cedure at outside ambients below 55°F should be limit ed to a readi­ness check of the refrigera tion system with the r equired final check and calibration left to be completed when the outside ambient rises above 55°F.
CLEANING
Due to the fact that drain pans in any air conditioning unit will have some moisture in them, algae and fungus will grow due to airborne bacteria and spores. Periodic clean­ing is necessary to prevent this build-up from plugging the drain.
ST ARTUP, ADJUSTMENTS, AND CHECKS
WARNING
HIGH VOLTAGE!
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, BOND THE FRAME OF THIS UNIT TO THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL PROVIDED OR OTHER ACCEPTABLE MEANS SERVICING OR INSTALLING THIS UNIT
. D
ISCONNECT ALL POWER BEFORE
.
PRE-STARTUP INSTRUCTIONS - GENERAL
CAUTION
TO
PREVENT PROPERTY DAMAGE OR PERSONAL INJURY THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TEST HAVE BEEN PERFORMED
Prior to the beginning of Startup, Adjustments, and Checks pr oce­dures, the following steps should be completed in the building.
MOVING MACHINERY HAZARD! T
O PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT POWER TO THE UNIT AND PADLOCK IN THE SERVICING FANS
This unit is equipped with an electronic ignition device to auto­matically light the main burners. It also has a power vent blower to exhaust combustion products.
On new installations, or if a major component has been replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct cov er s must be removed before
operating unit.
The Startup, Adjustments, and Checks procedure provides a step­by-step sequence which, if follow ed, will assure the proper st artup of the equipment in the minimum amount of time. Air balancing of duct system is not considered part of this procedure. However, it is an important phase of any air c onditioning sys tem st artup and should be performed upon completion of the Startup, Adjustment s,
.
WARNING
.
“OFF”
, DO
NOT START
POSITION BEFORE
TEMPORARY HEATING OR COOLING
If the unit is to be used for tempor ary heating or cooling, a “Startup, Adjustments, and Checks” must first be performed in accordance with this manual. Failure to comply with this requir ement will void the warranty. After the machines are used for temporary heating or cooling, inspect the coils, fans, and motors for unacceptable levels of construction dust and dirt and install new filters.
CONTRACTOR RESPONSIBILITY
The installing contractor must be certain that:
All supply and return air ductwork is in place, properly sealed, and corresponds with installation instructions.
All thermostats are mounted and wired in accordance with installation instructions.
All electric power, all gas, hot water or steam line connections, and the condensate drain installation have been made to each unit on the job. These main supply lines must be functional and capable of operating all unit s simultaneously.
Requirements are met for venting and combution air.
Air filters are in place.
Input rate and temperature rise are adjusted per rating plate.
ROOF CURB INSTALLATION CHECK
Inspect the roof curb for correct installation. The unit and curb assembly should be level. Inspect the flashing of the roof mount­ing curb to the roof, especially at the corners, for good workman­ship. Also check for leaks around g a s kets. Note any deficiencies in a separate report and forward to the contractor.
OBSTRUCTIONS, FAN CLEARANCE AND WIRING
Remove any extraneous construction and shipping materials that may be found during this procedure. Rotate all fans manually to check for proper clearances and that they rotate freely. Check for bolts and screws that may have jarred loose during shipment to the job site. Retighten if necessary. Re-tighten all electrical con­nections.
FIELD DUCT CONNECTIONS
Verify that all duct connections are tight and that there is no air bypass between supply and return.
FILTER SECTION CHECK
Remove filter section access panels and check that filter s are prop­erly installed. Note airflow arrows on filter frames.
13
PRE-STARTUP PRECAUTIONS
Transformer and Induced Draft Motor NOTE: On the 208/230 volt units only.
Ensure the transformer and induced draft motor are set on the appropriate voltage taps. Both the transformer tap and induced draft motor are set on 230v from the factory. To change the in­duced draft motor v olt age, r emo ve the black induced draft motor wire from the unused terminal on the ignition control board and swap it with the red wire coming from the induced draft motor.
It is important to your safety that the unit has been properly grounded during installation. Check gr ound lug connection in main control box for tightness prior to closing circuit breaker or discon­nect switch. Verify that supply voltage on line side of disconnect agrees with voltage on unit identification plate and is within the utilization voltage rang e as indicate d in Appendix B Electrical Data.
System Volta ge - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage class.
Nameplate Voltage - That voltage assigned to a piece of equip­ment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
Utilization Voltage - The voltag e of the line terminals of the equip­ment at which the equipment must give fully satisfactory perfor­mance. Once it is established that supply voltage will be main­tained within the utilization range under all system conditions, check and calculate if an unbalanced condition exists between phases. Calculate percent voltage unbalance as follows:
Three Phase Models
2) MAXIMUM VOLTAGE DEVIATIONS
3) PERCENT VOLTAGE UNBALANCE
HOW TO USE THE FORMULA: EXAMPLE: With voltage of 220, 216, and 213
1) Average Volt age = 220+216+213=649 / 3 = 216
2) Maximum Voltage Deviation s fro m Average Voltage = 220 - 216 = 4
3) Percent Voltage Unbalance = 100 x = = 1.8%
Percent voltage unbalance MUST NOT exceed 2%
= 100 X
FROM AVERAGE VOLT AG E
1) AVERAGE VOLTAGE
4
216
400 216
.
CONTROL VOLTAGE CHECK
With disconnect switch in the open “OFF” position, disconnect blue wire from low voltag e transf ormer TRANS1. Close the discon­nect switch to energize TRANS1 control transformer. Check pri­mary and secondary (24V) of control transformer TRANS1.
AIR FLOW ADJUSTMENTS
able for the required airflow. Refer to the following “Drive Adjustments” section.
When the final adjustments are complet e, the current dr aw of the motor should be checked and compared to the full load current rating of the motor. The amperage must not exceed the service factor stamped on the motor nameplate. The total airflow must not be less than that required f or oper ation of the electric heat ers or the furnace.
If an economizer is installe d, check the unit operating balance with the economizer at full outside air and at minimum outside air. Upon completion of the air flow balancing, we recommend replacing the variable pitched motor sheave with a properly-sized fixed sheave. A matching fix ed shea ve will provide longer belt and bear ­ing life and vibration free operation. Initially, it is best to have a variable pitched motor sheave for the purpose of airflow balanc­ing, but once the balance has been achieved, fixed sheaves main­tain alignment and minimize vibra tion mor e e f fectively. For direct drive units, move green wire for fan.
NOTE: Never run CFM below 300 CFM per ton. Evaporator freez­ing or poor unit performance is possible.
EVAPORATOR FAN ROTATION CHECK
Check that fan rotate s clockwise when viewe d fr om the driv e side of unit and in accordance with rotation arrow shown on blower housing. If it does not, reverse any two incoming power cables at Single Point Power Block. In this case, repeat bearing check.
Do not attempt to change load side wiring. In ternal wiring assur es all motors and compressors wi ll rotate in correct direction once evaporator fan motor rotation check has been made.
ELECTRICAL INPUT CHECK
Make preliminary check of evapor ator f an ampere dra w and verify that motor nameplate amps are not exceeded. A final check of amp draw should be made upon completion of air balancing of the duct system (see Appendix B).
SET EVAPORATOR FAN RPM
Actual RPM’s mus t be set and verified with a tachomet er or strobe light. Refer to Appendex A for basic unit fan RPM. Refer also to “Airflow ” section of this manual. With disconnect switch open, disconnect thermostat wires from terminals Y and W. This will pre­vent heating and mechanical cooling from coming on. Place a jumper wire across terminals R and G at TB1 terminal block. Close disconnect switch; evaporator fan motor will operate so RPM can be checked.
For gas heat units, the airflow must be adjusted so that the air temperature rise f alls within the r anges giv en s tate d on Dat a Plate (see Appendix A - Blower Performance).
NOTE: For 2 Spee d Models, airflow a djustmen ts mus t be made on high speed, i.e., 2nd stage cooling or in heat mode.
The drive on the supply fan is typically set in the middle of the RPM range. The drive motor sheave pitch diameter is field adjust-
BELT DRIVE MODELS ONLY
The drive on the supply fan is typically set in the middle of the RPM range. The drive motor she a v e pitch diameter is field adjust­able for the required airflow. Refer to “Motor She ave Adjustmens” section.
14
Loading...
+ 30 hidden pages