Prior to installation, thoroughly familiarize yourself with
this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to
educate the customer on its safe use.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of
single package heating and cooling units. See the Specification
Sheet applicable to your model for information regarding accessories.
*NOTE: Please contact your distributor or our website for the
applicable Specification Sheet referred to in this manual.
This Forced Air Central Unit Design Complies With Requirements
Embodied In The American National Standard / National Standard of Canada Shown Below.
When reporting shortages or damages, or ordering repair
parts, give the complete unit model and serial numbers as
stamped on the unit’s nameplate.
Replacement parts for this appliance are available through
your contractor or local distributor. For the location of your
nearest distributor, consult the white business pages, the
yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
DAIKIN NORTH AMERICA LLC
7401 SECURITY WAY
HOUSTON, TEXAS 77040
855-770-5678
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual to
familiarize yourself on the specific items which must be
adhered to, including maximum external static pressure to
unit, air temperature rise, minimum or maximum CFM and
motor speed connections.
WARN ING
DO
NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN
CERTIFIED BY DAIKIN FOR USE WITH THIS UNIT
DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND
HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON
APPROVED DEVICES
.
. S
ERIOUS PROPERTY
/OR
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
WARNING
O AVOID PROPERTY DAMAGE , PERSONAL INJURY OR DEATH, DO NOT USE
T
I
THIS UNIT IF ANY PART HA S BEEN UNDER WATER.
QUALIFIED SERVICE TECHNICIAN T O INSPECT THE FURNACE AND TO RE PLACE
ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN
UNDER WATER.
MMEDIATELY CALL A
-
Keep this literature in a safe place for future reference.
WARN ING
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE
- D
O NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
- WHAT T O D O IF YO U SMELL GA S:
* D
O NOT TRY TO LIGHT ANY APPLIANCE
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE
- I
* D
ANY PHONE IN YOUR BUILDING
* I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBORS PHONE
INSTRUCTIONS
* I
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
FIRE DEPARTMENT
. F
OLLOW THE GAS SUPPLIERS
.
.
.
.
WARNING
HOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN
S
OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE
TURNING OFF T HE ELECTRI CAL SUPPLY.
CAUTION
T
HIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER
DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW
STRUCTURE
FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR
TEMPERATURE AND EXPOSURE TO CORROSIVE OR VERY
DIRTY
. T
HIS TYPE OF USE MAY RESULT IN PREMATURE
ATMOSPHERES
.
WARNING
"
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT
BE PRESENT
DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARNING
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
HIGH VOLTAGE!
INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE
PERFORMED
MINIMUM) THE REQUIREMENTS OF AN
T
ECHNICIAN” AS SPECIFIED BY THE AIR CONDITIONING
HEATING AND REFRIGERATION INSTITUTE
A
TTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT
SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE
PERSONAL INJURY OR DEATH
ONLY BY
INDIVIDUALS MEETING(AT A
“E
NTRY LEVEL
(AHRI).
.
,
,
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY
HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND
SERVICE PERSONNEL EXERCISE CAUTION
.
2
GENERAL INFORMA TION
WARNING
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE,
T
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON
MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED,
AND MAINTAINED.
This unit is approved for outdoor installation ONLY . Rate d perf ormance is achieved aft er 72 hours of opera tion. Rated performance
is delivered at the specified airflow. See product specification
sheet for light commercial models. Specification sheets can be
found at www.daikincomfort.com for Daikin brand products.
Within the website, please select the commercial products menu
and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of
product pages that each contain links to that model’s specification sheet.
To assure that your unit operates safely and efficiently, it must be
installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and
ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard
of Canada CAN/CSA B149 Installation Codes.
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA)
HASISSUEDVARIOUSREGULATIONSREGARDINGTHEINTRODUCTIONANDDISPOSAL
OF
TE CHNICIANPERFORMANYWORKDONEONTHISUNIT. SHOULDYOUHAVE
ANY
QUESTIONSPLEASECONTACTTHELOCALOFFICEOFTHE EPA.
NATIONAL CODES
This product is designed and manufactur ed to permit installation
in accordance with National Codes. It is the inst aller’ s r e sponsibility to install the product in accordance with National Codes and/
or prevailing local codes and regulations.
The heating and cooling capacities of the unit should be greater
than or equal to the design heating and cooling loads of the area
to be conditioned. The loads should be c alculat ed b y an appr o ve d
method or in accordance with ASHRAE Guide or Manual J - Load
Calculations published by the Air Conditioning Contractors of
America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
System design and installation should also, where applicable, follow information pre sented in accept ed industry guides such as the
ASHRAE Handbooks. The manufacturer assumes no r esponsibility
for equipment installed in viola tion of an y c ode or r egula tion. The
mechanical installation of the packaged roof top units consists of
making final connections between the unit and building services;
supply and return duct connections; and drain connections (if required). The internal systems of the unit are completely factoryinstalled and tested prior to shipment.
Units are g ener ally ins t alled on a steel roof mounting curb assembly which has been shipped to the job site for installation on the
roof structure prior to the arrival of the unit. The model number
shown on the unit’s identification plate iden tifies the various components of the unit such as refrigeration tonnage, heating input
and voltage.
Carefully inspect the unit for damage including damage to the
cabinetry . Any bolt s or screws which ma y have loosened in tr ansit
must be re-tightened. In the even t of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage
to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, c arrier should be notified as
soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy , or indemnity bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the
carrier. The carrier is responsible for making prompt
inspection of damage and for a thorough investigation
of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage.
3
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. R ecycle or dispose of the pack aging
material according to local codes.
PRE-INSTALLATION CHECKS
Carefully rea d all instructions for the ins tallation prior t o installing
unit. Ensure each step or proce dur e is under stood and an y special
considerations are taken into account before starting installation.
Assemble all tools, hardware and supplies nee ded to complet e the
installation. Some items may need to be purchased locally.
UNIT LOCA TION
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit.
ALL INSTALLATIONS:
IMPORTANT NOTE: Unit should be energized 24 hours prior to
compressor start up to ensure crankcase heater has sufficiently warmed the compressors. Compressor damage may
occur if this step is not followed.
• T o avoid possible illness or death of the building occupant s,
do NOT locate outside air intake device (economizer,
manual fresh air intake, motorized fresh air intake) too
close to an exhaust outlet, gas vent termination, or
plumbing vent outlet. For specific distances required,
consult local codes.
• Allow minimum clearances from the enclosure for fire
protection, proper opera tion, and service access (see unit
clearances). These clearances must be permanently
maintained.
• The combustion air inlet and flue outlet on the unit must
never be obstructe d. If used, do not allow the economizer/
manual fresh air damper/ motorized fresh air damper to
become blocked by snow or debris. In some climates or
locations, it may be necessary to elev at e the unit to avoid
these problems.
• When the unit is heating, the temperature of the return
air entering the unit must be a minimum of 55° F.
GROUND LEVEL INSTALLATIONS ONLY:
• When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended .
Prepare a base that is 3” larger than the package unit
footprint and a minimum of 3” thick.
• The base should also be located where no runof f of wa ter
from higher ground can collect in the unit.
ROOFTOP INSTALLATIONS ONLY:
NOTE:Appliance is shipped from factory for vertical duct
application.
Proper installation of the unit ensure s tr ouble-free operation. Im-
proper installation can result in problems ranging from noisy
operation to property or equipment damages, dangerous conditions that could result in injury or personal property damage and
that are not cov ered by the w arranty. Give this booklet to the user
and explain it’s provisions. The user should retain these instructions for future reference.
• For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted
level.
• The flue outlet must be at least 12 inches fr om any opening
through which flue gases could enter a building, and at
least three feet above any forced air inlet located within
ten feet. The economizer/manual fresh air intake/
motorized fresh air intake and combustion air inlet
mounted on the unit are not affected by this restriction.
• To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e.
combustion air for the unit) will be frequently
contaminated by compounds containing chlorine or
fluorine. Common sources of such compounds include
swimming pool chemicals and chlorine bleaches, paint
stripper , adhesives, p aints, varnishe s, sealers, wax es (which
are not yet dried) and solvents used during construction
and remodeling. Various commercial and industrial
processes may also be sources of chlorine/fluorine
compounds.
• To avoid possible property damage or personal injury, the
roof must have sufficient structural strength to carry the
weight of the unit(s) and snow or water loads as required
by local codes. Consult a structur al engineer to determine
the weight capabilities of the roof.
• The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
• To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
• As indicated on the unit data plate, a minimum clearance
of 36” to any combustible material is required on the
furnace access side of the unit. All combustible materials
must be kept out of this area.
• This 36” clearance must also be maintained to insure
proper combustion air and flue gas flo w. The combustion
air intake and furnace flue dischar ge mus t not be block ed
for any reason, including blockage by snow.
• Adequate clearances from the furnace flue discharge to
any adjacent public w alkways, adjacen t buildings, building
openings or openable windows must be maintained in
accordance with the latest e dition of the National Fuel Gas
Code (ANSI Z223.1)
• Minimum horizontal clearance of 48” from the furnace
flue discharge to any electric me ters, ga s meters, regulat ors
and relief equipment is required.
4
UNIT PRECAUTIONS
•Do not stand or walk on the unit.
•Do not drill holes anywhere in panels or in the base fr ame
of the unit except where indicated. Unit access panels
provide structural support.
•Do not remove any access panels until unit has been
installed on roof curb or field supplied structure.
•Do not roll unit across finished roof without prior approval
of owner or architect.
•Do not skid or slide on any surface as this may damage
unit base. The unit must be store d on a flat, level surf ace.
Protect the condenser coil because it is easily damaged.
ROOF CURB INSTALLATIONS ONLY:
Curb installations must c omply with local codes and should be done
in accordance with the est ablished guidelines of the National R oofing Contractors Association.
Proper unit installation requires that the roof curb be firmly and
permanently attached to the roof structure. Check for adequate
fastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are
shipped unassembled. Field assembly, squaring, leveling and
mounting on the roof structure are the responsibility of the installing contractor. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory.
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
• Sufficient structural support mus t be determined prior to
locating and mounting the curb and package unit.
• Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before
mounting the package unit. Our full perimeter curbs
include duct connection frames to be assemble d with the
curb. Cantilevered type curbs are not available from the
factory.
• Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor.
The curbs must be supported on parallel sides by roof members.
The roof members must not penetrate supply and return duct
opening areas as damage to the unit might occur.
See the manual shipped with the roof curb for assembly and installation instructions.
CLEARANCES
24”
Min.*
36” Min.
*
Unit Clearances
*In situations that have multiple units, a 48” minimum clearance is
required between the condenser coils.
Adequate clearance around the unit should be k ept f or safe ty , ser vice, maintenance, and proper unit operation. A total clearance
of 75” on the main control panel side of the unit is r ecommende d
to facilitate possible fan shaft, coil, electric heat and gas furnace
removal. A clear ance of 48” is rec ommended on all other side s of
the unit to facilitate possible compressor removal, to allow service access and to insure proper ventilation and condenser airflow. The unit must not be installe d beneath an y obstruction. The
unit should be installed remote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.
NOTE: If the 48” minimum is used on the control panel side of a
DCG unit, a flue extension (MF# 220-GX-01) needs be to installed
to prevent flue gas recirculation.
24”
Min.*
NOTE: The unit and curb accessories are de signed to allow v ertical
duct installation before unit placement. Duct inst allation after unit
placement is not recommended.
CAUTION
ALL
CURBS LOOK SIMILAR
POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS
ON CURB ASSEMBLY
SUPERSEDES INFORMATION SHOWN
. TO
AVOID INCORRECT CURB
. I
NSTRUCTIONS MAY VARY IN CURB STYLES AND
.
INSULATED
PANELS
5
Roof Curb Installation
ROOF CURB POST -INSTALLA TION CHECK S
After installation, check the top of the curb, duct connection fr ame
and duct flanges to make sure gasket has been applied properly.
Gasket should be firmly applied to the top of the curb perimeter,
duct flanges and any exposed duct connection frame. If gasket is
loose, re-apply using strong weather resistant adhesive.
CAUTION
IF
UNITS ARE LIFTED TWO AT A TIME, THE FORK HOLES ON THE
CONDENSER END OF THE UNIT MUST NOT BE USED
LENGTH IS
IS RECOMMENDED
42” TO
PREVENT DAMAGE TO THE UNIT; HOWEVER
.
. M
INIMUM FORK
, 48”
PROTRUSION
Inspect curb to ensure that none of the utility services (electric)
routed through the curb protrude above the curb.
CAUTION
IF
PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB
.
ROOF TOP DUCT CONNECTIONS
Install all duct connections on the unit before placing the unit on
rooftop.
HORIZONTAL DISCHARGE
Refer t o IOD-7006 included in the litera ture pack for inst alling horizontal duct covers.
Flexible duct connectors between the unit and ducts are recommended. Insulate and weatherproof all external ductwork and
joints as required and in accordance with local codes.
11”4 7/8””
REMOVE
COVERS
Provisions for fork s have been include d in the unit base frame. No
other fork locations are approved.
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
• Unit must be lifted by the four lifting holes located at the
base frame corners.
• Lifting cables should be at tached to the unit with shackle s.
• The distance between the crane hook and the top of the
unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent
damage to the cabinet by the lift cables. Spreader bars
must be of sufficient length so that cables do not come in
contact with the unit during transport. Remove wood
struts mounted beneath unit base frame before setting
unit on roof curb. These struts are intended to protect
unit base frame from fork lift damage. Removal is
accomplished by extracting the sheet met al r etainer s and
pulling the struts through the base of the unit. Refer to
rigging label on the unit.
Important: If using bottom discharge with roof curb, ductwork
should be attached to the curb prior to ins talling the unit. Ductwork
dimensions are shown in Roof Curb Installation Instructions.
17”7 3/8”
12”
SUPPL Y
6 3/16”
Horizontal Discharge Duct Connections
RIGGING DET AILS
WARNING
O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
T
POSITION DURING ALL RIGGING AND MOVING OPERATIONS.
LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN
ADEQUATE CABLE SLING.
T
O FACILITATE
25”
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit,
center of gravity will cause condenser end t o be lower than supply
air end.
6
To assist in determining rigging requirements, unit weights are
shown as follows:
* Weights shown are belt drive with no accessories.
X
(in)Y(in)
Shipping
Weight
(lbs)
Operating
Weight
(lbs)
Corner Weights ( lbs )
ABCD
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT
BE PRESENT
DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARN ING
HIGH VOLTAGE!
O AVOID PERSONAL INJURY OR DEATH DUE TO
T
ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY
WIRING
. THE
OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE
BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT
ONTACT YOUR LOCAL REPRESENTATIVE IF
C
ASSISTANCE IS REQUIRED
INTERNAL POWER AND CONTROL WIRING
.
.
CAUTION
TO
PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM
SHARP EDGES
LOCAL CODES AND ORDINANCES
REMOVABLE ACCESS PANELS
. F
OLLOW NATIONAL ELECTRICAL CODE AND ALL
. DO
NOT ROUTE WIRES THROUGH
.
CAUTION
C
ONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT
WATER ENTRY INTO THE BUILDING
.
CAUTION
TO
PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
.
Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever curb is used,
care should be taken to center the unit. Check for proper alignment and orientation of supply and return openings with duct.
RIGGING REMOVAL
CAUTION
TO
PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT
.
Remove sprea der bars, lifting cable s and other rigging equipment.
For unit protection, use a fuse or HACR circuit breaker that is in
excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof
fittings. All exterior power supply and ground wiring must be in
approved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiring
to accessory controls must be done in accordance with these instructions, the latest edition of the Na tional Electrical Code (ANSI/
NFP A 7 0), and all local codes and ordinances. All field wiring shall
conform with the temperature limitations for Type T wire (63°F/
35°C rise).
The unit is factory wired for the voltage shown on the unit’s data
plate. Refer to model nomenclature in Appendix B for voltage requirement for your unit.
NOTE: If supply voltage is 208V, lead on primary of transformer
must be moved from the 230V to the 208V tap. Refer to wiring
diagram on unit for details.
Main power wiring should be sized f or the minimum wire ampacity
shown on the unit’s database. Size wires in accordance with the
ampacity tables in Article 310 of the National Electrical Code. If
long wires are required, it may be necessary to increase the wire
size to prevent e xce ssive volt age drop. Wires should be sized f or a
maximum of 3% voltage drop.
7
CAUTION
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
T
ONLY COPPER CONDUCTORS.
CAUTION
O PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING E RRORS,
T
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
ERIFY PROPER OPERATION AFTER SERVICING.
V
NOTE: A weather-tight disconnect switch, properly sized for the
unit total load, must be field or f actory inst alled. An e xt ernal field
supplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied
disconnect switch.
• Some disconnect switches are not fused. Protect the
power leads a t the point of distribution in accordance with
the unit data plate.
• The unit must be electrically grounded in accor dance with
local codes or, in the absence of local codes, with the latest
edition of the National Electrical Code (ANSI-NFPA 70). A
ground lug is provided for this purpose. Size grounding
conductor in accordance with T able 250-95 of the National
Electrical Code. Do not use the ground lug for c onnecting
a neutral conductor.
• Connect power wiring to the compressor co ntactor closest
to the entrance located within the main control box or to
electrical power block, if equipped.
MAIN POWER
LOW VOLTAGE
BLOCK
UNITSINSTALLEDON ROOF TOPS
Main power and low voltage wiring may enter the unit through
the condenser end of unit or through the roof curb. Install c onduit
connectors at the desired entrance locations. External connectors must be weatherproof. All holes in the unit base must be
sealed (including those around conduit nuts) to prevent wat er leakage into building. All required conduit and fittings are to be field
supplied.
Supply voltage to roof top unit mus t not vary by more than 10% of
the value indicated on the unit data plate. Phase voltage unbalance must not exceed 2%. Contact your local power company for
correction of improper voltage or phase unbalance.
HIGH VOLTAGE ENTRANCE
(REMOVE PLUG)
12 3/8”
30 1/4”*
* (6 Ton - 34 1/4”)
1:4
LOW VOLTAGE ENTRANCE
3.5 DIA.
LOW VOLTAGE
ENTRANCE
POWER THRU
THE CURB
Power and Low Voltage Block Connections
WARN ING
F
AILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE
OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT
ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE
DAMAGE TO THE UNIT ELECTRICAL COMPONENTS
.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source be
brought to the vicinity of the roof top unit for portable lights and
tools used by the service mechanic.
NOTE: Refer to local codes for requirements. These outlets can
also be factory installed.
POWER THRU
THE CURB
4 1/2”
47 1/2”
7 1/2”
Electrical Entrance and Thru Curb
Unit is equipped with a Low Voltage Terminal Block and has Single
Point wiring to the contactor or power block, if equipped.
LOW VOLTAGE CONTROL WIRING
1. A 24V thermostat must be installed for unit operation. It
may be purchased with the unit or field -supplied.
Thermostats may be programmable or electromechanical
as required.
2. Locate thermostat or remote sensor in the conditioned
space where it will sense average temperature. Do not
locate the device where it may be directly exposed to
supply air, sunlight or other sources of heat. Follow
installation instructions packaged with the thermostat.
8
3. Use #18 AWG wire for 24V control wiring runs not
exceeding 75 feet. U se #16 A WG wire for 24V con trol wiring
runs not exceeding 125 feet. Use #14 AWG wire for 24V
control wiring runs not exceeding 200 feet. Low voltage
wiring may be National Electrical Code (NEC) Class 2 where
permitted by local codes.
4. Route thermostat wires from sub-base terminals to the
unit. Control wiring should enter through the condenser
panel opening or through curb indicated in “Electrical
Entrance” figure. Connect thermostat and any accessory
wiring to low voltage terminal block TB1 in the main con trol
box.
NOTE:Field-supplied conduit may need to be ins talled depending
on unit/curb configuration. Use #18 AWG solid conductor wire
whenever connecting thermostat wires to terminals on sub-base.
DO NOT use larger than #18 AWG wire. A transition to #18 AWG
wire may be required before entering thermostat sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
GAS SUPPLY PIPING
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR
MAINTENANCE, REFER TO THIS MANUAL
ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER
SERVICE AGENCY OR THE GAS SUPPLIER
. FOR
.
ADDITIONAL
,
IMPORTANT NOTE: This unit is factory set to operate on natural
gas at the altitudes shown on the rating plate.
WARN ING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN
EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES
OBTAIN AND INSTALL THE PROPER CONVERSION KIT(S
DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND/OR
EQUIPMENT DAMAGE
NSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA
I
. H
IGH ALTITUDE KITS ARE FOR
). F
U.S.
AILURE TO
,
The rating plate is stamped with the model number, type of gas
and gas input rating. Mak e sure the unit is equippe d to oper ate on
the type of gas available. Conv ersion to propane (LP) g as is permitted with the use of the factory authorized conversion kit (see the
unit Technical Manual for the appropriate kit). For High Altitude
derates, refer to the latest edition of the National Fuel Gas Code
NFPA 54/ANSI Z223.1.
INLE T GAS PR ESSURE
NATURALM i n. 5.0" W .C ., Ma x. 10.0" W.C.
PROPANEMin. 1 1.0 " W. C., M ax . 14.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.
The minimum supply pressure should not vary from that sho wn in
the table above because this could prevent the unit from having
dependable ignition. In addition, gas input to the burners must
not exceed the rated input shown on the rating plate. Overfiring
of the unit could result in premature heat exchanger failure.
PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not undersize the natur al/propane gas piping fr om the meter/tank to the
unit. When sizing a trunk line, include all appliances on that line
that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas
and gas input rating. Mak e sur e the unit is equipped to oper ate on
the type of gas available. The gas line installation must comply
with local codes, or in the absence of local codes, with the latest
edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Pressure= .50 PSIG or less and Pressure Drop of 0.3" W.C.
(Based on 0.60 Specific Gravity Gas)
CFH =
Refer to the Proper Piping Practice drawing for the general layout
at the unit. The following rules apply:
.
1. Use black iron pipe and fit tings f or the supply piping. The
use of a flex connector and/or copper piping is permitted
as long as it is in agreement with local codes.
2. Use pipe joint compound on male thre a ds only. Pipe joint
compound must be resistan t to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum of
three inches long.
5. Use two pipe wrenches when making connection to the
gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location
(within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8. The unit must be connected to the building piping by one
of the following methods:
• Rigid metallic pipe and fittings
Nominal Black Pipe Size (inches)
1/23/411 1/41 1 /2
BTUH Furna ce In put
Heating Value of Gas (BT U/Cubic Foot
9
• Semirigid metallic tubing and metallic fittings (Aluminum
alloy tubing must not be used in exterior locations)
• Listed ga s appliance c onnector s used in acc or dance with
the terms of their listing that are complet ely in the same
room as the equipment
• In the prior two methods above the connector or tubing
must be protected from physical and thermal damage.
Aluminum alloy tubing and connectors must be coated
to protect agains t external corrosion when in cont act with
masonry, pla st er or insula tion or are subject t o r epe ate d
wettings by liquids (wat er - not rain w a ter, detergents or
sewage).
BURNER
DOOR
There will be air in the gas supply line after testing for leaks on a
new installation. Therefore, the air must be bled from the line by
loosening the ground joint union until pure ga s is expelled. Tighten
union and wait for five minutes until all ga s ha s been dissipa t ed in
the air. Be certain there is no open flame in the vicinity during air
bleeding procedure. The unit is placed in operation by closing the
main electrical disconnect switch for the unit.
PROP ANE GAS INSTALLATIONS
WARNING
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
T
OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS
DETECTING WARNING DE VICE.
OF ODORANT IN PROPANE GAS, A GAS DETECTING W ARNING DEVICE
IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK.
ONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A
C
GAS DETECTING WARNING DEVICE.
INCE RUST CAN REDUCE THE LEVEL
S
TBD
MANUAL
SHUT-OFF
GROUND JOINT
UNION
DRIP
LEG
Proper Piping Practice
NOTE: The unit gas supply entrance is factory sealed with plugs.
Keep plugs in place until gas supply is ready to be installed. Once
ready, replace the plugs with the supplied grommets and install
gas supply line.
GAS PIPING CHECKS
CAUTION
T
O PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE
FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS
CONNECTIONS AND PRESSURE TESTING:
•
HE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE
T
PLACING IN OPERATION.
FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.
EXCEED SPECI FIED PRES SURES FOR TESTI NG.
DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN
PREMATURE HEAT EXCHANGE FAILURE.
HIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM
•
T
THE GAS S UPPLY DURING ANY PRESSURE TE STING OF THAT SYSTEM AT
TEST PRESSUR E S IN EX CES S OF 1/2
HIS UNI T MU ST BE I SOLAT ED FRO M THE GAS SUPPL Y SYS TEM BY
•
T
CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE
TESTING OF THE GAS SUPPLY PI PING SYSTEM AT TEST PRESSURE S
EQUAL TO OR LESS THAN 1/2
BECAUSE OF THE DANGER OF EXPLOSION OR
N
IGHER PRESSURE MAY
H
(3.48 KPA).
PSIG
(3.48 KPA).
PSIG
EVER
IMPORTANT NOTE: Propane gas conversion kits must be installed
to convert units to propane gas. NOx screens must be removed
before converting to LP. Remove burner assembly and pull NOx
screens from each burner tube. When all the screens are out,
reassemble the burner assembly without the screens.
All propane gas equipment must conform to the safety standards
of the National Board of Fire Underwriter s (See NBFU Manual 58).
For satisfactory operation, propane gas supply pressure must be
within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on
three main factors:
1. Vaporization rate, which depends on (a) temperature of
the liquid, and (b) wetted surf ace area of the c ontainer or
containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size
required will depend on length of pipe run and total load
of all appliances.
TANKSAND PIPING
Complete information regarding tank sizing for vaporization,
recommended regulator settings and pipe sizing is available
from most regulat or manufacturers and pr opane gas suppliers .
Since propane gas will quickly dissolve white lead or most
standard commer cial compounds, special pipe dope must be
used. Shellac base compounds resistant to the actions of
liquefied petroleum ga ses such as Gasolac®, Stalactic®, Clyde’ s
or John Crane® are satisfactory.
See the following figure for typical propane gas piping.
®
WARNING
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY
T
NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.
, BE SURE THERE IS
10
First Stage
Regulator
200 PSIG
Maximum
Typical Propane Gas Piping
5 to 15 PSIG
(20 PSIG Max.)
Continuous
Second Stage
Regulator
11" W.C.
ROOF TOP LOCATIONAND INSTALLATION
The gas supply piping location and installation for roof top units
must be in accordance with local codes or, in the absence of locals
codes, with ordinances of the latest edition of the National Fuel
Gas Code (ANSI Z223.1).
A manual gas shut off valve must be field installed e xternal to the
roof top unit. In addition, a drip leg must be installed near the
inlet connection. A ground joint union connection is required between the external shut off valve and the unit connection to the
gas valve to permit removal of the burner assembly for servicing.
1. Route gas piping to unit so that it does not interfere with
the removal of access panels. Support and align piping to
prevent strains or misalignment of the manif old assembly .
2. All units are furnished with standard female NPT pipe
connections. Connection pipe sizes for DCG036 through
072 units is 1/2" NPT on 045 to 140 mBH units. The size of
the gas supply piping to the unit must be base d on leng th
of run, number of units on the system, g as char acteristics,
BTU requirement and av ailable supply pressure. All piping
must be done in accordance with local codes or, in the
absence of local codes, with the latest edition of the
National Fuel Gas Code (ANSI Z223.1).
NOTE:The gas connection size at the unit does NOT
establish the size of the supply line.
3. These units are designed for either natural or propane
(LP) gas and are specifically constructed at the factory for
only one of these fuels. The fuels are NOT int erchangeable.
However, the furnace can be converted in the field from
natural gas to LP gas with the appropriate factory kit (see
unit Technical Manual for the appropriate kit). Only a
qualified contractor, experienced with natural and propane
gas systems, should attempt conversion. Kit instructions
must be followed closely to assure safe and reliable unit
operation.
4. With all units on a common line operating under full fire,
natural gas main supply pressure should be adjusted to
approximately 7.0" w.c., measured at the unit gas valv e. If
the gas pressure a t the unit is greater than 10.5" w.c., the
contractor must furnish and install an external type
positive shut off service pressure regulator. The unit will
not function satisfactorily if supply gas pr essure is less than
5.5" w.c. or greater than 10.5" w.c..
NOTE:A minimum horizontal distance of 48" between
the regulator and the furnace flue discharge is required.
5. With all units on a common line operating under full LP
gas main supply pressure should be a t leas t 11.0" w .c. and
must be no greater than 13.0" w.c., measured at the unit
gas valve. Unit will not function satisfactorily if supply gas
pressure is less than 11.0" w.c. or greater than 13.0" w.c..
6. All pipe connections should be sealed with a pipe thread
compound, which is resistant to the fuel used with the
furnace. A soapy water solution should be used to check
all joints for leaks. A tap is located on the entering side of
the gas valve f or tes t g auge connection t o measure supply
(main) gas pressure. Another tap is provided on the
manifold side of the gas valve for checking manifold
pressure.
WARN ING
T
HIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE
DISCONNECTED
PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN
EXCESS OF
1/2 PSIG (13.8” W.C.).
FROM THE GAS SUPPLY SYSTEM DURING ANY
CAUTION
T
HIS UNIT MUST BE
SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE
DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN
PSIG.
ISOLAT ED
FROM THE GAS SUPPLY PIPING
1/2
7. There must be no obstruction to prevent the flow of
combustion and ventilating air. A vent stack is not required
and must never be used. The power venter will supply an
adequate amount of combustion air as long as the air
passageways are kept free of any obstructions and the
recommended external unit clearances are maintained.
CIRCULA TING AIR AND FIL TERS
DUCTWORK
The supply duct from the unit through a wall may be ins talled without clearance. However, minimum unit clearances must be maintained (see “Clearance s” section). The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly
attached to prevent air leaks.
Ductwork dimensions are shown in the roof curb installation
manual.
If desired, supply and return duct connections to the unit may be
made with flexible connections to reduce possible unit operating
sound transmission.
11
VENTING
PRE-STARTUP INSTRUCTIONS - GENERAL
NOTE: Venting is self-contained.
The indoor motor on DCG units are dual voltag e motor s. They ar e
factory wired for 230 volts. If field supply power is 208V, the
installer must swap the connections to the black and red loads
(located in the blower compartment) to ensure correct inductor
motor operation.
CONDENSA TE DRAIN CONNE CTION
CONDENSATE DRAIN CONNECTION
A 3/4” female NPT drain connection is supplied on the end of the
unit and bottom of the drain pan f or condensat e piping. An ext ernal trap must be installed for proper condensate drainage.
DRAIN
CONNECTION
UNIT2" MINIMUM
FLEXIBLE
TUBING-HOSE
OR PIPE
A POSITIVE LIQUID
SEAL IS REQUIRED
Drain Connection
3" MIN IMUM
Install condensate drain trap as shown. Use 3/4" drain line and
fittings or larger. Do not operate without trap.
HORIZONTAL DRAIN
Drainage of condensate directly on to the r oof ma y be accept able;
refer to local code. It is recommended that a small drip pad of
either stone, mortar, wood or metal be provided to prevent any
possible damage to the roof.
CLEANING
Due to the fact that drain pans in any air conditioning unit
will have some moisture in them, algae and fungus will
grow due to airborne bacteria and spores. Periodic cleaning is necessary to prevent this build-up from plugging the
drain.
ST ARTUP, ADJUSTMENTS, AND CHECK S
WARN ING
CAUTION
TO
PREVENT PROPERTY DAMAGE OR PERSONAL INJURY
START THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TESTS
HAVE BEEN PERFORMED
.
, DO
NOT
Prior to the beginning of Startup, Adjustments, and Checks pr ocedures, the following steps should be completed in the building.
WARN ING
MOVING MACHINERY HAZA RD!
O PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT
T
POWER TO THE UNIT AND PADLOCK IN THE
SERVICNG FANS
.
“OFF”
POSITION BEFORE
This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower
to exhaust combustion products.
On new installations, or if a major component has been replaced,
the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If
any sparking, odors, or unusual sounds are encountered, shut off
electrical power and recheck for wiring errors, or obstructions in
or near the blower motors. Duct cover s must be removed before
operating unit.
The Startup, Adjustments, and Checks procedure provides a s tepby-step sequence which, if follow ed, will assure the proper st artup
of the equipment in the minimum amount of time. Air balancing
of duct system is not considered part of this procedure. However,
it is an important phase of any air c onditioning syst em startup and
should be performed upon completion of the Startup, Adjustments ,
and Checks procedure. The St artup, Adjustment s, and Checks procedure at outside ambients below 55°F should be limit ed to a readiness check of the refrigera tion system with the requir ed final check
and calibration left to be completed when the outside ambient
rises above 55°F.
TEMPORARY HEATING OR COOLING
If the unit is to be used for tempor ary heating or cooling, a “Startup,
Adjustments, and Checks” must first be performed in accordance
with this manual. Failure to comply with this requir ement will void
the warranty. After the machines are used for temporary heating
or cooling, inspect the coils, fans, and motors for unacceptable
levels of construction dust and dirt and install new filters.
HIGH VOLTAGE!
O AVOID PERSONAL INJURY OR DEATH DUE TO
T
ELECTRICAL SHOCK, B
THE BUILDING ELECTRICAL GROUND BY USE OF THE
GROUNDING TERMINAL PROVIDED OR OTHER
ACCEPTABLE MEANS
SERVICING OR INSTALLING THIS UNIT
OND THE FRAME OF THIS UNIT TO
. D
ISCONNECT ALL POWER BEFORE
.
CONTRACTOR RESPONSIBILITY
The installing contractor must be certain that:
•All supply and return air ductwork is in place, properly
sealed, and corresponds with installation instructions.
•All thermostats are mounted and wired in accordance
with installation instructions.
12
•All electric power, all gas, hot water or steam line
connections, and the condensate drain installation have
been made to each unit on the job. These main supply
lines must be functional and capable of operating all unit s
simultaneously.
•Requirements are met for venting and combution air.
•Air filters are in place.
•Input rate and temperature rise are adjusted per rating
plate.
ROOF CURB INSTALLATION CHECK
Inspect the roof curb for correct installation. The unit and curb
assembly should be level. Inspect the flashing of the roof mounting curb to the roof, especially at the corners, for good workmanship. Also check for leaks around g a s kets. Note any deficiencie s in
a separate report and forward to the contractor.
OBSTRUCTIONS, FAN CLEARANCEAND WIRING
Remove any extraneous construction and shipping materials that
may be found during this procedure. Rotate all fans manually to
check for proper clearances and that they rotate freely. Check for
bolts and screws that may have jarred loose during shipment to
the job site. Retighten if necessary. Re-tighten all electrical connections.
Three Phase Models Only
2) MAXIMUM VOLTAGE DEVIATIONS
3) PERCENT VOLTAGE
UNBALANCE
HOW TO USE THE FORMULA:
EXAMPLE: With voltage of 220, 216, and 213
1) Average Voltage = 220+216+213=649 / 3 = 216
2) Maximum Voltage Deviation s fro m Average Voltage = 220 - 216 = 4
3) Percent Voltage Unbalance = 100 x = = 1.8%
Percent voltage unbalance MUST NOT exceed 2%
= 100 X
FROM AVERAGE VOLT AG E
1) AVERAGE VOLTAGE
4
216
400
216
.
AIR FLOW ADJUSTMENTS
When the final adjustments are comple te, the curren t draw of the
motor should be checked and compared to the full load current
rating of the motor. The amperage must not exceed the service
factor stamped on the motor nameplate. The total airflow must
not be less than that required f or oper ation of the electric heat ers
or the furnace.
If an economizer is installe d, check the unit operating balance with
the economizer at full outside air and at minimum outside air.
NOTE: Never run CFM below 350 CFM per ton, evapor ator freezing
or poor unit performance is possible.
FIELD DUCT CONNECTIONS
Verify that all duct connections are tight and that there is no air
bypass between supply and return.
FILTER SECTION CHECK
Remove filter section access panels and check that filter s are properly installed. Note airflow arrows on filter frames.
PRE-STARTUP PRECAUTIONS
It is important to your safety that the unit has been properly
grounded during installation. Check gr ound lug connection in main
control box for tightness prior to closing circuit break er or disconnect switch. Verify that supply voltage on line side of disconnect
agrees with voltage on unit identification plate and is within the
utilization voltage rang e as indicate d in Appendix B Electrical Data.
System Voltage - That nominal voltage value assigned to a circuit
or system for the purpose of designating its voltage class.
Nameplate Voltage - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the
purpose of defining the minimum and maximum voltage at which
the equipment will operate.
Utilization Voltage - The voltag e of the line terminals of the equipment at which the equipment must give fully satisfactory performance. Once it is established that supply voltage will be maintained within the utilization range under all system conditions,
check and calculate if an unbalanced condition exists between
phases. Calculate percent voltage unbalance as follows.
PSC MOTOR
Adjust the CFM for the unit by changing the speed tap of the indoor blower motor at the heat or cool tap on the control board
connection with the one of the speed taps on “M1” or “M2” (Black High Speed, Blue-Medium Speed, Red-Low Speed).
EEM Motor
Adjust the CFM for the unit by changing the position of the low
voltage leads on the motor terminal block. Green is for Fan Only.
Y ello w is for Cooling and Heat Pump Heating. Refer to Appendix A
for blower performance at each speed tap. NOTE: If more than
one lead is energized simultaneously, the motor will run at the
higher speed.
SET EVAPORATOR FAN RPM
Actual RPM’s mus t be set and verified with a tachomet er or strobe
light. Refer to Appendices A and B for basic unit fan RPM. Refer
also to “Airflow ” section of this manual. W ith disconnect switch
open, disconnect thermostat wires from terminals Y and W. This
will prevent heating and mechanic al cooling from coming on. Place
a jumper wire across terminals R and G at TB1 terminal block. Close
disconnect switch; evaporator fan motor will operate so RPM can
be checked.
For gas heat units, the airflow must be adjusted so that the air
temperature rise f alls within the r ange s given s tated on Data Plate
(see Appendix A - Blower Performance).
13
EVAPORATOR FAN ROTATION CHECK (THREE PHASE MODELS ONLY)
Check that fan rotate s clockwise when viewe d fr om the driv e side
of unit and in accordance with rotation arrow shown on blower
housing. If it does not, reverse any two incoming power cables at
Single Point Power Block. In this case, repeat bearing check.
Do not attempt to change load side wiring. In ternal wiring assur es
all motors and compressors will rotate in correct direction once
evaporator fan motor rotation check has been made.
ELECTRICAL INPUT CHECK
Make preliminary check of evapor ator f an ampere dra w and verify
that motor nameplate amps are not exceeded. A final check of
amp draw should be made upon completion of air balancing of
the duct system (see Appendix C).
BELT DRIVE MODELS ONLY
The drive on the supply fan is typically set in the middle of the
RPM range. The drive motor sheave pitch diameter is field adjustable for the required airflow. Refer to “Motor Shea ve Adjustmens”
section.
Upon completion of the air flow balancing, we recommend replacing the variable pitched motor sheave with a properly-sized
fixed sheav e. A ma tching fix e d she a v e will provide longer belt and
bearing life and vibration fr ee oper ation. Initially, it is best to have
a variable pitched motor sheav e for the purpose of airflow balancing, but once the balance has been achieved, fixed sheaves maintain alignment and minimize vibra tion mor e e f fectively. For direct
drive units, move fan speed wire.
BEARING CHECK
Prior to energizing any f ans, check and make sure tha t all setscrews
are tight so that bearings are properly secured to shafts.
TENSIONAND ALIGNMENT ADJUSTMENT
Correct belt tension is very important to the life of your belt. Too
loose a belt will shorten its life; too tight, premature motor and
bearing failure will occur. Check you belt drive for adequate “runin” belt tension by measuring the force required to deflect the
belt at the midpoint of the span length. Belt tension force can be
measured using a belt tension gauge, available through most belt
drive manufacturers.
S
P
A
N
L
E
N
G
T
H
*
D
E
F
t
F
L
E
C
T
I
O
N
O
R
C
E
t = Span length, inches
C = Center distance, inches
D = Larger sheave diameter, inches
d = Smaller sheave diameter, inches
h = Deflection height, inches
SMALL
TYPEDEFLECTION
BELTDRIVEUSEDNEW
AXStandard3.0 to 4.0 4.2 ± 0.5 5.5 ± 0.50.313
SHEAVE
DIAMETER
(in)
Recommended Pounds of Force Per Belt
DEFLECTION
FORCE (lbs)
(in)
New V-belts will drop rapidly during the first few hours of use.
Check tension frequently during the first 24 hours of operation.
T ension should f all between the minimum and maximum f orce. To
determine the deflection distance from a normal position, measure the distance from sheave to sheave using a straightedge or a
cord. This is your reference line. On multiple belt drives, an adjacent undeflected belt can be used as a reference.
MOTOR SHEAVE AD JUSTMENTS
VL, VM, & 2VP VARIABLE PITCH KEY TYPE MOTOR SHEAVES
The driving and driven motor sheave s should be in alignment with
each other and the shafts parallel.
VL & VM SHEAVES ADJUSTMENT
1. Loosen set screw “B” using a 5/32" Allen key.
2. Making half or full turns from closed position, adjust
sheave pitch diameter for desired speed. DO NOT OPEN
MORE THAN FIVE FULL TURNS.
3. Tighten set screw “B” securely over flat.
4. Carefully put on belts and adjust belt tension. DO NOT
FORCE BELTS OVER GROOVES.
5. Ensure all keys are in place and the se t screws tigh t befor e
starting drive. Recheck set screws and belt tension after
24 hours service.
NOTE: Future adjustments should be made by loosening the belt
tension and increasing or decreasing the pitch diameter of the
sheave by half or full turns as r equired. R eadjust belt tension be fore
starting drive.
D
*Apply force to the center of the span.
Belt Tension Adjustment
h
H
d
C
14
W ARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO
NOT FIRE GAS UNIT WITH FLUE BOX COVER REMOVED
.
C
B
VL & VM
NOTE:Do NOT operate sheave with flange projecting beyond
the hub end.
GAS SYSTEM CHECK
Pre-Operation Checks
1. Close the manual gas valve external to the unit.
2. Turn off the electrical power supply to the unit.
3. Set the room thermostat to its lowest possible setting.
4. Remove the heat exchanger door on the side of the unit
by removing screws.
5. This unit is equipped with an ignition device which
automatically lights the main burner. DO NOT try to light
burner by any other method.
6. Move the gas contr ol v alv e switch t o the OFF position. Do
not force.
7. Wait five minutes to clear out any gas.
8. Smell for gas, including near the gr ound. This is important
because some types of gas ar e heavier than air. If you have
waited five minutes and you do smell gas, immediately
follow the warnings on page 3 of this manual. If having
waited for five minutes and no gas smell is noted, move
the gas control valve switch to the ON position.
9. Replace the heat exchanger door on the side of the unit.
10. Open the manual gas valve external to the unit.
11. Turn on the electrical power supply to the unit.
12. Set the thermostat to desired setting.
NOTE:Except during brief periods when gas pr essure s are being
measured by qualifie d service personnel, the furnace access panel
must always be secur ed in place when the furnace is in opera tion.
An inspection port in the access panel is provided to monitor the
flame.
The first step in checking out the gas-fired furnace is to test the
gas supply piping to the unit for tigh tness and pur ge the s ys tem of
air using methods outlined in the latest edition of the National
Fuel Gas Code ANSI Z223.1. Verify that the disc onnect swit ch is in
the “OFF” position. A soapy water solution should be use d to check
for gas leaks. Since the unit is subject to considerable jarring during shipment, it is extremely important that all gas connections
and joints be tested for tightness. Gas piping downstream from
the unit inlet should be checked for leaks during the subsequent
sequence check.
The supply gas pressure should be a djust ed t o 7.0" w.c. on natural
gas and 11.0" on LP gas with the gas burners operating. If there is
more than one unit on a common gas line, the pressures should
be checked with all units under full fire. A supply pressure tap is
provided on the upstream side of the gas valve. A manifold pressure tap is provided on the gas valve. The normal manifold pressure for full input is 3.5" w.c. on natural gas and 9.5" w.c. for propane gas. Low fire natur al ga s 2.0” w .c., 6.0” low fire pr opane g as.
Minimum gas supply pressure is 5.5" w.c. for natural gas and 11.0"
for propane g as. In order to obt ain rating, gas supply pr essure must
be 11.0" w.c. for propane gas.
The pressure regulator on LP gas models is adjusted for 9.5" w.c.
manifold pressure and is intended to prevent over-firing only. Do
not attempt adjustment of the built-in pressure regulator unless
the supply pressure is at le ast 7.0" w.c. on natural gas or 13.0" w .c.
on propane gas. Check the loc ation of the ignition electrode and
the flame sensor for correct gap setting.
FLAME
SENSOR
GAS SUPPLY PRESSURES & REGULATOR ADJUSTMENTS
W ARNING
S
HOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT
OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE
UNIT BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
15
Flame Sensor and Ignition Electrode Location
MAXIMUM
INPUT
(BTUH)
45,000223,000#43# 55
NUMBER
of
BURNERS
MAXIMUM
BTUH/BURNER
GAS ORIFICES
NATURAL
(Dia)
PROPANE (LP)
(Dia)
Manifold Pressure Check
The gas valve has a tapped opening to facilitate measurement of
the manifold pressur e. A “U” Tube manomet er having a scale range
from 0 to 12 inches of water should be used for this measurement. The manifold pressure must be measured with the burners
operating.
115,000523,000#43# 55
140,000623,000#43# 55
90,000423,000#43# 55
Heat Exchanger and Burner Orifice Specifications
NOTE: G as appliances locate d more than 2000 feet abov e sea level
must be derated 4% per 1000 feet of total elevation and that
variance in gas heating value and specific gravity require change
in manifold pressure to obtain r ating, it is mandatory that the input
be adjusted at the installa tion site. All installations should be made
as outlined in the latest e dition of the National Fuel Gas Code ANSI
Z223.1,section “Procedure s To Be Followed To Place An Appliance
in Operation”. Refer also to the “User’s Information Manual”
supplied with the unit for additional informa tion on the gas furnace.
Gas Supply And Manifold Check
Gas supply pressure and manif old pressur e with the burners oper ating must be as specified on the rating plate.
Gas Inlet Pressure Check
Gas inlet pressure must be check e d and adjus te d in accor dance to
the type of fuel being consumed.
With Power And Gas Off:
1. Connect a water manometer or adequate gauge to the
inlet pressure tap of the gas valve.
Inlet gas pressure can also be measured by removing the
cap from the dripleg and installing a predrilled cap with a
hose fitting.
With Power And Gas On:
2. Put unit into heating cycle and turn on all other gas
consuming appliances.
INLE T GAS PR ESSURE
NATURALM i n. 5.0" W .C ., Ma x. 10.0" W.C.
PROPANEMin. 1 1.0 " W. C., M ax . 14.0" W.C.
NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value
Shown.
If operating pressure s diff er fr om above, mak e nece ssary pressur e
regulator adjustmen ts, check piping size, et c., and/ or consult with
local utility.
1. With disconnect switch open, remove field connected
thermostat wire from terminal R, W1 and W2 on TB1.
Place jumper wire between R, W1 and W2 to eng age high
stage heat. (note on 045 kbtu/hr units W2 is not used,
only jumper R to W1).
2. See Figure in input rating section for g as valve adjustmen t.
To adjust the pressure regulator, remove the adjustment screw or
cover on the gas valve. Turn out (counterclockwise) to decrease
pressure, turn in (clockwise) to increa se pressure. O nly small variations in gas flow should be made by means of the pr essur e regulator adjustment. In no case should the final manif old pr essur e vary
more than plus or minus 0.3 inches water c olumn from the specified nominal pressure. An y major change s in flow should be made
by changing the size of the burner orifices. The measured input
rate to the furnace must not exceed the rating specified on the
unit rating plate.
For natural ga s, the high stage manifold pre ssure must be between
3.2 and 3.8 inches water column (3.5 nominal). Low stage manifold pressure must be between 1.7 to 2.3 inches water column
(2.0 nominal).
3. To set low fire rate on 090, 115 and 140 kbtu/hr: Open
disconnect switch, and remove jumper from R to W2. To
set low fire manifold pressure, repeat steps above. Refer
to Figure in input rating section for location of high and
low stage adjustment.
For propane gas, the manifold pressure must be between 9.7 and
10.3 inches water column (10.0 nominal). Low st age manifold must
be between 5.7 and 6.3 inches water column (6.0 nominal).
Gas Input (Natural Gas Only) Check
It is the responsibility of the contractor to adjust the gas input to
the unit.
To measure the gas input use a gas meter and proceed as
follows:
1. Turn off g as supply t o all other appliances ex cept the unit.
2. With the unit operating, time the smallest dial on the
meter for one complete r evolution. If this is a 2 cubic f oot
dial, divide the seconds by 2; if it is a 1 cubic foot dial, use
the seconds as is. This gives the seconds per cubic foot of
gas being delivered to the unit.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
Example: Natural gas with a heating value of 1000 BTU per cubic
foot and 34 seconds per cubic foot as det ermined by St ep 2, then:
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE:
BTU content of the gas should be obtained from the gas
supplier. This measured input must not be greater than
shown on the unit rating plate.
16
Adjust input rate by varying the adjustment of the gas pressure
o
regulator on the gas valve. All adjustments must be made with
furnace operating at high fire and at normal operating temperature. A manometer should be connected t o the gas valve to verify
pressure is within the specified range (see following figures for
manometer connections). Clockwise rotation of the pr essure regulator screw increase s pre ssure and g as flow r at e. Turn screw counterclockwise to decrease pressure and gas flow rate. After adjustment the furnace temperatur e rise must be within the range specified on the unit data plate. NOTE: Thermal efficiency of the furnace is a product efficiency rating determined under continuous
operating conditions independent of any installed system.
Outlet Pre ssure
Tap
INLET
Inlet Pressure
Tap
Pressure Regulator
Adjustment
(Under Cap Screw)
OUTLET
Gas Valve
On/Off
Selector
Switch
White-Rodgers 36G22 - Single Stage
Open t
Atmosphere
M
r
e
t
o
m
e
n
a
e
o
s
H
Outlet
Pressure Boss
High Fire Re gulator
Adjust
Regulator
Vent
5. Using a leak detection solution or soap suds, check for le aks
at pressure boss screw. Bubbles forming indicate a leak.
SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE
GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE
ADJUSTING THE GAS VALVE PRESSURE REGULATOR
. O
NLY MINOR ADJUSTMENTS SHOULD BE MADE BY
.
4. Relight all other appliances turned off in s t ep 1. Be sur e all
pilot burners are operating.
Main Burner Flame Check
Flames should be stable, soft and blue (dust may cause orange
tips but they must not be yellow) and extending directly outward
from the burner without curling, floating or lifting off.
NOx Screen Check
Verify that the alignment of the NOx screens is at 6 o' clock. In
jurisdictions that do not require low NOx emissions, NOx screens
may be removed.
Temperature Rise Check
Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be
obtained.
1. All registers must be open; all duct dampers must be in
their final (fully or partially open) position and the unit
operated for 15 minutes before taking readings.
2. The temperature rise must be within the range specified
on the rating plate.
Low Fire
Regulator Adjust
Inlet
Pressure Boss
r
e
t
Man
e
o
m
White-Rodgers 36G54 (2-Stage) Connected to Manometer
Pressure Adjustments
To connect manometer to gas valve:
1. Back outlet pressure t est screw (inlet/ outlet pressur e boss)
out one turn (counterclockwise, not more than one turn).
2. Attach a hose and manometer t o the outlet pre ssure boss
of the valve.
To remove manometer from gas valve:
1. Remove manometer hose from outlet pressure boss.
2. Turn outlet pressure test screw in to seal pressure port
(clockwise, 7 in-lb. minimum).
3. Turn on electrical power and gas supply to the system.
4. Turn on system power and energize valve.
NOTE: Air temperatur e rise is the temperature dif ference between
supply and return air.
With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at
rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may
be necessary to change the blower speed. A higher blower speed
will lower the temperature rise. A slower blower speed will increase the temperature rise.
NOTE: Blower speed MUST be set to give the correct air
temperature rise through the unit as marked on the rating plate.
NORMAL SEQUENCE OF OPERA TION
HEATING
This unit has one (RS) Manual Reset Limit Control Switch. Check
the limit to make sure it has not tripped. The limit may arrive at
the job site tripped as a result of shipping shock.
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.