7½- TO 12½-TON THREE-PHASE
PACKAGED AIR CONDITIONERS
UP TO 11.3 EER
Cooling Capacity:
88,000 — 144,000 BTU/h
■ Contents
Nomenclature ......................... 2
Product Specifications ............ 4
Expanded Cooling Data .......... 8
Airflow Data .......................... 16
Heat Kit Electrical Data ........ 20
Dimensions .......................... 24
Wiring Diagrams .................. 29
Accessories .......................... 35
■ Standard Features
• R-410A chlorine-free refrigerant
• High-efficiency scroll compressors
• Two-stage cooling
• Copper tube / aluminum fin coils
• Power block for field wiring
• High- and low-pressure switches
• High-capacity, steel-cased filter drier
• Heater kits with single-point entry
• 24-volt terminal strip
• Units meet the performance outlined in Table 6.8.1A of ASHRAE Standard 90.1-2010
• AHRI Certified; ETL Listed
SS-DCC7www.daikincomfort.com6/15
■ Cabinet Features
• Heavy-gauge, galvanizedsteel cabinet with UV-resistant
powder-paint finish
• Built-in filter rack with standard 2” filters
• Convertible airflow orientation
• Easy to service
• Full perimeter rail
• Sloped drain pan
* Complete warranty details available from your local dealer or at www.daikincomfort.com.
Supersedes 11/14
NomeNclature
BrandFactory-Installed Options
D DaikinX No Opons
ConfigurationB Powered convenience outlet
C Standard EciencyC Low-ambient kit
THigh EciencyD Return air smoke detector
ApplicationE Supply air smoke detector
C CoolingF Non-powered convenience outlet;
G Gas HeatLow-ambient kit
H Heat PumpG Non-powered convenience outlet;
Supply Fan/Drive Type/Motorkit; Return & Supply air smoke detectors
B Belt Drive (singe speed) V Two-Speed Belt DriveU Non-powered convenience outlet;
D Direct DriveLow-ambient kit; Return air smoke detector
Factory-Installed OptionsW Low-ambient kit; Supply air smoke detector
XNo OponsY Low-ambient kit; Return & Supply
A Downow Economizerair smoke detectors
H Disconnect Switch (non-fused)Z Return & Supply air smoke detectors
JDownow Economizer; Disconnect Switch (non-fused)
Note: Not all opons available for all products.X Standard Aluminized Heat Exchanger
DCC0900453B***A *
1234,5,67,8,9101112131415 16
Revision Levels
Major & Minor
A Non-powered convenience outlet
Return air smoke detector
L Non-powered convenience outlet;
Q Powered convenience outlet; Low-ambient
T Powered convenience outlet; Low-ambient
V Low-ambient kit; Return air smoke detector
Factory-Installed Options
S Stainless-Steel Heat Exchanger
2www.daikincomfort.comSS-DCC7
NomeNclature
Factory-Installed Options
• Stainless-Steel Heat Exchanger (DCG units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.
• Low-Ambient Kit: Allows for cooling operaon at lower outdoor temperatures. On the 3- to 6-ton units, cooling operaon is extended
from 60°F ambient temperature to 35°F outside air temperature. On 7½- to 20-ton units, cooling operaon is extended from 35°F ambient temperature to 0°F outside air temperature.
• Economizers (Downow): Based on air condions, can provide outside air to cool the space.
• Electric Heat Kits (DCC and DCH units only): Available in all voltage opons.
• Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs
power to the outlet.
• Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units,
increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protecon) device must be sized accordingly.
• Disconnect Switch (non-fused): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the
unit. Please note that for air condioning (DCC units) and heat pump models (DCH units), the appropriate electric heat kit must be
ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models with a
powered convenience outlet opon and a disconnect switch (non-fused) opon, the power to the powered convenience outlet will be
shut o when the disconnect switch (non-fused) is in the o posion.
• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.
• Two-speed indoor fan blower models are available on 7½, 8½, 10, 12½, 15, & 20-ton units. Secon 6.4.3.10.b of ASHRAE Standard
90.1-2010 and Secon 6.5.3.2.1.a of ASHRAE Standard 90.1-2013 require a minimum of two fan speeds. Secon 140.4(m)1 of California
Energy Commission Title 24 2013 contains a similar provision. When the units with the two-speed indoor fan blowers operate on a call
for the rst stage of cooling, the fan operates at low speed, which is 66% of full speed. When the units operate on a call for the second
stage of cooling, the fan operates at full speed. In heang operaon, the fan operates at full speed. During venlaon operaon, the fan
operates at low speed.
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
Locang
Dimple
DCC090
***3V***A*
Locang
Dimple
DCC090
***4B***A*
Locang
Dimple
DCC090
***4V***A*
Locang
Dimple
DCC090
***7B***A*
Locang
Dimple
DCC090
***7V***A*
Locang
Dimple
4www.daikincomfort.comSS-DCC7
Product SPecificatioNS — 8½ toNS
DCC102
***3B***A*
Cooling Capacity
Total BTU/h102,000102,000102,000102,000102,000102,000
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
Locang
Dimple
DCC102
***3V***A*
Locang
Dimple
DCC102
***4B***A*
Locang
Dimple
DCC102
***4V***A*
Locang
Dimple
DCC102
***7B***A*
Locang
Dimple
DCC102
***7V***A*
Locang
Dimple
SS-DCC7www.daikincomfort.com5
Product SPecificatioNS — 10 toNS
DCC120
***3B***A*
Cooling Capacity
Total BTU/h116,000116,000116,000116,000116,000116,000
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
Voltage / Phase / Frequency208-230/3/60208-230/3/60460/3/60460/3/60575/3/60575/3/60
Standard Max Stac1.4"1.4"1.4"1.4"1.4"1.4"
Outdoor Fan FLA ea.2.002.000.850.850.670.67
Total Unit Amps5957.92826.921.420.7
Min. Circuit Ampacity
Max. Overcurrent Protecon (amps)
Entrance Power Supply
Entrance Control Voltage
1
2
6563.53129.92323
808040403030
Locang
Dimple
Locang
Dimple
Locang
Dimple
Locang
Dimple
Locang
Dimple
Locang
Dimple
Operating Weight (lbs)122512251225122512251225
Ship Weight (lbs)125012501250125012501250
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
Hi PR227244258269254274289302289.4311329343329.6 355375391371399421439410441466486
Lo PR105112122130111118129137115123134143121129141150127135147157131140153162
IDB: Entering Indoor Dry Bulb TemperatureShaded area reects ACCA (TVA)Rang CondionsAmps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and sucon access ngs.Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the sucon and liquid service ports, AHRI 95 test condions
Hi PR231249263274260279295308295318335350336362382399378407430448418450475495
Lo PR107114124133113120131140118125137146124131144153130138150160134143156166
IDB: Entering Indoor Dry Bulb TemperatureShaded area reects AHRI Rang CondionsAmps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and sucon access ngs.Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the sucon and liquid service ports, AHRI 95 test condions
High and low pressures are measured at the liquid and sucon access ngs.Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the sucon and liquid service ports, AHRI 95 test condions
High and low pressures are measured at the liquid and sucon access ngs.Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the sucon and liquid service ports, AHRI 95 test condions