Goodman DCC048 Installation Manual

Page 1
INSTALLATION INSTRUCTIONS
DCC/DCH SERIES
LIGHT COMMERCIAL PACKAGED HEATING AND COOLING UNIT
7.5 to 12.5 TON
Index
Replacement Parts................................................................ 2
Safety Instructions................................................................ 2
General Information ............................................................. 2
Unit Location ........................................................................ 3
Clearances ............................................................................ 4
Roof Curb Post-Installation Checks ....................................... 5
Roof Top Duct Connections................................................... 5
Rigging Details ...................................................................... 5
ATTENTION INSTALLING PERSONNEL:
Prior to installation, thoroughly f amiliarize yourself with this Installation Manual. Observe all safety warnings. During in­stallation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of single package heating and cooling units. See the Specification Sheet applicable to your model for information regarding accessories.
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
Electrical Wiring.................................................................... 7
Circulating Air and Filters...................................................... 9
Condensate Drain Connection .............................................. 9
Startup, Adjustments, and Checks ..................................... 10
Air flow Adjustments .......................................................... 11
Motor Sheave Adjustments ................................................ 12
Heat Pump Operation.........................................................14
Maintenance ...................................................................... 15
Troubleshooting.................................................................. 15
Appendix A Blower Performance Data................................ 17
Belt Drive - Standard Down Shot ................................... 17
Belt Drive - Standard Horizontal .................................... 18
Belt Drive - High Static Down Shot................................. 19
Belt Drive - High Static Horizontal.................................. 20
Appendix B Electrical Data..................................................21
Appendix C Unit Dimensions............................................... 22
IOD-1002D 12/2014
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2014
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
Page 2
REPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFF AIRS
DAIKIN NORTH AMERICA LLC
7401 SECURITY W AY
HOUSTON, TEXAS 77040
855-770-5678
WA RNING
T
HIS UNIT MUST NOT BE USED AS A “CONSTRUCTION HEATER DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES
. T
HIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE
.
WARNING
HIGH VOLTAGE! D
ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARNING
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, plea se read this manual to f amiliarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
Keep this literature in a safe place for future reference.
CAUTION
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION
.
W ARNING
T
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS
WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM
.
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
HIGH VOLTAGE!
INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE PERFORMED MINIMUM) THE REQUIREMENTS OF AN
T
ECHNICIAN” AS SPECIFIED BY THE AIR CONDITIONING
HEATING AND REFRIGERATION INSTITUTE
TTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT
A
SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH
ONLY BY
INDIVIDUALS MEETING(AT A
“E
.
GENERAL INFORMA TION
NTRY LEVEL
(AHRI).
,
,
WARNING
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE,
T
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELE CTRIC SHOCK OR CARBON MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED, AND MAINTAINED.
This unit is approved for outdoor inst allation ONLY. Rated perf or­mance is achieved after 72 hour s of operation. Rated perf ormance is delivered at the specified airflow. See outdoor unit specifica­tion sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.daikincomfort.com for Daikin brand prod­ucts. Within either website, please select the residential or com­mercial products menu and then select the submenu for the type of product to be installed, such as air conditioner s or heat pumps, to access a list of product pages that each contain links to that model’s specification shee t.
WARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO
NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER
I
MMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER
.
.
To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these in­stallation and operating instructions, all local building codes and ordinances.
2
Page 3
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA)
HAS ISSUED VARIOUS RE GULATIONS REGARDING THE INTRODUCTION AND DISPOSAL
REFRIGERANTS IN THIS UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY
OF
THE ENVIRONMENT AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL
HARM
. BECAUSE REGULATIONS MAY VARY DUE TO PASSAGE OF NEW LAWS, WE
FINES
A CERTIFIED TECHNICIAN PERFORM ANY WORK DONE ON THIS UNIT.
SUGGEST
SHOULD YOU HAVE ANY QUESTIONS PLEASE CONTACT THE LOCAL OFFICE OF THE EPA.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough inve stigation of each claim. The distributor or manufacturer will not accept claims from dealers for tr ansportation damage.
NOTE: When inspecting the unit for transportation damag e, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.
NATIONAL CODES
This product is designed and manufactur ed to permit installation in accordance with National Codes. It is the inst aller’ s r e sponsibil­ity to install the product in accordance with National Codes and/ or prevailing local codes and regulations.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calcula te d b y an appr ov e d method or in accordance with ASHRAE Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018 System design and installation should also, where applicable, fol­low information pre sented in accept ed industry guides such as the ASHRAE Handbooks. The manufacturer assumes no r esponsibility for equipment installed in viola tion of an y c ode or r egula tion. The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services; supply and return duct connections; and drain connections (if re­quired). The internal systems of the unit are completely factory­installed and tested prior to shipment.
PRE-INSTALLATION CHECKS
Carefully rea d all instructions f or the installation prior t o inst alling unit. Ensure each step or proce dur e is under stood and an y special considerations are taken into account before starting installation. Assemble all tools, hardware and supplie s needed to complet e the installation. Some items may need to be purchased locally.
UNIT LOCATION
WARNING
TO
PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
IMPORTANT NOTE: Remove wood shipping rails and metal ship­ping brace (if applicable) prior to installation of the unit on a roof curb.
ALL INSTALLATIONS: I
MPORTANT NOTE: Unit should be energized 24 hours prior to
compressor start up to ensure crankcase heater has suffi­ciently warmed the compressors. Compressor damage may occur if this step is not followed.
Units are g ener ally ins t alled on a steel roof mounting curb assem­bly which has been shipped to the job site for installation on the roof structure prior to the arrival of the unit. The model number shown on the unit’s identification plate iden tifies the various com­ponents of the unit such as refrigeration tonnage, heating input and voltage.
Carefully inspect the unit for damage. Any bolts or screws which may have loosened in tr ansit must be re-tightened. In the e vent of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, c arrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy , or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
NOTE: Appliance is shipped from factory for vertical duct application.
Proper installation of the unit ensur es tr ouble-free operation. Im­proper installation can result in problems ranging from noisy operation to property or equipment damages, dangerous condi­tions that could result in injury or personal property damage and could void the warranty. Give this booklet to the user and explain it’s provisions. The user should r etain these instructions f or futur e reference.
For proper operation and condensate drainage, the unit
must be mounted level.
T o avoid possible illness or death of the building occupants,
do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service acce ss (see Unit Clearances). These clearances must be permanently maintained.
3
Page 4
When the unit is heating, the temperature of the return
air entering the unit must be between 50°F and 100°F.
WARN ING
GROUND LEVEL INSTALLATIONS ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended . Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runoff of w at er
from higher ground can collect in the unit.
ROOF TOP INSTALLATIONS ONLY:
T o a v oid possible property damage or per sonal injury, the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structur al engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
As indicated on the unit’ s data plate, a minimum clear ance
of 36” to any combustible mat erial is required on the access side of the unit. All combustible materials must be kept out of this area.
Adequate clearances fr om the unit to any adjacent public
walkways, adjacent buildings, building openings or openable windows must be maintaine d in accordance with National Codes.
UNIT PRECAUTIONS
Do not stand or walk on the unit.
Do not drill holes anywhere in panels or in the base frame of the unit (except where indicated). Unit access panels provide structural support.
Do not remove any access panels until unit has been installed on roof curb or field supplied structure.
Do not roll unit across finished roof without prior approval of owner or architect.
Do not skid or slide on any surface as this may damage unit base. The unit must be store d on a flat, level surf ace. Protect the condenser coil because it is easily damaged.
TO
PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT
.
,
Sufficient structural support must be det ermined prior to
locating and mounting the curb and package unit.
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be a ssembled with the curb. Cantilevered type curbs are not available from the factory.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor. The curbs must be supported on parallel sides by roof members. The roof members must not penetrate supply and r eturn duct open­ing areas as damage to the unit might occur.
NOTE: The unit and curb accessories are de signed to allow v ertical duct installation placement is not recommended.
ALL
CURBS LOOK SIMILAR
POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY SUPERSEDES INFORMATION SHOWN
See the manual shipped with the roof curb for assembly and in­stallation instructions.
before unit placement. Duct installa tion after unit
CAUTION
. TO
AVOID INCORRECT CURB
. I
NSTRUCTIONS MAY VARY IN CURB STYLES AND
.
CLEARANCES
36”*
ROOF CURB INSTALLATIONS ONLY:
Curb installations must c omply with local codes and should be done in accordance with the est ablished guidelines of the National R oof­ing Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped unassembled. Field assembly, squaring, leveling and mounting on the roof structure are the responsibility of the in­stalling contractor. All required hardware necessary for the as­sembly of the sheet metal curb is included in the curb accessory.
36”*
36” MIN.
UNIT CLEARANCES
*In situations that have multiple units, a 48” minimum clearance is required between the condenser coils.
4
Page 5
Adequate clearance around the unit should be k ept f or safe ty , ser ­vice, maintenance, and proper unit operation. A t otal clearance of 75” on the main control panel side of the unit is recommende d t o facilitate possible fan shaft, coil, electric heat and gas furnace re­moval. A clearance of 48” is recommended on all other sides of the unit to facilitate possible compr essor remov al, to allow service access and to insure proper v entilation and condenser airflow . The unit must not be installed beneath any obstruction. The unit should be installed remote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.
CAUTION
IF
PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB
.
ROOF TOP DUCT CONNECTIONS
Install all duct connections on the unit before placing the unit on rooftop.
HORIZONTAL DISCHARGE
Refer t o IOD-7006 included in the litera ture pack for inst alling hori­zontal duct covers.
Flexible duct connectors between the unit and ducts are recom­mended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes.
INSULATED PANELS
Roof Curb Installation
ROOF CURB POST -INSTALLA TION CHECK S
After installation, check the top of the curb, duct connection fr ame and duct flanges to make sure gasket has been applied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct connection frame. If gasket is loose, re-apply using strong weather resistant adhesive.
5 7/8”
36 3/8”
REMOVE
COVERS
28 3/8”
13 7/8”
SUPPLY
6 1/4”
HORIZONTAL DISCHARGE DUCT CONNECTIONS
7 3/8”
12 5/8”
RETURN
RIGGING DET AILS
WARNING
O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
T
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.
T
O FACILITATE
PROTRUSION
Inspect curb to ensure that none of the utility services (electric) routed through the curb protrude above the curb.
CAUTION
DO
NOT LIFT UNITS TWO AT A TIME INCLUDED IN THE UNIT BASE FRAME PREVENT DAMAGE TO THE UNIT
. P
ROVISIONS FOR FORKS HAVE BEEN
. M
INIMUM FORK LENGTH IS
.
48” TO
Provisions for fork s have been include d in the unit base frame. No other fork locations are approved.
5
Page 6
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
• Unit must be lifted by the four lifting holes located at the base frame corners .
• Lifting c ables should be at tached to the unit with shackle s.
• The distance between the crane hook and the top of the unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base fr ame befor e setting unit on roof curb. These struts are intended to protect unit base frame from f ork lift damage. Removal is acc omplished by extracting the sheet metal retainers and pulling the struts through the base of the unit. Refer to rigging label on the unit.
• Your unit may be equipped with a steel shipping brace located underneath the unit (under compressors). If installing on a roof curb, the brace MUST be removed. Follow the following instructions for removal.
CAUTION
W
HEN UNIT IS SUSPENDED, BOARDS AND SHIPP ING BRACE WILL DROP WHEN
SCREWS ARE REMOVED
EMOVE FORK HOLE BRACKETS, BOARDS AND SHIPP ING BRACE FROM BOTTOM
R
OF UNIT BEFORE PLACING UNIT ONTO CURB
Before installing this unit on a roof curb:
1. Remove wooden strut s per installation instructions. These are the struts that are located in the fork holes and are used to protect the unit from damage while lifting with forks.
2. Locate and remove the twelve (12) scr ews tha t at tach the shipping brace to the side r ails. There will be six (6) screws on each side of the unit and they are in a diagonal pat tern.
See following figure.
. TO
PREVENT PERSONAL INJURY
, STAND CLEAR.
.
3. Lift unit per the “Rigging Details” section of the installation instructions, observing all warnings and cautions. Lift the unit high enough off the ground to reach under and gr asp the shipping brace.
4. Rotate the brace by tapping the ends until the brace falls free from the unit.
5. Dispose of the brace appropriately.
Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to ins talling the unit. Ductwork dimensions are shown in Roof Curb Installation Instructions.
Refer to the R oof Curb Installation Instructions for proper curb in­stallation. Curbing must be installed in compliance with the Na­tional Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end t o be lower than supply air end.
6
Page 7
To assist in determining rigging requirements, unit weights are
A
C
shown as follows:
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper align­ment and orientation of supply and return openings with duct.
Y
EVAP ORATOR COIL
COMPRESSOR 1
CG
COMPRESSOR 2
RETURN
SUPPLY
RIGGING REMOVAL
CAUTION
TO
PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT
Remove sprea der bars, lifting cable s and other rigging equipment.
BD
X
CORNER & CENTER OF GRAVITY LOCATIONS
ELECTRICAL WIRING
WARN ING
.
DCC Weights (lb s)
DATA
090 102 120 150
Corner Weight - A 313 310 310 420 Corner Weight - B 248 263 263 335 Corner Weight - C 250 258 258 290 Corner Weight - D 199 219 219 230 Unit Shipping Weight 1085 1125 1125 1300 Unit Operating Weight 1010 1050 1050 1275 X (I nche s) 4 4 45 45 41 Y (Inches) 27 28 28 27.5
DCH Weights (lbs)
DATA
090 102/120 150
Corn er W eight - A 28 5 345 4 35 Corn er W eight - B 285 325 3 45 Corn er W eight - C 285 320 3 00 Corn er W eight - D 285 300 2 40 Unit Ship ping W e ig ht 1175 1 3 10 1 3 50 Unit Operating Weight 1135 1285 1325 X (I nc hes) 4 8 48 41 Y (Inches) 30 30 27.5
NOTE: These weights are without accessories installed.
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICI NG OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARN ING
HIGH VOLTAGE! T
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY WIRING
. THE
OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT
ONTACT YOUR LOCAL REPRESENTATIVE IF
C
ASSISTANCE IS REQUIRED
INTERNAL POWER AND CONTROL WIRING
.
.
CAUTION
TO
PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES LOCAL CODES AND ORDINANCES REMOVABLE ACCESS PANELS
. F
OLLOW NATIONAL ELECTRICAL CODE AND ALL
. DO
NOT ROUTE WIRES THROUGH
.
CAUTION
C
ONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT
WATER ENTRY INTO THE BUILDING
.
For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maxi­mum overcurrent protection device. DO NOT EXCEED THE MAXI­MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
CAUTION
TO
PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
.
All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.
7
Page 8
The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these in­structions, the latest e dition of the National Electrical Code (ANSI/ NFP A 7 0), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/ 35°C rise).
The main power supply shall be three-phase, three wir e. The unit is factory wired for the voltage shown on the unit’s data plate.
POWER WIRING
NOTE: If supply voltage is 208V , all le ads on primary of transf ormer TRANS1 must be moved from the 230V to the 208V tap.
Main power wiring should be sized f or the minimum wire ampacity shown on the unit’s data plate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase the wire size to prevent e xcessiv e volt age drop. Wires should be sized f or a maximum of 3% voltage drop.
CAUTION
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
T
ONLY COPPER CONDUCTORS.
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS DANGEROUS OPERATION SERVICING
. W
IRING ERRORS CAN CAUSE IMPROPER AND
.
. V
ERIFY PROPER OPERATION AFTER
NOTE: A weather-tight disconnect switch, properly sized for the unit total load, must be field or f actory inst alled. An e xt ernal field supplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not cov ered by the field-supplied disc onnect switch.
• Some disconnect switches are not fused. Pr otect the power leads at the point of distribution in accordance with the unit’s data plate.
• The unit must be electrically grounded in accor dance with local codes or, in the absence of local codes, with the lates t edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding conductor in accordance with T able 250-95 of the National Electrical Code. Do not use the ground lug for c onnecting a neutral conductor.
• Connect power wiring to the Single Point Power block. This terminal block is located within the main control box.
COM NO NC
THERMOSTAT WIRING
POWER AND LOW VOLTAGE BLOCK LOCATIONS
WARN ING
F
AILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS
.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable lights and tools used by the service mechanic.
NOTE: Refer to local codes for requirements. These outlets can also be factory installed.
UNITS INSTALLED ON ROOF TOPS
Main power and low voltage wiring may enter the unit through the side or through the roof curb. Install conduit connect ors at the desired entr ance locations. External connector s must be weather ­proof. All holes in the unit base must be sealed (including those around conduit nuts) to prevent water leakage into building. All required conduit and fittings are to be field supplied.
Supply voltage to roof top unit mus t not vary by more than 10% of the value indicated on the unit’s data plate. Phase voltage unbal­ance must not exceed 2%. Contact your local power comp any for correction of improper voltage or phase unbalance.
8
Page 9
DIMPLES MA RK DRILL LOCATIONS
HIGH VOLTAGE EN TRANCE
10 3/16”
LOW VOLTAGE ENTRANC E
26 ½”
ELECTRICAL ENTRANCE LOCATIONS
Unit is equipped with Single Point Power Block and Low Voltage Block.
LOW VOLTAGE CONTROL WIRING
1. A 24V thermostat must be installed for unit operation. It may be purchased with the unit or field -supplied. Thermostats may be programmable or electromechanic al as required.
2. Locate thermostat or remote sensor in the conditioned space where it will sense average temperature. Do not locate the device where it may be directly exposed to supply air, sunlight or other sources of heat. Follow installation instructions packaged with the thermostat.
3. Use #18 AWG wire for 24V control wiring runs not exceeding 75 feet. U se #16 A WG wire for 24V con trol wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 where permitted by local codes.
4. Route thermostat wires from sub-base terminals to the unit. Control wiring should enter through the duct panel (dimple marks entrance location). Connect thermostat and any accessory wiring to low voltage terminal block TB1 in the main control box.
CIRCULATING AIR AND FILTERS
DUCTWORK
The supply duct from the unit through a wall may be ins talled with­out clearance. However, minimum unit clearances must be main­tained (see “Clearance s” section). The supply duct should be pro­vided with an access panel large enough to inspect the air cham­ber downstream of the heat exchanger. A cover should be tightly attached to pr event air leaks.
Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
CONDENSA TE DRAIN CONNE CTION
CONDENSATE DRAIN CONNECTION
A 3/4” female NPT drain connection is supplied on the end of the unit and bottom of the drain pan f or condensat e piping. An e xter ­nal trap must be installed for proper condensate drainage.
DRAIN CONNECTION
UNIT 2" MINIMUM
FLEXIBLE TUBING-HOSE OR PIPE
A POSITIVE LIQUID SEAL IS REQUIRED
Drain Connection
3" MIN IMUM
Install condensate drain trap as shown. Use 3/4” drain line and fittings or larger. Do not operate without trap.
HORIZONTAL DRAIN
Drainage of condensate directly on to the r oof ma y be accept able; refer to local code. It is recommended that a small drip pad of ei­ther stone, mortar , w ood or metal be provide d to prevent an y pos­sible damage to the roof.
NOTE: Field-supplied conduit may nee d t o be installed depending on unit/curb configuration. Use #18 AWG solid conductor wire whenever connecting thermostat wire s to terminals on sub-ba se. DO NOT use larger than #18 AWG wire. A transition to #18 AWG wire may be requir e d be fore entering thermostat sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
CLEANING
Due to the fact that drain pans in any air conditioning unit will have some moisture in them, algae and fungus will grow due to airborne bacteria and spores. Periodic clean­ing is necessary to prevent this build-up from plugging the drain.
9
Page 10
ST ARTUP, ADJUSTMENTS, AND CHECK S
WARN ING
the warranty. After the machines are used for temporary heating or cooling, inspect the coils, fans, and motors for unacceptable levels of construction dust and dirt and install new filters.
HIGH VOLTAGE!
O AVOID PERSONAL INJURY OR DEATH DUE TO
T
ELECTRICAL SHOCK, B THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL PROVIDED OR OTHER ACCEPTABLE MEANS SERVICING OR INSTALLING THIS UNIT
OND THE FRAME OF THIS UNIT TO
. D
ISCONNECT ALL POWER BEFORE
.
PRE-STARTUP INSTRUCTIONS - GENERAL
CAUTION
TO
PREVENT PROPERTY DAMAGE OR PERSONAL INJURY START THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TESTS HAVE BEEN PERFORMED
.
, DO
NOT
Prior to the beginning of Startup, Adjustments, and Checks pr oce­dures, the following steps should be completed in the building.
Prior to the beginning of Starup, Adjustments, and checks proceudres, the following steps should be completed in the building.
WARNING
MOVING MACHINERY HA ZARD !
\
T
O PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT POWER TO THE UNIT AND PADLOCK IN THE SERVICNG FANS
.
“OFF”
POSITION BEFORE
HEATING STARTUP
On new installations, or if a major component has been replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower motors. Duct covers must be removed before
operating unit.
CONTRACTOR RESPONSIBILITY
The installing contractor must be certain that:
All supply and return air ductwork is in place, properly sealed, and corresponds with installation instructions.
All thermostats are mounted and wired in accordance with installation instructions.
All electric power, all gas, hot water or steam line connections, and the condensate drain ins tallation ha ve been made to each unit on the job. These main supply lines must be functional and capable of operating all unit s simultaneously.
Air filters are in place.
ROOF CURB INSTALLATION CHECK
Inspect the roof curb for correct installation. The unit and curb assembly should be level. Inspect the flashing of the roof mount­ing curb to the roof, especially at the corners, for good workman­ship. Also check for leaks around g a s kets. Note any deficiencies in a separate report and forward to the contractor.
OBSTRUCTIONS, FAN CLEARANCE AND WIRING
Remove any extraneous construction and shipping materials that may be found during this procedure. Rotate all fans manually to check for proper clearances and that they rotate freely. Check for bolts and screws that may have jarred loose during shipment to the job site. Retighten if necessar y. Re-tighten all electrical con­nections.
FIELD DUCT CONNECTIONS
Verify that all duct connections are tight and that there is no air bypass between supply and return.
FILTER SECTION CHECK
Remove filter section access panels and check that filter s are prop­erly installed. Note airflow arrows on filter frames.
The Startup, Adjustments, and Checks procedure provides a s tep­by-step sequence which, if follow ed, will assure the proper st artup of the equipment in the minimum amount of time. Air balancing of duct system is not considered part of this procedure. However, it is an important phase of any air conditioning s yst em startup and should be performed upon completion of the Startup, Adjustments , and Checks procedure. The St artup, Adjustment s, and Checks pro­cedure at outside ambients below 55°F should be limit ed to a readi­ness check of the refrigera tion system with the requir ed final check and calibration left to be completed when the outside ambient rises above 55°F.
TEMPORARY HEATING OR COOLING
If the unit is to be used for tempor ary heating or cooling, a “Startup, Adjustments, and Checks” must first be performed in accordance with this manual. Failure to comply with this requir ement will void
PRE-STARTUP PRECAUTIONS
It is important to your safety that the unit has been properly grounded during installation. Check gr ound lug connection in main control box for tightness prior to closing circuit break er or discon­nect switch. Verify that supply voltage on line side of disconnect agrees with voltage on unit identification plate and is within the utilization voltage rang e as indicate d in Appendix B Electrical Data.
System Voltage - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage cla ss.
Nameplate Voltage - That voltage assigned to a piece of equip­ment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
10
Page 11
Utilization Voltage - The voltag e of the line terminals of the equip­ment at which the equipment must give fully satisfactory perfor­mance. Once it is establishe d that supply voltag e will be maintained within the utilization range under all sy stem conditions, check and calculate if an unbalanced condition exist s between phases. Calcu­late percent voltage unbalance as follows:
Three Phase Models Only
2) MAXIMUM VOLTAGE DEVIATIONS
3) PERCENT VOLTAGE UNBALANCE
HOW TO USE THE FORMULA: EXAMPLE: With voltage of 220, 216, and 213
1) Average Voltage = 220+216+213=649 / 3 = 216
2) Maximum Voltage Deviation s fro m Average Voltage = 220 - 216 = 4
3) Percent Voltage Unbalance = 100 x = = 1.8%
Percent voltage unbalance MUST NOT exceed 2%
= 100 X
FROM AVERAGE VOLT AG E
1) AVERAGE VOLTAGE
4
216
400 216
.
CONTROL VOLTAGE CHECK
With disconnect switch in the open “OFF” position, disconnect blue wire from low voltage transformer TRANS1. Close the disconnect switch to energize TRANS1 con trol transf ormer . Check primary and secondary (24V) of control tr ansformer TRANS1.
AIR FLOW ADJUSTMENTS
EVAPORATOR FAN ROTATION CHECK (THREE PHASE MODELS ONLY)
Check that fan rotates counter-clockwise when viewed from the drive side of unit and in accordance with r ot ation arro w shown on blower housing. If it does not, reverse the two incoming power cables. In this case, repeat bearing check.
Do not attempt to change load side wiring. In ternal wiring assur e s all motors and compressors will rotate in correct direction once evaporator fan motor rotation check has been made.
ELECTRICAL INPUT CHECK
Make preliminary check of evapor ator f an ampere dra w and verify that motor nameplate amps are not exceeded. A final check of amp draw should be made upon completion of air balancing of the duct system (see Appendix B).
SET EVAPORATOR FAN RPM
Actual RPM’s mus t be set and verified with a tachomet er or strobe light. Refer to Appendices A and B for basic unit fan RPM. Refer also to “Airflow ” section of this manual. W ith disconnect switch open, disconnect thermostat wires from terminals Y and W. This will prevent heating and mechanical c ooling from coming on. Place a jumper wire across terminals R and G at TB1 terminal block. Close disconnect switch; evaporator fan motor will operate so RPM can be checked.
NOTE: For 2 Spee d Models, airflow a djustmen ts mus t be made on high speed, i.e., 2nd stage cooling or in heat mode.
The drive on the supply fan is typically set in the middle of the RPM range. The drive motor she a v e pitch diameter is field adjust­able for the required airflow. Refer to the following “Drive Adjustments” section.
When the final adjustments are comple te, the curren t draw of the motor should be checked and compared to the full load current rating of the motor. The amperage must not exceed the service factor stamped on the motor nameplate. The total airflow must not be less than that required f or oper ation of the electric heat ers or the furnace.
If an economizer is installe d, check the unit operating balance with the economizer at full outside air and at minimum outside air. Upon completion of the air flow balancing, we recommend replacing the variable pitched motor shea ve with a properly-sized fixed sheave. A matching fixed sheave wi ll provide longer belt and bearing life and vibration free operation. Initially, it is best to have a variable pitched motor sheave for the purpose of airflow balancing, but once the balance has been achieved, fixe d sheav es maintain align­ment and minimize vibration more ef fectively . For dir ect drive units, move green wire f or fan.
START-UP PROCEDURE AND CHECKLIST FOR 2 SPEED MODELS:
Models with a V in the 11th position of the model number. For 2 speed models, the indoor blower will operate on low speed
when in “Fan Only” mode or while in first stage “Cooling” mode. Unit will operate on high speed in “Heating” mode and while in second stage “Cooling” mode.
The start-up procedure is the same as for “Air Conditioning Start­up Procedure” with the understanding that in Step 6, the indoor blower will run at low speed (~1175 motor rpm) and in Step 7, the indoor blower will operate at high speed (~1775 motor rpm).
NOTE: While in the Cooling Mode, to prevent frost from forming on the evaporator while the unit is operating in outdoor temperatures of 65°F or lower, it is recommended that a low ambient kit (LAKT-**) is used. This is strongly recommended for 2 Speed models due to the lower airflow while in the first stage cooling. To further protect the compressor from damage during low ambient conditions, a Freez estat Kit (F SK01) can be adde d that turns the compressor off when the evapor at or temper ature dr ops too low.
BELT DRIVE MODELS ONLY
NOTE: On “non-two speed models” (two-speed models ha ve a “V” in the eleventh character of the model number), never run CFM below 300 CFM per ton. Evaporator freezing or poor unit perfor­mance is possible.
The drive on the supply fan is typically set in the middle of the RPM range. The drive motor she a v e pitch diameter is field adjust ­able for the required airflo w . Ref er to “Motor She ave Adjustmens” section.
11
Page 12
Upon completion of the air flow balancing, we rec ommend replac­ing the variable pitched motor sheave with a properly-sized fixed sheave. A matching fix ed shea ve will provide longer belt and bear ­ing life and vibration free operation. Initially, it is best to have a variable pitched motor sheave for the purpose of airflow balanc­ing, but once the balance has been achieved, fixed sheaves main­tain alignment and minimize vibra tion mor e e f fectively. For direct drive units, move fan speed wire.
BEARING CHECK
Prior to energizing any f ans, check and make sure tha t all setscrews are tight so that bearings are properly secured to shafts.
For heat pump units, the airflow must be adjusted so that the air temperature rise f alls within the r anges giv en s tate d on Dat a Plate (see Appendix A - Blower Performance).
TENSION AND ALIGNMENT ADJUSTMENT
Correct belt tension is very important to the life of your belt. Too loose a belt will shorten its life; too tight, premature motor and bearing failure will occur. Check you belt drive for adequate “run­in” belt tension by measuring the force r equired to deflect the belt at the midpoint of the span length. Belt tension f or ce can be mea­sured using a belt tension gauge, av ailable through most belt drive manufacturers.
S
P
A
N
L
E
N
G
T
H
*
D
E
F
L
F
O
D
C
t
E
C
T
I
O
N
R
C
E
h
H
d
TYPE
MODEL
BELT DRIVE Used New
7.5 Ton 2.6 to 3.6 3.75 +/- 0. 5 4.0 +/- 0.5 9/3 2 +/- 1/16
8.5 Ton 2.6 to 3.6 3.75 +/- 0. 5 4.0 +/- 0.5 9/3 2 +/- 1/16 10 Ton 3.0 to 4.0 3.75 +/- 0. 5 4.0 +/- 0.5 9/3 2 +/- 1/16
1 2.5 T on 2.6 to 3.6 3.75 +/- 0. 5 4.0 +/- 0.5 9/3 2 +/- 1/16
A, AX Standard
SHEAVE
DIAMETE
R (in )
DEFLECTION
FORCE (lbs)
DEFLEC TION
(in )
RECOMMENDED POUNDS OF FORCE PER BELT
When new V-belts are installed on a drive, the initial tension will drop rapidly during the first fe w hours of use. Check tension fre­quently during the first 24 hours of operation. Subsequent retentioning should fall between the minimum and ma ximum force. To determine the deflection distance from a normal position, use a straightedge or stretch a cord from sheave to sheave to use as a reference line. On multiple belt drives, an adjacent undeflected belt can be used as a ref er ence.
MOTOR SHEA VE ADJUSTMENTS
VL, VM & 2VP VARIABLE PITCH KEY TYPE MOTOR SHEAVES
The driving and driven motor sheave s should be in alignment with each other and the shafts parallel.
VL & VM SHEAVES ADJUSTMENT
1. Loosen set screw “B” using a 5/32" Allen key.
2. Making half or full turns from closed position, adjust sheave pitch diameter for desired speed. DO NOT OPEN MORE THAN FIVE FULL TURNS.
3. Tighten set screw “B” securely over flat.
4. Carefully put on belts and adjust belt tension. DO NOT FORCE BELTS OVER GROOVES.
5. Ensure all keys are in place and the se t screws tigh t befor e starting drive. Recheck set screws and belt tension after 24 hours service.
*Apply force to the center of the span.
t = Span length, inches C = Center distance, inches D = Larger sheave diameter, inches
d = Smaller sheave diameter, inches h = Deflection height, inches
DRIVE BELT TENSION ADJUSTMENT
NOTE: Future adjustments should be made by loosening the belt
tension and increasing or decreasing the pitch diameter of the sheave by half or full turns as r equired. R eadjust belt tension be fore starting drive.
12
Page 13
9. Turn the thermosta t system switch to “ OFF” and disconnect all power when servicing the unit.
WARN ING
C
B
VL & VM
NOTE: Do not operate shea ve with flange projecting be yond the hub end.
REFRIGERATION SYSTEM CHECKS
Ensure the hold-down bolts on the compressor are secure and ha ve not vibrated loose during shipment. Check that vibration grom­mets have been installe d. Visually check all piping and clamps. The entire refrigeration system has been factory charged and tested, making it unnecessary to field charge. Factory charges are shown on the unit nameplate.
AIR CONDITIONING START-UP PROCEDURE
Begin with power turned off at all disconnects.
1. Turn thermostat system switch to “Cool,” and fan switch to “Auto” and turn temperature setting as high as it will go.
2. Inspect all registers and set them to the normal open position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan swit ch to the “ON” position. The blower should operate after a 7-second dela y.
5. Turn the f an s witch t o “Auto” position. The blower should stop after a 65 second delay.
6. Slowly lower the cooling temperatur e until first st age COOL (LOW COOL) starts. The blower, both fans, and first stage compressor should now be operating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.
7. Lower the cooling temperatur e further until second stag e COOL (HIGH COOL) starts. The blower, both fans, and both compressors should now be operating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.
8. Turn the temperature setting to the highest position, stopping the unit. The indoor blower will continue to run for 65 seconds.
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICI NG OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
HEAT PUMP START-UP PROCEDURE
10. Check the cooling mode for the heat pump in the same manner as above. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contractor is energized. The compressor, blower and fan should then be running. After the cooling mode is checked out, turn the thermostat system switch to “OFF”.
11. Turn the thermostat system switch to “HEAT” and fan switch to “AUTO”.
12. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor, blower and fan should now be running with the reversing valv e in the de­energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.
13. If the outdoor ambient is abov e 80°F, the unit may trip on its high pressure cut out when on hea ting. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable but-DO NOT FAIL TO TEST.
If the outdoor ambient is low and the unit operates properly on the heating cycle, you ma y check the pressure cutout operation by blocking off the indoor return air un til the unit trips.
14. If unit operates properly in the heating cycle, raise the temperature set ting until the heating sec ond stage mak e s contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly.
NOTE: If outdoor thermostats are installed the outdoor ambient must be below the set point of the se thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.
15. For thermostats with emer gency heat switch, return to s tep
11. The emergency heat switch is loc ated a t the bottom of the thermostat. Move the swit ch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emer g ency heat light will come on.
16. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost c ontr ol, observe at least one defrost cycle to make sure the unit defrosts completely.
13
Page 14
FINAL SYSTEM CHECKS
1. Check to see if all supply and re turn air grilles are adjus ted and the air distribution system is balanced for the best compromise between heating and cooling.
2. Check for air leaks in the ductwork. See Sections on
Air Flow Adjustments.
3. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing ag ainst e ach other or sheet metal surfaces or edg es. If so, correct the trouble.
4. Set the thermostat at the appropriate setting for cooling and heating or automatic change over for normal use.
5. Be sure the Owner is instructed on the unit oper ation, filter , servicing, correct thermostat operation, e t c.
REFRIGERATION PERFORMANCE CHECK
Check that compressor RLA corresponds to values shown in Ap­pendix B. RLA draw can be much lower than values listed at low load conditions and low ambient condensing temperatures. Val­ues in Appendix B can slightly exceed at high load conditions and high ambient condensing temperatures.
HEAT PUMP OPERATION
COOLING CYCLE
When the heat pump is in the cooling cycle, it operates exactly as a Summer Air Conditioner unit. In this mode, all the charts and data for service that apply to summer air conditioning apply t o the heat pump. Most apply on the heating cycle except that “con­denser” becomes “evaporator”, “evaporator” becomes “con­denser”, “cooling” becomes “heating”.
HEATING CYCLE
The heat pump operat es in the he a ting cycle by redirecting refrig­erant flow through the r efriger ant circuit e xternal to the compre s­sor . This is accomplishe d with through the re versing valv e. Hot dis­charge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes thr ough the expansion device to the outdoor coil (condenser on the cooling cycle) wher e the liquid is evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pre ssure) reverse positions in the reversing valve.
The following figures show a schematic of a he at pump on the cool­ing cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system.
The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the re­verse of refriger an t flo w.
When the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperatur e of the outdoor air in order to extract heat from the air. Thus, the greater the dif­ference in the outdoor temper ature and the outdoor coil tempera­ture, the greater the he ating cap acity of the heat pump. This phe­nomenon is a characteristic of a heat pump. It is a good pr actice to provide supplementary heat for all heat pump installations in ar­eas where the temperature drops below 45° F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the r efrigeran t in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the out­door coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the out­door coil and lessen the time required for defrosting. The indoor blower continues to run and the supplemen t ary heaters are ener­gized.
14
Page 15
DEFROST CONTROL
NOTE: DCH models have one stage of mechanical heating. The de­frost accumulation period will start when either first or second stage defrost thermostat closes. Defrost termination occurs when both thermostats open or the 10 minute cycle has completed.
During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30,60 and 90 minutes may be selected by connecting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 31° F), and when the wall thermostat calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sen­sor remains closed. When the sensor opens (appro ximately 75° F), the defrost cycle is t erminated and the timing period is rese t. If the defrost cycle is not terminated due to the sensor temperature, a ten minute override interrupts the unit’s defrost period.
FILTERS
CAUTION
T
O PREVENT PRO PERTY DAMAG E DUE TO FIRE AND LOSS O F EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Every application may r equire a differ ent frequency of replacement of dirty filters. Filters must be replaced at least every three (3) months during operating seasons.
Dirty filters are the most common cause of inadequat e he a ting or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local condi­tions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean filter.
MAINTENANCE
WARN ING
HIGH VOLTAGE!
ISCONNECT ALL POWER BEFORE SERVICI NG OR
D
INSTALLING THIS UNIT BE PRESENT DAMAGE, PERSONAL INJURY OR DEATH
. F
. M
AILURE TO DO SO MAY CAUSE PROPERTY
ULTIPLE POWER SOURCES MAY
.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER
. FOR
.
ADDITIONAL
,
CAUTION
S
HEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION
.
The Self Contained Packaged Air Conditioner and He at Pump should operate for man y year s without exce ssive service calls if the unit is installed properly . Howev er it is recommended that the homeowner inspect the unit before a seasonal start up. The coils should be free of debris so adequate airflow is achiev ed. The re turn and sup­ply registers should be free of any ob s tructions. The filter s should be cleaned or replaced. The se few steps will help to keep the pr od­uct up time to a maximum. The Service section that follow s should help in identifying problems if the unit does not operat e properly.
Disposable return air filters are supplied with this unit. See the unit Specification Sheet or Technical Manual for the correct size and part number. To remove the filte rs, remove the filter access panel on return side of the unit.
CABINET FINISH MAINTENANCE
Use a fine gra de automotiv e wax on the c abinet finish t o maintain the finish’s original high luster. This is especially important in in­stallations with extended periods of direct sunlight.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently a s necessary to keep the finne d areas free of lint, hair and debris.
LUBRICATION
The fan shaft bearings , the 1 to 2 HP supply fan motors, the con­denser fan motors and compressors are permanently lubricated.
FUNCTIONAL PARTS
Refer to the unit Parts Catalog for a list of functional parts. Parts are available from your distributor.
TROUBLESHOOTING
THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SER VICE AGENCY ONLY: OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT.
Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle.
INADEQUATE AIR VOLUME THROUGH INDOOR COIL
When a heat pump is in the heating cycle, the indoor coil is func­tioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass thr ough the indoor coil to pre­vent exce ssive discharge pressur e, and high pressure cut out.
15
Page 16
OUTSIDE AIR INTO RETURN DUCT
Do not introduce cold outside air into the return duct of a heat pump installation. For units with 2-speed motor s, do not allow air entering the indoor coil to drop below 65° F. Air below this tem­perature will cause low discharge pr e ssur e, thus low suction pre s­sure, and excessive de frost cy cling resulting in lo w heating output. It may also cause false defrosting.
UNDERCHARGE
An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost ac­cumulation on the outdoor coil.
POOR “TERMINATING” SENSOR CONTACT
The unit’s defrost terminating sensor must mak e good thermal con­tact with the outdoor coil tubing. Poor contact may not termina te the unit’s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure.
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO:
1. Solenoid not energized - In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdrive r. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.
2. No voltage at unit’s solenoid - Check unit voltage. If no voltage, check wiring circuit.
3. Valve will not shift:
a. Undercharged - check for leaks; b. Valve Body Damaged - Replace valve; c. Unit Pr operly Charge d - If it is on the he ating cycle, raise
the discharge pressur e by re stricting airflow thr ough the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. DO NOT TAP THE VALVE BODY. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off and wait until the discharge and suction pressure equalize, and repea t above st eps. If the valve does not shift, replace it.
16
Page 17
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD DOWN SHO T
DCC/DCH090 STANDARD BELT DRIVE DOWN SHOT
ESP, In
O
H
2
0.1
0.3
0.5 3447 798 1.23 3049 754 0.94 2606 710 0.71
0.7 3400 848 1.33 2950 798 1.01 2474 754 0.75
0.9 3303 890 1.41 2871 848 1.11 2408 804 0.82
1.1 2838 897 1.23
012345
CFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHP CFMRPMBHP
DCC/DCH102 STANDARD BELT DRIVE DOWN SHOT
ESP, In
H
O
2
0.1
0.3
0.5 3237 841 1.29 2684 803 0.96 2453 754 0.77
0.7 3303 890 1.47 2753 847 1.09
0.9 2807 896 1.26
012345
CFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHP CFMRPMBHP
INCLUDES 2 SPEED MODELS AT HIGH SPEED
TURNS OPEN
3617 704 1.07 3293 653 0.84
3541 749 1.15 3179 704 0.88 2757 656 0.66
INCLUDES 2 SPEED MODELS AT HIGH SPEED
TURNS OPEN
3372 747 1.11 3078 703 0.91 2814 658 0.70
3187 797 1.16 2952 753 0.97 2650 703 0.73
DCC/DCH120 STANDARD BELT DRIVE DOWN SHOT INCLU DES 2 SPEED MODELS AT HIGH SPEED
ESP, In
O
H
2
0.2
0.4
0.6 4442 880 2.02 4066 830 1.63 3717 786 1.31
0.8 4001 885 1.77 3622 835 1.41
1.0 3603 890 1.55
1.2
012345
CFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHPCFMRPMBHP CFMRPMBHP
4632 781 1.76 4203 742 1.41 3927 691 1.17 3510 658 0.9
4488 825 1.85 4183 783 1.54 3733 748 1.23 3512 693 1
TURNS OPEN
DCC/DCH150 STANDARD BELT DRIVE DOWN SH OT INCLUDES 2 SPEED MODELS AT HIGH SPEED
5 TURN S1 TURN 2 T U R N S0 TURNS 3 TURNS 4 TURN S
ESP
(IN W . C.) CFM B HP CFM BHP CF M BHP CFM BHP CFM BHP CFM BHP
0.2 5378 2.35 4967 1.92 4710 1.59 4512 1.33
0.4 5514 2.92 5349 2.56 4750 1.97 4583 1.71 4319 1.40 4030 1.13
0.6 5204 2.69 4919 2.27 4488 1.81 4258 1.54
0.8 4830 2.42 4649 2.09 4019 1.55
1.0 4497 2.19 4264 1.86
NOTE: Unit fact o ry shipped at 2.5 turns open. Tables represent dry coil without filter .
To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.
17
Page 18
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD HORIZONTAL
NOTE: For 2 Speed Models, blow er perf ormance da t a reflects High spee d perf ormance.
DCC/DCH090 STANDARD BELT DRIVE HORIZONTAL
ESP, In
O
H
2
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5 3780 841 1.52 3405 803 1.23 3053 753 0.94 2608 709 0.68 2225 665 0.53
0.7 3687 885 1.6 3327 847 1.29 2968 805 1.02 2423 758 0.73
0.9 3236 891 1.39 2850 852 1.1 2352 807 0.8
1.1 2713 896 1.17
DCC/DCH102 STANDARD BELT DRIVE HORIZONTAL
ESP, In
H
O
2
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5 3630 838 1.49 3255 800 1.2 2903 750 0.91 2458 706 0.65
0.7 3537 882 1.57 3177 844 1.26 2818 802 0.99
0.9 3086 888 1.36 2700 849 1.07
1.1 2563 893 1.14
012345
INCLUDES 2 SPEED MODELS AT HIGH SPEED
TURNS OPEN
450123
3625 701 1.08 3309 660 0.86
3815 797 1.44 3468 747 1.11 3177 703 0.88 2796 663 0.68
INCLUDES 2 SPEED MOD ELS AT HIGH SPEED
TURNS OPEN
3475 698 1.05 3159 657 0.83
3665 794 1.41 3318 744 1.08 3027 700 0.85 2646 660 0.65
DCC/DCH120 STANDARD BELT DRIVE HORIZONTAL INCLUDES 2 SPEED MODELS AT HIGH SPEED
ESP, In
H
O
2
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.2
0.4
0.6 4467 824 1.81 4221 784 1.55 3689 741 1.18
0.8 4564 873 2.06 4170 830 1.68 3677 785 1.29
1.0 4129 875 1.81 3498 835 1.34
1.2 3558 879 1.49
012345
4497 780 1.7 4200 736 1.41 3735 691 1.06 3322 648 0.83
TURNS OPEN
4562 736 1.58 4253 691 1.29 3893 642 1
DCC/DCH150 STANDARD BELT DRIVE HORIZONTAL INCLUDES 2 SPEED MODELS AT HIGH SPEED
0 TURNS 1 TURN 2 TURNS 3 TURNS 4 TURNS 5 TURNS
ESP
(IN W.C.) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 5570 2.27 4935 1.70 4584 1.36
0.4 58713.2056392.7753072.3149021.8846371.5541781.19
0.6 56103.0053582.5750512.1546031.7243411.41
0.8 5391 2.83 5010 2.33 4 799 2.00 43 93 1.61
1.0 5078 2.59 4676 2.11 4 448 1.79
1.2 4521 2.20 4226 1.83
NOTE: Unit fact o ry shipped at 2.5 turns open. Tables represent dry coil without filter.
To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.
18
Page 19
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC DOWN SHO T
DCC/H0 90 DO WN SHO T HIG H S TATI C BEL T DRIVE
ESP, In
H
O
2
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
DCC/H1 02 DO WN SHO T HIG H S TATI C BEL T DRIVE
ESP, In
O
H
2
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
3256 1156 2.31 2939 1126 2.01
2.1
01
DO NOT
OPERATE
3381 1119 2.22 2890 1080 1.78 3089 1129 2.04
012345
3231 1116 2.19 2740 1077 1.75
3722 1063 2.25 3041 1023 1.67 2503 976 1.31 3359 1075 2.04 2540 1031 1.5
3572 1060 2.22 2891 1020 1.64 3209 1072 2.01
TURNS OPEN
4523
3401 909 1.51
3428 965 1.71 2943 915 1.3
3471 1015 1.9 3012 971 1.5 2423 920 1.12
TURNS OPEN
3251 906 1.48
3278 962 1.68 2793 912 1.27
3321 1012 1.87 2862 968 1.47
DCC/H1 20 DO WN SHO T HIG H S TATI C BEL T DRIVE INCLUDES 2 SPEED MO DELS AT HI G H SPEED
ESP, In
O
H
2
0.8
1.0
1.2
1.4
1.6
1.8
2.0
012345
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
4513 1054 2.75 4127 1003 2.26 3568 950 1.71
4126 1064 2.52 3597 1008 1.92 4438 1116 2.97 3759 1069 2.25 3956 1124 2.55
4050 1179 3.05 3473 1132 2.32
TURNS OPEN
4435 940 2.22 4078 886 1.82
4462 997 2.47 4103 945 2.05 3539 892 1.52
DCC/H1 50 DO WN SHO T HIGH STAT IC BELT DRIVE I NCL U DES 2 SPEED MO DEL S AT HIGH SP EED
ESP, In
H
O
2
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
012345
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
5947 4.16 5656 3.58 5376 3.12 4933 2.52
5708 3.93 5459 3.40 4950 2.79 4441 2.18 5776 4.64 5510 4.07 5245 3.48 4844 2.88 4525 2.45 5465 4.30 5199 3.74 4894 3.17 4404 2.54 5145 3.97 4871 3.41 4495 2.83 4805 3.63 4565 3.13 4142 2.55 4429 3.27 4233 2.85
TURNS OPEN
5978 3.87 5691 3.38 5324 2.81
NOTE: Unit facto ry shippe d at 2.5 turns open. Tables represent dry coil without filter.
To compensate for filter , add 0.08" t o measured E.S.P. SCFM correction for we t coil = 4%.
19
Page 20
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC HORIZONTAL
DCC/H0 90 HO RIZONTAL HIGH S T AT IC BELT DR IVE
ESP, In
O
H
2
0.9
1.1
1.3
1.5
1.7
1.9
2.1
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
012345
DO NOT
OPERATE
3388 1103 2.18 3036 1069 1.84 2959 1114 2 2527 1124 1.86
3514 1057 2.07 2949 1019 1.62
DCC/H1 02 HO RIZONTAL HIGH S T AT IC BELT DR IVE
ESP, In
O
H
2
0.9
1.1
1.3
1.5
1.7
1.9
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3188 1146 2.23 2809 1111 1.97
012345
3364 1054 2.04 2799 1016 1.59
3238 1100 2.15 2886 1066 1.81
TURNS OPEN
TURNS OPEN
3447 902 1.54
3398 956 1.65 3006 908 1.31
3486 1008 1.87 2960 962 1.44
3297 899 1.51 2856 905 1.28
3336 1005 1.84 2810 959 1.41
DCC/H1 20 HO RIZONTAL HIGH S T AT IC BELT DR IVE I NCL UDES 2 SPEED MO DELS AT HIGH S PEED
ESP, In
O
H
2
0.8 1
1.2
1.4
1.6
1.8 2
012345
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
DO NOT
OPERATE
4760 1105 3.23 4071 1061 2.43 3342 1012 1.86 4364 1114 2.91 3579 1067 2.05
4587 1056 2.82 3971 1006 2.17
TURNS OPEN
4602 884 2.13 4749 940 2.44 4180 885 1.89 4251 945 2.12 3642 896 1.58
4443 1001 2.5 3744 951 1.8
DCC/H1 50 HO RI ZONT AL HIGH S T ATIC BELT DRIV E
ESP, In
O
H
2
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
012345
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
--- --- --- --- --- --- --- --- 5858 3.51 5538 2.97
--- --- --- --- --- --- 5894 3.85 5502 3.20 5282 2.78
--- --- --- --- 5780 4.04 5570 3.55 5110 2.88 4869 2.47
--- --- 5900 4.49 5501 3.77 5312 3.33 4793 2.64 4598 2.28 5860 4.76 5514 4.08 5257 3.54 4945 3.01 4382 2.34 --- --­5615 4.49 5315 3.88 5020 3.32 4504 2.66 --- --- --- --­5529 4.40 4906 3.49 4601 2.96 --- --- --- --- --- --­4938 3.78 4541 3.15 4222 2.65 --- --- --- --- --- ---
TURNS OPEN
NOTE: Unit factory shipped at 2.5 turns open. Tables represent dry coil without filter.
To compensate for filter , add 0.08" to me asured E.S.P. SCFM correction for wet c oil = 4%.
20
Page 21
APPENDIX B ELECTRICAL DATA
ELECTRICAL DA TA
MODELS
7.5 TON COOLER
7.5 TON HEAT
PUMP
8.5 TON
10 TON
VOLTAGE
VOLTAGE
(NAMEPLATE)
208/230-60-3 187 253 2 13.1 83.1 2 1/4 1.40 BD STD STATIC 1.5 5.0 2 6.0
460-60-3 414 506 2 6.1 41.0 2 1/4 0.80 BD STD STATIC 1.5 2.5 2 2.9
575-60-3 518 633 2 4.4 33 2 1/4 0.55 BD STD STATIC 1.5 2.3 2 2.4
208/230-60-3 187 253 2 13.1 83.1 2 1/4 1.40 BD STD STATIC 2.0 7.8 2 6.0
460-60-3 414 506 2 6.1 41.0 2 1/4 0.80 BD STD STATIC 2.0 3.9 2 2.9
575-60-3 518 633 2 4.4 33 2 1/4 0.55 BD STD STATIC 2.0 2.5 2 2.4
208/230-60-3 187 253 2 14.5 98.0 2 1/4 1.40 BD STD STATIC 2.0 7.8 2 6.0
460-60-3 414 506 2 6.3 55.0 2 1/4 0.80 BD STD STATIC 2.0 3.9 2 2.9
575-60-3 518 633 2 6.0 41.0 2 1/4 0.55 BD STD STATIC 2.0 2.5 2 2.4
208/230-60-3 187 253 2 16.0 110.0 2 1/3 2.40 BD STD STATIC 2.0 7.8 2.0 6.4
460-60-3 414 506 2 7.8 52.0 2 1/3 1.20 BD STD STATIC 2.0 3.9 2.0 3.0
LIMITATIONS
MIN MAX Qty RLA LRA Qty HP FLA HP FLA HP FLA
COMPRESSOR (ea)
OD FAN MOTORS
(ea)
ID MOTOR APPL
ID FAN MOTOR
(ea)
2 Speed ID Fan
Motor (ea)
12.5 TON
575-60-3 518 633 2 6.4 38.9 2 1/3 0.67 BD STD STATIC 2.0 2.5 2.0 2.4
208/230-60-3 187 253 2 22.4 149.0 2 1/3 2.40 BD STD STATIC 3.0 9.4 3.0 9.1
460-60-3 414 506 2 10.6 75.0 2 1/3 1.20 BD STD STATIC 3.0 4.7 3.0 4.3
575-60-3 518 633 2 7.70 54.0 2 1/3 0.67 BD STD STATIC 3.0 4.2 3.0 3.5
MINIMUM AIR FLOW FOR ELECT RI C HEAT
UNIT
7.5 TON
8.5 TON
10 TON
12.5 TON
HEATER KIT
MODEL NUMBER
EHK*-16 3000 3200 EHK*-30 3000 3200 EHK*-45 3000 3200 EHK*-16 3400 3400 EHK*-30 3400 3400 EHK*-45 3400 3400 EHK*-16 3500 3500 EHK*-30 3500 3500 EHK*-45 4000 4000
EHK*-16 4000 4000 EHK*-30 4300 4300 EHK*-45 4500 4500
MINIMUM CFM
Downshot
MINIMUM CFM
Horizontal
ATTENTION INSTALLING PERSONNEL
Use only the heater kit specified for each model as dictated by the table above.
21
Page 22
APPENDIX C UNIT DIMENSIONS
7.5 8.5 10 12.5
Y 52 7/8" 52 7/8" 52 7/8" 58 7/8"
99 1/8”
Y
61 3/4”
12 5/8”
5 7/8”
13 7/8”
28 3/8”
SUPPLY
6 1/4”
Horizontal Discharge
7 3/8”
RETURN
NOTE
For horizontal discharge, r emove supply and return duct cover panels from the end of the unit. Save all washered screws. According to the model size, remove (6 or 8) factory sup­plied panel clips that are secured to the base pan, behind the filter access panel. With the insulated side of the panel facing up, attach the clips. Place the provided gasket mate­rial completely around the perimeter of the clip side on both panels. Place the assembled panels over the supply and re­turn duct openings in the base pan and push down to snap panels into place. Ensure the panel is evenly seated on the flanges around the duct openings and the gasket is creating a good seal.
36 3/8”
5 3/8”
6 1/2”
RETURN
SUPPL
Y
7 1/2”
Vertical Discharge (Bottom of Unit)
22
Page 23
Start-up Checklist
*Store in job file
Date: ___________________________________
Model Number: ___________________________________
Serial Number: ___________________________________
Technician: ___________________________________
Pre Start-Up
(Check each item as completed)
Verify all pack aging ma t erial ha s been r emov ed. Remove all shipping brackets per installation instructions.
Verify the job site volt age agrees with the unit serial plate. Verify condensa te c onnection is inst alle d per ins t alla tion instructions. Verify pr oper clearance around the unit f or safety, service, maintenance and proper unit operation. Verify pr oper we a therpr oofing of all ductw ork, roof curbs and electrical connections.
Location: __________________________________________
__________________________________________ __________________________________________
Unit #: __________________________________________
Check that the flue screen is in place. Check gas piping f or leaks. Verify g a s pressure to the unit is within the range specified on the serial plate. Check to ensure that all fans, pulleys and wheels ar e secure. Check for proper belt tension and alignment per installation instructions. Check refriger ant piping for rubbing and leaks. Repair if necessary. Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges. Check all electrical connections and terminals. Tighten as needed. Verify tha t the crankcase heaters hav e been energized for 24 hours. Verify the scroll compressor(s) are rotating in the right direction. Verify all acce ssorie s are installed and operating correctly. Check filters and replace if necessary. Verify the ins t allation of the thermos t a t.
23
9/2014
Page 24
ELECTRICA
L
Start-up Checklist
Start-Up
(Insert the values as each item is completed.)
Supply Voltage Circuit 1 Compressor Amps Circuit 2 Compressor Amps
Blower Amps
Condenser Fan Amps
BLOWER EXTERNAL STATIC PRESSURE
Return Air Static Pressure Supply Air Static Pressure
Total External Static Pressure
Blower Wheel RPM
TEMPERATURES
Outdoor Air Temperature
Return Air Temperature
Co oling S upply A i r Tem p erat ure
He ating Sup p ly A ir Temperature
L1 - L2 L2 - L3 L3 - L1
L1 L2 L3 L1 L2 L3 L1 L2 L3
Fan 1Fan 2Fan 3
IN. W.C. IN. W.C. IN. W.C. RPM
DB WB DB WB DB WB DB
PRESSU RES
Ga s Inlet Pressure
Ga s Manifold Pressure
Superh ea t (O rific e Syst em)
Superh ea t (O rific e Syst em)
Discharge Circuit 1
Subcooling (TXV Syst em)
Discharge Circuit 2
Subcooling (TXV Syst em)
(HEAT P UM P ONLY)
Discharge Circuit 1 Discharge Circuit 2
Suction Circuit 1
Suction Circuit 2
Suction Circuit 1 Suction Circuit 2
IN. W.C. IN. W.C. (Low Fire) IN. W.C. (High Fire) PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F PSIG °F PSIG °F PSIG °F
24
Loading...