Goodman CAUF, CAPF, CAPT, CHPF, CSCF Installation Manual

UPFLOW/DOWNFLOW COILS
INSTALLATION INSTRUCTIONS
1. Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these sym­bols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
HIGH VOLTAGE!
ISCONNECT
D
INSTALLING MAY DAMAGE
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR (HEREINAFTER SHOULD SERVICE THE EQUIPMENT FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
THIS UNIT
BE
PRESENT
,
PERSONAL INJURY OR DEATH
. I
MPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF
ALL
POWER BEFORE SERVICING OR
. M
ULTIPLE POWER SOURCES
. F
AILURE TO DO SO MAY CAUSE PROPERTY
.
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS MANUAL
. THE
MANUFACTURER WILL NOT BE RESPONSIBLE
. IF
YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY
.
. IN
ADDITION, IN
,
2. Shipping Inspection
Upon receiving the product, inspect it for damage from shipment. Shipping damage, and subsequent investigation is the responsi­bility of the carrier. Verify the model number, specifications, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for trans­portation damage or installation of incorrectly shipped units.
2. 1 Handling
Use caution when transporting / carrying unit.. Do not carry unit with hooks or sharp object. The preferred method of carrying the unit after arrival at the job site is to carry by two­wheel hand truck from the back or sides or by hand by carry­ing at the cabinet corners.
3. Codes & Regulations
This product is designed and manufactured to comply with na­tional codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the in­staller. The manufacturer assumes no responsibility for equip­ment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and dis­posal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of sub­stantial fines. Should you have any questions please contact the
local office of the EPA.
4. Replacement Parts
Inspect the unit to verify all required components are present and intact. Report any missing components immediately to the manufacturer or to the distributor. Make sure to include the full product model number and serial number when reporting and/ or obtaining service parts. Replacement parts for this product are available through your contractor or local distributor. For the location of your nearest distributor consult the white busi­ness pages, the yellow page section of the local telephone book or contact:
HOMEOWNER SUPPORT
GOODMAN MANUFACTURING COMPANY, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484
877– 254 – 4729
5. Pre-Installation Instructions
5.1 Preparation
Keep this document with the unit. Carefully read all instruc­tions for the installation prior to installing product. Make sure each step or procedure is understood and any special consid­erations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to com­plete the installation. Some items may need to be purchased locally. Make sure everything needed to install the product is on hand before starting.
5.2 Clearances
Refrigerant lines must be routed depending on configuration of unit to maintain the required 24” minimum clearance for service. Consult all appropriate regulatory codes prior to de­termining final clearances. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protec­tive barrier to prevent such damage. Always install units such that a positive slope in condensate line (1/4" per foot) is al­lowed.
6. Application Information
Coils are designed for indoor installation only and must be in­stalled downstream (discharge air) of the furnace. The CAPF/CAPT product line may be installed in upflow or downflow orienta­tions.
IO-284H 02/2018
5151 San Felipe, Suite 500, Houston, TX 77056
© 2005-2006, 2012-2013, 2015-2018 Goodman Manufacturing Company , L.P .
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
7. Condensate Drain Piping
In all cooling applications where condensate overflow may cause damage, a secondary drain pan must be provided by the installer and placed under the entire unit with a separate drain line prop­erly sloped and terminated in an area visible to the owner. This secondary drain pan can provide extra protection to the area under the unit should the primary drain plug up and overflow. As expressed in our product warranty, we will not be liable for any damages, structural or otherwise due to the failure to follow this installation requirement.
Condensate drain connections are located in the drain pan at the bottom of the coil/enclosure assembly. Use the female (3/4” FPT) threaded fitting that protrudes outside of the enclosure for exter­nal connections. The connectors required are 3/4" NPT male, ei­ther PVC or metal pipe, and must be hand tightened to a torque of no more than 37 in-lbs. to prevent damage to the drain pan con­nection. An insertion depth between .36 to .49 inches (3-5 turns) should be expected at this torque.
1. Ensure drain pan hole is NOT obstructed.
2. To prevent potential sweating and dripping on finished space, it may be necessary to insulate the condensate drain line located inside the building. Use Armaflex® or similar mate­rial.
A Secondary Condensate Drain Connection, now called for by many building codes, has been provided. Pitch the drain line 1/4" per foot to provide free drainage. Provide required support to drain line to prevent bowing. Install a condensate trap in the primary drain line to ensure proper drainage. If the secondary drain line is required, run the line separately from the primary drain and end it where condensate discharge can be easily seen.
CAUTION
IF
SECONDARY DRAIN IS NOT INSTALLED, THE SECONDARY ACCESS
MUST
BE
PLUGGED
8. Refrigerant Lines
.
8. 1 Tubing Size/Length
For the correct tubing size, follow the specification for the condenser/heat pump. Give special consideration to minimiz­ing the length of refrigerant tubing when installing coils. Refer to Remote Cooling/Heat Pump Technical Publication TP-107* Long Line Set Application R-410A for guidelines for line lengths over 80’. Leave a minimum 3" straight in line set from braze joints before any bends.
8.2Tubing Preparation
All cut ends are to be round, burr free, and cleaned. Any other condition increases the chance of a refrigerant leak. Use a pipe cutter to remove the closed end of the spun closed suction line.
8.3Brazing
Braze joints should be made only with the connections pro­vided external to the cabinet. Do not alter the cabinet nor braze inside the cabinet. To avoid overheating after brazing, quench all brazed joints with water or a wet rag.
A
PPLYING TOO MUCH HEAT TO ANY TUBE CAN MELT THE TUBE HEAT REQUIRED TO BRAZE TUBES OF VARIOUS SIZES MUST BE PROPORTIONAL TO THE SIZE OF THE TUBE
ERVICE PERSONNEL MUST USE THE APPROPRIATE HEAT LEVEL FOR THE
S
SIZE OF THE TUBE BEING BRAZED
.
.
. T
8.4Special Instructions for Flowrator (Piston) Version
Coils in flowrator version are equipped with a check style flowrator for refrigerant management. For most installations with matching applications, no change to the flowrator piston is required. However, in mix-matched applications, a piston change may be required. See the piston kit chart or consult your local distributor for details regarding mix-matched pis­ton sizing. If the mix-matched application requires a different piston size, change the piston in the distributor on the indoor coil before installing the coil and follow the procedure shown below.
8.5Tubing Connections for Flowrator Model
ORCH
CAUTION
THE
COIL IS SHIPPED UNDER PRESSURE WITH AN MIXTURE INSTRUCTIONS
A
QUENCHING CLOTH IS STRONGLY RECOMMENDED TO PREVENT
SCORCHING OR MARRING OF THE EQUIPMENT FINISH WHEN BRAZING CLOSE TO THE PAINTED SURFACES MINIMUM SILVER CONTENT
. USE
APPROPRIATE SERVICE TOOLS AND FOLLOW THESE
TO
PREVENT INJURY
.
. USE
BRAZING ALLOY OF
.
NOTE: Refrigerant tubing must be routed to allow adequate ac-
cess for servicing and maintenance of the unit. Do not handle coil assembly with manifold or flowrator tubes.
Doing so may result in damage to the tubing joints. Always use clean gloves for handling coil assemblies.
R-410A
GAS
5%
1. Loosen the 13/16 nut 1 TURN ONLY to allow high pressure tracer gas to escape. No gas indicates a possible leak.
2. After the gas has escaped, remove the nut and discard the plastic or brass cap.
3. Remove the check piston to verify it is correct and then re­place the piston. See piston kit chart in instructions.
4. Use a tube cutter to remove the spin closure on the suc­tion line. DO NOT USE A CUTTING METHOD THAT WOULD RESULT IN THE GENERATION OF COPPER SHAVINGS OR COPPER DUST.
5. Slide the 13/16 nut into place on the tailpiece supplied in the literature bag or with the unit.
6. Insert liquid line into the supplied tailpiece.
2
Figure 1
7. Insert the suction line into the connection, slide the insula­tion and the rubber grommet at least 18" away from the braze joint. Braze both liquid and suction line joints.
8. AFTER THE TAILPIECE HAS COOLED, confirm position of the white Teflon® seal and hand tighten the 13/16 nut.
CAUTION
E
XCESSIVE TORQUE CAN CAUSE ORIFICES TO STICK
SETTINGS WHEN TIGHTENING ORIFICES
TORQUE
.
. USE
THE PROPER
LIQUID LINE
RUBBER GROMMET
LIQUID LINE SET
Figure 2.2
5. Insert liquid line set into liquid tube expansion and slide grommet about 18" away from braze joint.
6. Insert suction line set into suction tube expansion and slide insulation and grommet about 18" away from braze joint.
7. Braze suction and liquid line joints.
9. Top flange s can be bent f or e ase in inst allation t o the duct flanges.
9. Torque the 13/16” nut to 10-20 ft-lbs. or 1/6 turn past hand tight.
10. Replace suction line grommet and insulation.
8. 6 Tubing Connections for TXV Version
TXV models come with factory installed non-adjustable TXV with the bulb permanently located on the suction tube.
1. Remove coil access panel.
2. Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indicates possible leak.
3. Replace the refrigerant tubing panel.
4. Remove the spin closure on both the liquid and suction tubes using a tubing cutter. DO NOT USE A CUTTING METHOD THAT WOULD RESULT IN THE GENERATION OF COPPER SHAVINGS OR COPPER DUST.
SUCTION TUBE
Top Flange D etail V iew
FILLER PLATE
Unfolded View
SUCTION LINE SET
Figure 2.1
RUBBER GROMMET
Figure 3
10.Filler Plates
Filler plates are supplied on all 17.5, 21, & 24.5 inch chassis to be used for adapting the unit to a furnace one size smaller. If the plenum and furnace openings are the same size, the filler plates must be removed. See Figure 3.
3
Loading...
+ 5 hidden pages