Goodman APG154811541A, APG153609041A, APG154911541A, APG156014041A, GPG152407041A Technical Manual

...
TECHNICAL MANUTECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANUTECHNICAL MANU
ALAL
AL
ALAL
*PG15
Package Gas Units
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
Select Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
®
C
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult a tax professional if they have questions about the applicability of these credits.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
US
RT6313001r11
April 2010
Copyright © 2007 - 2009-2010 Goodman Manufacturing Company, L.P.
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
PG15240704 1 * *G / A
BRAND:
G: Goodman Brand or Distinctions
A: Amana Brand
®
®
PRODUCT
TYPE:
Single Package
Cooling/Heating
PRODUCT FAMILY:
G: Gas/Electric
PRODUCT
SERIES:
SEER
Rating
NOM INAL CAPACITY:
24: 24,000 BT UH 30: 30,000 BT UH 36: 36,000 BT UH 37: 36,000 BT UH 42: 42,000 BT UH 48: 48,000 BT UH 49: 48,000 BT UH 60: 60,000 BT UH
EFRIGERANT :
4: R-410A
HEATING INPUT
070: 69,000 BTUH
090: 92,000 BTUH 115: 115,000 BTUH 140: 138,000 BTUH
M IN OR REVI SION:
MAJOR REVISIO N:
VOLTAGE:
1: 20 8-230V/1ph/60Hz 3: 20 8-230v/3ph/60H z 4: 46 0v/ 3ph/60Hz
WARNING
WARNING
WARNING
WARNING
arising from improper service or service procedures. If you install or perform service on this unit, you assume responsibility for any personal injury or property damage which may result. Many jurisdictions require a license to install or service heating and air conditioning equipment.
Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Goodman will not be responsible for any injury or property damage
2
HIGH VOLTAGE!
WARNING
WARNING
dividuals meeting (at a minimum) the requirements of an "entry level technician" as specified by the Air-Condition­ing, Heating, and Refrigeration Institute (AHRI). Attempt­ing to install or repair this unit without such background may result in product damage, personal injury or death.
Installation and repair of this unit should be performed ONLY by in-
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
APG152407041A*
APG153009041A*
APG153609041A*
APG153709041A*
APG154209041A*
APG154811541A*
APG154911541A*
APG156014041A*
* Indicates minor revision & is not used for order entry or inventory management
GPG152407041A*
GPG153009041A*
GPG153609041A*
GPG153709041A*
GPG154209041A*
GPG154811541A*
GPG154911541A*
GPG156014041A*
The models listed below qualify
for the 2009 and 2010 Federal Tax Credits
for Energy Efficiency**
APG152407041A*
APG153007041A*
APG153709041A*
APG154209041A*
APG154911541A*
GPG152407041A*
GPG153007041A*
GPG153709041A*
GPG154209041A*
GPG154911541A*
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consum­ers consult a tax professional if they have questions about the applicability of these credits.
WARNING
WARNING
WARNING
WARNING
Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations re­garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device that is not design certified by Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance.
To prevent the risk of property damage, personal injury, or death,
3
PRODUCT DESIGN
*PG15 Package Gas Units are designed for outdoor installa­tions only in either residential or light commercial applica­tions and are available in 2, 2-1/2, 3, 3-1/2, 4 & 5 ton sizes. They are designed for 208/230 volt single phase applications.
The connecting ductwork (Supply and Return) can be con­nected for either horizontal or vertical airflow. In the vertical application, a matching Roof Curb is recommended.
A return air filter must be installed behind the return air grille(s) or provision must be made for a filter in an accessible loca­tion within the return air duct. The minimum filter area should not be less than those sizes listed in the Specification Sec­tion. Under no circumstances should the unit be operated without return air filters.
A 3/4" pipe is provided for removal of condensate water from the indoor coil. (Do not reduce the drain line size).
Refrigerant flow control is achieved by use of a TXV or ori­fice.
*PG15 units use the FasTest Access Fitting System which consists of a saddle that is either soldered to the suction and liquid lines or is fastened with a locking nut to the access fitting box (core) and then screwed into the saddle. NOTE:
The core must not be removed from the saddle until the refrigerant charge has been removed. Failure to do so could result in property damage or personal injury.
The single phase units use permanent split capacitors (PSC) design compressors. Starting components are therefore not required. A low MFD run capacitor assists the compressor to start and remains in the circuit during operation.
The *PG15*****41AA models are equipped with X-13 blower motors. X-13 motors are constant torque motors with very low power consumption and are energized by a 24V signal from the ignition control board. The X-13 features an inte­grated control module.
Air for condensing (cooling cycle) is drawn through the out­door coil by a propeller fan, and is discharged vertically out the top of the unit. The outdoor coil is designed for .0 static. No additional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed, across the coil and back into the conditioned space by the indoor blower.
The *PG15 series package units use the Compliant Scroll compressor; there are a number of design characteristics which are different from the traditional reciprocating compres­sor.
- Due to their design Scroll compressors are inherently more tolerant of liquid refrigerant. NOTE: Even though the com­pressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued flood back or flooded start condi­tions may wash oil from the bearing surfaces causing prema­ture bearing failure.
- These Scroll compressors use "POE" orpolyolester oil which is NOT compatible with mineral oilbased lubricants like 3GS. "POE" oil must be used if additional oil is required.
- Compliant scroll compressors perform “quiet” shutdowns that allow the compressor to restart immediately without the need for a time delay. This compressor will restart even if the system has not equalized.
- Operating pressures and amp draws may differ from stan­dard reciprocating compressors. This information may be found in the “Cooling Performance Data” section.
Some other models of the *PG15 series package units use a 2 stage scroll compressor. The basic scroll design has been modified with the addition of an internal unloading mecha­nism that opens a by-pass port in the first compression pocket, effectively reducing the displacement of the scroll. The opening and closing of the by-pass port is controlled by an internal electrically operated solenoid.
The ZPS modulated scroll uses a single step of unloading
to go from full capacity to approximately 67% capacity. A single speed, high efficiency motor continues to run while the scroll modulates between the two capacity steps.
4
PRODUCT DESIGN
Location and Clearances
NOTE: To ensure proper condensate drainage, unit must be installed in a level position.
48" MIN
2" MIN
36" MIN (FOR SERVICE)
.
12" MIN
Outside Slab Installation
NOTE: Ro of overha ng should be n o more than 36 " and provi-
sions made to deflect the warm discharge air out from the overhang. Minimum clearances are required to avoid air recir­culation and keep the unit operating at peak efficiency.
3"
MIN
(FOR SERVICE)
36" MIN
NOTE: To ensure proper condensate drainage, unit must be installed in a level position.
In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top in­stallations) the installer must provide service platform for ser­vice person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edition of the National Fuel Gas Code ANSIZ223.1.
NOTE: Unit can als o use roof c urb (and pla tform for l eveling, where necessary) to utilize bottom discharge.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING IF A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.
IMPORTANT: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing the unit.
Refer to Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Rooftop Installation
5
PRODUCT DESIGN
High Altitude Derate - U.S. Installations Only
IMPORTANT NOTE: The gas/electric units naturally derate
with altitude. Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate. Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for altitude adjustments.
When this package unit is installed at high altitude, the ap­propriate High Altitude orifice kit must be installed. As alti-
NATURAL GAS AND LP GAS INSTALLATIONS AT ALTITUDES > 2000 FT
tude increases, there is a natural reduction in the density of both the gas fuel and combustion air. This kit will provide the proper design certified input rate within the specified altitude range. High altitude kits are not approved for use in Canada. For installations above 2,000 feet, use kit HA-02. The HA-02 kit is used for both Natural and LP gas at high altitudes.
Use LPM-06 propane conversion kit for propane conversions at altitudes below 2000 feet. Natural gas installations below 2000 feet do not require a kit.
For propane conversions above 2000 feet, high altitude kit HA-02 is required in addtion to LPM-05 propane conversion kit.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
U.S. BURNER ORIFICE 45/55 47/55 47/56 - 47/56 48/57 48/58 49/58
HA02
CANADA BURNER ORIFICE 45/55 - - 48/57 - - - -
22,500 BTUH NAT/20,OOO BTUH/L.P.
20,000 BTUH NAT/20,OOO BTUH/L.P.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
U.S. BURNER ORIFICE 44/55 44/55 45/56 - 45/56 46/57 47/58 47/58
HA02
CANADA BURNER ORIFICE 44/55 - - 47/57 - - - -
25,000 BTUH NAT/20,OOO BTUH/L.P.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
U.S. BURNER ORIFICE 43/55 43/55 44/56 - 44/56 44/56 45/57 45/57
HA02
CANADA BURNER ORIFICE 43/55 - - 46/57 - - - -
6
PACKAGE GAS SPECIFICATIONS
UNIT DIMENSIONS
SUCTION/LIQUID PRESSURE PORTS
BEHIND COMPRESSOR ACCESS PANEL
COMBUSTION AIR INTAKE
HEAT EXCHANGE ACCESS PANEL
CONDENSATE DRAIN CONNECTION
F
O
R
E
Y
T
T
I
N
V
E
A
C
R
G
20
24
47
GAS SUPPLY ENTRANCE
3/4" NPT FEMA LE
FLUE EXHAUST
HOOD
FLUE EXHAUST
C
4 3/4
16 1/8
19 1/8
7 5/16
7 7/8
POWER WIRE ENTRANCE
CONTROL WIRE ENTRANCE
51
18 7/16
1 3/8
5 1/2
16
7 15/16
B
(INCHES)
SUPPLY
3
EVAPORATOR/CONTROL PANEL ACCESS PANEL
DIMENSION
B
MEDIUM
16
RETURN
A3240 B1618
C9 1/214
A
2 3/4
LARGE
MEDIUM CHASSIS
*PG15[24-37]
LARGE CHASSIS
*PG15[42-60]
5 1/4
COMBUSTION AIR INTAKE
SUPPLY
EXHAUST FLUE HOOD
BLOWER ACCESS PANEL
11
5 3/4
22
11
RETURN
22
7
PACKAGE GAS SPECIFICATIONS
*PG152407041AA *PG153009041AA *PG153609041AA *PG153709041AA
COOL ING COOLING CAPACITY, BTUH
CAPACI TY HIGH STAGE 23,200 29,000 35,400 35,000
LOW STAGE N/A N/A 24,400 N/A
SEER / EER 15.0 / 12.0 14.5 / 12.0 15.0 / 11.0 14.5 / 12.0
HEATI NG BTUH INPUT (US) HIGH FIRE 69,000 92,000 92,000 92,000
CAPACI TY OUTPUT (US) HIGH FIRE (Natural Gas) 55,000 73,500 73,500 73,500
OUTPUT (US) HIGH FIRE (LP) 50,000 69,000 69,000 69,000
BTUH INPUT (US) LOW FIRE 52,000 69,000 69,000 69,000
OUPUT (US) LOW FIRE (Natural) 41,500 55,000 55,000 55,000
OUTPUT (US) LOW FIRE (LP) 37,000 50,000 50,000 50,000
A.F.U.E. 80 80 80 80
RATED EXTERNAL STATIC (" w.c .) 0.50 0.50 0.50 0.50
TEMPERATURE RIS E (°F) 35- 65 45-7 5 45-75 45-7 5
PRESSURE SWITCH TRIP POINT (" w.c.) -.33" -.33" -.33" -.33"
UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
EL EC TRI C AL UNIT AMPS (TOTAL) 18.7 17.5 22.2 20.1
SP ECI F IC AT I ON MINIMUM CIRCUIT AMPACITY 22.1 21 26.5 24.2
HEATI NG NUMBER OF BURNERS 3 4 4 4
SE CT I ON ORIF ICE SIZE NATURAL 43 43 43 43
COMPR ESSO R TYPE Scr oll Scr oll Scro ll Scrol l
RATED LOAD AMPS 13.5 14.1 16.7 16.7
COND ENSER HORSEPOWER 1/6 1/4 1/4 1/4
FAN MO TOR RPM 815 830 1075 830
COND ENSER BLADE DIAMETER (INCHES) 22 22 22 2 2
FAN NUMBER OF BLADES 3 3 3 3
COND ENSER FA CE AREA - SQ. FT. 12.3 12 .3 12. 3 12.3
COI L NUMBER OF ROWS 1 2 1 2
EV APO RAT O R HORSEPOWER - NO. OF SPEEDS 1/2 - X-13 1/2 - X-13 1/2 - X-13 1/2 - X-13
BLOW ER FULL LOAD AMPS 4.1 1 .86 4. 1 1 .86
MOT OR LOCKED ROTOR AMPS N/A N/A N/A N/A
EV APO RAT O R DIAMETER X WIDTH (INCHES) 10 x 8 10 x 9 10 x 9 10 x 9
BLOW ER RAT ED SCFM COOLING 845 1050 800 / 1225 1050
EV APO RAT O R FAC E AREA - SQ. FT. 4.33 4 .33 4.33 4.33
COI L NUMBER OF ROWS 2 3 4 4
HEATI NG PRIMARY LIMIT SETTING (°F) 160 160 160 160
LIMITS AUXILIARY LIMIT SETTING (°F) 150 150 150 1 50
GENERAL EXPANSION DEVICE TXV 0.065 TXV TXV
IN FORM ATIO N REFRIGERANT CHARGE R-410A (Oz.) 81 102 99 112
MAXIMUM OVERCURRENT PROTECTION
ORIFICE SIZE LP 55 55 55 55
LOCKED ROTOR AMPS 58.3 73 82 79
FULL L OA D AMPS 1. 10 1. 5 1.4 1.5
LOCKED ROTOR AMPS 1.7 3.0 2.9 3.0
CFM 2400 2700 2700 2700
FIN S PE R INCH 22 16 22 1 6
MOTOR SPEED TAP - COOLING T4 T3, T4 T3, T4 T3, T4
RPM / AMPS 724 / 1.21 960 / 3.06
MAX EXTERNAL STATIC PRESS ("w.c.) 0.5 0. 5 0.5 0.5
FIN S PE R INCH 14 14 14 1 4
FIL TER SI ZE - S Q. FT.
DRAIN SIZE (INCHES) 3/4 3/4 3/4 3/4
ROLLOUT LIMIT SETTING (°F) 300 300 300 300
POWER SUPPLY ENTRANCE SIZE (INCHES) 1 1/8 1 1/8 1 1/8 1 1 /8
LOW VOLTAGE ENTRANCE SIZE (INCHES) 7/8 7/8 7/8 7/8
SHIPPING WEIGHT LBS. 439 475 480 480
OPERATING WEIG HT LBS. 417 453 458 45 8
(2)
(3)
30 35 40 40
2.7 4.2 4.2 4.2
*PG15[24-37]***41AA
640 / 0 .98 960 / 3 .06
960 / 3.06
(1) Units installed in Canada are cer tif ed only to 4 500 fee t. (2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only. (3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
8
PACKAGE GAS SPECIFICATIONS
*PG154211541AA *PG154811541AA *PG154911541AA *PG156014041AA
COO LIN G CA PAC ITY, B TU H
HIGH STA GE 40,0 00 4 7,50 0 47 ,000 56,500
LOW STA GE N/A 3 5,0 00 3 3,00 0 41 ,000
SE ER/ EE R 1 4.5 / 12 .0 15 .0 / 1 1. 0 15 .0 / 1 2.0 14. 0 / 1 0. 1
BT UH INP U T (US ) HIG H FIR E 1 15, 000 1 15, 000 11 5,0 00 13 8, 000
OU TP UT (US ) HIG H FI RE (N atu ra l G as ) 9 2,0 00 9 2, 00 0 9 2,00 0 11 0, 200
OU TP UT (US ) HIG H FI RE (L P) 8 3,0 00 8 3,0 00 8 3 ,00 0 99 ,0 00
BT UH INP U T (US ) LOW F IR E 86, 000 8 6,0 00 86 ,00 0 10 3, 000
OU PU T ( US ) L OW F IRE ( Nat ur al) 6 9,0 00 69, 00 0 6 9, 000 83 ,00 0
OU TP UT (US ) LO W FIRE (L P) 62, 000 6 2,0 00 6 2, 000 74, 00 0
A.F .U .E. 80 8 0 8 0 8 0
RATE D EX TE RNAL STAT IC (" w.c. ) 0. 50 0.50 0 .50 0.50
TEMPE RATUR E RISE ( °F) 45-75 45-75 45-75 4 5-75
PR ESS UR E S WI TC H T RI P P OI NT (" w.c .) -.3 3" -.3 3" - .3 3" -.3 3"
VOL TA GE (N AM EPL AT E) 2 08- 230 /1/ 60 20 8-2 30 /1/60 208 -23 0/1 /60 2 08- 230 /1/ 60
UNIT AMPS (TOTA L) 22. 2 29 .4 2 5.5 3 5.6
MINI M UM CIRCU IT A MPACITY 26.6 34. 8 3 0.8 42.1
MAX IMUM O VER CURRE NT PR OTEC TION
NUM BER OF BURNERS 5 5 5 6
ORIFICE SIZE N ATURAL 43 43 43 43
ORIFICE SIZE LP 55 55 55 55
TYPE Scroll Scroll Scro ll Scr oll
RATE D LO AD AMP S 17. 9 21.2 21.2 2 5.6
LOC KED R OTO R A MPS 1 12 96 9 6 118
HORS EPOWER 1/ 4 1/3 1/4 1/3
RPM 107 5 1 075 10 75 1075
FULL LO AD AMPS 1.4 2.5 1.4 2.5
LOC KED R OTO R A MPS 2.9 5. 8 2.9 5 .2
BL ADE DI AM ETE R ( INC HE S) 22 2 2 22 2 2
NUMB ER O F BLA DES 3 4 3 4
CFM 3 500 35 00 3500 350 0
FACE AREA - SQ. FT. 15.3 15.3 15.3 15.3
NUM BER OF ROW S 2 2 2 2
FINS PER INCH 16 16 16 16
HORS EPOWER - NO. OF SPEED S 3/4 - X- 13 3 /4 - X- 13 3/4 - X-13 1 - X-13
FULL LO AD AMPS 2.87 6.00 2. 87 7.60
LOC KED R OTO R A MPS N/ A N/ A N /A N/ A
MOTO R SP EE D TAP - COOL ING T3, T4 T3, T4 T3, T4 T3, T4
RPM / AMPS 890 / 3. 8
DIA METER X WI DTH (INC HES) 11 x 10 1 1 x 10 11 x 10 11 x 10
RATE D SCFM COOL ING 120 0 110 0 / 1510 1300 1300 / 18 10
MAX EX TE RN AL STATI C PRE SS ("w.c. ) 0 .5 0.5 0.5 0. 5
FACE AREA - SQ. FT. 5.67 5.67 5.67 5.67
NUM BER OF ROW S 4 4 4 4
FINS PER INCH 14 14 14 14
FILTER SIZE - SQ. FT.
DRAI N SIZE (INCHES ) 3/ 4 3/4 3/4 3/ 4
PR IMA RY L IM IT SE TTI NG (° F) 170 1 70 1 70 16 0
AU XIL IA RY LIM IT S ETT ING (°F ) 1 50 1 50 1 50 15 0
ROL LOUT LIM IT SET T ING (°F) 300 300 3 00 300
EX PAN SI ON DEVIC E 0. 072 T XV TX V T XV
REFRIG ERANT CHARGE R- 410 A ( Oz .) 162 1 69 167 177
POW E R S UPP L Y EN TR ANC E SI ZE (IN CH ES ) 1 1/ 8 1 1/ 8 1 1 /8 1 1 /8
LOW VO LT AGE E NTR ANC E SIZE (I NC HES ) 7/ 8 7/8 7/ 8 7 /8
SH IPP ING W EI GHT LB S. 5 60 560 560 56 5
OPERATING WEIGHT LBS. 538 538 538 543
(2)
(3)
40 5 0 50 60
647 / 1.66
890 / 3 .8
5.1 5.1 5.1 6.3
*PG15[42-60]***41AA
890 / 3.8
778 / 1.98 1030 / 5.7
(1) Units installed in Canada are cer tif ed only to 4 500 fee t. (2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only. (3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
9
PACKAGE GAS SPECIFICATIONS
S
*PG15360 9041AB * PG154811541AB *P G156014041AB
COOLING COOLING CAP ACI TY, BT UH
CAPACITY HIGH STAGE 35,40 0 4 7,500 56,500
LOW STAG E 2 4,40 0 3 5,0 00 41, 000
SEER/EER 15.0 / 11.0 15.0 / 11.0 14.0 / 10.1
HEATING BTUH INPUT (US) HIGH FIRE 92,000 115,000 138,000
CAPACITY OUTPUT (US) HIGH FIRE (Natural Gas) 73,500 92,000 110,200
OUTPUT (US) HIGH FIRE (LP) 69,000 83,000 99,000
BTUH INPUT (US) LOW FIRE 69,000 86,000 103,500
OUPUT (US) LOW FIRE (Natural) 55,000 69,000 83,000
OUTPUT (US) LOW FIRE (LP) 5 0,000 62,000 74,000
A.F.U.E. 80 80 80
RATE D E XTERN AL STA TIC (" w.c. ) 0.50 0.5 0 0.50
TEMPERA TURE RISE (°F) 45-75 4 5-75 45-75
PRESSURE SWITCH TRIP POINT (" w .c.) -.33" -.33" -.33"
UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60
EL ECT RIC AL UNIT AMP S (TOTA L) 22.3 20.1 3 4.6
SPEC IFI CATI ON MIN IMUM CI RC UIT AMPACI TY 26 .5 34. 8 42.1
MAXIMU M OVE RCU RREN T PRO TECTIO N
HEATING NU MBE R O F B URN ERS 4 5 6
SEC TIO N ORIFICE SIZE NATURAL 43 43 43
ORIFICE SIZE LP 55 55 55
COMPR ESSOR
RA TE D L OA D A MPS 16 .7 21. 2 25.8
CONDENSER HORSEPO WER 1/4 1 /4 1/4
FAN MOTOR RPM 830 1075 107 5
CONDENSER BLADE DIAMETER (INCHES) 22 22 22
FAN NUMBER OF BLADES 3 3 3
CONDENSER FACE AREA - SQ . FT. 12.3 15.3 1 5.3
COIL NU MBE R O F RO W S 1 2 2
EVAP ORAT O R
BLOWE R FULL LOAD AMPS 4.1 6 7.6
MOTO R LOCKED ROTOR AMPS N/A N/A N/A
EVAP ORAT O R DIAMETE R X WIDT H (INCHES ) 10 x 9 11 x 10 1 1 x 10
BLOWE R RATED S CF M CO OL ING 800 / 122 5 1100 / 151 0 1300 / 1 810
EVAP ORAT O R FACE A REA - SQ. F T. 4.33 5.67 5. 67
COIL NU MBE R O F RO W S 4 4 4
HEATING PRIMARY LIMIT SETTING (°F) 160 170 160
LIMITS AUXILIARY LIMIT SETTING (°F) 150 150 150
GENERAL EXPANSION DEVICE TXV TXV TXV
IN FO RM ATI ON REFR IGERANT CH ARG E R -410A (Oz .) 102 172 18 0
TYPE Scroll Scr oll Scrol l
LOCKED ROTOR AMPS 82 96 118
FULL LOAD AMPS 1.5 1 .4 1.4
LOCKED ROTOR AMPS 3.0 5.2 5.2
CFM 2700 3500 3500
FINS PER INCH 22 16 16
HOR SEPO W ER - N O. OF SPE EDS 1/ 2 - X- 13 3/4 - X -13 1 - X -13
MOT OR SPEED TAP - COOLI NG T3, T4 T3, T4 T3,T 4
RPM / A MPS
MAX E XTER NAL STA TIC PRESS (" w.c.) 0.5 0.5 0 .5
FINS PER INCH 14 14 14
FILTER SIZE - SQ. FT .
DRAIN SIZE ( INCHE S) 3/4 3/ 4 3 /4
ROL LOU T LI MI T SET TING (°F ) 300 300 300
POWER SUPPLY ENTRANCE SIZE (INCHE
LOW VOLTAGE ENTRANCE SIZE (INCHES) 7/8 7/8 7/8
SHIPPING WEIGHT LBS. 480 560 565
OPERATING WEIGHT LBS. 458 538 543
(2)
(3)
*PG15[36-60]***41AB
40 50 60
640 / 0.98 960 / 3.06
4.2 5 .1 6.3
1 1/8 1 1/8 1 1/8
647 / 1. 66
890 / 3.8
778 / 1.98 1030 / 5.7
(1) Units installed in Canada are cer tif ed only to 4 500 fee t. (2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only. (3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
10
ACCESSORIES
ACCESSOR IES
Part Number Description
LPM-06 Propane Conversion Kit
HA-02 High Altitude Kit
PGC101/10 2/103 Roof Curb
PGED101/102 Downflow Economizer, Smal l and Medium Chassis
PGED103 Downflow Ec onomi zer, Larg e Cha ssis
PGEH101/102 Hor izon tal Economizer, Smal l and Medium Chassis
PGEH103 Horizon tal Ec onomizer, Large Chassis
PGMDD101/102 Manual 25% Fresh Air Damper Downfl ow Appli cation, Sma ll and Medium Chas sis
PGMDD103 Manual 25% Fresh Air Damper Downfl ow Appli cation, Large Chas sis
PGMDH101 Manual 25% Fresh Air Damper Horizontal Application, Small Chassis
PGMDH102 Manual 25% Fresh Air Damper Horizontal Application, Medi um Chass is
PGMDH103 Manual 25% Fresh Air Damper Hori zontal Appl ic ation, Large Chassis
PGMDMD101/102 Motor iz ed 25% Fresh Air Damper Downflow Applicati on,Sma ll a nd Medium Chassis
PGMDMD103 Motorized 25% Fresh Air Downflow Appl ication, La rge Chassis
PGMDMH101 Motorized 25% Fresh Air Damper Horizontal Application, Small Chassis
PGMDMH102 Motorized 25% Fresh Air Damper Hori zontal Appl ic ation, Medi um Chassis
PGMDMH103 Motorized 25% Fresh Air Damper Hori zontal Appl ic ation, Large Chassis
SQRPG101/102 Squa re to Round Adapter w/ 16" Round Downflow Appl ica tion, Sm all and Medium Chas si s
SQRPG103 Squa re to Round Adapter w/ 18" Ro und Downfl ow Appl ica tion, Large Chas si s
SQRPGH101/102 Squa re to Round Adapter w/ 16" Round Horizontal Appl ic ation, S mall and Mediu m Chass is
SQRPGH103 Square to Round Adapter w/ 18" Round Horizontal Appl ication, La rge Chassis
PGFR101/102/103 Internal Filter Rack All Chassis
GPGHFR101-103
CDK36 Flush Mount Concentric Duct Kit
CDK36515 Flush Mount Concentric Duct Kit w/ Filter
CDK36530 Step Down Concentric Duct Kit
CDK36535 Step Down Concentric Duct Kit w/ Filter
CDK4872 Flush Mount Concentric Duct Kit
External Horizontal Filter Rac k for Goo dman/Amana Gas/E lectric & Multi-posi tion Package Units Al l Chas sis
CDK4872515 Flush Mount Concentric Duct Kit w/ Filter
CDK4872530 Step Down Concentric Duct Kit
CDK4872535 Step Down Concentric Duct Kit w/ Filter
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
11
BLOWER PERFORMANCE DATA
*PG15240701A * - Rise Range: 35° - 65°
Un it
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS CFM WATTS AMPS CFM W ATTS AMPS
0.1 742 84 0.75 52 907 134 1.18 57 857 116 1.04 907 134 1.18 1,040 185 1.33
0.2 677 89 0.82 57 857 140 1.24 61 816 126 1.16 857 140 1.24 988 198 1.40
0.3 631 97 0.90 62 814 149 1.32 64 760 131 1.18 814 149 1.32 949 208 1.42
0.4 575 101 0.92 X 761 154 1.33 X 721 140 1.25 761 154 1.33 903 213 1.49
0.5 526 111 1.01 X 727 165 1.41 X 670 145 1.31 727 165 1.41 871 222 1.55
0.6 - - - - 678 169 1.47 X 629 155 1.39 6 78 169 1.47 824 228 1.5 8
0.7 - - - - - - - - - - - - - - - - -
0.8
*PG153009041A* - Rise Range: 45° - 75°
Un it
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS CFM WATTS AMPS CFM W ATTS AMPS
0.1 1,065 168 1.42
0.2 1,003 174 1.48
0.3 961 185 1.55
0.4 913 195 1.62
0.5 855 202 1.69
0.6 814 212 1.76
0.7 749 218 1.82
0.8 713 227 1.87
*PG153609041A* - Rise Range: 45° - 75°
Un it
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS CFM WATTS AMPS CFM W ATTS AMPS
0.1 1,065 168 1.42 49 1,255 257 2.10 55 924 120 1.08 1,333 304 2.41 1,418 360 2.92
0.2 1,003 174 1.48 52 1,217 269 2.19 57 863 128 1.14 1,293 314 2.48 1,375 371 3.00
0.3 961 185 1.55 54 1,165 274 2.21 59 812 138 1.24 1,237 321 2.54 1,316 376 3.05
0.4 913 195 1.62 57 1,113 285 2.30 62 745 145 1.27 1,193 333 2.71 1,279 387 3.13
0.5 855 202 1.69 60 1,073 296 2.36 64 702 154 1.35 1,158 341 2.77 1,245 392 3.19
0.6 814 212 1.76 63 1,018 302 2.41 68 643 159 1.37 1,101 345 2.78 1,193 400 3.22
0.7 749 218 1.82 69 991 313 2.4 8 70 601 168 1.44 - - - - - -
0.8 713 227 1.87
T1 - 1st Stage Heating Speed
------- --------- -
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 Cooling Spped T4 - Cooling Speed T5 - Cooling Speed
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed
T2 - 2nd Stage Heating Speed
1,255 257 2.1 0
49
1,217 269 2.1 9
52
1,165 274 2.2 1
54
1,113 285 2.3 0
57
1,073 296 2.3 6
60
1,018 302 2.4 1
63
991 313 2.48
69
-- - -
72
-- - -
72
T3 - Cooling Speed T4 - Cooling Spped T5 - Cooling Spped
55 1,148 170 1.55 1,148 170 1.55 1,333 304 57 1,092 176 1.66 1,092 176 1.66 1,293 314 59 1,044 184 1.72 1,044 184 1.72 1,237 321 62 994 194 1.77 994 194 1.77 1,193 333 64 929 210 1.89 929 210 1.89 1,158 341 68 811 222 1.99 811 222 1.99 1,101 345 70 763 224 2.03 763 224 2.03
715 236 2.07 7 15 236 2.07
T3 - 1st Stage Cooling T4 - 2nd Stage Cooling T5 - Cooling Speed
502 173 1.52 - - -
*PG15[24-36]***41A*
-- -
-- -
-- -
2.41
2.48
2.54
2.71
2.77
2.78
*PG153709041A* - Rise Range: 45° - 75°
Un it
Stati c CFM WATTS AMPS RISE CFM WATTS AMPS RISE CFM WATTS AMPS CFM WATTS AMPS CFM W ATTS AMPS
0.1 1,065 168 1.42
0.2 1,003 174 1.48
0.3 961 185 1.55
0.4 913 195 1.62
0.5 855 202 1.69
0.6 814 212 1.76
0.7 749 218 1.82
0.8 713 227 1.87
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 Cooling Spped T4 Cooling Speed T5 - Cooling Speed
1,255 257 2.1 0
49
1,217 269 2.1 9
52
1,165 274 2.2 1
54
1,113 285 2.3 0
57
1,073 296 2.3 6
60
1,018 302 2.4 1
63
991 313 2.48
69
-- - -
72
55 1,148 170 1.55 1,148 170 1.55 57 1,092 176 1.66 1,092 176 1.66 59 1,044 184 1.72 1,044 184 1.72 62 994 194 1.77 994 194 1.77 64 929 210 1.89 929 210 1.89 68 811 222 1.99 811 222 1.99 70 763 224 2.03 763 224 2.03
715 236 2.07 7 15 236 2.07
1,418 360 2.9 2 1,375 371 3.0 0 1,316 376 3.0 5 1,279 387 3.1 3 1,245 392 3.1 9 1,193 400 3.2 2
-- -
-- -
X = Outside of Temperature Rise Range - Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
12
BLOWER PERFORMANCE DATA
d
*PG154211541A* - Rise Range: 45° -75°
*PG15[42-60]***41A*
Un it
Stati c CFM W ATTS AMPS RISE CFM WATTS AMPS RISE CF M WA TTS AMPS CFM WATTS A MPS CFM WATTS A MPS
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 Cooling Spped T4 Cooling Speed T5 - Cooling Speed
0.1 1,065 168 1.42 49 1,255 257 2.10 55 1,335 260 1.01 1,468 337 1.28 1,619 431 1.64
0.2 1,003 174 1.48 52 1,217 269 2.19 57 1,274 268 1.04 1,412 349 1.33 1,560 445 1.69
0.3 961 185 1.55 54 1,165 274 2.21 59 1,204 281 1.10 1,346 359 1.37 1,504 456 1.71
0.4 913 195 1.62 57 1,113 285 2.30 62 1,136 287 1.11 1,275 363 1.40 1,441 463 1.76
0.5 855 202 1.69
0.6 814 212 1.76
1,073 296 2.36
60
1,018 302 2.41
63
64 1,069 300 1.15 1,221 370 1.44 68 1,009 312 1.19 1,170 386 1.47
1, 380 4 75 1. 80 1, 325 4 89 1. 84
0.7 749 218 1.82 69 991 313 2.48 70 946 319 1.22 1,105 397 1.52 1,268 495 1.88
0.8 713 227 1.87
*PG154811541A* - Rise Range: 45° - 75°
Un it
Stati c CFM W ATTS AMPS RISE CFM WATTS AMPS RISE CF M WA TTS AMPS CFM WATTS A MPS CFM WATTS AMPS
0.1 1140 178 1.52
0.2 1090 188 1.57
0.3 1038 199 1.67
0.4 980 212 1.76
0.5 914 220 1.79
0.6 852 231 1.9
0.7 806 242 1.97
0.8 741 248 2.01
*PG154911541A* - Rise Range: 45° - 75°
Un it
Stati c CFM W ATTS AMPS RISE CFM WATTS AMPS RISE CF M WA TTS AMPS CFM WATTS A MPS CFM WATTS AMPS
0.1 1140 178 1.52
0.2 1090 188 1.57 59 1374 318 2.56 63 1090 188 1.57
0.3 1038 199 1.67 62 1322 327 2.68 65 1038 199 1.67
0.4 980 212 1.76 65 1273 338 2.72 68 980 212 1.76
0.5 914 220 1.79 70 1224 352 2.82 70 914 220 1.79
0.6 852 231 1.9 75 1176 365 2.88 73 852 231 1.9
0.7 806 242 1.97 X 1121 379 2.93 X 806 242 1.97
0.8 741 248 2.01
T1 - 1st Stage Heating Spee
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed
-- - -
72
T2 - 2nd Sta ge H eat ing Spee d
1417 305 2.46
56
1374 318 2.56
59
1322 327 2.68
62
1273 338 2.72
65
1224 352 2.82
70
1176 365 2.88
75
1121 379 2.93
X
1068 391 2.98
X
56
1417 305 2.46
1068 391 2.98
X
886 331 1.27 1,042 406 1.54
T3 - 1st St age Cooling T4 - 2n d Sta ge Cool ing T5 - Coo lin g S ppe d
61 1,140 178 1.52 1,616 436 3.34 1,696 503 4.04 63 1,090 188 1.57 1,573 449 3.46 1,650 517 4.15 65 1,038 199 1.67 1,527 462 3.59 1,608 530 4.25 68 980 212 1.76 1,485 474 3.69 1,566 543 4.39 70 914 220 1.79 1,443 489 3.80 1,523 556 4.43 73 852 231 1.90 1,399 502 3.86 1,480 569 4.55
X8062421.971,3565133.991,441580 4.65 X7412482.011,3075254.05 - - -
T3 - 1st St age Cooling T4 - 2n d Sta ge Cool ing T5 - Co olin g Speed
61
1140 178 1.52
1,468 337 1.28 1,412 349 1.33 1,346 359 1.37 1,275 363 1.40 1,221 370 1.44 1,170 386 1.47 1,105 397 1.52
741 248 2.01
X
1,042 406 1.54
1, 198 5 02 1. 90
1,696 503 4.04 1,650 517 4.15 1,608 530 4.25 1,566 543 4.39 1,523 556 4.43 1,480 569 4.55 1,441 580 4.65
-- -
*PG156014041A* - Rise Range: 45° - 75° High 30° - 60° Lo w
Un it
Stati c CFM W ATTS AMPS RISE CFM WATTS AMPS RISE CF M WA TTS AMPS CFM WATTS A MPS CFM WATTS AMPS
0.1 1773 488 3.64 43 1773 488 3.64 58 1,3 79 246 1.95 1,919 700 4. 81 2,115 783 5.54
0.2 1713 501 3.73 45 1713 501 3.73 61 1,3 22 258 2.03 1,862 714 4. 94 2,078 787 5.57
0.3 1693 509 3.78 45 1693 509 3.78 61 1,2 68 266 2.10 1,810 720 5. 01 2,009 802 5.67
0.4 1653 518 3.84 46 1653 518 3.84 63 1,1 87 280 2.19 1,755 734 5. 07 1,953 813 5.87
0.5 1597 529 3.91 48 1597 529 3.91 65 1,1 33 287 2.23 1,705 743 5. 09 1,933 805 5.77
0.6 1534 541 3.99 50 1534 541 3.99 68 1,0 68 294 2.29 1,647 748 5. 16 - - -
0.7 1485 552 4.09 52 1485 552 4.09 70 1,0 26 307 2.38 - - - - - -
0.8 - - -
T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed
-- - -
-
T3 - 1st St age Cooling T4 - 2n d Sta ge Cool ing T5 - Co olin g Speed
-- - - - - - - -
X = Outside of Temperature Rise Range - Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.
13