•Refer to Service Manual RS6300007 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
•Select Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
®
C
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult
a tax professional if they have questions about the applicability of these credits.
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
2
HIGH VOLTAGE!
WARNING
WARNING
dividuals meeting (at a minimum) the requirements of an
"entry level technician" as specified by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). Attempting to install or repair this unit without such background
may result in product damage, personal injury or death.
Installation and repair of this unit
should be performed ONLY by in-
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
APG152407041A*
APG153009041A*
APG153609041A*
APG153709041A*
APG154209041A*
APG154811541A*
APG154911541A*
APG156014041A*
* Indicates minor revision & is not used for order entry or inventory management
GPG152407041A*
GPG153009041A*
GPG153609041A*
GPG153709041A*
GPG154209041A*
GPG154811541A*
GPG154911541A*
GPG156014041A*
The models listed below qualify
for the 2009 and 2010 Federal Tax Credits
for Energy Efficiency**
APG152407041A*
APG153007041A*
APG153709041A*
APG154209041A*
APG154911541A*
GPG152407041A*
GPG153007041A*
GPG153709041A*
GPG154209041A*
GPG154911541A*
**Note that these tax credits are subject to specific requirements set
forth in the American Recovery and Reinvestment Act of 2009 and
in the Internal Revenue Code. Goodman recommends that consumers consult a tax professional if they have questions about the
applicability of these credits.
WARNING
WARNING
WARNING
WARNING
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
PRODUCT DESIGN
*PG15 Package Gas Units are designed for outdoor installations only in either residential or light commercial applications and are available in 2, 2-1/2, 3, 3-1/2, 4 & 5 ton sizes.
They are designed for 208/230 volt single phase applications.
The connecting ductwork (Supply and Return) can be connected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible location within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Section. Under no circumstances should the unit be operated
without return air filters.
A 3/4" pipe is provided for removal of condensate water from
the indoor coil. (Do not reduce the drain line size).
Refrigerant flow control is achieved by use of a TXV or orifice.
*PG15 units use the FasTest Access Fitting System which
consists of a saddle that is either soldered to the suction and
liquid lines or is fastened with a locking nut to the access
fitting box (core) and then screwed into the saddle. NOTE:
The core must not be removed from the saddle until
the refrigerant charge has been removed. Failure to do
so could result in property damage or personal injury.
The single phase units use permanent split capacitors (PSC)
design compressors. Starting components are therefore not
required. A low MFD run capacitor assists the compressor
to start and remains in the circuit during operation.
The *PG15*****41AA models are equipped with X-13 blower
motors. X-13 motors are constant torque motors with very
low power consumption and are energized by a 24V signal
from the ignition control board. The X-13 features an integrated control module.
Air for condensing (cooling cycle) is drawn through the outdoor coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
The *PG15 series package units use the Compliant Scroll
compressor; there are a number of design characteristics
which are different from the traditional reciprocating compressor.
- Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant. NOTE: Even though the compressor section of a Scroll compressor is more tolerant of
liquid refrigerant, continued flood back or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure.
- These Scroll compressors use "POE" orpolyolester oil which
is NOT compatible with mineral oilbased lubricants like 3GS.
"POE" oil must be used if additional oil is required.
- Compliant scroll compressors perform “quiet” shutdowns
that allow the compressor to restart immediately without the
need for a time delay. This compressor will restart even if the
system has not equalized.
- Operating pressures and amp draws may differ from standard reciprocating compressors. This information may be
found in the “Cooling Performance Data” section.
Some other models of the *PG15 series package units use a
2 stage scroll compressor. The basic scroll design has been
modified with the addition of an internal unloading mechanism that opens a by-pass port in the first compression
pocket, effectively reducing the displacement of the scroll.
The opening and closing of the by-pass port is controlled by
an internal electrically operated solenoid.
The ZPS modulated scroll uses a single step of unloading
to go from full capacity to approximately 67% capacity. A
single speed, high efficiency motor continues to run while
the scroll modulates between the two capacity steps.
4
PRODUCT DESIGN
Location and Clearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
48" MIN
2" MIN
36" MIN
(FOR
SERVICE)
.
12" MIN
Outside Slab Installation
NOTE: Ro of overha ng should be n o more than 36 " and provi-
sions made to deflect the warm discharge air out from the
overhang. Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency.
3"
MIN
(FOR SERVICE)
36" MIN
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top installations) the installer must provide service platform for service person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
National Fuel Gas Code ANSIZ223.1.
NOTE: Unit can als o use roof c urb (and pla tform for l eveling,
where necessary) to utilize bottom discharge.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE IS
USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
IMPORTANT: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing
the unit.
Refer to Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.
Rooftop Installation
5
PRODUCT DESIGN
High Altitude Derate - U.S. Installations Only
IMPORTANT NOTE: The gas/electric units naturally derate
with altitude. Do not attempt to increase the firing rate by
changing orifices or increasing the manifold pressure. This
can cause poor combustion and equipment failure. At all
altitudes, the manifold pressure must be within 0.3 inches
W.C. of that listed on the nameplate for the fuel used. At all
altitudes and with either fuel, the air temperature rise must
be within the range listed on the unit nameplate. Refer to the
Installation Manual provided with the LP kit for conversion
from natural gas to propane gas and for altitude adjustments.
When this package unit is installed at high altitude, the appropriate High Altitude orifice kit must be installed. As alti-
NATURAL GAS AND LP GAS INSTALLATIONS AT ALTITUDES > 2000 FT
tude increases, there is a natural reduction in the density of
both the gas fuel and combustion air. This kit will provide the
proper design certified input rate within the specified altitude
range. High altitude kits are not approved for use in Canada.
For installations above 2,000 feet, use kit HA-02. The HA-02
kit is used for both Natural and LP gas at high altitudes.
Use LPM-06 propane conversion kit for propane conversions
at altitudes below 2000 feet. Natural gas installations below
2000 feet do not require a kit.
For propane conversions above 2000 feet, high altitude kit
HA-02 is required in addtion to LPM-05 propane conversion
kit.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
20003000400045005000600070008000
U.S. BURNER ORIFICE45/55 47/55 47/56-47/56 48/57 48/58 49/58
HA02
CANADA BURNER ORIFICE45/55--48/57----
22,500 BTUH NAT/20,OOO BTUH/L.P.
20,000 BTUH NAT/20,OOO BTUH/L.P.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
20003000400045005000600070008000
U.S. BURNER ORIFICE44/55 44/55 45/56-45/56 46/57 47/58 47/58
HA02
CANADA BURNER ORIFICE44/55--47/57----
25,000 BTUH NAT/20,OOO BTUH/L.P.
INPUT/BURNER
HIGH ALTITUDE
KIT
ELEVATION ABOVE SEA-LEVEL (FEET)
20003000400045005000600070008000
U.S. BURNER ORIFICE43/55 43/55 44/56-44/56 44/56 45/57 45/57
SP ECI F IC AT I ONMINIMUM CIRCUIT AMPACITY22.12126.524.2
HEATI NGNUMBER OF BURNERS3444
SE CT I ONORIF ICE SIZE NATURAL43434343
COMPR ESSO RTYPEScr ollScr ollScro llScrol l
RATED LOAD AMPS13.514.116.716.7
COND ENSER HORSEPOWER1/61/41/41/4
FAN MO TORRPM8158301075830
COND ENSERBLADE DIAMETER (INCHES)2222222 2
FANNUMBER OF BLADES3333
COND ENSERFA CE AREA - SQ. FT.12.312 .312. 312.3
COI LNUMBER OF ROWS1212
EV APO RAT O RHORSEPOWER - NO. OF SPEEDS1/2 - X-131/2 - X-131/2 - X-131/2 - X-13
BLOW ERFULL LOAD AMPS4.11 .864. 11 .86
MOT ORLOCKED ROTOR AMPSN/AN/AN/AN/A
EV APO RAT O RDIAMETER X WIDTH (INCHES)10 x 810 x 910 x 910 x 9
BLOW ERRAT ED SCFM COOLING8451050800 / 12251050
EV APO RAT O RFAC E AREA - SQ. FT.4.334 .334.334.33
COI LNUMBER OF ROWS2344
HEATI NGPRIMARY LIMIT SETTING (°F)160160160160
LIMITSAUXILIARY LIMIT SETTING (°F)1501501501 50
GENERALEXPANSION DEVICETXV0.065TXVTXV
IN FORM ATIO NREFRIGERANT CHARGE R-410A (Oz.)8110299112
MAXIMUM OVERCURRENT PROTECTION
ORIFICE SIZE LP55555555
LOCKED ROTOR AMPS58.3738279
FULL L OA D AMPS1. 101. 51.41.5
LOCKED ROTOR AMPS1.73.02.93.0
CFM2400270027002700
FIN S PE R INCH2216221 6
MOTOR SPEED TAP - COOLINGT4T3, T4T3, T4T3, T4
RPM / AMPS 724 / 1.21960 / 3.06
MAX EXTERNAL STATIC PRESS ("w.c.)0.50. 50.50.5
FIN S PE R INCH1414141 4
FIL TER SI ZE - S Q. FT.
DRAIN SIZE (INCHES)3/43/43/43/4
ROLLOUT LIMIT SETTING (°F)300300300300
POWER SUPPLY ENTRANCE SIZE (INCHES)1 1/81 1/81 1/81 1 /8
LOW VOLTAGE ENTRANCE SIZE (INCHES)7/87/87/87/8
SHIPPING WEIGHT LBS.439475480480
OPERATING WEIG HT LBS.41745345845 8
(2)
(3)
30354040
2.74.24.24.2
*PG15[24-37]***41AA
640 / 0 .98
960 / 3 .06
960 / 3.06
(1) Units installed in Canada are cer tif ed only to 4 500 fee t.
(2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only.
(3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
MAX EX TE RN AL STATI C PRE SS ("w.c. )0 .50.50.50. 5
FACE AREA - SQ. FT.5.675.675.675.67
NUM BER OF ROW S4444
FINS PER INCH14141414
FILTER SIZE - SQ. FT.
DRAI N SIZE (INCHES )3/ 43/43/43/ 4
PR IMA RY L IM IT SE TTI NG (° F)1701 701 7016 0
AU XIL IA RY LIM IT S ETT ING (°F )1 501 501 5015 0
ROL LOUT LIM IT SET T ING (°F)3003003 00300
EX PAN SI ON DEVIC E0. 072T XVTX VT XV
REFRIG ERANT CHARGE R- 410 A ( Oz .)1621 69167177
POW E R S UPP L Y EN TR ANC E SI ZE (IN CH ES )1 1/ 81 1/ 81 1 /81 1 /8
LOW VO LT AGE E NTR ANC E SIZE (I NC HES )7/ 87/87/ 87 /8
SH IPP ING W EI GHT LB S.5 6056056056 5
OPERATING WEIGHT LBS.538538538543
(2)
(3)
405 05060
647 / 1.66
890 / 3 .8
5.15.15.16.3
*PG15[42-60]***41AA
890 / 3.8
778 / 1.98
1030 / 5.7
(1) Units installed in Canada are cer tif ed only to 4 500 fee t.
(2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only.
(3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
9
PACKAGE GAS SPECIFICATIONS
S
*PG15360 9041AB * PG154811541AB *P G156014041AB
COOLINGCOOLING CAP ACI TY, BT UH
CAPACITYHIGH STAGE35,40 04 7,50056,500
LOW STAG E2 4,40 03 5,0 0041, 000
SEER/EER15.0 / 11.015.0 / 11.014.0 / 10.1
HEATINGBTUH INPUT (US) HIGH FIRE92,000115,000138,000
CAPACITYOUTPUT (US) HIGH FIRE (Natural Gas)73,50092,000110,200
OUTPUT (US) HIGH FIRE (LP)69,00083,00099,000
BTUH INPUT (US) LOW FIRE69,00086,000103,500
OUPUT (US) LOW FIRE (Natural)55,00069,00083,000
OUTPUT (US) LOW FIRE (LP)5 0,00062,00074,000
A.F.U.E.808080
RATE D E XTERN AL STA TIC (" w.c. )0.500.5 00.50
TEMPERA TURE RISE (°F)45-754 5-7545-75
PRESSURE SWITCH TRIP POINT (" w .c.)-.33"-.33"-.33"
SPEC IFI CATI ON MIN IMUM CI RC UIT AMPACI TY26 .534. 842.1
MAXIMU M OVE RCU RREN T PRO TECTIO N
HEATINGNU MBE R O F B URN ERS456
SEC TIO NORIFICE SIZE NATURAL434343
ORIFICE SIZE LP555555
COMPR ESSOR
RA TE D L OA D A MPS16 .721. 225.8
CONDENSER HORSEPO WER1/41 /41/4
FAN MOTORRPM8301075107 5
CONDENSERBLADE DIAMETER (INCHES)222222
FANNUMBER OF BLADES333
CONDENSERFACE AREA - SQ . FT.12.315.31 5.3
COILNU MBE R O F RO W S122
EVAP ORAT O R
BLOWE RFULL LOAD AMPS4.167.6
MOTO RLOCKED ROTOR AMPSN/AN/AN/A
EVAP ORAT O R DIAMETE R X WIDT H (INCHES )10 x 911 x 101 1 x 10
BLOWE RRATED S CF M CO OL ING800 / 122 51100 / 151 01300 / 1 810
EVAP ORAT O R FACE A REA - SQ. F T.4.335.675. 67
COILNU MBE R O F RO W S444
HEATINGPRIMARY LIMIT SETTING (°F)160170160
LIMITSAUXILIARY LIMIT SETTING (°F)150150150
GENERALEXPANSION DEVICETXVTXVTXV
IN FO RM ATI ON REFR IGERANT CH ARG E R -410A (Oz .)10217218 0
TYPEScrollScr ollScrol l
LOCKED ROTOR AMPS8296118
FULL LOAD AMPS1.51 .41.4
LOCKED ROTOR AMPS3.05.25.2
CFM270035003500
FINS PER INCH221616
HOR SEPO W ER - N O. OF SPE EDS1/ 2 - X- 133/4 - X -131 - X -13
MOT OR SPEED TAP - COOLI NGT3, T4T3, T4T3,T 4
RPM / A MPS
MAX E XTER NAL STA TIC PRESS (" w.c.)0.50.50 .5
FINS PER INCH141414
FILTER SIZE - SQ. FT .
DRAIN SIZE ( INCHE S)3/43/ 43 /4
ROL LOU T LI MI T SET TING (°F )300300300
POWER SUPPLY ENTRANCE SIZE (INCHE
LOW VOLTAGE ENTRANCE SIZE (INCHES)7/87/87/8
SHIPPING WEIGHT LBS.480560565
OPERATING WEIGHT LBS.458538543
(2)
(3)
*PG15[36-60]***41AB
405060
640 / 0.98
960 / 3.06
4.25 .16.3
1 1/81 1/81 1/8
647 / 1. 66
890 / 3.8
778 / 1.98
1030 / 5.7
(1) Units installed in Canada are cer tif ed only to 4 500 fee t.
(2) Calcula ted extern al filter size based on air velocity of 300 ft/min . and app lies to dis pos abl e fi lte rs only.
(3) Maximum Ove rcu rre nt Protec tio n Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
10
ACCESSORIES
ACCESSOR IES
Part NumberDescription
LPM-06Propane Conversion Kit
HA-02High Altitude Kit
PGC101/10 2/103Roof Curb
PGED101/102Downflow Economizer, Smal l and Medium Chassis
PGED103Downflow Ec onomi zer, Larg e Cha ssis
PGEH101/102Hor izon tal Economizer, Smal l and Medium Chassis
PGEH103Horizon tal Ec onomizer, Large Chassis
PGMDD101/102Manual 25% Fresh Air Damper Downfl ow Appli cation, Sma ll and Medium Chas sis
PGMDD103Manual 25% Fresh Air Damper Downfl ow Appli cation, Large Chas sis
PGMDH101Manual 25% Fresh Air Damper Horizontal Application, Small Chassis
PGMDH102Manual 25% Fresh Air Damper Horizontal Application, Medi um Chass is
PGMDH103Manual 25% Fresh Air Damper Hori zontal Appl ic ation, Large Chassis
PGMDMD101/102Motor iz ed 25% Fresh Air Damper Downflow Applicati on,Sma ll a nd Medium Chassis
PGMDMD103Motorized 25% Fresh Air Downflow Appl ication, La rge Chassis
PGMDMH101Motorized 25% Fresh Air Damper Horizontal Application, Small Chassis
PGMDMH102Motorized 25% Fresh Air Damper Hori zontal Appl ic ation, Medi um Chassis
PGMDMH103Motorized 25% Fresh Air Damper Hori zontal Appl ic ation, Large Chassis
SQRPG101/102Squa re to Round Adapter w/ 16" Round Downflow Appl ica tion, Sm all and Medium Chas si s
SQRPG103Squa re to Round Adapter w/ 18" Ro und Downfl ow Appl ica tion, Large Chas si s
SQRPGH101/102Squa re to Round Adapter w/ 16" Round Horizontal Appl ic ation, S mall and Mediu m Chass is
SQRPGH103Square to Round Adapter w/ 18" Round Horizontal Appl ication, La rge Chassis
PGFR101/102/103Internal Filter Rack All Chassis
GPGHFR101-103
CDK36Flush Mount Concentric Duct Kit
CDK36515Flush Mount Concentric Duct Kit w/ Filter
CDK36530Step Down Concentric Duct Kit
CDK36535Step Down Concentric Duct Kit w/ Filter
CDK4872Flush Mount Concentric Duct Kit
External Horizontal Filter Rac k for Goo dman/Amana Gas/E lectric
& Multi-posi tion Package Units Al l Chas sis
CDK4872515Flush Mount Concentric Duct Kit w/ Filter
CDK4872530Step Down Concentric Duct Kit
CDK4872535Step Down Concentric Duct Kit w/ Filter
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
11
BLOWER PERFORMANCE DATA
*PG15240701A * - Rise Range: 35° - 65°
Un it
Stati cCFMWATTS AMPSRISECFM WATTS AMPSRISECFM WATTS AMPSCFM WATTS AMPSCFM W ATTSAMPS
X = Outside of Temperature Rise Range - Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.5" w.c.
12
BLOWER PERFORMANCE DATA
d
*PG154211541A* - Rise Range: 45° -75°
*PG15[42-60]***41A*
Un it
Stati cCFM W ATTS AMPSRISECFMWATTS AMPSRISECF M WA TTS AMPSCFM WATTS A MPSCFM WATTSA MPS
T3 - 1st St age Cooling T4 - 2n d Sta ge Cool ing T5 - Co olin g Speed
-- - - - - - - -
X = Outside of Temperature Rise Range - Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.5" w.c.
13