This Forced Air Central Unit Design Complies With
Requirements Embodied in The American National
Standard / National Standard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central Furnaces
This manual is to be used by qualified, professionally trained HVAC technicians
only. Goodman does not assume any responsibility for property damage or
personal injury due to improper service procedures or services performed by
an unqualified person.
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,
that during its lifetime a product may require service. Products should be serviced only by a qualified service technician
who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing
instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
This unit should not be connected to, or used in conjunction with, any devices that are not design certified for use with
this unit or have not been tested and approved by Goodman. Serious property damage or personal injury, reduced unit
performance and/or hazardous conditions may result from the use of devices that have not been approved or certified by
Goodman.
WARNING
Do not store com bustible materials or use gasoline
or other flammable liquids or vapors in the vicinity
of this appliance as property damage or personal
injury could occur. Have your contractor point out
and identify the various cut-off devices, switches,
etc., that serves your co mfort equipment.
WARNING
Goodman will not be responsible for any injury or property damage arising from improper service or service
procedures. If you perform service on your own product, you assum e responsibility for any personal injury or property
dam age wh ich ma y result.
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple power sources
may be present. Failure to do so may cause property damage, personal injury or death.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this
product. For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE 1-877-254-4729 (U.S. only)
email us at: hac.consumer.affairs@goodmanmfg.com
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500
(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
2
email us at: hac.consumer.affairs@amanahvac.com
Your telephone company will bill you for the call.
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE 1-877-254-4729 (U.S. only)
fax us at: (931) 438-4362
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-931-433-6101.
(Not a technical assistance line for dealers.)
Page 3
IMPORTANT INFORMATION
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:
•
Never purge refrigerant into an enclosed room or
space. By law, all refrigerants must be reclaimed.
•
If an indoor leak is suspected, thoroughly ventilate
the area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible
frostbite or blindness, avoid contact with refrigerant
and wear gloves and goggles. If liquid refrigerant
does contact your skin or eyes, seek medical help
immediately.
• Always follow EPA regulations. Never burn refrig erant, as poisonous gas will be produced.
WARNING
To avoid possible injury, explosion or death, practice
safe handling of re frige rants.
WARNING
The compressor POE oil for R-410A units is
extremely susceptible to moisture absorption and
could cause compressor failure. Do not leave system
open to atmosphere any longer than necessary
for installation.
WARNING
To avoid pos sible exp los ion:
•
Never apply flame or steam to a refrigerant cylinder.
If you must heat a cylinder for faster charging,
partially immers e it in wa rm w ate r.
•
Never fill a cylin de r m ore than 80% fu ll of liqu id
refrigerant.
• Never add anything other than R-22 to an R-22 cylinder
or R-410A to an R-410A cylinder. The service equipment
used must be listed or certified for the type of
refrigerant used.
• Store cylinders in a cool, dry place. Never use a
cylinder as a plat form or a roller.
WARNING
To avoid possible explos ion, use only returnable (not
disposable) service cylinders when removing refrigerant f rom a syst em.
• Ensure the cylinder is free of damage which could
lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed
5 years.
• Ensure the pressure rating meets or exceeds 400
lbs.
When in doubt, do not use cylinder.
WARNING
System contamina nts, improper se rvice procedure
and/or physical abuse affecting hermetic com pressor
electrical terminals may cause dangerous s ystem
venting.
The successful development of hermetically sealed refrigeration compressors has completely sealed the compressor's
moving parts and electric motor inside a common housing,
minimizing refrigerant leaks and the hazards sometimes
associated with moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is a
method whereby electrical current is transmitted to the
compressor motor through terminal conductors which pass
through the compressor housing wall. These terminals are
sealed in a dielectric material which insulates them from the
housing and maintains the pressure tight integrity of the
hermetic compressor. The terminals and their dielectric
embedment are strongly constructed, but are vulnerable to
careless compressor installation or maintenance procedures and equally vulnerable to internal electrical short
circuits caused by excessive system contaminants.
In either of these instances, an electrical short between the
terminal and the compressor housing may result in the loss
of integrity between the terminal and its dielectric embedment. This loss may cause the terminals to be expelled,
thereby venting the vaporous and liquid contents of the
compressor housing and system.
A venting compressor terminal normally presents no danger
to anyone, providing the terminal protective cover is properly
in place.
If, however, the terminal protective cover is not properly in
place, a venting terminal may discharge a combination of
(a ) hot lubricating oil and refrigerant
(b ) flammable mixture (if system is contaminated
with air)
in a stream of spray which may be dangerous to anyone in the
vicinity. Death or serious bodily injury could occur.
Under no circumstances is a hermetic compressor to be
electrically energized and/or operated without having the
terminal protective cover properly in place.
See Service Section S-17 for proper servicing.
3
Page 4
PRODUCT IDENTIFICATION
A
The model number is used for positive identification of component parts used in manufacturing. Please use this number when
requesting service or parts information.
mana® Brand/Goodma n® B r a nd Package Gas up to 13 Seer R410A
A
ga s/electric unit. Init ial r elease.
A
mana® Brand/Goodma n® B r a nd Package Gas up to 13 Seer R410A
ga s/electric unit. Re lease of models with Hone y well V alve.
Thr e e Phase Pa ck age Gas Units
G
oodman® Brand Package Gas up to 13 Seer R410A gas /electric unit. 208-
23 0/3/ 60. Init ial re lease.
oodman® Brand Package Gas up to 13 Seer R410A gas /electric unit. 208-
G
23 0/3/ 60. Rele as e of models wit h Honeywell Valve.
These units have R410A refrigerant
4
Page 5
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when
requesting service or parts information.
mana® Brand/Goodma n® B r a nd Package Gas up to 15 Seer R410a
A
ga s/electric units. Initial release.
A
mana® Brand/Goodma n® B r a nd Package Gas up to 15 Seer R410a
ga s/electric units. Sound impr ovements. Change con denser m otor and blade.
mana® Brand/Goodma n® B r a nd Package Gas up to 15 Seer R410a
A
ga s/electric units. In it ial r elease of 8 models that w ill co mplete 2009 Tax
Reb ate li neup.
These units have R410A refrigerant
5
Page 6
ACCESSORIES
ACCESSORIES
Part Nu mberDescription
LPT-03
LPM-05Propane Conversion Kit (*PG15)
HA-02High Altitud e Kit
PGC101/102/103Roof Curb
PG ED101/102Downflow Economizer, Small and Medium Chassis
PGED103Downflow Economizer, Larg e Chassis
PGEH101/102Hori zontal Economizer, Small and Medium Chassis
PGEH103Horizontal Economizer, Large Chassis
PGM DD101 /10 2Manual 25% Fresh Air Damper Downflow Application, Smal l and Medium Chassis
PGM DD103Manual 25% Fresh Air Damper Downflow Application, Large Chassis
PGM DH101Manual 25% Fresh Air Damper Horizontal Application, Small Chassis
PGM DH102Manual 25% Fresh Air Damper Horizontal Application, Medium Chassis
PG MDH103Manual 25% Fresh Air Damper Horizontal Application, Large Chassis
PG MDMD101/102Motorized 25% Fresh Air Damper Downflow Application,Small and Medium Chassis
PGM DM D10 3Motorized 25% Fresh Air Downflow Application, Large Chassis
Propane Conversion Kit (*PG13) (LPT-00A may be used on models with AA revisions)
LPT-03 can be used with either White-Rodgers or Honeywell gas valve.
PGM DM H101Motorized 25% Fresh Air Damper Horizontal Application, Small Chassis
PGMDMH102Motorized 25% Fresh Air Damper Horizontal Application, Medium Chassis
PG MDMH103Motorized 25% Fresh Air Damper Horizontal Application, Large Chassis
SQRPG101/102Square to Round Adapter w/ 16" Round Downflow Application, Small and Medium Chassis
SQRPG103Squar e to Round Adapter w/ 18" Round Downflow Application, Large Chassis
SQ RPGH101/102Square to Round Adapter w/ 16" Round Horizontal Application, Small and M e dium Chassis
SQRPGH103Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis
PGFR101/102/103Internal Filter Rack All Chassis
GP GHFR101-103
CDK36Flush Moun t Co ncentr ic Du ct Kit
CDK36515Flush Mount Concentric Duct Kit w/ Filter
CDK36530Step Down Concentric Duct Kit
CDK36535Step Down Concentric Duct Kit w/ Filter
CDK4872Flush Moun t Co ncentr ic Du ct Kit
CDK4872515Flush Mount Conc entric Duct Kit w/ Fi lter
External Horizontal Filter Rack for Goodman/Amana Gas/Electr ic
& Multi-position Package Units All Chassis
CD K4872530Step Down Concentric Duct Kit
CDK4872535Step Down Concentric Duct Kit w/ Filter
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
6
Page 7
LIGHTING INSTRUCTIONS*PG13**M*AA
FOR YOUR SAFETY RE A D BEFORE OPER ATING
If you do not follow these instructions exactly,
a fire or explos ion may result caus i ng property
damage , perso nal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burners. Do n
try to l i gh t th e bur n e rs by han d .
B. BEFORE OPERATING smell around
the ap plia n ce area for gas . Be sure to
smel l ne xt t o the floor becau se s o me ga s
is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch;
do not use any tel ephone in your
building.
Immed iately call your supplier
from a neighbor’s phone. Follow
the gas suppliers instructions.
ot
If you cannot reach your gas supplier,
cal l the fire de p a r tm ent.
C. Use only your hand to move the gas
control switch or kno b. Never use
tools. If the gas control switch or knob
will not oper ate, don’t try to repa ir it,
call a qualified service technician.
Force or att empted repair may resul t in
a fire or explosion.
D. Do not use this appliance if any part
has been under water. Imme diately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been und er water.
OP ERATING I NST RUCTIONS
1. S TOP! Read the safety information
above on this label.
2. Set the therm ostat to l owest setting.
3. Turn off all electric power to the
appliance.
4. This appliance is equipped with an
automatic ignition system which
automatically lights the burners. Do n
try to l i gh t th e burners by ha nd .
5. Remove control access panel.
6. Move the g as control switch or knob
to "OFF".
GAS CONTROL
SWITCH SHOWN
IN "ON" POSITION
GAS CONTROL
KNOB
ot
7. Wait five (5) minutes to clear out any
gas. If you then sme ll gas, STOP!
Follow "B" in the safety information
above on this la be l. If you don’t smell
gas, go to th e ne xt step.
8. Move the gas cont rol switch or knob
to "ON".
9. Replace control access panel.
10. Turn on all electric power to the
appliance.
11. Set the thermostat to the desired
setting.
12. If the appliance will not operate,
follow the instructions "To Turn Off Gas
T o Appliance" and call your service
technician or gas supplier.
GAS
CONTROL
SWITCH
SHOWN
IN "ON "
POSITION
TO TURN OFF GA S TO APPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the
appliance if service is to be performed.
3. Remove cont ro l access panel.
4. Move the gas control switch or knob
to "OFF". Do not force.
5. Replace control access panel.
WARNING:
alteration, service or
maintenance can
cause injury or
property damage.
Refer to the user’s
information manual
provided with this
consult a qualified
or the gas supplier.
This furnace must be
instructions and local
codes. In the absence
of local codes, follow
the National Fuel Gas
Co de , ANSI Z2 23.1 .
Fo r ou td oo r
installation only.
WARNING:
install ed, operated
and maintained in
accordance with the
manufacturer’s
ins t ructions , thi s
product could ex po se
you to substances
in fuel combustion
which can cause
death or serious
illness and which
are kno wn to the
St at e o f Ca l ifo r ni a to
cause cancer, birth
defects or other
reproduc tive harm.
This product contains
fiberglas s insulation.
Fiberglass insulation
contains a chemical
California to cause
cancer .
Improper
If not
FOR Y O UR S AFETY
other flamm able v a pors and liquids in the v ic inity of this
or any other appliance.
Do not store or use gas o line o r
B14933-239
7
Page 8
LIGHTING INSTRUCTIONS*PG13**M*AB
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly,
a fire or explosion may result causing pro p e r ty
dam age, pers onal injury or loss of li fe.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burners. Do not
try to light the burners by h and.
B. BEFORE OPERATING smell around
the appliance area for gas. Be sure to
smell next to the floor because some gas
is heavier than air and will settle on the
floor.
WHA T TO DO IF YOU SMELL GAS
Do not try to ligh t any appliance.
Do not touch any elect r ic swi t ch;
do not use any telephone in your
building.
Immediately call your supplier
from a neighbor's phone. Follow
the gas suppliers instructions .
If you cannot reach your gas supplie r,
call the fire department.
C. Use only your hand to mov e the gas
control switch or knob. Nev e r use
tools. If the gas control switch or knob
will not operate, don't try to repair it,
call a qualified service technician.
Force or attempted repair may result in
a fire or explosion.
D. Do not use this appli an c e if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
OPE RATING INSTRUCTIONS
1. ST OP! Read the safety information
above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the
appliance.
4. This appliance is equipped with an
automatic ignition system which
automatically l ight s the burne rs. Do not
try to light the burners by hand.
5. Remove cont rol access panel.
6. Move the gas control switch or knob
to "OFF".
GAS CONTROL
SWITCH SHOWN
IN "ON" POSITION
7. Wait five (5) minutes to clear out any
gas. If you then smell gas, STOP!
Follow "B" in the safety information
above on this label. If you don't smell
gas, go to the next step .
8. Move the gas control switch or knob
to "ON".
9. Replace control access p anel.
10. Turn on all elect ric power to the
appliance.
11. Set the therm o stat to the desired
setting.
12. If the a ppliance will not operate,
follow the instruction s "To Turn Off Gas
To Appliance" and call your service
technician or gas supplier.
TO TURN OFF GAS TO A PPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn o ff all electric power to the
appliance if service is to be performed.
3. Remove control access panel.
4. Move the gas control switch or knob
to "OFF". Do not force.
5. Replace control access panel.
WARNING :
alteration, service or
maintenance can
cause injury or
property damage.
Refer to the user's
infor mation ma nual
provided with this
consu lt a qu alified
or the gas supplier.
This furnace must be
instructions and local
codes. In the absence
of local codes, follow
the National Fuel Gas
Code , ANSI Z22 3.1.
WARNING :
installed, operated
and maintained in
accordance with the
manufacturer's
inst r uctions, thi s
product could expose
you to subst ances
in fu el combustion
which can cause
death or serious
illness and which
are known to the
State of California to
cause cancer, birth
defects or other
repr oductive harm.
This product contains
fiberglass insulation.
Fiberg lass insu la tion
cont ains a chemical
California to cause
cancer.
Improper
If not
FOR YOUR SAFETY
other fla mmable vapors and liquids in the v icinity of this
or any other appliance.
8
Do not store or use gasoline or
0140F00688 Rev A
Page 9
LIGHTING INSTRUCTIONS*PG15
G
A
I
N
L
R
A
R
I
D
U
O
R
B
T
E
I
N
A G
A
Z
O
E
P
U
A
M
E
N
L
,
"
O
N
/
M
S
E
T
E
E
V
Z
G
A
M
A
N
U
A
L
E
V
E
R
I
"
N
O
A
G
A
L
S
S
H
O
W
N
P
N
"
O
S
S
N
R
C
H
E
"
9
Page 10
ACCESSORIES
ROOF CURBS
B
A
R
S
C
1 5/8
14 1/2
1 3/8
MODELABCRETURNSUPPLY
PGC101/102/10346 1/439 3/814 1/212 1/2 x 23 15 x 22 1/2
DOWNFLOW FILTER RACK
(PGFR101/102/103)
25
1 1/2
2
3
26 1/2
Filter Size: 14" x 25" x 2"
Measurement in inches.
14
NOTE: PGFR cannot be used with downflow economizers.
10
Page 11
ACCESSORIES
16 X 20 x 2”
FILTER
+
16 X 20
MIST ELIMINATOR
PGED103
(DOWNFLOW ECONOMIZER)
PGED103
A B
16 18
A
14 X 25 FILTER ATTACHMENT
25
B
ECONOMIZER
(HORIZONTAL APPLICATIONS)
B
18
A
E
C
MODELABCDEFILTER
PG E H101/10225 1/418 1/81813 3/416 1/816 x 25 x 1
PG E H10335 1/418 1/81818 1/416 1/816 x 25 x 1
16 1/8
D
Measurement in inches.
11
Page 12
ACCESSORIES
MOTORIZED/MANUAL FRESH AIR DAMPERS -
(HORIZONTAL APPLICATIONS)
B
7 5/8
5 3/4
A
MANUAL
MODELAB
PGM DH10126 1/2 29 3/4
PGM DH10231 1/2 29 3/4
PGMDH1033029 3/4
MOTORIZED
MODELAB
PGMDMH101 26 1/2 29 3/4
PGMDMH102 31 1/2 29 3/4
PG M D MH 103 3 02 9 3/4
MOTORIZED/MANUAL FRESH AIR DAMPERS
B
(DOWNFLOW APPLICATIONS)
12 1/8
10
1
PGMDD103
6
BOTTOM VIEW
A
11 7/8
5 3/4
B
A
11 7/8
A
12
BOTTOM VIEW
12 1/8
10
1
PGMDD101/102
6
5 3/4
A
11 7/8
B
MANUAL
MODELAB
PGMDD101/1021616
PGMDD1031816
MOTORIZED
MODELAB
B
PGMDMD101/1021616
PGMDMD103181 6
Page 13
ACCESSORIES
A
SQUARE TO ROUND CONVERTER
(DOWNFLOW APPLICATIONS)
12 1/414 3/4
C
D
S
R
B
MODELABCDRETURNSUPPLY
SQRPG101/10222 3/412 1/422 1/414 3/41616
SQRPG10322 3/412 1/422 1/414 3/41818
22 3/422 1/4
22 3/422 1/4
16 ø16 ø
12 1/414 3/4
18 ø18 ø
SQUARE TO ROUND CONVERTER
(HORIZONTAL APPLICATIONS)
B
C
A
MODELABC
SQRPG101/1021616 1/216 1/2
SQRPG1031818 1/218 1/2
Measurements are in inches.
13
Page 14
ACCESSORIES
GPGHFR101-103
(EXTERNAL HORIZONTAL FILTER RACK)
16” x 25" x 2" FILTER
14
Page 15
PRODUCT DESIGN
Locations and Clearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top
installations) the installer must provide a service platform for
the service person with rails or guards in accordance with
local codes or ordinances or in their absence with the latest
edition of the National Fuel Gas Code ANSI Z223.1.
IMPORTANT NOTE: If using bottom discharge with roof
curb, ductwork should be attached to the curb prior to
installing the unit.
Refer to Roof curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower
than supply air end.
NOTE: Roof overhang should be no more than 36".
Minimum clearances are required to avoid air recirculation
and keep the unit operating at peak efficiency. A minimum
12 inch clearance is required to the condenser coil.
NOTE: The flue outlet hood is packaged separately inside
the unit and must be installed prior to operation.
WARNING
TO PREVENT POSSIBLE DAMAGE, THE UNIT SHOULD
REMAIN I N AN UPRIGH T POSI TION DURI NG ALL
RIGGING AND MOVI NG OPERATI ONS. TO FACIL ITATE
LIFTING AND MOVI NG IF A CR ANE IS USED , PLAC E
THE UN IT IN AN AD EQUATE CAB LE SL I DE .
NOTE: A roof curb can be used to utilize bottom discharge.
APG/GPG Package Units are designed for outdoor installations only in either residential or light commercial applications.
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
The connecting ductwork (Supply and Return) can be connected for either horizontal or down discharge airflow. In the
down discharge applications a matching Roof Curb is recommended .
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible location
within the return air duct. The minimum filter area should not
be less than those sizes listed in the Specification Section.
Under no circumstances should the unit be operated without
return air filters.
15
Page 16
PRODUCT DESIGN
A 3/4" - 14 NPT drain connector is provided for removal of
condensate water from the indoor coil. In order to provide
proper condensate flow, do not reduce the drain line size.
NOTE: Tighten drain to a maximum torque of 10 in-lbs.
Refrigerant flow control is achieved by use of thermostatic
expansion valves (TXV) or flowrator.
The single phase models use permanent split capacitors
(PSC) design compressors. Starting components are therefore not required. A low MFD run capacitor assists the
compressor to start and remains in the circuit during operation.
A/GPG three phase units use three phase compressors.
Starting components and run capacitors are therefore not
required.
A/GPG Package Gas Units are designed for outdoor installations only in either residential or light commercial applications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes. They
are designed for 208/230 volt single phase applications or
208/230 volt 3 phase applications.
The connecting ductwork (Supply and Return) can be connected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible location
within the return air duct (3 phase models have an internal
downflow filter rack). The minimum filter area should not be
less than those sizes listed in the Specification Section.
Under no circumstances should the unit be operated without
return air filters.
A/GPG model units use either PSC or X13 type indoor blower
motors. X-13 motors are constant torque motors with very low
power consumption and are energized by a 24V signal from
the ignition control board. The X-13 features an integrated
control module.
Air for condensing (cooling cycle) is drawn through the
outdoor coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
Most A/GPG series package units use the Compliant Scroll
compressor; there are a number of design characteristics
which are different from the traditional reciprocating compressor.
- Due to their design Scroll compressors are inherently
more tolerant of liquid refrigerant. NOTE: Even though the
compressor section of a Scroll compressor is more
tolerant of liquid refrigerant, continued flood back or
flooded start conditions may wash oil from the bearing
surfaces causing premature bearing failure.
- These Scroll compressors use "POE" or polyolester oil
which is NOT compatible with mineral oilbased lubricants like 3GS. "POE" oil must be used if additional oil
is required.
- Compliant scroll compressors perform “quiet” shutdowns
that allow the compressor to restart immediately without
the need for a time delay. This compressor will restart
even if the system has not equalized.
- Operating pressures and amp draws may differ from
standard reciprocating compressors. This information
may be found in the “Cooling Performance Data” section.
Some models of the A/GPG15 series package units use a 2
stage scroll compressor. The basic scroll design has been
modified with the addition of an internal unloading mechanism that opens a by-pass port in the first compression
pocket, effectively reducing the displacement of the scroll.
The opening and closing of the by-pass port is controlled by
an internal electrically operated solenoid.
The ZPS modulated scroll uses a single step of unloading
to go from full capacity to approximately 67% capacity. A
single speed, high efficiency motor continues to run while
the scroll modulates between the two capacity steps.
A scroll is an involute spiral which, when matched with a
mating scroll form as shown, generates a series of crescent
shaped gas pockets between the two members.
During compression, one scroll remains stationary (fixed
scroll) while the other form (orbiting scroll) is allowed to orbit
(but not rotate) around the first form.
16
Page 17
PRODUCT DESIGN
As this motion occurs, the pockets between the two forms
are slowly pushed to the center of the two scrolls while
simultaneously being reduced in volume. When the pocket
reaches the center of the scroll form, the gas, which is now
at a high pressure, is discharged out of a port located at the
center.
During compression, several pockets are being compressed
simultaneously, resulting in a very smooth process. Both
the suction process (outer portion of the scroll members)
and the discharge process (inner portion) are continuous.
ELECTRICAL WIRING
The units are designed for operation on 60 hertz current and
at voltages as shown on the rating plate. All internal wiring
is complete. Ensure the power supply to the compressor
contactor is brought to the unit as shown on the supplied unit
wiring diagram. The 24V wiring must be connected between
the unit control panel and the room thermostat.
All line voltage connections must be made through weather
proof fittings. All exterior power supply and ground wiring
must be in approved weather proof conduit. Low voltage
wiring from the unit control panel to the thermostat requires
coded cable. See the following figures for ground level and
rooftop wiring.
JUNCTION BOX
LINE VOLTAGE WIRING
Power supply to the unit must be N.E.C. Class 1, and must
comply with all applicable codes. The unit must be electrically grounded in accordance with the local codes or, in their
absence, with the latest edition of the National Electrical
Code, ANSI/NFPA No. 70, or in Canada, Canadian Electrical Code, C22.1, Part 1. A fused disconnected must be
provided and sized in accordance with the unit minimum
circuit ampacity.
The best protection for the wiring is the smallest fuse or
breaker which will hold the equipment on line during normal
operation without nuisance trips. Such a device will provide
maximum circuit protection.
WARNING
DO NOT EXCEED THE MAXIMUM OVERCURRENT
DEVICE SIZE SHOWN ON THE UNIT DATA PLATE.
The unit transformer is connected for 230V operation. If the
unit is to operate on 208V, reconnect the transformer primary
lead and the induced draft blower leads as shown on the unit
wiring diagram.
17
Page 18
PRODUCT DESIGN
WARNING
TO AVOID THE RISK OF PROPERTY DAM AGE,
PERSONAL INJURY OR FIRE, USE ONLY COPPER
CONDUCTORS.
If it is necessary for the installer to supply additional line
voltage wiring to the inside of the package unit, the wiring
must comply with all local codes. This wiring must have a
minimum temperature rating of 105°C. and must be routed
away from the burner compartment. All line voltage splices
must be made inside the unit control box.
GAS SUPPLY AND PIPING
CAUTION
THIS PACKAGE GAS UNIT IS FACTORY SET TO
OPERATE ON NATURAL GAS AT THE ALTITUDES
SHOWN ON THE RATING PLATE. IF OPERATION
ON PROPANE IS REQUIRED, OBTAIN AND INSTALL
THE PROPER CONVERS ION KIT(S) BEFORE
OPERA TING THIS U NIT. FAILURE TO DO SO
MAY RESULT IN UNSATISFACTORY OPERATION
AND/OR EQUIPMENT DAMAGE.
The rating plate is stamped with the model number, type of
gas, and gas input rating. Make sure the unit is equipped to
operate on the type of gas available.
Inlet Gas Pressure
NaturalMin. 5.0" W.C., Max. 10.0" W.C.
PropaneMin. 11.0" W.C., Max. 13.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value
Shown in the table above.
The minimum supply pressure must not be varied downward
because this could lead to unreliable ignition. In addition, gas
input to the burners must not exceed the rated input shown
on the rating plate. Overfiring of the unit could result in
premature heat exchanger failure.
GAS PIPING
CAUTION
The gas pipe supplying the unit must be properly sized based
on the cubic feet per hour of gas flow required, specific gravity
of the gas and length of the run. The gas line installation must
comply with local codes, or in the absence of local codes,
with the latest edition of the National Fuel Gas Code ANSI
Z223.1.
1. Use black iron or steel pipe and fittings for the building
piping.
2. Use pipe joint compound on male threads only. Pipe joint
compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter
the gas valve. The drip leg must be a minimum of three
inches long.
5. Use two pipe wrenches when making connection to the
gas valve to keep it from turning.
6. Install a manual shut off valve. This shut off valve should
be conveniently located within six (6) feet of the unit, and
between the meter and unit.
7. Tighten all joints securely.
8. Connect the unit to the building piping by one of the
following methods.
a.Rigid metallic pipe and fittings.
b.Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing shall not be used in exterior
locations.
c.Listed gas appliance connectors used in accor-
dance with the terms of their listing that are
completely in the same room as the equipment.
TO AVOID PO SSIBLE UNS ATISFACTOR Y OPERAT ION
OR EQUIPMEN T DAM AGE D UE TO UND ERFIRING OF
EQUIPMENT, DO NOT UNDERSIZE THE NATURAL
GAS/PROPANE PIPING FROM THE METER/TANK TO
THE FURNACE. WHEN SIZING A TRUNK LINE PER
THE TABLES, INCLUDE ALL APPLIANCES ON THAT
LINE THAT COULD BE OPERATED SIMULTANEOUSLY.
18
Page 19
PRODUCT DESIGN
NOTE: In "b" and "c", the connector or tubing must be
installed so as to be protected against physical and
thermal damage. Aluminum-alloy tubing and connectors
must be coated to protect against external corrosion where
they are in contact with masonry, plaster, or insulation or
are subject to repeated wettings by such liquids as water
(except rain water), detergents, or sewage.
MANUAL
SHUT-OFF
VALVE
DRIP LEG
GROUND JOINT UNION
(INSTALLED AHEAD OF GAS VALVE)
GROMMET
NOTE: The unit gas supply entrance is factory sealed with
plugs. Keep plugs in place until gas supply is ready to be
installed. Once ready, replace the plugs with the supplied
grommets and install gas supply line.
CHECKING THE GAS PIPING
CAUTION
TO A VOID THE POSSIBILITY OF PROPERTY DAMAGE,
PERSONAL INJUR Y OR FIRE, THE FOLLOWING
INSTRUCTIONS MUST BE PERFORMED REGARDING
GAS CONNECTIONS AND PRESSURE TESTING.
The unit and its gas connections must be leak tested before
placing in operation. Because of the danger of explosion or
fire, never use a match or open flame to test for leaks. Never
exceed specified pressure for testing. Higher pressure may
damage the gas valve and cause overfiring which may result
in heat exchanger failure.
This unit must be isolated from the gas supply system by
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.48 kPa).
TANKS AND PIPING - PROPANE UNITS
WARNING
PERSONAL INJURY HAZARD
IRON OXIDE (RUST) CAN REDUCE THE LEVEL OF
ODORANT IN PROPANE GAS. A GAS DETECTING
DEVICE IS THE ONLY RELIABLE METHOD TO DETECT
A PROPANE GAS LEAK. CONTACT YOUR LOCAL
PROPANE SUPPLIER ABOUT INSTALLING A GAS
DETECTING WARNING DEVICE TO ALERT YOU IN
THE EVENT THAT A GAS LEAK SHOULD DEVELOP.
FAILURE TO DETECT A PROPANE GAS LEAK COULD
RESULT IN AN EXPLOSION OR FIRE WHICH COULD
CAUSE SERIOUS PERSONAL INJURY OR DEATH.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See
NBFU Manual 58) or Natural Standards of Canada B149.2,
Installation Code for Propane Gas Burning Appliances and
Equipment.
For satisfactory operation, propane gas pressure must be 10
inch W.C. at the unit manifold with all gas appliances in
operation. Maintaining proper gas pressure depends on
three main factors.
1. Vaporization rate, which depends on (a) temperature of
the liquid, and (b) "wetted surface" area of the container
or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended from the standpoint of both cost and
efficiency.)
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size
required will depend on length of pipe run and total load
of all appliances.
Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas
suppliers.
Propane is an excellent solvent, and special pipe dope must
be used when assembling piping for this gas as it will quickly
dissolve white lead or most standard commercial compounds. Shellac base compounds resistant to the actions
of liquefied petroleum gases such as Gasolac®, Stalactic®,
Clyde's or John Crane are satisfactory.
19
Page 20
PRODUCT DESIGN
TYPICAL PROPANE PIPING
PROPANE GAS PIPING CHARTS
First Stage
Regulator
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Ma x.)
Continuous
Second Stage
Regulator
11" W.C.
WARNING
IF YOUR PROPANE GAS APPLIANCE IS INSTALLED IN
AN EXCAVATED AREA OR A CONFINED SPACE, W E
STRONGLY RECOMMENDED THAT YOU CONTACT
YOUR PROPANE SUPPLIER ABOUT INSTALLING A
GAS DETECTING WARNING DEVICE THAT WOULD
ALERT YOU TO A GAS LEAK.
• PROPANE GAS IS HEAVIER THAN AIR AND ANY
LEAKING GAS CAN SETTLE IN ANY LOW AREAS
OR CONFINED SPACES.
• PROPANE GAS ODORANT MAY FADE, MAKING
THE GAS UNDETECTABLE EXCEPT WITH A
WARNING DEVICE.
AN UNDETECTED GAS LEAK WILL CREATE A
DANGER OF EXPLOSION OR FIRE. IF YOU SUSPECT
THE PRESENCE O F GAS, FOLLOW THE INSTRUCTIONS ON PAGE 7. FAILURE TO DO S O COULD
RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
PROPANE TANK SIZING (MINIMUM)
TANK SIZE REQUIRED IF LOWEST OUTDOOR
MAXIMUM GAS TEMPERATURE (AVG. FOR 24 HOURS) REACHES
NEEDED TO
VAPORIZE*
125K BTU/HR
(50 CFH)
250K BTU/HR
(100 CFH)
375K BTU/HR
(150 CFH)
500K BTU/HR
(200 CFH)
750K BTU/HR
(300 CFH)
* AVERAGE RATE/HOUR WITHDRAWL IN 8 HOUR PERIOD
32°F20°F10°F0°F-10°F-20°F -30°F
115
115
115
250
250
400
GAL
250
GAL
300
GAL
400
GAL
750
GAL
GAL
250
GAL
400
GAL
500
GAL
1000
GAL
GAL
250
GAL
500
GAL
750
GAL
1500
GAL
GAL
400
GAL
500
GAL
1000
GAL
2000
GAL
GAL
500
GAL
1000
GAL
1500
GAL
2500
GAL
GAL
1000
GAL
1500
GAL
2000
GAL
4000
GAL
600
GAL
1500
GAL
2500
GAL
3500
GAL
5000
GAL
Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10
PSIG Setting. Capacities in 1,000 BTU/HR
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at
11" W.C. Setting. Capacities in 1,000 BTU/HR
The refrigerant used in the system is R-410A. It is a clear,
colorless, non-toxic and non-irritating liquid. R-410A is a
50:50 blend of R-32 and R-125. The boiling point at atmospheric pressure is -62.9°F.
A few of the important principles that make the refrigeration
cycle possible are: heat always flows from a warmer to a
cooler body. Under lower pressure, a refrigerant will absorb
heat and vaporize at a low temperature. The vapors may be
drawn off and condensed at a higher pressure and temperature to be used again.
20
Page 21
SYSTEM OPERA TION
The indoor evaporator coil functions to cool and dehumidify
the air conditioned spaces through the evaporative process
taking place within the coil tubes.
NOTE: The pressures and temperatures shown in the
refrigerant cycle illustrations on the following pages are for
demonstration purposes only. Actual temperatures and pressures are to be obtained from the "Expanded Performance
Chart".
Liquid refrigerant at condensing pressure and temperatures,
(270 psig and 122°F), leaves the outdoor condensing coil
through the drier and is metered into the indoor coil through
the metering device. As the cool, low pressure, saturated
refrigerant enters the tubes of the indoor coil, a portion of the
liquid immediately vaporizes. It continues to soak up heat and
vaporizes as it proceeds through the coil, cooling the indoor
coil down to about 48°F.
Heat is continually being transferred to the cool fins and tubes
of the indoor evaporator coil by the warm system air. This
warming process causes the refrigerant to boil. The heat
removed from the air is carried off by the vapor.
As the vapor passes through the last tubes of the coil, it
becomes superheated. That is, it absorbs more heat than is
necessary to vaporize it. This is assurance that only dry gas
will reach the compressor. Liquid reaching the compressor
can weaken or break compressor valves.
The compressor increases the pressure of the gas, thus
adding more heat, and discharges hot, high pressure superheated gas into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being warmer
than the outdoor air, first loses its superheat by heat transferred from the gas through the tubes and fins of the coil. The
refrigerant now becomes saturated, part liquid, part vapor and
then continues to give up heat until it condenses to a liquid
alone. Once the vapor is fully liquefied, it continues to give up
heat which subcools the liquid, and it is ready to repeat the
cycle.
HEATING
The heating cycle is accomplished by using a unique tubular
design heat exchanger which provides efficient gas heating
on either natural gas or propane gas fuels. The heat
exchangers compact tubular construction provides excellent
heat transfer for maximum operating efficiency.
Inshot type gas burners with integral cross lighters are used
eliminating the need for adjustable air shutters. The same
burner is designed for use on either natural or propane gas
fuels.
The induced draft blower draws fuel and combustion air into
the burners and heat exchanger for proper combustion. A
pressure switch is used in conjunction with the I. D. blower
to detect a blocked flue condition.
Blower operation is controlled by the ignition control module.
The module allows for field adjustment of the blower delay at
the end of the heating cycle. The range of adjustment is for
90, 120, 150 or 180 seconds. The factory delay setting is 30
seconds delay on 150 seconds delay off.
Direct Spark Ignition (DSI) Systems
APG/GPG units are equipped with a direct spark ignition
system. Ignition is provided by 22,000 volt electronic spark.
A flame sensor then monitors for the presence of flame and
closes the gas valve if flame is lost.
3.Induced draft blower is energized at high speed for the
pre-purge period. Pre-purge timer begins after control
recognizes pressure switch has closed.
4.Trial-for-ignition period begins after pre-purge period
expires. Low and high stage gas valves are energized
along with the igniter for trial-for-ignition period. Igniter
is de-energized when flame is detected.
5.Flame is achieved and detected during trial-for-ignition
period. Flame stabilization period begins when flame
is detected.
6.De-energize high stage gas valve and switch induced
draft blower to low speed within five seconds of flame
detection.
7.Air circulating blower is energized at low heat speed
after heat ON delay time expires. Heat ON delay timer
begins when flame is detected.
8.Control monitors thermostat, flame, limit, and pressure switch inputs during low stage heating.
9.Thermostat “W1” input is removed.
10. Low stage gas valve is de-energized.
11. Induced draft blower remains energized at low speed
for post purge period.
12. Air circulating blower remains energized at low heat
speed for heat OFF delay. Heat OFF delay begins
when “W1” input is removed.
13. Control returns to Standby and awaits next thermostat
request.
B. Heating Operation: High stage heat
1.Thermostat type is set to two-stage.
2.Thermostat “W1” and “W2” inputs initiate high stage
heating.
3.Induced draft blower is energized at high speed for the
pre-purge period. Pre-purge timer begins after control
recognizes pressure switch has closed.
4.Trial-for-ignition period begins after pre-purge period
expires. Low and high stage gas valves are energized
along with the igniter for trial-for-ignition period. Igniter
is de-energized when flame is detected.
5.Flame is achieved and detected during trial-for-ignition
period. Flame stabilization period begins when flame
is detected.
6.Gas valve and induced draft blower remain at high
stage and high speed.
7.Air circulating blower is energized at high heat speed
after heat ON delay time expires. Heat ON delay timer
begins when flame is detected.
8.Control monitors thermostat, flame, limit, and pressure switch inputs during high stage heating.
9.Thermostat “W1” and “W2” inputs are removed.
10. High and low stage gas valves are de-energized.
11. Induced draft blower switches from high speed to low
speed and remains energized for post purge period.
12. Air circulating blower remains energized at high heat
speed for High Stage Heat OFF Delay period then
switches to low heat speed for the remainder of the
selected heat OFF delay. Heat OFF delay begins
when “W1” and “W2” inputs are removed.
13. Control returns to Standby and awaits next thermostat
request.
22
Page 23
SYSTEM OPERA TION
IGNITION CONTROL SEQUENCE OF OPERATION (CONT.)
A/GPG15
A. Cooling Operation: Low stage cool
1.Thermostat type is set to two-stage.
2.Thermostat “Y1” or thermostat “Y1” and “G” input
initiates low stage cooling.
3.IDT/ODT/Pressure/Loss of Charge Switch circuits are
checked for closed condition. Cooling operation can
proceed only if these circuits are closed.
4.Low stage compressor output is energized.
5.Condenser fan motor is energized at low speed.
6.Air circulating blower is energized at low cool speed
after cool ON delay expires. Cool ON delay timer
begins when thermostat inputs are detected.
7.Control monitors thermostat, gas valve, flame, and IDT/
ODT/Pressure/Loss of Charge Switches during low
stage cooling.
8.Thermostat “Y1” or “Y1” and “G” inputs are removed.
9.Low stage compressor output is de-energized. Low
speed condenser fan motor is de-energized.
10. Air circulating blower remains energized at low cool
speed for the cool OFF delay. Cool OFF delay timer
begins when thermostat input is removed.
11. Control returns to Standby and awaits next thermostat
request.
B. Cooling Operation: High stage cool
Thermostat type is set to two-stage.
Thermostat “Y1” and “Y2” or “Y1”, “Y2” and “G” inputs
initiate high stage cooling.
IDT/ODT/Pressure/Loss of Charge Switch circuits are
checked for closed condition. Cooling operation can proceed
only if these circuits are closed.
1.Low and high stage compressor outputs are energized.
2.Condenser fan motor is energized at high speed.
3.Air circulating blower is energized at high cool speed
after cool ON delay expires. Cool ON delay timer
begins when thermostat inputs are detected.
Control monitors thermostat, gas valve, flame, and
IDT/ODT/Pressure/Loss of Charge Switches during
high stage cooling operation.
Thermostat “Y1” and “Y2” or “Y1”, “Y2” and “G” inputs
are removed.
Low and high stage compressor outputs are deenergized.
High speed condenser fan motor is de-energized.
4.Air circulating blower switches to low cool speed for
the cool OFF delay. Cool OFF delay timer begins
when thermostat input is removed.
Control returns to Standby and awaits next thermostat
request.
A. Continuous Fan Operation
1.Thermostat “G” input initiates Continuous Fan operation.
2.Air circulation blower shall be immediately energized
at the continuous fan speed. For purposes of this
specification, the continuous fan speed shall be the
low heat speed.
3.Thermostat “G” input is removed.
4.Air circulation blower is immediately de-energized.
5.Control returns to Standby and awaits next thermostat
request.
23
Page 24
SYSTEM OPERA TION
PCBAG100 CONTROL BOARD
DESCRIPTION
The ignition control is designed for use in gas heating/electric
cooling package equipment (rooftop applications) and operates with a two stage heat and two stage cooling system. It
is a direct spark ignition system that uses a 22,000 volt spark
to ignite the burners. A flame sensor is used to monitor the
flame.
The board has the option of using a single or two stage thermostat. The board also controls the indoor blower and has
an adjustable heat fan off delay.
There is also a fault recall button for recalling the last 5 fault
codes. To recall the fault codes, depress the fault recall button for at least 2 seconds but not more than 4 seconds. To
clear the fault code memory, depress the fault recall button
for at least 5 seconds.
L2
T1
INDUCER
LOW
K4
Q3
The following tables list the functions for the connectors
and terminals, the timings, and the fault codes for the
PCBAG100 control board.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is uni t. M ult iple power
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
124VACLimit Switch Output
224VAC24VAC Input to Control
324VACLimit Switch Input
424VACUnused
524VAC24VAC Common
624VACPressure Switch Output
724VACMain Valve High Output
824VACPressure Switch Input
9UnusedMain Valve Low Output
Table 2: Circuit Definitions and Voltage Ratings
for the 6-Circuit Connector Circuits
for the 9-Circuit Connector Circuits
Line Voltage L1L1
Transformer Line L1L1
Air Circulating Blower Line 1L1
Induced Draft Blower Low SpeedDI Low or "Inducer Low"
Induced Draft Blower High SpeedDI High or "Inducer High"
Condenser Fan Motor Low SpeedODF Low
Condenser Fan Motor High SpeedODF High
Line Voltage L2L2
Transformer Line L2L2
Air Circulating Blower Line 2L2
Induced Draft Blower Line 2L2
Condenser Fan Motor Line 2L2
Direct Spark IgniterT1
Flame DetectionFS
Flame Failure Response Time
Low to High Stage Delay Selectable 5 minutes or 10 minutes (Default = 10 minutes)
Heat ON Delay30 Seconds
Heat OFF Delay
High Stage Heat OFF Delay30 Seconds
Cool ON Delay6 Seconds
Cool OFF Delay45 Seconds
Continuous Fan ON Delay0 Seconds
Continuous Fan OFF Delay0 Seconds
Ignition Attempts3
RecyclesInfinite
Automatic Restart 60 Minutes
Pressure Switch Lockout Delay5 Minutes
Factory Test Mode Active Time2 Minutes Maximum
2 Seconds within Flame Stabilization Period
2 Seconds or Per ANSI Z21.20 Outside of Flame Stabilization Period
Open High Temperature Limit4
Flame Detected with Gas Valve De-Energized5
Compressor Short Cycle Delay Active6
Limit Opened 5 Times in Same Call For Heat7
Indoor Thermostat/Outdoor Thermostat is Open8
Pressure Switch/Loss of Charge Switch is Open9
Normal FlameOn
No Flame PresentOff
Low Flame Current1
Flame Detected with Gas Valve De-energized2
Table 5: LED Status Codes and Corresponding System Condition
LED Flashes/Status
26
Page 27
SYSTEM OPERA TION
PCBAG123 IGNITION CONTROL SEQUENCE OF OPERATION
A/GPG13
Continous Fan
1. When the thermostat calls for continuous fan (G) with
out a call for heat or cooling, the indoor the fan has a
7 second delay on make and energizes the “HEAT”
speed. The fan remains energized as long as the call
for fan remains without a call for heat or cooling. The fan
call “G” has a 60 second delay on break. Note: When
the Configuration tab is broken, the continuous fan
mode “G” will have a 7 second delay on make and a 60
second delay on break and the “COOL” speed tap will
be energized.
2. If a call for cool (Y) occurs during continuous fan, the
blower will switch over to “COOL” speed.
3. If a call for heat (W) occurs during continuous fan, the
blower will remain energized through the heat cycle or
until “G” is de-energized.
4. The continuous fan operation will function while the
control is in heat mode lockout.
Cool Mode
1.When the thermostat calls for cooling (“Y”), the control
energizes the cooling speed fan after a 7 second on
delay. The control provides a 3 minute anti-short cycle
protection for the compressor. If the compressor has
been off for 3 or more minutes, the compressor immediately energizes when the thermostat calls for cool. If
the compressor has not been off for at least 3 minutes
when a call for cool occurs, the control waits until 3
minutes has elapsed from the time the compressor
was last de-energized before re-energizing the compressor.
2.When the thermostat removes the call for cooling (“Y”)
the compressor is deenergized and the control
deenergizes the cooling speed fan after a cooling off
delay period of 60 seconds.
Note: A call for cooling has priority over continuous fan. If
G is energized while Y is energized, during the cooling fan
on delay, the fan will remain off until the delay is over.
Note: The cooling fan operation will continue to function
while the control is in heat lockout.
Note: If a call for heat exist with a call for cooling, the call
for heat shall proceed as normal except the fan remains
energized on cool speed.
2.PRE-PURGE - The control energizes the induced draft
motor, flashes code “2” on LED, and waits for the
pressure switch to close. When the pressure switch
has closed, the control stops flashing the LED and
begins timing the 15 second pre-purge period. (Note:
Under normal operation, the LED will not flash if the
pressure switch closes immediately after energizing
the induced draft motor.)
3.IGNITION - The control energizes the gas valve and
spark. If flame is not established within 7 seconds, the
gas valve and spark is de-energized and the control
goes to an inter-purge. If flame is established, the
spark is de-energized and the control goes to heat
blower on delay.
4.Heat Blower On Delay - The control waits for 30 second
heat fan on delay and then energizes the indoor blower
heat speed. If the blower is already energized by a call
for cooling or continuous fan, or in a blower off delay
period, the on delay is skipped and control goes to
steady heat.
5.STEADY HEAT - Control inputs are continuously
monitored to ensure limit and pressure switches are
closed, flame is established, and the thermostat call
for heat remains.
6.POST PURGE - When the thermostat demand for heat
is satisfied, the control immediately deenergizes the
gas valve. The inducer output remains on for a 29
second post-purge period.
7.Heat Blower Off Delay - The indoor blower motor is deenergized after the selected blower off delay time.
Blower timing begins when the thermostat is satisfied.
Blower Off Delay Setti ngs
L2 L2 L2
Diagnost ic LED
COOL HEAT
UNUSED
L2
L1 D1
L1
FS
2
3
54
6
987
121110
1
speed up
Heat Mode
1.CALL FOR HEAT - The thermostat calls for heat by
energizing the “W” terminal. The control checks to see
if the end switch is open. If the end switch is closed, the
control will flash code “3” on the LED and wait indefinitely for the end switch to open. The control will
lockout the call for heat if the end switch is closed
before the induced draft motor is energized.
Transformer
27
Page 28
SYSTEM OPERA TION
Typical Package Cooling or Package Gas
Indoor
Coil
Thermostatic
Expansion
Valve
Restrictor
Orifice
Assy
Either a thermostatic expansion valve or restrictor orifice assembly may be used depending on model, refer to the parts
catalog for the model being serviced.
Outdoor
Coil
Restrictor Orifice Assembly in Cooling Operation
In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the center of the
orifice.
28
Page 29
SCHEDULED MAINTENANCE
Package gas units require regularly scheduled maintenance
to preserve high performance standards, prolong the service
life of the equipment, and lessen the chances of costly
failure.
In many instances the owner may be able to perform some
of the maintenance; however, the advantage of a service
contract, which places all maintenance in the hands of a
trained serviceman, should be pointed out to the owner.
HIGH VOL TAGE!
Disconnect ALL power before servicing
or insta llin g this uni t. M ultip le po wer
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
ONCE A MONTH
1. Inspect the return filters of the evaporator unit and clean
or change if necessary. NOTE: Depending on operation
conditions, it may be necessary to clean or replace the
filters more often. If permanent type filters are used, they
should be washed with warm water and dried.
2. When operating on the cooling cycle, inspect the condensate line piping from the evaporator coil. Make sure
the piping is clear for proper condensate flow.
ONCE A YEAR
QUALIFIED SERVICE PERSONNEL ONLY
1. Clean the indoor and outdoor coils.
2. Clean the cabinet inside and out .
3. Motors are permanently lubricated and do not require
oiling. TO AVOID PREMATURE MOTOR FAILURE, DO
NOT OIL.
4. Manually rotate the outdoor fan and indoor blower to be
sure they run freely.
5. Inspect the control panel wiring, compressor connections, and all other component wiring to be sure all
connections are tight. Inspect wire insulation to be
certain that it is good.
6. Check the contacts of the compressor contactor. If they
are burned or pitted, replace the contactor.
7. Using a halide or electronic leak detector, check all
piping and etc. for refrigerant leaks.
8. Check the combustion chamber (Heat Exchanger) for
soot, scale, etc. Inspect all burners for lint and proper
positioning.
9. Start the system, using the proper instrumentation check
gas inlet and manifold pressures, burner flame and
microamp signal. Adjust if necessary.
10.Start the system and run a Heating Performance Test.
If the results of the test are not satisfactory, see the
"Service Problem Analysis" Guide for the possible
cause.
TEST EQUIPMENT
Proper test equipment for accurate diagnosis is as essential as regular hand tools.
The following is a must for every service technician and
service shop:
1. Thermocouple type temperature meter - measure dry
bulb temperature.
2. Sling psychrometer- measure relative humidity and wet
bulb temperature.
3. Amprobe - measure current.
4. Volt-Ohm Meter - testing continuity, capacitors, motor
windings and voltage.
5. Accurate Leak Detector - testing for refrigerant leaks.
6. High Vacuum Pump - evacuation.
7. Electric Vacuum Gauge, Manifold Gauges and high
vacuum hoses - to measure and obtain proper vacuum.
8. Accurate Charging Cylinder or Electronic Scale - measure proper refrigerant charge.
9. Inclined Manometer - measure static pressure and
pressure drop across coils.
Other recording type instruments can be essential in
solving abnormal problems, however, in many instances
they may be rented from local sources.
Proper equipment promotes faster, more efficient service,
and accurate repairs with less call backs.
HEATING PERFORMANCE TEST
Before attempting to diagnose an operating fault, run a
Heating Performance Test and apply the results to the
Service Problem Analysis Guide.
To conduct a heating performance test, the BTU input to the
package gas unit must be calculated.
After the heating cycle has been in operation for at least
fifteen minutes and with all other gas appliances turned off,
the gas meter should be clocked.
To find the BTU input, multiply the number of cubic feet of
gas consumed per hour by the heating value of the gas
being used. (The calorific value of the gas being used is
found by contacting your local utility.)
It takes forty (40) seconds on the gas meter for the hand on
the cubic foot dial to make one complete revolution, with all
appliances off, except the unit. Using the gas rate chart,
observe the forty (40) seconds, locate and read across to the
one (1) cubic foot dial column. There you will find the number
90, which shows that ninety (90) cubic feet of gas will be
consumed in one (1) hour.
Let's assume the local gas utility has stated that the calorific
value of the gas is 1025 BTU per cubic foot.
Multiplying the ninety (90) cubic feet by 1025 BTU/ft3 gives us
an input of 92,250 BTU/hr.
Checking the BTU input on the rating plate of the unit being
tested.
Should the figure you calculated not fall within five (5) percent
of the nameplate rating of the unit, adjust the gas valve
pressure regulator or resize orifices. In no case should the
input exceed that shown on the rating plate.
To adjust the pressure regulator on the gas valve, turn down
(clockwise) to increase pressure and input, and out (counterclockwise) to decrease pressure and input.
Since propane gas is not normally installed with a gas meter,
clocking will be virtually impossible. The gas orifices used
with propane are calculated for 2500 BTU gas per cubic foot
and with proper inlet pressures and correct piping size, full
capacity will be obtained.
With propane gas, no unit gas valve regulator is used;
however, the second stage supply line pressure regulator
should be adjusted to give 11" water column with all other gas
consuming appliances running.
The dissipation of the heat transferred to the heat exchanger
is now controlled by the amount of air circulated over its
surface.
The flow rate (CFM) of air circulated is governed by the
external static pressure in inches of water column of duct
work, cooling coil, registers and etc., applied externally to
the unit versus the motor speed tap.
A properly operating unit must have the BTU input and flow
rate (CFM) of air, within the limits shown to prevent short
cycling of the equipment. As the external static pressure
goes up, the temperature rise will also increase. Consult the
proper tables for temperature rise limitation.
CAUTION
ALWAY S CO NN ECT A M ANOM ETE R TO THE 1/8" PIPE
TAP AT THE GAS VALVE BEFORE ADJUSTING THE
PRESSU RE RE GULATO R. IN NO CA SE S HOULD TH E
FINAL MANIFOLD PRES SURE VAR Y MORE THA N
PLUS OR MINUS .3 INC HES W ATER CO LU MN FRO M
3.5 INCHES WAT ER COLU MN FOR NAT UR AL G AS O R
10 INCH ES WATER COLUMN FOR PROPANE GAS.
31
Page 32
SERVICING
COOLING ANALYSIS CHART
Com plaint
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POS S I BL E CAUSE"
Pow er Failure
Blown Fuse
Loose Connection
Shorted or Broken Wires
Open Overload
Faulty Thermostat
Faulty Transformer
Shorted or Open Capacitor
Shorted or Grounded Compressor
Compressor Stuc k
Faulty Compressor Contactor
2nd Stage Compress or Not Energized
Faulty Ignition Control
Open Control Circuit
Low V oltage
Faulty Evap. Fan Motor
Shorted or Grounded Fan Motor
Improper Cooling Anticipator
Shortage of Refrigerant
Restricted Liquid Line
Dirty Air Filter
Dirty Indoor Coil
Not enough air across Indoor Coil
Too much air across Indoor Coil
Overcharge of Refrigerant
Dirty Outdoor Coil
Noncondensibles
Recirculation of Condensing Air
Infiltration of Outdoor Air
Improperly Located Thermostat
Air Flow Unbalanced
System Undersized
Broken Internal Parts
Inefficient Compressor
High Pressur e Control Open
Unbalanced Power, 3PH
Wrong Type Expansion Valve
Expansion Device Restricted
Expansion Valve Bulb Loose
Inoperative Expansion Valve
Loose Hold-dow n Bolts
Compressor runs - goes off on overload
Compressor cycles on overload
Unsatisfactory
Cooling
System runs continuously - little cooling
Too cool and then too warm
Not cool enough on warm days
No Coo ling
SYMPTOM
System will not start
Compressor will not start - fan runs
Comp. and Cond. Fan will not start
Evaporator fan will not start
Condenser fan will not start
•
•••
•••
••••••
•••
••••
••
•••
••
••
••••
••••
•
•
•••
••
••
••
••••
••••
••••
••••
••••
•••••
••••
•••
•••
•••
••
••
••
•••
•
•••
••••••
••••••
•••
Certain areas too cool, others too warm
Compressor is no isy
•
•
•
System
Operating
Pressures
Low suction pressure
Low head pressure
High suction pressure
•
Test Method
Remed y
See S er vice Procedure Ref.
High head pressure
Test VoltageS-1
Inspect Fuse Size & TypeS-4
Inspect Connection - TightenS-2
Test Circuits With OhmmeterS-3
Test Continuity of Ov erloadS-17A
Test continuity of Thermostat & WiringS- 3
Check control circuit with voltmeterS-4
Test Capacit orS-15
Test Motor WindingsS-17B
Use Te s t CordS-17D
Test continuity of Coil & ContactsS-7, S-8
Test Unloader Solenoid (2 stage compressor only)S-17C
Test Ignition Cont rolS-313
Test Control Circuit w ith VoltmeterS-4
Test VoltageS-1
Repair or ReplaceS-16
Test Motor WindingsS-16
Check resistance of AnticipatorS-3
Test For Leaks, Add RefrigerantS-103
Replace Restricted PartS-112
Inspect Filter-Clean or Replace
Inspect Coil - Clean
Speed Blow er, Check Duct Static PressS-200
Reduce Blow er SpeedS-200
Recover Part of ChargeS-113
Inspect Coil - Clean
Recover Charge, Evacuate, RechargeS-114
Remove Obstruction to Air Flow
Check Windows, Doors, Vent Fans, Etc.
Relocate Thermostat
Readjust Air Volume Dampers
Refigure Cooling Load
Replace Compressor
Test Compre ssor EfficiencyS-104
Reset And Test Cont rolS-12
Test Voltage
Replace Valve
Remove restriction or replace expansion device
Tighten Bulb Bracket
Check Valve OperationS-110
Tighten Bolts
32
Page 33
SERVICING
e
Com p laintNo He atUns at isfactory Heat
POSSIBLE CAUSE
GAS HEATING ANALYSIS CHART
DOTS IN ANALYSIS
GUIDE INDICATE
"PO S S IBL E CAUSE"
Pow er Fa ilure
Blown Fuse
Loose Connection
Shorted or Broken Wires
No Low Voltage
Faulty Thermostat
Faulty Transformer
Poor or High Resistance Ground
Improper Heat Anticipator Setting
Improper Thermostat Location
Faulty Limit or Roll Out Switch
Faulty Flame Sensor
Faulty Ignition Control
Gas Valve or Gas Supply Shut Off
Faulty Induced Draft Blower
Dirty Flame Sensor, Low uA
Flame Sensor not in Flame, Low uA
Faulty Gas Valve
No High Stage Heat (2 Stage Only)
Open Aux illary Limit
Improper Air Flow or Distribution
Locking out on Main Limit
Delayed Ignition
Flashback
Orific e Size
Gas Pressure
Cracked Heat Exchanger
Stuck Gas Valve
Furnace Undersized
Faulty Pressure Switch
Blocked or Restricted Flue
Open Roll Out Switch
Bouncing On Pressure Sw itch
SYMPTOM
System Will No t Start
Burner Won't Ignite
Burner Ignites-Locks Out
Burner Shuts Off prior to T'Stat being Satasfi
Short Cycles
Long Cycles
Soot and /or Fumes
To Much Heat
Not Enough Heat
•
•
•
•
•
••••
•
•
••••
••••
•••
•
•••
•
•••
•
•
•••
••
••
••
•••
•
•
•••
••••
•
•••
•••
•
••
••
Test Volt ageS-1
Test Volt ageS-4
Check WiringS-2
Check WiringS-3
Check TransformerS-4
Check ThermostatS-3
Check TransformerS-4
Measure Ground ResistanceS-313
Adjust Heat Anticipa t or SettingS-3
Relocate Thermostat
Test ControlS-300,S-301,S-302
Test Flame SensorS- 314
Test ControlS-313
Turn Valves to On PositionS-304
Test Blow erS-303
Clean Flame SensorS-314
Test/Adjust Position of Flame SensorS-314
Replace Gas V alveS- 304
Check Thermostat, Control, Gas ValveS-3,S-313,S-304
Reset ControlS-301
Check Duct Static
Check Controls, Gas Press., & Temp. RiseS- 300
Test for Delayed IgnitionS-308
Test for FlashbackS-309
Check OrificesS-306
Check Gas Pressur eS-307
Check Burner FlamesS-302
Replace Gas V alveS- 304
Replace w ith Proper Size Furnace
•
Test Pressure SwitchS-310
Check Flue/Drawdown Pressur eS-310
Test ControlS-302
Test Negative PressureS-310
Checking Temperature Rise .......................... 51
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple power sources
may be present. Failure to do so may cause property damage, person al inj ury or death.
34
Page 35
SERVICING
S-1 CHECKING VOLTAGE
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove doors, control panel cover, etc. from unit being
tested.
With power ON:
WARNING
Line Voltage now present.
2. Using a voltmeter, measure the voltage across terminals
L1 and L2 of the contactor for single phase units, and L3,
for 3 phase units.
3. No reading - indicates open wiring, open fuse(s) no power
or etc. from unit to fused disconnect service. Repair as
needed.
4. With ample voltage at line voltage connectors, energize
the unit.
5. Measure the voltage with the unit starting and operating,
and determine the unit Locked Rotor Voltage.
Locked Rotor Voltage is the actual voltage available at
the compressor during starting, locked rotor, or a stalled
condition. Measured voltage should be above minimum
listed in chart below.
To measure Locked Rotor Voltage attach a voltmeter to
the run "R" and common "C" terminals of the compressor,
or to the T1 and T2 terminals of the contactor. Start the unit
and allow the compressor to run for several seconds, then
shut down the unit. Immediately attempt to restart the
unit while measuring the Locked Rotor Voltage.
6. Voltmeter should read within the voltage tabulation as
shown. If the voltage falls below the minimum voltage,
check the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the local
power company in regards to either low or high voltage.
Unit Supply Voltage
VoltageMin.Max.
460437506
208/230198253
Max. Voltage Deviation
% Voltage =
ImbalanceAverage Voltage
To find the percentage of imbalance, measure the incoming
power supply.
L1 - L2 = 240V
L1 - L3 = 232V Avg. V =
L2 - L3 =
Total 710V
To find Max. deviation:240 - 236.7 = +3.3
Max deviation was 4.7V
% Voltage Imbalance =
If the percentage of imbalance had exceeded 3%, it must be
determined if the imbalance is in the incoming power supply
or the equipment. To do this rotate the legs of the incoming
power and retest voltage as shown below.
L1
L1
By the voltage readings we see that the imbalance rotated or
traveled with the switching of the incoming legs. Therefore the
imbalance lies within the incoming power supply.
If the imbalance had not changed then the problem would lie
within the equipment. Check for current leakage, shorted
motors, etc.
From Average Voltage X 100
710 = 236.7
238V 3
232 - 236.7 = -4.7
238 - 236.7 = +1.3
4.7= 1.99%
236.7
L1 - L2 = 240V
L1 - L3 = 227V
L2 - L3 = 238V
L2
L3
L3L2
Rotate all 3 incoming
legs as shown.
L1 - L2 = 227V
L1 - L3 = 238V
L2 - L3 = 240V
Three phase units require a balanced 3 phase power supply
to operate. If the percentage of voltage imbalance exceeds
3% the unit must not be operated until the voltage condition
is corrected.
35
Page 36
SERVICING
S-2 CHECKING WIRING
HIGH VOL TAGE!
Disconnect ALL power before servicing
or insta llin g this uni t. M ultip le po wer
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Check wiring visually for signs of overheating, damaged
insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected
open wires.
3. If any wires must be replaced, replace with comparable
gauge and insulation thickness.
2. With voltmeter, check for 24 volts at wires C and G.
3. No voltage indicates the trouble is in the thermostat or
wiring.
4. Check the continuity of the thermostat and wiring. Repair
or replace as necessary.
S-3B COOLING ANTICIPATOR
The cooling anticipator is a small heater (resistor) in the
thermostat. During the "off" cycle, it heats the bimetal
element helping the thermostat call for the next cooling cycle.
This prevents the room temperature from rising too high
before the system is restarted. A properly sized anticipator
should maintain room temperature within 1 1/2 to 2 degree
range.
The anticipator is supplied in the thermostat and is not to be
replaced. If the anticipator should fail for any reason, the
thermostat must be changed.
S-3 CHECKING THERMOSTAT, WIRING, AND
ANTICIPATOR
THERMO ST AT W IRE SIZ I NG CHART
LENGTH OF RUN
25 fe et18
50 fe et16
75 fe et14
100 fe et14
125 fe et12
150 fe et12
M IN. COPPER WI RE
GAUGE (AWG)
S-3A THERMOSTAT AND WIRING
WARNING
Line Voltage now present.
With power ON, thermostat calling for cooling
1. Use a voltmeter to check for 24 volts at thermostat wires
C and Y in the condensing unit control panel.
2. No voltage indicates trouble in the thermostat, wiring or
external transformer source.
3. Check the continuity of the thermostat and wiring. Repair
or replace as necessary.
Indoor Blower Motor
With power ON:
S-3C HEATING ANTICIPATOR
The heating anticipator is a wire-wound adjustable heater,
which is energized during the "ON" cycle to help prevent
overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail
for any reason, the thermostat must be replaced. See the
following for recommended heater anticipator setting.
To determine the proper setting, use an ammeter to measure
the current on the "W" wire going to the thermostat.
Use an amprobe as shown below. Wrap 10 turns of thermostat wire around the stationary jaw of the amprobe and divide
the reading by 10.
10 TURNS OF
THERMOSTAT WIRE
(From "W" on thermostat)
STATIONARY JAW
OF AMPROBE
READS 4 AMPS
CURRENT DRAW
WOULD BE .4 AMPS
WARNING
Line Voltage now present.
1. Set fan selector switch at thermostat to "ON" position.
36
Checking Heat Anticipator Amp Draw
Page 37
SERVICING
S-4 CHECKING TRANSFORMER AND CON-
TROL CIRCUIT
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
A step-down transformer (208/240 volt primary to 24 volt secondary) is provided with each indoor unit. This allows ample
capacity for use with resistance heaters. The outdoor sections do not contain a transformer.
WARNING
Disconnect ALL power before servicing.
1. Remove control panel cover, or etc., to gain access to
transformer.
With power ON:
NOTE: Most single phase contactors break only one side of
the line (L1), leaving 115 volts to ground present at most
internal components.
1. Remove the leads from the holding coil.
2. Using an ohmmeter, test across the coil terminals.
If the coil does not test continuous, replace the relay or
contactor.
S-8 CHECKING CONTACTOR CONTACTS
SINGLE PHASE
HIGH VOL TAGE!
Disconn ect ALL po wer be for e ser vic in g
or inst all ing th is u nit . M ult ip le po wer
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Disconnect the wire leads from the terminal (T) side of the
contactor.
2. With power ON, energize the contactor.
WARNING
Line Voltage now present.
2. Using a voltmeter, check voltage across secondary
voltage side of transformer (R to C).
3. No voltage indicates faulty transformer, bad wiring, or bad
splices.
4. Check transformer primary voltage at incoming line
voltage connections and/or splices.
5If line voltage available at primary voltage side of trans-
former and wiring and splices good, transformer is inoperative. Replace.
S-7 CHECKING CONTACTOR AND/OR RELAYS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
The compressor contactor and other relay holding coils are
wired into the low or line voltage circuits. When the control
circuit is energized, the coil pulls in the normally open
contacts or opens the normally closed contacts. When the
coil is de-energized, springs return the contacts to their
normal position.
WARNING
LINE VOLTAGE NOW PRESENT.
T2
VOLT/OHM
METER
Ohmmete r fo r te st in g hol di n g coil
Voltmeter fo r testing contac ts
TESTING COMPRESSOR CONTACTOR
(Single Phase)
3. Using a voltmeter, test across terminals.
A.L1 - L2 - No voltage. Check breaker or fuses on main
power supply.
B.L2 - T1 - No voltage indicates CC1 contacts open.
If a no voltage reading is obtained - replace the contactor.
T1
CC
L1L2
37
Page 38
SERVICING
THREE PHASE
Using a voltmeter, test across terminals.
A.L1-L2, L1-L3, and L2-L3 - If voltage is present,
proceed to B. If voltage is not present, check breaker
or fuses on main power supply..
B.T1-T2, T1-T3, and T2-T3 - If voltage readings are not
the same as in "A", replace contactor.
4. Start the system and place a piece of cardboard in front
of the condenser coil, raising the condensing pressure.
5. Check pressure at which the high pressure control cutsout.
T3L3T2
CC
T1
VOLT/OHM
METER
L1
L2
Ohmmeter for testing holding coil
Voltmeter for testing contacts
TESTING COMPRESSOR CONTACTOR
(ThreePhase)
S-9 CHECKING FAN RELAY CONTACTS
The fan relays are incorporated into the control board. See
section S-313 for checking control board.
S-12 CHECKING HIGH PRESSURE CONTROL
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
The high pressure control senses the pressure in the liquid
line. If abnormally high condensing pressures develop, the
contacts of the control open, breaking the control circuit
before the compressor motor overloads. This control is
automatically reset.
1. Using an ohmmeter, check across terminals of high
pressure control, with wire removed. If not continuous,
the contacts are open.
3. Attach a gauge to the dill valve port on the base valve.
With power ON:
If it cuts-out at 610 PSIG ± 10 PSIG, it is operating normally
(See causes for high head pressure in Service Problem
Analysis Guide). If it cuts out below this pressure range,
replace the control. The control should reset at 420 PSIG ±
25 PSIG.
S-13 CHECKING LOW PRESSURE CONTROL
The low pressure control senses the pressure in the suction
line and will open its contacts on a drop in pressure. The low
pressure control will automatically reset itself with a rise in
pressure.
The low pressure control is designed to cut-out (open) at
approximately 7 PSIG ± 3 PSIG. It will automatically cut-in
(close) at approximately 25 PSIG ± 5 PSIG.
Test for continuity using a VOM and if not as above, replace
the control.
S-15 CHECKING CAPACITOR
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and main
windings of a single phase permanent split capacitor motor.
The capacitors primary function is to reduce the line current
while greatly improving the torque characteristics of a motor.
This is accomplished by using the 90° phase relationship
between the capacitor current and voltage in conjunction with
the motor windings so that the motor will give two phase
operation when connected to a single phase circuit. The
capacitor also reduces the line current to the motor by
improving the power factor.
CAPACITOR, START
SCROLL COMPRESSOR MODELS
Hard start components are not required on Scroll compressor equipped units due to a non-replaceable check valve
located in the discharge line of the compressor. However
hard start kits are available and may improve low voltage
starting characteristics.
This check valve closes off high side pressure to the compressor after shut down allowing equalization through the
scroll flanks. Equalization requires only about one or two
seconds during which time the compressor may turn backwards.
38
Page 39
SERVICING
Your unit comes with a 180-second anti-short cycle to prevent
the compressor from starting and running backwards.
MODELS EQUIPPED WITH A HARD START DEVICE
A start capacitor is wired in parallel with the run capacitor to
increase the starting torque. The start capacitor is of the
electrolytic type, rather than metallized polypropylene as
used in the run capacitor.
A switching device must be wired in series with the capacitor
to remove it from the electrical circuit after the compressor
starts to run. Not removing the start capacitor will overheat
the capacitor and burn out the compressor windings.
These capacitors have a 15,000 ohm, 2 watt resistor wired
across its terminals. The object of the resistor is to discharge
the capacitor under certain operating conditions, rather than
having it discharge across the closing of the contacts within
the switching device such as the Start Relay, and to reduce
the chance of shock to the servicer. See the Servicing
Section for specific information concerning capacitors.
RELAY, START
A potential or voltage type relay is used to take the start
capacitor out of the circuit once the motor comes up to speed.
This type of relay is position sensitive. The normally closed
contacts are wired in series with the start capacitor and the
relay holding coil is wired parallel with the start winding. As
the motor starts and comes up to speed, the increase in
voltage across the start winding will energize the start relay
holding coil and open the contacts to the start capacitor.
Two quick ways to test a capacitor are a resistance and a
capacitance check.
OHMMETER
CAPACITOR
TESTING CAPACITOR RESISTANCE
2. Set an ohmmeter on its highest ohm scale and connect
the leads to the capacitor -
a.Good Condition - indicator swings to zero and
slowly returns to infinity. (Start capacitor with
bleed resistor will not return to infinity. It will still
read the resistance of the resistor).
b.Shorted - indicator swings to zero and stops there
-replace.
c.Open - no reading - replace. (Start capacitor
would read resistor resistance.)
S-15B CAPACITANCE CHECK
Using a hookup as shown below, take the amperage and
voltage readings and use them in the formula:
S-15A RESISTANCE CHECK
HIGH VOL TAGE!
Disconnect ALL power before servicing
or insta llin g this uni t. Mult ip le po wer
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Discharge capacitor and remove wire leads.
WARNING
Discharge capacitor through a 20 to 30 OHM
resistor before handling.
VOLTMETER
15 AMP
FUSE
AMMETER
CAPACIT O R
TESTING CAPACITANCE
39
Page 40
SERVICING
WARNING
Discharge capacitor through a 20 to 30 OHM
resistor before handling.
Capacitance (MFD) = 2650 X Amperage
Voltage
S-16A CHECKING FAN AND BLOWER MOTOR
WINDINGS (PSC MOTORS)
The auto reset fan motor overload is designed to protect the
motor against high temperature and high amperage conditions by breaking the common circuit within the motor, similar
to the compressor internal overload. However, heat generated within the motor is faster to dissipate than the compressor, allow at least 45 minutes for the overload to reset, then
retest.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
4. Using an ohmmeter, check the motor windings for continuity to ground (pins to motor shell). If the ohmmeter
indicates continuity to ground, the motor is defective and
must be replaced.
5. Using an ohmmeter, check the windings for continuity (pin
to pin). If no continuity is indicated, the thermal limit (over
load) device may be open. Allow motor to cool and retest.
Motor
Connector
(3-pin)
Motor OK when
R > 100k ohm
(3-pin)
WINDING TEST
S-16D CHECKING GE X13TM MOTORS
Applies to *PG15*****41A*
1. Remove the motor leads from its respective connection
points and capacitor (if applicable).
2. Check the continuity between each of the motor leads.
3. Touch one probe of the ohmmeter to the motor frame
(ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is obtained
from lead to ground, replace the motor.
S-16C CHECKING ECM MOTOR WINDINGS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Disconnect the 5-pin and the 16-pin connectors from the
ECM power head.
2. Remove the 2 screws securing the ECM power head and
separate it from the motor.
3. Disconnect the 3-pin motor connector from the power
head and lay it aside.
The GE X13TM Motor is a one piece, fully encapsulated, 3
phase brushless DC (single phase AC input) motor with ball
bearing construction. Unlike the ECM 2.3/2.5 motors, the GE
X13TM features an integral control module.
Note: The GE TECMate will not currently operate the GE
X13TM motor.
1. Using a voltmeter, check for 230 volts to the motor
connections L and N. If 230 volts is present, proceed to
step 2. If 230 volts is not present, check the line voltage
circuit to the motor.
2. Using a voltmeter, check for 24 volts from terminal C to
either terminal 1, 2, 3, 4, or 5, depending on which tap is
being used, at the motor. If voltage present, proceed to
step 3. If no voltage, check 24 volt circuit to motor.
3. If voltage was present in steps 1 and 2, the motor has failed
and will need to be replaced.
Note: When replacing motor, ensure the belly band is
between the vents on the motor and the wiring has the
proper drip loop to prevent condensate from entering the
motor.
40
Page 41
SERVICING
C
123
Low Voltage Connections
GE X13TM MOTOR CONNECTIONS
High Voltage
Connections
3/16"
LGN
4
1/4”
5
Ignition of the discharge can also occur at the venting terminal
or inside the compressor, if there is sufficient contaminant air
present in the system and an electrical arc occurs as the
terminal vents.
Ignition cannot occur at the venting terminal without the
presence of contaminant air, and cannot occur externally
from the venting terminal without the presence of an external
ignition source.
Therefore, proper evacuation of a hermetic system is essential at the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open flame,
electrical power, and other heat sources should be extinguished or turned off prior to servicing a system.
S-17A RESISTANCE TEST
Each compressor is equipped with an internal overload.
The line break internal overload senses both motor amperage
and winding temperature. High motor temperature or amperage heats the disc causing it to open, breaking the common
circuit within the compressor on single phase units.
Heat generated within the compressor shell, usually due to
recycling of the motor, high amperage or insufficient gas to
cool the motor, is slow to dissipate. Allow at least three to
four hours for it to cool and reset, then retest.
Fuse, circuit breaker, ground fault protective device, etc. has
not tripped -
S-17 CHECKING COMPRESSOR
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
If the compressor terminal PROTECTIVE COVER and gasket
(if required) are not properly in place and secured, there is a
remote possibility if a terminal vents, that the vaporous and
liquid discharge can be ignited, spouting flames several feet,
causing potentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if
the terminal cover is not properly in place and if the discharge
impinges on a sufficient heat source.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove the leads from the compressor terminals.
See warnings S-17 before removing compressor
terminal cover .
2. Using an ohmmeter, test continuity between terminals SR, C-R, and C-S, on single phase units or terminals T1,
T2 and T3, on 3 phase units.
C
OHMMETER
S
COMP
R
TESTING COMPRESSOR WINDINGS
41
Page 42
SERVICING
If either winding does not test continuous, replace the
compressor.
NOTE: If an open compressor is indicated, allow ample
time for the internal overload to reset before replacing
compressor.
WARNING
Damage can occur to the glass embedded terminals if
the leads are not properly removed. This can result in
terminal and hot oil discharging.
S-17B GROUND TEST
If fuse, circuit breaker, ground fault protective device,
etc., has tripped, this is a strong indication that an
electrical problem exists and must be found and corrected. The circuit protective device rating must be
checked, and its maximum rating should coincide with
that marked on the equipment nameplate.
With the terminal protective cover in place, it is acceptable to replace the fuse or reset the circuit breaker
TIME ONLY to see if it was just a nuisance opening. If
it opens again,
DO NOT continue to reset.
ONE
WARNING
Disconnect ALL power before servicing.
Disconnect all power to unit, making sure that all
power legs are open.
1. DO NOT remove protective terminal cover. Disconnect the three leads going to the compressor terminals at the nearest point to the compressor.
2. Identify the leads and using a Megger, Hi-Potential
Ground Tester, or other suitable instrument which
puts out a voltage between 300 and 1500 volts, check
for a ground separately between each of the three
leads and ground (such as an unpainted tube on the
compressor). Do not use a low voltage output
instrument such as a volt-ohmmeter.
Carefully retest for ground, directly between compressor
terminals and ground.
5. If ground is indicated, replace the compressor.
S-17C UNLOADER TEST PROCEDURE
(2 STAGE COMPRESSORS ONLY)
A nominal 24-volt direct current coil activates the internal
unloader solenoid. The input control circuit voltage must be
18 to 28 volt ac. The coil power requirement is 20 VA. The
external electrical connection is made with a molded plug
assembly. This plug contains a full wave rectifier to supply
direct current to the unloader coil.
UNLOADER SO LENOID
(Molded Plug)
HI-POT
COMPRESSOR GROUND TEST
3. If a ground is indicated, then carefully remove the
compressor terminal protective cover and inspect for
loose leads or insulation breaks in the lead wires.
4. If no visual problems indicated, carefully remove the
leads at the compressor terminals.
42
Unloader Test Procedure
If it is suspected that the unloader is not working, the following
methods may be used to verify operation.
1. Operate the system and measure compressor current.
Cycle the unloader ON and OFF at 10 second intervals.
The compressor amperage should go up or down at least
25 percent.
2. If step one does not give the expected results, shut unit
off. Apply 18 to 28 volt ac to the unloader molded plug
leads and listen for a click as the solenoid pulls in.
Remove power and listen for another click as the unloader
returns to its original position.
3. If clicks can’t be heard, shut off power and remove the
control circuit molded plug from the compressor and
measure the unloader coil resistance. The resistance
should be 32 to 60 ohms, depending on compressor
temperature.
Page 43
SERVICING
4. Next check the molded plug.
A.Voltage check: Apply control voltage to the plug
wires (18 to 28 volt ac). The measured dc voltage
at the female connectors in the plug should be
around 15 to 27 vdc.
B.Resistance check: Measure the resistance from
the end of one molded plug lead to either of the two
female connectors in the plug. One of the connectors should read close to zero ohms while the other
should read infinity. Repeat with other wire. The
same female connector as before should read zero
while the other connector again reads infinity.
Reverse polarity on the ohmmeter leads and repeat. The female connector that read infinity previously should now read close to zero ohms.
C.Replace plug if either of these test methods doesn’t
show the desired results.
S-17D OPERATION TEST
If the voltage, capacitor, overload and motor winding test fail
to show the cause for failure:
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove unit wiring from disconnect switch and wire a test
cord to the disconnect switch.
NOTE: The wire size of the test cord must equal the line wire
size and the fuse must be of the proper size and type.
2. With the protective terminal cover in place, use the three
leads to the compressor terminals that were disconnected at the nearest point to the compressor and
connect the common, start and run clips to the respective
leads.
3. Connect good capacitors of the right MFD and voltage
rating into the circuit as shown.
4. With power ON, close the switch.
WARNING
Line Voltage now present.
A.If the compressor starts and continues to run, the cause
for failure is somewhere else in the system.
B.If the compressor fails to start - replace.
S-18 TESTING CRANKCASE HEATER
(OPTIONAL ITEM)
The crankcase heater must be energized a minimum of four
(4) hours before the condensing unit is operated.
Crankcase heaters are used to prevent migration or accumulation of refrigerant in the compressor crankcase during the
off cycles and prevents liquid slugging or oil pumping on start
up.
A crankcase heater will not prevent compressor damage due
to a floodback or over charge condition.
WARNING
Disconnect ALL power before servicing.
1. Disconnect the heater lead in wires.
2. Using an ohmmeter, check heater continuity - should
test continuous. If not, replace.
S-100 REFRIGERATION REPAIR PRACTICE
DANGER
Always remove the refrigerant charge in a proper
manner before applying heat to the system.
When repairing the refrigeration system:
WARNING
Disconnect ALL power before servicing.
1. Never open a system that is under vacuum. Air and
moisture will be drawn in.
2. Plug or cap all openings.
3. Remove all burrs and clean the brazing surfaces of the
tubing with sand cloth or paper. Brazing materials do not
flow well on oxidized or oily surfaces.
4. Clean the inside of all new tubing to remove oils and pipe
chips.
5. When brazing, sweep the tubing with dry nitrogen to
prevent the formation of oxides on the inside surfaces.
6. Complete any repair by replacing the liquid line drier in
the system, evacuate and charge.
BRAZING MATERIALS
Copper to Copper Joints - Sil-Fos used without flux (alloy
of 15% silver, 80% copper, and 5% phosphorous). Recommended heat 1400°F.
Copper to Steel Joints - Silver Solder used without a flux
(alloy of 30% silver, 38% copper, 32% zinc). Recommended
heat - 1200°F.
43
Page 44
SERVICING
S-101 LEAK TESTING
(NITROGEN OR NITROGEN-TRACED)
WARNING
To avoid the risk of fire or explosion, never use
oxygen, high pressure air or flammable gases for leak
testing of a refrigeration system.
WARNING
To avoid possible explosion, the line from the
nitrogen cylinder must include a pressure regulator
and a pressure relief valve. The pressure relief valve
must be set to open at no more than 150 psig.
Pressure test the system using dry nitrogen and soapy water
to locate leaks. If you wish to use a leak detector, charge the
system to 10 psi using the appropriate refrigerant then use
nitrogen to finish charging the system to working pressure,
then apply the detector to suspect areas. If leaks are found,
repair them. After repair, repeat the pressure test. If no leaks
exist, proceed to system evacuation.
1. Connect the vacuum pump, vacuum tight manifold set
with high vacuum hoses, thermocouple vacuum gauge
and charging cylinder as shown.
2. Start the vacuum pump and open the shut off valve to the
high vacuum gauge manifold only. After the compound
gauge (low side) has dropped to approximately 29 inches
of vacuum, open the valve to the vacuum thermocouple
gauge. See that the vacuum pump will blank-off to a
maximum of 25 microns. A high vacuum pump can only
produce a good vacuum if its oil is non-contaminated.
LOW SIDE
GAUGE
AND V ALVE
HIGH SIDE
GAUGE
AND V ALVE
S-102 EVACUATION
WARNING
REFRIGERA NT U NDER PR ESSUR E!
Failure to follow proper procedures may cause
property damage, personal injury or death.
This is the most important part of the entire service procedure.
The life and efficiency of the equipment is dependent upon the
thoroughness exercised by the serviceman when evacuating
air (non-condensables) and moisture from the system.
Air in a system causes high condensing temperature and
pressure, resulting in increased power input and reduced
performance.
Moisture chemically reacts with the refrigerant oil to form
corrosive acids. These acids attack motor windings and
parts, causing breakdown.
The equipment required to thoroughly evacuate the system is
a high vacuum pump, capable of producing a vacuum equivalent to 25 microns absolute and a thermocouple vacuum
gauge to give a true reading of the vacuum in the system
NOTE: Never use the system compressor as a vacuum pump
or run when under a high vacuum. Motor damage could occur.
WARNING
Do not fron t se at th e s er vic e va lve (s) wi th the
compressor open, with the suction line of the
comprssor closed or severely restricted.
EVACUATION
3. If the vacuum pump is working properly, close the valve to
the vacuum thermocouple gauge and open the high and
low side valves to the high vacuum manifold set. With the
valve on the charging cylinder closed, open the manifold
valve to the cylinder.
4. Evacuate the system to at least 29 inches gauge before
opening valve to thermocouple vacuum gauge.
5. Continue to evacuate to a maximum of 250 microns.
Close valve to vacuum pump and watch rate of rise. If
vacuum does not rise above 1500 microns in three to five
minutes, system can be considered properly evacuated.
6. If thermocouple vacuum gauge continues to rise and
levels off at about 5000 microns, moisture and noncondensables are still present. If gauge continues to rise
a leak is present. Repair and re-evacuate.
7. Close valve to thermocouple vacuum gauge and vacuum
pump. Shut off pump and prepare to charge.
44
Page 45
SERVICING
S-103 CHARGING
WARNING
REFRIGERANT UNDER PRESSURE!
* Do not overcharge sy stem w ith refrigerant.
* Do not operate unit in a vacuum or at negative
pressure.
Failure to follow proper procedures may cause
property damage, personal injury or death.
CAUTIO N
Use refrigerant certified to ARI standards. Used
refrigeran t may cause compressor damage and wi ll
void the warranty. Most portable mac hines cannot
clean used refrigerant to me et ARI standards.
CAUTION
Operating the compressor with the suction valve
closed will void the warranty and cause serious
compressor damage.
NOTE: Even though the compressor section of a Scroll
compressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
S-104 CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is broken or damaged
scroll flanks on Scroll compressors, reducing the ability of
the compressor to pump refrigerant vapor.
The condition of the scroll flanks is checked in the following
manner.
1. Attach gauges to the high and low side of the system.
2. Start the system and run a “Cooling Performance Test.
If the test shows:
a. Below normal high side pressure.
b. Above normal low side pressure.
c. Low temperature difference across coil.
d. Low amp draw at compressor.
And the charge is correct. The compressor is faulty - replace
the compressor.
Charge the system with the exact amount of refrigerant.
Refer to the specification section or check the unit name-
plates for the correct refrigerant charge.
An inaccurately charged system will cause future problems.
1. Using a quality set of charging scales, weigh the proper
amount of refrigerant for the system. Allow liquid refrigerant only to enter the high side.
2. After the system will take all it will take, close the valve
on the high side of the charging manifold.
3. Start the system and charge the balance of the refrigerant
through the low side.
NOTE: R410A should be drawn out of the storage container
or drum in liquid form due to its fractionation properties, but
should be "Flashed" to its gas state before entering the
system. There are commercially available restriction devices
that fit into the system charging hose set to accomplish this.
DO NOT charge liquid R410A into the compressor.
4. With the system still running, close the valve on the
charging cylinder. At this time, you may still have some
liquid refrigerant in the charging cylinder hose and will
definitely have liquid in the liquid hose. Reseat the liquid
line core. Slowly open the high side manifold valve and
transfer the liquid refrigerant from the liquid line hose and
charging cylinder hose into the suction service valve port.
CAREFUL: Watch so that liquid refrigerant does not
enter the compressor.
Due to their design, Scroll compressors are inherently more
tolerant of liquid refrigerant.
S-105B THERMOSTATIC EXPANSION VALVE
The expansion valve is designed to control the rate of liquid
refrigerant flow into an evaporator coil in exact proportion to
the rate of evaporation of the refrigerant in the coil. The
amount of refrigerant entering the coil is regulated since the
valve responds to temperature of the refrigerant gas leaving
the coil (feeler bulb contact) and the pressure of the refrigerant in the coil.
This regulation of the flow prevents the return of liquid
refrigerant to the compressor.
The three forces which govern the operation of the valve are:
(1) the pressure created in the power assembly by the feeler
bulb, (2) evaporator pressure, and (3) the equivalent pressure
of the superheat spring in the valve.
0% bleed type expansion valves are used on the indoor coils.
The 0% valve will not allow the system pressures (High and
Low side) to equalize during the shut down period. The valve
will shut off completely at approximately 100 PSIG Pressure.
Good thermal contact between the feeler bulb and the
suction line is essential to satisfactory valve control and
performance.
The bulb must be securely fastened to a clean straight
section of the suction line. Application of the bulb to a
horizontal run of line is preferred. If a vertical installation
cannot be avoided the bulb should be mounted so that the
capillary tubing comes out at the top.
THE VALVES PROVIDED ARE DESIGNED TO MEET THE
SPECIFICATION REQUIREMENTS FOR OPTIMUM PRODUCT OPERATION. DO NOT USE SUBSTITUTES.
Overfeeding by the expansion valve results in high suction
pressure, cold suction line, and possible liquid slugging of
the compressor.
If these symptoms are observed:
1. Check for an overcharged unit by referring to the cooling
performance charts in the servicing section.
2. Check the operation of the power element in the valve as
explained in S-110 Checking Expansion Valve Operation.
3. Check for restricted or plugged equalizer tube.
S-107 UNDERFEEDING
Underfeeding by the expansion valve results in low system
capacity and low suction pressures.
If these symptoms are observed:
1. Check for a restricted liquid line or drier. A restriction will
be indicated by a temperature drop across the drier.
2. Check the operation of the power element of the valve as
described in S-110 Checking Expansion Valve Operation.
S-108 SUPERHEAT
The expansion valves are factory adjusted to maintain 12 to
15 degrees superheat of the suction gas. Before checking
the superheat or replacing the valve, perform all the procedures outlined under Air Flow, Refrigerant Charge, Expansion Valve - Overfeeding, Underfeeding. These are the most
common causes for evaporator malfunction.
CHECKING SUPERHEAT
Refrigerant gas is considered superheated when its temperature is higher than the saturation temperature corresponding
to its pressure. The degree of superheat equals the degrees
of temperature increase above the saturation temperature at
existing pressure. See Temperature - Pressure Chart on
following page.
CAUTION
To prevent personal injury, carefully connect and
disconnect manifold gauge hoses. Escaping liquid
refrigerant can cause burns. Do not vent refrigerant
to atmosphere. Recover during system repair
or final unit disposal.
3. Refer to the superheat table provided for proper system
superheat. Add charge to lower superheat or recover
charge to raise superheat.
Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
EXAMPLE:
a. Suction Pressure = 143
b. Corresponding Temp. °F. = 50
c. Thermometer on Suction Line = 61°F.
To obtain the degrees temperature of superheat, subtract
50.0 from 61.0°F.
The difference is 11° Superheat. The 11° Superheat would
fall in the ± range of allowable superheat.
SUPERHEAT AND SUBCOOLING ADJUSTMENT
ON TXV APPLICATIONS
1. Run system at least 10 minutes to allow pressure to
stabilize.
2. Temporarily install thermometer on liquid (small) line
near pressure switches with adequate contact and
insulate for best possible reading.
3. Check subcooling and superheat. Systems with TXV
application should have a subcooling and superheat of
12 - 15 ºF.
a.If subcooling and superheat are low, adjust TXV
to 9 ± 3ºF then check subcooling.
b.If subcooling is low and superheat is high, add
charge to raise subcooling to 10ºF then check
superheat.
c.If subcooling and superheat are high, adjust TXV
valve to 12 - 15 ºF then check subcooling.
d.If subcooling is high and superheat is low, adjust
TXV valve to 12 - 15 ºF superheat and remove
charge to lower the subcooling to 2 - 15 ºF.
The TXV should NOT be adjusted at light load conditions
55º to 60ºF, under such conditions only the subcooling
can be evaluated. This is because suction pressure is
dependent on the indoor coil match, indoor airflow, and
wet bulb temperature. NOTE: Do NOT adjust charge
based on suction pressure unless there is a gross
undercharge.
4. Disconnect manifold set. Installation is complete.
1. Run system at least 10 minutes to allow pressure to
stabilize.
2. Temporarily install thermometer on suction (large) line
near compressor with adequate contact and insulate for
best possible reading.
Refrigerant liquid is considered subcooled when its temperature is lower than the saturation temperature corresponding
to its pressure. The degree of subcooling equals the degrees
of temperature decrease below the saturation temperature
at the existing pressure.
1. Attach an accurate thermometer or preferably a thermocouple type temperature tester to the liquid line close to
the pressure switch.
2. Install a high side pressure gauge on the high side (liquid)
service valve at the front of the unit.
3. Record the gauge pressure and the temperature of the
line.
4. Compare the hi-pressure reading to the "Required Liquid
Line Temperature" chart on the following page. Find the
hi-pressure value on the left column. Follow that line right
to the column under the design subcooling value. Where
the two intersect is the required liquid line temperature.
Alternately you can convert the liquid line pressure
gauge reading to temperature by finding the gauge
reading in Temperature - Pressure Chart and reading to
the left, find the temperature in the °F. Column.
5. The difference between the thermometer reading and
pressure to temperature conversion is the amount of
subcooling.
Add charge to raise subcooling. Recover charge to lower
subcooling.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.
EXAMPLE:
a. Liquid Line Pressure = 417
b. Corresponding Temp. °F. = 120°
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling subtract 109°F from
120°F.
The difference is 11° subcooling. See the specification sheet
or technical information manual for the design subcooling
range for your unit.
S-110 CHECKING EXPANSION VALVE OPERA-
TION
1. Remove the remote bulb of the expansion valve from the
suction line.
2. Start the system and cool the bulb in a container of ice
water, closing the valve. As you cool the bulb, the
suction pressure should fall and the suction temperature
will rise.
3. Next warm the bulb in your hand. As you warm the bulb,
the suction pressure should rise and the suction temperature will fall.
4. If a temperature or pressure change is noticed, the
expansion valve is operating. If no change is noticed, the
valve is restricted, the power element is faulty, or the
equalizer tube is plugged.
5. Capture the charge, replace the valve and drier and
evacuate.
S-111 FIXED ORIFICE RESTRICTOR DEVICES
The fixed orifice restrictor device (flowrator) used in conjunction with the indoor coil is a predetermined bore (I.D.).
It is designed to control the rate of liquid refrigerant flow into
an evaporator coil.
The amount of refrigerant that flows through the fixed orifice
restrictor device is regulated by the pressure difference
between the high and low sides of the system.
In the cooling cycle when the outdoor air temperature rises,
the high side condensing pressure rises. At the same time,
the cooling load on the indoor coil increases, causing the
low side pressure to rise, but at a slower rate.
Since the high side pressure rises faster when the temperature increases, more refrigerant flows to the evaporator,
increasing the cooling capacity of the system.
When the outdoor temperature falls, the reverse takes
place. The condensing pressure falls, and the cooling loads
on the indoor coil decreases, causing less refrigerant flow.
A strainer is placed on the entering side of the tube to prevent
any foreign material from becoming lodged inside the fixed
orifice restriction device.
If a restriction should become evident, proceed as follows:
1. Recover refrigerant charge.
2. Remove the orifice or tube strainer assembly and replace.
3. Replace liquid line drier, evacuate and recharge.
CHECKING EQUALIZATION TIME
During the "OFF" cycle, the high side pressure bleeds to the
low side through the fixed orifice restriction device. Check
equalization time as follows:
1. Attach a gauge manifold to the suction and liquid line dill
valves.
2. Start the system and allow the pressures to stabilize.
3. Stop the system and check the time it takes for the high
and low pressure gauge readings to equalize.
If it takes more than seven (7) minutes to equalize, the
restrictor device is inoperative. Replace, install a liquid line
drier, evacuate and recharge.
49
Page 50
SERVICING
S-112 CHECKING RESTRICTED LIQUID LINE
When the system is operating, the liquid line is warm to the
touch. If the liquid line is restricted, a definite temperature
drop will be noticed at the point of restriction. In severe cases,
frost will form at the restriction and extend down the line in the
direction of the flow.
Discharge and suction pressures will be low, giving the
appearance of an undercharged unit. However, the unit will
have normal to high subcooling.
Locate the restriction, replace the restricted part, replace
drier, evacuate and recharge.
S-115 COMPRESSOR BURNOUT
When a compressor burns out, high temperature develops
causing the refrigerant, oil and motor insulation to decompose forming acids and sludge.
If a compressor is suspected of being burned-out, attach a
refrigerant hose to the liquid line dill valve and properly remove
and dispose of the refrigerant.
NOTICE
Violation of EPA regulations may result in fines
or other penalties.
S-113 OVERCHARGE OF REFRIGERANT
An overcharge of refrigerant is normally indicated by an
excessively high head pressure.
An evaporator coil, using an expansion valve metering device,
will basically modulate and control a flooded evaporator and
prevent liquid return to the compressor.
An evaporator coil, using a fixed orifice restrictor device
(flowrator) metering device, could allow refrigerant to return to
the compressor under extreme overcharge conditions.
Also with a fixed orifice restrictor device (flowrator) metering
device, extreme cases of insufficient indoor air can cause
icing of the indoor coil and liquid return to the compressor, but
the head pressure would be lower.
There are other causes for high head pressure which may be
found in the "Service Problem Analysis Guide."
If other causes check out normal, an overcharge or a system
containing non-condensables would be indicated.
If this system is observed:
1. Start the system.
2. Remove and capture small quantities of refrigerant as
from the suction line access fitting until the head pressure
is reduced to normal.
3. Observe the system while running a cooling performance
test. If a shortage of refrigerant is indicated, then the
system contains non-condensables.
S-114 NON-CONDENSABLES
If non-condensables are suspected, shut down the system
and allow the pressures to equalize. Wait at least 15
minutes. Compare the pressure to the temperature of the
coldest coil since this is where most of the refrigerant will be.
If the pressure indicates a higher temperature than that of the
coil temperature, non-condensables are present.
Non-condensables are removed from the system by first
removing the refrigerant charge, replacing and/or installing
liquid line drier, evacuating and recharging.
Now determine if a burn out has actually occurred. Confirm
by analyzing an oil sample using a Sporlan Acid Test Kit, AK3 or its equivalent.
Remove the compressor and obtain an oil sample from the
suction stub. If the oil is not acidic, either a burnout has not
occurred or the burnout is so mild that a complete clean-up
is not necessary.
If acid level is unacceptable, the system must be cleaned by
using the clean-up drier method.
CAUTIO N
Do no t allow the slud ge or oil to con tact the skin .
Severe burns may result.
NOTE: The Flushing Method using R-11 refrigerant is no
longer approved by Amana® Brand Heating-Cooling.
Suction Line Drier Clean-Up Method
The POE oils used with R410A refrigerant is an excellent
solvent. In the case of a burnout, the POE oils will remove any
burnout residue left in the system. If not captured by the
refrigerant filter, they will collect in the compressor or other
system components, causing a failure of the replacement
compressor and/or spread contaminants throughout the
system, damaging additional components.
Use part number RF000127 suction line filter drier kit. This
drier should be installed as close to the compressor suction
fitting as possible. The filter must be accessible and be
rechecked for a pressure drop after the system has operated
for a time. It may be necessary to use new tubing and form
as required.
NOTE: At least twelve (12) inches of the suction line
immediately out of the compressor stub must be discarded
due to burned residue and contaminates.
1. Remove compressor discharge line strainer.
2. Remove the liquid line drier and expansion valve.
3Purge all remaining components with dry nitrogen or
carbon dioxide until clean.
4. Install new components including liquid line drier.
5. Braze all joints, leak test, evacuate, and recharge system.
50
Page 51
SERVICING
6. Start up the unit and record the pressure drop across the
drier.
7. Continue to run the system for a minimum of twelve (12)
hours and recheck the pressure drop across the drier.
Pressure drop should not exceed 6 PSIG.
8. Continue to run the system for several days, repeatedly
checking pressure drop across the suction line drier. If
the pressure drop never exceeds the 6 PSIG, the drier has
trapped the contaminants. Remove the suction line drier
from the system.
9. If the pressure drop becomes greater, then it must be
replaced and steps 5 through 9 repeated until it does not
exceed 6 PSIG.
NOTICE: Regardless, the cause for burnout must be determined and corrected before the new compressor is started.
S-200 CHECKING EXTERNAL STATIC PRESSURE
The minimum and maximum allowable duct static pressure
is found in the Technical Information Manual.
Too great of an external static pressure will result in insufficient air that can cause icing of the coil, whereas too much
air can cause poor humidity control, and condensate to be
pulled off the evaporator coil causing condensate leakage.
Too much air can cause motor overloading and in many cases
this constitutes a poorly designed system. To determine
proper air movement, proceed as follows:
1. Using a draft gauge (inclined manometer) measure the
static pressure of the return duct at the inlet of the unit,
(Negative Pressure).
NOTE: Both readings may be taken simultaneously and read
directly on the manometer if so desired.
4. Consult proper table for quantity of air.
If the external static pressure exceeds the minimum or
maximum allowable statics, check for closed dampers, dirty
filters, undersized or poorly laid out ductwork.
S-201 CHECKING TEMPERATURE RISE
Temperature rise is related to the BTUH output of the unit and
the amount of air (CFM) circulated over the heat exchanger.
All units are designed for a given range of temperature
increase. This is the temperature of the air leaving the unit
minus the temperature of the air entering the unit.
The more air (CFM) being delivered through a given unit the
less the rise will be; so the less air (CFM) being delivered, the
greater the rise. The temperature rise should be adjusted in
accordance to a given unit specifications and its external
static pressure.
1. Check BTUH input to unit do not exceed input rating
stamped on rating plate.
2. Take entering and leaving air temperatures.
3. Select the proper speed tap or dip switch setting for direct
drive units.
4. Take motor amperage draw to determine that the motor is
not overloaded during adjustments.
INCLINED
MANOMETER
SUPPLY
RETURN
Total External Static
2. Measure the static pressure of the supply duct, (Positive
Pressure).
3. Add the two readings together.
T
SUPPLY
SUPPLY
RETURN
T
RETURN
RISE = SUPPLY -TRETURN
Checking Temperature Rise
T
51
Page 52
SERVICING
S-300 TESTING PRIMARY LIMIT CONTROL
APG/GPG units use a snap-disk type primary limit device.
Sometimes referred to as "stat on a stick". The limit setting
is fixed and must not be readjusted in the field.
COLOR
Volt / Ohm
Meter
TESTING PRIMARY LIMIT CONTROL
Refer to the specification section to determine the proper limit
cutout temperature for the model being serviced.
In all instances the limit control is wired in series with the
ignition control.
If the temperature within the furnace should exceed this
setting, the control will open, de-energizing the ignition
control which in turn will open the electrical circuit to the gas
valve.
The control will automatically reset when the temperature
within the combustion chamber is sufficiently lowered.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove electrical power to unit. Some units may have
more than one source of power.
2. Remove the wires from the limit control terminals.
3. Using an ohmmeter, test for continuity across the two
terminals.
4. If limit test open allow unit to cool and retest.
5. If still open, replace the control.
IDENTIFYING
SLEEVES
S-301 TESTING AUXILIARY LIMIT
The auxiliary limit control is a preset nonadjustable control
mounted in the blower compartment area.
It is connected in series with the rollout switch wiring to the
gas valve. If its temperature should be exceeded, it will open,
interrupting the voltage to the gas valve causing it to open.
An additional limit (primary limit) control is required for safety
control of high temperature within the furnace or ductwork.
AUX. LIM I T
HIGH VOL TAGE!
Disconnect ALL power before servicing
or inst all ing th is u ni t. M ult ip le po wer
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove the wires from the auxiliary limit control terminals.
2. Using an ohmmeter, test for continuity across the two
terminals. No reading indicates the control is open. Push
the red reset button, test again - if still open, replace the
control.
52
Page 53
SERVICING
VOLT / OHM
MET ER
R E D
RESET
BUTTON
C OLO R
ID ENTIFYING
T AB
TESTING AUXILIARY LIMIT CONTROL
S-302 CHECKING FLAME ROLLOUT SWITCH
APG/GPG units are equipped with a temperature-activated
manual reset control. This control is mounted to the manifold
assembly and is wired in series with the auxiliary limit and
gas valve. The control is designed to open should a flame roll
out occur. An over firing condition or flame impingement on
the heat shield can also cause the control to open.
If the rollout control has opened, the circuit between the
ignition control and gas valve will be interrupted and the
ignition control module will go into lockout. The servicer
should reset the ignition control by opening and closing the
thermostat circuit. The servicer should look for the ignitor
glowing which indicates there is power to the ignition control.
The servicer should measure the voltage between each side
of the rollout control and ground while the ignition control is
try to power the gas valve.
If a limit switch opens, the indoor blower is energized on heat
speed and the induced draft blower is energized. The LED
on the control flashes "4" to indicate an open limit switch.
The blower and inducer remain on while the limit switch is
open. The gas valve is de-energized. Power to the thermostat "R" is removed while the limit switch is open.
When the limit switch re-closes, the induced draft motor runs
through its post purge and the indoor blower goes through the
heat off delay.
If a call for heat exists when the limit switch re-closes, the
control goes through a pre-purge period and then makes an
ignition attempt. The indoor blower remains on (for the delay
off time) during the re-ignition attempt.
1. If no voltage is measured on either side of control it
indicates ignition control or wiring to control problem.
2. If voltage is measured on one side of the control and
not the other, it indicates the control is open.
3. If voltage is measured on both sides of the control the
wiring to gas valve or valve is at fault.
Servicing procedure with furnace not firing.
1. Confirm that the outer door was in place and all screws
tightened. (No leaks under the door.)
2. Check to see if any damage was done to the furnace
especially the wiring.
3. Confirm that heat exchanger is not obstructed by feeling
for discharge air from the flue hood when the combustion
blower is running but the unit is not firing.
If the above steps do not suggest the reason the control has
tripped the furnace should be fired.
1. Remove the heating compartment door.
2. Turn of the power or open the thermostat circuit.
3. Reset the rollout control.
4. Turn power on and put the unit into a call for heating.
VOLT / OHM
M E TER
RED
RESET
BUTTON
CHECKING FLAME ROLLOUT SWITCH
Limit Switch Operation (Applies to Primary, Auxiliary,
and Roll Out Limits) DSI systems.
CO LO R
IDENTIFYING
TAB
CAUTION
Flame rollout could occur. Keep face and hands a
safe distan ce from burn er area.
5.Look under the heat shield as the unit is running.
Flames should be drawn into firing tubes.
a.If only one burners flame is not drawn into the tube,
that tube is restricted.
b.If, without the air circulation blower running, all
flames are not drawn into the tubes either the
collector box, combustion blower, or flue outlet is
obstructed. If the combustion blower or flue outlet
is obstructed, the pressure switch should have
opened preventing the unit from firing, also inspect
the unit pressure switch and wiring.
c.If the burner flame is not drawn into the tube only
when the air circulation blower is running, then a
cracked heat exchanger tube is present.
53
Page 54
SERVICING
S-303 TESTING INDUCER MOTOR
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Disconnect the motor wire leads from its connection point
at integrated ignition control module.
2. Using and ohmmeter, test for continuity between each of
the motor leads.
3. Touch one probe of the ohmmeter to the motor frame
(ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is obtained
to ground, replace the motor.
4. After completing check and/or replacement of induced
draft blower motor.
5. Turn on electrical power and verify proper unit operation.
Gas Valve
On/Off
Switch
Outlet
Outlet Pressure
Tap
Inlet Pressure
Tap
Inlet
W/R 36G54-238
WHITE ROGERS MODEL 36G 2-STAGE GAS VALVE
S-304 TESTING GAS VALVE
Direct Spark Ignition (DSI) Systems
A combination redundant operator type gas valve which
provides all manual and automatic control functions required
for gas fired heating equipment is used on 13 SEER models.
A two-stage combination redundant operator type gas valve
which provides all manual and automatic control functions
required for gas fired heating equipment is used on 15 SEER
models.
The valve provides control of main burner gas flow, pressure
regulation, and 100 percent safety shut-off.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Ensure gas valve and main gas supply are on.
2. Using a voltmeter, check from the purple and blue wires
on 1 stage gas valves and from C and M on 2 stage gas
valves for 24 volts to gas valve.
3. If 24 volts are present and no gas flows through the valve,
replace valve.
W/R 36G22-202
WHITE ROGERS MODEL 36G 1-STAGE GAS VALVE
Pressu re Regulator
Inlet
Pressure
Tap
Gas Valve On/Off
Selector Switch
(under cap screw)
Outlet
Pressure
Tap
HONEYWELL MODEL VR8215 1-STAGE GAS VALVE
54
Page 55
SERVICING
S-305 CHECKING MAIN BURNERS
The main burners are used to provide complete combustion
of various fuels in a limited space, and transfer this heat of the
burning process to the heat exchanger.
Proper ignition, combustion, and extinction are primarily due
to burner design, orifice sizing, gas pressure, primary and
secondary air, vent and proper seating of burners.
BECKETT BURNER
WARNING
Disconnect gas and el ectr ical po wer sup ply.
In checking main burners, look for signs of rust, oversized and
undersized carry-over ports restricted with foreign material,
etc.
S-306 CHECKING ORIFICES
A predetermined fixed gas orifice is used in all of these
furnaces. That is an orifice which has a fixed bore and
position.
A
GAS
STREAM
B
DENT OR
BURR
GAS
STREAM
The length of Dimension "A" determines the angle of Gas
Stream Defraction, "B".
A dent or burr will cause severe deflection of gas stream.
No resizing should be attempted until all factors are taken into
consideration such as inlet manifold gas pressure, alignment, and positioning, specific gravity and BTU content of the
gas being consumed.
The only time resizing is required is when a reduction in firing
rate is required for an increase in altitude.
Orifices should be treated with care in order to prevent
damage. They should be removed and installed with a boxend wrench in order to prevent distortion. In no instance
should an orifice be peened over and redrilled. This will
change the angle or deflection of the vacuum effect or
entraining of primary air, which will make it difficult to adjust
the flame properly. This same problem can occur if an orifice
spud of a different length is substituted.
B
WARNING
Discon nec t gas an d ele ctric al po we r su pply.
1. Check orifice visually for distortion and/or burrs.
2. Check orifice size with orifice sizing drills.
3. If resizing is required, a new orifice of the same physical
size and angle with proper drill size opening should be
installed.
S-307 CHECKING GAS PRESSURE
Gas inlet and manifold pressures should be checked and
adjusted in accordance to the type of fuel being consumed.
55
Page 56
SERVICING
A
WARNING
Disconnect gas an d electrical powe r supply.
1. Connect a water manometer or adequate gauge to the
inlet pressure fitting of the gas valve.
2. Remove the pressure tap fitting at the manifold if provided
or check at the gas valve outlet fitting and connect another
manometer or gauge.
Open to
Atmosphere
Inlet
Pressure
Tap
Gas Valve On/Off
Selector Switch
Pressu re Regulator
(under cap screw)
Outlet
Pressure
Tap
Open to
tmosphere
Low Pressure
Adjust
High Pressure
Adjust
Open to
Atmosphere
Outlet
Gas Valve
On/Off
Switch
Manometer
Inle t Pressure
Hose
Tap
Outlet Pressur e
Tap
Manometer
Hose
Inlet
Open to
Atmosphere
Manometer
WHITE ROGERS MODEL 36G 2-STAGE GAS VALVE
Open to
Atmosphere
Open to
Atmosphere
Inlet Pressure
Manifold
Pressure
HONEYWELL MODEL VR8215 1-STAGE GAS VALVE
MEASURING INLET AND MANIFOLD GAS PRESSURE
With Power ON:
WARNING
Line Voltage now present.
3. Put furnace into heating cycle and turn on all other gas
consuming appliances.
For NATURAL GAS:
a.Inlet pressure should be a nominal 7" w.c.
b.(2 stage heat models only) Manifold pressure on
low stage should be2.0” w.c. ± .3"w.c.
c.Manifold pressure for 1 stage heat models and high
stage for 2 stage heat models should be 3.5” ±
.3"w.c.
For PROPANE GAS:
a.Inlet pressure should be a nominal 11" w.c.
b.(2 stage heat models only) Manifold pressure on
low stage should be 6" w.c.
c.Manifold pressure for 1 stage heat models and high
stage for 2 stage heat models should be 10” w.c.
Inlet Pressure
WHITE ROGERS MODEL 36G 1-STAGE GAS VALVE
56
Manifold
Pressure
Manifold Gas Pressure
Natural Gas3.5" w.c.
Propane Gas10.0" w.c.
Single Stage
Manifold Gas Pressure
Gas
Natural Low Stage 1.6 - 2.2" w.c. 2.0" w.c.
Propane Low Stage 5.7 - 6.3" w.c. 6.0" w.c.
High Stage 3.2 - 3.8" w.c. 3.5" w.c.
High Stage 9.7 - 10.3" w.c. 10.0" w.c.
Range
Nominal
Two Stage
Page 57
SERVICING
If operating pressures differ from above, make necessary
pressure regulator adjustments, check piping size, etc., and/
or consult with local utility.
S-308 CHECKING FOR DELAYED IGNITION
Delayed ignition is a delay in lighting a combustible mixture
of gas and air which has accumulated in the combustion
chamber.
When the mixture does ignite, it may explode and/or rollout
causing burning in the burner venturi.
If delayed ignition should occur, the following should be
checked:
1. Improper gas pressure - adjust to proper pressure. (See
S-307)
2. Improper burner positioning - burners should be in locating slots, level front to rear and left to right.
3. Carry over (lighter tube or cross lighter) obstructed clean.
4. Main burner orifice(s) deformed, or out of alignment to
burner - replace.
S-309 CHECKING FOR FLASHBACK
Flashback will also cause burning in the burner venturi, but is
caused by the burning speed being greater than the gas-air
flow velocity coming from a burner port.
Flashback may occur at the moment of ignition, after a burner
heats up or when the burner turns off. The latter is known as
extinction pop.
Since the end results of flashback and delayed ignition can
be the same (burning in the burner venturi) a definite attempt
should be made to determine which has occurred.
If flashback should occur, check for the following:
1. Improper gas pressure - adjust to proper pressure. See
S-307.
2. Check burner for proper alignment and/or replace burner.
33.Improper orifice size - check orifice for obstruction.
If the pressure switch opens before the ignition period, the
induced draft blower will remain on and the control will stay
in pre-purge until the pressure switch is closed for an entire
15 second pre-purge period. The LED will flash a code of "3"
to indicate open pressure switch.
If the pressure switch opens after the gas valve has been
energized, the control will de-energize the gas valve and run
the indoor blower through the heat off delay. The inducer
stays on until the pressure switch re-closes. Then the
control makes another ignition attempt.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Remove wires from the electrical terminals.
2. Using a VOM check from Common to NO (Normally
Open) - should read open.
If switch reads as noted proceed to Step 3, otherwise
replace control.
3. Remove the pressure control hose from the control and
interconnect with an inclined manometer as shown:
HOSE
TO J-TUBE
1/4" CO PPER TEE
PRESSURE SWITCH
INCLINED
MANOMETER
Reconnect wires to the Common and NO terminals.
With Power ON:
S-310 CHECKING PRESSURE CONTROL
A pressure control device is used to measure negative
pressure at the induced draft blower motor inlet to detect a
partial or blocked flue.
Pressure Switch Operation (DSI Direct Spark System)
The pressure switch is ignored unless there is a call for heat.
When the control receives a call for heat, the control checks
to see that the pressure switch is open. If the control sees
that the pressure switch is closed before the induced draft
blower is energized, the LED will flash a code of "2" (to
indicate the pressure switch is stuck closed) and the inducer
will remain off until the pressure switch opens.
WARNING
Line Voltage now present.
4. Energize furnace for heating cycle. The induced draft
blower motor will begin to run. The inclined manometer
should read approximately -1.2" ± 0.3" W.C with no
combustion.
5. Remove and check the two electrical wires and using the
VOM check from Common to NO (Normally Open), it
should read closed (with I.D. motor running). If not as
above, replace pressure control.
6. Reconnect all wires to the control and place in heating
cycle.
7. As the unit fires on high stage, the inclined manometer
negative pressure will drop to -1.0" ± 0.3" W.C.
57
Page 58
SERVICING
8. If not as listed, replace control.
Note: the pressure switch must be mounted with the dia-
phragm in a vertical position.
S-311 HIGH ALTITUDE APPLICATION
High Altitude Derate - U.S. Installations Only
IMPORTANT NOTE: The gas/electric units naturally derate
with altitude. Do not attempt to increase the firing rate by
changing orifices or increasing the manifold pressure. This
can cause poor combustion and equipment failure. At all
altitudes, the manifold pressure must be within 0.3 inches
W.C. of that listed on the nameplate for the fuel used. At all
altitudes and with either fuel, the air temperature rise must
be within the range listed on the unit nameplate. Refer to the
Installation Manual provided with the LP kit for conversion
from natural gas to propane gas and for altitude adjustments.
When this package unit is installed at high altitude, the
appropriate High Altitude orifice kit must be installed. As
altitude increases, there is a natural reduction in the density
of both the gas fuel and combustion air. This kit will provide
the proper design certified input rate within the specified
altitude range. High altitude kits are not approved for use in
Canada. For installations above 2,000 feet, use kit HA-02.
The HA-02 kit is used for both Natural and LP gas at high
altitudes.
Use LPM-05 (2 stage heat models) or LPT-03 (1 stage heat
models) propane conversion kit for propane conversions at
altitudes below 2000 feet. Natural gas installations below
2000 feet do not require a kit.
(LPT-00A may be used on models with AA revisions. LPT03 is compatible with both the White Rodgers and the
Honeywell gas valves.)
S-313 TESTING IGNITION CONTROL MODULE
NOTE: Failure to earth ground the unit, or a high resistance
connection in the ground may cause the control to lockout
due to failure to flame sense.
L2
FS
C9
U6
5
4
U7
3
U4
2
1
U5
INDUCER
LOW
T1
K4
Q3
T2
U3
HIGH
U1
K3K5
L1
U2
LOW
ODF
K7
HIGH
PARK
K6
P2
K2
K1
For propane conversions above 2000 feet, high altitude kit
HA-02 is required in addtion to the propane conversion kit.
Natural gas and LP gas installations at altitudes > 2000 ft
INPUT/BURNER
U.S. BURNER ORIFICE45/55 47/55 47/56- 47/56 48/57 48/58 49/58
CANADA BURNER ORIFICE45/55-- 48/57----
INPUT/BURNER
U.S. BURNER ORIFICE44/55 44/55 45/56- 45/56 46/57 47/58 47/58
CANADA BURNER ORIFICE44/55-- 47/57----
INPUT/BURNER
U.S. BURNER ORIFICE43/55 53/55 44/56- 44/56 44/56 45/57 45/57
CANADA BURNER ORIFICE43/55-- 46/57----
HIGH ALTITUDE
KIT
HA02
HIGH ALTITUDE
KIT
HA02
HIGH ALTITUDE
KIT
HA02
20,000 BTUH NAT/20,OOO BTUH/L.P.
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
22,500 BTUH NAT/20,OOO BTUH/L.P.
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
25,000 BTUH NAT/20,OOO BTUH/L.P.
ELEVATION ABOVE SEA-LEVEL (FEET)
2000 3000 4000 4500 5000 6000 7000 8000
58
180
SPEEDUP
SW1
FAULT
RECALL
150
120
90
BLOWER
OFF
DELAY
NONE
5 MIN
10MIN
STAGE
DELAY
F1
ECON
RCW1W2GY2
Y1
PCBAG100 DSI Control Board
Testing Direct Spark Ignition (DSI) Systems
PCBAG100 Board
Heating Mode
Indoor thermostat calling for heat (15 second prepurge time
and 7 second trial for ignition).
1. Check for 230 volts from L1 terminal of control module
to L2. No voltage - check wire connections, continuity,
etc.
Page 59
SERVICING
2. Check for 24 volts at "R" to "C" thermostat terminals.
a.No voltage - check 3 amp automotive type fuse on
control board. A blown fuse could indicate a short
in the 24 volt circuit (thermostat or limit circuit).
b.Voltage Present - check limit and rollout (S-301
and S-302). If limit and rollout are closed, then
check for 24 VAC at the gas valve terminals.
c.No 24 VAC at gas valve - check 9 pin connector
and wires from ignition control to gas valve. If wires
and connections at 9 pin connector check good,
replace ignition control.
d.Voltage present at gas valve - replace gas valve.
Testing High Stage Heat Operation with Low Stage
Heat Operating:
1. Board set for 2 stage thermostat:
a.Check for 24 Volts at thermostat terminals W2
and C on the control board.
b.No voltage - check thermostat and thermostat
wiring.
c.Voltage present - check for 24 volts at gas valve
terminals C and HI.
d.No voltage present at valve - check 9 pin connector
and wires from ignition control to gas valve. If wires
and connections at 9 pin connector check good,
replace ignition control.
e.Voltage present at gas valve - replace gas valve.
2. Board set for 1 stage thermostat:
a.Wait the selected delay time (either 5 or 10
minutes, depending on jumper setting).
b.Check for 24 volts at gas valve terminals C and HI.
c.No voltage present - check 9 pin connector and
wires from ignition control to gas valve. If wires and
connections at 9 pin connector check good,
replace ignition control.
d.Voltage present at gas valve terminals C and HI -
replace valve.
b.Voltage present - check pressure switch circuit. If
pressure switch circuit checks closed, proceed to
step 4.
4. Check for 24 volts at contactor coil.
a.No voltage - check 6 pin connector and wires from
contactor coil to 6 pin connector on control board.
If wires and connector check good, replace control.
b.Voltage present - replace contactor.
Testing High Stage Cooling Operation with Low Stage
Cooling Operating:
1. Board set for 2 stage thermostat:
a.Check for 24 volts at thermostat terminals C and
Y2 on control board.
bNo voltage - check thermostat and thermostat
wiring.
c.Voltage present - check pressure switch circuit. If
pressure switch circuit checks closed, proceed to
next step.
d.Check for 24 volts to compressor unloader sole-
noid. If no voltage present, check 6 pin connector
and wires from compressor unloader solenoid to 6
pin connector on board. If connector and wires
check good, replace control.
2. Board set for 1 stage thermostat:
a.Wait the selected delay time (either 5 or 10
minutes, depending on jumper setting)
b.Check for 24 volts at compressor unloader sole-
noid.
c.No voltage - check 6 pin connector and wires from
compressor unloader solenoid to 6 pin connector
on board. If connector and wires check good,
replace control.
Cooling Mode
Indoor thermostat calling for cool.
1. Check for 230 volts from L1 terminal of control module to
L2. No voltage - check wire connections, continuity, etc.
2. Check for 24 volts at R and C thermostat terminals on
ignition control.
a.No voltage - check 3 amp automotive type fuse on
control board. A blown fuse could indicate a short
in the 24 volt circuit.
b.Voltage present - proceed to step 3.
3. Check for 24 volts at thermostat terminals C and Y1.
a.No voltage - check thermostat wiring and thermo-
stat.
59
Page 60
SERVICING
LED
Flashes/Status
Internal Control Fault, M ic ro Controller
Off
Detected Hardware Failure, or Gas V alve
Detec te d E nergize d When it S hou ld be
De-energized
1Lock out Due t o E x ce s s ive Retries
2Pressure Switch Stuck Closed
3Pressure Switch Stuck Open
4Open High Temp erature Lim it
5
Flam e P res ent O uts id e the F lam e
Detect Mode
6Com press or Short Cy c le Delay A c t ive
7
8
9
Limit Opened Five Times within the
Sam e Call for Heat
Indoor Thermos t at/ O utd oor Thermos t at
is Op en
Pres s ure S witc h/ Los s of Charge Swit c h
is Op en
St eady O NNormal
Red LED Fault Codes
LED
Flashes/Status
2
Flame Present Outside the Flame Detect
Mode
1Low Flame Signal Current
Steady ONNormal Flame
OFFNo Flame Present
Amber LED Flame Status Codes
NOTE: The flash rate is 0.25 seconds on, 0.25 seconds
off, with a 2-second pause between codes.
NORMAL SEQUENCE OF OPERATION
(DSI Direct Spark Ignition System)
PCBAG123 Board
1. Thermostat calls for heat by energizing "W". The control
checks the pressure switch for open condition. If the
pressure switch is closed the control will flash code "3"
and wait for the pressure switch to open.
2. The induced draft motor is energized and the control
flashes code "2" and waits for the pressure switch to
close. Once the pressure switch is closed, the LED stops
flashing and the control begins timing the 15 second prepurge.
System Condition
Flame Condition
Blower Off Delay Setti ngs
L2 L2 L2
Diagnostic LED
COOL HEAT
UNUSED
L2
L1 D1
L1
FS
2
3
54
6
987
121110
1
speed up
Transformer
DSI Control Board
3. The control energizes the spark igniter and gas valve for
7 seconds. If flame is established, the control goes into
a 30 second heat on delay.
4. The indoor blower is energized at the heat speed after a
30 second on delay.
5. The control monitors the safety circuit inputs, flame, and
thermostat during operation.
6. When the thermostat is satisfied, the gas valve is deenergized and the induced draft blower remains on for a
29 second post purge. The indoor blower remains on for
the selected heat blower off delay (90, 120, or 150
seconds). Indoor blower off timing begins when thermostat call for heat ends.
Testing Direct Spark Ignition (DSI) systems
Thermostat calling for heat (15 second prepurge time and 7
second trial for ignition).
1. Check for 230 VAC from L1 terminal of control module to
L2. No voltage - check wire connections, continuity, etc.
2. Check for 24 VAC at "R" to "C" thermostat terminals.
a.No voltage - check 3 amp automotive type fuse on
control board. A blown fuse would indicate a short
in the 24 VAC circuit (thermostat or limit circuit).
b.Voltage Present - check limit, auxiliary limit and
rollout (S-300, S-301 and S-302). If limit, auxiliary
limit and rollout are closed, then check for 24 VAC
at the gas valve terminals.
No 24 VAC at gas valve - replace Control board.
60
Page 61
SERVICING
B1809918 Ignition Board Fault Codes
Status Light
OnNormal Operation
Off
1 Blink
2 BlinksPressure Switch Open Check Pressure Switch
3 Blinks
4 Blinks
5 BlinksFalse Flame SensedSticking Gas Valve
6 Blinks
Equipment Status
No Power or
Internal Control Fault
Ignition Failure,
Open Rollout Switch,
or Open Aux. Limit
Switch
Pressure Switch
Closed
Open Main Limit
Switch
Compressor Output
Delay
Check
Check Input Power,
Check Fuse on Control,
Replace Control
Check Gas Flow,
Check Gas Pressure,
Check Gas Valv e,
Check Flame Sensor,
Check Flame Rollout,
Check Aux. Limit.
Check Pressure Switch
Main Limit Switch Open
3 Minute Compressor
Anti-Cycle Timer
NOTE: The flash rate is 0.25 seconds on, 0.25 seconds
off, with a 2-second pause between codes.
S-314 CHECKING FLAME SENSOR
A flame sensing device is used in conjunction with the ignition
control module to prove combustion. If a microamp signal is
not present the control will de-energize the gas valve and
"retry" for ignition or lockout.
DSI Direct Spark Ignition Systems
HIGH VOLTAGE!
Disconnect ALL power before servicing
or insta llin g th is un it. M ult iple powe r
sources may be present. Failure to do so
may cause property damage, personal injury
or death.
1. Disconnect the flame sensor wire from terminal FS of the
ignition control module.
Flame
Sensor
Flame Sensor
2. Connect a microamp meter in series with this wire and
terminal FS.
3. Be sure the negative side of the meter is to the wire and
the positive of the meter is to terminal FS.
4. Turn on Power.
WARNING
Line Voltage now present.
5. With Power ON, Place the unit into a heating cycle.
6. As soon as flame is established a microamp reading
should be evident once proof of flame (microamp reading)
is established, the hot surface ignitor will be de-energized.
7. The nominal microamp reading is 4 microamps.
8. If the microamp current is less than 0.5 microamp the
control will lockout and flash a code of 1 flash after
attempting to reestablish flame sense.
9. If the microamp reading is less than the minimum specified, check for high resistance wiring connections, the
distance (3/16") between the sensor and burner, flame
sensor connections, dirty flame sensor or poor grounding.
10.If no reading, check for continuity on all components and
if good - replace ignition control module.
NOTE: Contaminated fuel or combustion air can create a
nearly invisible coating on the flame sensor. This coating
works as an insulator causing a loss in the flame sense
signal. If this situation occurs the flame sensor must be
cleaned with steel wool. Do not use sand paper, the silicone
in sand paper will further contaminate the sensor.
61
Page 62
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
64
1K RELAY
CONTACTS
WB
T
1
T
R
ECONOMIZER
TR
TR1
P
JUMPER
1
P
BLUE
INSTALL AS SHOWN
POTENTIOMETER OPTIONAL
MINIMUM DAMPER POSITION
BARBER COLEMAN AD-931-105
1K
COIL
RELAY
1K RELAY
AB
WIRING DIAGRAM
GOODMAN MANUFACTURING CO.
50F
LOCKOUT
THERMOSTAT
COMPRESSOR
PINK
1K RELAY
2
13
ORANGE
WHITE
3
1
ENTHALPY
2
CONTROL
ORANGE
MODEL PGED(H)101/102 ECONOMIZER
GREEN
BLUE
C
G
YELLOW
Y
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
62
PINK
MULTI-STAGE T'STAT
GMC# CHT90-120
Y2
(OR EQUIVALENT)
Y1
GMC( CHT90-120 OR EQUIVALENT)
NOTE: RECOMMEND MULTI-STAGE T'S TAT
Page 63
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ECONOMIZER
GPC13MED102 & 103 FOR *PG13 & 15**M4*
(WIRING DIAGRAM FOR USE WITH ECONOMIZERS BUILT SINCE MARCH 2008)
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
(WIRING DIAGRAM FOR USE WITH ECONOMIZERS BUILT SINCE MARCH 2008)
63
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.