This manual is to be used by qualified, professionally trained HVAC technicians only. The
manufacturer does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its
lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the
safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate
service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
T
HIS UNIT SHOULD NOT BE CONNECTED TO. OR USED IN
CONJUNCTION WITH, ANY DEVICES THAT ARE NOT DESIGN CERTIFIED
FOR USE WITH THIS UNIT OR
NOT BEEN TESTED AND APPROVED BY THE MANUFACTURER
HAVE
ERIOUS PROPERTY DAMAGE OR PERSONAL INJURY, REDUCED UNIT
S
PERFORMANCE
AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF
DEVICES THAT HAVE NOT BEEN APPROVED OR CERTIFIED BY THE
MANUFACTURER
.
.
HIGH VOLTAGE
D
ISCONNECT
UNIT
F
AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH
ALL
POWER BEFORE SERVICING OR INSTALLING THIS
. M
ULTIPLE POWER SOURCE S MAY BE PRESENT
.
.
O
TO
PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLICANCE
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR
REPAIR (HEREINAFTER
,
.
MANUAL SHOULD SERVICE THE EQUIPMENT
BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SERVICE OR SERVICE PROCEDURES
ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY
RESULT
. IN
LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY
LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT
INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT
SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR
REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS
. THE
MANUFACTURER WILL NOT
. IF
YOU SERVICE THIS UNIT, YOU
ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE
. I
MPROPER
.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product.
For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at: customerservice@goodmanmfg.com
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
email us at: customerservice@goodmanmfg.com
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
2
Outside the U.S., call 1-713-861-2500.
Page 3
IMPORTANT INFORMATION
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
R
EFRIGERANTS ARE HEAVI ER THAN AIR
YOUR LUNGS OR IN ANY ENCLOSED SPACE
BREATHI NG OR DEATH
EVER PURGE REFRIGE RANT INTO AN ENCLOSED ROOM OR SPACE
• N
ALL REFRIGE RANTS MUST BE RECLA IMED
F AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE ARA
• I
BEFORE BEGINNING WORK
IQUID REFRIGERANT CAN BE VERY COLD
• L
BLINDNESS, AVOID CONTACT WITH REFRIGERANT AND WAR GLOVES AND
GOGGL ES
. IF
MEDICAL HELP IMMEDIATELY
• A
LWAYS FOLLOW
POISONOUS GAS WILL BE PRODUCED
:
LIQUID REFRIGERANT DOES CONTACT YOUR SKIN OR EYES, SEEK
EPA
REGULATIONS
. T
HEY CAN “PUSH OUT” THE OXYGEN IN
. TO
AVOID POSSIBLE DIFFICULTY IN
. BY
.
.
. TO
AVOI D POSSIBLE FROSTBITE OR
LAW
,
TO
AVOID POSSIBLE EXPLOSION
EVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLIN DER
• N
HEAT A CYLIN DER FOR FASTER CHARGIN G, PARTIALLY IMMERSE IT IN WARM
WATER
.
EVER FILL A CYLIN DER MORE THAN
• N
EVER ADD ANYTHING OTHER THAN
• N
TO AN
410A
LISTED OR CERTIFIED FOR THE TYPE OF REFRIGERANT USED
• S
TORE CYLIN DERS IN A COOL, DRY PLACE
PLATFORM OR A ROLLER
R-410A
:
CYLINDER
.
. THE
.
. N
EVER BURN REFRIGERANT, AS
.
TO
AVOID POSSIBLE EXPLOSION, USE ONLY RETU RNABL E (NOT DISPOSABLE
SERVICE CYLINDERS WHEN REMOVING REFRIGE RANT FROM A SYSTEM
• E
NSURE THE CYLINDER IS FREE OF DAMAGE WHICH COULD LEAD TO A
LEAK OR EXPLOSION
• E
NSURE THE HYDROSTATIC TEST DATE DOES NOT EXCEED
• E
NSURE THE PRESSURE RATING MEETS OR EXCEEDS
.
. IF
YOU MUST
80%
FULL OF LIQUID REFRIGERANT
R-22 TO AN R-22
SERVICE EQUIPMENT USED MUST BE
CYLIN DER OR
.
. N
EVER USE A CYLIN DER AS A
.
5
YEARS
.
400 PSIG.
.
R-
)
THE U
NITED STATES ENVIRONMENTAL PROTECT ION AGENC Y
HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND
OF
DISPOSAL
FOLLOW
LEAD
MAY
LOCAL
S
YSTEM CONTAMINA NTS, IMPROPER SERVICE PROCED URE AND/OR PHYSICAL
ABUSE AFFECTIN G HERMETIC COMPRESSOR ELECTRICAL TERMINALS MAY CAUSE
DANGEROUS SYSTEM VENTING
REFRIGE RANTS INTRODUCED INTO THIS UNIT
THESE REGULATIONS MAY HARM THE ENVIRONMENT AND CAN
TO
THEH IMPOSITION OF SUBSTANTIAL FINES
VARY BY JURISDICTION
EPA
OFFICE
. S
HOULD QUESTIONS ARISE, CONTACT YOUR
.
. T
.
("EPA")
. F
AILURE TO
HESE REGULA TIONS
The successful development of hermetically sealed refrigeration
compressors has completely sealed the compressor's moving
parts and electric motor inside a common housing, minimizing
refrigerant leaks and the hazards sometimes associated with
moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is a method
whereby electrical current is transmitted to the compressor
motor through terminal conductors which pass through the
compressor housing wall. These terminals are sealed in a
dielectric material which insulates them from the housing and
maintains the pressure tight integrity of the hermetic compressor. The terminals and their dielectric embedment are strongly
constructed, but are vulnerable to careless compressor installation or maintenance procedures and equally vulnerable to
internal electrical short circuits caused by excessive system
contaminants.
HEN IN DOUBT, DO NOT USE CYLINDER
W
TO
AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
OF
HANDLING
REFRIG ERANTS
.
.
In either of these instances, an electrical short between the
terminal and the compressor housing may result in the loss of
integrity between the terminal and its dielectric embedment. This
loss may cause the terminals to be expelled, thereby venting the
vaporous and liquid contents of the compressor housing and
system.
A venting compressor terminal normally presents no danger to
anyone, providing the terminal protective cover is properly in
place.
If, however, the terminal protective cover is not properly in place,
a venting terminal may discharge a combination of
(a) hot lubricating oil and refrigerant
(b) flammable mixture (if system is contaminated
with air)
in a stream of spray which may be dangerous to anyone in the
vicinity. Death or serious bodily injury could occur.
Under no circumstances is a hermetic compressor to be electrically energized and/or operated without having the terminal
protective cover properly in place.
See Service Section S-17 for proper servicing.
3
Page 4
PRODUCT IDENTIFICATION
AN Z 130181 AA
1234,56,7,8910,11
Brand
A -
Amana® brand
Type
N1 - 208/230V Single-Phase 60 Hz
Deluxe Split System
2 - 220/240V Single-Phase 50 Hz
Type3 - 208/230V Three-Phase 60 Hz
X:Condens er R-4 10A4 - 4 60V Three-Pha se 60 Hz
Z:Heat Pump R-410A5 - 380/415V Three-Phase 50 Hz
SEER
11 - 11 SEER
13 - 13 SEER
14 - 14 SEER
16 - 16 SEER
18 = 1-1/2 Tons
24 = 2 Tons
30 =
2-1/2 Tons
Major/Minor Revis ions
3-1/2 Tons
42 =
48 = 4 Tons
59 = 5 Tons
Engineering
Voltage
Nominal Capacity
36 = 3 Tons60 = 5 Tons
61 = 5 Tons
4
Page 5
PRODUCT IDENTIFICATION
SS Z 141 AA
1234,5910,11
Brand
G
Goodman® brand
(Standard Feature Set)
S
Goodman® brand
(High Feature Set)
A
Amana® brand
Deluxe
D
Goodman® brand
Deluxe
V
Value Li ne
Type
S1 - 208/230V Single-Phase 60 Hz
Split System
Type3 - 208/230V Three-Phase 60 Hz
X:Condenser R-410A4 - 460V Three-Phase 60 Hz
Z:Heat Pump R-410A5 - 380/415V Three-Phase 50 Hz
036
6,7,8
Engineering
Maj or/Mi nor Revi si ons
Voltage
2 - 220/240V Single-Phase 50 Hz
SEER
13 - 13 SEER018 = 1-1/2 Tons042 = 3-1/2 Tons
14 - 14 SEER024 = 2 Tons048 = 4 Tons
16 - 16 SEER030 = 2-1/2 Tons059 = 5 Tons
18 - 18 SEER036 = 3 Tons060 = 5 Tons
038 = 3 Tons
5
Page 6
PRODUCT IDENTIFICATION
A
=
CAP F1824A 6 A
12345,6,7,891 011,12
BrandEngineering*
CIndoor Coil
Unit Application2 = R-22
AUpfl ow/Downfl ow Coil
H Horizontal A-Coil
Horizontal Slab Coil
S
Coated Coils
T
Nominal Width for Gas Furnace
A = Fits 1 4" Furnace Cabinet
B = Fits 17-1/2" Furnace Cabinet
C =
Fits 21" Furnace Cabinet
D = Fits 24-1/2" Furnace Cabinet
N
Does Not Apply (Horizontal Slab Coils
Major/Minor Revisions
Refrigerant Charge
4 = R-410A
6 = R-410A or R-22
Cabinet Finish
U Unpai nted
PPainted
N Unpainted Cas e
Expansion Device
FFlowrator
T4 - 5 Tons
Expansi on Valve4 - 5 Tons
1824 =
3030 =
3131 =
3636 =
3642 =
3743 =
4860 = Factory-Installed Non-Adjustable
4961 =
Nominal Capacity @ 13 SEER
1-1/2 - 2 Tons
2-1/2 Tons
2-1/2 Tons
3 Tons
3 - 3-1/2 Tons
3 - 3-1/2 Tons
6
Page 7
PRODUCT IDENTIFICATION
A
A
H
MBR800
1,2345,6789
Brand
MB - Modular Blower1: 208-230V/60Hz/1 P
TypeA: Fi rst Seri es
R -
Speed
E -
Vari able Speed
AirflowA: No Ci rcuit Breaker
8:
12:
16:
20:
800 CFM
1200 CFM
1500 CFM
2000 CFM
B:Ci rcuit Breaker
1
Elect rical
Design Se ries
Circuit Breaker
Factory Heat
00 No Heat
7
Page 8
PRODUCT IDENTIFICATION
W
A
12345,6,7,891011 ,12
BrandEngineering*
A Airhandler
Unit ApplicationRefrigerant Charge
C Ceiling Mount PSC Motor4 = R-410a
DDownflow PSC Motor
Multi Position
EElectrical
Vari a bl e Sp eed
RMul ti Pos iti on PSC Motor
SMul ti Posi tion EEM Motor
TCoated Coils
W Wal l Mount PSC/EEM Motor
Cabinet Finish1830 = 1-1/2 - 3-1/2 Tons
U Unpainted3137 = 3 Tons
PPainted3642 = 3 - 3-1/2Tons
NUncased
Expansion Device
FFlowrator
TExpansion Valve1803 =1-1/2 Tons Cooling/3 kW Electric Heat
UF364216AA
Maj or/Mi nor Revisi ons
1 208/240V, 1 Phase, 60 Hz
Nominal Capacity
@ 13 SEER Dedicated Application
3636 = 3 Ton
Multi-Position & Downflow Application
Multi-Position & Downflow Application @10 SEER
1729 = 3 Ton
Ceing Mount & Wall Mount Applications
(Nominal Cooling Capacity/Electric Heat kW)
1805 =1-1/2 Tons Cooling/5 kW Electric Heat
2405 =2 Tons Cooling/5 kW Electric Heat
3608 =3 Tons Cooling/8 kW Electric Heat
3105 =1-1/2 - 2-1/2 Tons Cooling/5 kW Electric Heat
3210 =2 - 2-1/2 Tons Cooling/5 kW Electric Heat
3705 =3 Tons Cooling/5 kW Electric Heat
3708 =3 Tons Cooling/8 kW Electric Heat
3710 =3 Tons Cooling/10 kW Electric Heat
An "F" in the model number denotes a
Factory Installed Float Switch is present.
All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-240v, 60 hz, 1 phase.
8
Page 9
PRODUCT IDENTIFICATION
ARU F 18 B 14AA
123 4 5,6 7 8 910,11
BrandEngineering*
ASingl e-Pi ece
Ai rhandl er
Unit ApplicationRefrigerant Charge
C Ceiling Mount PSC Motor4 = R-410a
RMul ti Pos iti on PSC Motor
SMul ti Posi ti on EEM MotorElectrical
W Wall Mount PSC/EEM Motor1 208/240V, 1 Phase, 60 Hz
Maj or/Mi nor Revi si ons
Cabinet Finish
UUnpaintedB =
PPaintedC = 21" Wide
NUncasedD = 24 -1/2" Wide
Expansion Device
FFlowrator18 =
TExpansion Valve24 = 2 Tons47 =
1-1/2 Tons
25 = 2 Tons48 = 4 Tons
2-1/2 - 3 Tons
29 =
2-1/2 Tons
30 =
36 =3 Tons60 =5 Tons
2-1/2 - 3 Tons
37 =
Nominal Capacity @ 13SEER
Cabinet Width
1/2" Wide
17-
3-1/2 Tons
42 =
3-1/2 Tons
49 = 4 Tons
59 = 5 Tons
61 = 5 Tons
Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.
9
Page 10
PRODUCT IDENTIFICATION
A
A
GS X 11 0901AA
1234,56,7,8910,11
LIGHT COMMERCIAL
Brand
G - Goodman brand
A - Amana brand
Type
S1 - 208/230V Single-Phase 60 Hz
Split Sys tem
2 - 220/240V Single-Phase 50 Hz
Type3 - 208/230V Three-Phase 60 Hz
X:Condens er R-41 0A4 - 460V Three-Phase 60 Hz
Z:Heat Pump R-410A5 - 380/415V Three-Phase 50 Hz
SEER
11 - 11 SEER
13 - 13 SEER
14 - 14 SEER
16 - 16 SEER036 - 3 Tons
048 - 4 Tons
060 - 5 Tons
090 - 7-1/2 Tons
120 - 10 Tons
Maj or/Mi nor Revi si ons
Engineering
Voltage
Nominal Capacity
10
R090A
123,4,56,7
Brand
Single Piece
A
Ai r Handler
Unit Application
R090 7-1/2 Tons
Multi Position
PSC Motor
For use with GSX/GSZ11 Light Commercial models only.
Maj or/Mi nor Revisi ons
Engineering
Nominal Capacity
120 10 Tons
Page 11
PRODUCT IDENTIFICATION
GSX11 LIGHT COMMERCIAL
LIGHT COMMERCIAL
OODMAN® BRAND SPLIT
G
Model/RevDescription
GSX11090*AA
GSX11120*AA
GSX111203AB
GSX110903AB
GSX111204AB
GSX110904AB
Introduction of Goodman Light Commercial 11 SEER, R-410A Condensers.
208-230V and 460V 3 Phase condensing units with new ball valve/brackets, suction
tube/assembly and panel w/offset.
R410A CONDENSERS 11 SEER
X-
GSZ11 LIGHT COMMERCIAL
OODMAN SPLIT Z-R410A HEAT PUMP 11 SEER
G
Model/RevDescription
GSZ11090*AA
GSZ11120*AA
GSZ110903AB
GSZ111203AB
GSZ110904AB
GSZ111204AB
Introduction of Goodman Light Commercial 11 SE ER, R-410A Heat Pumps.
208-230V and 460V 3 Phase R410A heat pump units with new ball valve/brack ets, suction
tube/assembly and panel w/offset.
AR LIGHT COMMERCIAL
SINGLE PIECE
A
Model/RevDescription
AR0904A
AR1204A
Introducation of new 7.5 & 10 Ton Air Handler Models, for use with GSX11 and GSZ11
Light Commercial Models.
MULTI-POSITION PSC MOTOR
R-
11
Page 12
PRODUCT IDENTIFICATION
Split System Heat Pumps
ASZ13
MANA® BRAND SPLIT
A
Model/RevDescription
ASZ130**1AAInitial release of Amana® Brand 13 SEER Heat Pump R410A.
ASZ130**1ABIntroduces new revisions with improved circuiting for effective defrost.
ASZ130[18, 36-60]1AB
ASZ130[24-30]1AC
ASZ130[18, 36-60]1AC
ASZ130[24-30]1AD
ASZ130[18, 36-60]1AD
ASZ130[24-30]1AE
ASZ130241BARelease of 2 Ton models, converting from 3/8" to 5mm condenser coils
ASZ130181AF
ASZ130[24-30]1AG
ASZ130481AF
ASZ130361AG
ASZ130421AH
Introduces models c ontaining crankcas e heater, CCH s witch and upgraded defrost
control.
Relocation of low pressure switch from liquid line to suction line as a compressor
safeguard to prevent low pressure from entering.
Initial release of models using single speed PSC motors; removal of low ambient
temperature switch.
Current reversing valve change from Dunan to new SanHua reversing valve
Current Ranco reversing valve 0151M00020 replaced by SanHua 0151R00070 reversing
va lve
Change from copper wound motor to aluminum wound motor.
R410A HEAT PUMP 13 SEER
Z-
ASZ130481AG
ASZ130601AF
Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
12
Page 13
PRODUCT IDENTIFICATION
Split System Heat Pumps
ASZ14
MANA® BRAND SPLIT
A
Model/RevDescription
ASZ140**1AA
ASZ140**1ABScrew locations moved in the top panel, base pans, louvers, and control box covers.
Models containing crankcase heater, CCH switch and upgraded defrost control.
Release of single phase models with new 6 pole motor.
Relocation of low pressure switch from liquid line to suction line as a compressor
safeguard to prevent low pressure from entering.
Release of 2 Ton models with a compressor change from ZP21K5EPFV130 to
ZP20K5EPFV130.
Changed from four-piece louver assembly to a two piece louver assembly. Added a corner
post on 26" and 29" chassis.
Single phase models with new 6 pole motor.
Changed from four-piece louver assembly to a two piece louver assembly. Added a corner
post on 26" and 29" chassis.
R410A HEAT PUMP 13 SEER
Z-
VSZ130421AFCompressor change from ZP36K5EPFV130 to ZP34K5EPFV130.
VSZ130241CB
VSZ130181AF
VSZ130241BD
VSZ130301AG
VSZ130481AFRanco 0151M00020 reversing valve replaced by SanHua 0151R00070 reversing valve
VSZ130241BECreate new Motor & Replace 0131M00294 with 0131M00800
VSZ130601ADCreate new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
2 Ton models changing from the current four piece louver assembly, to a two piece louver
plus a corner post on Goodman and value series 26" and 29" chassis.
Reversing valve change from Dunan to new SanHua.
18
Page 19
PRODUCT IDENTIFICATION
Split System Heat Pumps
VSZ14
ALUE SPLIT
V
Model/RevDescription
VSZ14[018-060]1AAIntroduction of ready 15, 14 SEER heat pumps to meet the 2015 efficiency requirement.
VSZ140(18-30)1ABEnergy guide update. PCBDM160 with new software.
R410A HEAT PUMP 14 SEER
Z-
VSZ140421AB
VSZ140491AB
VSZ140[181,301]AC
VSZ140[361,481,601]AB
VSZ140[181, 301]AD
VSZ140361AC
VSZ140[241, 421, 491]AC
VSZ140241AD
VSZ140[481,601]AC
Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap.
Refrigerant charge reduction.
Change from copper wound motor to aluminum wound motor.
Refrigerant Charge Reduction
Equivalent motor wit h Aluminum Windings replacing Copper Windings.
Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
19
Page 20
PRODUCT IDENTIFICATION
Split System Heat Pumps
GSZ13
OODMAN SPLIT
G
Model/RevDescription
GSZ13**1AAInitial release with Regal Beloit motor.
GSZ13**1AB
GSZ13**3AA
GSZ13**4AA
GSZ130[24 & 30]1ACRelease of minor revision with improved circuiting for effective defrost.
GSZ130[24 & 36]1BAInitial release of models with 5mm Smart Coil™.
Release of 2 Ton models with a compressor change from ZP21K5EPFV130 to
ZP20K5EPFV130.
2 Ton models changing from the current four piece louver assembly, to a two piece louver
plus a corner post on Goodman and value series 26" and 29" chassis .
Release of models containing crankcase heater, CCH switc h and upgraded defrost control.
Relocation of low press ure switch from liquid line to suction line as a compress or safeguard
to prevent low pressure from entering.
Changing from the current four piece louver ass embly , to a two piece louver plus a c orner
post on Goodman and value series 26" and 29" chassis.
R410A HEAT PUMP 13 SEER
Z-
GSZ130361BC
GSZ130[42 & 48]1AE
GSZ130361BD
GSZ130421AF
GSZ130[36 & 48]3ACRelease of 3 phase models with new 6 pole motor.
GSZ14**1AAInitial release of 14 SEER models.
GSZ130481AG
GSZ130483AE
GSZ130484AD
GSZ130[191,311] AD
GSZ130241BE
GSZ130251AC
GSZ130601AE Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
Releas e of models with new 6 pole motor/fan combination.
Models wit h new 6 pole motor/fan combination. Changing from the c urrent four piece louver
assembly, to a two piece louver plus a corner post on Goodman and value series 26" and
29" chassis.
Releas e of two piece louver plus corner post on 26" and 29" chassis with compressor
changing from ZP36K5EPFV130 to ZP34K5EPFV130.
Replac ed Ranco revers ing valve 0151M00020 with SanHua 0151R00070 reversing valve .
Create new Motor & Replace 0131M00294 with 0131M00800
20
Page 21
PRODUCT IDENTIFICATION
GSZ14
OODMAN SPLIT
G
Model/RevDescription
GSZ140(18-60)1KA
GSZ140491AA
GSZ140(18-30)1KBEnergy guide update. PCBDM160 with new software.
Introduction of ready 15 14 SEER heat pumps to meet the 2015 energy efficiency
requirement .
R410A HEAT PUMP 14 SEER
Z-
Split System Heat Pumps
GSZ140301KC
GSZ140361KB
Migrating from copper to aluminum motors.
GSZ140[421,491]KB Motor ch ange on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Incre ase blade gap.
GSZ140181KC
GSZ140361KC
GSZ140[241,301]KD
GSZ140[481,601]KB
GSZ140[241, 301]KE
GSZ140[481, 601]KC
GSZ140181KD
GSZ140[421, 491]KC
GSZ140241KF
GSZ140371AB
Refrigerant charge re duction.
New mod el re visions, GSZ140241KD, GSZ140301KD, GSZ140481KB and GSZ140601KB
will have the BOMs changed and have a lower refrigerant charge.
New model revisions to deplete current overstock of Ranco reversing valves
Change from copper wound motor to aluminum wound motor.
Refrigerant Charge Reduction
Equivalent motor with Aluminum Windings replacing Copper Windings.
Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
GSZ140[481,601]KD
GSZ16
OODMAN SPLIT
G
R410A HEAT PUMP 16 SEER
Z-
Model/RevDescription
GSZ160[18-48]1BAInitial release of Goodman 16 S EER, 13 EER Heat Pumps with 9.0+ HSPF
GSZ1160601BAInitial release of Goodman 5 Ton 16 SEER, 13 EER Heat Pumps
GSZ160241BB
GSZ160301BB
GSZ160181BB 16 SEER 1.5T Heat Pumps, Remove Hard Start Kit
GSZ160181BC Equivalent motor with Aluminum W indings replacing Copper Windings.
GSZ160[361, 481]BC Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap.
Swit ching current Goodman 16SEER condensers and heat pumps with grille tops to louver
tops to be consistent with other Goodman units having louver-style top panels.
21
Page 22
PRODUCT IDENTIFICATION
Split System Heat Pumps
SSZ14
PECIAL HIGH FEATUR E SPLIT
S
Model/RevDescription
SSZ140**1AAInitial release of Goodman 14 SEER Heat Pump R410A.
SSZ140**1ABScrew locations moved in the top panel, base pans, louvers, and control box covers.
Added discharge line mufflers. Replaced TXV and compensator with flowrator and
accumulator.
Sanhua (RANCO) reversing valves.
Introduction of heat pumps with accumulators, crankcase heaters, and upgraded defrost
control.
Changed from four-piece louver ass embly to a two piece louver assembly. Added a corner
post on Goodman 26" and 29" chassis.
Revision made for design improvement.
Relocation of low pressure switch from liquid line to suction line as a compressor
safeguard to prevent low pressure from entering.
Chassis size reduction from large to medium.
R410A HEAT PUMP 14 SEER
Z-
SSZ140381AAInitial release of 35" chassis with 6-channel flowrator and ZP29K5 compressor.
SSZ140[18-30]1BAUpdated ratings and agency information.
SSZ140241BB
SSZ140251AE
SSZ140361BE
SSZ140371AE
SSZ140[421,481,601]AK
22
Change from copper wound motor to aluminum wound motor.
Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
Page 23
PRODUCT IDENTIFICATION
Split System Heat Pumps
SSZ16
PECIAL HIGH FEATURE SPLIT
S
Model/RevDescription
SSZ160**1AAInitial releas e of Goodman 16 SEER Heat Pump R410A.
SSZ160**1ABScrew locations moved in the top panel, base pans, louvers, and control box covers.
SSZ160**1AC
SSZ16[024-48]1AC
SSZ160601AD
SSZ160361AF
SSZ160[42-60]1AD
SSZ160241AF
SSZ160[36, 48]1AD
SSZ160601AE
SSZ160241AF
SSZ160[36-48]1AE
SSZ160601BA
SSZ160241AH
Broad Ocean Motor. Updated muffler and standardized TXV. Compensator using ASZ18
SEER weldment to the SSZ160601AC.
Discharge line mufflers added.
Added discharge line mufflers. Replaced TXV and compensator with flowrator and
accumulator.
Sanhua (RANCO) reversing valves.
Introduction of heat pumps with accumulators, crankcase heaters, and upgraded defrost
control.
Changed from four-piece louver assembly to a two piece louver assembly. Added a corner
post on Goodman 26" and 29" chassis.
R410A HEAT PUMP 16 SEER
Z-
SSZ160601BBUltratech® compressor
SSZ160241AKChange from copper wound motor to aluminum wound motor.
23
Page 24
PRODUCT IDENTIFICATION
ging
Split System Condensers
GSX13
OODMAN BRAND SPLIT
G
Model/RevDescription
GSX130**1AAInitial release of Goodman 13 SEER R-410A Condensers with Regal Beloit motors
GSX13061[1/3/4]AA
GSX130363AB
GSX130484AB
GSX130603AB
GSX130604AB
GSX130**1ABBroad Ocean motors.
GSX130483AB3 Phase model with new 6 pole motor.
GSX130483AC
GSX130181EA
GSX130181EB
GSX130**1BA
GSX130**3AA
GSX130**4AA
GSX130301BBReplaced fan mot or to -294 and fan blade to -18 on GSX130301BA models.
GSX130[42, 48]1BC
GSX130301BC
GSX130601BB
GSX130[42, 48]1BBNew 6 pole motor/fan combination.
Introduction of Goodman 13 SEER R-410A Condensers that supplement our current 5 ton
models.
Changed from the current four piece louver assembly, to a two piece louver plus a corner
post on Goodman and value series 26" and 29" chassis.
3 phase model chan
plus a corner post on Goodman and value series 26" and 29" chassis.
Introduction of 1.5 ton condenser with Rechi Compressor.
Introduction of Goodman 13 SEER R-410A Condensers using SmartCoil® coils. Units will
have new louvers because units are smaller. Piston s ize c hange. Other components
unchanged.
Changed from the current four piece louver assembly, to a two piece louver plus a corner
post on Goodman and value series 26" and 29" chassis.
R410A CONDENSERS 13 SEER
X-
from the current four piece louver ass embly, to a two piece louver
GSX130181CARotary c ompressor.
GSX130421CA
GSX130481CA
GSX130361CAReplaced current compressor with compressor ZP29K5EPFV130.
GSX130[18-36]1DACondenser conversion to 23" chassis for the 1.5 - 3 ton models.
GSX130181ED
GSX13031DB
GSX130361EAIntroduction of Goodman 3 ton conversion from 29" chassis to 26".
GSX130361EB
GSX130371AAImproved decibel ratings for Canadian market.
GSX130181EF Change from motor 0131M00276 to 0131M00593 on units GSX130181 & VSX130181
GSX130363ADChange from copper wound motor to aluminum wound mot or.
GSX130241EC
GSX130301BF
Introduction of Goodman 3.5 and 4 ton 13 SEER condensing units wit h reciprocating
compressor.
Changed from a 4 leg Rechi Compressor 50N382XV-ZAKM to 3 Leg Rechi Compressor
50N382XV-5AKM. Changed Suction line Assy from 0210R01608 to 0210R01406. This
minor
Improved coil circuit assembly for greater capac ity/efficiency and a new discharge tubing
assembly.
Changed from the current four piece louver assembly, to a two piece louver plus a corner
post on Goodman and value series 26" and 29" chassis.
Create new Motor & Replace 0131M00294 with 0131M00800
*GSX13 CONTINUED ON THE NEXT PAGE
24
Page 25
PRODUCT IDENTIFICATION
Split System Condensers
GSX13
OODMAN BRAND SPLIT
G
Model/RevDescription
GSX130611ACCreate new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
GSX130241ED
GSX130[301,601]B G
GSX130361EE
GSX130[421,481]B F
Fact ory Refrigerant Charge Optimization
R410A CONDENSERS 13 SEER
X-
25
Page 26
PRODUCT IDENTIFICATION
GSX14
OODMAN BRAND SPLIT
G
Model/RevDescription
GSX14**1AAIntroduction of Goodman 14 SEER R-410A models.
GSX160[481,611]FF Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807
Ball Valve Re-work 0151R00045 & 0151R00046
Initial release creates and launches 2 new SKUs in the 16 SEER single-stage AC
product line.
Refrigerant charge reduction.
Equivalent motor with Aluminum Windings replacing Copper Windings.
Switching current Goodman 16SEER condensers and heat pumps with grille tops to
louver tops to be consistent with other Goodman units having louver-style top
panels.
27
Page 28
PRODUCT IDENTIFICATION
Revisi
Split System Condensers
SSX14
PECIAL HIGH FEATURE SPLIT
S
Model/RevDescription
SSX140**1AAInitial release of Goodman 14 SEER AC 410A.
SSX140**1AB
SSX14018, 241ACRevised condenser coils by removing [1] haripin.
SSX140301ACModel contains the Broad Ocean motor 0131M00060
SSX14036-601ACModels contain the Broad Ocean motor 0131M00061
SSX14030,361ADRevised condenser coils by removing [1] haripin.
ons have screw locations moved in the top panel, base pans, louvers, and control
box covers.
Converts 1.5 - 3.5 ton condenser coil tubes from 3/8" tube diameter to 5mm tube
diameter.
Changing from the current four piece louver assembly, to a two piece louver plus a corner
post on Goodman and value series 26" and 29" c hassis.
Revision made for design improvement.
Revision for SSZ140421B* in 29 base pan and it will the reduce the unit charge from 180
oz. to 170 oz. and replace the 1/4 hp outdoor unit motor with 1/6 hp motor.
R410A CONDENSERS 14 SEER
X-
SSX14030-421AERevised condenser coils by removing [1] haripin.
SSX140[18-48]1BA
SSX14042-481CA
SSX140[18-36]1BB
SSX140421CB
SSX140601AF
Introduction of Goodman 14 SEER R-410A Condensers with SmartCoil® Coils.
Relocation of low pressure switch from liquid line to suction line as a compressor
safeguard to prevent low pressure from entering.
28
Page 29
PRODUCT IDENTIFICATION
Split System Condensers
SSX16
PECIAL HIGH FEATURE SPLIT
S
Model/RevDescription
SSX160**1AAIntroduces Goodman 16 SEER AC 410A
SSX160**1AB
SSX160**1AB
SSX160591AA
SSX160[24, 36, 48]1BA
SSX160[30 & 42]1AA
SSX160[24, 36]1BC
SSX160[30, 42]1AB
SSX160601BAZPS49K compressor.
SSX160[24,36,60]1BB
New revisions have screw locations moved in the top panel, base pans, louvers, and
control box covers.
New revisions have screw locations moved in the top panel, base pans, louvers, and
control box covers.
SmartCoil® coils.
Changing from the current four piece louver assembly, to a two piece louver plus a corner
post on Goodman and value series 26" and 29" c hassis.
Relocation of low pressure switch from liquid line to suction line as a compressor
safeguard to prevent low pressure from entering.
R410A CONDENSER 16 SEER
X-
DSX16
ELUXE SPLIT
D
Model/RevDescription
DSX160**1AAInitial release of Goodman 2-stage, 16 SEER condensing units with R-410A.
R410A HEAT PUMP 16 SEER
X-
DSX160[24, 36]1BAConversion of 2 & 3 ton models to SmartCoil® Coils.
Release of all models of 13 SEER Dayton uncased air handlers suitable for use with R-22
& R-410A.
Converted copper coils, manifolds, hairpins, flowrators, 90° flowrator stub to aluminum.
Conversion of copper 3/8" return bends to aluminum 5/16" return bends.
UL1995 heater change.
Change in the air handler design. The motor changed from an existing P SC to a constant
torque motor.
Creation of new ACNF Minor Rev models to produce coils with non acid etched fins.
ADPF
SINGLE PIECE DOWNFLO W AIR HANDLER PSC MOTOR PAINTE D FLOW ATER
A-
Model/RevDescription
ADPF****16AAIntroduction of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A.
ADPF364216AB
ADPF486016AB
ADPF304216AC
ADPF****1BAReplacement of all ARPFcoils using wavy fin with louver enhanced fin.
ADPF182416CA
ADPF486016CA
Replacement of the current s pot welded blower housing with the same c inched or crimped
design used on the 80% furnace line.
Replacement of the current s pot welded blower housing with the same c inched or crimped
design used on the 80% furnace line.
Replacement of the current s pot welded blower housing with the same c inched or crimped
design used on the 80% furnace line.
Replacement of existing air handler copper coils and other associated parts with
aluminum components.
37
Page 38
PRODUCT IDENTIFICATION
Air Handlers
AEP F
SINGLE PIECE E-MULTI-POSITION VARIABLE SPEED PAINTE D FLOW ATER
A-
Model/RevDescription
AEPF****16AAIntroducation of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A.
AEPF****16BAIntroduction of new models adding lower kW hit kits on the S&R plate.
AEPF****16BB
AEPF****16CAReplacement of all ARPFcoils using wavy fin with louver enhanced fin.
AEPF****1BAIntroduction of R-22 Only Air Handlers.
AEPF313716AAIntroduction of 3-Ton Air Handler units with 3-row coil.
Replacement of the current s pot welded blower housing with the same c inched or crimped
design used on the 80% furnace line.
38
Page 39
PRODUCT IDENTIFICATION
Air Handlers
ARUF
SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR UNPAINTED FLOW RATOR
A-
Model/RevDescription
ARUF172916AA
A24-00-2RCA
ARUF****16AAIntroduction of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A
ARUF364216AB
ARUF486016AB
ARUF364216AC
ARUF****16BAReplaced wavy fin with louver enhanced fin.
ARUF****1BAIntroducation of R-22 Only Air Handlers.
ARUF****16CA
ARUF***14A A
ARUF***14A B
ARUF18B14AB
ARUF24B14BA
ARUF36C14BA
ARUF42C14AB
Introduction of new Air Handler Models with all aluminum evaporator coils. Conversion
includes coils, manifold, hairpin, flowrators, 3/8" return bend to 5/16" aluminum return
bends.
Replaced current spot welded blower housing with cinched/crimped design used on the
80% furnace line.
Replaced existing air handler copper coils and other associated parts with aluminum
components.
Initial release of the redesigned air handlers manufactured at the Houston furnace facility.
R-410A only. 2 & 3 ton coil replacement. 2 ton replaced w/3 row/16" tall; 3 ton replaced
with 18" tall coil. 3.5 ton model blower motor changes from 10X8 to 10X10.
The aluminum models changes the RBs, COs, and coil slabs to 9mm braze joints.
Serial plate changes
Initial release of new ready 2015 Air Handler Models that meet the 2015 energy efficiency
levels (for 7mm 14 SEER Heat Pumps).
Initial release of new ready 2015 Air Handler Models that meet the 2015 energy efficiency
levels (for 7mm 14 SEER Heat Pumps).
ARPF
SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR PAINTED FLOW RATER
A-
Model/RevDescription
ARPF364216AB
ARPF486016AB
Replacement of the current spot welded blower housing with the same cinched or crimped
design used on the 80% furnace line.
ARPF****16BAWavy fin replaced with louver enhanced fin.
ARPF****1BAIntroduction of R-22 Only Air Handlers.
ARPF****16CAReplaced air handler copper coils and other associated parts with aluminum components.
39
Page 40
PRODUCT IDENTIFICATION
SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR PAINTE D FLOW RATER TXV
A-
Model/RevDescription
ARPT***14AAInitial release of the new air handlers.
ARPT***14ABInitial release of the air handlers manufactured at the Houston furnace facility.
Air Handlers
ARPT - R410A ONLY
ARPT[18-36]B14AC
ARPT[36-60]D14AC
Serial plate changes.
ASP F
SINGLE PIECE AIR HANDLER S-MULTI-POSITION EEM MOTOR PAINTE D FLOW RATOR
A-
Model/RevDescription
ASPF****16AAIntroduction of new ASPF Air Handlers.
Initial releas e of modified ASPF control scheme, to ensure blower operation during and
ASPF****16BA
ASPF****16CA
ASPF****16DA
ASPF****16EA
after call for heat on units with heat kits and replacing wavy fin with louver enhanced fin on
coil.
Replaced existing air handler copper coils and other associate departs with aluminum
components.
Initial releas e of models with Emerson SelecTech motor. Replaced Regal-Beloit X-13
motor.
Replaced of exis ting air handler copper coils and other associated parts with aluminum
components and replaced Regal-Beloit X-13 motor with Emerson SelecTech motor.
ASPT
SINGLE PIECE AIR HANDLER S-MULTI-POSITION EEM MO TOR PAINTE D TXV
A-
Model/RevDescription
ASPT(24/36/48/60)*14Introduction of new generation ASPT air handlers.
9mm return bend coil changes to new generation of ASPT air handlers.
Programmed Broad Ocean Motor. The supplier can program the motor instead of furnace
plant, thus eliminating any programming installing issues. The programmed label will
provide by supplier.
X13 Motor IP changed to IGBT (Broad Ocean).
Initial release of models with 2+ 2 coil slab assy. These models are required to meet
higher tonnage rating in Cabinet.
Nidec Pre-programmed Motor. Nidec motor can be programmed by the supplier instead of
programming at the furnace plant, thus eliminating any programming installing issues.
Initial release of models with a 2 slab, low airflow resistant coil with a fixed speed ECM.
53" cabinet size. ASPT42C and ASPT48C 2+2 models discontinued.
40
Page 41
PRODUCT IDENTIFICATION
Air Handlers
ASUF
SINGLE PIECE AIR HANDLER S-ENERGY EFFICIENT MOTOR UNPAINTED FLOW RATOR
A-
Model/RevDescription
ASUF29B14AA
ASUF39C14AA
ASUF49C14AA
ASUF59D14AA
ASUF49C14AB
ASUF59D14AB
ASUF59D14ACFour row, piston, 9 mm return bend coil.
ASUF59D14ADNidec Pre-programmed Motor. Nidec motor can be programmed by the supplier.
Initial releas e of models in the mid-range efficiency air handler. Incorporates smart frame
chassis with EEM (X-13) style motors and piston type flowrators.
Initial releas e of mid-range efficiency air handler with X-13 motor & fixed orifice flowrator.
9 mm return bend coil.
Programmed Broad Ocean Motor. The supplier can program the motor.
Changed from X13 Motor IP to IGBT (Broad Ocean).
MBR
ODULAR BLOWER AIR HANDLER R-MULTI-POSITION PSC MOTOR
M
Model/RevDescription
MBR****AA-1AAInitial release of a module blower with PSC blower motor.
MBR****AA-1ABA quality improvement to use 0.75" Quiet Flex Insulation.
MBR****AA-1ACRelease of MBR/MBVC Models(Minor Revisions) for 11th St Plant. Dayton to Houston
MBE
ODULAR BLOWER AIR HANDLER E-MULTI-POSITION VARIABLE-SPEED
M
Model/RevDescription
MBE****AA-1AAIntroduction of a module blower with variable speed blower motor.
MBE****AA-1BAIntroduction of new models adding lower kW hit kits on the S&R plate.
41
Page 42
PRODUCT IDENTIFICATION
-
AWUF
SINGLE PIECE AIR HANDLER WALL MOUNT UNPAINTED FLOW RATOR
A-
Model/RevDescription
AWUF****16AA
AWUF370**16AA
AWUF3005-101AAInitial release of modelw with Burr Oak Louvered Fin coil.
Introduction of a 13 SEER Dayton wall mount air handlers suitable for use with R-22 and R
410A. Coil adapters have been added to coil circuits.
Air Handlers
AWUF****1BA
AWUF****16BA
AWUF(18/24/30)0316BAIntroduction of 3 kW heater in the AWUF air handlers.
Changed from copper tube hairpin to aluminum tube hairpin. Aluminum manifolds and
flowrators are purchased parts.
Introduction of higher 14 SEER AWUF series air-handlers.
Replaced 16x20x1 with 18x20x1 filter.
Drain pan water sensor switch added.
Revised for the UL1995 heater changes.
Introduction of 14 SEER Dayton small chassis wall mount air handlers with fixed speed
X13 Stylemotor to match the 1.5 and 2.0 ton AC, AC+EER, and HP models with factory
installed heat from 3 kW to 10 kW.
Release gasket and caps to seal leak. With this modification we will able to meet 2% at 1
inch static leak and 1.4% leak rate at 0.5 inch static. Modified all current AWUF units to
pass current air leak rate.
42
Page 43
PRODUCT IDENTIFICATION
CAPF
INDOOR C OIL A-UPFLOW/DOWNFLOW PAINTE D FLOW RATOR
C-
Model/RevDescription
CAPF*****6AAInitial release of CAPF Dayton Upflow/Downflow coils.
CAPF*****6BABurr Oak Louvered Fin released in place of the Wavy Fin.
CAPF36***CARedesigned for performance improvement from 2 row to 3 row.
CAPF*****6DAReplaced exis ting copper coils and other associated parts with aluminum components.
Model DescriptionGSX110903GSX110904GSX111203GSX111204
FS K0 1A*
ASC0 1
LAKT-0 1
LSK03*
Freeze Protection Kitxxxx
Anti Short Cycle Kit xxxx
Low Ambient Kitxxxx
Liquid Line Solenoid Kit
xxxx
GSZ11
Model DescriptionGSZ110903GSZ110904GSZ111203GSZ111204
FS K0 1A*
ASC0 1
OT-EHR18-60
LAKT-0 1
LSK03*
Freeze Protection Kitxxxx
Anti Short Cycle Kit xxxx
Emergency Heat Relay Kit------------
Low Ambient Kitxxxx
Liquid Line Solenoid Kit
xxxx
ELECTRIC HEATER KITS
AHKD
Model
No minal
kW
Electrical
Characteristics
Stages
Weigh t
(lbs.)
AHKD15-315208-230/3/6015660
AHKD15-415460/3/6015530
AHKD20-320208-230/3/6025970
AHKD20-420460/3/6025735
AHKD30-330208-230/3/60260100
AHKD30-430460/3/6025850
Max.
Ove rcurrent
Protection
NOTES:
•AR Series Air Handlers do not have factory installed electric heat. Purchased as an accessory, these are the ONLY heater kits that can be
used with the AR Series.
•The electrical characteristics of the air handler, electric heater kits and building power supply must be compatible.
47
Page 48
ACCESSORIES
ASX13
ModelDescription
1
ABK-20
Anchor Bracket KitXXXXXXX
ASX13
018*
ASX13
024*
ASX13
030*
ASX13
036*
ASX13
042*
ASX13
048*
ASX13
060*/061*
ASC01Anti-Short Cycle KitXXXXXXX
CSR-U-1Hard-start KitXXXX
CSR-U-2Hard-start KitXX
CSR-U-3Hard-start KitXX
2
FSK01A
Freeze Protection KitXXXXXXX
LSK02ALiquid Line Solenoid KitXXXXXXX
TX2N4A³TXV KitXX
TX3N4
TX5N4
3
3
TXV KitXX
TXV KitXXX
G/VSX13
ModelDescription
1
ABK-20
ABK-21
Anchor Bracket KitXXXXXXX
4
Anchor Bracket KitXXXX
G/VSX13
018*
ASC01Anti-Short Cycle KitXXXXXXX
CSR-U-1Hard-start KitXXXX
CSR-U-2Hard-start KitXX
CSR-U-3Hard-start KitXX
1
FSK01A
Freeze Protection KitXXXXXXX
LSK02ALiquid Line Solenoid KitXXXXXXX
TX2N4A³TXV KitXX
TX3N4
TX5N4
2
2
TXV KitXX
TXV KitXXX
CSB-15Sound Blanket KitXXX
CSB-16Sound Blanket KitXXXX
G/VSX13
024*
G/VSX13
030*
G/VSX13
036*
G/VSX13
042*
G/VSX13
048*
G/VSX13060*
GSX13061*
GSX13 Three-Phase models
ModelDescription
ABK-20
1
Anchor Bracket Kit XXXXX
GSX13
0363*
ASC01Anti-Short Cycle Kit XXXXX
FSK01A
2
Freeze Protection KitXXXXX
LSK02ALiquid Line Solenoid KitXXXXX
TX3N4
TX5N4
3
3
TXV KitX
TXV KitXXXX
CSB-15Sound Blanket KitXXXX
CSB-16Sound Blanket KitX
LAKT01Low Ambient KitXXXXX
0163R00002Crankc ase Heater KitX
0163R00003Crankc ase Heater KitXX
0163R00004Crankc ase Heater KitXX
48
GSX13
0483*
GS X1 3
0484*
GSX130
[60/61]3*
GSX130
[60/61]4*
1
Contains 20 brackets; four brackets needed to anchor unit to pad
2
Installed on indoor coil.
3
Field-installed, non-bleed, expansion valve kit - Condensing units
and heat pumps with reciprocating compressors require the use
of start-assist components when
used in conjuntion with an indoor
coil using a non-bleed thermal
expansion valve refrigerant.
4
For use on the GSX13 & VSX13
23" chassis only. Contains 20
brackets; four brackets needed
to anchor unit to pad.
ABK-20Anchor Bracket KitXXXXXXXX
ASC01Anti-Short Cycle KitXXXXXXXX
CSR-U-1Hard-start KitXXXX
CSR-U-2Hard-start KitXX
CSR-U-3Hard-start KitXXX
FSK01AFreeze Protection KitXXXXXXXX
LSK02ALiquid Line Solenoid KitXXXXXXXX
TXV- 30Fi xe d TXV Ki tXXX
TXV- 42Fi xe d TXV Ki tXX
TXV- 48Fi xe d TXV Ki tX
TXV- 60Fi xe d TXV Ki tXX
1
Installed on indoor coil
2
Required for heat pump applications w here ambient temperatures f all below 0°F w ith 50% or higher relative humidy.
50
A/GSX16
024F*
A/GSX16
030F*
A/GSX16
036F*
A/GSX16
042F*
A/GSX16
048F*
A/GSX16
060F*
A/GSX16
061F*
Page 51
ACCESSORIES
ASX/DSX18
ModelDescription
ABK-20
1
Anchor Bracket KitXXX
A/DSX18
036*
ASC01Anti-Short Cycle KitXXX
CSR-U-1Hard-start KitX
CSR-U-2Hard-start KitX
CSR-U-3Hard-start KitXX
FSK01A
1
Freeze Protection KitXXX
LSK02ALiquid Line Solenoid KitXXX
TX2N4ATXV Kit
TX3N4TXV KitX
TX5N4TXV KitXX
1
Installed on indoor coil
2
Required for heat pump applications w here ambient temperatures f all below 0°F w ith 50% or higher r elative humidity.
A/DSX18
048*
/DSX18
060*
51
Page 52
ACCESSORIES
ASZ13
ModelDescription
ASZ1 3
018
AFE18-60AAll-Fuel KitXXXXXXX
ASC01Anti-Short Cycle KitXXXXXXX
4
CSR-U-1
CSR-U-2
CSR-U-3
FSK01A
Hard-start KitXXXX
4
Hard-start KitXX
4
Hard-start KitXX
2
Freeze Protection KitXXXXXXX
LSK02ALiquid Line Solenoid KitXXXXXXX
OT/EHR18-60Emergency Heat Relay kitXXXXXXX
3
OT18-60A
TX2N4A
4
TX3N4
4
TX5N4
1
Contains 20 brackets; four brackets needed to anchor unit to pad
2
Installed on indoor coil.
3
Required for heat pump applications where ambient temperatures fall below 0°F with 50% or higher relative humidity.
4
Condensing units & heat pumps with reciprocating compressors require the use of start-assist components when used in conjuntion with an indoor coil using a non-bleed expansion valve refrigerant
metering device.
5
Field-installed, non-bleed, expansion valve kit - Condensing units and heat pumps with reciprocating compressors require the use of start-assist components when used in conjuntion with an indoor coil
using a non-bleed thermal expansion valve refrigerant.
Outdoor Thermostat w/Lockout StatXXXXXXX
4
TXV K itXX
TXV K itXX
TXV K itXXX
ASZ1 3
024
ASZ1 3
030
ASZ1 3
036
ASZ1 3
042
ASZ1 3
048
ASZ1 3
060
52
Page 53
ACCESSORIES
GSZ13
ModelDescription
AFE18-60A
ASC01
All-Fuel Kit
Anti-Short Cycle Kit
G/VSZ13
018
G/VSZ13
024
G/VSZ13
030
G/VSZ13
036
G/VSZ13
042
G/VSZ13
048
G/VSZ13
060
XXXXXXX
XXXXXXX
CSB-15
CSB-16
CSR-U-1
CSR-U-2
CSR-U-3
FSK01A
Sound Blanket
Sound Blanket
4
Hard-start KitXXXX
4
Hard-start KitXX
4
Hard-start KitXX
2
Freeze Protection KitXXXXXXX
XXXX
XXX
LSK02ALiquid Line Solenoid KitXXXXXXX
OT/EHR18-60Emergency Heat Relay kitXXXXXXX
3
OT18-60A
TX2N4A
5
TX3N4
5
TX5N4
Outdoor Thermostat w/Lockout StatXXXXXXX
5
TXV K itXX
TXV K itXX
TXV K it
XXX
GSZ13 Three-Phase
ModelDescription
GS Z1 3
036*
AFE18-60AAll-Fuel KitXXXXX
ASC01Anti-Short Cycle KitXXXXX
2
FSK01A
Freeze Protection KitXXXXX
LSK02ALiquid Line Solenoid KitXXXXX
OT/EHR18-60Emergency Heat Relay kitXXXXX
3
OT18-60A
5
TX3N4
5
TX5N4
Outdoor Thermostat w/Lockout StatXXXXX
TXV K itXX
TXV K itXXX
CSB-15Sound Blanket KitXXXX
CSB-16Sound Blanket KitX
LAKT01Low Ambient KitXXXXX
1
Contains 20 brackets; four brackets needed to anchor unit to pad
2
Installed on indoor coil.
3
Required for heat pump applications where ambient temperatures fall below 0°F with 50% or higher relative humidity.
4
Condensing units & heat pumps with reciprocating compressors require the use of start-assist components when used in conjuntion with an indoor coil using a non-bleed
expansion valve refrigerant metering device.
5
Field-installed, non-bleed, expansion valve kit - Condensing units and heat pumps with reciprocating compressors require the use of start-assist components when used
in conjuntion with an indoor coil using a non-bleed thermal expansion valve refrigerant.
GS Z1 3
048*
GS Z1 3
048*
GS Z1 3
060*
GS Z1 3
060*
53
Page 54
ACCESSORIES
SSZ14
ModelDescription
SSZ14
018*
AFE18-60AAll-Fuel KitXXXXXXX X
CSR-U-1Hard-start KitXXXXX
CSR-U-2Hard-start KitXXX
CSR-U-3Hard-start KitXX
1
FSK01A
Freeze Protection KitXXXXXXX X
LSK02ALiquid Line Solenoid Kit XXXXXXX X
2
OT18-60A
Outdoor ThermostatXXXXXXX X
OT/EHR18-60Emergency Heat Relat KitXXXXXXX X
TX2N4A³TXV KitXX
TX3N4³TXV KitXXX
TX5N4³
TXV K itXX X
ASZ14
ModelDescription
AFE18-60AAll-Fuel KitXXXXXXX X
CSR-U-1Hard-start KitXXXXX
CSR-U-2Hard-start KitXXX
CSR-U-3Hard-start KitXX
1
FSK01A
Freeze Protection KitXXXXXXX X
LSK02ALiquid Line Solenoid Kit XXXXXXX X
2
OT18-60A
Outdoor ThermostatXXXXXXX X
OT/EHR18-60Emergency Heat Relat KitXXXXXXX X
TX2N4A³TXV KitXX
TX3N4³TXV KitXXX
* Revision level that may or may not be designated.
Refer to the minimum ai rflow requir ements for each of the heat kits.
ASPT
Heater Kit (kW)
35681015192021 or 25
AVPTC24B14550650700800850NRNRNRNR
AVPTC30C14600700750875950NRNRNRNR
AVPTC36C14NR85090010001200144015001500NR
AVPTC48C14NR85090010001200144015001500NR
†
AVPTC 42D 14
AVPTC 48D 14
AVPTC 60D 14
Note: Airf low data show n applies to the electric heat only in either legacy mode or communicating mode operation
NR - Not r at ed
* Within thermostat user menu CTK0* communicating thermostat w ill display 20KW for OFF- OFF- ON dip sw itch selection, 21kW for
†For match up w ith a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits s hall be set to 850 cfm speed tap of ON-ON-ON.
††For match up w ith a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airf low for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
†††For match up w ith a 3.5 ton outdoor unit: Heater kit application shall not exc eed 20 kW.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cf m speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable f or this indoor application.
850**12501300150015501720NR1800NR
††
†††
NR12501300150015501720NR18151850
NR12501300150015501780NR18501850
MINIMUM CFM REQUIRED FOR HEATER KITS, See notes below
67
Page 68
ACCESSORIES
ARUF & ASPT
MODEL LIST FOR DOWNFLOW KIT
DFK-BDFK-CDFK-D
DOWN FLOW KITD OWNFLOW KITDOWNFLOW KIT
ARUF25B14**ARUF37C14**ARUF37D14**
ARUF29B14**ARUF43C14**ARUF43D14**
ARUF31B14**ARUF49C14**ARUF47D14**
ASPT24B14**ASPT37C14**
ASPT29B14**ASPT47C14**
ASPT37B14**ASPT59C14**
ARUF49D14**
ARUF61D14**
ASPT61D14**
ASPT47D14**
ASPT49D14**
MODEL
35681015192025
ARUF25B14715715715715950
ARUF29B14715715715715950
ARUF31B14715715715715875875
ARUF37C14117011701170117013451345
ARUF43C14117011701170117013451345
ARUF49C14117011701170117013401430
ARUF37D14117011701170117013451345
ARUF43D14117011701170117013451345
ARUF47D14117011701170117013451345
ARUF49D14124012401240124015201520
ARUF61D141590159015901590171517151715
HEATER KIT (kW)
MINIMUM CFM REQUIRED FOR HEATER KITS
MODEL
ASPT24B14
ASPT29B14
ASPT37B14
ASPT37C14
ASPT47C14
ASPT59C14
ASPT47D14
ASPT49D14
ASPT61D14*
35681015192025
715715715715850
7157157157158751050
7157157157158751050
117011701170117013451345
117011701170117013451345
117011701170117013451345
124012401240124015201520
1590159015901590171517151715
1590159015901590171517151715
HEATER (kW)
68
Page 69
PRODUCT DESIGN
This section gives a basic description of cooling unit operation,
its various components and their basic operation. Ensure your
system is properly sized for heat gain and loss according to
methods of the Air Conditioning Contractors Association (ACCA)
or equivalent.
CONDENSING UNIT
The condenser air is pulled through the condenser coil by a direct
drive propeller fan. This condenser air is then discharged out of
the top of the cabinet. These units are designed for free air
discharge, so no additional resistance, like duct work, shall be
attached.
The suction and liquid line connections on present models are of
the sweat type for field piping with refrigerant type copper. Front
seating valves are factory installed to accept the field run copper.
The total refrigerant charge for a normal installation is factory
installed in the condensing unit.
GSX, GSZ, ASX, ASZ, SSX, SSZ, DSX, DSZ, VSX, and VSZ models are
available in 1 1/2 through 5 ton sizes and use R-410A refrigerant.
They are designed for 208/230 volt single phase applications.
GSX/GSZ *****3 models are available in 3, 4, and 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt 3phase applications.
ASX, ASZ, DSX and DSZ R-410A model units use the Copeland Scroll
"Ultratech" Series compressors which are specifically designed
for R-410A refrigerant. These units also have Copeland
ComfortAlert diagnostics.
GSX, GSZ, SSX, SSZ, VSX, and VSZ R-410A model units, except for
GSX130181C*, VSX130181B*, VSX130241E*, VSX130421B*, and
VSX130481B*, use the Copeland Scroll "Ultratech" Series compressors which are specifically designed for R-410A refrigerant.
There are a number of design characteristics which are different
from the traditional reciprocating and/or scroll compressors.
"Ultractech" Series scroll compressors will not have a discharge
thermostat. Some of the early model scroll compressors required
discharge thermostat.
"Ultratech" Series scroll compressors use "POE" or polyolester
oil which is NOT compatible with mineral oil based lubricants
like 3GS. "POE" oil must be used if additional oil is required.
The MBR blower cabinet uses a PSC motor. It is approved for
applications with cooling coils of up to 0.5 inches W.C. external
static pressure.
The MBR/MBE blower cabinets with proper coil matches can be
positioned for upflow, counterflow, horizontal right or horizontal left operation. All units are constructed with R-4.2 insulation.
In areas of extreme humidity (greater than 80% consistently),
insulate the exterior of the blower with insulation having a vapor
barrier equivalent to ductwork insulation, providing local codes
permit.
The CAUF, CAPF and CAPT coils are designed for upflow and
counterflow applications. The CACF and CHPF coils are designed
for horizontal applications.
AR*F, ASPF, ASUF, ASPT
Multi-Position Air Handler
These one-piece multi-position air handlers are used with R410A and are available in 2 to 5 ton sizes with optional 3 kW to
25kW electric heat kits available for field installation. The AR*F
unit’s blower design includes a PSC motor and is compatible with
heat pumps and cooling applications. ASUF and ASPT units use
an EEM blower motor and are compatible with heat pumps and
cooling applications.
This appliance can be installed in the vertical or left horizontal
position without modification. The horizontal right and downflow
positions require product modification. This product is designed
®
for zero inches (0 inches) clearance; however, adequate access
for service or replacement must be considered without removing
permanent structure. This unit can be installed on a platform
when deemed necessary.
In an attic installation a secondary drain pan must be provided
by the installer and placed under the entire unit with a separate
drain line properly sloped and terminated in an area visible to
the owner. This secondary drain pan is required in the event that
there is a leak or main drain blockage. Closed cell insulation
should be applied to the drain lines in unconditioned spaces
where sweating may occur.
NOTE: Single piece air handlers are factory-sealed to achieve a
2% or less leakage rate at 1.0" water gauge external duct static
pressure.
COILS AND BLOWER COILS
MBR/MBE blower cabinets are designed to be used as a two-piece
blower and coil combination. MBR/MBE/MBVC blower sections
can be attached to cased evaporator coil. This two-piece arrangement allows for a variety of mix-matching possibilities providing
greater flexibility. The MBE/MBVC blower cabinets use a variable
speed motor that maintains a constant airflow with a higher duct
static.
MBE blower cabinests are approved for applications with cooling coils of up to 0.8 inches W.C. external static pressure. The MBE
models includes a feature that allows airflow to be changed by
+10% or -15%. The MBVC models allow airflow trimming of +/10%.
69
Page 70
PRODUCT DESIGN
The ASX [16 & 18], ASZ [16 & 18], DSX[16 & 18] and DSZ [16 & 18]
series split system units use a two-stage scroll compressor. The
two-step modulator has an internal unloading mechanism that
opens a bypass port in the first compression pocket, effectively
reducing the displacement of the scroll. The opening and closing
of the bypass port is controlled by an internal electrically
operated solenoid.
The ZPS/ZRS two-step modulated scroll uses a single step of
unloading to go from full capacity to approximately 67% capacity. A single speed, high efficiency motor continues to run while
the scroll modulates between the two capacity steps.
FIGURE A
As this motion occurs, the pockets between the two forms are
slowly pushed to the center of the two scrolls while simultaneously being reduced in volume. When the pocket reaches the
center of the scroll form, the gas, which is now at a high pressure,
is discharged out of a port located at the center.
During compression, several pockets are being compressed
simultaneously, resulting in a very smooth process. Both the
suction process (outer portion of the scroll members) and the
discharge process (inner portion) are continuous.
Some design characteristics of the Compliant Scroll compressor
are:
• Compliant Scroll compressors are more tolerant of liquid
refrigerant.
NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
• "Ultratech" Series scroll compressors use "POE" or polyolester
oil which is NOT compatible with mineral oil based lubricants like 3GS. "POE" oil must be used if additional oil is
required.
• Compliant scroll compressors perform "quiet" shutdowns
that allow the compressor to restart immediately without the
need for a time delay. This compressor will restart even if the
system has not equalized.
NOTE: Operating pressures and amp draws may differ from
standard reciprocating compressors. This information can
be found in the unit's Technical Information Manual.
A scroll is an involute spiral which, when matched with a mating
scroll form as shown, generates a series of crescent shaped gas
pockets between the two members.
During compression, one scroll remains stationary (fixed scroll)
while the other form (orbiting scroll) is allowed to orbit (but not
rotate) around the first form.
70
Page 71
PRODUCT DESIGN
c
CAPACITY CONTROL - LEGACY MODELS
During the compression process, there are several pockets within
the scroll that are compressing gas. Modulation is achieved by
venting a portion of the gas in the first suction pocket back to the
low side of the compressor thereby reducing the effective displacement of the compressor. See Figure A. Full capacity is
achieved by blocking these vents, increasing the displacement to
100%. A solenoid in the compressor, controlled by an external 24volt ac signal, moves the slider ring that covers and uncovers
these vents. The vent covers are arranged in such a manner that
the compressor operates somewhere around 67% capacity when
the solenoid is not energized and 100% capacity when the
solenoid is energized. The loading and unloading of the two step
scroll is done “on the fly” without shutting off the motor between
steps. See Figure B below. The unloaded mode default was chosen
for two reasons:
Molded Plug w/
Rectifier
24 Va
1. It is expected that the majority of run hours will be in the low
capacity, unloaded mode.
2. It allows a simple two-stage thermostat to control capacity
through the second stage in both cooling and possibly heating if desired.
UNLOADER SOLENOID
A nominal 24-volt direct current coil activates the internal
unloader solenoid. The input control circuit voltage must be 18
to 28 volt ac. The coil power requirement is 20 VA. The external
electrical connection is made with a molded plug assembly. This
plug is connected to the Comfort Alert™ or CoreSense™ Module
(dependent upon which module you are using) which contains a
full wave rectifier to supply direct current to the unloader coil.
C
R
Internal Unloader
Coil
FIGURE B
Line
Run Capacitor
S
Line
COOLING
The refrigerant used in the system is R-410A. It is a clear,
colorless, non-toxic and non-irritating liquid. R-410A is a 50:50
blend of R-32 and R-125. The boiling point at atmospheric
pressure is -62.9°F.
A few of the important principles that make the refrigeration cycle
possible are: heat always flows from a warmer to a cooler body.
Under lower pressure, a refrigerant will absorb heat and vaporize
at a low temperature. The vapors may be drawn off and condensed at a higher pressure and temperature to be used again.
The indoor evaporator coil functions to cool and dehumidify the
air conditioned spaces through the evaporative process taking
place within the coil tubes.
NOTE: The pressures and temperatures shown in the refrigerant
cycle illustrations on the following pages are for demonstration
purposes only. Actual temperatures and pressures are to be
obtained from the "Expanded Performance Chart".
Liquid refrigerant at condensing pressure and temperatures,
(270 psig and 122°F), leaves the outdoor condensing coil through
the drier and is metered into the indoor coil through the metering
device. As the cool, low pressure, saturated refrigerant enters the
tubes of the indoor coil, a portion of the liquid immediately
vaporizes. It continues to soak up heat and vaporizes as it
proceeds through the coil, cooling the indoor coil down to about
48°F.
Heat is continually being transferred to the cool fins and tubes
of the indoor evaporator coil by the warm system air. This
warming process causes the refrigerant to boil. The heat removed
from the air is carried off by the vapor.
As the vapor passes through the last tubes of the coil, it becomes
superheated. That is, it absorbs more heat than is necessary to
vaporize it. This is assurance that only dry gas will reach the
compressor. Liquid reaching the compressor can weaken or
break compressor valves.
The compressor increases the pressure of the gas, thus adding
more heat, and discharges hot, high pressure superheated gas
into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being warmer than
the outdoor air, first loses its superheat by heat transferred from
the gas through the tubes and fins of the coil. The refrigerant now
becomes saturated, part liquid, part vapor and then continues to
give up heat until it condenses to a liquid alone. Once the vapor
is fully liquefied, it continues to give up heat which subcools the
liquid, and it is ready to repeat the cycle.
71
Page 72
SYSTEM OPERATION
HEATING
The heating portion of the refrigeration cycle is similar to the
cooling cycle. By energizing the reversing valve solenoid coil, the
flow of the refrigerant is reversed. The indoor coil now becomes
the condenser coil, and the outdoor coil becomes the evaporator
coil.
The check valve at the indoor coil will open by the flow of
refrigerant letting the now condensed liquid refrigerant bypass
the indoor expansion device. The check valve at the outdoor coil
will be forced closed by the refrigerant flow, thereby utilizing the
outdoor expansion device.
The restrictor orifice used with the CA*F, CHPF and CH**FCB coils
will be forced onto a seat when running in the cooling cycle, only
allowing liquid refrigerant to pass through the orifice opening.
In the heating cycle, it will be forced off the seat allowing liquid
to flow around the restrictor. A check valve is not required in this
circuit.
COOLING CYCLE
For legacy room thermostat: When the room thermostat calls for
cool, the contacts of the room thermostat close making terminals R to Y1 & G (if thermostat calls for low stage cool), or R to
Y1, Y2 & G (if thermostat calls for high stage cool), the low voltage
circuit of the transformer is completed. Current now flows
through the magnetic holding coils of the compressor contactor
(CC) and fan relay (RFC). If thermostat calls for high stage cool,
the microprocessor on the UC board will also energize the
compressor high stage solenoid to run the compressor at full
capacity.
This draws in the normally open contact CC, starting the compressor and condenser fan motors in either low or high stage
depending on the thermostat’s demand. At the same time, contacts RFC close, starting the indoor fan motor.
When the thermostat is satisfied, it opens its contacts, breaking
the low voltage circuit, causing the compressor contactor and
indoor fan relay to open, shutting down the system.
If the room thermostat fan selector switch should be set on the
“on” position, then the indoor blower would run continuously
rather than cycling with the compressor.
GSZ, ASZ, SSZ, DSZ, and VSZ models energize the reversing valve
thorough the "O" circuit in the room thermostat. Therefore, the
reversing valve remains energized as long as the thermostat
subbase is in the cooling position. The only exception to this is
during defrost.
For heat pumps, during cooling cycle the reversing valve is
energized as the room thermostat closes “O” terminal to R and
the microprocessor on the UC board responds to such a condition by energizing the solenoid coil on the reversing valve.
DEFROST CYCLE
The defrosting of the outdoor coil is jointly controlled by the
defrost control board and the defrost thermostat.
Solid State Defrost Control
During operation the power to the circuit board is controlled by
a temperature sensor, which is clamped to a return bend (3/8"
coils) or a feeder tube (5 mm coils) entering the outdoor coil.
Defrost timing periods of 30, 60, or 90 minutes may be selected
by connecting the circuit board jumper to 30, 60, or 90 respectively. Accumulation of time for the timing period selected starts
when the sensor closes (approximately 31° F), and when the room
thermostat calls for heat. At the end of the timing period, the unit’s
defrost cycle will be initiated provided the sensor remains
closed. When the sensor opens (approximately 75° F), the defrost
cycle is terminated and the timing period is reset. If the defrost
cycle is not terminated due to the sensor temperature, a ten
minute override interrupts the unit’s defrost period. The new
upgraded defrost control has a 12 minute override interrupt.
HEATING CYCLE
The reversing valve on the GSZ, SSZ, ASZ and DSZ models is
energized in the cooling cycle through the "O" terminal on the
room thermostat.
These models have a 24 volt reversing valve coil. When the
thermostat selector switch is set in the cooling position, the "O"
terminal on the thermostat is energized all the time.
Care must be taken when selecting a room thermostat. Refer to the
installation instructions shipped with the product for approved
thermostats.
When the room thermostat calls for heat, the contacts of the
room thermostat close making terminals R to Y & G, the low
voltage circuit of the transformer is completed. Current now
flows through the magnetic holding coils of the compressor
contactor (CC) and fan relay (RFC).
This draws in the normally open contact CC, starting the compressor condenser fan motors. At the same time, contacts RFC
close, starting the indoor fan motor.
When the thermostat is satisfied, it opens its contacts, breaking
the low voltage circuit, causing the compressor contactor and
indoor fan relay to open, shutting down the system.
If the room thermostat fan selector switch should be set to the
“on” position, then the indoor blower would run continuously
rather than cycling with the compressor.
When the thermostat is satisfied, appropriate commands are
sent to the UC control. The compressor relay and outdoor fan
relay is de-energized. The compressor high stage solenoid
is de-energized if it was energized. The UC control sends an
appropriate command to the indoor unit to de-energize the
indoor blower motor.
72
Page 73
SYSTEM OPERATION
COOLING CYCLE
Reversing Valve
(Energized)
Indoor
Coil
HEATING CYCLE
Outdoor
Coil
Accumulator
Thermostatic
Expansion
Valve
Bi-Flow
Filter Dryer
Check Valve
Indoor
Coil
Reversing Valve
(De-Energized)
Outdoor
Coil
Accumulator
Thermostatic
Expansion
Valve
Bi-Flow
Filter Dryer
Check Valve
73
Page 74
SYSTEM OPERATION
EXPANSION VALVE/CHECK VALVE ASSEMBLY IN
COOLING OPERATION
Most expansion valves used in current Amana® Brand Heat Pump products
use an internally checked expansion valve.
This type of expansion valve does not require an external check valve as shown above.
However, the principle of operation is the same.
RESTRICTOR ORIFICE ASSEMBLY IN
COOLING OPERATION
EXPANSION VALVE/CHECK VALVE ASSEMBLY IN
HEATING OPERATION
RESTRICTOR ORIFICE ASSEMBLY IN
HEATING OPERATION
In the cooling mode, the orifice is pushed into its seat,
forcing refrigerant to flow through the metered hole in
the center of the orifice.
74
In the heating mode, the orifice moves back off its seat,
allowing refrigerant to flow unmetered around the
outside of the orifice.
Page 75
SYSTEM OPERATION
AFE18-60A CONTROL BOARD
DESCRIPTION
The AFE18 control is designed for use in heat pump applications
where the indoor coil is located above/downstream of a gas or
fossil fuel furnace. It will operate with single and two stage heat
pumps and single and two stage furnaces. The AFE18 control will
turn the heat pump unit off when the furnace is turned on. An antishort cycle feature is also incorporated which initiates a 3
minute timed off delay when the compressor goes off. On initial
power up or loss and restoration of power, this 3 minute timed
off delay will be initiated. The compressor won’t be allowed to
restart until the 3 minute off delay has expired. Also included is
a 5 second de-bounce feature on the “Y, E, W1 and O” thermostat
inputs. These thermostat inputs must be present for 5 seconds
before the AFE18 control will respond to it.
An optional outdoor thermostat, OT18-60A, can be used with the
AFE18 to switch from heat pump operation to furnace operation
below a specific ambient temperature setting, i.e. break even
temperature during heating. When used in this manner, the “Y”
heat demand is switched to the “W1” input to the furnace by the
outdoor thermostat and the furnace is used to satisfy the first
stage “Y” heat demand. On some controls, if the outdoor thermo-
stat fails closed in this position during the heating season, it will
turn on the furnace during the cooling season on a “Y” cooling
demand. In this situation, the furnace produces heat and
increases the indoor temperature thereby never satisfying the
cooling demand. The furnace will continue to operate and can
only be stopped by switching the thermostat to the off position
or removing power to the unit and then replacing the outdoor
thermostat. When the AFE18 receives a “Y” and “O” inputfromthe indoor thermostat, it recognizes this as a cooling demand
in the cooling mode. If the outdoor thermostat is stuck in the
closed position switching the “Y” demand to the “W1” furnace
input during the cooling mode as described above, the AFE18
won’t allow the furnace to operate. The outdoor thermostat will
have to be replaced to restore the unit to normal operation.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
75
Page 76
TROUBLESHOOTING CHART
COOLING/HP ANALYS IS CH AR T
Com plaint
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
Pow er Failur e
Blow n Fuse
Unbalanced Power, 3PH
Loose Connection
Shorted or Broken Wires
Open Fan Overload
Faulty Thermostat
Faulty Transformer
Shorted or Open Capacitor
Internal Compress or Overload Open
Shorted or Grounded Compressor
Comp re ss or Stuc k
Faulty Compressor Contactor
Faulty Fan Relay
Open Control Circuit
Low Voltage
Faulty Evap. Fan Motor
Shorted or Grounded Fan Motor
Improper Cooling Anticipator
Shortage of Refrigerant
Restricted Liquid Line
Open Element or Limit on Elec. Heater
Dirty A ir Filter
Dirty Indoor Coil
Not enough air across Indoor Coil
Too much air across Indoor Coil
Overcharge of Refrigerant
Dirty Outdoor Coil
Noncondensibles
Recirculation of Condens ing A ir
Infiltration of Outdoor Air
Improperly Located Thermostat
Air Flow Unbalanced
Sys tem Undersiz ed
Broken Internal Parts
Broken Valves
Ineff icient Compressor
Wrong Type Expansion Valve
Expansion Device Restricted
Oversized Expansion Valve
Undersized Expansion Valve
Expansion Valve Bulb Loose
Inoperative Expansion Valve
Loose Hold-dow n Bolts
Faulty Reversing Valve
Faulty Defrost Control
Faulty Defrost Thermostat
Flow rator Not Seating Properly
No Co oling
SYMPTOM
System will not start
Compressor will not start - fan runs
Comp. and Cond. Fan will not start
Evaporator fan will not start
Condenser fan will not start
Compressor runs - goes off on overload
Compressor cycles on overload
Unsatisfactory
Cooling/Heating
System runs continuously - little cooling/htg
Too cool and then too warm
•
•••
•••
•••
••••••
••
••••
••
•••••
•
••
•••
•••
•
•
•••
••
••
••
••
•••• •
♦♦
••••
••••
••••
•••
•••
••
•••
•••
••
••
••
••••
•
••••••
•••••••
••
•••••
•••
•
•
• C ooling or He ating C ycle (He at Pum p)
•••
System
Ope rati ng
Pressures
Not cool enough on warm days
Certain areas too cool, others too warm
Compressor is noisy
System runs - blows cold air in heating
Unit will not terminate defrost
Unit will not defrost
Low suction pressure
Low head pressure
High suction pressure
High head pressure
♦
♦
♦
♦
♦
♦
♦
•
♦
••
♦
♦
••
♦
♦
♦
•
••
•
•
♦
••
•
♦♦♦♦♦♦
♦♦♦♦♦♦
♦♦♦♦♦♦♦
Heatin g Cycle Only (He at Pum p)
♦
Test Method
Remedy
See Service Procedure Ref.
Tes t V olta geS -1
Inspect Fuse Size & TypeS-1
Tes t V olta geS -1
Ins pect Connection - TightenS-2, S- 3
Test Circuits With OhmmeterS-2, S-3
Test Continuity of OverloadS-17A
Test Continuity of Thermostat & WiringS-3
Check Control Circuit w ith VoltmeterS-4
Test CapacitorS-15
Test Continuity of OverloadS-17A
Test Motor WindingsS-17 B
Us e Tes t Cor dS- 17D
Test Continuity of Coil & ContactsS-7, S-8
Test Continuity of Coil A nd ContactsS-7
Test Control Circuit w ith V oltmeterS-4
Tes t V olta geS -1
Repair or ReplaceS-16
Test Motor WindingsS- 16
Check Resistance of AnticipatorS-3B
Test For Leaks, Add RefrigerantS-101,103
Remove Restriction, Replace Restricted PartS-112
Test Heater Element and ControlsS-26,S-27
Inspect Filter-Clean or Replace
Inspect Coil - Clean
Check Blow er Speed, Duct Static Press, FilterS-200
Reduce Blow er SpeedS- 200
Recover Part of ChargeS-113
Inspect Coil - Clean
Recover Charge, Evac uate, RechargeS -114
Remove Obstruction to Air Flow
Check Window s, Doors , V ent Fans, Etc.
Relocate Thermostat
Readjust Air Volume Dampers
Refigure Cooling Load
Replace CompressorS-115
Test Compressor Ef ficiencyS-104
Test Compressor Ef ficiencyS-104
Replace ValveS-110
Remove Restriction or Replace Expansion DeviceS-110
Replace Valve
Replace Valve
Tighten Bulb BracketS-105
Check Valve OperationS-110
Tigh ten B olts
Replace Valve or SolenoidS-21, 122
Tes t Con tro l S- 24
Test Defros t ThermostatS-25
Check Flow rator & Seat or Replace Flow ratorS-111
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to
do so may cause property damage, personal injury or death.
77
Page 78
SERVICING
S-1CHECKING VOLTAGE
1. Remove outer case, control panel cover, etc., from unit being
tested.
With power ON:
WARNING
Line Voltage now present.
2. Using a voltmeter, measure the voltage across terminals L1
and L2 of the contactor for the condensing unit or at the field
connections for the air handler or heaters.
3. No reading - indicates open wiring, open fuse(s) no power or
etc., from unit to fused disconnect service. Repair as needed.
4. With ample voltage at line voltage connectors, energize the
unit.
5. Measure the voltage with the unit starting and operating, and
determine the unit Locked Rotor Voltage. NOTE: If checking
heaters, be sure all heating elements are energized.
Locked Rotor Voltage is the actual voltage available at the
compressor during starting, locked rotor, or a stalled condition. Measured voltage should be above minimum listed in
chart below.
To measure Locked Rotor Voltage attach a voltmeter to the run
"R" and common "C" terminals of the compressor, or to the T
and T2 terminals of the contactor. Start the unit and allow the
compressor to run for several seconds, then shut down the
unit. Immediately attempt to restart the unit while measuring
the Locked Rotor Voltage.
6. Locked rotor voltage should read within the voltage tabulation as shown. If the voltage falls below the minimum voltage,
check the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the local
power company in regard to either low or high voltage.
Unit Supply Voltage
VoltageMin.Max
208/230197253
460414506
S-2CHECKING WIRING
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Check wiring visually for signs of overheating, damaged
insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected open
wires.
3. If any wires must be replaced, replace with comparable gauge
and insulation thickness.
S-3CHECKING THERMOSTAT AND WIRING
Thermostat Wiring: The maximum wire length for 18 AWG thermostat wire is 100 feet.
S-3A THERMOSTAT WIRING
WARNING
Line Voltage now present.
1
With power ON, thermostat calling for cooling
1. Use a voltmeter to check for 24 volts at thermostat wires C and
Y in the condensing unit control panel.
2. No voltage indicates trouble in the thermostat, wiring or
external transformer source.
3. Check the continuity of the thermostat and wiring. Repair or
replace as necessary.
Indoor Blower Motor
With power ON:
WARNING
Line Voltage now present.
NOTE: When operating electric heaters on voltages other than
240 volts, refer to the System Operation section on electric
heaters to calculate temperature rise and air flow. Low voltage
may cause insufficient heating.
78
1. Set fan selector switch at thermostat to "ON" position.
2. With voltmeter, check for 24 volts at wires C and G.
3. No voltage indicates the trouble is in the thermostat or wiring.
4. Check the continuity of the thermostat and wiring. Repair or
replace as necessary.
Resistance Heaters
1. Set room thermostat to a higher setting than room temperature so both stages call for heat.
2. With voltmeter, check for 24 volts at each heater relay.
Page 79
SERVICING
3. No voltage indicates the trouble is in the thermostat or wiring.
4. Check the continuity of the thermostat and wiring. Repair or
replace as necessary.
NOTE: Consideration must be given to how the heaters are wired
(O.D.T. and etc.). Also safety devices must be checked for continuity.
S-4CHECKING TRANSFORMER AND CONTROL CIRCUIT
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
A step-down transformer (208/240 volt primary to 24 volt secondary) is provided with each indoor unit. This allows ample
capacity for use with resistance heaters. The outdoor sections
do not contain a transformer (see note below).
WARNING
Disconnect ALL power before servicing.
1. Remove control panel cover, or etc., to gain access to transformer.
With power ON:
WARNING
Line Voltage now present.
2. Using a voltmeter, check voltage across secondary voltage
side of transformer (R to C).
3. No voltage indicates faulty transformer, bad wiring, or bad
splices.
4. Check transformer primary voltage at incoming line voltage
connections and/or splices.
5 If line voltage available at primary voltage side of trans-
former and wiring and splices good, transformer is inoperative. Replace.
S-7CHECKING CONTACTOR AND/OR RELAYS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
The compressor contactor and other relay holding coils are
wired into the low or line voltage circuits. When the control
circuit is energized, the coil pulls in the normally open contacts
or opens the normally closed contacts. When the coil is deenergized, springs return the contacts to their normal position.
NOTE: Most single phase contactors break only one side of the
line (L1), leaving 115 volts to ground present at most internal
components.
NOTE: The compressor contactor/relay in ComfortNet
ready equipment is fully integrated into the unitary (UC) control. The compressor contactor/relay coil on the UC control
is non-serviceable.
1. Remove the leads from the holding coil.
2. Using an ohmmeter, test across the coil terminals.
If the coil does not test continuous, replace the relay or contactor.
TM
S-8CHECKING CONTACTOR CONTACTS
WARNING
Disconnect ALL power before servicing.
SINGLE PHASE:
1. Disconnect the wire leads from the terminal (T) side of the
contactor.
2. With power ON, energize the contactor.
WARNING
Line Voltage now present.
3. Using a voltmeter, test across terminals.
A. L2 - T1 - No voltage indicates CC1 contacts open.
If a no voltage reading is obtained - replace the contactor.
79
Page 80
SERVICING
T2
VOLT/OHM
METER
Ohmmeter for testing holding coil
Voltmeter for testing contacts
TESTING COMPRESSOR CONTACTOR
(Single Phase)
THREE PHASE
Using a voltmeter, test across terminals:
A.L1-L2, L1-L3, and L2-L3 - If voltage is present, proceed to
B. If voltage is not present, check breaker or fuses on
main power supply..
B.T1-T2, T1-T3, and T2-T3 - If voltage readings are not the
same as in "A", replace contactor.
T1
CC
L1L2
T3L3T2
T1
1. Disconnect wire leads from terminals 2 and 4 of Fan Relay
Cooling and 2 and 4, 5 and 6 of Fan Relay Heating.
2. Using an ohmmeter, test between 2 and 4 - should read open.
Test between 5 and 6 - should read continuous.
3. With power ON, energize the relays.
WARNING
Line Voltage now present.
4
OHMMETER
2
5
TESTING FAN RELAY
4. Using an ohmmeter, test between 2 and 4 - should read
continuous . Test between 5 and 6 - should read open.
5. If not as above, replace the relay.
CHECKING RELAY CONTACTS - PSC FAN MOTOR
3
1
CC
VOLT/OHM
METER
Ohmmeter for testing holding coil
Voltmeter for testing contacts
TESTING COMPRESSOR CONTACTOR
(Three-Phase)
S-9CHECKING FAN RELAY CONTACTS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
L2
L1
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect the motor leads from 6-circuit fan motor wire
harness.
2. Connect a voltmeter between circuit 3 and circuits 2 (low
speed) or 1 (high speed).
NOTE: Circuit 3 is connected directly to L2.
3. Energize the system at low or high stage.
WARNING
Line Voltage now present.
4. The measured voltage between circuit 3 and circuits 2 or 1
should be approximately 0VAC, which indicates the relay
contacts are closed. A voltage measurement of approximately 115VAC indicates the relay is open. Replace the
control if the relay checks open when it should be closed. See
notes and cautions below.
80
Page 81
SERVICING
NOTE: Ensure any ON delays have expired before making
voltage measurements
CAUTION: Prolonged operation with the condenser fan motor
disconnected will cause the high pressure switch to trip.
S-10 MBR/AR*F ELECTRONIC BLOWER TIME DELAY
RELAY
The MBR/AR*F contains an Electronic Blower Time Delay Relay
board, B1370735. This board provides on/off time delays for the
blower motor in cooling and heat pump heating demands when
“G” is energized.
During a cooling or heat pump heating demand, 24Vac is
supplied to terminal “G” of the EBTDR to turn on the blower
motor. The EBTDR initiates a 7 second delay on and then
energizes it’s onboard relay. The relay on the EBTDR board
closes it’s normally open contacts and supplies power to the
blower motor. When the “G” input is removed, the EBTDR
initiates a 65 second delay off. When the 65 seconds delay
expires the onboard relay is de-energized and it’s contacts open
and remove power from the blower motor.
During an electric heat only demand, “W1” is energized but “G”
is not. The blower motor is connected to the normally closed
contacts of the relay on the EBTDR board. The other side of this
set of contacts is connected to the heat sequencer on the heater
assembly that provides power to the first heater element. When
“W1” is energized, the sequencer will close it’s contacts within
10 to 20 seconds to supply power to the first heater element and
to the blower motor through the normally closed contacts on the
relay on the EBTDR. When the “W1” demand is removed, the
sequencer opens it contacts within 30 to 70 seconds and
removes power from the heater element and the blower motor.
The EBTDR also contains a speedup terminal to reduce the delays
during troubleshooting of the unit. When this terminal is
shorted to the common terminal, “C”, on the EBTDR board, the
delay ON time is reduced to 3 seconds and the delay OFF time
is reduced to 5 second.
Two additional terminals, M1 and M2, are on the EBTDR board.
These terminals are used to connect the unused leads from the
blower motor and have no affect on the board’s operation.
S-12 CHECKING HIGH PRESSURE CONTROL
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
The high pressure control capillary senses the pressure in the
compressor discharge line. If abnormally high condensing
pressures develop, the contacts of the control open, breaking the
control circuit before the compressor motor overloads. This
control is automatically reset.
1. Using an ohmmeter, check across terminals of high pressure
control, with wire removed. If not continuous, the contacts
are open.
2. Attach a gauge to the dill valve port on the base valve.
With power ON:
WARNING
Line Voltage now present.
3. Start the system and place a piece of cardboard in front of the
condenser coil, raising the condensing pressure.
4. Check pressure at which the high pressure control cuts-out.
If it cuts-out at 610 PSIG ± 10 PSIG, it is operating normally
(See causes for high head pressure in Service Problem Analysis Guide). If it cuts out below this pressure range, replace
the control.
S-11 CHECKING LOSS OF CHARGE PROTECTOR
(Heat Pump Models)
The loss of charge protectors senses the pressure in the liquid
line and will open its contacts on a drop in pressure. the low
pressure control will automatically reset itself with a rise in
pressure.
The low pressure control is designed to cut-out (open) at
approximately 21 PSIG. It will automatically cut-in (close) at
approximately 50 PSIG.Test for continuity using a VOM and if
not as above, replace the control.
S-13 CHECKING LOW PRESSURE CONTROL
The low pressure control senses the pressure in the suction line
and will open its contacts on a drop in pressure. The low pressure
control will automatically reset itself with a rise in pressure.
The low pressure control is designed to cut-out (open) at approximately 21 PSIG for heat pumps and 55 PSIG for air conditioners.
It will automatically cut-in (close) at approximately 50 PSIG for
heat pumps and 95 PSIG for air conditioners.
Test for continuity using a VOM and if not as above, replace the
control.
81
Page 82
SERVICING
S-10 COPELAND COMFORT ALERT™
DIAGNOSTICS - 3-WIRE MODULE
Applies to ASX /ASZ and DSX/DSZ units
Comfort Alert™ is self-contained with no required external sensors and is designed to install directly into the electrical box of
any residential condensing unit that has a Copeland Scroll™
compressor inside.
Once attached, Comfort Alert provides around-the-clock monitoring for common electrical problems, compressor defects and
broad system faults. If a glitch is detected, an LED indicator
flashes the proper alert codes to help you quickly pinpoint the
problem. See Diagnostic Table: 3-Wire Comfort Alert Module on
previous page.)
S-10B COPELAND CORESENSE™
DIAGNOSTICS - 3-WIRE MODULE
Applies to ASX /ASZ and DSX/DSZ units
Bold line shows field
installed wiring
Dashed line shows thermostat
demand wi ring in system without
HTCO, HPCO, CPCO, and ECB
Comfort Alert
Diagnostics Module
HTCO High Temperature Cut Out Switch
HPCO High Pressure Cut Out Switch
LPCO Low Pressure Cut Out Switch
Y
C
R
Schematic Abbreviation Descriptions
CC
ECB
HTCO
LOGIC
R
CC Compressor Cont actor
ECB Electro nic Control Board
(Defrost or Time Delay)
Wiring Schematic - 3-Wire Comfort Alert Module
LPCO
C
HPCO
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
The CoreSense™ module is self-contained with no required exter-
Y1
nal sensors and works with any residential condensing unit that
has a Copeland Scroll™ compressor inside.
Once attached, CoreSense™ provides around-the-clock monitoring for common electrical problems, compressor defects and
broad system faults. If a glitch is detected, an LED indicator
flashes the proper alert codes to help you quickly pinpoint the
problem. See Diagnostic Table: 3-Wire CoreSense™ Module on
following pages.)
82
Page 83
SERVICING
DIAGNOSTICS TABLE: 2-WIRE COMFORT ALERT™ MODULE
Status LEDStatus LED DescriptionStatus LED Troubleshooting Information
Green “POWER” Module has power
Red “TRIP”
Yellow “ALERT”Long Run Time
Flash Code 1
Yellow “ALERT”System Pressure Trip
Flash Code 2
Yellow “ALERT”Short Cycling
Flash Code 3
Yellow “ALERT”Locked Rotor
Flash Code 4
Yellow “ALERT”Open Circuit
Flash Code 5
Yellow “ALERT”Open Start Circuit
Flash Code 6
Yellow “ALERT”Open Run Circuit
Flash Code 7
Yellow “ALERT”Low Voltage
Flash Code 9
Thermostat demand signal1. Compress or protector is open
Y1 is present, but the2. Outdoor unit power disconnect is open
com pressor is not 3. Com pressor circuit breaker or fuse(s) is open
running 4. Broken wire or connec tor is not making contac t
Compressor is2. Evaporator blower is not running
running extremely3. Evaporator coil is frozen
long run cy cles4. Faulty metering device
Discharge or suction2. Condenser coil poor air circulation (dirty, block ed, damaged)
pressure out of limits or3. Condenser fan is not running
compressor overloaded4. Return air duct has substantial leakage
Compres sor is running2. Time delay relay or control board defective
only briefly3. If high pressure switch present go to Flash Code 2 information
Current only in run circuit2. Open circuit in compress or start wiring or connections
Current only in start c ircuit2. Compress or run winding is dam aged
Control circuit < 17VAC2. Low line voltage (contact utility if voltage at disconnect is low)
Supply voltage is present at module terminals
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
1. Low refrigerant charge
5. Condenser coil is dirty
6. Liquid line restriction (filter drier block ed if present in system)
7. Thermostat is malfunctioning
1. High head press ure
5. If low pressure switc h present in system,
check Flash Code 1 information
1. Thermostat demand signal is intermittent
4. If low pressure switch present go to Flash Code 1 information
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
3. Exces sive liquid refrigerant in compressor
4. Compressor bearings are seized
1. Outdoor unit power disc onnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Open circuit in compress or supply wiring or connections
6. Unusually long compressor protector reset time
due to extreme ambient temperature
7. Compressor windings are damaged
1. Run capacitor has failed
3. Compressor start winding is damaged
1. Open circuit in compress or run wiring or connections
1. Control circuit transformer is overloaded
•FLASH CODE NUMBER CORRESPONDS TO A NUMBER OF LED FLASHES, FOLLOWED BY A PAUSE AND THEN REPEATED
•TRIP AND ALERT LEDS FLASHING AT SAME TIME MEANS CONTROL CIRCUIT VOLTAGE IS TOO LOW FOR OPERATION.
•LAST ALERT FLASH CODE IS DISPLAYED FOR 1 MINUTE AFTER MODULE IS POWERED ON.
83
Page 84
SERVICING
Once attached, CoreSense™ provides around-the-clock monitoring for common electrical problems, compressor defects and
broad system faults. If a glitch is detected, an LED indicator
flashes the proper alert codes to help you quickly pinpoint the
problem. See Diagnostic Table: 2-Wire Comfort Alert™ Module on
following pages.)
Indoor
Unit
HTCO H igh Temperature Cut Out Switch
HPCO High Pressure Cut Out Switch
LPCO Low Pres sure Cut Out Switch
C
Y
Schematic Abbreviation Descriptions
CC Compre ssor Contactor
ECB Electronic Control Board
(Defrost or Time Delay)
Wiring Schematic - 3-Wire CoreSense™ Alert Module
Reset
Switch
Run/Alert
LED
Trip/Lock-Out
Red LED
Protection
Output
Data Port
One
Current
Sensor
Schematic Abbreviation Descriptions
HTCO High Temperature Cut Out Switch
HPCO High Pres sure Cut Out Switch
LPCO Low Pressure Cut Out Switch
CC Compressor Contactor
ECB Electronic Control Board
Wiring Schematic - 2-Wire CoreSense™ Module
(Defrost or Time Delay)
DIAGNOSTICS - 2-WIRE MODULE
Applies to ASX130[18-60]CA, ASX140[18-36]1CA,
ASX140421DA, and ASX140[48-60]1BA units
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
The CoreSense™ module is self-contained with no required external sensors and works with any residential condensing unit that
has a Copeland Scroll™ compressor inside.
84
Page 85
SERVICING
DIAGNOSTICS TABLE: CORESENSE
Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated.
TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation.
™ MODULE
85
Page 86
SERVICING
DIAGNOSTICS TABLE: CORESENSE™ MODULE (CONT.)
Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated.
TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation.
86
Page 87
SERVICING
Table 1 - Quick Reference Table
87
Page 88
SERVICING
S-15 CHECKING CAPACITOR
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and main windings
of a single phase permanent split capacitor motor. The capacitors primary function is to reduce the line current while greatly
improving the torque characteristics of a motor. This is accomplished by using the 90° phase relationship between the capacitor current and voltage in conjunction with the motor windings,
so that the motor will give two phase operation when connected
to a single phase circuit. The capacitor also reduces the line
current to the motor by improving the power factor.
The line side of this capacitor is marked with "COM" and is wired
to the line side of the circuit.
CAPACITOR, START
SCROLL COMPRESSOR MODELS
In most cases hard start components are not required on Scroll
compressor equipped units due to a non-replaceable check valve
located in the discharge line of the compressor. However, in
installations that encounter low lock rotor voltage, a hard start
kit can improve starting characteristics and reduce light dimming within the home. Only hard start kits approved by Amana
brand or Copeland should be used. "Kick Start" and/or "Super
Boost" kits are not approved start assist devices.
The discharge check valve closes off high side pressure to the
compressor after shut down allowing equalization through the
scroll flanks. Equalization requires only about 1/2 second.
To prevent the compressor from short cycling, a Time Delay
Relay (Cycle Protector) has been added to the low voltabe
circuit.
S-15ARESISTANCE CHECK USING A DIGITAL MULTI-
METER
Figure 1Figure 2
4. Reading will immediately return to the OL = (Open Line)
(Figure 2). Every attempt of Step 2 will show the same result
®
as was in step 4 and Step 5. This indicates that the capacitor
is good.
5. If there is no Change, then capacitor is dead and must be
replaced.
Check for Analog Meter
A. Good Condition - indicator swings to zero and slowly
returns to infinity. (Start capacitor with bleed resistor will
not return to infinity. It will still read the resistance of the
resistor).
B. Shorted - indicator swings to zero and stops there - replace.
C. Open - no reading - replace. (Start capacitor would read
resistor resistance.)
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
Check for Digital Test
1. Set the meter on Ohm range (Set it at lease 1000 Ohm
=1k).
WARNING
Discharge capacitor through a 20 to 30 OHM
resistor before handling.
2. Connect the Meter leads to the Capacitor terminals.
3. Digital meter will show a reading momentarily (Figure 1).
Note the reading.
88
S-15B CAPACITANCE CHECK USING A DIGITAL MULTI-
METER (IN CAPACITANCE MODE)
WARNING
Discharge capacitor through a 20 to 30 OHM
resistor before handling.
NOTE: You can do this test with a multi-meter if you have a
Capacitance meter on your multi-meter.
1. Remove the capacitor from the circuit.
2. Now Select "Capacitance" on your multi-meter.
3. Now connect the capacitor terminals to the multi-meter
leads.
4. If the reading is near to the actual value of the capacitor (i.e.
the printed value on the capacitor). The capacitor is good.
(Note that the reading may be less than the actual printed
value of the capacitor).
5. If you read a significantly lower capacitance or none at all,
then capacitor is dead and must be replaced.
Page 89
SERVICING
A
S-16ACHECKING FAN AND BLOWER MOTOR WINDINGS
(PSC MOTORS)
The auto reset fan motor overload is designed to protect the motor
against high temperature and high amperage conditions by
breaking the common circuit within the motor, similar to the
compressor internal overload. However, heat generated within
the motor is faster to dissipate than the compressor, allow at
least 45 minutes for the overload to reset, then retest.
5. If line voltage is present, reinsert the 5-pin connector and
remove the 16-pin connector.
6. Check for signal (24 volts) at the transformer.
7. Check for signal (24 volts) from the thermostat to the "G"
terminal at the 16-pin connector.
8. Using an ohmmeter, check for continuity from the #1 & #3
(common pins) to the transformer neutral or "C" thermostat
terminal. If you do not have continuity, the motor may
function erratically. Trace the common circuits, locate and
repair the open neutral.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
9. Set the thermostat to "Fan-On". Using a voltmeter, check for
24 volts between pin # 15 (G) and common.
10. Disconnect power to compressor. Set thermostat to call for
cooling. Using a voltmeter, check for 24 volts at pin # 6 and/
or #14.
11. Set the thermostat to a call for heating. Using a voltmeter,
check for 24 volts at pin #2 and/or #11.
1. Remove the motor leads from its respective connection points
and capacitor (if applicable).
2. Check the continuity between each of the motor leads.
3. Touch one probe of the ohmmeter to the motor frame (ground)
and the other probe in turn to each lead.
If the windings do not test continuous or a reading is obtained
from lead to ground, replace the motor.
S-16B CHECKING FAN AND BLOWER MOTOR (ECM
MOTORS)
1
2
3
4
5
Lines 1 and 2 will be connected
for 12OVAC Power Connector
}
applications only
Gnd
AC Line Connection
AC Line Connection
An ECM is an Electronically Commutated Motor which offers many
significant advantages over PSC motors. The ECM has near zero
rotor loss, synchronous machine operation, variable speed, low
noise, and programmable air flow. Because of the sophisticated
electronics within the ECM motor, some technicians are intimated by the ECM motor; however, these fears are unfounded. GE
offers two ECM motor testers, and with a VOM meter, one can
easily perform basic troubleshooting on ECM motors. An ECM
OUT - OUT +
DJUST +/-
Y1Y/Y2
816
7
15
6
14
G (FAN)
motor requires power (line voltage) and a signal (24 volts) to
operate. The ECM motor stator contains permanent magnet. As a
result, the shaft feels "rough" when turned by hand. This is a
characteristic of the motor, not an indication of defective bear-
COOL
DELAY
5
13
EM Ht/W2
4
12
24 Vac (R)
ings.
3
11
COMMON2
WARNING
Line Voltage now present.
1. Disconnect the 5-pin connector from the motor.
2. Using a volt meter, check for line voltage at terminals #4 & #5
W/W1
COMMON1O (REV VALVE)
16-PIN ECM HARNESS CONNECTOR
2
19
HEAT
10
BK/PWM (SPEED)
at the power connector. If no voltage is present:
3. Check the unit for incoming power See section S-1.
4. Check the control board, See section S-40.
If you do not read voltage and continuity as described, the
problem is in the control or interface board, but not the motor.
If you register voltage as described , the ECM power head is
defective and must be replaced.
89
Page 90
SERVICING
S-16C CHECKING ECM MOTOR WINDINGS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect the 5-pin and the 16-pin connectors from the ECM
power head.
2. Remove the 2 screws securing the ECM power head and
separate it from the motor.
3. Disconnect the 3-pin motor connector from the power head
and lay it aside.
4. Using an ohmmeter, check the motor windings for continuity
to ground (pins to motor shell). If the ohmmeter indicates
continuity to ground, the motor is defective and must be
replaced.
5. Using an ohmmeter, check the windings for continuity (pin
to pin). If no continuity is indicated, the thermal limit (over
load) device may be open. Allow motor to cool and retest.
3-pin motor
connector
16-pin
connector
For most applications, the settings are to be changed according
to the electric heat size and the outdoor unit selection.
The MBE/AEPF products use a General Electric ECMTM motor. This
motor provides many features not available on the traditional
PSC motor. These features include:
•Improved Efficiency
•Constant CFM
•Soft Start and Stop
•Improved Humidity Control
MOTOR SPEED ADJUSTMENT
Each ECM™ blower motor has been preprogrammed for operation
at 4 distinct airflow levels when operating in Cooling/Heat Pump
mode or Electric Heat mode. These 4 distinct levels may also be
adjusted slightly lower or higher if desired. The adjustment
between levels and the trim adjustments are made by changing
the dipswitch(s) either to an "OFF" or "ON" position.
DIPSWITCH FUNCTIONS
The MBE / AEPF air handler motors have an electronic control that
contains an eight (8) position dip switch. The function of these
dipswitches are shown in Table 1.
Dipswitch Functions
Dipswitch
Number
1
2
3N/A
4I ndoor Thermostat
5Cooling & Heat
6Pump CFM
7
8
Function
Electric He at
CFM Trim Adju st
Table 1
5-pin
connector
S-16DECM CFM ADJUSTMENTS MBE / AEPF
MBE MOTOR
This section references the operation characteristics of the MBE/
AEPF models motor only. The ECM control board is factory set
with the dipswitch #4 in the “ON” position and all other dipswitches
are factory set in the “OFF” position. When MBE/AEPF are used
with 2-stage cooling units, dipswitch #4 should be in the "OFF"
position.
90
CFM DELIVERY
Tables 2, 3, 5 and 6 show the CFM output for dipswitch combinations 1-2, and 5-6.
Electric Heat Operation
ModelSwitch 1Switch 2CFM
MBE1200
OFF
ON
OFF
OFF
OFF
ON
1,200
1,000
800
ONON600
MBE1600
OFF
ON
OFF
OFF
OFF
ON
1,600
1,400
1,200
ONON1,000
MBE2000
OFF
OFF
ONOFF1,800
OFFON1,600
2,000
ONON1,200
Table 2
Page 91
SERVICING
Cooling/Heat Pump Operation
ModelSwitch 5Switch 6CF M
1,200
1,000
800
1,600
1,400
1,200
2,000
1,800
1,600
MBE 1200
MBE 1600
MBE 2000
OFF
ON
OFF
ONON600
OFF
ON
OFF
ONON1,000
OFF
ON
OFF
ONON1,200
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
Table 3
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 30% of the cooling
setting.
Dipswitch Functions
The AEPF air handler motor has an electronic control that contains an eight (8) position dip switch. The function of these
dipswitches are shown in Table 9.
Dipswitch NumberFunction
1
2
3N/A
4Indoor Thermostat
5
6
7
8
Table 9
Electric Heat
Cooling & Heat Pump CFM
CFM Trim Adjust
Model
AEPF1830
AEPF3036
AEPF3137
AEPF4260
SwitchSwitch
1278
OFFOFFOFFOFF1 1001210
ONOFFOFFOFF890935
OFFONOFFOFF700770
OFFOFFOFFOFF20502150
ONOFFOFFOFF17501835
OFFONOFFOFF16001680
ONONOFFOFF12001260
ONONOFFON10201070
Emergecny
(Electric)
Hea t
Hea t Pump
w/Backup
Hea t
Table 10
Model
AEP F183
0
AEPF3036ONOFFOFFOFF41580
AEPF3137 OFFONOFFOFF3 ½1480
AEPF4260ONONOFFOFF31200
Sw itchSw itch
5678
OFFOFFOFFOFF2 ½1100
ONOFFOFFOFF2800
OFFONOFFOFF1 ½60 0
OFFOFFOFFOFF51 800
ONONOFFON2 ½1020
Nom ina l
Cooling
Tonnage
CFM
Table 11
Thermostat “Fan Only Mode”
During “Fan Only Mode” operation, the CFM output is 30% of the
cooling setting.
CFM Trim Adjust
Minor adjustments can be made through the dip switch combination of 7-8. The following Table 12 shows the switch position
for this feature.
CFM Delivery
Tables 10-Electric Heat and 11-Cooling/Heat Pump show the CFM
output for dipswitch combinations 1-2, and 5-6.
CFMSwitch 7Switch 8
+10 %ONOFF
-15%OFFON
Humidity Control
When using a Humidistat (normally closed), cut jumper PJ6 on the
control board. The Humidistat will only affect cooling airflow by
adjusting the Airflow to 85%.
91
Page 92
SERVICING
(
y
)
g
I
d
t
d
i
l
gg
d?
Ch
k
f
l
i
fl
(t
h
l
t
t
ity)
Check
for
undercharged
condition
Check
and
plug
leaks
in
return
ducts
cabinet
I
t
t
N
t
U
i
g
th
g
t
/
t
l
d
l
id
ll
d
t
ti
d
y
d
t
d
lt
y
y
g
g
g
y
y
y
different
92
have completel
- Turn pow er OFF prior to repair.
Wait 5 minutes af ter
disconnec ting pow er before
opening motor.
- Handle electronic motor/c ontrol w ith care.
- Turn pow er OFF prior to repair.
Wait 5 minutes af ter
disconnec ting pow er before
opening motor.
- Handle electronic motor/c ontrol w ith care.
- Check 230 Vac pow er at motor.
- Ch ec k low vo ltag e ( 24 Va c R t o C) at motor .
- Check low voltage connec tions
(G, Y, W, R, C) at motor.
- Check for unseated pins in connec tors
on motor harnes s.
- Test w ith a temporary jumper betw een R - G.
-
- Check for loose motor mount.
- Make sure blow er w heel is tight on shaf t.
- Perform motor/control replacement chec k,
ECM motors only.
- Turn pow er OFF prior to repair.
- Check line voltage for variation or "sag".
- Check low voltage connec tions
(G, Y, W, R, C) at
motor, uns eated pins in motor
harness connectors.
- Check-out sy stem controls - Thermostat.
- Perform Moisture Check.*
- Turn pow er OFF prior to repair.
.
.
capac
look alike, different modules ma
,
en
a
h the
oo muc
ow
r
modes. Even thou
ow a
or
e harnesses with "drip loop" under motor.
ec
-
- Does removing panel or filter
reduce "puffing"?
- Check/replace f ilter.
- Check/correct duct restrictions.
- Adjust to correct blow er speed setting.
s.
resu
e
uce unexpec
rammed for specific operatin
pro
pro
ma
.- Arran
------------
------------
es an
are factor
CHART CONTINUED ON NEXT PAGE
warran
uc
pro
s a
- Manual disconnect sw itch off or
door sw itch open.
- Blow n fuse or circ uit breaker.
- 24 Vac w ires misw ired.
- Unseated pins in w iring
harness connec tors.
- Bad motor/control module.
- Moisture present in motor or control module.
- Loose motor mount.
- Blow er w heel not tight on motor shaft.
- Bad motor/control module.
- Variation in 230 Vac to motor.
- Unseated pins in w iring harness
connectors.
- Erra tic CFM c omma nd fr om
"BK" terminal.
- Improper thermostat connection or setting.
- Moisture present in motor/control module.
- Incorrec t or dirty filter(s ).
- Incorrec t supply or return ductw ork.
- Incorrec t blow er speed setting.
equipment manufacturer
e vo
u
mo
ro
con
or
.-
or as recommended b
Troubleshooting Chart for GE/Regal-Beloit ECM Variable Speed Air Circulator Blower Motors
- This is normal start-up for
variable speed motor.
- No move ment.
- Motor rocks,
but w on't start.
- It is normal for motor to
oscillate w ith
no load on shaft.
- Varies up and dow n
or intermittent.
- "Hunts" or "puff s" at
high CFM (speed).
e
u
n p
ra
e
ensa
SymptomFault Description(s)Possible CausesCorrective ActionCautions and Notes
- Motor rocks
slig htly
w hen starting.
- Motor w on't
start.
- Motor
oscillates up &
dow n w hile
being tested
off of blow er.
- Motor starts,
but runs
erratically.
s con
-
*Moisture Check
- Connectors are oriented "down"
mo
e wron
n
s
e:
o
an
You must use the correct replacement control/motor module since the
mpor
functionality. The ECM variable speed motors are c
-
Note:
Page 93
SERVICING
(
y
)
g
I
d
t
d
i
l
gg
d?
Ch
k
f
l
i
fl
(t
h
l
t
t
ity)
Check
for
undercharged
condition
Check
and
plug
leaks
in
return
ducts
cabinet
I
t
t
N
t
U
i
g
th
g
t
/
t
l
d
l
id
ll
d
t
ti
d
y
d
t
d
lt
y
y
g
g
g
y
y
y
different
have completel
- Turn pow er OFF prior to repair.
Wait 5 minutes af ter
disconnec ting pow er before
opening motor.
- Handle electronic motor/control
w ith care.
- Turn pow er OFF prior to repair.
Wait 5 minutes af ter
disconnec ting pow er before
opening motor.
- Handle electronic motor/control
w ith care.
- Turn pow er OFF prior to repair.
- Check low voltage (Thermostat)
w ires and connections.
- Verify f an is not in delay mode -
w ait until delay complete.
- Perform motor/control replacement
chec k, ECM motors only.
- Is fan in delay mode? - w ait until delay time
complete.
- Perform motor/control replacement chec k, ECM
motors only.
- Check for Triac sw itched t'stat
or solid state relay.
CHART CONTINUED FROM PREVIOUS PAGE.
- 24 Vac w ires miswired or loose.
- "R" missing/not connec ted at motor.
- Fan in delay mode.
Troubleshooting Chart for GE/Regal-Beloit ECM Variable Speed Air Circulator Blower Motors
- Stay s a t low CFM despite
system call for cool
or heat CFM.
SymptomFault Des cription(s)Possible CausesCorre ctive ActionCautions and Notes
- "R" missing/not connec ted at motor.
- Fan in delay mode.
- Stays at high CFM.
- Motor starts,
but runs
erratically.
- Current leakage from controls
into G, Y, or W.
- Blow er w on't shut of f.
- Turn pow er OFF prior to repair.
- Check/replace f ilter.
- Check/correct duct restrictions.
- Adjust to correct blower speed setting.
- Turn pow er OFF prior to repair.
- Check for loose blow er housing,
panels, etc .
- Check for air w histling thru seams in
ducts , cabinets or panels.
- Check for cabinet/duct deformation.
- Turn pow er OFF prior to repair.
- Does removing panel or filter
reduce "puffing"?
- Check/replace f ilter.
- Turn pow er OFF prior to repair.
Wait 5 minutes af ter
disconnec ting pow er before
opening motor.
- Handle electronic motor/control
w ith care.
.
.
capac
look alike, different modules ma
,
en
a
h the
oo muc
ow
r
modes. Even thou
ow a
or
e harnesses with "drip loop" under motor.
ec
-
- Check/correct duct restrictions.
- Adjust to correct blower speed setting.
- Replace motor and perform
Moistur e Check.*
s.
resu
e
uce unexpec
rammed for specific operatin
pro
pro
ma
.- Arran
es an
are factor
warran
uc
pro
s a
- High static cr eating high blow er speed.
- Incorrect supply or return ductw ork.
- Incorrect or dirty filter(s).
- Incorrect blow er speed setting.
- Loose blow er housing, panels, etc.
- High static cr eating high blow er
speed.
- Air leaks in ductw ork, cabinets,
or panels.
- High static cr eating high blow er speed.
- Incorrect or dirty filter(s).
- Incorrect supply or return ductw ork.
- Incorrect blow er speed setting.
- Moisture in motor/control module.
equipment manufacturer
e vo
u
mo
ro
con
or
.-
or as recommended b
e
- Air noise.
- Noisy blow er or cabinet.
- "Hunts" or "puff s" at
high CFM (speed).
- Motor failure or
malfunction has
occurred and moisture
is present.
u
n p
ra
e
ensa
s con
*Moisture Check
-
- Evidence of
- Excessive
noise.
Moisture.
- Connectors are oriented "down"
mo
e wron
n
s
e:
o
an
You must use the correct replacement control/motor module since the
mpor
-
functionality. The ECM variable speed motors are c
Note:
93
Page 94
SERVICING
S-16E BLOWER PERFORMANCE DATA
SPEEDSTAT IC
0.11,2401,5001,8002,160
0.21,1701,4601,7402,080
HIGH
MEDIUM
LOW
NOTE: External static is for blower @ 230 Volts. It does not include Coil, Air Filter or Electric Heaters.
0.31,1201,3601,6801,990
0.41,0601,2801,6101,890
0.59801,2001,5201,790
0.69001,1101,4301,690
0.19001,3801,5401,730
0.28501,3201,4901,670
0.37901,2701,4501,590
0.47401,2001,4001,520
0.56801,14013,5601,420
0.66051,0401,2801,320
0.16501,1701,1301,520
0.25901,1301,1001,450
0.35401,0801,0701,360
0.45001,0201,0301,290
0.54309509901,200
0.63308309301,090
MBR800**-*
SCFM
MBR1200**-*
SCFM
MBR1600**-*
SCFM
MBR2000**-*
SCFM
S-16F CHECKING HIGH EFFICIENCY MOTORS
The motor is a one piece, fully encapsulated, 3 phase brushless
DC (single phase AC input) motor with ball bearing construction.
1. Using a voltmeter, check for 230 volts to the motor connections L and N. If 230 volts is present, proceed to step 2. If 230
volts is not present, check the line voltage circuit to the motor.
2. Using a voltmeter, check for 24 volts from terminal C to either
terminal 1, 2, 3, 4, or 5, depending on which tap is being used,
at the motor. If voltage present, proceed tostep 3. If no voltage,
check 24 volt circuit to motor.
3. If voltage was present in steps 1 and 2, the motor has failed
and will need to be replaced.
NOTE: When replacing motor, ensure the belly band is
between the vents on the motor and the wiring has the proper
drip loop to prevent condensate from entering the motor.
High Voltage
Connections
3/16"
C
123
LGN
4
5
Low Voltage Connections
1/4”
MOTOR CONNECTIONS
94
Page 95
SERVICING
S-16G EEM BLOWER REPLACEMENT
For AWUF19-25, AWUF31-32, and AWUF37 Air Handlers.
1. Disconnect power at main electrical panel.
2. Remove front access panel.
3. Remove the two screws on each side holding the lower control
box and move out of the way to give access to the blower
assembly
6. Install cardboard or rug over coil to protect fins from damage.
5. Loosen or remove set screw on blower wheel hub and ensure
the wheel slides freely on the shaft of the motor.
7. Remove the three 3/8" screws holding the blower in place.
8. Lower blower onto coil.
9. Slide blower assembly all the way to the left side of cabinet.
95
Page 96
SERVICING
10. Remove the bolts holding the motor bracket to the blower and
slide out of blower shell.
S-17 CHECKING COMPRESSOR
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
If the compressor terminal PROTECTIVE COVER and gasket (if
required) are not properly in place and secured, there is a remote
possibility if a terminal vents, that the vaporous and liquid
discharge can be ignited, spouting flames several feet, causing
potentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if the
terminal cover is not properly in place and if the discharge
impinges on a sufficient heat source.
Ignition of the discharge can also occur at the venting terminal
or inside the compressor, if there is sufficient contaminant air
present in the system and an electrical arc occurs as the terminal
vents.
Ignition cannot occur at the venting terminal without the presence of contaminant air, and cannot occur externally from the
venting terminal without the presence of an external ignition
source.
Therefore, proper evacuation of a hermetic system is essential
at the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open flame,
electrical power, and other heat sources should be extinguished
or turned off prior to servicing a system.
11. Replace the motor and reinstall blower and control box.
12. Reconnect power and test operation.
96
Page 97
SERVICING
S-17ARESISTANCE TEST
Each compressor is equipped with an internal overload.
The line break internal overload senses both motor amperage
and winding temperature. High motor temperature or amperage
heats the disc causing it to open, breaking the common circuit
within the compressor on single phase units.
Heat generated within the compressor shell, usually due to
recycling of the motor, high amperage or insufficient gas to cool
the motor, is slow to dissipate. Allow at least three to four hours
for it to cool and reset, then retest.
Fuse, circuit breaker, ground fault protective device, etc. has not
tripped -
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Remove the leads from the compressor terminals.
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
S-17B GROUND TEST
If fuse, circuit breaker, ground fault protective device, etc., has
tripped, this is a strong indication that an electrical problem
exists and must be found and corrected. The circuit protective
device rating must be checked, and its maximum rating should
coincide with that marked on the equipment nameplate.
With the terminal protective cover in place, it is acceptable to
replace the fuse or reset the circuit breaker ONE TIME ONLY to see
if it was just a nuisance opening. If it opens again, DO NOT
continue to reset.
Disconnect all power to unit, making sure that all power legs are
open.
1. DO NOT remove protective terminal cover. Disconnect the
three leads going to the compressor terminals at the nearest
point to the compressor.
2. Identify the leads and using an ohmmeter on the R x 10,000
scale or the highest resistance scale on your ohmmeter check
the resistance between each of the three leads separately to
ground (such as an unpainted tube on the compressor).
3. If a ground is indicated, then carefully remove the compressor terminal protective cover and inspect for loose leads or
insulation breaks in the lead wires.
4. If no visual problems indicated, carefully remove the leads
at the compressor terminals.
5. Carefully retest for ground, directly between compressor
terminals and ground.
6. If ground is indicated, replace the compressor. The resistance
reading should be infinity. If there is any reading on meter,
there is some continuity to ground and compressor should
be considered defective.
2. Using an ohmmeter, test continuity between terminals S-R, CR, and C-S, on single phase units or terminals T2, T2 and T3,
on 3 phase units.
C
OHMMETER
TESTING COMPRESSOR WINDINGS
If either winding does not test continuous, replace the compressor.
NOTE: If an open compressor is indicated, allow ample time for
the internal overload to reset before replacing compressor.
S
COMP
R
OHMMETER
WARNING
Damage can occur to the glass embedded terminals if
the leads are not properly removed. This can result in
terminal and hot oil discharging.
S-17C UNLOADER TEST PROCEDURE
A nominal 24-volt direct current coil activates the internal
unloader solenoid. The input control circuit voltage must be 18
to 28 volt ac. The coil power requirement is 20 VA. The external
electrical connection is made with a molded plug assembly. This
plug contains a full wave rectifier to supply direct current to the
unloader coil.
97
Page 98
SERVICING
Y
UNLOADER SOLENOID
Unloader Test Procedure
If it is suspected that the unloader is not working, the following
methods may be used to verify operation.
1. Operate the system and measure compressor current. Cycle
the unloader ON and OFF at 10 second intervals. The compressor amperage should go up or down at least 25 percent.
2. If step one does not give the expected results, shut unit off.
Apply 18 to 28 volt ac to the unloader molded plug leads and
listen for a click as the solenoid pulls in. Remove power and
listen for another click as the unloader returns to its original
position.
3. If clicks can’t be heard, shut off power and remove the control
circuit molded plug from the compressor and measure the
unloader coil resistance. The resistance should be 32 to 60
ohms, depending on compressor temperature.
4. Next check the molded plug.
A.Voltage check: Apply control voltage to the plug wires
(18 to 28 volt ac). The measured dc voltage at the
female connectors in the plug should be around 15 to
27 vdc.
B.Resistance check: Measure the resistance from the
end of one molded plug lead to either of the two female
connectors in the plug. One of the connectors should
read close to zero ohms while the other should read
infinity. Repeat with other wire. The same female
connector as before should read zero while the other
connector again reads infinity. Reverse polarity on
the ohmmeter leads and repeat. The female connector
that read infinity previously should now read close to
zero ohms.
C.Replace plug if either of these test methods doesn’t
show the desired results.
S-17DOPERATION TEST
If the voltage, capacitor, overload and motor winding test fail to
show the cause for failure:
(Molded Pl ug)
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Remove unit wiring from disconnect switch and wire a test
cord to the disconnect switch.
NOTE: The wire size of the test cord must equal the line wire size
and the fuse must be of the proper size and type.
2. With the protective terminal cover in place, use the three
leads to the compressor terminals that were disconnected at
the nearest point to the compressor and connect the common,
start and run clips to the respective leads.
3. Connect good capacitors of the right MFD and voltage rating
into the circuit as shown.
4. With power ON, close the switch.
WARNING
Line Voltage now present.
A. If the compressor starts and continues to run, the cause for
failure is somewhere else in the system.
B. If the compressor fails to start - replace.
COPELAND COMPRESSOR
03 A 12345 L
EAR
S-17E CHECKING 3-PHASE SCROLL COMPRESSOR
ROTATION
Verify the proper rotation of Copeland scroll compressors as
follows:
NOTE: The compressor may run backwards (noisy operation)
for 1 or 2 seconds at shutdown. This is normal and does not
harm the compressor.
1. Install gauges and verify that the suction pressure drops
while the discharge pressure increases.
2. Listen for normal compressor sound levels. Reverse rotation
results in elevated or unusual sound levels.
3. Reverse rotation will result in substantially reduced amp
draw from tabulated values.
To correct improper rotation, switch any two power supply leads
at the outdoor unit contactor.
MONTH
SERIAL
NUMBER
PLANT
98
Page 99
SERVICING
The 3-phase scroll compressors are direction of rotation
sensitive. They will rotate in either direction depending on
the phasing of the power. There is no negative impact on
durability caused by operating 3-phase compressors in
reversed rotation. The compressor's internal protector will
trip, de-energizing the compressor. Continued operation of
3-phase scroll compressors with the rotation reversed will
contribute to compressor failure. All 3-phase scroll compressors should be checked for correct phase rotation.
S-18 TESTING CRANKCASE HEATER (OPTIONAL ITEM)
The crankcase heater must be energized a minimum of four (4)
hours before the condensing unit is operated.
Crankcase heaters are used to prevent migration or accumulation of refrigerant in the compressor crankcase during the off
cycles and prevents liquid slugging or oil pumping on start up.
A crankcase heater will not prevent compressor damage due to a
floodback or over charge condition.
WARNING
Disconnect ALL power before servicing.
1. Disconnect the heater lead in wires.
2. Using an ohmmeter, check heater continuity - should test
continuous. If not, replace.
NOTE: The positive temperature coefficient crankcase heater is
a 40 watt 265 voltage heater. The cool resistance of the heater
will be approximately 1800 ohms. The resistance will become
greater as the temperature of the compressor shell increases.
S-21 CHECKING REVERSING VALVE AND SOLENOID
Occasionally the reversing valve may stick in the heating or
cooling position or in the mid-position.
When stuck in the mid-position, part of the discharge gas from
the compressor is directed back to the suction side, resulting in
excessively high suction pressure. An increase in the suction
line temperature through the reversing valve can also be measured. Check operation of the valve by starting the system and
switching the operation from COOLING to HEATING cycle.
If the valve fails to change its position, test the voltage (24V) at
the valve coil terminals, while the system is on the COOLING
cycle.
If no voltage is registered at the coil terminals, check the
operation of the thermostat and the continuity of the connecting
wiring from the "O" terminal of the thermostat to the unit.
S-24 TESTING DEFROST CONTROL
To check the defrost control for proper sequencing, proceed as
follows: With power ON; unit not running.
1. Jumper defrost thermostat by placing a jumper wire across
the terminals "DFT" and "R"/"R-DFT" at defrost control
board.
2. Connect jumper across test pins on defrost control board.
3. Set thermostat to call for heating. System should go into
defrost within 21 seconds.
4. Immediately remove jumper from test pins.
5. Using VOM check for voltage across terminals "C & O". Meter
should read 24 volts.
6. Using VOM check for voltage across fan terminals DF1 and
DF2 on the board. You should read line voltage (208-230 VAC)
indicating the relay is open in the defrost mode.
7. Using VOM check for voltage across "W"/"W2" & "C" terminals on the board. You should read 24 volts.
8. If not as above, replace control board.
9. Set thermostat to off position and disconnect power before
removing any jumpers or wires.
NOTE: Remove jumper across defrost thermostat before
returning system to service.
S-25 TESTING DEFROST THERMOSTAT
1. Install a thermocouple type temperature test lead on the tube
adjacent to the defrost control. Insulate the lead point of
contact.
2. Check the temperature at which the control closes its contacts by lowering the temperature of the control. Part #
0130M00009P which is used on 2 and 2.5 ton units should
close at 34°F ± 5°F. Part # 0130M00001P or B1370803 which
is used on 3 thru 5 ton units should close at 31°F ± 3°F.
3. Check the temperature at which the control closes its contacts by lowering the temperature of the control. Part #
0130M00085, which is used onunits with 5 mm coils, should
close at 30°F ± 5°F.
4. Check the temperature at which the control opens its contacts
by raising the temperature of the control. Part #0130M00009P
which is used on 2 and 2.5 ton units should open at 60°F ± 5°F.
Part # 0130M00001P or B1370803 which is used on 3 thru
5 ton units should open at 75°F ± 6°F.
5. Check the temperature at which the control opens its contacts
by raising the temperature of the control. Part # 0130M00085,
which is used on units with 5 mm coils, should open at 60°F
± 5°F.
6. If not as above, replace control.
SEQUENCE OF OPERATION
Refer to the installation instructions and wiring diagrams provided with the MBR/AR*F for specific wiring connections and
system configuration.
MBR/AR*F WITH SINGLE STAGE CONDENSERS
1.0 Cooling Operation
1.1 On a demand for cooling, the room thermostat energizes “G”
and “Y” and 24Vac is supplied to “Y” at the condensing unit
and the “G” terminal on the EBTDR board.
1.2 The compressor and condenser fan are turned on and after
a 7 second on delay, the relay on the EBTDR board is energized
and the blower motor starts.
99
Page 100
SERVICING
1.3 When the cooling demand “Y” is satisfied, the room thermo-
stat removes the 24Vac from “G” and “Y”.
1.4 The compressor and condenser fan are turned off and after
a 65 second delay off, the relay on the EBTDR board is deenergized and the blower is turned off.
2.0 Heating Operation
2.1 On a demand for heat, the room thermostat energizes “W1”
and 24Vac is supplied to heat sequencer, HR1, on the heater
assembly.
2.2 The contacts M1 and M2 will close within 10 to 20 seconds
and turn on heater element #1. The normally closed
contacts on the EBTDR are also connected to terminal M1.
When M1 and M2 close, the blower motor will be energized
thru the normally closed contacts on the EBTDR board. At
the same time, if the heater assembly contains a second
heater element, HR1 will contain a second set of contacts,
M3 and M4, which will close to turn on heater element #2.
NOTE: If more than two heater elements are on the heater
assembly, it will contain a second heat sequencer, HR2,which
will control the 3rd and 4th heater elements if available. If the
first stage heat demand, “W1” cannot be satisfied by the heat
pump, the temperature indoors will continue to drop. The room
thermostat will then energize “W2” and 24Vac will be supplied
to HR2 on the heater assembly. When the “W2” demand is
satisfied, the room thermostat will remove the 24Vac from HR2.
The contacts on HR2 will open between 30 to 70 seconds and
heater elements #3 and #4 will be turned off. On most digital/
electronic thermostats, “W2” will remain energized until the
first stage demand “W1” is satisfied and then the “W1” and
“W2” demands will be removed.
2.3 When the “W1” heat demand is satisfied, the room thermo-
stat will remove the 24Vac from HR1. Both set of contacts
on the relay opens within 30 to 70 seconds and turn off the
heater element(s) and the blower motor.
MBR/AR*F WITH SINGLE STAGE HEAT PUMPS
3.0 Cooling Operation
On heat pump units, when the room thermostat set to the
cooling mode, 24Vac is supplied to “O” which energizes the
reversing valve. As long as the thermostat is set for cooling, the
reversing valve will be in the energized position for cooling.
3.1 On a demand for cooling, the room thermostat energizes “G”
and “Y” and 24Vac is supplied to “Y” at the heat pump and
the “G” terminal on the EBTDR board.
3.2 The heat pump turned on in the cooling mode and after a 7
second on delay, the relay on the EBTDR board is energized
and the blower motor starts.
3.3 When the cooling demand is satisfied, the room thermostat
removes the 24Vac from “G” and “Y”.
3.4 The heat pump is turned off and after a 65 second delay off,
the relay on the EBTDR board is de-energized and the blower
motor is turned off.
4.0 Heating Operation
On heat pump units, when the room thermostat set to the heating
mode, the reversing valve is not energized. As long as the
thermostat is set for heating, the reversing valve will be in the
de-energized position for heating except during a defrost cycle.
Some installations may use one or more outdoor thermostats
to restrict the amount of electric heat that is available above a
preset ambient temperature. Use of optional controls such as
these can change the operation of the electric heaters during the
heating mode. This sequenceof operation does not cover those
applications.
4.1 On a demand for first stage heat with heat pump units, the
room thermostat energizes “G” and “Y” and 24Vac is supplied to “Y” at the heat pump unit and the “G” terminal on the
EBTDR board. The heat pump is turned on in the heating mode
and the blower motor starts after a 7 second on delay.
4.2 If the first stage heat demand cannot be satisfied by the heat
pump, the temperature indoors will continue to drop. The
room thermostat will then energize terminal “W2’ for second stage heat and 24Vac will be supplied to heat sequencer
HR1 on the heater assembly.
4.3 HR1 contacts M1 and M2 will close will close within 10 to
20 seconds and turn on heater element #1. At the same time,
if the heater assembly contains a second heater element,
HR1 will contain a second set of contacts, M3 and M4, which
will close and turn on heater element #2. The blower motor
is already on as a result of terminal “G” on the EBTDR board
being energized for the first stage heat demand.
NOTE: If more than two heater elements are on the heater
assembly, it will contain a second heat sequencer, HR2, which
will control the 3rd and 4th heater elements if available. If the
second stage heat demand, “W2” cannot be satisfied by the heat
pump, the temperature indoors will continue to drop. The room
thermostat will then energize “W3” and 24Vac will be supplied
to HR2 on the heater assembly. When the “W3” demand is
satisfied, the room thermostat will remove the 24Vac from HR2.
The contacts on HR2 will open between 30 to 70 seconds and
heater elements #3 and #4 will be turned off. On most digital/
electronic thermostats, “W3” will remain energized until the
first stage heat demand “Y” is satisfied and then the “G”, “Y”,
“W2” and “W3” demands will be removed.
4.4 As the temperature indoors increase, it will reach a point
where the second stage heat demand, “W2”, is satisfied.
When this happens, the room thermostat will remove the
24Vac from the coil of HR1. The contacts on HR1 will open
between 30 to 70 seconds and turn off both heater element(s).
The heat pump remains on along with the blower motor
because the “Y” demand for first stage heat will still be
present.
4.5 When the first stage heat demand “Y” is satisfied, the room
thermostat will remove the 24Vac from “G” and “Y”. The heat
pump is turned off and the blower motor turns off after a 65
second off delay.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.