•Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
®
C
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures performed by an unqualified person.
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
GMVC80604CXAA
PRODUCT
TYPE:
G: Goodman®
: Amana®
Brand Gas
SUPPL Y TYPE:
C: Counterflow/
Horizontal
D: Dedicate
Down flow
M: Upflow/
Horizontal
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
WARNING
WARNING
viduals meeting the requirements of an "entry level technician", at a minimum, as specified by the Air-Conditioning,
Heating, and Refrigeration Institute (AHRI). Attempting to
install or repair this unit without such background may
result in product damage, personal injury or death.
Installation and repair of this unit
should be performed
ONLY by indi-
2
HIGH VOLTAGE!
Page 3
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
AMVC80604B*A*
AMVC80805C*A*
AMVC81005C*A*
ADVC80603B*A*
ADVC80805C*A*
ADVC81005C*A*
GMVC80604B*A*
GMVC80805C*A*
GMVC81005C*A*
AMVC80604B*B*
AMVC80805C*B*
AMVC81005C*B*
ADVC80603B*B*
ADVC80805C*B*
ADVC81005C*B*
GMVC80604B*B*
GMVC80805C*B*
GMVC81005C*B*
*These models available in Natural Gas and Low NOx.
WARNING
WARNING
WARNING
WARNING
property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the
use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by Goodman for use with this unit. Serious
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
Page 4
PRODUCT DESIGN
General Operation
Models covered by this manual come with a new 4-wire communicating PCB. When paired with a compatible communicating indoor unit and a CTK0*** communicating thermostat, these models can support 4-wire communication protocol and provide more troubleshooting information. These
models are also backward compatible with the legacy thermostat wiring.
The ADVC8, AMVC8, and GMVC8 furnaces are equipped
with an electronic ignition device to light the burners and an
induced draft blower to exhaust combustion products.
An interlock switch prevents furnace operation if the blower
door is not in place. Keep the blower access doors in place
except for inspection and maintenance.
These furnaces are also equipped with a self-diagnosing electronic control module. In the event a furnace component is
not operating properly, the control module's dual 7-segment
LED's will display an alpha-numeric code, depending upon
the problem encountered. These LED's may be viewed
through the observation window in the blower access door.
Refer to the Troubleshooting Chart for further explanation of
the LED codes and Abnormal Operation - Integrated Igni-tion Control section in the Service Instructions for an explanation of the possible problem.
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning Contractors of America.
*Obtain from: American National Standards Institute 1430
Broadway New York, NY 10018
Location Considerations
•The furnace should be as centralized as is practical
with respect to the air distribution system.
•Do not install the furnace directly on carpeting, tile, or
combustible material other than wood flooring.
•When suspending the furnace from rafters or joists,
use 3/8" threaded rod and 2” x 2” x 1/8” angle as
shown in the Installation and Service Instructions. The
length of the rod will depend on the application and
clearance necessary.
•When installed in a residential garage, the furnace
must be positioned so the burners and ignition source
are located not less than 18 inches (457 mm) above
the floor and protected from physical damage by vehicles.
WARNING
O PREVENT POSSI BLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATI ON,
T
THIS FURNACE MUST BE
CATEGORY III VENTI NG.
Notes:
1. Category I Venting is venting at a non-positive pressure.
A furnace vented as Category I is considered a fan-assisted appliance and the vent system does not have to
be “gas tight.”
NOTE: Gas furnaces with induced draft blowers draw
products of combustion through a heat exchanger allowing,
in some instances, common venting with natural draft
appliances (i.e. water heaters).
All installations must be vented in accordance with National
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition. In
Canada, the furnaces must be vented in accordance with
the National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B149.2 - latest editions and amendments.
NOTE: The vertical height of the Category I venting system
must be at least as great as the horizontal length of the
venting system.
2. Line voltage wiring can enter through the right or left side
of the furnace. Low voltage wiring can enter through the
right or left side of furnace.
3. Conversion kits for propane gas and high altitude natural
and propane gas operation are available. See High Altitude Derate chart for details.
Accessibility Clearances (Minimum)
Unobstructed front clearance of 24" for servicing is recommended.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS - INCHES
SidesTopRearFront*
1036 11
* 24" clearance for serviceability recommended.
** Single Wall Vent (SW) to be used only as a conncetor.
Refer to the venting tables outlined in the Installation Manual for
additional venting requirements.
Note: In all cases accessibility clearance shall take precedence over clearances from the enclosure where accessibility clearances are greater. All dimensions are given in inches.
ATE GORY I VENTED. DO NOT VENT USI NG
C
Vent
SWB
4
Page 5
PRODUCT DESIGN
A
Alcove Illustration
REAR
S
I
E
D
I
S
LCOVE
24" at front is required for servicing or cleaning.
Note: In all cases accessibility clearance shall take
precedence over clearances from the enclosure where
accessibility clearances are greater. All dimensions are
given in inches.
High Altitude Derate
When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be installed. This is required due to the natural reduction in the density of both the
gas fuel and combustion air as altitude increases. The kit
will provide the proper design certified input rate within the
specified altitude range.
High altitude kits are purchased according to the installation altitude and usage of either natural or propane gas. Refer
to the chart above for a tabular listing of appropriate altitude
ranges and corresponding manufacturer’s high altitude Natural Gas and Propane Gas kits. For a tabular listing of appropriate altitude ranges and corresponding manufacturer's High
Altitude Pressure Switch kits, refer to either the Pressure
Switch Trip Points & Usage Chart in this manual or the Accessory Charts in Service Instructions.
D
E
Single Stage Thermostat
A single-stage thermostat with only one heating stage may
be used to control this furnace. The application of a singlestage thermostat does not offer “true” thermostat-driven twostage operation, but provides a timed transition from low to
high fire. The furnace will run on low stage for a fixed period
of time before stepping up to high stage to satisfy the
thermostat’s call for heat. The delay period prior to stepping
up can be set at either a fixed 5 minute time delay or a load
based variable time between 1 and 12 minutes (AUTO mode).
If the AUTOmode is selected, the control averages the cycle
times of the previous three cycles and uses the average to
determine the time to transition from low stage to high stage.
To use a single-stage thermostat, turn off power to the furnace, move the thermostat selection DIP switch to the OFF
position. Set the desired transition time by setting the transition delay DIP switch to the desired ON/OFF position. Turn
power back on. Refer to the following figure.
Heat OFF Delay
DIP Switches
ON OFF
3
4
Thermostat
Stage Delay
S1
Move to the ON position
to select two-stage
thermostat or OFF to
select single stage
thermostat
Move to the ON position
to select Auto transition
delay or OFF for 5 minute
transition delay
INPUT PER BURNER - 22,500 BTUH NATURAL GAS / 20,000 BTUH L.P.
ELEVATION ABOVE SEA-LEVEL ( FEET)
US BURNER
ORIFICE
CANADA BURNER
ORIFICE
HA-02 HIGH ALTITUDE CONVERSION KIT REQUIRED
Tabled data is based upon the furnace input being reduced for altitudes above sea level. U.S. 4% per 1,000 feet.
Part Number0130M0006320162904201629030130F000670130F00071
Open Setting (°F)
AMVC80604B*A*
GMVC80604B*A*
AMVC80805C*A*
GMVC80805C*A*
AMVC81005C*A*
GMVC81005C*A*
ADVC80603B*A*
ADVC80805C*A*
ADVC81005C*A*
140150160190200
------1------
1-- ----------
---1---------
---------1---
---------1---
------------ 1
10
ROLLOUT LIMIT SWITCHES
Part N umber10123529
Open Setting (°F)
AM VC8 060 4B***
GM VC 806 04B ***
AM VC8 080 5C***
GM VC 808 05C ***
AM VC8 100 5C***
GM VC 810 05C ***
ADVC80603B***
ADVC80805C***
ADVC81005C***
300
2
2
2
1
1
1
AUXILIARY LIMIT SWITCHES
Part Number0130F00038
Open Setting (°F)
AMVC80604B***
GM V C 806 04 B***
AMVC80805C***
GM V C 808 05 C***
AMVC81005C***
GM V C 810 05 C***
ADVC80 603B***
ADVC80 805C***
ADVC81 005C***
120
1
1
1
1
1
1
Page 11
PRODUCT DESIGN
MODE L
AMVC80604B*B*
GMVC80604B*B*
AMVC80805C*B*
GMVC80805C*B*
AMVC81005C*B*
GMVC81005C*B*
PRESSURE SWITCH TRIP POINTS
AND USAGE C HART
SQUARE NOSE
TRIP POINT
ID BLOWER
PR ES SUR E SW IT CH -
LOW STAGE
-0.35-0.650130 F000 49
-0.35-0.650130 F000 49
-0.30-0.5 5B13702 10
TRIP P OINT
ID BLOWER
PRESSURE SWITCH -
HIGH STAGE
AMVC8/GMVC8***B*
ID BLOW ER
PRESSURE
SWITC H
PART #
ADVC80603B*B*
ADVC80805C*B*
ADVC81005C*B*
-0.30-0.5 5B13702 10
-0.35-0.650130 F000 49
-0.35-0.650130 F000 49
PRIMARY LIMIT
Part Number0130M00063201629050130F000360130F00067
Open Setting (°F)
AMVC80 60 4B*B *
GMVC80604B*B*
AMVC80 80 5C*B *
GMVC80805C*B*
AMVC81 00 5C*B *
GMVC81005C*B*
ADVC806 03B*B*
ADVC808 05C*B*
ADVC810 05C*B*
140145180190
1---------
1---------
---1------
----- ----1
----- ----1
----- -1---
ROLLOUT LIMIT SWITCHES
Part N umber10123529
Open Setting (°F)
AM VC8 060 4B***
GM VC 806 04B ***
AM VC8 080 5C***
GM VC 808 05C ***
AM VC8 100 5C***
GM VC 810 05C ***
ADVC80603B***
ADVC80805C***
ADVC81005C***
300
2
2
2
1
1
1
AUXILIARY LIMIT SWITCHES
Part Number0130F00038
Open Setting (°F)
AMVC80604B***
GMVC80604B***
AMVC80805C***
GMVC80805C***
AMVC81005C***
GMVC81005C***
ADVC80 603B***
ADVC80 805C***
ADVC81 005C***
120
1
1
1
1
1
1
11
Page 12
PRODUCT DESIGN
Coil Matches:
A large array of Amana® brand coils are available for use with the ADVC8 furnaces, in downflow applications, and with
AMVC8 and GMVC8 furnaces, in either upflow or horizontal applications. These coils are available in both cased and
uncased models (with the option of a field installed TXV expansion device). These 80%+ furnaces match up with the
existing Amana® brand coils as shown in the chart below.
Coil Matches (for Goodman® and Amana® Brand units using R22 and R-410A):
A: Fits 14" Furnace Cabinet
B: F it s 17 1/ 2" Furnace Ca bi net
C: Fits 21" Furnace Cabinet
D: Fits 24 1/2" Furnace Cabinet
N: Does Not Apply (Horizontal Slab Coils)
12
• All CAPF coils in B, C, & D widths have insulated blank off plates for use with one size smaller furnaces.
• All CAPF coils have a CAUF equivalent.
• All CHPF coils in B, C & D heights have an insulated Z bracket for use with one size smaller furnace.
• All proper coil combinations are subject to being ARI rated with a matched outdoor unit.
Page 13
PRODUCT DESIGN
Thermostats:
ComfortNet™ CTK0*** Thermostat Kit
Refer to the product marketing literature for a complete list of thermostats offered.
Filters:
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty
Upflow Filters
Return air filters may be installated at the furnace side and/or bottom return openings. The furnace bottom return opening
and side openings will accommodate the following filter sizes depending on cabinet size:
Side Return Opening(s)Bottom Return Opening
Cabinet
Width
(in. )
All16 x 25 x 14001412 x 25 x 1300
Nominal
Filter Size
(in. )
Approx.
Flow Area
2
(in
)
Cabinet
Width
(in. )
17-1/214 x 25 x 1350
2116 x 25 x 1400
24-1/220 x 25 x 1500
Nominal
Filter Size
(in. )
Approx.
Flow Area
(in2)
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.
M I NI M UM FI L TER SI ZE S
FURNACE INPUTFILTER SIZE
60M
80M
100M
DISPOSABLE NOMINAL 300 F.M. FACE VELOCITY
768 i n
960 i n
1022 in
2
2
2
13
Page 14
PRODUCT DESIGN
Downflow Filters
Return air filters may be installated at the at the downflow top return. A field supplied center filter support must be provided
by the installer in order to use the top return. The furnace will accommodate the following downflow top return filter sizes
depending on cabinet size:
Counterflow Top Return
Optional
Access
Door
Return Air
"A"
Min
Cabine t Widt h
17 1/214.2
2113.0
24 1/211.3
17 1/219.7
2118.8
24 1/217.7
17 1/225.0
2124.3
24 1/223.4
Filter Area
2
(in
)
600215 X 20 X 1
800220 X 20 X 1
1000225 X 20 X 1
Qty
Filter Si ze
(in)
Dimension "A"
(in)
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere
in the duct system such as a central return.
* Off Heating - This fan de la y timin g i s adjus ta bl e (90, 120, 1 50 or 180 seco nds ), 1 50 se co nds as sh ip ped .
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
* Off Hea tin g - Thi s fan delay t iming i s adjus ta bl e (90 , 120, 150 or 18 0 s econds), 150 seconds a s sh ip ped .
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
* Off Heating - This fan delay timing is adjustable (90, 120, 150 or 180 seconds), 150 seconds as shipped.
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
* Off Heating - This fan delay timing is adjustable (90, 120, 150 or 180 seconds), 150 seconds as shipped.
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
* Off Heating - This fan delay timing is adjustable (90, 120, 150 or 180 seconds), 150 seconds as shipped.
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
* Off Hea tin g - This fan delay t imin g is adj ustable (90, 120, 150 or 18 0 seco nds), 1 50 seconds as sh ipped.
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
21
Page 22
BLOWER PERFORMANCE SPECIFICATIONS
(+)
)
(+)
)
AMVC8/GMVC8
AMVC80604B***
GMVC80604B***
Cooling
Speed Tap
High (Single) Stage Cooling Speed Charts
AMVC80805C***
GMVC80805C***
Ad ju st
Tap
CFM
Cooling
1
Speed Tap
Adjust
Tap
CFM
1
Minus (-)540Minus (-)720Minus (-)720
A
Normal600Normal800Normal800
A
Plus (+)660Plus (+)880Plus (+)880
Minus (-)720Minus (-)990Minus (-)990
B
Normal800Normal1100Normal1100
B
Plus (+)880Plus (+)1210Plus (+)1210
Minus (-)990Minus (-)1260Minus (-)1260
C
Normal1100Normal1400Normal1400
C
Plus (+)1210Plus (+)1540Plus (+)1540
Minus (-)1260Minus (-)1620Minus (-)1620
D
Normal1400Normal1800Normal1800
Plus
1540Plus (+
D
1980Plus (+)2,000*
AMVC8/GMVC8 Low Stage Cooling Speed Charts
AMVC81005C***
GMVC81005C***
Cooling
Speed Tap
A
B
C
D
Adjust
Tap
CFM
1
AMVC80604B***
GMVC80604B***
Cooling
Speed Tap
Ad ju st
Tap
CFM
1
Speed Tap
AMVC80805C***
GMVC80805C***
Cooling
Adjust
Tap
CFM
Cooling
1
Speed Tap
AMVC81005C***
GMVC81005C***
Adjust
Tap
CFM
1
Minus (-)351Minus (-)468Minus (-)468
A
Normal390Normal520Normal520
A
A
Plus (+)429Plus (+)572Plus (+)572
Minus (-)468Minus (-)644Minus (-)644
B
Normal520Normal715Normal715
B
B
Plus (+)572Plus (+)787Plus (+)787
Minus (-)644Minus (-)819Minus (-)819
C
Normal715Normal910Normal910
C
C
Plus (+)787Plus (+)1001Plus (+)1001
Minus (-)819Minus (-)1053Minus (-)1053
D
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
Normal910Normal1170Normal1170
Plus
1001Plus (+
D
D
1287Plus (+)1287
22
Page 23
BLOWER PERFORMANCE SPECIFICATIONS
p
p
AMVC8/GMVC8
Continuous Fan Speed Chart
Co nt inous Fan Speeds
Model
AMVC80604B***
GMVC80604B***
AMVC80805C***
GMVC80805C***
AMVC81005C***
GMVC81005C***
1
Continuous fan speed is 25% of furnace maximum CFM
2
Three continuous fan speeds are possible with the
Furnace
Maximum CFM
1760530
2000600
2000600
Continuous Fan
eed
S
CTK0*** thermostat: 25%, 50%, and 75% of furnace
maximum CFM
ADVC8 Continuous Fan Speed Chart
Cont inous Fan Speeds
Model
Furnace
Maximum CFM
Continuous Fan
eed
S
1,2
1,2
ADVC80603B***
ADVC80805C***
ADVC81005C***
1
Continuous fan speed is 25% of furnace maximum CFM
2
Three continuous fan speeds are possible with the
1760530
2000600
2000600
CTK0*** thermostat: 25%, 50%, and 75% of furnace
maximum CFM
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
23
Page 24
BLOWER PERFORMANCE SPECIFICATIONS
p
ADVC8 Heating Speed Chart
ADVC80603B***
(Rise Range: 30° - 60°F)
Heating
Speed
Tap
AA
BB
CC
DD
Adj ust Tap
Minus (-)66094555Minus (-)850121555
Normal735105049Normal945135049
Plus ( +)810115545Plus (+)1040148545
Minus (-)725103550Minus (-)915130551
Normal805115045Normal1015145046
Plus ( +)885126541Plus (+)1115159542
Minus (-)790112546Minus (-)975139548
Normal875125041Normal1085155043
Plus ( +)960137538Plus (+)1195170539
Minus (-)850121543Minus (-)1040148545
Normal945135038Normal1155165040
Plus ( +)1040148535Plus (+)1270181537
ADVC81005C***
(Rise Range: 35° - 65°F)
Low-
Stage
CFM
High-
Stage
CFM
Rise (°F)
Heating
Speed
Tap
ADVC80805C***
(Rise Range: 35° - 65°F)
Adjust
Tap
Low-
Stage
CFM
HighStage
CFM
Rise (°F)
Heating
Speed
Ta
A
B
C
D
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
Adj ust Tap
Minus (-)975139561
Normal1085155055
Plus ( +)1195170550
Minus (-)1040148557
Normal1155165052
Plus ( +)1270181547
Minus (-)1105157554
Normal1225175049
Plus ( +)1350192544
Minus (-)1135162053
Normal1260180047
Plus ( +)1385198043
Low-
Stage
CFM
High-
Stage
CFM
Rise (°F)
24
Page 25
BLOWER PERFORMANCE SPECIFICATIONS
ADVC8High (Single) Stage Cooling Speed Charts
ADVC80603B***ADVC80805C***
Cooling
Speed Tap
Adju st
Tap
CFM
Cooling
1
Speed Tap
Adjust
Tap
Minus (-)540Minus (-)720Minus (-)765
AAA
Normal600Normal800Normal850
Plus (+)660Plus (+)880Plus (+)935
Minus (-)720Minus (-)990Minus (-)1035
BBB
Normal800Normal1100Normal1150
Plus (+)880Plus (+)1210Plus (+)1265
Minus (-)900Minus (-)1260Minus (-)1305
CC
Normal1000Normal1400Normal1450
Plus (+)1100Plus (+)1540Plus (+)1595
Minus (-)1080Minus (-)1620Minus (-)1665
DD
Normal1200Normal1800Normal1850
Plus (+)1320Plus (+)1980Plus (+)2,000*
ADVC8 Low Stage Cooling Speed Charts
CFM
Cooling
1
Speed Tap
ADVC81005C***
Adjust
Tap
C
D
CFM
1
ADVC80603B***ADVC80805C***
Cooling
Speed Tap
Adju st
Tap
CFM
Cooling
1
Speed Tap
Adjust
Tap
CFM
1
Speed Tap
ADVC81005C***
Cooling
Adjust
Tap
CFM
1
Minus (-)351Minus (-)468Minus (-)497
Normal390Normal520Normal553
AAA
Plus (+)429Plus (+)572Plus (+)608
Minus (-)468Minus (-)644Minus (-)673
BB
Normal520Normal715Normal748
B
Plus (+)572Plus (+)787Plus (+)822
Minus (-)585Minus (-)819Minus (-)848
CC
Normal650Normal910Normal943
C
Plus (+)715Plus (+)1001Plus (+)1037
Minus (-)702Minus (-)1053Minus (-)1082
DD
Normal780Normal1170Normal1203
D
Plus (+)858Plus (+)1287Plus (+)1323
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
25
Page 26
BLOWER PERFORMANCE SPECIFICATIONS
NOFF
Circulator Blower Speed Adjustment Switches
Sw itch Bank : S3
Cooling Speed
Taps
AOFFOFF
BONOFF
COFFON
D*ONON
(*Indicates factory setting)
DIP Sw itc h No.
12
Sw it ch Bank: S3
Adjust Taps
Nor mal*OFFOFF
10%ONOFF
-10%OFFON
Nor malONON
(*Indicates factory setting)
DIP Sw itc h No.
34
Note: There are dual 7-segment LED's adjacent
to the selection dipswitches. The airflow rounded
to the nearest 100 CFM, is displayed on the dual
7-segment LED's. The CFM display alternates
with the operating mode.
Example:
If the airlfow demand is 1230 CFM, the LED's will
display 12. If the airflow demand is 1275 CFM,
the LED's will display 13.
Sw it ch Bank: S4
Heating Speed
Taps
AOFFOFF
B*ONOFF
COFFON
DONON
(*Indicates factory setting)
DIP Sw itc h No.
78
Dehumidification Enable Switch
O
9
10
S5
DEHUM
Unused
Move to the ON position
to enable dehumidification
Note: Continuous fan speed will be 25% of the
furnace's maximum airflow capability. If the furnace maximum CFM capaibility is 1760 CFM, the
continuous fan speed will be 0.30 X 1760 CFM =
530 CFM.
Example: If the furnace maximum CFM capaibility
is 1760 CFM, the continuous fan speed will be
0.30 X 1760 CFM = 530 CFM.
Note: The optional usage of a dehumidistat allows
the furnace’s circulator blower to operate at a slightly
lower speed (85% of desired speed) during a combined
thermostat call for cooling and dehumidistat call for
dehumidification. This can be done through an
independent dehumidistat or through a thermostat’s
DEHUM terminal (if available). This lower blower speed
enhances dehumidification of the conditioned air as it
passes through the AC coil. For proper function, a
dehumidistat applied to this furnace must operate on
24 VAC and utilize a switch which opens on humidity
rise.
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
26
Page 27
BLOWER PERFORMANCE SPECIFICATIONS
Ramping Profile
Switch Bank: S4
Ramp ing
Profiles
A*OF FOFF
BONOFF
COFFON
DONON
(*Indicates factory setting)
DIP Switch No.
56
OFF
Profile A: provides only an OFF delay of one (1) minute at
100% of the cooling demand airflow.
Note: The multi-speed circulator blower also offers several
custom ON/OFF ramping profiles. These profiles may be
used to enhance cooling performance and increase comfort
level. The ramping profiles are selected using DIP switches
5 and 6. Refer to the following figure for switch positions
and their corresponding taps. Refer to the bullet points below
for a description of each ramping profile. Verify CFM by
noting the number displayed on the dual 7-segment LED
display.
100% CFM100% CFM
OFF
1 min
OFF
50% CFM
1/2 min
100% CFM
100% CFM
OFF
1 min
Profile B: ramps up to full cooling demand airflow by first
stepping up to 50% of the full demand for 30 seconds. The
motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
27
Page 28
BLOWER PERFORMANCE SPECIFICATIONS
Ramping Profile
OFF
Profile C: ramps up to 82% of the full cooling demand airflow
and operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile C also has a
one (1) minute 100% OFF delay.
OFF
100% CFM
OFF
OFF
Profile D: ramps up to 50% of the demand for 1/2 minute,
then ramps to 82% of the full cooling demand airflow and
operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile D has a 1/2
minute at 50% airflow OFF delay.
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM maximum.
28
Page 29
PERFORMANCE
MPER
RE R
÷ CFM
130140150
900
FORMULAS
BTU OUTPUT = CFM x 1.08 x RISE
1.08
BTU OUTPUT
RISE =
100
2400 CFM
2200
2000
1800
1600
1400
1200
1100
1000
OUTPUT BTU/HR x 1000
800
BTU OUTPUT vs TEMPERATURE RISE CHART
600 CFM
700
30405060708090110120
100
90
80
70
60
ISE
50
ATU
TE
40
30
20
10
29
Page 30
WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ID BLOWER TWO-STAGE PRESSURE
HOT
SURFACE
IGNITER
2 CIRCUIT
2
1
CONNECTOR
BK
WH
BK
WH
RD
RD
ECM MTR
HARNESS
NOTES:
1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE
FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH
WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT
LEAST 105°C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO
N.E.C. AND LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST
RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE
IN STANDBY (NO THERMOSTAT INPUTS)
GY
0140F00818 REV. B
LOW FIRE
PRESSURE
SWITCH
TWO STAGE
GAS VALVE
(HONEY WELL)
2
HI
3
C
1
PM
PU
AUTO RESET PRIMARY
3
2
1
BURNER COMPARTMENT
BLOWER COMPARTMENT
EAC
WH
BL
BR
13
RD
10
YL
7
RD
4
RD
1
YL
24 V
3 A
FUSE
BL
4
BK
3
2
1
CIRCULATOR
BLOWER
C
WH
BL
BR
MANUAL RESET ROLLOUT LIMIT
LIMIT CONTROL
WH
RD
BK
HUM
LINE
BL
YL
14
15
12
11
8
9
5
6
2
3
2
1
24 V THERMOSTAT CONNECTIONS
5
BK
4
3
GR
2
PK
1
SWITCH ASSEMBLY
NO
YL
CONTROLS
PU
NEUTRAL
FS
BK
OR
COOL
GN
ADJUST
DELAY
HEAT
DEHUM
UNUSED
DELAY
HEAT OFF
T-STAT
2ND STG DLY
SEE
NOTE 5
W1
C
G
R
WH
24V HUM.
YL
C
HIGH FIRE
PRESSURE SWITCH
PU
INDUCED
DRAFT
BLOWER
GND
PU
AUTO RESET
AUXILIARY
LIMIT CONTROL
5 CIRCUIT CONNECTOR
5
4
3
2
1
4 CIRCUIT MOTOR
4
CONNECTOR
3
2
DIP SWITCHES
1
INTEGRATED
CONTROL
MODULE
DIAGNOSTIC
LED'S
DEHUM
W2
Y2
Y1
O
GND
INDUCTOR COIL
70kBTU,90kBTU,
115kBTU MODELS
*MVC8, *DVC8 W
YL
RD
BR
YL
NO
RD
WH
BK
TWO-STAGE
TRANSFORMER
BK
ONLY
COLOR CODES:
PK PINK
BR BROWN
WH WHITE
BL BLUE
GY GRAY
RD RED
YL YELLOW
OR ORANGE
PU PURPLE
GN GREEN
BK BLACK
YL
40 VA
WH
BL
FLAME
SENSOR
OR
GN
BL
RD
115
VAC
WH
WH
BK
BLOWER
COMPARTMENT
DOOR SWITCH
(OPEN WHEN
DOOR OPEN)
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (115V)
HI VOLTAGE FIELD
INTEGRATED CONTROL
JUNCTION BOX
BK
CHASSIS GROUND
24
VAC
BK
PLUG CONNECTION
WH
DISCONNECT
OVERCURRENT PROTECTION DEVICE
WARNING:
DISCONNECT POWER
BEFORE SERVICING.
WIRING TO UNIT
MUST BE PROPERLY
POLARIZED AND
GROUNDED.
DOOR
SWITCH
INDUCTOR COIL
70kBTU,90kBTU,
115kBTU MODELS
LINE
INTEGRATED CONTROL MODULE
LINE
FUSE 3 A
R
TO +VDC
24V THERMOSTAT CONNECTIONS
Y1
W1
W2
TO
MICRO
Y2
G
O
DEHUM
24V HUM.
C
TO
R
TO
MICRO
INTEGRATED CONTROL MODULE
JUNCTION
TERMINAL
INTERNAL TO
Ø /60 HZ POWER SUPPLY WITHTO 115VAC/ 1
ONLY
EAC
IND HI
IND LO
HUM
IGN
FS
FLAME SENSOR
TH (4)
AUTO RESET AUXILIARY LIMIT
CONTROLS
HLO (10)
PSO (7)
PS1 (2)
PS2 (12)
HIGH FIRE
PRESS. SWTICH
HLI (1)
MVL (13)
MVH (14)
MVC (8)
GND (5)
TR (11)
GND (4)
+ VDC (1)
RX (2)
TX (3)
HUMIDIFIER
IRING
TO
GND
115 VAC/ 1
POWER SUPPLY WITH
OVERCURRENT
PROTECTION DEVICE
L
WARNING:DISCONNECT
POWER BEFORE
SERVICING. WIRING
N
TO UNIT MUST BE
PROPERLY POLARIZED
AND GROUNDED.
GND
L
JUNCTION BOX
INDOOR
AIR
CIRCULATOR
BLWR
ELECTRONIC
AIR CLEANER
ID
BLWR
HUMIDIFIER
HOT SURFACE
IGNITER
115 VAC
24 VAC
24V HUM.
NO
NO
INDOOR
AIR
CIRCULATOR
BLWR
EQUIPMENT GND
FIELD SPLICE
SWITCH (TEMP.)
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
D
Ø /60 HZ
N
DISCONNECT
GND
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
40 VA
TRANSFORMER
AUTO RESET PRIMARY
LIMIT CONTROL
LOW FIRE PRESS.
SWITCH
C
C
MANUAL RESET ROLLOUT
LIMIT CONTROLS
GND
FIELD GND
IGNITER
IAGRAM
INTEGRATED CONTROL MODULE
PM
HI
C
GAS
VALVE
30
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 31
SCHEMATICS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
INTEGRATED CONTROL MODULE
HUM
Y2
DE
Y1
Y2
DEHUM
Y1Y1O
Y21DEHUM
R
W2
W1
C
GO
2
G
W2
R
W1
C
2O
W2
W1
G1
2
R
C
1
1
3
6
9
12
15
4
7
10
13
ST5
INDUCTOR COIL
GND
TX
RX
12V
ST4
FS
WH
IGN-N
IND-N
IND-LO
IND-HI
IGN
BK
R
ANSI Z21 .20 AU TOMATIC IGNITIO N SYST EM 24 VAC 60Hz 0.8 A. M AX.
EAC
HUM
BK
WH
59-4715 R EV. F
LINE
LOAD
TRANSFORMER
CONTROL ASSEMBLY SCHEMATIC
ADVC8/AMVC8/GMVC8_____X* MODEL FURNACES
This schematic is for reference only. Not all wiring is as shown above,
refer to the appropriate wiring diagram for the unit being serviced.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
31
Page 32
SCHEMATICS
Y2
O
W2
W1
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
XFMR
G
DEHU M
P
μ
C
4
8
R
Y112
6
N/C
122
DI PSWX
334
TX/RX
1
VARIABLE SPEED
CIRCULATOR
HI
2
LO
3
INDUCER
4
EAC
RJ11
P
μ
RS485
COMM
COMM
STATU S LED
DUAL LED
DISPLAYS
71593
101
PS2
PS1
N/C
AUXRLSHL
TYPICAL SCHEMATIC
14
WR 50C51-289 INTEGRATED IGNITION CONTROL
ADVC8/AMVC8/GMVC8_____X* MODEL FURNACES
32
DRA IN
SWITCH
HUM
15
IGN
ZCNTL
LOHI
138
GAS V ALVE
5-11
GROUND
WIRING SCHEMATIC
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
This schematic is for reference only. Not all wiring is as shown above. Refer to the appropriate wiring diagram for the unit being serviced.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.