Goodman AMVM960603BX, GMVM960603BX, GMVM960805CX, AMVM961005DX, GMVM961005DX Installation Instructions Manual

...
I
NSTALLATION INSTRUCTIONS FOR
M
ODULATING
*MVM96 & *CVM96
GAS F
URNACE
(Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace)
Installer: Affix all manuals adjacent to the unit.
These furnaces comply with requirements em­bodied in the American National Standard / Na­tional Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central Furnaces.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good
safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if
there is a direct conflict between existing practices and the content of this manual, the precautions listed here
take precedence.
*NOTE: Please contact your distributor
or our website for the applicable
Specification Sheet referred to in this manual.
IO-406E 05/13
5151 San Felipe Suite 500
Houston, TX 77056
www.goodmanmfg.com • www.amana-hac.com
© 2011 - 2013 Goodman Manufacturing Company, L.P.
T ABLE OF CONTENTS
SAFETY CONSIDERATIONS ...................................... 4
S
HIPPING INSPECTION............................................ 5
E
LECTROSTATIC DISCHARGE (ESD)
P
RECAUTIONS ....................................................... 5
T
O THE INSTALLER ................................................ 5
I
MPORTANT NOTE TO THE OWNER REGARDING
PRODUCT WARRANTY ......................................... 6
Product Description ............................................... 6
F
EATURES ............................................................ 6
Product Application ................................................ 7
Location Requirements & Considerations ......... 8
C
LEARANCES AND ACCESSIBILITY ............................ 9
E
XISTING FURNACE REMOVAL ................................9
T
HERMOSTAT LOCATION ........................................10
Combustion & Ventilation Air
Requirements .............................................. 10
Installation Positions ...........................................13
Horizontal Applications & Considerations .......14
F
URNACE SUSPENSION ........................................ 14
D
RAIN TRAP AND LINES ....................................... 14
L
EVELING .......................................................... 14
A
LTERNATE ELECTRICAL AND
GAS LINE CONNECTIONS.................................. 14
D
RAIN PAN ........................................................ 14
F
REEZE PROTECTION...........................................14
Propane Gas/High Altitude Installations ........... 14
Vent/Flue Pipe & Combustion Air Pipe .............. 15
D
UAL CERTIFICATION: NON-DIRECT/DIRECT VENT ....15
M
ATERIALS AND JOINING METHODS ...................... 15
P
ROPER VENT/FLUE AND COMBUSTION AIR
PIPING PRACTICES .......................................... 17
T
ERMINATION LOCATIONS ..................................... 17
S
PECIAL VENTING REQUIREMENTS FOR
INSTALLATIONS IN CANADA ................................ 19
S
TANDARD FURNACE CONNECTIONS ................................ 19
C
OMBUSTION AIR PIPE .................................................19
A
LTERNATE FURNACE CONNECTIONS ...............................20
N
ON-DIRECT VENT (SINGLE PIPE) PIPING.......................21
D
IRECT VENT (DUAL PIPE) PIPING ................................. 22
V
ENT/INTAKE TERMINATIONS FOR
INSTALLATION OF MULTIPLE
DIRECT VENT FURNACES .................................. 23
C
ONCENTRIC VENT TERMINA TION ........................... 23
S
IDE WALL VENT KIT ........................................... 24
Condensate Drain Lines & Drain Trap..................... 24
S
TANDARD RIGHT OR LEFT SIDE
DRAIN HOSE CONNECTIONS .............................24
U
PRIGHT INSTALLATIONS-TRAP
RIGHT SIDE ...............................................24
ON
U
PRIGHT INST ALLA TIONS-TRAP
LEFT SIDE .................................................25
ON
H
ORIZONTA L INSTALLATIONS .................................... 26
Electrical Connections............................................. 27
W
IRING HARNESS ................................................. 28
115 V
OLT LINE CONNECTIONS ................................. 28
J
UNCTION BOX RELOCATION ................................... 28
24 V
OLT THERMOSTA T WIRING ................................ 28
S
INGLE-STAGE HEATING
THERMOSTAT APPLICATION ................................ 29
24 V
OLT DEHUMIDISTA T WIRING .............................. 30
F
OSSIL FUEL APPLICA TIONS .................................... 30
L
INE VOLT AGE ACCESSORIES
(ELECTRONIC AIR CLEANER AND HUMIDIFIER) ..... 30
24 V
OLT HUMIDIFIER ............................................. 31
Gas Supply and Piping ............................................ 31
H
IGH ALTITUDE DERATE .......................................... 31
P
ROPANE GAS CONVERSION ................................... 31
G
AS PIPING CONNECTIONS ..................................... 31
P
ROPANE GAS TANKS AND PIPING ............................ 34
Circulating Air & Filters ........................................... 34
D
UCT WORK - AIR FLOW ....................................... 34
C
HECKING DUCT STA TIC ......................................... 35
B
OTTOM RETURN AIR OPENING
[UPFLOW MODELS] ........................................ 35
F
ILTERS - READ THIS SECTION
BEFORE INSTALLING THE RETURN AIR DUCT WORK ..... 36
U
PRIGHT INSTALLA TIONS ......................................... 36
H
ORIZONTA L INSTALLATIONS .................................... 37
Startup Procedure & Adjustment ............................ 37
H
EA TING OPERATION WITH CTK01 THERMOSTAT
(COMMUNICATING)...........................................38
H
EATING OPERATION WITH
CTK02** & CTK03** THERMOSTAT
(MODULATING COMMUNICATING) ....................... 38
H
EAT ANTICIPATO R SETTING .................................. 38
C
ONDENSATE DRAIN TRAP PRIMING ...................... 38
F
URNACE OPERATION ..........................................38
G
AS SUPPLY PRESSURE MEASUREMENT ............... 39
G
AS MANIFOLD PRESSURE MEASUREMENT ........... 40
G
AS INPUT RATE MEASUREMENT
(NATURAL GAS ONLY).....................................40
T
EMPERATURE RISE ............................................41
C
IRCULATOR BLOWER SPEEDS ................................ 41
B
LOWER HEA T OFF DELAY TIMINGS .......................... 43
ComfortNet™ System .............................................. 43
O
VERVIEW .......................................................... 43
A
IRFLOW CONSIDERA TIONS ..................................... 43
2
T ABLE OF CONTENTS
DIP Switches ............................................................ 45
N
ETWORK TROUBLESHOOTING .................................. 46
S
YSTEM TROUBLESHOOTING .................................... 46
F
AULT RECALL SEQUENCE ...................................... 46
F
AULT CLEAR SEQUENCE: ...................................... 4 7
Normal Sequence of Operation ............................... 47
P
OWER UP ......................................................... 47
H
EA TING MODE .................................................... 47
C
OOLING MODE.................................................... 48
F
AN ONL Y MODE .................................................. 48
Operational Checks ................................................. 48
Safety Circuit Description........................................ 48
F
URNACE CONTROL BOARD .................................... 48
P
RIMARY LIMIT..................................................... 48
A
UXILIARY LIMIT ................................................... 48
R
OLLOUT LIMIT .................................................... 48
P
RESSURE SWITCHES ............................................ 49
F
LAME SENSOR.................................................... 49
Troubleshooting....................................................... 49
E
LECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ....... 49
D
IAGNOSTIC CHART............................................... 49
R
ESETTING FROM LOCKOUT .................................... 49
Maintenance ............................................................. 49
A
NNUAL INSPECTION .............................................. 50
F
ILTERS .............................................................. 50
B
URNERS ............................................................ 50
I
NDUCED DRAFT AND CIRCULATOR BLOWERS ............... 50
C
ONDENSATE TRAP AND DRAIN SYSTEM
(QUALIFIED SERVICER ONLY) ............................... 50
F
LAME SENSOR (QUALIFIED SERVICER ONLY) ............. 50
Before Leaving an Installation ................................. 51
Repair and Replacement Parts ................................ 51
T roubleshooting Codes ........................................... 52
Wiring Diagram ........................................................ 58
Special Instructions for Products Installed
in the State of Massachusetts ........................ 59
3
WARNING
G
OODMANWILLNOTBERESPO NSIBLEFORANYINJURYORPROPERTY
DAMAGEARISINGFROMIMPROPERSERVICEORSERVICEPROCEDURES
I
FYOUINSTALLORPERFORMSERVICEONTHISUNIT,YOUASSUME
RESPO NSIBILITYFORANYPERSONALINJURYORPROPERTYDAMAGE
WHICHMAYRESU LT
INSTALLORSERVICEHEATINGANDAIRCONDITIONINGEQUIPMEN T
.M
ANYJURISDICTIO N SREQUIREALICENSETO
.
WARNING
TO
.
PREVENTPERSONALINJURYORDEATHDUETOIMPROPER
INSTALLATION,ADJUSTMENT,ALTERA TI O N,SERVICEORMAINTENANCE
REFERTOTHISMANUAL
INFORMATIO N,CONSU LTAQUALIFIEDINSTALLER,SERVICERAGENCYOR
THEGASSUPPLIER
.FOR
ADDITIONALASSISTANCEOR
.
,
SAFETY CONSIDERATIONS
Adhere to the following warnings and cautions when install­ing, adjusting, altering, servicing, or operating the furnace. T o ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and applica­tion of this product.
This furnace is manufactured for use with natural gas. It may be field converted to operate on L.P. gas by using the appro­priate L.P. conversion kit listed in the PROPANE GAS/HIGH ALTITUDE INST ALLATIONS section of this manual
Install this furnace only in a location and position as specified in LOCATION REQUIREMENTS & CONSIDERATIONS sec- tion and INST ALLATION POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the fur­nace as specified in COMBUSTION & VENTILATION AIR
REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors. Connect this furnace to an approved vent system only, as specified in VENT/FLUE PIPE & COMBUSTION AIR PIPE section of this manual.
Never test for gas leaks with an open flame. Use a commer­cially available soap solution made specifically for the detec­tion of leaks to check all connections, as specified in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s in­tended temperature-rise range with a duct system which has external static pressure within the allowable range, as speci­fied on the furnace rating plate and OPERATIONAL CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain­ing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
WARNING
IF
THEINFORMATIONINTHESEINSTRUCTION SISNOTFOLLOWED
EXACTLY,AFIREOREXPLOSIONMAYRESU LTCAUSINGPROPERTY
,
DAMAGE
PERSONALINJURYORLOSSOFLIFE
DO
NOTSTOREORUSEGASOLINEOROTHERFLAMMABLEVAPORSAND
LIQUIDSINTHEVICINITYOFTHISORANYOTHERAPPLIANCE
.
.
WHATTODOIFYOUSMELLGAS:
ONOTTRYTOLIGHTANYAPPLIANCE
D
ONOTTOUCHANYELECTRICALSWITCH;DONOTUSEANYPHONE
D
INYOURBUILDING
MMEDIATELYCALLYOURGASSUPPLIERFROMANEIGHBOR’S
I
PHONE
.F
FYOUCANNOTREACHYOURGASSUPPLIER,CALLTHEFIRE
I
DEPARTMENT
NSTALLATIONANDSERVICEMUSTBEPERFORMEDBYAQUALIFIED
I
INSTALLER,SERVICEAGENCYORTHEGASSUPPLIER
.
OLLOWTHEGASSUPPLIER’SINSTRU CTIONS
.
.
.
.
WARNING
T
HISPRODUCTCONTAI NSORPRODUCESACHEMICALORCHEMICALS WHICHMAYCAUSESERIOUSILLNESSORDEATHANDWHICHARE KNOWNTOTHESTATEOFCALIFORNIATOCAUSECANCER,BIRTH DEFECTSOROTHERREPRODUCTIVEHARM
.
WARNING
H
EATINGUNITSHOULDNOTBEUTILIZEDWITHOUTREASONABLE
ROUT INE,INSPECTION,MAINTENANCEANDSUPERVISION
BUILDINGINWHICHANYSUCHDEVICEISLOCATEDWILLBEVACAN T
CARESHOULDBETAKENTHATSUCHDEVICEISROUT INELYINSPECTED
MAINTAINEDANDMONITORED.INTHEEVENTTHATTHEBUILDING
MAYBEEXPOSEDTOFREEZINGTEMPERATURESANDWILLBEVACAN T
ALLWATER‐BEARINGPIPESSHOULDBEDRAINED,THEBUILDINGSHOULD
BEPROPERLYWINTERIZED,ANDTHEWATERSOURCECLOSED.INTHE
EVENTTHATTHEBUILDINGMAYBEEXPOSEDTOFREEZING
TEMPERATURESANDWILLBEVACAN T,ANYHYDR ONICCOILUNITS
SHOULDBEDRAINEDASWELLAND,INSUCHCASE,ALTERNATIVEHEAT
SOURCESSHOULDBEUTILIZED
.
.IF
THE
,
,
,
,
WARNING
A gas-fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND CONSIDERA TIONS section of this manual.
This furnace may be used as a construction site heater only if certain conditions are met. These conditions are listed in the PRODUCT APPLICATION section of this manual.
TO
PREVENTPOSSIBLEPROPERTYDAMAGE,PERSONALINJURYOR DEATHDUETOELECTRICALSHOCK,THEFURNACEMUSTBELOCATEDTO PROTECTTHEELECTRICALCOMPONENTSFROMWATER
4
.
CARBON MONOX IDE POI SONING HAZARD
Spec ial Warnin g f o r In s t a l lat ion of Fur na c e or A ir Ha n dl i n g Un it s in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide prod uc ing devi ces (such as an autom obile, space heater, g as water heater , etc.) should no t be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissio ns. If a furnace or air handler is instal led in an enclosed area such as a garage, utility room or par king area and a carbo n monoxide producing device is operated there in, there must be adequate, dire ct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing de vi ce continues to operate in the enclosed area. Carb on monoxide em issions can be (re)circulated through out the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
B10259-216
-
WARNING
S
HOULDOVERHEAT INGOCCURORTHEGASSUPPLYFAILTOSHUTOFF TURNOFFTHEMANUALGASSHUTOFFVALVEEXTERNALTOTHE FURNACEBEFORETURNINGOFFTHEELECTRICALSUPPLY
.
,
WARNING
P
OSSIBLEPROPERTYDAMAGE,PERSONALINJURYORDEATHDUETO
FIRE,EXPLOSION,SMOKE,SOOT,COND E NSATION,ELECTRICALSHOCK
ORCARBO NMONOXIDEMAYRESU LTFROMIMPROPERINSTALLATION
REPAIROPERATION,ORMAINTENANCEOFTHISPRODUCT
.
,
SHIPPING INSPECTION
All units are securely packed in shipping containers tested ac­cording to International Safe Transit Association specifications. The carton must be checked upon arrival for external damage. If damage is found, a request for inspection by carrier’s agent must be made in writing immediately .
The furnace must be carefully inspected on arrival for damage and bolts or screws which may have come loose in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible damage to shipment or container .
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon as possible - preferably within five days.
4. File the claim with the following support documents within a nine month statute of limitations.
Original or certified copy of the Bill of Lading, or indemnity bond.
Original paid freight bill or indemnity in lieu thereof.
Original or certified copy of the invoice, showing trade and other discounts or reductions.
Copy of the inspection report issued by carrier’s representative at the time damage is reported to carrier .
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching unit.
An electrostatic discharge can adversely affect electrical compo­nents.
Use the following precautions during furnace installation and ser­vicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the same elec­trostatic potential, these steps will help avoid exposing the inte­grated control module to electrostatic discharge. This procedure is applicable to both installed and non-installed (ungrounded) fur­naces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
TO THE INSTALLER
Before installing this unit, please read this manual thoroughly to familiarize yourself with specific items which must be adhered to, including but not limited to: unit maximum external static pres­sure, gas pressures, BTU input rating, proper electrical connec­tions, circulating air temperature rise, minimum or maximum CFM, and motor speed connections.
5
IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WAR-
RANTY
Y our warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please con­tact your installing contractor or contact customer service (877­254-4729) to obtain a copy .
T o receive the Lifetime Heat Exchanger Limited Warranty (good for as long as you own your home) and the 10-year Parts Limited Warranty , online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Complete warranty details are available from your local dealer or, for Goodman www.goodmanmfg.com, and for Amana® brand products, visit www.amana-hac.com.
To register your Goodman www.goodmanmfg.com and click “W arranty Registration”. Com­plete the registration as prompted.
T o register your Amana® brand unit, go to www .amana-hac.com and click on “Warranty Registration”. Complete the registra­tion as prompted.
Product limited warranty certificates for models currently in pro­duction can be viewed at www.goodmanmfg or www.amana­hac.com. If your model is not currently in production or does not appear on the website, please contact your installing contractor or contact customer service at (877-254-4729) to obtain a copy of your warranty certificate.
Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that specific product. T o view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online Product Registration pages are located in this same section.
WARNING
®
brand products, visit
®
brand unit, go to
However, this reduces the benefit s of the ComfortNet system as the enhancements will only apply to the furnace.
The modulating furnace operation is based off of negative pres­sure created by the draft inducer . The furnace control board receives commands from the room thermostat. The furnace control board then controls the RPM of the (3 phase) inducer by varying the frequency and voltage to the inducer . This is known as variable frequency drive (VFD). The inducer , pres­sure switches, and gas valve are linked by pneumatic tubing. The gas valve modulates based on this negative pressure.
*
*
26
9
8
7
10
11
3
12
33
13
15
14
17
16
18
19
20
21
26
27
23
25
10
11
6
5
7
4
3
*
*
2
1
*
*
*
*
*
31
18
19
20
28
BLOWER COMPARTMENT BURNER COMPARTMENT
23
UPFLOW/HORIZONTAL
5
27
32
25
TO
PREVENTPROPERTYDAMAGE,PERSONALINJURYORDEATHDUETO FIRE,DONOTINSTALLTHISFURNACEINAMOBILEHOME,TRAILER,OR RECREATIONALVEHICLE
P
RODUCT DESCRIPTION
.
FEATURES
This furnace is a part of the ComfortNet™ family of products. The CTK0* thermostat kit allows this furnace to be installed as part of a digitally communicating system. The ComfortNet system pro­vides automatic airflow configuration, enhanced setup features, and enhanced diagnostics. It also reduces the number of thermo­stat wires to a maximum of four. It may be also installed as p art of a non-communicating system using a standard 24 V AC thermo­stat.
This product may be installed with the ComfortNet thermostat and a non-ComfortNet compatible single stage air conditioning unit.
6
20
13
17
18
33
24
3
31
19
12
9
COUNTERFLOW/HORIZONTAL
8
7
28
3
15
29
18
20
2
6
7
1
4
14
BLOWER COMPARTMENT
16
30
19
21
1 Gas V alve 2 Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 Combustion Air Intake Connection 6 Hot Surface Igniter 7 Rollout Limit 8 Burners
9 Flame Sensor 10 Flue Pipe Connection 11 Flue Pipe 12 Primary Limit 13 Gas Line Entrance 14 Flue Pipe Connection (Alternate) 15 Rubber Elbow 16 Variable-Speed Induced Draft Blower 17 Electrical Connection Inlets (Alternate) 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations 21 Drain Trap 22 Blower Door Interlock Switch 23 Inductor (Not All Models) 24 Two-Stage Integrated Control Module
(with fuse and diagnostic LED) 25 24 Volt Thermostat Connections 26 Transformer (40 VA) 27 ECM Variable Speed Circulator Blower 28 Auxiliary Limit 29 Junction Box 30 Electrical Connection Inlets 31 Coil Front Cover 32 Combustion Air Inlet Pipe (*CVM96 only) 33 "H" Fitting
P
RODUCT APPLICA TION
This furnace is primarily designed for residential home-heating ap­plications. It is NOT designed or certified for use in mobile homes, trailers or recreational vehicles. Neither is it designed or certified for outdoor applications. The furnace must be installed indoors (i.e., attic space, crawl space, or garage area provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commer­cial applications:
Schools, Office buildings, Churches, Retail stores,
Nursing homes, Hotels/motels, Common or office areas
In such applications, the furnace must be installed with the follow­ing stipulations:
It must be installed per the installation instructions provided and per local and national codes.
It must be installed indoors in a building constructed on site.
It must be part of a ducted system and not used in a free air delivery application.
It must not be used as a “make-up” air unit.
It must be installed as a two-pipe system.
All other warranty exclusions and restrictions apply This furnace is an ETL dual-certified appliance and is appropriate for use with natural or propane gas (NOTE: If using propane, a propane conversion kit is required).
Dual certification means that the combustion air inlet pipe is OP­TIONAL and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in which combustion air is taken from the installation area or from air ducted from the outside or ,
Direct vent (dual pipe) central forced air furnace in which all combustion air supplied directly to the furnace burners through a special air intake system outlined in these instructions.
This furnace may be used as a construction site heater ONL Y if all of the following conditions are met:
The vent system is permanently installed per these installation instructions.
A room thermostat is used to control the furnace. Fixed jumpers that provide continuous heating CANNOT be used and can cause long term equipment damage.
Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained.
Air filters are installed in the system and maintained during construction replaced as appropriate during construction, and upon completion of construction.
The input rate and temperature rise are set per the furnace rating plate.
100% outside air is provided for combustion air requirements during construction. T emporary ducting can be used.
NOTE: Do not connect the temporary duct directly to the furnace. The duct must be sized for adequate combustion and ventilation in accordance with the latest edition of the National Fuel Gas Code NFP A 54/ANSI Z223.1 or CAN/CSA B149.1 Installation Codes.
The furnace heat exchanger , components, duct system, air filters and evaporator coils are thoroughly cleaned following final construction clean up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) are verified according to these installation instructions.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
Gas furnaces must be installed by a licensed plumber or gas fitter.
A T -handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and operation instructions, all local building codes and or­dinances. In their absence, follow the latest edition of the Na-
tional Fuel Gas Code (NFP A 54/ANSI Z223.1), and/or CAN/CSA
7
B149.1 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFP A 54/ANSI Z223.1)
can be obtained from any of the following:
American National Standards Institute
1430 Broadway
New Y ork, NY 10018
National Fire Protection Association
1 Batterymarch Park
Quincy , MA 02269
CSA International
8501 East Pleasant V alley
Cleveland, OH 44131
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accor­dance with “ASHRAE Guide” or “Manual J-Load Calculations” pub­lished by the Air Conditioning Contractors of America.
A copy of the CAN/CSA B149.1 Installation Codes can also be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
L
OCATION REQUIREMENTS
& C
ONSIDERA TIONS
Follow the instructions listed below and the guidelines provided in the Combustion and Ventilation Air Requirements section when selecting a furnace location.
WARNING
TO
PREVENTPOSSIBLEEQUIPM EN TDAMAGE,PROPERTYDAMAGE
PERSONALINJURYORDEATH,THEFOLLOWINGBULLETPOINTSMUSTBE
OBSERVEDWHENINSTALLINGTHISUNIT
.
,
WARNING
P
OSSIBLEPROPERTYDAMAGE,PERSONALINJURYORDEATHDUETO
FIRE,EXPLOSION,SMOKE,SOOT,COND E NSATION,ELECTRICALSHOCK
ORCARBO NMONOXIDEMAYRESU LTFROMIMPROPERINSTALLATION
REPAIROPERATION,ORMAINTENANCEOFTHISPRODUCT
.
,
Centrally locate the furnace with respect to the proposed or existing air distribution system.
Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
Provide provisions for venting combustion products outdoors through a proper venting system. Special consideration should be given to vent/flue pipe routing and combustion air intake pipe when applicable. Refer to V ent/Flue Pipe and Combustion Air Pipe -T ermination Locations for appropriate termination locations and to determine if the piping system from furnace to termination can be accomplished within the guidelines given. NOTE: The length of flue and/or combustion air piping can be a limiting factor in the location of the furnace.
Locate the furnace so condensate flows downwards to the drain. Do not locate the furnace or its condensate drainage system in any area subject to below freezing temperatures without proper freeze protection. Refer to Condensate Drain Lines and T rap for further details.
Ensure adequate combustion air is available for the furnace. Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon monoxide. Refer to
Combustion and Ventilation Air Requirements.
Set the furnace on a level floor to enable proper condensate drainage. If the floor becomes wet or damp at times, place the furnace above the floor on a concrete base sized approximately 1-1/2" larger than the base of the furnace. Refer to the Horizontal Applications and Considerations for leveling of horizontal furnaces.
Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible material. The only combustible material allowed is wood.
A special accessory subbase must be used for upright counterflow unit installations over any combustible material (including wood). Refer to subbase instructions for installation details. (NOTE: A subbase will not be required if an air conditioning coil is located beneath the furnace between the supply air opening and the combustible floor.
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace where the combustion air is exposed to the following substances:
permanent wave solutions chlorinated waxes or cleaners chlorine-based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene) printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials
Isolate a non-direct furnace from an area contaminated by any of the above substances. This protects the non-direct vent furnace from airborne contaminants. T o ensure that the enclosed non-direct vent furnace has an adequate supply of combustion air, air must be ducted in from a nearby uncontaminated room or from outdoors. Refer to the Combustion and Ventilation Air Requirements for details.
8
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling coil. Premature heat exchanger failure will result if the cooling coil is placed upstream of the furnace.
For vertical (upflow or downflow) applications, the minimum cooling coil width shall not be less than furnace width minus 1”. Additionally , a coil inst alled above an upflow furnace or under a counterflow furnace may be the same width as the furnace or may be one size larger than the furnace. Example: a “C” width
coil may be installed with a “B” width furnace.
For upflow applications, the front of the coil and furnace must face the same direction.
If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source are located not less than 18 inches (457 mm) above the floor. Protect the furnace from physical damage by vehicles.
If the furnace is installed horizontally , ensure the access doors are not on the “up/top” or “down/bottom” side of the furnace.
Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel.
On Counterflow Installations, the air conditioning coil must be downstream on the supply (positive) side of the furnace heat exchanger.
Counterflow Installation over a noncombustible floor. Before setting the furnace over the plenum opening, ensure the surface around the opening is smooth and level. A tight seal should be made between the furnace base and floor by using a silicone rubber caulking compound or cement grout.
Counterflow Installation over a combustible floor. If installation over a combustible floor becomes necessary , use an accessory subbase (see Specification Sheet applicable for your model for details.) A special accessory subbase must be used for upright counterflow unit installations over any combustible material including wood. Refer to subbase instructions for installation details. Follow the instructions with the subbase for proper installation. Do not install the furnace directly on carpeting, tile, or other combustible material other than wood flooring. (NOTE: The subbase will not be required if an air conditioning coil is installed between the supply air opening on the furnace and the floor.)
CLEARANCES AND ACCESSIBILITY
In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances
are greater.
*CVM96* MINIMUM CLEARANCE TO COMBUST IBLE MATERIALS
(INCHES)
POSITION SIDES REAR FRONT BOTTOM FLUE TOP
Downflow 0" 0" 3" NC 0" 1"
Horizontal 6" 0" 3" C 0" 6"
C = If placed on combustible floor, floor MUS T be wood only. NC = For installation on non-combustible floors only. A combustible subbase must be used for installations on combustible flooring.
NOTES:
For servicing or cleaning, a 24” front clearance is required.
Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above.
In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances
are greater.
Installations must adhere to the clearances to combustible mate­rials to which this furnace has been design certified. The minimum clearance information for this furnace is provided on the unit’s clear­ance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas, electri­cal, and drain trap and drain line connections. NOTE: In addition to the required clearances to combustible materials, a minimum of 24 inches service clearance must be available in front of the unit.
TOP
TOP
SIDE SIDE SIDE
BOTTOM
BOTTOM
Upflow Counterflow Horizontal
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting sys-
tem serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the Ameri-
can National Standard/National Standard of Canada for Gas­Fired Central Furnaces ANSI Z21.4, CSA-2.3 latest edition Section 1.23.1.
The following steps shall be followed with each appliance con­nected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
*MVM96* MI NIMUM CLEARAN CE TO CO MBU STIBLE MATERIALS
(INCHES)
POSITION SIDES REAR FRONT BOTTOM FLUE TOP
Upflow 0" 0" 3" C 0" 1"
Horizontal 6" 0" 3" C 0" 6"
C = If placed on combustible floor, floor M UST be wood only.
NOTES:
For servicing or cleaning, a 24” front clearance is required.
Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above.
1. Seal any unused openings in the venting system;
2. Inspect the venting system for proper size and horizon­tal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the Natural Gas and Propane Installa­tion Code, CSA B149.1-05 and these instructions. De­termine that there is no blockage or restriction, leak­age, corrosion and other deficiencies which could cause an unsafe condition.
9
3. As far as practical, close all building doors and win­dows and all doors between the space in which the appliance(s) connected to the venting system are lo­cated and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermost at so appliance shall operate continuously .
7. Test for spillage from draft hood appliances at the draft hood relief opening after 5 minutes of main burner op­eration. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accor­dance with the National Fuel Gas Code ANSI Z223.1/ NFP A 54 and/or National Gas and Prop ane Installation Code CSA B149.1-05.
9. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation Codes.
THERMOSTAT LOCATION
The thermostat should be placed approximately five feet from the floor on a vibration-free, inside wall in an area having good air circulation. Do not install the thermostat where it may be influ­enced by any of the following:
Drafts, or dead spots behind doors, in corners, or under cabinets.
Hot or cold air from registers.
Radiant heat from the sun.
Light fixtures or other appliances.
Radiant heat from a fireplace.
Concealed hot or cold water pipes, or chimneys.
Unconditioned areas behind the thermostat, such as an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions and further precautions.
C
OMBUSTION
& V
ENTILA TION AIR REQUIREMENTS
WARNING
TO
AVOIDPROPERTYDAMAGE,PERSONALINJURYORDEATH
SUFFICIEN TFRESHAIRFORPROPERCOMBUSTIONANDVENTILATIONOF
FLUEGASESMUSTBESUPPLIED
SUPPLIEDINTOTHEFURNACEAREA
.M
OSTHOMESREQUIREOUTSIDEAIRBE
.
,
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying com­bustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances of air.
House depressurization can cause back drafting or improper com­bustion of gas-fired appliances, thereby exposing building occu­pants to gas combustion products that could include carbon mon­oxide.
When the furnace is installed as a direct vent (2-pipe system) furnace, no special provisions for air for combustion are re­quired. However, if this furnace is to be installed in the same space with other gas appliances, such as a water heater , ensure there is an adequate supply of combustion and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Instal­lation Codes or applicable provisions of the local building codes for determining the combustion air requirements for the appli­ances.
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
The following information on air for combustion and ventilation is reproduced from the National Fuel Gas Code NFPA 54/ANSI
Z223.1 Section 9.3.
9.3* Air for Combustion and Ventilation.
9.3.1 General.
9.3.1.1 Air for combustion, ventilation, and dilution of flue gases for
appliances installed in buildings shall be obtained by application of one of the methods covered in 9.3.2 through 9.3.6. Where the requirements of
9.3.2 are not met, outdoor air shall be introduced in accordance with meth­ods covered in 9.3.3 through 9.3.6.
Exception No. 1: This provision shall not apply to direct vent appliances.
9.3.1.2 Appliances of other than natural draft design and other than Cat­egory 1 vented appliances shall be provided with combustion, ventilation, and dilution air in accordance with the appliance manufacturer’s instruc­tions.
9.3.1.3 Appliances shall be located so as not to interfere with proper circulation of combustion, ventilation, and dilution air.
10
9.3.1.4 Where used, a draft hood or a barometric draft regulator shall be installed in the same room or enclosure as the appliance served so as to prevent any difference in pressure between the hood or regulator and the combustion air supply.
9.3.1.5 Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air require­ments.
9.3.2 Indoor Combustion Air. The required volume of indoor air shall be determined in accordance with the method in 9.3.2.1 or 9.3.2.2 except that where the air infiltration rate is known to be less than 0.40 ACH, the method in 9.3.2.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appli­ances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with 9.3.2.3, are considered a part of the required volume.
9.3.2.1* Standard Method. The minimum required volume shall be 50 ft
3
per 1,000/Btu/hour (4.8m3/kW).
9.3.2.2* Known Air Infiltration Rate Method. Where the air infiltration rate of a structure is known, the minimum required volume shall be deter­mined as follows: (1) For appliances other than fan-assisted, calculate using the following
equation: Required Volume
> ________ _________
other
(2) For fan-assisted appliances, calculate using the following equation:
Required Volume
> ________ _________
fan
3
21 ft
I
other
ACH 1000 Btu/hr
3
15 ft
I
fan
ACH 1000 Btu/hr
where:
I I
= all appliances other than fan-assisted input in Btu per hour
other
= fan-assisted appliances input in Btu per hour
fan
ACH = air change per hour (percent of volume of space exchanged
per hour, expressed as a decimal)
Figure A.9.2.3.3.(1) All Combustion Air from Adjacent
Indoor Spaces through Indoor Combustion Air Openings.
(2) Combining spaces in different stories. The volumes of spaces in dif-
ferent stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in.2/1000 Btu/hr (4400 mm2/kW) of total input rating of all appliances.
9.3.3 Outdoor Combustion Air. Outdoor combustion air shall be pro­vided through opening(s) to the outdoors in accordance with the methods in 9.3.3.1 or 9.3.3.2. The minimum dimension of air openings shall not be less than 3 in. (80 mm).
9.3.3.1 Two Permanent Openings Method. Two permanent openings, one commencing within 12 in. (300 mm) of the top and one commencing within 12 in. (300 mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows:
(1)*Where directly communicating with the outdoors or where communi-
cating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2/4000 Btu/hr (550 min2/kW) of total input rating of all appliances in the enclosure. [See Figure A.9.3.3.1(1)(a)
and Figure A.9.3.3.1(1)(b).]
(3) For purposes of this calculation, an infiltration rate greater than 0.60
ACH shall not be used in the equations in 9.3.2.2(1) and 9.3.2.2(2).
9.3.2.3 Indoor Opening Size and Location. Openings used to connect indoor spaces shall be sized and located in accordance with the following:
(1)*Combining spaces on the same story . Each opening shall have a mini-
mum free area of 1 in.2/1000Btu/hr (2200 mm2/kW) of the total input rating of all appliances in the space but not less than 100 in.2 (0.60m2). One opening shall commence within 12 in. (300 mm) of the top, and one opening shall commence within 12 in. (300 mm) of the bottom, of the enclosure [see Figure A.9.3.2.3(1)]. The minimum dimension of air openings shall be not less than 3 in. (80 mm).
11
Figure A.9.3.3.1(1)(a) All Combustion Air From Outdoors -
Inlet Air from Ventilated Crawl Space and Outlet Air
to Ventilated Attic.
Figure A.9.3.3.1(1)(b) All Combustion Air From Outdoors through Ventilated Attic.
(2)* Where communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 in.2/2000 Btu/hr (1100 min2/kW) of total input rating of all appliances in the enclosure.
[See Figure A.9.3.3.1(2).]
Figure A.9.3.3.1(2) All Combustion Air From Outdoors
through Horizontal Ducts.
9.3.3.2* One Permanent Opening Method. One permanent openings,
commencing within 12 in. (300 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall com­municate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure A.9.3.3.2) and shall have a minimum free area of the following: (1) 1 in.
2
/3000 Btu/hr (700 mm2 per kW) of the total input rating of all
appliances located in the enclosure, and
(2) Not less than the sum of the areas of all vent connectors in the space.
Figure A.9.3.3.2 All Combustion Air
From Outdoors through Single Combustion Air Opening.
9.3.4 Combination Indoor and Outdoor Combustion Air. The use of a
combination of indoor and outdoor combustion air shall be in accordance with (1) through (3) (see example calculation in Annex J]:
(1) Indoor Openings: Where used, openings connecting the interior spaces
shall comply with 9.3.2.3.
(2) Outdoor Opening(s) Location. Outdoor opening(s) shall be located in
accordance with 9.3.3.
(3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be calcu-
lated in accordance with the following:
(a) The ratio of the interior spaces shall be the available volume of
all communicating spaces divided by the required volume.
(b) The outdoor size reduction factor shall be 1 minus the ratio of
interior spaces.
12
(c) The minimum size of outdoor opening(s) shall be the full size of
outdoor opening(s) calculated in accordance with 9.3.3, multi­plied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in. (80 mm).
9.3.8.5 Ducts shall not be screened where terminating in an attic space.
9.3.8.6 Horizontal upper combustion air ducts shall not slope downward
toward the source of combustion air.
9.3.5 Engineered Installations. Engineered combustion air installations shall provide an adequate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.
9.3.6 Mechanical Combustion Air Supply. Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied form outdoors at the minimum rate of 0.35 ft hr (0.034 m
9.3.6.1 Where exhaust fans are installed, additional air shall be provided to replace the exhausted air.
9.3.6.2 Each of the appliances served shall be interlocked to the mechanical air supply system to prevent main burner operation where the mechanical air supply system is not in operation.
9.3.6.3 Where combustion air is provided by the building’s mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air.
9.3.7 Louvers, Grilles, and Screens.
9.3.7.1 Louvers and Grilles. The required size of openings for combus-
tion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25 percent free area, and metal louvers and grilles will have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in the open position.
3
/min per kW) for all appliances located within the space.
3
/min per 1000 Btu/
9.3.8.7 The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or factory built chimney shall not be used to supply combustion air.
Exception: Direct vent appliances designed for installation in a solid fuel­burning fireplace where installed in accordance with the manufacture’s installation instructions.
9.3.8.8 Combustion air intake openings located on the exterior of the building shall have the lowest side of the combustion air intake openings located at least 12 in. (300 mm) vertically from the adjoining grade level.
I
NST ALLA TION POSITIONS
A/GMVM96 models may be installed upflow or horizontally with left or right side down. A/GCVM96 models may be in­stalled downflow or horizontally with left or right side down.
Do not install this furnace on its back. For upright upflow fur- naces, return air ductwork may be attached to the side panel(s) and/or basepan. For horizontal upflow furnaces, return air duct­work must be attached to the basepan. For both upright or horizontal counterflow furnaces, return ductwork must be attached to the basepan (top end of the blower compartment). NOTE: Ductwork must never be attached to the back of the furnace. Refer to “Recommended Installation Positions” figure for appro­priate installation positions, ductwork connections, and resulting airflow arrangements.
9.3.7.2 Minimum Scree Mesh Size. Screens shall not be smaller than 1/ 4 in. mesh.
9.3.7.3 Motorized Louvers. Motorized louvers shall be interlocked with the appliance so they are proven in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the main burner form igniting should the louver fail to open during burner startup and to shut down the main burner if the louvers close during burner operation.
9.3.8 Combustion Air Ducts. Combustion air ducts shall comply with
9.3.8.1 through 9.3.8.8.
9.3.8.1 Ducts shall be constructed of galvanized steel or a material having equivalent corrosion resistance, strength, and rigidity.
Exception: Within dwellings units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one fireblock is removed.
9.3.8.2 Ducts shall terminate in an unobstructed space, allowing free move­ment of combustion air to the appliances.
9.3.8.3 Ducts shall serve a single space.
9.3.8.4 Ducts shall not serve both upper and lower combustion air open-
ings where both such openings are used. The separation between ducts servicing upper and lower combustion air openings shall be maintained to the source of combustion air.
13
Recommended Installation Positions
H
ORIZONT AL APPLICA TIONS
& C
ONSIDERA TIONS
When installing a furnace horizontally , additional consideration must be given to the following:
FURNACE SUSPENSION
If suspending the furnace from rafters or joists, use 3/8" threaded rod and 2”x2”x1/8” angle iron as shown in the following diagram. The length of rod will depend on the application and the clearances necessary .
If the furnace is installed in a crawl space it must be suspended from the floor joist or supported by a concrete pad. Never install the furnace on the ground or allow it to be exposed to water.
LEVELING
Leveling ensures proper condensate drainage from the heat ex­changer and induced draft blower . For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The furnace should also be level from back to front or have a slight tilt with the access doors downhill (approximately 3/4 inches) from the back panel. The slight tilt allows the heat exchanger condensate, gen­erated in the recuperator coil, to flow forward to the recuperator coil front cover.
ALTERNATE ELECTRICAL AND GAS LINE CONNECTIONS
This furnace has provisions allowing for electrical and gas line con­nections through either side panel. In horizontal applications the connections can be made either through the “top” or “bottom” of the furnace.
DRAIN PAN
A drain pan must be provided if the furnace is installed above a conditioned area. The drain pan must cover the entire area under the furnace (and air conditioning coil if applicable).
FREEZE PROTECTION
Refer to Horizontal Applications and Conditions - Drain T rap and Lines.
2" 2" 3/8"
ANGLE IRON
XX
(3
PLACES
)
DRAIN TRAP AND LINES
In horizontal applications the condensate drain trap is secured to the furnace side panel, suspending it below the furnace. A mini­mum clearance of 4 3/4 inches below the furnace must be pro­vided for the drain trap. Additionally, the appropriate downward piping slope must be maintained from the drain trap to the drain location. Refer to Condensate Drain T rap and Lines for further de­tails. If the drain trap and drain line will be exposed to temperatures near or below freezing, adequate measures must be taken to pre­vent condensate from freezing.
P
ROP ANE GAS/HIGH AL TITUDE INST ALLA TIONS
WARNING
P
OSSIBLEPROPERTYDAMAGE,PERSONALINJURYORDEATHMAY
OCCURIFTHECORRECTCONVERSIONKITSARENOTINSTALLED
APPROPRIATEKITSMUSTBEAPPLIEDTOENSURESAFEANDPROPER
FURNACEOPERATION
QUALIFIEDINSTALLERORSERVICEAGENCY
.ALL
CONVERSIONSMUSTBEPERFORMEDBYA
.
.THE
This furnace is shipped from the factory configured for natural gas up to 10,000 ft. altitude. Propane conversions require the proper LP kit to compensate for the energy content difference be­tween natural and propane gas.
LP kits include a manifold assembly, including an LP gas valve, orifices and LP burners.
Altitude Kit
Gas
Natural None
Propane LPKMOD*****
0-10,000
Orifice
#45
1.25MM
Manifold Pressure
Low Stage
High
(50% firing
Stage
1
3.5" w.c. 1" w.c. Non e
2
10.0" w.c. 2.6" w.c. None
rate)
Pressure
Switch
Change
NOTE:
In Canada, gas furnaces are only certified to 4500 feet .
1
Except 115,000 B TU: #43
2
Except 115,000 B TU: #55
For furnaces being converted to LP gas, it is strongly recom­mended that a LPLP03 kit also be installed. The use of this kit will prevent the furnace from firing when the LP gas supply pressure is too low to support proper combustion.
14
Furnace Model LP K it
A/GMVM960603BX A/GMVM960805CX A/GMVM961005DX A/GMVM961155DX A/GCVM960604CX LPKMOD060CF A/GCVM960805DX LPKMOD080CF A/GCVM961005DX LPKMOD100CF
LPKMOD060UF LPKMOD080UF LPKMOD100UF LPKMOD115UF
The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified in­staller, or service agency .
V
ENT/FLUE PIPE
& C
OMBUSTION AIR PIPE
It is the responsibility of the installer to follow the manufacturers’ recommendations and to verify that all vent/flue piping and connec­tors are compatible with furnace flue products. Additionally, it is the responsibility of the installer to ensure that all piping and con­nections possess adequate structural integrity and support to pre­vent flue pipe separation, shifting, or sagging during furnace opera­tion.
DUAL CERTIFICATION: NON-DIRECT/DIRECT VENT
This furnace is dual certified and may be installed as a non-direct vent (single pipe) or direct vent (dual pipe) appliance. A non-direct vent installation requires only a vent/flue pipe, while a direct vent installation requires both a vent/flue pipe and a combustion air intake pipe. Refer to the appropriate section for details concerning piping size, length, number of elbows, furnace connections, and terminations.
WARNING
F
AILURETOFOLLOWTHESEINSTRUCTIO N SCANRESU LTINBODILY
INJURYORDEATH
GIVENINTHISSECTION
.C
AREFULLYREADANDFOLLOWALLINSTRUCTIONS
.
WARNING
U
PONCOMPLETIONOFTHEFURNACEINSTALLATION,CAREFULLY
INSPECTTHEENTIREFLUESYSTEMBOTHINSIDEANDOUTSID EOFTHE
FURNACETOASSUREITISPROPERLYSEALED
SYSTEMCANRESU LTINSERIOUSPERSONALINJURYORDEATHDUETO
EXPOSURETOFLUEPRODUCTS,INCLUDINGCARBO NMONOXIDE
.L
EAKSINTHEFLUE
.
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensation takes place. Because of the relatively low flue gas temperature and water con­densation requirements, PVC or ABS pipe is used as venting material.
In addition to PVC and ABS pipe and fittings, Innoflue® by Centrotherm Eco Systems and PolyPro® by M&G Duravent are also approved vent and combustion air materials for instal­lations in the U.S.A. and Canada. Manufacturers Installation instructions for these products must be followed. These prod­ucts have specific instructions for installing, joining and termi­nating. Do not mix materials or components of one manufac­turer with materials or components of another manufacturer .
All furnaces are built with 2" vent / intake pipe and connec­tors. For furnaces requiring installation of 3" pipe, the transi­tion from 2" to 3" should be done as close to the furnace as practically possible.
This furnace must not be connected to T ype B, BW , or L vent or vent connector, and must not be vented into any portion of a fac­tory built or masonry chimney except when used as a pathway for PVC as described later in this section. Never common vent this appliance with another appliance or use a vent which is used by a solid fuel appliance.
WARNING
TO
AVOIDBODILYINJURY,FIREOREXPLOSION,SOLVENTCEMENTS
MUSTBEKEPTAWAYFROMALLIGNITIONSOURCES(I.E
FLAMES,ANDEXCESSIVEHEAT)ASTHEYARECOMBUSTIBLELIQUIDS
VOIDBREATHINGCEMENTVAPO RSORCONTA C TWITHSKINAND/OR
A
EYES
.
.,
SPARKS,OPEN
.
MATERIALS AND JOINING METHODS
Two- or three-inch nominal diameter PVC Schedule 40 pipe meet­ing ASTM D1785, PVC primer meeting ASTM F656, and PVC solvent cement meeting ASTM D2564 specifications must be used. Fittings must be DWV type fittings meeting ASTM D2665 and ASTM D331 1. Carefully follow the pipe manufacturer’s instruc­tions for cutting, cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC or ABS cellular core (Foam Core) plastic pipe is also acceptable as a flue/vent and intake pipe mate­rial. PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used. Fittings must be DWV type fittings meeting ASTM D2665 and ASTM D3311. Carefully follow the manufactures instructions for cutting, cleaning and solvent cementing of PVC.
For Canadian installations; all PVC pipe, fittings and joining materials must be UL S636 listed.
As an alternative to PVC pipe, primer, solvent cement, and fittings, ABS materials which are in compliance with the fol­lowing specifications may be used: Two-or-three-inch solid wall ABS Schedule 40 pipe must meet ASTM D1527 and, if used in Canada, must be CSA listed or, two-or-three-inch cellular core ABS Schedule 40 pipe must meet ASTM F628 and, if used in Canada, must be CSA listed. Solvent cement for ABS to ABS joints must meet ASTM D2235 and, if used in Canada, must be CSA listed. The solvent cement for the PVC to ABS transition joint must meet ASTM D3138. Fittings must be DWV type fittings meeting ASTM D2661 and ASTM D331 1 and, if used in Canada, must be CSA listed. Carefully follow the manufacturers’ instructions for cutting, cleaning, and sol­vent cementing PVC and/or ABS.
15
DIRECT VENT TERMINAL CLEARANCES
A= Clearance above grade,
veranda, porch, deck or balcony. (See 1.24.6-i(9)b.)
B= Clearance to window or
door that may b e opened.
C= Clearance to permanently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal.
E= Clearance to unventilated soffit. * * F= Clearance to outside corner. * * G= Clearance to inside corner. * * H= Clearance to each side of center
line exten ded ab o ve meter / regulator assembly.
Canadian Installations
12 in. (30 cm) 12 in. (30 cm)
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
**
**
3 ft. (91 cm) within a height 15 ft. (4.5 m) above the meter/regulator assembly.
1
v
U.S. Installations
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 9 in. (23 cm) for appliances > 10,000 Btuh (3 kW) and 50,000 Btuh (15 kW), 12 in. (30 cm) for appliances > 500,000 Btuh (15 kW).
*
2
V X
I= Clearance to service
regulator vent outlet.
J= Clearance to nonmechanical air
supply inlet to building or the combustion air inlet to any other appliance.
K= Clearan ce to a mechanical
air supply inlet.
L= Clearance above paved sidewalk or
paved driveway located on public property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves
both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instruction.”
Canadian Installations
3 ft. (91 cm). *
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m) 3 ft. (91 cm) above if within
7 ft. (2.13m) † *
12 in. (30 cm) ‡ *
1
U.S. Installations
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 9 in. (23 cm) for appliances > 10,000 Btuh (3kW) and 50,000 Btuh (15 kW), 12 in. (30 cm) for appliances > 50,000 Btuh (15 kW).
10 ft. (3 m) horiz ontally.
2
OTHER THAN DIRECT VENT TERMINAL CLEARANCES
A= C learance above grade,
veranda, porch, deck or balcony. (See 1.24.6-i(9)b.)
B= C learance to window or
door that may be opened.
C= Clearance to permanently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal.
E= C learance to unventilated soffit. * * F= Clearance to outside corner. * * G= Clearance to inside corner. * * H= Clearance to each side of center
line extended above meter/regulator assembly.
Canadian Installations
12 in. (30 cm) 12 in. ( 30 cm )
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
**
**
3 ft. (91 cm) within a height 15 ft. (4.5 m) above the meter/regulator assembly.
1
U.S. Installations
4 ft. (1.2 m) below or to side of opening; 1 ft. (300 m) above opening.
*
2
I= Clearance to sevice
regulator vent outlet.
J= Clearance to nonmechanical air
supply inlet to building or the combustion air inlet to any other appliance.
K= Clearance to a mechanical
air supply inlet.
L= Clearance above paved sidewalk or
paved driveway located on public property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paveable driveway that is located between two single family dwellings and serves
both dwelling.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instruction.”
Canadian Installations
3 ft. (91 cm). *
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m) 3 ft. (91 cm) above if within
7 ft. (2.13m) † 7 ft. (2.13m)
12 in. (30 cm) ‡ *
1
U.S. Installations
4 ft. (1.2 m) below or to side of opening; 1 ft. (300 m) above opening.
10 ft. (3 m) horizontally.
16
2
All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM D331 1. A medium radius (1/4 bend DWV) elbow measures 3 1/ 16” minimum from the plane of one opening to the centerline of the other opening for 2” diameter pipe, and 4 9/16” minimum for 3” pipe.
The use of two short radius 45 degree elbows is permitted to provide clearance to refrigerant piping above the furnace.
PROPER VENT/FLUE AND COMBUSTION AIR PIPING PRACTICES
Adhere to these instructions to ensure safe and proper furnace performance. The length, diameter , and number of elbows of the vent/flue pipe and combustion air pipe (when applicable) affects the performance of the furnace and must be carefully sized. All piping must be installed in accordance with local codes and these instructions.
Piping must be adequately secured and supported to prohibit sag­ging, joint separation, and/or detachment from the furnace. Hori­zontal runs of vent/flue and combustion air piping must be prop­erly supported. PVC pipe supports must be no more than 5' apart. For ABS pipe, supports must be no more than 3' apart. Horizontal pipe runs must maintain a 1/4 inch per foot downward slope, back towards the furnace, to properly return condensate to the furnace’s drain system.
PREFERRED
ACCEPTABLE
TRANSITION NO LESS THAN 45 DEGREES TO HORIZONTAL PLANE TO AVOID CREATING A W ATER TRAP IN VENT PIPING.
NO TRANSI TION ON HORIZONTAL PL ANE, THIS CREATES A WATER TRAP AND RESTRICTS FLUE GASES
Precautions should be taken to prevent condensate from freezing inside the vent/flue pipe and/or at the vent/flue pipe termination. All vent/flue piping exposed to temperatures below 35°F for extended periods of time must be insulated with 1/2” thick closed cell foam. Also, all vent/flue piping exposed outdoors in excess of the termi­nations shown in this manual (or in unheated areas) must be insu­lated with 1/2” thick closed cell foam. Inspect piping for leaks prior to installing insulation.
TERMINATION LOCATIONS
NOTE: Refer to Location Requirements and Considerations for
combustion air contaminant restrictions. The following bullets and diagram describe the restrictions con-
cerning the appropriate location of vent/flue pipe and combustion air intake pipe (when applicable) terminations. Refer to Non-Direct Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping lo­cated in this section for specific details on termination construc­tion.
All terminations (flue and/or intake) must be located at least 12 inches above ground level or the anticipated snow level.
Vent terminations (non-direct and direct vent) must terminate at least 3 feet above any forced air inlet located within 10 feet.
NOTE: This provision does not apply to the combustion air intake termination of a direct vent application.
The vent termination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter a building (door, window , or gravity air inlet).
The vent termination running vertically through a roof must terminate at least 12 inches above the roof line (or the anticipated snow level) and be at least 12 inches from any vertical wall (including any anticipated snow build up).
A vent termination shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent application should not terminate in an area which is frequently dusty or dirty .
NOTE: In Canada, the current edition of CAN/CSA B149.1 takes precedence over the preceding termination restriction.
17
3
REMOVE
PIPE
4
REMOVE
AND RELOCATE
CABINET GROMMET
2
DETACH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
5
5
EXTERNALLY
EXTERNALLY
MOUNT
MOUNT
RUBBER ELBOW
RUBBER ELBOW
AND SECURE FLANGE
AND SECURE FLANGE
WITH 4 SCREWS
WITH 4 SCREWS
REMOVED IN STEP 1
REMOVED IN STEP 1
3
REMOVE
PIPE
INSTALL CABINET GROMMET
IN 2 LOCATIONS
2
REMOVE
3 SCREWS
RUBBER ELBOW
AND SECURE FLANGE
WITH 4 SCREWS
4
REMOVED IN STEP 1
DETATCH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
ID BLOWER WITH
RUBBER COUPLING
COUNTERFLOW-HORIZONTAL MODEL ALTERNATE VENT
TO USE ALTERNATE COMBUSTION AIR LOCATION, REMOVE INTERNAL PIPE AS PER ABOVE. CAP UNUSED CABINET OPENINGS
CABINET WITH
5
7
EXTERNALLY
MOUNT
6
SECURE TO
AND HOSE
CLAMPS
SECURE TO
SCREWS
ALTERNATE COMBUSTION AIR LO CATION ON C’FLOW -HOR MODELS
COUNTERFLOW- HOR IZONTAL MODEL
AL TER NATE CO MBUST ION AI R LOCATION
18
Loading...
+ 42 hidden pages