Goodman GMVM, ACVM, GCVM, AMVM Service Instructions Manual

Page 1
Service Instructions
96% Modulating Gas Furnaces
ACVM, AMVM, GCVM, GMVM
& Accessories
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
Copyright © 2011 - 2013 Goodman Manufacturing Company, L.P.
RS6612001r9
November 2013
1
Page 2
TABLE OF CONTENTS
IMPORTANT INFORMATION ........................... 2-3
PRODUCT IDENTIFICATION ........................ 4 - 7
ACCESSORIES........................................... 8 - 10
LIGHTING INSTRUCTIONS ...............................11
PRODUCT DESIGN ...................................12 - 31
OPERATION ...............................................32 - 56
COMFORTNET™ SYSTEMS............................58
ABBREVIATIONS & DEFINITIONS ....................59
ABBREVIATIONS & OPERATION .....................60
SERVICE AND OPERATION......................61 - 62
OPERATIONAL CHECKS ..........................63 - 64
MAINTENANCE ..................................................65
SERVICING TABLE OF CONTENTS ................66
SERVICING .................................................67 - 74
TROUBLESHOOTING................................75 - 79
STATUS CODES...............................................80
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATER IALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPL IANCE.
WARNING
G
OODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES.
I
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR P ROPERTY DAMAGE WHICH
MAY RESULT.
M
ANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL O R SERVICE HEATING AND A IR CONDITIONING EQUIPMENT.
HIGH VOLTAG E D
ISCONNECT ALL POWER BEFOR E SERVICING OR
INSTALLING THIS UNIT. BE PR ESENT. DAMAGE, PERSO NAL INJURY OR DEATH.
2
WARNING
MULTIPLE POWER SOURCES MAY
FAILURE TO DO SO M AY CAU SE PROPERTY
Page 3
IMPORTANT INFORMATION
Speci al Wa r ning for Inst allation of Furnace or Air Handling Units in Enclosed A reas such as Garage s, Utility Ro oms or Parki ng A r eas
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as un ve n tilated garages, ut ility rooms or parking areas because of the danger of car bon monox ide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circu l a ted throughout the structure if t he furnace or air han dler is operating in any mode.
CO can cause serious illness in clud ing per man e nt brain dama ge or deat h.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
customerservice@goodmanmfg.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
hac.consumer.affairs@amanahvac.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
3
Page 4
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
GMVM960603BXAA
PRODUCT TYPE:
G: G oodman A: Amana
Brand
®
SUPPLY TYPE
M: Upflow/Horizontal C : Downflow/Hori z ontal
FURNACE TYPE
V: Variable-Speed
COMMUNICATION FEATURE
M: Modulating Furn ac e 4-Wir e Comm unic ation Re ady
NOMINAL INPUT
060: 60,000 Btuh 080: 80,000 Btuh 10 0: 100,000 B tuh 11 5: 115,000 B tuh
AFUE
96 : 96%
AIRFLO W CAPABILITY @ 0.5" ES P
3: 120 0 4: 160 0 5: 200 0
CABINET WID TH
B: 17-1/2" C: 2 1" D: 2 4- 1/2 "
MAJOR REVISION
A: Initial Release
MINOR REVISION
A: Initial R elease
ADD IT IO NAL FEAT URE S
N: Natural Gas X: Low NOx
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
4
Page 5
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
, Downflow/Horizontal Left and Right, 40" tall,
same as AA revision above, but BA revision
Upflow/Horizontal Left or Right, 40" tall, Induced
same as AA revision above, but BA revision
ACVM96******
ACVM96******
AMVM96******
AMVM96******
ACVM96******AA
ACVM96******BA
AMV M96******AA
AMV M96******BA
Amana® Brand 96% M odulating Gas Furnace
Induced Draft, ClimateTalk™ communicating furnace. Modulating gas input fr om 35% -100% of rated input. 4 wire serial ECM motor. Independent humidification with capable thermostat.
Amana® Brand 96% M odulating Gas Furnace,
models furnace cabinet Air Leakage must be <2.0%.
Amana® Brand 96% M odulating Gas Furnace,
Draft, ClimateTalk™ communicating furnace. Modulating gas input fr om 35% -100% of rated input. 4 wire serial ECM motor. Independent humidification wit h capable thermostat.
Amana® Brand 96% M odulating Gas Furnace,
models furnace cabinet Air Leakage must be <2.0%.
MODEL # MFG. # DESCRIPTION
GCVM96******
GCVM96******
GM VM96******
GM VM96******
GCVM96******AA
GCVM96******BA
GMVM 96******AA
GMVM 96******BA
Goodman® Brand 96% Modulating Gas Furnace
Induced Dra ft, ClimateTalk™ communicating furnace. Modulating gas input from 35% -100% of rated input. 4 wir e serial ECM motor . Independent humidification with capable thermostat.
Goodman® Brand 96% Modulating Gas Furnace
models furnace cabinet Air Leakage must be <2.0%.
Goodman® Brand 96% Modulating Gas Furnace,
Induced Dra ft, ClimateTalk™ communicating furnace. Modulating gas input from 35% -100% of rated input. 4 wir e serial ECM motor . Independent humidification with capable thermostat.
Goodman® Brand 96% Modulating Gas Furnace
models furnace cabinet Air Leakage must be <2.0%.
, Down flow/Horizontal Left and Right, 40" tall,
, same as the AA revision above but BA
Upflow/Horizon ta l Left or Right, 40" tall,
, same as the AA revision above but BA
5
Page 6
PRODUCT IDENTIFICATION
MODEL # MFG # DESCRIPTION
The AFE18-60A control is designed for use wher e the indoor c oil is loc ated above/downst ream
. F or use with current ar c hit ec tural grey Goodman® and Amana® Br and 96% variable speed,
. F or use with current ar c hit ec tural grey Goodman® and Amana® B rand 96% variable
AFE18-60A
AMU1620 AMU1625 AMU2020 AMU2025
GMU162 0 GMU162 5 GMU202 0 GMU202 5
ASAS-10 ASAS-11 ASAS-12 ASAS-18
N/A
P1251305F P1251306F P1251307F P1251308F
N/A
P1251301F P1251302F P1251303F P1251304F
Foss il Fuel Kit.
of a gas or fossil fuel furnace when used wit h a heat pump. I t will operate with single and t wo stage heat pumps and single and two st age furnaces. The AFE18-60A control will turn the heat pump unit off when t he fur n ace is turned on. A n a nti-short c ycle featur e in itiates a 3 minute timed off dela y when the compressor goes off.
Media Air Cleaner
modulat i ng f urnac e models. The Amana (AMU*) and Goodman ( GMU*) Media A ir Cleaner is a high efficiency air filtration device designed to remov e d irt, d ust , pollen and other microscopic parti c les from the air pa ssing through it. Flexible perf or mance range up to 2,000 CF M capacity. The air cleaner should be installed in the system so that all the system air is c irculated through the air cleaner. T he air c leaner will only r emov e the airbor n e c o ntaminants delivered t o i t. Maximum performance is obt a ined wh en the syste m blower is set for continuous operation. Carbon filter s (optional) are available.
Electronic Air Cleaner
speed, modulating f ur nace models. The High-Efficiency E lectronic Air Cleaner is designed t o r emov e air contaminants down t o .01 microns. Carbon filters (optional) remove odors. Dual indicat or lights show unit operation at a gla nc e . Electronic prov ing swit ch cycles the air cleaner On/Off w ith the system fan. D urable po wder-coat pa int finish resists corrosio n.
CFB17
CTK01
CTK01BA
CTK02**
CTK03A*
P1228004F
CTK01AA
CTK01BA
CTK02**
CTK03A*
Do wn flow Subb ase Kit
are available for the following f u r na ce widths: 17 .5" wide (CFB17), 21" wid e (CFB21) and 24" wid e (CFB24). The kits must be used to preve nt ex cessive t emper ature f rom reaching co mbustible mate rials, if the fur n ace is installed on a co mbustible floor. T his subbase eff ec tiv ely separat ed the fur nac e base and plenum f rom combust ible materials. To ensure safe inst allat ion, do not install the c ount er flow floor base directly on carpeting, tile, or other combustible mat erial other than wood flooring.
Co mmu n icating T hermostat K i t
communicat ing sy stem. Designed for use wit h compatible Amana® B rand or Goodman® Brand Air Handlers or Furnaces and outdoor split A C or H eat P ump units. This thermostat supports up to three stages of heat, t wo stages of cooling, dual fuel applications, dehumidific at ion, filter maintenance reminders, outdoor temperat ur e display and advanc ed menus inc luding diagnostics. The CTK01AA k it includes a communicating t ouchscreen thermo st at and sub base, 230V-24V 40va transformer, terminal blocks( 2 ), wire j umpers, mounting sc rews, installation manual and homeowner guide.
Co mmu n icating T hermostat K i t
communicat ing sy stem. Designed for use wit h compatible Amana® B rand or Goodman® Brand Air Handlers or Furnaces and outdoor split A C or H eat P ump units. This thermostat supports up to three stages of heat, t wo stages of cooling, dual fuel applications, dehumidific at ion, filter maintenance reminders, outdoor temperat ur e display and advanc ed menus inc luding diagnostics. The CTK01BA kit includes a communicating t ouc hscreen thermo st at and sub base, t ermi nal blo cks(2), mount i ng scre ws, i nst alla tion manual and homeowner guid e.
Co mmu n icating T hermostat K i t
system. Designed for use wit h c ompatible A mana® Brand or G oodman® Brand A ir Handlers or Furnaces and outdoor split A C or Heat Pump units. The CTK02** thermostat features full color, high definition display , advanc ed programming opt ions including humidific at ion control & heat and cool maximum temperat ur e sett ings, a U S B pl ug allo win g de alers the ability to insert pre-progra mmed operating paramete r s and deal er information by use of an online data entry system.
Co mmu n icating T hermostat K i t
for use with compatible Amana® Brand or Goodman® Brand A ir Handlers or Furnaces and outdoor split AC or Heat P u mp units. The CTK03A* the r mostat features full c ol or hi gh de finition di splay, c a n b e used with RedLINK wir eless accessories.
. For use with Goodman®, & Amana® Brand modulating furnace models. These kits
- Digitally communicating touchscreen thermostat, a necessar y part of any
- Digitally communicating touchscreen thermostat, a necessar y part of any
- Digitally communicating thermost at, a necessary part of any communic ating
- Digitally communicating touchscreen thermost at from Honeywell. Designed
6
Page 7
PRODUCT IDENTIFICATION
MODEL # MFG # DESCRIPTION
DCVK-20
DCVK-30
DEHUM1
EFR01
0170K00000S
0170K00001S
P1254001F
P1254002F
P1227801F
P1221001
P1221002F
N/A
N/A
Concentric Vent Kit
terminat ions of a dir ec t v ent furnace to be "concentrically" vent ed through a wall or roof. T his kit allows a single penetration to support terminations for bot h the vent/flue and the combustion air intake pipe. The DCVK-2 0 ( 2") and DCV K-30 (3") kits are certified for models listed above. See specification sheets on future models for use of the vent kit.
Dehumidistat.
models. Wall mounted, 24 volt humidity control available as a Dehumidistat used t o r educ e the airflow in the air condit ioning mode when necessary to lower the humidity in an occ upi ed home to prevent dew build-up assoc iated with high humidity levels. This contr o l features a moisture-sensitiv e nylon element and also provides positive ON-OFF settings for manual operat ion . The control is a normally closed switch that opens on humidity rise causing the blower to switch to a lower speed to c ontrol the humidit y within the struct ure.
E xt ern al F ilter R ack Kit
modulating gas furnaces. This kit is intended t o pr ovide a location, exter nal to the f ur nac e c asing for installation of a per manent filter. The rac k is mounted over the in door air blow er c ompart ment ar ea of either side panel, and provide filter retention as well as a loc ation for attaching r e turn air ductwork.
Side Wall Only Concentric Vent Kit
2" - 3" v ent systems. The vent ki t must terminate outside the str ucture. This kit is NOT intended for use with single pipe (indirect vent) installations.
Side Wall Only Concentric Vent Kit
2" vent systems. The ven t kit must ter minate outside the structure. T his kit is NOT int ended for use with single pipe (indirect vent) installation
. F or use with Amana® Br and Modulati ng furnace models. This kit is designed to allow
For use wit h Goodman® & Amana® Br and two-stage variable speed modulating furnac e
. F or use with Goodman® and A mana® Brand 96% upflow, variable speed *M VM
. For use with 96% modulating f urn ac e models. This kit is to be used with
. For use with 96% modulating f urn ac e models. This kit is to be used with
MODE L # MFG # DESCRIPTION
LPLP03
LPKMOD060UF
LPKMOD080UF
LPKMOD100UF
LPKMOD115UF
LPKMOD060CF
LPKMOD080CF
LPKMOD100CF
RF000142
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LP Gas Low Pressure Kit
single-stage, tw o-stage and m odulating furnaces c onverted to LP gas. The kit monitors gas line pres sure wit h a pressure sw it ch and will open the circuit to t he gas v alve if the LP tank press ure gets low .
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
LP Conversion Kit
with LP orific es and modulat ing LP gas valve. New burners designed for use with LP gas are also included.
D ra in Coup ling Kit
kit prevents condensat e from get ting in the inducer an d routes the condens ate t o a drain.
. Des igned for application on Goodman® and Amana® Brand's 80% and 90%
For use with A/GMVM9603BX** furnace. The kit comes with a gas manifold equipped
For use with A/GMVM960805CX** furnace. The kit comes with a gas manifold equipped
For use with A/GMVM961005DX** furnace. The kit comes with a gas manifold equipped
For use with A/GMVM961155DX** furnace. The kit comes with a gas manifold equipped
For use with A/GCVM960604CX** furnac e. The kit comes with a gas manifold equipped
For use with A/GCVM960805DX** furnac e. The kit comes with a gas manifold equipped
For use with A/GCVM961005DX furnac e. The kit comes with a gas manifold equipped
For use when the drain/vent elbow has been removed in a horizontal left installation . This
7
Page 8
ACCESSORIES
AMANA® BRAND Furnace Accessories
MODEL
NUM BER
Description
AMVM960603BX** X X X X X X
AMVM960805CX** X X X X X X
AMVM961005DX** X X X X X X
ACVM960604CX** X X X X X X X
ACVM960805DX** X X X X X X X
MODEL
NUM BER
Description
AMVM960603BX** X X XXXXX
AFE180-60A AMU / GMU ASAS / GSAS CFB17 CFB21 CFB24 CTK01* CTK02** CTK03AA
Fossil Fuel
Kit
0170K00000S 0170K00001S DCVK-20 DCVK-30 D EHUM1 EFR01
Concentric
Side Wall
Vent Kit (3")
Media
Air Cleaners
Not used in this application
Concentric
Side Wall
Vent Kit (2")
Electronic
Air Cleaner
Concentric
Vent Kit
(2")
Downflow
Subbase
17 .5"
Concentric
Vent Kit
(3")
Downflow
Subbase
21"
Dehumidistat
Downflow
Subbase
24.5"
External
Filter Rack
Com.
Thermostat
Kit
LPKMOD­06/08/11UF
LPKMOD-
06/08/11CF
Propane
Gas
Conversion
Kit
Com
Thermostat
Kit
-M odulating, High Def
Com
Thermostat
-M odulating, High Def
Kit
AMVM960805CX** X X X X X X
AMVM961005DX** X X X X X X
ACVM960604CX** X X XXXXX
ACVM960805DX** X X XXXXX
Not used in this application
8
Page 9
ACCESSORIES
g
g
GOODMAN® BRAND Furna ce Accessories
MODEL
NUM BER
Description
GM VM 960603B X** X X X X X X
GM VM 960805C X** X X X X X X
GMVM961005DX**XXX XXX
GM VM 961155DX** X X X X X X
GCVM960604CX** X X X X X X X
GCVM960805DX** X X X X X X X
GCVM961005DX**XXX XXXX
MODEL
NUM BER
Description
GMVM960603BX**XXXXXXXX
AFE180-60A AMU / GMU ASAS / GSAS CFB 17 CFB21 CFB24 CTK01* CTK02** CT K03AA
Fossil Fuel
Kit
0170K00000S 0170K00001S DC VK-20 D CVK-30 D EH UM1 EFR01
Concentric
Side Wall
Vent Kit (3")
Media
Air Cleaners
Not used in this application
Concentric
Side Wall
Vent Kit (2")
Electronic
Air Cleaner
Concentric
Vent Kit
(2")
Downflow
Subbase
17.5 "
Concentric
Vent Kit
(3")
Downflow
Subbase
21"
Dehumidistat
Downflow
Subbase
24.5"
External
Filte r
Rack
Com.
Thermostat
Kit
LPKMOD-
06/ 08/11UF
LPKMOD-
06/08 /11CF
Propane
Gas
Conversion
Kit
Com
Thermostat
Kit
-M odulating, h Def
Hi
RF 000142
Drain Kit
Com
Thermostat
Kit
-M odulating, h D ef
Hi
GMVM960805CX**XX XXXXX
GMVM961005DX**XX XXXXX
GMVM961155DX**XX XXXXX
GCVM960604CX**XXXXXXXX
GCVM960805DX**XXXXXXXX
GCVM961005DX**XX XXXXX
Not used in this application
9
Page 10
ACCESSORIES
EXTERNAL FIL TER RACK (EFR01 )
Used on 96% Upflow Modulating Furnaces
CONCENTRIC VENT CONVERSION KIT ( DCVK-20
The DCVK-20 (2") or the DCVK-30 (3") is a concentric vent
kit approved with furnaces listed in this manual. This concentric vent kit allows for vertical or horizontal vent
termination. The illustrations give a brief view of the kit and its application.
Vent
Strap (Field Supplied)
Combustion Air
Vent
See the section in this manual under "Vent Flue and Com­bustion Air Pipe Terminations" for more information or con­sult the Installation and Operating Instructions (IO-619*).
UNIT SIDE
PANEL
FRONT
OF UNIT
BASE
OF UNIT

DCVK-30)

Roof Boot/Flashing (Field Supplied)
RETURN AIR
CUTOUT AREA
Combustion Air
Vent
SLOTS IN FILTER CLEAR SCREWS
ON UNIT
Maintain 12" (18" for Canada) minimum clearance above highest anticipated snow level. Maximum of 24" above roof.
BLOWER DECK
LOWER EDGE
SCREW
SCREWS
FILTER RACK ASSEMBLY
(FACE FILTER OPENING
TOWARDS FRONT
OF UNIT)
Flush to
1" maximum
Combustion Air
45 Elbow (Field Supplied)
DCVK
(Horizontal Installation)
SIDE WALL VENT KIT (0170K00000S)
This side wall only vent kit #0170K00000S is to be used with 2” - 3” vent systems. This kit is NOT intended for use with single pipe (indirect vent) installations.
The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side­by-side or with one pipe above the other.
See the section in this manual under "Vent Flue and Com­bustion Air Pipe Terminations" for more information or con­sult the Installation Instructions (IO-635).
Support (Field Supplied)
45 Elbow (Field Supplied)
Vent
Combustion Air
DCVK
(Vertical Installation)
The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side­by-side or with one pipe above the other.
See the section in this manual under "Vent Flue and Com­bustion Air Pipe Terminations" for more information or con­sult the Installation Instructions (IO-805).
Horizontal Installation
SIDE WALL VENT KIT (0170K00001S)
This side wall only vent kit #0170K00001S is to be used with 2” vent systems. This kit is NOT intended for use with single pipe (indirect vent) installations.
10
Ve rtic a l In s ta lla tio n
Page 11
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY
READ BE FO RE OPERATING
If you do not follow these instructions
WARNING:
explosion may result causing propertyExactly, a fire or damage, personal injury or
loss of life.
A. This appliance does not have a pilot. It is equipped with an ign itio n device which automatically lights the burner. Do not try
to light the burner by hand. B. smell all around the appliance
BEFORE OPERATING
area for gas. Be sure to smell next to the floor settle on the floor.
WH AT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electric switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control lever. Never use tools. If the lever will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
LIRE AVANT DE METTRE
EN MARCHELIRE
AVERTISSEMENT :
la lettre les instructions dans le presént manuel risque de déclencher un incendie ou une explosion entraînant des dommages matériels, des lesions corporelles ou la perte de vies humaines.
Cet appareil ne comporte pas de veilleuse. Il est
A.
muni d'un dispositif d'allumage qui allume automatiquement le brûleur. Ne pas tenter d'allumer le brûleur manuellement.
B. AVANT DE LE FAIRE FONCTIONNER,
une odeur de gaz. Renifler prés du plancher, car certains gaz sont plus lourds que l'air et peuvent s'accumuler au niveau du sol.
QUE FAIRE S'IL Y A UNE ODEUR DE GAZ
Ne pas tenter d'allumer d'appareils. Ne toucher à aucun interrupteur; ne pas vous servir des téléphones dans le bâtiment.
Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur de gaz
Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le ser vice des incendies.» C. Ne pousser ou tourner la manette d'admission du gaz qu'à la main. Ne jamais emploer d'outil à cette fin.
Si la manette reste coincée, ne tenter pas de la réparer; appelez un technicien qualifié. Quiconque tente de forcer la manette ou de la réparer peut provoquer une explosion ou un incendie.»
D. Ne pas se servir de cet appareil s'il a été plongé dans l'eau, même partiellement. Faire inspecter l'appareil par un technicien qualifié et remplacer toutr partie du
systéme de contrôle et toute commande qui ont été plongées dans l'eau.»
Quiconque ne respecte pas à
er
OPERATING INSTRUCTIONS
STOP
!
STOP. "B"
"OFF"
GAS INLET
ARRIVEE
DU GAZ
ROBINET A GAZ MANUEL, EN POS "ON/MARCHE"
MANUAL GAS LEVER SHOWN IN "ON" POS
1. Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the bur ner. Do not try to light the burner by hand.
5. Push the gas control lever to Position. Do not force.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you then smell gas, Follow in the safety. information ab ov e on this label if you don't smell gas, go to next step.
7. Push gas control lever to
"ON".
8. Replace access panel.
9. Turn on all electric power to the appliance.
10. Set thermostat to desired setting.
11. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas com pa ny.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest sett ing.
2. Turn off all electric power to the appliance if service is to be performed.
3. Push the gas control lever to Position. Do not force.
4. Replace control access panel.
"OFF"
MISE EN MARCHE
ARRÊTEZ
1. Lisez les instructions de sécurité dans la section supérieure de cette étiquette.
.
2. Régler le thermostat à la température la plus basse.
3. Couper l'alimentation électrique de l'appareil.
4. Cet appareil menager etant dote d'un systeme d'allumage automatique, ne pas essayer à allumer le brûleur manuellement.
5. Pousse le levier du contrÔle du gaz a
position.
6. Attendre cinq (5) minutes pour laisser echapper tout le
gaz. Renifler tout autour de l'appareil, y compris prés du plancher, pour déceler une odeur de gaz. Si c'est le cas,
Passer à l'etape B des instructions de secu rite
ARRÊTEZ.
sur la portion superieure de cette etiquette. S'il n'y a pas d'odeur de gaz, passer à l'etàpe suivante.
7. Pousse le levier du contrôle du gaz à position.
8. Remettre en place le panneau d'accés.
9. Mettre l' appareil sous tension.
10. Régler le thermostat à la temp érature désirée.
11. Si l'appareil ne se met pas en marche, suivre les instructions intitulées Comment couper l'admission de gaz de l'appareil et appeler un technicien qualifié ou le fournisseur de gaz.
"OFF/ ARRET"
"ON/MARCHE"
POUR COUPER L'ADMISSION DE GAZ DE L'APPAREIL
1. Régle r le thermostat à la t emp ér a t ure la plus bassé .
2. Couper l'alimentation électrique de l'appareil s'il faut procéder à des operations d'entretien.
3. Pousse le levier du contrôle du gaz à position. Ne pas forcer.
4. Remettre en place le panneau d'accés.
"OFF/ ARRET"
0140F00996 REV A
11
Page 12
PRODUCT DESIGN
Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace. To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and appli­cation of this product.
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE REFER TO THIS MANUAL INFORMATION, CONS ULT A QUALIFIED INSTALLER, SERVICER AGENCY OR THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
WARNING
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY
,
DAMAGE
PERSONAL INJURY OR LOSS OF LIFE
DO
NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
WHAT TO DO IF YOU SMELL GA S:
O NOT TRY TO LIGHT ANY APPLIANCE
D
D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE
IN YOUR BUILDING
I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
PHONE
. F
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE
I
DEPARTMENT
I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
.
OLLOW THE GAS SUPPLIER’S INSTRUCTIONS
.
.
.
.
W ARNING
T
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODU C TIVE HARM
.
WARNING
TO
PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO
,
PROTECT THE ELECTRICAL COMPONENTS FROM WATER
.
CARBON MONOX IDE POI SONING HAZARD
Spec ial Warnin g for Instal lat i on of Furna c e or A ir Ha n dl i n g Un it s in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space heater, g as water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissio ns. If a furnace or air ha ndler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device co ntinues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated through out the structure if t he furnace or air handler is operating in any mode.
WARNING
H
EATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASON ABLE ROUTINE, INSPECTION, MAINTENANCE AND SUPERVISION BUILDING IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VACANT CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUTINELY INSPECTED MAINTAINED AND MONITORED. IN THE EVENT THAT THE BUILDING MAYBE EXPOSED TO FREEZING TEMPERATU RES AND WILL BE VACANT ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE BUILDING SHOULD BE PROPERLY WINTERIZED, AND THE WATER SOURCE CLOSED. IN THE EVENT THAT THE BUILDING MAY BE EXPOS ED TO FREEZING TEMPERATURES AND WILL BE VACANT, ANY HYDRON IC COIL UNITS SHOULD BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED
.
12
. IF
THE
CO can cause serious illness including permanent brain damage or death.
-
B10259-216
,
,
,
,
S
HOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
W ARNING
,
.
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, EXPLOSION, SMOKE, SOOT, CONDENSATION, ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION, OR MAINTENANCE OF THIS PRODUCT
WARNING
,
.
Page 13
PRODUCT DESIGN
Electrostatic Discharge (ESD) Precautions NOTE: Discharge body’s static electricity before touching
unit. An electrostatic discharge can adversely affect electri­cal components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from dam­age. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic dis­charge. This procedure is applicable to both installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’ s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
WARNING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECR EATIONAL VEHICLE
.
Product Description
Features
General Information
The modulating furnace is part of the Goodman® brand & Amana® brand family of communicating ready products. The furnace may be used with conventional single or multi-stage thermostats as well as Goodman CTK01 communicating thermostats & CTK02** & CTK03 communicating-modulat­ing thermostats using the ClimateTalk™ communicating pro­tocol. Burner manifold pressure is controlled by negative air pressure created by the draft inducer. Gas valve, pressure switch assembly, and induced draft blower are linked to­gether by pneumatic tubing. The furnace features a Honeywell gas valve capable of variable gas input rates as low as 35% and up to 100% of rated input. Indoor air is delivered by an Emerson UltraTech® ECM motor which bases the CFM need off of the burner input. The modulating furnace operation is
based off of negative pressure created by the draft inducer. The Integrated Furnace Control (IFC) receives commands from the room thermostat. The IFC then controls the RPM of the (3 phase) inducer by varying the frequency and voltage to the inducer. This is known as variable frequency drive (VFD)..
Acceptable Equipment Combinations
With CTK0* Communicating Thermostat:
1. Modulating furnace alone
2. Modulating furnace with Goodman® brand / Amana® brand communicating split A/C or H/P unit (no sepa­rate dual fuel control is required)
3. Modulating furnace with non-communicating 1 stage A/C split unit (can not support a 2 stage A/C or a non­communicating heat pump)
With Conventional Non-Communicating Thermostat (Single or Multi-Stage)
1. Modulating furnace alone
2. Modulating furnace with Goodman / Amana communi­cating split A/C or H/P unit (a dual fuel thermostat or separate dual fuel control is required for H/P)
3. Modulating furnace with non-communicating split A/C or H/P (a dual fuel thermostat or separate dual fuel control is required for H/P)
Product Application This furnace is primarily designed for residential home-heat-
ing applications. It is NOT designed or certified for use in mobile homes, trailers or recreational vehicles. Neither is it designed or certified for outdoor applications. The furnace MUST be installed indoors (i.e., attic space, crawl space, or garage area provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial com­mercial applications:
Schools, Office buildings, Churches, Retail stores,
Nursing homes, Hotels/motels,
Common or office areas
In such applications, the furnace must be installed with the following stipulations:
It must be installed per the installation instructions pro­vided and per local and national codes.
It must be installed indoors in a building constructed on site.
It must be part of a ducted system and not used in a free air delivery application.
It must not be used as a “make-up” air unit.
It must be installed with two-pipe systems for combus­tion air.
13
Page 14
PRODUCT DESIGN
All other warranty exclusions and restrictions apply This furnace is an ETL dual-certified appliance and is appropri­ate for use with natural or propane gas (NOTE: If using propane, a propane conversion kit is required).
Dual certification means that the combustion air inlet pipe is optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in which combustion air is taken from the installation area or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which all combustion air supplied directly to the furnace burners through a special air intake system outlined in these in­structions.
This furnace may be used as a construction site heater ONLY if all of the following conditions are met:
The vent system is permanently installed per these in­stallation instructions.
A room thermostat is used to control the furnace. Fixed jumpers that provide continuous heating CANNOT be used and can cause long term equipment damage.
Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained.
Air filters are installed in the system and maintained dur­ing construction replaced as appropriate during construc­tion, and upon completion of construction.
The input rate and temperature rise are set per the fur­nace rating plate.
100% outside air is provided for combustion air require­ments during construction. Temporary ducting can be used.
NOTE: Do not connect the temporary duct directly to the furnace. The duct must be sized for adequate combus­tion and ventilation in accordance with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA B149.1 Installation Codes.
The furnace heat exchanger, components, duct system, air filters and evaporator coils are thoroughly cleaned fol­lowing final construction clean up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) are verified according to these installation instructions.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
Gas furnaces must be installed by a licensed plumber or gas fitter.
A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installa­tion and operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of
the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
1430 Broadway
New York, NY 10018
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calcula­tions” published by the Air Conditioning Contractors of America.
A copy of the CAN/CSA B149 Installation Codes can also be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
Location Requirements & Considerations
Follow the instructions listed below and the guidelines provided in the Combustion and Ventilation Air Requirements section when selecting a furnace location.
Furnace Models
The 96% AFUE modulating furnace comes in up flow / hori­zontal and down flow / horizontal models
Upflow Models
A/GMVM960603BX** A/GMVM960805CX** A/GMVM961005DX** A/GMVM961155DX**
Down Flow Models
A/GCVM960604CX** A/GCVM960805DX**
A/GCVM961005DX
14
Page 15
PRODUCT DESIGN
Furnace Components Heat Exchanger Assembly
The primary heat exchanger is a tubular type constructed of high quality steel (stainless steel for Amana Brand, alumi­nized for Goodman) the heat exchanger assembly consists of primary and secondary sections crimped together on a back transition plate. The secondary heat exchanger is a single pass coil consisting of stainless steel tubes and alu­minum fins. These stainless steel tubes are expanded on to the aluminum fins to enhance heat transfer. Each tube in the secondary heat exchanger contains an internal turbulator to effectively scrub heat from the flue gases. Flue gas conden­sation takes place in the secondary heat exchanger as la­tent heat is transferred from the flue gases to heat the condi­tioned space.
Burners
Depending on the size of the furnace, each furnace will have from three to five inshot burners. Burners are precisely con­structed of aluminized steel and designed to provide proper ignition and flame stability. When converting the modulating furnace to L.P. gas, the factory installed burners must be replaced by burners that come in the L.P. kit.
Gas Manifold Assembly
Each gas manifold is fitted with the appropriate number of #45 natural gas orifices. At 100% of gas input, each burner will provide approximately 20,000 BTUH. The A/ GMVM951155DX models uses #43 gas orifices at 22,500 per hour. If converting to LP gas, the factory installed mani­fold assembly must be replaced by the manifold assembly provided in the LP kit.
ECM Motor
An Emerson® UltraTech® four wire indoor fan motor provides supply air to the conditioned space. This is the same motor used on Goodman & Amana previous generation communi­cating furnaces.
Induced Draft Blower (IDB)
All modulating furnace models use a three phase induced draft blower to draw flue gases through the heat exchanger. The inducer uses ball bearings and is permanently lubricated. This motor is driven at varying speeds by the VFD (variable frequency drive) section of the IFC. The IFC takes typical single phase power supplied to the furnace and converts it to a three phase supply to operate the draft inducer at the de­sired speed. The windings of the induced draft motor will have equal resistance +/- 5%. Normal resistance readings at room temperature will range from 14-17 ohms. The voltage sup­plied by the IFC to drive the induced draft blower will vary from 15-110 volts A/C between any two windings. This would be read between any two of the three power wires between the IFC and the induced draft blower. This voltage to the IBD will vary between furnace models and is dependant on what percentage of maximum fire is being called for. The power wires are colored red, white, and black. A green colored ground wire is also present.
Hot Surface Igniter
Modulating furnaces use a 115 volt silicon nitride hot surface igniter. This is the familiar and reliable 0131F00008S igniter with 17 second warm up time. At room temperature the ig­niter has a resistance range of 37 - 68 ohms. The H.S.I. is connected electrically to the IFC by a 3/16" push-on connec­tion.
Gas Valve
Modulating furnaces use a 24 VAC pneumatically operated gas valve by Honeywell. The valve is energized by the inte­grated furnace control on a call for heat, wired in series through the front-cover pressure switch. The firing rate percentage is determined by the negative pressure created by the opera­tion of the draft inducer. The gas valve is factory set and non- adjustable in the field. Do not remove the seal covering the regulator screws or attempt to adjust either of the regulator screws.
Inductor Coil
Wired in series with ¾ and 1 HP ECM motors; the inductor coil conditions the power supply to the motor, smoothing out spikes and electrical noise. With voltage applied to one side of the inductor coil, the output voltage to the motor should be the same as incoming voltage.
Integrated Furnace Control (IFC)
The IFC is the main control center for the furnace. It has many functions including;
Receiving commands from the thermostat for heating, and cooling, continuous fan operation.
Receiving commands for dehumidification and humidi­fication.
Communicating with the ECM motor for proper air de­livery to the conditioned space.
Assuring safe ignition by checking the state of pres­sure switches and limit switches before and after igni­tion.
Assuring safe operation by continuously monitoring the presence of flame, the state of the pressure switches and limit and roll out switches.
Displays information on the dual seven segment dis­plays regarding thermostat call, air flow delivery and fault status
Controlling the speed of the induced draft blower by variable voltage & frequency.
Features of the IFC:
Aux Terminals Located next to the low voltage connector, there are two terminals labeled aux in & aux out. A factory jumper is installed between these two terminals. As an op­tion; the jumper may be removed and the terminals wired up to a normally closed float switch. The switch must be closed for normal operation. If the switch is sensed open, the IFC will:
Terminate a call for gas heat.
15
Page 16
PRODUCT DESIGN
When the modulating furnace is installed with a com­municating thermostat and a non-communicating a/c unit, the IFC will open the Y1 relay to turn off the con­densing unit
Log and display an auxiliary open error code
Once the auxiliary switch re-closes the IFC reverts back to normal operation
Hum Terminals A pair of ¼” HUM terminals are located on the board to power a humidifier. These are dry contacts rated at 1 amp. A typical application of these contacts would be to supply one of the Hum contacts with power from the L1 ter­minal and connect the remaining Hum terminal to a humidi­fier transformer primary. When used with the CTK02** or CTK03 thermostat, these contacts will close with a call for humidity and the furnace indoor blower will be powered at continuous fan speed. When used with a 24 volt control sys­tem, the Hum contacts will close on a call for heat when the induced draft blower is powered.
EAC Terminal A ¼” EAC terminal is provided. Any time the indoor blower motor is powered, the EAC terminal will be powered. Contact is rated for 1 amp
Flame Proving. Flame signal is continuously monitored by the IFC. The flame rod, flame rod wire and proper grounding are all critical to proving the presence of flame. Because of the design of the Honeywell flame proving system, reading flame signal with a microamp meter will not provide reliable and consistent results and is therefore not a recommended practice. The IFC has a built in warning (E6) if flame signal is approaching the low threshold.
Field Test Mode This feature can be used by the service technician to quickly bring a furnace up to high fire. Entering field test mode will by-pass the staging routine and allow the furnace to run at 100% of rated input. To use field test mode; during a call for heat, press the fault recall button twice within 5 seconds, the display will change to Ft, then press and hold the fault recall button for a few seconds until the display flashes Ft. The furnace will stay in field test mode for 5 min­utes or until the call for heat is removed.
Dual 7 Segment Displays The modulating furnace IFC has dual 7 segment displays to provide service information. This information includes; present thermostat demand, CFM, and fault codes.
Fault Recall This feature allows the service person to check for any fault history. The board memory is capable of record­ing and storing 10 fault codes. To use this feature, the fur­nace must not have an existing thermostat call. Pressure fault recall button from 2-5 seconds (until the display goes blank) then release, all faults will be displayed one at a time, beginning with the most recent, max of 3 consecutive faults will be stored. When all errors have been displayed the dis­play returns to ON. To erase stored faults, hold the fault recall button until the display starts flashing, then release.
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THIS UNIT
.
,
WARNING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, EXPLOSION, SMOKE, SOOT, COND E NSATION, ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESU LT FROM IMPROPER INSTALLATION REPAIR OPERATION, OR MAINTENANCE OF THIS PRODUCT
.
Centrally locate the furnace with respect to the proposed or existing air distribution system.
Ensure the temperature of the return air entering the fur­nace is between 55°F and 100°F when the furnace is heat­ing.
Provide provisions for venting combustion products out­doors through a proper venting system. Special consider­ation should be given to vent/flue pipe routing and combus­tion air intake pipe when applicable. Refer to Vent/Flue Pipe and Combustion Air Pipe -Termination Locations for appropriate termination locations and to determine if the piping system from furnace to termination can be accom­plished within the guidelines given. NOTE: The length of flue and/or combustion air piping can be a limiting factor in the location of the furnace.
Locate the furnace so condensate flows downwards to the drain. Do not locate the furnace or its condensate drain­age system in any area subject to below freezing tem­peratures without proper freeze protection. Refer to Con- densate Drain Lines and Trap for further details.
Ensure adequate combustion air is available for the fur­nace. Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon monoxide. Refer to Combustion and Ven-
tilation Air Requirements.
Set the furnace on a level floor to enable proper conden­sate drainage. If the floor becomes wet or damp at times, place the furnace above the floor on a concrete base sized approximately 1-1/2" larger than the base of the furnace. Refer to the Horizontal Applications and Considerations for leveling of horizontal furnaces.
Ensure upflow or horizontal furnaces are not installed di­rectly on carpeting, or any other combustible material. The only combustible material allowed is wood.
A special accessory subbase must be used for upright counterflow unit installations over any combustible mate­rial (including wood). Refer to subbase instructions for installation details. (NOTE: A subbase will not be required if an air conditioning coil is located beneath the furnace between the supply air opening and the combustible floor.
,
16
Page 17
PRODUCT DESIGN
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace where the combustion air is exposed to the following substances:
permanent wave solutions chlorinated waxes or cleaners chlorine-based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene) printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials
Isolate a non-direct furnace from an area contaminated by any of the above substances. This protects the non- direct vent furnace from airborne contaminants. To ensure that the enclosed non-direct vent furnace has an adequate supply of combustion air, vent from a nearby uncontami­nated room or from outdoors. Refer to the Combustion and Ventilation Air Requirements for details.
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cool­ing coil. Premature heat exchanger failure will result if the cooling coil is placed upstream of the furnace.
For vertical (upflow or downflow) applications, the mini­mum cooling coil width shall not be less than furnace width minus 1”. Additionally, a coil installed above an upflow furnace or under a counterflow furnace may be the same width as the furnace or may be one size larger than the furnace. Example: a “C” width coil may
be installed with a “B” width furnace.
For upflow applications, the front of the coil and fur­nace must face the same direction.
If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source are located not less than 18 inches (457 mm) above the floor. Protect the furnace from physical damage by vehicles.
If the furnace is installed horizontally, ensure the access doors are not on the “up/top” or “down/bottom” side of the furnace.
Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel.
On Counterflow Installations, the air conditioning coil must be downstream on the supply (positive) side of the furnace heat exchanger.
Counterflow Installation over a noncombustible floor. Be­fore setting the furnace over the plenum opening, ensure the surface around the opening is smooth and level. A tight seal should be made between the furnace base and floor by using a silicone rubber caulking compound or cement grout.
Counterflow Installation over a combustible floor. If instal- lation over a combustible floor becomes necessary, use an accessory subbase (see Specification Sheet applicable for your model for details.) A special accessory subbase must be used for upright counterflow unit installations over any combustible material including wood. Refer to sub­base instructions for installation details. Follow the instruc­tions with the subbase for proper installation.
Do not install the furnace directly on carpeting, tile, or other
combustible material other than wood flooring. (NOTE: The subbase will not be required if an air conditioning coil is installed between the supply air opening on the furnace and the floor.)
CLEARANCES AND ACCESSIBILITY
*MVM96* MINIMUM CLEARNACE TO COMBUSTIBLE MATERIALS
(INCHES)
POSITION* FRONT SIDES REAR TOP FLUE FLOOR
Upflow30010C
HorizontalAlcove6040C
* = All posit ioning is determined as in st alled unit is viewed from the front. C = I f pl aced on combust ible floor, f l oor M U ST be w ood only. NC = For in st al l ation on non-combustible fl oor s only. A com bustible subbase must be used f or in s t al l at ions on combustible floor in g.
*CVM96* MINIMUM CLEARNACE TO COMBUSTIBLE MATERIALS
(INCHES)
POSITION* FRONT SIDES REAR TOP FLUE FLOOR
Upflow10010NC
HorizontalAlcove6040C
* = All posit ioning is determined as in st alled unit is viewed from the front. C = I f pl aced on combust ible floor, f l oor M U ST be w ood only. NC = For in st al l ation on non-combustible fl oor s only. A com bustible subbase must be used f or in s t al l at ions on combustible floor in g.
Installations must adhere to the clearances to combustible mate­rials to which this furnace has been design certified. The mini­mum clearance information for this furnace is provided on the unit’s clearance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas, electrical, and drain trap and drain line connections. If the alternate combustion air intake or vent/flue connections are used additional clearance must be provided to accommodate these connections. Refer to Vent/Flue Pipe and Combustion Air Pipe for details. NOTE: In addition to the required clearances to com­bustible materials, a minimum of 24 inches service clearance must be available in front of the unit.
17
Page 18
PRODUCT DESIGN
TOP
TOP
SIDE SIDE SIDE
BOTTOM
BOTTOM
Upflow Counterflow Horizontal
A furnace installed in a confined space (i.e., a closet or utility room) must have two ventilation openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr of furnace input rating. Refer to Specification Sheet applicable to your model for minimum clearances to combustible surfaces. One of the venti­lation openings must be within 12 inches of the top; the other opening must be within 12 inches of the bottom of the confined space.
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting sys-
tem serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the Ameri-
can National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.4, CSA-2.3 latest edition Section 1.23.1.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system;
2. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the Natural Gas and Propane Installation Code, CSA B149.1-05 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall oper­ate at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the draft hood relief opening after 5 minutes of main burner opera­tion. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or National Gas and Propane Installation Code CSA B149.1-05.
9. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fire­place dampers and any other gas burning appliance to their previous conditions of use.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation Codes.
THERMOSTAT LOCATION
The thermostat should be placed approximately five feet from the floor on a vibration-free, inside wall in an area having good air circulation. Do not install the thermostat where it may be influ­enced by any of the following:
• Drafts, or dead spots behind doors, in corners, or under cabinets.
• Hot or cold air from registers.
• Radiant heat from the sun.
• Light fixtures or other appliances.
• Radiant heat from a fireplace.
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat, such as an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions and further precautions.
Combustion & V entilation Air Requirements
WARNING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH SUFFICIEN T FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF FLUE GASES MUST BE SUPPLIED SUPPLIED INTO THE FURNACE AREA
. M
OST HOMES REQUIRE OUTSIDE AIR BE
.
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying com­bustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing building occupants to gas combustion products that could include car­bon monoxide.
,
18
Page 19
PRODUCT DESIGN
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Installation Codes or appli­cable provisions of the local building codes for determining the combustion air requirements for the appliances.
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
Installation Positions
This furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this furnace on its back. For upright upflow furnaces, return air ductwork may be attached to the side panel(s) and/or basepan. For hori- zontal upflow furnaces, return air ductwork must be attached to the basepan. For both upright or horizontal counterflow furnaces, return ductwork must be attached to the basepan (top end of the blower compartment). NOTE: Ductwork must never be attached to the back of the furnace. Contact your distributor for proper airflow requirements and number of required ductwork connections. Refer to “Recommended Installation Positions” figure for appropriate installation positions, ductwork connec­tions, and resulting airflow arrangements.
FURNACE SUSPENSION
If suspending the furnace from rafters or joists, use 3/8" threaded rod and 2”x2”x1/8” angle iron as shown in the following diagram. The length of rod will depend on the application and the clear­ances necessary.
If the furnace is installed in a crawl space it must be suspended from the floor joist or supported by a concrete pad. Never install the furnace on the ground or allow it to be exposed to water.
2" 2" 3/8"
ANGLE IRON
XX
(3
PLACES
)
Horizontal Applications & Considerations
Horizontal applications, in particular, may dictate many of the installation’s specifics such as airflow direction, ductwork con­nections, flue and combustion air pipe connections, etc. The basic application of this furnace as a horizontal furnace differs only slightly from an upright installation. When installing a fur­nace horizontally, additional consideration must be given to the following:
DRAIN TRAP AND LINES
In horizontal applications the condensate drain trap is secured to the furnace side panel, suspending it below the furnace. A mini­mum clearance of 4 3/4 inches below the furnace must be pro­vided for the drain trap. Additionally, the appropriate downward piping slope must be maintained from the drain trap to the drain location. Refer to Condensate Drain Trap and Lines for further details. If the drain trap and drain line will be exposed to tempera­tures near or below freezing, adequate measures must be taken to prevent condensate from freezing.
LEVELING
Leveling ensures proper condensate drainage from the heat ex­changer and induced draft blower. For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The fur­nace should also be level from back to front or have a slight tilt with the access doors downhill (approximately 3/4 inches) from the back panel. The slight tilt allows the heat exchanger conden­sate, generated in the recuperator coil, to flow forward to the recuperator coil front cover.
Horizontal Furnace
19
Page 20
1
PRODUCT DESIGN
ALTERNATE VENT/FLUE AND COMBUSTION AIR CONNECTIONS
In horizontal installations with the furnace laying on the left hand side, the alternate vent connection may be used. In this configuration, the internal elbow is removed The stan­dard piping connections may also be used in these posi­tions. Refer to Vent/Flue Pipe and Combustion Air Pipe for details concerning the conversion to the alternate vent/flue and combustion air connections.
When using the horizontal alternate vent configuration, you must use the RF000142 vent drain kit. See following illustra­tion.
ALTERNATE ELECTRICAL AND GAS LINE CONNECTIONS
This furnace has provisions allowing for electrical and gas line connections through either side panel. In horizontal applications the connections can be made either through the “top” or “bottom” of the furnace.
DRAIN PAN
A drain pan must be provided if the furnace is installed above a conditioned area. The drain pan must cover the entire area under the furnace (and air conditioning coil if applicable).
FREEZE PROTECTION
Refer to Horizontal Applications and Conditions - Drain Trap and Lines.
Propane Gas/High Altitude Installations
WARNING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION QUALIFIED INSTALLER OR SERVICE AGENCY
. ALL
CONVERSIONS MUST BE PERFORMED BY A
.
. THE
Recommended Installation Positions
NOTE: Alternate “vertical” piping connections can not be used
when an upflow furnace is installed with supply air discharging to the right, or when a counterflow furnace is installed with supply air discharging to the left. In either case, use the standard flue and combustion air piping connections.
This furnace is shipped from the factory configured for natural gas up to 10,000 ft. altitude. Propane conversions require the proper LP kit to compensate for the energy content differ­ence between natural and propane gas.
LP kits include a manifold assembly, including an LP gas valve, orifices and LP burners.
Gas
Altitude Kit
Natural None
Propane LPKMOD** ***
NOTE:
Exc ept 115,000 BTU: #43
2
Exc ept 115,000 BTU: #55
0-7 000
In Canada , gas fur nace s ar e onl y c ertified to 4500 feet.
Orifice
#45
1.25MM
1
Manifold Pressure
High Stage Low Stage
3.5" w .c. 1" w.c. None
2
10.0" w. c. 2. 6" w.c. None
Pressure
Switch
Change
Fur nace Model LP Kit
A/GMVM960603BX A/GMVM960805CX A/GMVM961005DX
A/GMVM961155DX
LPKMOD060UF LPKMOD080UF LPKMOD100UF
LPKMOD115UF
A/GCVM960604CX LPKMOD060CF A/GCVM960805DX LPKMOD080CF
A/GCVM961005DX LPKMOD100CF
The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified in­staller, or service agency.
20
Page 21
PRODUCT DESIGN
Vent/Flue Pipe & Combustion Air Pipe
WARNING
F
AILURE TO FOLLOW THESE INSTRUCTIO N S CAN RESU LT IN BODILY INJURY OR DEATH GIVEN IN THIS SECTION
. C
AREFULLY READ AND FOLLOW ALL INSTRUCTIONS
.
WARNING
U
PON COMPLETION OF THE FURNACE INSTALLATION, CAREFULLY INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF THE FURNACE TO ASSURE IT IS PROPERLY SEALED SYSTEM CAN RESU LT IN SERIOUS PERSONAL INJURY OR DEATH DUE TO EXPOSURE TO FLUE PRODUCTS, INCLUDING CARBON MONOXIDE
. L
EAKS IN THE FLUE
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensation takes place. Because of the relatively low flue gas temperature and water con­densation requirements, PVC pipe is used as venting material.
This furnace must not be connected to Type B, BW, or L vent or vent connector, and must not be vented into any portion of a factory built or masonry chimney except when used as a path­way for PVC as described later in this section. Never common vent this appliance with another appliance or use a vent which is used by a solid fuel appliance. Do not use commercially avail­able “no hub connectors” other than those shipped with this prod­uct.
It is the responsibility of the installer to follow the manufacturers’ recommendations and to verify that all vent/flue piping and con­nectors are compatible with furnace flue products. Additionally, it is the responsibility of the installer to ensure that all piping and connections possess adequate structural integrity and support to prevent flue pipe separation, shifting, or sagging during furnace operation.
DUAL CERTIFICATION: NON-DIRECT/DIRECT VENT
This furnace is dual certified and may be installed as a non-direct vent (single pipe) or direct vent (dual pipe) appliance. A non-direct vent installation requires only a vent/flue pipe, while a direct vent installation requires both a vent/flue pipe and a combustion air intake pipe. Refer to the appropriate section for details concern­ing piping size, length, number of elbows, furnace connections, and terminations.
.
used. Fittings must be DWV type fittings meeting ASTM D2665 and ASTM D3311. Carefully follow the pipe manufacturer’s in­structions for cutting, cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC or ABS cellular core (Foam Core) plastic pipe is also acceptable as a flue/vent and intake pipe material. PVC primer meeting ASTM F656 and PVC solvent ce­ment meeting ASTM D2564 specifications must be used. Fit­tings must be DWV type fittings meeting ASTM D2665 and ASTM D3311. Carefully follow the manufactures instructions for cutting, cleaning and solvent cementing of PVC.
MATERIALS AND JOINING METHODS
As an alternative to PVC pipe, primer, solvent cement, and fit­tings, ABS materials which are in compliance with the following specifications may be used. Two-or-three-inch ABS Schedule 40 pipe must meet ASTM D1527 and, if used in Canada, must be CSA listed. Solvent cement for ABS to ABS joints must meet ASTM D2235 and, if used in Canada, must be CSA listed. The solvent cement for the PVC to ABS transition joint must meet ASTM D3138. Fittings must be DWV type fittings meeting ASTM D2661 and ASTM D3311 and, if used in Canada, must be CSA listed. Carefully follow the manufacturers’ instructions for cutting, cleaning, and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/ 16” minimum from the plane of one opening to the centerline of the other opening for 2” diameter pipe, and 4 9/16” minimum for 3” pipe.
PROPER VENT/FLUE AND COMBUSTION AIR PIPING PRACTICES
Adhere to these instructions to ensure safe and proper furnace performance. The length, diameter, and number of elbows of the vent/flue pipe and combustion air pipe (when applicable) affects the performance of the furnace and must be carefully sized. All piping must be installed in accordance with local codes and these instructions.
Piping must be adequately secured and supported to prohibit sagging, joint separation, and/or detachment from the furnace. Horizontal runs of vent/flue piping must be supported every three to five feet and must maintain a 1/4 inch per foot downward slope, back towards the furnace, to properly return condensate to the furnace’s drain system.
PREFERRED
WARNING
TO
AVOID BODILY INJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS MUST BE KEPT AWAY FROM ALL IGNITION SOURCES (I.E FLAMES, AND EXCESSIVE HEAT) AS THEY ARE COMBUSTIBLE LIQUIDS
VOID BREATHING CEMENT VAPO RS OR CONTA CT WITH SKIN AND/OR
A
EYES
.
Two- or three-inch nominal diameter PVC Schedule 40 pipe meet­ing ASTM D1785, PVC primer meeting ASTM F656, and PVC solvent cement meeting ASTM D2564 specifications must be
.,
SPARKS, OPEN
.
21
Page 22
PRODUCT DESIGN
ACCEPT ABLE
TRANSITION NO LESS THAN 45 DEGREES TO HORIZONTA L P LANE T O AVOID CREATING A WATER TRAP IN VENT PIPING.
NO TRANSITION ON HORIZONTAL PLANE, THIS CREATES A WATER TRAP AND RESTRICTS FLUE GASES
Precautions should be taken to prevent condensate from freezing inside the vent/flue pipe and/or at the vent/flue pipe termination. All vent/flue piping exposed to temperatures below 35°F (2°C) for extended periods of time must be insulated with 1/2” thick closed cell foam. Also all vent/flue piping exposed outdoors in excess of the terminations shown in this manual (or in unheated areas) must be insulated with 1/2” thick closed cell foam. In­spect piping for leaks prior to installing insulation.
TERMINATION LOCATIONS
NOTE: Refer to Location Requirements and Considerations for
combustion air contaminant restrictions. The following bullets and diagram describe the restrictions con-
cerning the appropriate location of vent/flue pipe and combustion air intake pipe (when applicable) terminations. Refer to Non-Di- rect Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping located in this section for specific details on termination con­struction.
All terminations (flue and/or intake) must be located at least 12 inches above ground level or the anticipated snow level.
Vent terminations (non-direct and direct vent) must termi­nate at least 3 feet above any forced air inlet located within 10 feet.
NOTE: This provision does not apply to the combustion air intake termination of a direct vent application.
The vent termination of a non-direct vent application must terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window, or gravity air inlet into any building.
The vent termination of a direct vent application must ter­minate at least 12 inches from any opening through which flue gases may enter a building (door, window, or gravity air inlet).
The vent termination of vent pipe run vertically through a roof must terminate at least 12 inches above the roof line (or the anticipated snow level) and be at least 12 inches from any vertical wall (including any anticipated snow build up).
A vent termination shall not terminate over public walk­ways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent ap­plication should not terminate in an area which is frequently dusty or dirty.
Non-Direct Vent
&
Direct Vent
Vent/ F lue Terminations
Non-Direct Vent
Vent/Flue Termination
No Terminations Above Walkway
4' min.
4'
min.
Grade or Highest
Anticipated Snow Level
Forced Air
Inlet
12" min.
Vent /F lue Termi nation
Direct Vent
12" min.
Non-Direct Vent
Vent/ F lue Termin at ion
Vent Termination Clearances
NOTE: In Canada, the CAN/CSA B149 Gas Installation Code
takes precedence over the preceding termination restrictions.
22
Page 23
PRODUCT DESIGN
V X
v
DIRECT VENT TERMINAL CLEARANCES
A= Clearance above grade,
veranda, porch, deck o r balcony. (See 1.24.6-i(9)b.)
B= Clearanc e to window or
door that may be opened.
C= Clearance to permanently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal.
E= Clearance to unventilated soffit. * * F= Clearance to outside corner. * * G= Clearance to inside corner. * * H= Clearance to each side of center
line extended above meter/regulator assembly.
Canadian Installations
12 in. (30 cm) 12 in. (30 cm)
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
**
**
3 ft. (91 cm) within a height 15 ft. (4.5 m) above the meter/regulator assembly .
1
OTHER THAN DIRECT VENT TERMINAL CLEARANCES
A= C leara nce a bove grade,
veranda, porch, deck or balcony. (See 1.24.6-i(9)b.)
B= C leara nce to wind ow or
door that may be opened.
C= Clearance to per man ently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal.
E= C leara nce to unv ent ilated soffit. * * F= Clearance to outside corner. * * G= Clearance to inside corner. * * H= Clearance to eac h side of center
line extend ed above meter/regul ator assembly.
Canadian Installations
12 in. (30 cm) 12 in. (30 cm)
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for applia nces > 100,000 Btuh (30 kW).
**
**
3 ft. (91 cm) within a height 15 ft. (4.5 m) above the meter/regulator assembly.
1
U.S. Installations
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 9 in. (23 cm) for appliances > 10,000 Btuh (3 kW) and 50,000 Btuh (15 kW), 12 i n. (30 cm) for appliances > 500,000 Btuh (15 kW).
*
U.S. Installati ons
4 ft. (1.2 m) below or to side of opening; 1 ft. (300 m) above opening.
*
2
2
I= Clearance to service
regulator vent outlet.
J= Clearance to nonmech ani cal air
supply inlet to building or the combustion air inlet to any other appliance.
K= Clearance to a mechanical
air supply inlet.
L= Clearance above paved sidew al k or
paved driveway located on public property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single fanily dwellings and serves
both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
I= Clearance to sevice
regulator vent outlet.
J= Cl earance to nonmechanica l ai r
supply inlet to building or the combustion air inlet to any other appliance.
K= Clearance to a mechanical
air supply inlet.
L= Clearance above paved sidewalk or
paved driveway located on public property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paveable driveway that is located between two single family dwellings and
serves both dwelling.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
Canadian Installations
3 ft. (91 cm). *
6 in. (15 cm) for appliance s 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,0 00 Btu h (3k W) an d 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m) 3 ft. (91 cm) above if within
7 ft. (2.13m) † *
12 in. (30 cm) ‡ *
Canadian Installations
3 ft. (91 cm). *
6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m) 3 ft. (91 cm) above if within
7 ft. (2.13m) † 7 ft. (2.13m)
12 in. (30 cm) ‡ *
1
1
U.S. Installations
6 in. (15 cm) for appliances 10,00 0 Btuh (3 kW), 9 in. (23 cm) fo r appliances > 10,000 Btuh (3kW) and 50,000 Btuh (15 kW), 12 in. (30 cm) for appliances > 50,000 Btuh (15 kW ).
10 ft. (3 m) horizontally.
U.S. Installations
4 ft. (1.2 m) below or to side of opening; 1 ft. (300 m) above opening.
10 ft. (3 m) horizontally.
2
2
23
Page 24
PRODUCT DESIGN
SPECIAL VENTING REQUIREMENTS FOR INSTALLATIONS IN CANADA
All installations in Canada must conform to the requirements of CSAB149 code. All vent system components, including primer and cement, must be listed to ULC S636. The certi­fied pipe and fittings should be clearly marked with the ULC standard “S636”. The primer and cement used must be of the same manufacturer as the vent system. For Royal Pipe Sys­tem 636; use GVS-65 Primer (Purple) and GVS-65 PVC Solvent Cement. For IPEX System 636, use PVC/CPVC Primer, Purple or clear. Use PVC Solvent Cement (Gray).
For Canadian installations, ABS may be used as a combus­tion air pipe only. ABS is not an approved vent material in Canada. If ABS is used as a combustion air pipe, it must be CSA certified. Always follow the manufacturer’s instructions in the use of primer and cement. Do not use primer and ce­ment around potential sources of ignition. Do not use primer or cement beyond its expiration date.
The vent can be run through an existing unused chimney provided the space between the vent pipe and the chimney is insulated and closed with a weather-t
ight, corrosion-resistant
flashing.
STANDARD FURNACE CONNECTIONS
It is the responsibility of the installer to ensure that the piping connections to the furnace are secure, airtight, and adequately supported.
As shipped, attachment “couplings” for vent/flue and combustion air intake pipe connections are provided on the furnace’s top cover (upflow) or basepan (counterflow). To use the standard connec­tions, field supplied vent/flue pipe and combustion air intake pipe (when applicable) should be secured directly to the furnace at these locations.
VENT/FLUE PIPE
Vent/flue pipe can be secured to the vent/flue coupling using the rubber coupling and worm gear hose clamps provided with this furnace (see “Standard Connections” figure). The rubber coupling allows separation of the vent/flue pipe from the furnace during servicing. Combustion Air and Vent piping should be routed in a manner to avoid contact with refrigerant lines, metering devices, condensate drain lines, etc.
COMBUSTION AIR PIPE
DIRECT VENT INSTALLATIONS
On upflow units secure the combustion air intake pipe directly to the air intake coupling. On counterflow units secure the com­bustion air intake pipe to the air intake coupling using the rubber coupling and worm gear hose clamps provided with the unit. The counterflow rubber coupling allows service removal of air intake piping internal to the furnace blower compartment.
ON-DIRECT VENT INSTALLATIONS
N
A minimum of one 90° elbow should be installed on the combus­tion air intake “coupling” to guard against inadvertent blockage.
(DIRECT VENT ONLY)
90 PVC
ELBOW
(NON-DIRECT VENT)
COMBUSTION
AIR PIPE
OR
VENT/FLUE
PIPE
RUBBER
COUPLING
WITH WORM
GEAR CLAMPS
UPFLOW COUNTERFLOW
90 PVC ELBOW
(NON-DIRECT VENT)
COMBUSTION
AIR PIPE
(DIR EC T VENT ONLY)
OR
RUBBER COUPLINGS WITH WORM
GEAR CLAMPS
VENT/FLUE
PIPE
Standard Connections
WARNING
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
.
. USE
GLOVES AS A
ALTERNATE VENT/FLUE LOCATION
The alternate vent/flue location is the large hole directly in line with the induced draft blower outlet. To use the alternate vent/flue location refer to the following steps and the “Alternate Vent/Flue Location” figure.
NOTE: Counterflow instructions follow the upflow instructions.
1. Remove and save the four screws securing the vent/ flue coupling to the furnace top panel.
Counterflow units.
Remove and save the four screws securing the vent/ flue coupling to the furnace basepan. Also remove the three screws securing the furnace’s internal vent/flue piping to the blower deck.
24
Page 25
PRODUCT DESIGN
2. Upflow and Counterflow units. Loosen the worm gear hose clamps on the rubber el-
bow and detach it from both the induced draft blower and the vent/flue pipe.
3. Upflow and Counterflow units. Remove the vent/flue pipe from the furnace.
4. Cut the vent/flue pipe 3.75 inches from the flanged end of the pipe (see “Vent/Flue Pipe Cut s” figure). The sec­tion of pipe attached to the coupling will reach through the side panel to the induced draft blower . Discard re­maining pipe and elbows.
Counterflow units.
Cut the vent/flue pipe 3.75 inches from the blower deck cou­pling (see “Vent/Flue Pipe Cuts” figure). Save vent/flue pipe attached to blower deck coupling for use in the alternate lo­cation. Discard remaining pipe and elbows.
FLANGE
3.75"
CUT HERE
Counterflow units. Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location (basepan). Plug remaining hole in blower deck with plastic plug included in the drain kit bag.
6. Upflow and Counterflow units. Insert cut section of vent/flue pipe and coupling into al-
ternate vent/flue location. Using a rubber coupling and worm gear hose clamps from the drain kit bag, attach the vent/flue pipe and coupling to the induced draft blower. Secure the coupling to the cabinet using the screws removed in step 1 or with field-supplied 3/8” #8 self tapping screws.
WARNING
THE
RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABIN E T EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD SUPPLIED VENT/FLUE PIPING, AS DAMAGE CAN RESU LT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE
. W
HEN THE
-
,
,
Vent/Flue Pipe Cuts
5. Remove plastic plug from alternate vent/flue location. Relocate and install plug in standard vent/flue location (top cover).
25
Page 26
PRODUCT DESIGN
A
A
A
A
3
REMOVE
PIPE
4
REMOVE
AND RELOCATE
CABINET PLUG
2
DETACH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
5
5
EXTERNALLY
EXTERNALLY
MOUNT
MOUNT
RUBBER ELBOW
RUBBER ELBOW
ND SECURE FLANG E
ND SECURE FLANG E
WITH 4 SC REWS
WITH 4 SC REWS
REMOVED IN STEP 1
REMOVED IN STEP 1
3
REMOVE
PIPE
INSTALL CABINET PLUGS
IN 2 LOCAT IONS
2
REMOVE
3 SCREWS
4
DETATCH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
RUBBER ELBOW
ND SECURE FLANG E
WITH 4 SC REWS
REMOVED IN STEP 1
ID BLOWER WITH
RUBBER COUPL IN G
COUNTERFLOW-HORIZONTAL MODEL ALTERNATE VENT
TO USE ALTERNATE COMBUSTION
IR LOCATION, REMOVE INTERNAL PIPE AS PER ABOVE. CAP UNUSED CABINET OPENINGS
CABINET WITH
5
7
EXTERNALLY
MOUNT
6
SECURE TO
AND HOSE
CLAMPS
SECURE TO
SCREWS
ALTER NATE COMBUSTION AIR LOCATION ON C’FLOW -HOR MODELS
COUNTERFLOW-HORIZONTAL MODEL
AL TERNATE COMBUSTION AIR LOCATION
26
Page 27
PRODUCT DESIGN
7. Upflow and Counterflow units. For upright installations, externally mount the rubber
elbow to the vent/flue coupling using a worm gear hose clamp. Secure field supplied vent/flue piping to the rubber elbow using a worm gear hose clamp. NOTE: Use of the alternate vent/flue location for upright instal­lations, requires the drain trap be installed on the same side of the unit as the flue pipe.
8. Upflow and Counterflow units. For horizontal installations, externally secure the
field-supplied vent/flue pipe directly to the vent/flue cou­pling using a PVC or ABS coupling or elbow .
ALTERNATE COMBUSTION AIR INTAKE LOCATION
The alternate combustion air intake location consists of a large, unobstructed hole (alternate vent connection is aligned with the Induced Draft Blower). To use the alternate combustion air intake location, refer to the following steps, and the “Alternate Combus­tion Air Intake Location” figure.
1. Remove and save the four screws securing the com­bustion air intake coupling to the basepan. Remove an additional three screws securing the furnace’s internal combustion air intake pipe to the blower deck.
2. Remove the combustion air intake pipe from the fur­nace and cut the pipe at the basepan coupling. Save the basepan coupling and gasket from the blower deck coupling for use in the alternate location. Discard the remaining pipe.
3. Remove plastic plug from alternate combustion air in­take location. Relocate and install plug in standard air intake location (basepan). Plug the remaining hole in the blower deck with the plastic plug included in the drain kit bag.
4. With the gasket facing the cabinet side panel, and the flange’s flat spot facing forward, secure the combustion air intake coupling to the cabinet using the screws re­moved in step 1 or with field-supplied 3/8” #8 self -drill­ing screws.
CAUTION
BE
SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS
WHEN REIN STALLING COUPLING AND SCREWS
.
5. For non-direct vent installations installed horizon- tally, a minimum of one 90° elbow should be installed
on the combustion air intake coupling to guard against inadvertent blockage. No elbow is required on the al­ternate combustion air intake of upright installations, however, a minimum clearance of 2 inches is required to assure proper air supply .
6. For direct vent installations , secure field-supplied combustion air intake pipe directly to the air intake coupling.
NOTE: A PVC coupling or elbow is required on counterflow units.
NON-DIRECT VENT (SINGLE PIPE) PIPING
Non-direct vent installations require only a vent/flue pipe. The vent pipe can be run horizontally with an exit through the side of the building or run vertically with an exit through the roof of the building. The vent can also be run through an existing unused chimney; however, it must extend a minimum of 12 inches above the top of the chimney. The space between the vent pipe and the chimney must be closed with a weather-tight, corrosion-resistant flashing. For details concerning connection of the vent/flue pipe to the furnace, refer to Vent/Flue Pipe and Combustion Air - Stan- dard Furnace Connections or Alternate Furnace Connections for specific details. Refer to the following Non-Direct Vent (Single Pipe) Piping - Vent/Flue Pipe Terminations for specific details on termination construction.
Although non-direct vent installations do not require a combus- tion air intake pipe, a minimum of one 90° elbow should be at­tached to the furnace’s combustion air intake if: an upright instal­lation uses the standard intake location, or a horizontal installa­tion uses the alternate air intake location. This elbow will guard against inadvertent blockage of the air intake.
VENT/FLUE PIPE LENGTHS AND DIAMETERS
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue pipe system of a non­direct vent installation. In addition to the vent/flue pipe, a single 90° elbow should be secured to the combustion air intake to prevent inadvertent blockage. The tee used in the vent/flue termi­nation must be included when determining the number of elbows in the piping system.
*MVM 9/*CVM9 Di r ec t Vent (2 - Pipe) and No n-Direct Vent (1- Pipe)
Maxim um Allowable Length of Vent/Flue Pipe & Combustio n A ir Pipe (ft)
Unit Input
100,000 100,000 3 250 243 236 229 222 215 208 201 194 115,000 115,000 3 220 213 206 199 192 185 178 171 164
1) Maximum allowable limits listed on individual lengths for inlet and flue
2) Minimum requirement for each vent pipe is five (5) feet in length and
3) Tee used in the vent/flue termination must be included when deter-
4) 2 1/2” or 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Elbows should
6) One 90° elbow should be secured to the combustion air intake con-
Pipe Size
(4)
(Btu)
60,000
80,000 80,000 3 250 243 236 229 222 215 208 201 194
or 2 1/2
or 2 1/2
or 2 1/2
or 2 1/2
and NOT a combination.
one elbow/tee.
mining the number of elbows in the piping system.
be considered equivalent to one 90 deg. elbow.
nection.
012345678
(in.)
2
250 245 240 235 230 225 220 215 210
2
250 245 240 235 230 225 220 215 210
2
90 85 80 75 70 65 60 55 50
2
75 70 65 60 55 50 45 40 35
Num ber of El bows
(3) (5)
(6)
(1 ) (2 )
27
Page 28
PRODUCT DESIGN
VENT/FLUE PIPE TERMINATIONS
NOTE: If either a 90 degree or 45 degree elbow is used for
termination, it must be pointed downward. The vent/flue pipe may terminate vertically, as through a roof, or
horizontally, as through an outside wall. Vertical vent/flue pipe terminations should be as shown in the
following figure. Refer to Vent/Flue Pipe and Combustion Air Pipe - Termination Locations for details concerning location re­strictions. The penetration of the vent through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent.
Horizontal vent/flue pipe terminations should be as shown in the following figure. Refer to Vent/Flue Pipe and Combustion Air Pipe
- Termination Locations for details concerning location restric­tions. A 2 3/8” diameter wall penetration is required for 2” diam­eter pipe. A 3” diameter hole is required for a 2 1/2” pipe and a 3 1/2” diameter hole is required for 3” diameter pipe. The wall penetration should be sealed with silicone caulking material.
In a basement installation, the vent/flue pipe can be run between joist spaces. If the vent pipe must go below a joist and then up into the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows.
NOTE: Terminate both pipes in the same pressure zone (same side of roof, no major obstacles between pipes, etc.).
TEE (OPTIONAL)
COMBUSTION AIR INT AKE
(OPTIONAL)
*Not required for
single pipe installation
E
N
I
L
F
O
O
R
INTAKE
SCREEN
OPTIONAL
12” MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL
6
9
12” MIN HEIGHT DIFFERENCE BETWEEN INT A KE AN D VENT
M
3
-
.
X
A
M
.
N
I
12" MIN.
VENT/FLUE TEE (
TURNED DOWN or
90° ELBOW TUR NED
12" MIN. ABOVE
HIGHEST ANTI CIP A T ED
SNOW LEVEL
OPTIONAL)
or
45° E L B OW
DOWN
Horizontal Termination (Single Pipe)
Above Highest Anticipated Snow Level
DIRECT VENT (DUAL PIPE) PIPING
The inlet air screens provided in the installation instruction packet are available for the installer to use in the inlet of the combustion air pipe to prevent animals from building nests in the combustion air pipe. Installation of screens, while strongly recommended, is not required and will not affect performance of the unit.
Direct vent installations require both a combustion air intake and a vent/flue pipe. The pipes may be run horizontally and exit through the side of the building or run vertically and exit through the roof of the building. The pipes may be run through an existing unused chimney; however, they must extend a minimum of 12 inches above the top of the chimney. The space between the pipes and the chimney must be closed with a weather tight, corrosion resis­tant flashing. Both the combustion air intake and a vent/flue pipe terminations must be in the same atmospheric pressure zone. Refer to Vent/Flue and Combustion Air Pipe - Termination Loca- tions or Concentric Vent Termination for specific details on termi- nation construction. For details concerning connection of pipes to the furnace, refer to the Vent/Flue Pipe and Combustion Pipe
- Standard Furnace Connections or Alternate Furnace Connec­tions.
ELBOWS
STRAIGHT
28
VENT/FLUE & COMBUSTION AIR PIPE LENGTHS &DIAMETERS
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue and combustion air in­take pipe systems of a direct vent (dual pipe) installation. The number of elbows tabulated represents the number of elbows and/or tees in each (Vent/Flue & Combustion Air Intake) pipe. If there is a difference between the two pipes, count the pipe with the most fittings. Elbows and/or tees used in the termina­tions must be included when determining the number of elbows in the piping systems.
Page 29
V
V
PRODUCT DESIGN
If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objec­tionable, insulation of the combustion air pipe may be required. Use 1/2” thick closed cell foam insulation such as Armaflex™ or Insultube™ where required.
VENT/FLUE AND COMBUSTION AIR PIPE TERMINATIONS
The vent/flue and combustion air pipes may terminate vertically, as through a roof, or horizontally, as through an outside wall.
Vertical pipe terminations should be as shown in the following figure. Refer to Vent/Flue Pipe and Combustion Pipe - Termina- tion Locations for details concerning location restrictions. The penetrations through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent.
ENT/FLUE
12" MIN.
SCREEN
(OPTIONAL)
10”- 24”
6” MAX
4” MIN
90º OR 45°
ELBOW
SCREEN
(OPTIONAL)
12" MIN. TO GRADE OR HIGHEST ANTICIPATED
SNOW LEVEL
Standard Horizontal Terminations (Dual Pipe)
Vent & Combustion Air Intake Measurements for Stan­dard Horizontal Terminations (Dual Pipe)
Center to center = 10” min / 24” max. Vertical separation: 0” - 24” Vent termination from wall = 8” min / 12” max. Combustion air intake from wall = 6” max. Vent and intake clearance to ground
or anticipated snow level = 12” min.
_____________________________________
12" MIN. TO ROOF
OR HIGHEST ANTICIPAT ED
SNOW LEVEL
_____________________________________
TEE (OPTION AL)
ENT/FLUE
COMBUSTION
AIR INTAKE
12" MIN.
SCREEN
(OPTIONAL)
12" MIN. TO ROOF
OR HIGHEST ANTICIPATED
SNOW LEVEL
Vertical Terminations (Dual Pipe)
Horizontal terminations should be as shown in the following fig­ure. Refer to Vent/Flue Pipe and Combustion Pipe - Termination Location for location restrictions. A 2 3/8” diameter wall penetra­tion is required for 2” diameter pipe. A 3” diameter hole is required for a 2 1/2” pipe and a 3 1/2” diameter hole is required for 3” diameter pipe. The wall penetration should be sealed with caulk­ing material.
90° ELBOWS
3” - 24”
AIR INTAKE
SCREEN
(OPTIONAL)
12" MIN. ABOVE
HIGHEST ANTICIPAT ED
SNOW LEVEL
Alternate Horizontal Vent Termination (Dual Pipe)
29
Page 30
PRODUCT DESIGN
90° ELBOWS
AIR INTAKE
SCREEN
(OPTIONAL )
3”-24” BETWEEN PIPES
3” MIN
3”MIN 24”MAX
12” MIN SEPARATION
12" MIN. ABOVE
HIGHEST ANTICIPA TED
SNOW LEVEL
Combustion Air Intake may also be snorkeled to obtain 12” min ground clearance.
Alternate Vent Termination Above Anticipated Snow
Level (Dual Pipe)
In a basement installation, the pipes may be run between the joist spaces. If the pipes must go below the joist and then up into the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows.
VENT/INTAKE TERMINATIONS FOR INSTALLATION OF M ULTIPLE DIRECT VENT FURNACES
If more than one direct vent furnace is to be installed vertically through a common roof top, maintain the same minimum clear­ances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit.
If more than one direct vent furnace is to be installed horizontally through a common side wall, maintain the clearances as in the following figure. Always terminate all exhaust vent outlets at the same elevation and always terminate all air intakes at the same elevation.
OPTIONAL INTAKE SCREENS
12” MIN TO GRADE OR HIGHEST ANTICIPATED SNOW LEVEL
Termination of Multiple Direct Vent Furnaces
CONCENTRIC VENT TERMINATION
Refer to the directions provided with the Concentric Vent Kit (DCVK) for installation specifications.
30
Page 31
PRODUCT DESIGN
Condensate Drain Lines & Drain Trap
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensation takes place. The condensate which is generated must be piped to an appro­priate drain location.
In upright installations, the furnace’s drain hoses may exit either the right or left side of the furnace. NOTE: If the alternate vent/flue outlet is utilized in an upright installation, the drain trap and drain connections must be located on the same side as the alternate vent/flue outlet.
In horizontal installations, the drain hoses will exit through the bottom (down side) of the unit with the drain trap suspended be­neath the furnace. The field-supplied drain system must be in accordance with all local codes and the instructions in the follow­ing sections.
Follow the bullets listed below when installing the drain system. Refer to the following sections for specific details concerning fur­nace drain trap installation and drain hose hook ups.
The drain trap supplied with the furnace must be used.
The drain line between furnace and drain location must be constructed of 3/4” PVC.
The drain line between furnace and drain location must maintain a 1/4 inch per foot downward slope toward the drain.
Do not trap the drain line in any other location than at the drain trap supplied with the furnace.
Do not route the drain line outside where it may freeze.
If the drain line is routed through an area which may see temperatures near or below freezing, precautions must be taken to prevent condensate from freezing within the drain line.
If an air conditioning coil is installed with the furnace, a common drain may be used. An open tee must be installed in the drain line, near the cooling coil, to relieve positive air pressure from the coil’s plenum. This is necessary to prohibit any interference with the function of the furnace’s drain trap.
NOTE: In vertical installations, air conditioning coil condensate may drain into the furnace trap as long as there is a trap between the coil and the furnace trap and the drain pipe is not terminating below the water level of the furnace trap.
STANDARD RIGHT OR LEFT SIDE DRAIN HOSE CONNECTIONS
All installations positions require the use of the drain trap, hoses, tubes, and clamps. The following quantity of hoses, tubes, and hose clamps are provided with the unit.
HOSE A QTY: 1
HOSE B QTY: 1
DRAIN TRAP QTY: 1
GREEN HOSE CLAMPS QTY: 3
RED HOSE CLAMP QTY: 1
Hose and Tube Identification
TUBE 1 QTY: 1
SILVER HOSE CLAMP QTY: 1
TUBE 2 QTY: 2
31
Page 32
OPERATION
UPRIGHT INSTALLATIONS-TRAP ON RIGHT SIDE
In a upright installation drain hoses are connected to drain ports on the rubber elbow and the recuperator coil front cover. The drain lines are then routed through the right side panel and into the drain trap secured to the outside of the cabinet.
NOTE: Refer to Alternate Vent/Flue Hose Connections for up- right installations using an alternate vent/flue outlet.
1. Remove the rubber plug from the right side of the front cover drain port.
2. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear side panel grommet hole.
3. Cut and remove 1/4 inch from the end of the drain port on the rubber elbow.
RUBBER ELBOW
(EXTERNALLY
MOUNTED)
4. Insert Tube 1 into rubber elbow drain port and secure with silver hose clamp. Angle tube outward toward front of furnace.
5. Cut 17 3/4 inches from the long end of Hose B and dis­card. Secure the remaining hose to Tube 1 with a green hose clamp. Route the other end of Hose B to front right side panel grommet hole.
For details concerning mounting of the drain trap, refer to Hori-
zontal Drain Trap Mounting.
6. Insert short end of each of tube 2 through side panel grommet holes. Secure tubes to hoses A and B with green hose clamps. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
FRONT
COVER
DRAIN
PORT
RED HOSE
CLAMP
RUBBER
ELBOW
DRAIN PORT
HOSE B
SILVER HOSE CLAMP
TUBE 1
GREEN HOSE
CLAMPS
(3 PLACE S)
HOSE A
DRAIN TRAP
TUBE(S) 2
Upright “Standard” Connections - Right Side
(Upflow Shown, Counterflow Similar)
32
Page 33
OPERATION
ALTERNATE VENT/FLUE DRAIN HOSE CONNECTIONS
Upright installations using the alternate vent/flue outlet will require “right-side only” drain hoses to be connected as follows. Refer to Vent/Flue Pipe and Combustion Air Pipe for details on alternate vent/flue pipe connection.
1. Remove the rubber plug/cap from the right-side drain port on the front cover . Save for use in step 3.
2. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear right side panel grommet hole.
3. Remove grommet from front right-side panel drain hole. Seal hole in grommet with large end of plug. Reinstall grommet and plug into side panel drain hole.
4. Cut 1/4 inch from the end of the drain port on the exter­nally mounted rubber elbow. Discard cut portion.
5. Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp. Angle tube toward trap.
6. Cut 17 3/4 inches from the long end of Hose B and dis­card.
7. Secure straight end of Hose B to exposed end of Tube 1 with a green hose clamp. Route hose toward right side panel grommet holes.
8. Insert short end of one Tube 2 through rear right side panel grommet drain hole. Secure tube to Hose A with a green hose clamp.
9. Insert short end of remaining Tube 2 into Hose B from rubber elbow and secure with green hose clamp. En­sure hoses and tubes maintain a downward slope for proper drainage and are not kinked or binding.
FRONT
COVER
DRAIN PORT
HOSE
RED HOSE
CLAMP
HOSE
A
GREEN
HOSE
CLAMPS
(3 PLACES)
Upright “Alternate” Connections - Right Side Only
(Upflow Shown, Counterflow Similar)
RIGHT SIDE
PANEL
RUBBER
ELBOW
RUBB ER EL B O W
DRAIN PORT
SILVER HOSE CLAMP
TUBE 1
B
SIDE PANEL
GROMMET
HOLES
TUBE(S) 2
DRAIN TRAP
33
Page 34
80 5
OPERATION
UPRIGHT INSTALLATIONS-TRAP ON LEFT SIDE
NOTE: For left side trap installation, grommets must be moved
to the left side of the furnace and the plugs installed on the right side of the furnace.
1. Remove the rubber plug/cap from the left side drain port on the front cover.
2. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear side panel grommet hole.
3. Cut and remove 1/4 inch from the end of the drain port on the rubber elbow.
4. Insert Tube 1 into rubber elbow drain port and secure with silver hose clamp. Angle tube outward toward front of furnace.
LEFT
SIDE PANEL
FRONT COVER
DRAIN PORT
RED HOSE
CLAMP
HOSE A
5. Cut “X” inches from the long end of Hose B and dis­card. Refer to table for appropriate length to cut. Se­cure remaining hose to Tube 1 with a green hose clamp. Route other end of Hose B to front left side panel grommet hole.
NOTE: Long hose “B” must always be connected to Tube 1 and the elbow and not on the front cover.
6. Insert short end of each Tube 2 through side panel grommet holes. Secure tubes to Hose A and Hose B with green hose clamps. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
RUBBER
ELBOW
RUBBER
ELBOW
DRAIN PORT
SIDE PANEL
DRAIN
HOLES
TUBE(S) 2
DRAIN
TRAP
Cabinet Width
(inches)
17 1/2 60_3 7
21
Models
(kBTU_Tons)
60_4
80_5 100_ 5 115_ 5
"X" Length to Cut F r om Long
GREEN
HOSE B
HOSE CLAMP
Upright “Standard” Connections - Left Side
(Upflow Shown, Counterflow Similar)
End of Ho se B
(inches)
3 1/2
None24 1/2
2. Secure drain trap to side panel at the mounting holes (dimples or crosshairs on counterflow models) located below the grommet drain holes.
3. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
SILVER HOSE
CLAMP
TUBE 1
GREEN HOSE
CLAMP
UPRIGHT DRAIN TRAP MOUNTING (LEFT OR RIGHT SIDE PANEL)
1. Insert drain tubes into drain trap and position the drain trap against the side panel. NOTE: Drain tubes must reach the bottom of the drain trap.
34
Page 35
OPERATION
HORIZONTAL INSTALLATIONS RIGHT SIDE DOWN
Horizontal installations with the right side down require that the drain hoses be connected to the right side front cover drain port and the rubber elbow drain port.
NOTE: On counterflow models, relocation of the front cover pressure switch hose is required.
Make connections as follows:
1. Remove the rubber plug/cap from right side of the front cover drain port.
Counterflow furnaces
Relocate the front cover pressure switch hose connec­tion from the left side pressure tap to the right (down) side tap. The pressure switch hose must be connected to the down side to guard against blocked drain condi­tions. Cut hose to appropriate length to minimize sag­ging. Plug left (unused) pressure tap with plug removed from right side.
2. Secure Hose A to front cover drain tap with a red hose clamp. Route hose to rear right (down) side panel grom­met holes.
3. Cut 1/4 inch from the end of the drain port on the rubber elbow and discard.
4. Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp. Angle tube outward toward front of furnace.
5. Cut 17 3/4 inches from the long end of Hose B and dis­card.
6. Secure remaining end of Hose B to exposed end of Tube 1 with a green hose clamp. Route hose to front right down side panel grommet holes.
7. Cut 5 1/2 inches straight length from the long end of each Tube 2 and discard the radius pieces.
8. Insert approximately one inch of each Tube 2 through the right down side panel grommet holes. Secure tubes to Hose A and Hose B using green hose clamps. En­sure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound.
For details concerning mounting of the drain trap, refer to Con-
densate Drain Lines and Drain Trap - Horizontal Drain Trap Mount­ing.
FRO NT COVER DRAIN PORT
RED HOSE
CLAMP
HOSE A
HOSE B
TUBES 2
DRAIN TRAP
Allow 4-3 /4”
minimum
for trap
FRONT
COVER
PRESSURE
TAP
GREEN
HOSE
CLAMP
TUBE 1
(3 PLACES)
Horizontal Connections - Right Side Down
(Upflow Shown, Counterflow Similar)
RUBBER ELBOW
DRAIN PORT
SILVER HO SE
CLAMP
RUBBER
ELBOW
RIGHT
SIDE
PANEL
VENT
FIELD SUPPLIED HOSE AND CONNECTORS
NOTE:
MAKE SMALL LOOP IN HOSE TO SERVE AS “P-TRAP”
When using the horizontal alternate
vent configuration, you must use the
RF000142 vent drain kit.
RF000142 KIT
35
Page 36
OPERATION
Horizontal installations with the left side panel down will require drain hoses to be connected to the left side front cover drain port and the side drain port on the rubber elbow.
1. Remove the rubber plug/cap from the front cover left (down) side drain port.
2. Relocate the front cover pressure switch hose connec­tion from the right side (as shipped) pressure tap to the left (down) side tap. The pressure switch hose must be connected to the down side to guard against blocked drain conditions. Cut hose to appropriate length to mini­mize sagging. Plug right (unused) pressure tap with plug removed from left side.
3. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear left (down) side panel grom­met holes. NOTE: For left side drainage, grommets must be relocated to left side panel.
4. Remove the rubber cap from the side drain port on the rubber elbow.
5. Secure the short end of Hose B to rubber elbow side drain port using a green hose clamp. NOTE: For left side drainage, route hose to far left (down) side panel grommet holes. NOTE: Horizontal left side connections (when using new side port drain elbow) does not require connecting a hose to the induced draft blower housing.
6. Cut 5 1/2 inches straight length from the long end of each Tube 2 and discard radius ends.
7. Insert approximately one inch of each Tube 2 through left side panel grommet hole. Secure tubes to Hose A and Hose B with a green hose clamps. NOTE: Tube must reach bottom of trap. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
For details concerning mounting of the drain trap, refer to Con-
densate Drain Lines and Drain Trap - Horizontal Drain Trap Mount­ing.
HORIZONTAL DRAIN TRAP MOUNTING (LEFT OR RIGHT SIDE PANEL)
1. Position the drain trap against side panel with drain tubes inserted into trap. Note that the trap may be orientated with the outlet facing either the furnace’s top cover or base pan.
2. Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes.
3. Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding.
4. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
GREEN HOSE
CLAMP
PRESSURE
LEFT SI D E
PANE L
FRON T COVER
DRAIN PORT
RED HOSE CLAMP
36
FRONT COVER
TAP
SIDE PANEL
GROMMET
HOLES
Horizontal Connections - Left Side Down
(Upflow Shown, Counterflow Similar)
HOSE B
HOSE A
GREEN HOSE
CLAMP
TUBE(S) 2
DRAIN TRAP
Allow
4-3/4” minimum
for trap
Page 37
OPERATION
Electrical Connections
WARNING
HIGH VOLTAGE !
TO
AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO
THE UNIT MUST BE POLARIZED AND GROUNDED
WARNING
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING
.
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS OPERATION
WIRING HARNESS
The wiring harness is an integral part of this furnace. Field alteration to comply with electrical codes should not be required. Wires are color coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C. Any replacement wiring must be a copper conductor.
115 VOLT LINE CONNECTIONS
Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that speci­fied on the unit rating plate. Power supply to the furnace must be NEC Class 1, and must comply with all applicable codes. The furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing prop­erly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating plate. An elec­trical disconnect must be provided at the furnace location.
Connect hot, neutral, and ground wires as shown in the wiring diagram located on the unit’s blower door. For direct vent appli­cations, the cabinet opening to the junction box must be sealed air tight using either an UL approved bushing such as Heyco Liquid Tight or by applying non-reactive UL approved sealant to bushing.
. W
IRING ERRO RS CAN CAUSE IMPROPER AND DANGEROUS
. V
ERIFY PROPER OPERATION AFTER SERVICING
.
.
Line polarity must be observed when making field connections. Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a right side (left side for counterflows) electrical connection with the junction box located inside the burner compartment. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the other side of the burner compartment prior to making electrical connections. To relo­cate the junction box, follow the steps shown below.
NOTE: Wire routing must not to interfere with circulator blower operation, filter removal, or routine maintenance.
JUNCTION BOX RELOCATION
WARNING
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
.
. USE
GLOVES AS A
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS UNIT
.
,
WARNING
HIGH VOLTAGE !
TO
AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE
N
ATIONAL ELECTRIC CODE
.
Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a right side electrical connection. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the left side prior to making electrical connec­tions. To relocate the junction box, perform the following steps.
1. Remove the burner compartment door.
2. Remove and save the two screws securing the junction box to the side panel.
3. Relocate junction box and associated plugs and grom­mets to opposite side panel. Secure with screws re­moved in step 2.
WARNING
TO
AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE
FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE
.
37
Page 38
OPERATION
To ensure proper unit grounding, the ground wire should run from the furnace ground screw located inside the furnace junc­tion box all the way back to the electrical panel. NOTE: Do not use gas piping as an electrical ground. To confirm proper unit grounding, turn off the electrical power and perform the following check.
1. Measure resistance between the neutral (white) con­nection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which interrupts unit voltage when the blower door is opened for servic­ing. Do not defeat this switch.
24 VOLT THERMOSTAT WIRING
IMPORTANT NOTE
W
IRE ROUT ING MUST NOT INTERFERE WITH CIRCULATOR BLOWER
OPERATION, FILTER REMO VAL OR ROUT INE MAINTENANCE
REMO VABLE PLUG CONNECTOR IS PROVIDED WITH THE CONTROL TO
A
MAKE THERMOSTAT WIRE CONNECTIONS WIRE CONNECTIONS MADE TO THE PLUG, AND REPLACED
STRONGLY
TERMINAL BE TWISTED TOGETH ER PRIOR TO INSERTING INTO THE PLUG CONNECTOR OPERATION
RECO MMENDED THAT MULTIPLE WIRES INTO A SINGLE
. F
AILURE TO DO SO MAY RESU LT IN INTERMITTENT
.
. T
HIS PLUG MAY BE REMOVED
. IT IS
.
,
IMPORTANT NOTE
DIP
SWITCH
#13 MUST BE
THE
CTK01
SET TO COMMUNICATING MODULATING THERMOSTAT, CHECK TO MAKE SURE DIP SWITCH IN THE POSITION WHEN USING A NON-COMMUNICATING SINGLE-STAGE THERMOSTAT
COMMUN ICAT ING THERMOSTAT, DIP SWITCH
ON
POSITION
2-
OFF
POSITION (FACTORY POSITION
.
SET TO MATCH THERMOSTAT TYPE
#13
. T
HIS IS ALSO THE CORRECT SETTING FOR A NON
STAGE THERMOSTAT
. TO
USE
CTK02**
). T
HIS IS ALSO THE CORRECT
. TO
USE
MUST BE
#13 IS
-
When installed with a non-communicating thermostat, the fur­nace integrated control module provides terminals for both “W1” and “W2”, and “Y1” and “Y2” thermostat connections. This allows the furnace to support the following system applications: ‘Two­Stage Heating Only’, ‘Two-Stage Heating with Single Stage Cool­ing’, and ‘Two-Stage Heating with Two-Stage Cooling’. Refer to the following figures for proper connections to the integrated con­trol module.
Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located in the blower compartment. The following figure shows connections for a “heat/cool system”.
This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment. Consult the wiring diagram, lo­cated on the blower compartment door, for further details of 115 Volt and 24 Volt wiring.
NOTE: Use of ramping profiles requires a jumper between Y1 and O.
IMPORTANT NOTE
T
HERMOSTAT
C
OMFORT ALERT™ MODULE OR IF THE OUTDOOR UNIT IS A PART OF
THE COMFORTNET™ FAMILY OF EQUIPM EN T
“R”
REQUIRED IF OUTDOOR UNIT IS EQUIPPED WITH A
.
DEHUM
W2
W1
1Y12
24 V THERM OSTAT CONNECTIONS
Low Voltage Connections with Auxiliary Terminals
C
R
G
Y2
O
AUX
The auxiliary contacts are shipped with a factory installed jumper. As an option, the auxiliary contacts may be wired to a normally closed float switch. In the event of open contacts, the furnace will be disabled until the condition is corrected. These are 24 volt terminals fed internally , do not apply another voltage source to these terminals.
R
R
Y C
Remote
Condensing Unit
(Single -St age Co oli n g)
NEU
Furnace Integrated
Control Module
Dehumidistat
[Optional]
Thermostat - Single-Stage Heating with Single-Stage Cooling
IMPORTANT NOTE
TO
APPLY A SINGLE-STAGE HEATING THERMOSTAT, THE THERMOSTAT SELECTOR SWITCH ON THE INTEGRATED CONTROL MODULE SET ON SINGLE-STAGE
.
MUST BE
_____________________________________
R
R
Y C
Remote
Condensing Unit
(Single-Stage Cooling)
Thermostat - Two-Stage Heating with Single-Stage Cooling
NEU
Furnace Integrat ed
Control Module
Dehumidistat
[Optional]
38
Page 39
OPERATION
Y2
Y2
Y2
Remote
Condensing Unit
(Two-Stage Cooling)
Thermostat - Two-Stage Heating with Two-Stage Cooling
W1 W2
W1 W2
NEU
Furnace Integrated
Dehumidistat
[Optional]
Control Module
IMPORTANT NOTE
SET
DIP SWITCH
COOL I N G THERMOSTAT
#14 TO ON
POSITION WHEN USING A
.
Thermostat Wiring Diagrams
2-
STAGE
THERMOSTAT APPLICATION
The modulating furnace can be operated with a CTK01 com­municating thermostat or a CTK02** or CTK03AA communi­cating-modulating thermostat. It also facilitates operation with a non-communicating single or two stage heat / cool thermo­stat.
NOTE: DIP switch #13 (Heating thermostat selection)must be checked and set regardless of the thermostat chosen. Factory setting is OFF (single stage), this is also the correct position if using CTK02** thermostat. To use a CTK01 or a non-communicating two stage thermostat, set the switch to the ON position.
Operation with CTK03AA
1. Humidification Options are ON / OFF with the CTK03AA. When “On” is selected, the humidification relay on the furnace control board will function during a heat call if a humidity demand exists. Selecting “Off” means the hu­midification relay will not function.
2. If the CTK03AA is set up so the compressor off delay is 0 min, it will display a cool / heat call immediately regard­less of the delay built into the outdoor unit control board. This means the CTK03AA could show COOL ON when the outdoor unit is still in a delay period. The recommen­dation is to set up the compressor delay to at least 3 minutes
3. Dual Fuel – When the CTK03AA calls for gas heat, the heat pump will shut off, after a delay of approximately 3 minutes it will then turn on gas heat.
4. Dehumidification (lowering of CFM to 85%) only happens during low stage cooling operation. The dehumidification feature is not active during high stage cool. The CTK03AA can be set up to overcool the home in order to reach the RH set point.
NOTE: In non-communicating installations with a condensing unit, DIP switch #14 must be checked and set to match a single or two stage condensing unit. Factory setting is OFF (single stage).
24 VOLT DEHUMIDISTAT WIRING
The optional usage of a dehumidistat allows the furnace’s circula­tor blower to operate at a slightly lower speed (85% of desired speed) during a combined thermostat call for cooling and dehu­midistat call for dehumidification. This can be done through an independent dehumidistat or through a thermostat’s DEHUM ter­minal (if available). This lower blower speed enhances dehumidi­fication of the conditioned air as it passes through the AC coil. For proper function, a dehumidistat applied to this furnace must operate on 24 VAC and utilize a switch which opens on humidity rise. Refer to the “Thermostat Wiring Diagrams” figure for ad­ditional wiring details.
To install/connect a dehumidistat:
1. Turn OFF power to furnace.
2. Secure one dehumidistat lead to the terminal marked “DEHUM” on the furnace integrated control module.
3. Secure the other dehumidistat lead to the terminal marked “R” on the furnace integrated control module.
4. Secure the dehumidistat ground wire (typically the green lead) to the ground screw on the furnace junction box. NOTE: Ground wire may not be present on all dehumidistats.
5. Turn ON power to furnace.
To enable the dehumidify function on the integrated control mod­ule, set the dehumidification ENABLE DIP switch from OFF to ON.
Once the switch is set, the dehumidify function is enabled during a combination call for cooling (T-Stat) and dehumidification (DEHUM-Stat). Refer to the DIP switch chart in the back sec­tion of this manual.
FOSSIL FUEL APPLICATIONS
This furnace can be used in conjunction with a heat pump in a fossil fuel application. A fossil fuel application refers to a com­bined gas furnace and heat pump installation which uses an out­door temperature sensor to determine the most cost efficient means of heating (heat pump or gas furnace).
A heat pump thermostat with three stages of heat is required to properly use a two-stage furnace in conjunction with a heat pump. Refer to the fossil fuel kit installation instructions for additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installation instructions. All furnace connections must be made to the fur­nace two-stage integrated control module and the “FURNACE” terminal strip on the fossil fuel control board.
39
Page 40
A
OPERATION
115 VOLT LINE CONNECTION OF ACCESSORIES (HUMIDIFIER AND ELECTRONIC AIR CLEANER)
WARNING
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING
.
The furnace integrated control module is equipped with line volt­age accessory terminals for controlling power to an electronic air cleaner.
The accessory load specifications are as follows. (The furnace control board also has a set of dry contacts for humidifier connection.)
Humidifier 1.0 Amp maximum at 120 VAC
Electronic Air Cleaner 1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any accessories. Follow the humidifier or air cleaner manufacturers’ instructions for locating, mounting, grounding, and controlling these accesso­ries. Accessory wiring connections are to be made through the 1/4" quick connect terminals provided on the furnace integrated control module. The Electronic air cleaner hot terminal is iden­tified as EAC. It is necessary to remove the protective tab on the board cover to access the EAC Terminal. The EAC neu­tral terminal is identified as NEUTRAL. A line voltage hu­midifier may be connected between one of the HUM con­tacts and NEUTRAL. The other HUM contact must be fed from the L1 terminal.
All field wiring must conform to applicable codes. Connections should be made as shown in the following figure.
If it is necessary for the installer to supply additional line voltage wiring to the inside of the furnace, the wiring must conform to all local codes, and have a minimum temperature rating of 105°C. All line voltage wire splices must be made inside the furnace junction box.
The integrated furnace control HUM (dry contacts) are closed whenever the inducer is energized in a non-communicating installation. When used with a CTK02** communicating ther­mostat, the HUM terminals are closed whenever there is a call for humidity. The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts whenever the circulator blower is energized.
24 VOLT HUMIDIFIER
A 24 volt humidifier can be powered by feeding one of the HUM terminals with a field installed wire from the R terminal or by connecting to the NO side of the low fire pressure switch.
Gas Supply and Piping
The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high altitude.
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPM EN T DAMAGE, THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING
.
Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appli­ances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.
NEUTRAL
L1
UX OUT
AUX IN
Accessories Wiring
40
Inlet Gas Supply Pressure Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c. Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.
HIGH ALTITUDE
The modulating furnace is approved up to 10,000 ft altitude. Do not derate the furnace by adjusting the manifold pressure to
a lower pressure. In some areas the gas supplier may artificially derate the gas in
an effort to compensate for the effects of altitude. If the gas is artificially derated, the appropriate orifice size must be determined based upon the BTU/ft3 content of the derated gas and the alti­tude. Refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and information provided by the gas supplier to determine the proper orifice size.
.
Page 41
OPERATION
PROPANE GAS CONVERSION
WARNING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION QUALIFIED INSTALLER OR SERVICE AGENCY
. ALL
CONVERSIONS MUST BE PERFORMED BY A
.
. THE
This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations.
LP KIT
MODEL
LPKMOD060UF *MVM960603BX LPKMOD080UF *MVM960805CX
LPKMOD100UF *MVM961005DX LPKMOD115UF *MVM961155DX
LPKMOD060CF *CVM960604CX LPKMOD080CF *CVM960805DX
LPKMOD 100C F *CVM961005DX
(*= A or G)
The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified in­staller, or service agency.
GAS PIPING CONNECTIONS
WARNING
TO
AVOID POSSIBLE UNSATISFACTORY OPERATION OF EQUIPMEN T DAMAGE DUE TO UNDERFIRIN G OR EQUIPM EN T, USE THE PROPER SIZE OF NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE METER/TANK TO THE FURNACE
.
When sizing a trunk line, be sure to include all appliances which will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
Length of Nominal Black Pipe Size
Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas) BTUH Furnace Input
CFH =
Heat i ng Value of Gas (BTU/Cubic Foot)
In Cubic Feet of Gas Per Hour (CFH)
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/2" pipe to a larger pipe size.
The following stipulations apply when connecting gas piping. Re­fer to Gas Piping Connections figure for typical gas line connec­tions to the furnace.
Gas piping must be supported external to the furnace cabinet so that the weight of the gas line does not distort the burner rack, manifold or gas valve.
Use black iron or steel pipe and fittings for building piping. Where possible, use new pipe that is properly chamfered, reamed, and free of burrs and chips. If old pipe is used, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.
Use pipe joint compound on male threads ONLY. Al­ways use pipe joint compound (pipe dope) that is AP­PROVED FOR ALL GASSES. DO NOT apply com­pound to the first two threads.
Use ground joint unions.
Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.
Always use a back-up wrench when making the con­nection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory. Maximum torque for the gas valve connection is 375 in-lbs; ex­cessive over-tightening may damage the gas valve.
Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is in­stalled, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.
41
Page 42
A
OPERATION
GAS LINE
PLUG IN
GAS LINE
HOLE
PIPE UNION
BURNERS
MANIFOLD
GROUND JOINT
PIPE UNION
GAS VALVE
GAS VALVE
BURNERS
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION)
DRIP LEG
GROM M E T IN STAN DA RD
GAS LINE HOLE
MANUAL
SHUT OFF VALVE
(UPST R EAM FROM
PIPE UNION)
HEIGHT REQUIRED
BY LOCAL CODE
GROMMET
IN STANDARD
GAS LINE HOLE
DRIP LEG
DRIP LEG
BURNERS
GAS VALVE
PLUG IN
LTE RNATE
GAS LINE
GAS VALVE
BURNERS
HOLE
PLUG IN ALTERNA T E
GAS LINE HOL E
ALTERNATE GAS
LINE LOCATION
MANIFOLD
HORIZONTAL [UPFLOW MODEL]
42
DRAIN TRAP
Gas Piping Connections
ALTERNATE GAS
LINE LOCATION
DRAIN TRAP
MANIFOLD
PLUG IN ALTERNA T E GAS LINE HOLE
HORIZONTAL[COUNTERFLOW]
Page 43
OPERATION
Tighten all joints securely.
Connect the furnace to the building piping by one of the following methods:
Rigid metallic pipe and fittings.Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing must not be used in exterior lo­cations. In order to seal the grommet cabinet penetra­tion, rigid pipe must be used to reach the outside of the cabinet. A semi-rigid connector to the gas piping may be used from there.
Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace.
Protect connectors and semirigid tubing against physi­cal and thermal damage when installed. Ensure alumi­num-alloy tubing and connectors are coated to protect against external corrosion when in contact with ma­sonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.
DIRECT/STANDARD INLET PIPING
GAS PIPING CHECKS
Before placing unit in operation, leak test the unit and gas con­nections.
WARNING
TO
AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH
OR OPEN FLAME TO TEST FOR LEAKS
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other ap­proved testing methods.
NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPA).
.
PROPANE GAS TANKS AND PIPING
WARNING
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
When gas piping enters directly to the gas valve through the stan­dard inlet hole, the installer must supply straight pipe with a ground
joint union to reach the exterior of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
.
. USE
GLOVES AS A
INDIRECT/ALTERNATE INLET PIPING
When gas piping enters indirectly to the gas valve through the alternate gas inlet hole the following fittings (starting from the gas
valve) to reach the outside of the cabinet must be supplied:
Close nipple.
90 degree elbow.
2½ inch nipple.
90 degree elbow.
Straight pipe, with a ground joint union, to reach the exterior
of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
WARNING
IF
THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR CONFI NED SPACE, IT IS STRO NGLY RECOMMENDED TO CONTA CT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK
S
INCE PROPANE GAS IS HEAVIER THAN AIR, ANY LEAKING GAS CAN
SETTLE IN ANY LOW AREAS OR CONFI NED SPACES
ROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE
P
EXCEPT WITH A WARNING DEVICE
A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in pro­pane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instruc­tions listed in the Safety Precautions section of this manual.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 10” WC + .5” WC a t the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liq­uid, and “wetted surface” area of the container or con­tainers.
.
.
.
43
Page 44
OPERATION
2. Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and be­tween second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, rec­ommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most stan­dard commercial compounds, special pipe dope must be used. Shellac-based compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
Refer to the following illustration for typical propane gas installa­tions and piping.
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting. Capacities in 1,000 BTU/hour.
Pipe or Tubing Length
Feet
10 39 92 199 329 501 275 567 1,071 2,205 3,307 20 26 62 131 216 346 189 393 732 1,496 2,299 30 21 50 107 181 277 152 315 590 1,212 1,858 40 19 41 90 145 233 129 267 504 1,039 1,559 50 18 37 79 131 198 114 237 448 913 1,417 60 16 35 72 1,211 187 103 217 409 834 1,275
80 13 29 62 104 155 89 185 346 724 1,066 100 11 26 55 90 138 78 162 307 630 976 125 10 24 48 81 122 69 146 275 567 866 150 9 21 43 72 109 63 132 252 511 787 200 8 19 39 66 100 54 112 209 439 665 250 8 17 36 60 93 48 100 185 390 590
*Data in accordance with NFPA pamphlet No. 54
Tubing Size, O.D. Type L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
Nominal Pipe Size
Schedule 40
Propane Gas Piping Chart II
Circulating Air & Filters
DUCT WORK - AIR FLOW
200 PSIG Maximum
5 to 15 PSIG (20 PS IG Max.)
Continuous
Second Stage Regulator
11" W.C.
First Stage Regulator
Propane Gas Installation (Typ.)
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/h ou r.
Pipe or Tubing Length
Feet
10 730 1,700 3,200 5,300 8,300 3,200 7,500 20 500 1,100 220 3,700 5,800 2,200 4,200 30 400 920 2,000 2,900 4,700 1,800 4,000 40 370 850 1,700 2,700 4,100 1,600 3,700 50 330 770 1,500 2,400 3,700 1,500 3,400 60 300 700 1,300 2,200 3,300 1,300 3,100
80 260 610 1,200 1,900 2,900 1,200 2,600 100 220 540 1,000 1,700 2,600 1,000 2,300 125 200 490 900 1,400 2,300 900 2,100 150 190 430 830 1,300 2,100 830 1,900 175 170 400 780 1,200 1,900 770 1,700 200 160 380 730 1,100 1,800 720 1,500
To convert to capacities at 15 psig settings - multiply by 1.130 To convert to capacities at 5 psig setti n gs - multiply by 0.879
Tubing Size, O.D. Type L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
Nominal Pipe Size
Schedule 40
Propane Gas Piping Chart I
WARNING
N
EVER ALLOW THE PRODUCTS OF COMBUSTION, INCLUDING CARB ON MONOXIDE, TO ENTER THE RETU RN DUCT WORK OR CIRCULATION AIR SUPPLY
.
Duct systems and register sizes must be properly designed for the CFM and external static pressure rating of the furnace. De­sign the ductwork in accordance with the recommended meth­ods of “Air Conditioning Contractors of America” Manual D.
Install the duct system in accordance with Standards of the Na­tional Board of Fire Underwriters for the Installation of Air Condi­tioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the return duct connected to the furnace. NOTE: Ductwork must never be at- tached to the back of the furnace. For upflow installations requir- ing 1800 CFM or more, use either two side returns or bottom return or a combination of side /bottom. Flexible joints may be used for supply and return connections to reduce noise transmis­sion. To prevent the blower from interfering with combustion air or draft when a central return is used, a connecting duct must be installed between the unit and the utility room wall. Never use a room, closet, or alcove as a return air chamber.
CHECKING DUCT STATIC
Refer to your furnace rating plate for the maximum ESP (ex­ternal duct static) rating.
Total external static refers to everything external to the fur­nace cabinet. Cooling coils, filters, ducts, grilles, registers must all be considered when reading your total external static pressure. The supply duct pressure must be read between the furnace and the cooling coil. This reading is usually taken by removing the “A” shaped block off plate from the end on the coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.
44
Page 45
OPERATION
Too much external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as follows;
1. With clean filters in the furnace, use a draft gauge (in­clined manometer) to measure the static pressure of the return duct at the inlet of the furnace. (Negative Pres­sure)
2. Measure the static pressure of the supply duct. (Positive Pressure)
3. The difference between the two numbers is .4” w.c.
Example:
static reading from return duct = -0.1" w.c. static reading from supply duct = 0.3" w.c. total external static pressure on this system = 0.4"
w.c. NOTE: Both readings may be taken simultaneously and
read directly on the manometer if so desired. If an air condi­tioner coil or Electronic Air Cleaner is used in conjunction with the furnace, the readings must also include theses com­ponents, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum listed on the furnace rating plate, check for closed dampers, registers, undersized and/or oversized poorly laid out duct work.
BOTTOM RETURN AIR OPENING [UPFLOW MODELS]
The bottom return air opening on upflow models utilizes a “lance and cut” method to remove sheet metal from the duct opening in the base pan. To remove, simply press out the lanced sections by hand to expose the metal strips retaining the sheet metal over the duct opening. Using tin snips, cut the metal strips and re­move the sheet metal covering the duct opening. In the corners of the opening, cut the sheet metal along the scribe lines to free the duct flanges. Using the scribe line along the duct flange as a guide, unfold the duct flanges around the perimeter of the opening using a pair of seamer pliers or seamer tongs. NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise is­sues.
WARNING
E
DGES OF SHEET METAL HOLES MAY BE SHARP PRECAUTION WHEN REMOVING SHEET METAL FROM RETURN AIR OPENINGS
.
CUT USING TIN SNIPS
. USE
GLOVES AS A
PRESS OUT BY HAND
Checking Static Pressure
CUT FOUR CORNERS AFTER REMOVING SHEET METAL
SCRIBE LINES OUTLINING DUCT FLANGES
Duct Flange Cut Outs
When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating ele­ment. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is recom­mended that a removable access panel be provided in the outlet air duct. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream. The access panel must be made to prevent air leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return air entering the furnace must be between 55°F and 100°F.
45
Page 46
OPERATION
FILTERS - READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCT WORK
Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this furnace, but must be provided, sized and installed externally by the installer. Filters must comply with UL900 or CAN/ULCS111 standards. If the furnace is installed without filters, the warranty will be voided.
On upflow units, guide dimples locate the side return cutout loca­tions. Use a straight edge to scribe lines connecting the dimples. Cut out the opening on these lines. NOTE: An undersized open­ing will cause reduced airflow.
Refer to Minimum Filter Area tables to determine filter area re­quirements.
COO LING AI RFLOW REQU IRE MENT (CFM)
600 800 1000 1200 1400 1600 2000
0603__XA --- --- 627* 627* 672 768 --­0805__XA --- --- --- 836* 836* 836* 960
Input
Airflow
1005__XA 1155__XA
0604__XA --- --- 320* 320* 336 384 --­0805__XA
Input
Airflow
1005__XA
--- --- --- 940* 940* 940* 960
COO LING AI RFLOW REQU IRE MENT (CFM)
600 800 1000 1200 1400 1600 2000
--- --- --- 427* 427* 427* 480
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
COOLING AIRFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
0603__XA --- --- 564* 564* 672 768
UPFLOW
COUNTERFLOW
UPFLOW
UPRIGHT INSTALLATIONS
Depending on the installation and/or customer preference, differ­ing filter arrangements can be applied. Filters can be installed in the central return register or a side panel external filter rack kit (upflows). As an alternative a media air filter or electronic air cleaner can be used as the requested filter.
The following figure shows possible filter locations.
AIR FLOW
CENTRAL
RETURN
GRILLE
SIDE RETURN
EXTERNAL FILTER
FILTER
RETURN
(Field Supplied)
(EITHER SIDE)
FILTER
ACCESS
DOOR
DUCT
FILTER
SUPPORT
BRACKET
RACK KIT
FILTER
Possible Upright Upflow
FILT
ER
R
E
T
L
I
F
CENTRAL
RETURN
GRILLE
0805__XA --- --- --- 752* 752* 768 960
Input
Airflow
1005__XA 1155__XA
0604__XA --- --- 641* 641* 672 768 --­0805__XA
Input
Airflow
1005__XA
--- --- --- 940* 940* 940* 960
COUNTERFLOW
COOLING AIRFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
--- --- --- 854* 854* 854* 960
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
46
AIR FLOW
Possible Upright Counterflow
Filter Locations
Page 47
OPERATION
HORIZONTAL INSTALLATIONS
Filters must be installed in either the central return register or in the return air duct work.
IGNITION
(80%)
Startup Procedure & Adjustment
Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation. In addition to the following start-up and adjustment items, refer to further information in Operational Checks section.
100%
IGNITION
(80%)
78%
57%
MIN.
2 MINS.
Operation with Conventional 1-Stage Thermostat
(DIP switch selections 1-Stage heat)
Call for heat, thermostat energizes W1 on IFC (W2 input is ignored).
After a successful Light Off Sequence and expiration of the Ignition Stabilization Period:
After 2 minutes, the IFC increases to 57% at a rate of 1% per second
After 10 total minutes, the IFC increases to 78% at a rate of 1% per second.
After 20 total minutes, the IFC increases to 100% at a rate of 1% per second for the remainder of the call for heat.
The circulator is adjusted to the appropriate CFM, cor­responding to the current firing rate.
UNIT CALL FOR HEAT ENDS
10 MINS.
8 MINS.
70%
10 MINS.
60%
50%
2 MINS.
MIN.
8 MINS.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
Call for 1st-Stage Heat - Thermostat contacts close R to W1.
After a successful Light Off Sequence and expiration of the Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC increases to 50% fort he next 8 minutes.
Thereafter, the IFC will increase 10%, at a rate of 1% per second, every 10 minutes for the remainder of the call for heat (See above figure).
The circulator is adjusted to the appropriate CFM, cor­responding to the current firing rate.
47
Page 48
OPERATION
90%
IGNITION
(80%)
70%
60%
50%
MIN.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
2 MINS.
8 MINS.
Call for 2nd-Stage Heat - Thermostat contacts close R to W1 and W2.
After a successful Light Off Sequence and expiration of the Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC increases to 80%.
Thereafter, the IFC will increase 10%, at a rate of 1% per second, every 10 minutes for the remainder of the call for heat.
The circulator is adjusted to the appropriate CFM, cor­responding to the current firing rate.
UNIT CALL FOR HEAT ENDS
CALL FOR 2ND STAGE HEAT
OPERATION
IGNITION
100%
(80%)
78%
50%
2 MINS.
MIN.
10 MINS.
The IFC remains at the current firing rate until the 1st­Stage call for heat is satisfied.
HEATING OPERATION WITH CTK01 THERMOSTAT (COMMUNI-
CATING)
When the Thermostat Heat Setup DIP switch is set to 2-Stage heat, the IFC operation will be compatible with a CTK01communicating thermostat.
When a call for heat is sent, the furnace will go through the Light Off Sequence, After the successful Light Off Sequence and expiration of the Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC accepts the specific Heat Requested Demand.
If the differential is equal to or less than 2 degrees, the IFC will follow the conventional 2-Stage algorithm, equivalent to a W1 request..
If the heat differential is greater than 2 degrees, the IFC will follow the conventional 2-Stage algorithm, equivalent to a W2 request.
The circulator will operate per the heat airflow profile.
HEATING OPERATION WITH CTK02** THERMOSTAT (MODU
COMMUNICATING)
LATING
When the Thermostat Heat Setup DIP switch is set to 1-Stage heat, the IFC operation will be compatible with a modulating communicating thermostat (CTK02**).
When a call for heat is sent, the furnace will go through the Light Off Sequence, After the successful Light Off Sequence and expiration of the Ignition Stabilization Period:
The IFC adjusts to the low firing rate.
After 2 minutes, the IFC accepts the specific Heat Requested Demand.
If the differential is 2 degrees or less, the Heat Current Demand Status will show 50%.
If the specific Heat Requested Demand is above 2 de­grees, the Heat Current Demand Status will track the specific Heat Requested Demand.
The circulator will operate per the heat airflow profile.
HEAT ANTICIPATOR SETTING
The heat anticipator in the room thermostat must be correctly adjusted to obtain the proper number of cycles per hour and to prevent “overshooting” of the setting. Set the heat anticipator setting to 0.7 amps. Follow the thermostat manufacturer’s in­structions on how to adjust the heat anticipator setting.
Call for 2nd-Stage Heat with 1st-Stage call for heat call in progress, with conventional 2-Stage Thermostat.
The IFC increases the firing rate to 100% at a rate of 1% per second for the remainder of the W2 call.
The circulator is adjusted to the appropriate CFM, cor­responding to the current firing rate.
Call for 2nd-Stage Heat satisfied; Call for 1st-Stage Heat re­mains.
48
DRAIN TRAP PRIMING
The drain trap must be primed prior to furnace startup. To prime, fill the drain trap with water. This ensures proper furnace drainage upon startup and prohibits the possibility of flue gases escaping through the drain system. Air conditioning condensate may be drained into the furnace trap. Please see requirements in Condensate Drain Lines & Drain Trap section.
Page 49
OPERATION
FURNACE OPERATION
Purge gas lines of air prior to startup. Be sure not to purge lines into an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other ap­proved method. Verify that all required kits (propane gas, etc.) have been appropriately installed.
FURNACE STARTUP
1. Close the manual gas shutoff valve external to the fur­nace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF position.
6. Wait five minutes then smell for gas. Be sure check near the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the Safety Instructions on page 5 of this manual. If you do not smell gas after five minutes, move the fur­nace gas valve manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the fur­nace.
10. Turn on the electrical power to the furnace.
1 1. Adjust the thermostat to a setting above room tem-
perature.
12. After the burners are lit, set the thermostat to desired temperature.
FURNACE SHUTDOWN
1. Set the thermostat to the lowest setting. The integrated control will close the gas valve and ex-
tinguish flame. Following a 15 second delay , the in­duced draft blower will be de-energized. After a 120, 150, 180 or 210-second delay period (field selectable delay OFF [90, 120, 150, 180] plus 30-second ramp down), the circulator blower de-energizes.
2. Remove the burner compartment door and move the furnace gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the fur­nace.
4. Replace the burner compartment door.
GAS SUPPLY PRESSURE MEASUREMENT
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPM EN T DAMAGE, THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING
.
The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure boss or at a hose fitting installed in the gas piping drip leg. The supply pressure must be measured with the burners operating. To measure the gas supply pressure, use the following procedure.
PS
CONNECTION
ATMOSPHERE
PORT
FLOW
DIRECTION
Honeywell Model VR9205R
2-PIN
m
o
t
e
r
e
p
t
n
M
o
O
t
A
m
e
o
s
h
p
r
e
i
o
a
e
m
n
M
t
e
n
a
s
o
e
H
e
r
Outlet
Pressure
Tap
1/8 NPT
POWER CONNECTOR
Inlet Pressure Tap 1/8 NPT
Honeywell Model VR9205R Connected to Manometer
49
Page 50
OPERATION
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2. Connect a calibrated water manometer (or appropriate gas pressure gauge) at either the gas valve inlet pres­sure boss or the gas piping drip leg. See Honeywell VR9205R gas valve figure for location of inlet pressure boss.
NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205R gas valve, a field-supplied hose barb fitting must be installed prior to making the hose connection.
3. Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.
Field Test Mode is intended to help a service person troubleshoot and check out an installed appliance. T o enter Field Test Mode the Fault Recall Push-But-
ton must be pressed twice within a 5 second period at
any time during a heating cycle, at which time the display will show “Ft”. While the display is showing “Ft”,
pressing and holding the Fault Recall Push-Button for 3 seconds will enable the field test mode and override the normal firing rate sequence at a rate of 100% for 5 minutes or until the end of the call for heat. The dis­play will show the normal “Hi” while the control is firing at 100%. If the Fault Recall Push-Button has not been pressed within 5 seconds of displaying “Ft” the display will revert back to normal.
4. Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.
Inlet Gas Supply Pressure Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c. Propane G a s Minimum: 11.0" w.c. Maximum: 13.0" w.c.
If supply pressure differs from table, make the necessary adjust­ments to pressure regulator, gas piping size, etc., and/or con­sult with local gas utility.
5. Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in step
3.
Gas Line
Gas Shutoff Valve
Gas Line To Furnace
Open To Atmosphere
Drip Leg Cap With Fitting
Manomete r Hose
Manometer
Measuring Inlet Gas Pressure (Alt. Method)
GAS MANIFOLD PRESSURE MEASUREMENT
CAUTION
TO
PREVENT UNRELIABLE OPERATION OR EQUIPM EN T DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE
. GAS
VALVE IS FACTORY SET AND DOES
F
IELD ADJUSTMENT
. DO
NOT ATTEM PT TO ADJUST VALVE
NOT
REQUIRE ANY
.
The manifold pressure must be measured with the burners oper­ating. To measure the manifold pressure, use the following procedure.
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2. Turn off all electrical power to the system.
3. Outlet pressure tap connections: Remove the outlet pres­sure boss plug. Install an 1/8" NPT hose barb fitting into the outlet pressure tap.
4. Attach a hose and manometer to the outlet pressure barb fitting.
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W1” con­tacts to provide a call for low stage heat.
7. Modulating furnaces light at 80% of max input. For natu­ral gas the expected manifold pressure at ignition will be in a range of 1.8" - 2.5" WC. For LP gas the range will be
5.8" - 6.8" WC. NOTE: Measure the gas manifold pressure with the burn-
ers firing. After every time the main power is turned off and back on, the furnace will enter a calibration routine on the next call for heat The inducer will ramp up and
down during the calibration routine. After calibration, the furnace will proceed to ignition cycle.
50
Page 51
OPERATION
8. Field Test Mode is intended to help a service person troubleshoot and check out an installed appliance by bringing the furnace up to High fire (100% input), by-pass­ing the normal modulating routine.
To enter Field Test Mode the Fault Recall Push-Button must be pressed twice within a 5 second period at any time during a heating cycle, at which time the display will show “Ft”. While the display is showing “Ft”, pressing and holding the Fault Recall Push-Button for 3 seconds will enable the field test mode and override the normal firing rate sequence at a rate of 100% for 5 minutes or until the end of the call for heat. The display will show the normal “Hi” while the control is firing at 100%. If the Fault Recall Push-Button has not been pressed within 5 sec­onds of displaying “Ft” the display will revert back to nor­mal.
NOTE: Gas valve is factory set and does NOT require any field adjustment. Do NOT attempt to adjust valve.
9. Turn off all electrical power and gas supply to the sys­tem.
10.Remove the manometer hose from the hose barb fitting.
11.Remove the 1/8" NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure boss plug and seal with a high quality thread sealer.
12.Turn on electrical power and gas supply to the system.
13.Close thermostat contacts “R” and “W1/W2” to energize the valve.
Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug. Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY!
NOTE: For natural gas to LP conversion, consult the furnace Specification Sheet.
Manifold Gas Pressu re
Gas
Natural High Stage 3.2 - 3.8" w.c. 3.5 " w.c.
Propane Hi g h Sta g e 9.5 - 10 .5" w.c. 10.0" w .c.
Rang e Nominal
GAS INPUT RATE MEASUREMENT (NATURAL GAS ONLY)
The gas input rate to the furnace must never be greater than that specified on the unit rating plate. To measure natural gas input using the gas meter, use the following procedure.
1. Turn OFF the gas supply to all other gas-burning appli-
ances except the furnace.
2. While the furnace is operating, time and record one
complete revolution of the smallest gas meter dial.
3. Calculate the number of seconds per cubic foot (sec/
ft3) of gas being delivered to the furnace. If the dial is a one cubic foot dial, divide the number of seconds re­corded in step 2 by one. If the dial is a two cubic foot dial, divide the number of seconds recorded in step 2 by two.
4. Calculate the furnace input in BTUs per hour (BTU/hr). Input equals the sum of the installation’s gas heating value and a conversion factor (hours to seconds) di­vided by the number of seconds per cubic foot. The measured input must not be greater than the input indi­cated on the unit rating plate.
EXAMPLE: Installation’s gas heating (HTG) value: 1,000 BTU/ft
3
(Obtained from gas supplier) Installation’s seconds per cubic foot: 34 sec/ ft
3
Conversion Factor (hours to seconds): 3600 sec/hr Input = (Htg. value x 3600) ÷ seconds per cubic foot Input = (1,000 BTU/ft3 x 3600 sec/hr) ÷ 34 sec/ ft
3
Input = 106,000 BTU/hr
NOTE: The final manifold pressure cannot vary by more than ±
0.3” w.c. for Natural and
+ 0.5” for LP from the specified setting. Consult your local gas supplier if additional input rate adjustment is required.
5. Turn ON gas to and relight all other appliances turned
off in step 1. Be certain that all appliances are func-
tioning properly and that all pilot burners are operating. T emperature Rise Temperature rise must be within the range specified on the unit
rating plate. An incorrect temperature rise may result in condens­ing in or overheating of the heat exchanger. An airflow and tem­perature rise table is provided in the Specification Sheet appli­cable to your model. Determine and adjust temperature rise as follows:
1. Operate furnace with burners firing for approximately
ten minutes. Ensure all registers are open and all duct
dampers are in their final (fully or partially open) posi-
tion.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must
not be influenced by radiant heat by being able to “see”
the heat exchanger.
3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Al-
low adequate time for thermometer readings to stabi-
lize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce tem-
perature rise. Decrease blower speed to increase tem-
perature rise. Refer to Startup Procedure and
Adjustment -Circulator Blower Speeds for speed
changing details.
51
Page 52
OPERATION
Temperature Rise Measurement
SUPPLY AIR
RETUR N AIR
2. Determine the proper air flow for the cooling system. Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton. Most manu­facturers recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer’s instructions must be checked for required air flow. Any electronic air cleaners or other devices may require specific air flows, consult installation instructions of those devices for requirements.
3. Knowing the furnace model, locate the high stage cool­ing air flow charts in the Specification Sheet applicable to your model. Look up the cooling air flow determined in step 2 and find the required cooling speed and ad­justment setting.
Example: A *MVM960603BX furnace installed with a
2.5 ton air conditioning system. The air flow needed is 1000 CFM. Looking at the cooling speed chart for *MVM960603BX, find the air flow closest to 1000 CFM. A cooling airflow of 1000 CFM can be attained by se­lecting the cooling speed “C” and the adjustment to “normal”.
CIRCULATOR BLOWER SPEEDS
WARNING
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK
TURN
OFF
POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS
,
.
This furnace is equipped with a multi-speed circulator blower. This blower provides ease in adjusting blower speeds. The heating blower speed is shipped set at “B”, and the cooling blower speed is set at “D”. These blower speeds should be adjusted by the installer to match the installation requirements so as to pro­vide the correct heating temperature rise and correct cooling CFM.
Use the dual 7-segment LED display adjacent to the DIP switches to obtain the approximate airflow quantity. The airflow quantity is displayed as a number on the display, rounded to the nearest 100 CFM. The display alternates airflow delivery indication and the operating mode indication.
Example: The airflow being delivered is 1225 CFM. The display indicates 12. If the airflow being delivered is 1275, the display indicates 13.
1. Determine the tonnage of the cooling system installed with the furnace. If the cooling capacity is in BTU/hr di­vide it by 12,000 to convert capacity to TONs.
Example: Cooling Capacity of 30,000 BTU/hr. 30,000/12,000 = 2.5 T ons
4. Continuous fan speed is selectable at 25%, 50%, 75% or 100% of the furnace’s maximum airflow capability .
Example: If the furnace’s maximum airflow capability is 2000 CFM, the continuous fan speed will be 0.25 x 2000 or 500 CFM.
5. Locate the blower speed selection DIP switches on the integrated control module. Select the desired “cooling” speed tap by positioning switches 1 and 2 appropri­ately . Select the desired “adjust” tap by positioning switches 9 and 10 appropriately . Refer to the DIP switch chart for switch positions and their correspond­ing taps. V erify CFM by noting the number displayed on the dual 7-segment LED display .
6. The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using DIP switches 7 and 8. Refer to the following figure for switch positions and their corresponding taps. Refer to the bullet points below for a description of each ramp­ing profile. Verify CFM by noting the number displayed on the dual 7-segment LED display .
52
Page 53
DIP Switches
---
--- ---
--- --- ---
ON --- ---
--- --- --- ---
OFF --- --- ---
--- --- --- --- ---
OFF --- --- --- ---
--- --- --- --- --- ---
OFF
--- --- --- --- --- --- --- ---
Dip Switch
--- --- --- --- --- --- --- --- --- ---
OFF OFF
OFF ON
ON
ON ---
123456789101112131415161718
A OFF OFF --- --- --- --- --- --- --- --- --- --- --- --- -- - --- --- ---
--- --- --- --- --- --- --- --- --- --- --- ---
--- --- --- --- --- --- --- --- --- --- --- --- --- ---
--- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
ON OFF
ON ON
B ON OFF --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
C OFF ON --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
D
A --- --- OFF OFF - -- --- --- --- --- --- --- --- --- --- -- - --- --- ---
B------
C --- --- OFF ON --- --- --- --- --- --- --- --- --- --- --- --- --- ---
ON OFF
D --- --- ON ON --- --- --- --- --- --- --- --- --- --- --- --- --- ---
A --- --- --- --- OFF OFF --- --- --- --- --- --- --- --- --- --- --- ---
B --- --- --- ---
OFF OFF
--- --- --- --- --- --- --- --- --- --- --- --- --- ON
--- --- --- --- --- --- --- --- --- --- --- --- ---
C --- --- --- --- OFF ON --- --- --- --- --- --- --- --- --- --- --- ---
D --- --- --- --- ON O N --- --- --- --- --- --- --- --- --- --- --- ---
A --- --- --- --- --- ---
B --- --- --- --- --- --- ON OFF --- --- --- --- --- --- --- --- --- ---
C --- --- --- --- --- --- OFF ON --- --- --- --- --- --- --- --- --- ---
D --- --- --- --- --- --- ON ON --- --- --- --- --- --- --- --- --- ---
2-Stage
Plus 10% --- --- --- --- --- --- --- --- ON OFF --- --- --- --- --- --- --- ---
Minus 10% --- --- --- --- --- --- --- --- OFF ON --- --- --- --- --- --- --- ---
0 Tri m Adjust --- --- --- --- --- -- - --- ---
90 Seconds --- --- --- --- -- - --- --- --- --- --- OFF OFF --- --- --- --- --- ---
0 Tri m Adjust --- --- --- --- --- -- - --- --- ON ON --- -- - --- --- --- --- - - - - - -
120 Seconds --- --- --- --- --- --- --- --- --- --- ON OF F --- -- - --- --- --- ---
150 Seconds --- --- --- --- --- --- --- --- --- ---
180 Seconds --- --- --- --- --- --- --- --- --- --- ON ON --- --- --- --- --- ---
1-Stage
2 Stage Stat --- --- --- --- --- --- --- --- --- --- - -- --- ON --- --- --- --- ---
1 Sta ge Stat --- --- --- --- --- --- --- --- --- --- --- ---
Compressor
Enabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- ON
Disabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- OFF
Disabled --- --- --- --- --- --- --- --- --- --- --- --- --- ---
Compressor
Enabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
Enabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
Disabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- OFF
Enabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- -- - ---
Disabled --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- OFF
Tap
Purpose Function
Switch
Cooling
Speed Tap
Bank
Speed
Heating
1
Continuous
Tap
Fan
Speed
Cooling
Ramping
Taps
Adjust
2
Delay
Hea t Off
T-Stat Heat
Compressor
Bias
Dehum
3
Pull Up
Pull Down
Not applicable (Indicates factory setting)
---
Communic ating thermostats are used onl y with Bi as, Pull Up, Pull Dow n dip sw itc hes.
53
Page 54
OPERATION
Profile A provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
OFF
100% CFM 100% CFM
OFF
1 min
Profile B ramps up to full cooling demand airflow by first stepping up to 50% of the full demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1) minute OFF delay at 100% of the cooling airflow is provided.
OFF
50% CFM
1/2 min
100% CFM
100% CFM
OFF
1 min
Profile C ramps up to 85% of the full cooling demand air­flow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C also has a one (1) minute 100% OFF delay.
OFF
100% CFM
OFF
Profile D ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
OFF
OFF
7. Select the heating speed for your model from the heating speed chart in the Specification Sheet. The “adjust” setting (already established by the cooling speed selection) deter­mines which set of speeds are available. The selected speed must provide a temperature rise within the rise range listed with the particular model.
8. Select the desired “heating” speed tap by positioning switches 3 and 4 appropriately. Refer to figure above. Verify CFM by noting the number displayed on the dual 7-segment LED display.
In general lower heating speeds will: reduce electrical consump­tion, lower operating sound levels of the blower, and increase the outlet air temperature delivered to the home. The speeds avail­able allow the blower performance to be optimized for the particu­lar homeowner’s needs.
DIP SWITCHES
There are 18 DIP switches on the modulating furnace IFC. Switches are located in 3 rows, each having 6 switches. Switches are numbered from 1 to 18. The “ON” position is “UP’. The chart shows all 18 DIP switches, their function and their factory position.
Switches 1 & 2 Select cooling speed A, B, C or D. Factory setting is D (both switches up in the “ON” position. These switches are ignored when using a CTK0* communicating thermostat.
Switches 3 & 4 Select heating speed A, B, C or D. Factory setting is B (3 ON, 4 OFF) These switches are ignored when using a CTK0* communicating thermostat.
Switches 5 & 6 Select continuous fan speed A, B, C or D. Factory setting is B (5 ON, 6 OFF) These selections are based off of percentages of the maximum CFM that each model furnace is rated for; A = 25%, B = 50%, C = 75%, D = 100%. These switches are ignored when using a CTK0* communicating thermostat.
Switches 7 & 8 Select cooling ramping profiles A, B, C or D. Factory setting is A (both switches down in the “OFF” position).Each ramping profile provides a different routine for the indoor blower motor to follow in a call for cooling. Rather than bringing the motor up to cooling speed immediately, ramping profiles bring the motor up to cooling speed in stages.
NOTE: Reductions in CFM for ramping are not added to re- ductions in CFM for DEHUM. Example; CFM is reduced for the fist several minutes of a cooling call by 15%, if a call for DEHUM is present during this CFM reduction; CFM will not be reduced by another 15%. Rather, after the ramping time period has expired, the CFM would continue at the 15% re­duction to satisfy the DEHUM request. These switches are ignored when using a CTK0* communicating thermostat .
Switches 9 & 10 Select CFM Trim Adjustment. Choices are 0%, + 10%, -10%. Factory setting is A. Trim adjust­ments add or subtract from the CFM selections made by heat and cool CFM selections. Trim adjustments affect cool­ing, and heating fan speeds. These switches are ignored when using a CTK0* communicating thermostat .
Switches 11 & 12 Select fan off delay in heat. Choices are 90, 120, 150, or 180 seconds. Factory setting is C, 150 sec­onds. These switches are ignored when using a CTK0* com­municating thermostat.
Switch 13 Selects thermostat type for heating. Factory setting for this switch is OFF, this is the correct setting for a conventional single stage stat or a CTK02** communicating­modulating stat. To use a conventional two stage heating thermostat or a CTK0* thermostat, move this switch to the ON position.
54
Page 55
OPERATION
Switch 14 Selects compressor setup for cooling. Factory
position is OFF. This is the correct position for a single stage condensing unit. In this position, Y from the room thermostat would connect to Y1 on the IFC. Full CFM selected by switches 1 & 2 will be delivered during a Y1 call. If using a two stage outdoor unit, move this switch to the ON position and wire Y1 from the room stat to Y1 on the IFC, wire Y2 on the room stat to Y2 on the IFC. This switch is ignored when using a CTK0* communicating thermostat.
Switch 15 Selects DEHUM. Enabling this feature will re­duce CFM in a call for cooling by 15%. Factory position is OFF, in this position DEHUM is disabled. To use this feature the DIP switch must be turned to the ON position and a nor­mally closed dehumidistat be used. This switch is ignored when using a CTK0* communicating thermostat.
Switches 16, 17, 18 These are system switches critical to the ClimateTalk™ communicating network and must be left in the factory enabled ON position.
Pressure Switch Calibration Routine The modulating furnace must go through a pressure switch calibration rou­tine before it can begin its first heat cycle. This is performed automatically by the furnace and requires no action on the part of the installer other than to have the system compo­nents installed completely and correctly. On the initial power up, or any time that power to the furnace is switched off then back on again and a call for heat is applied, the furnace will go through a calibration routine. During the calibration rou­tine the IFC runs the induced draft blower at different speeds to determine the opening and closing points of the pressure switches. It records this information and uses it as reference points for determining the draft inducer speeds for all gas input rates from 35% - 100%.
Before beginning a calibration routine, the IFC will check that both pressure switches are in the open position.
· The IFC powers the draft inducer at a predetermined speed and checks to see if the LPS has closed
· If the LPS is not closed the IFC will increase the draft inducer RPM in small steps until it detects a closed LPS.
· The IFC then begins to reduce RPM until it detects that the LPS is open.
· It records the RPM point where the LPS went open
· The IFC then increases the inducer RPM by a large predetermined step and checks to see if the HPS is closed.
· If the HPS is not closed the IFC will increase the draft inducer RPM in small steps until it detects a closed HPS.
System
Ai r Cond itione r +
Furnace
He at Pum p +
Furnace
Furn ac e + Non-
Comm 1stg Air
Conditioner
S ystem O p e rating
Mode
Cooling Air Conditioner
Heati ng Furnace
Continuous Fan Thermostat
Co oling He at Pump
Heat Pum p H e ati ng
Only
Auxiliary He ating Fur nace
Continuous Fan Thermostat
Co oling Fur nace
Heati ng Furnace
Continuous Fan Thermostat
Airflow Deman d S our ce
He a t P ump
For example, assume the system is an air conditioner matched with a furnace. With a call for low stage cooling, the air conditioner will calculate the system’s low stage cool­ing airflow demand. The air conditioner will then send a fan request along with the low stage cooling airflow demand to the furnace. Once received, the furnace will send the low stage cooling airflow demand to the ECM motor. The ECM motor then delivers the low stage cooling airflow. See the applicable ComfortNet air conditioner or heat pump installa­tion manual for the airflow delivered during cooling or heat pump heating.
In continuous fan mode, the CTK0* thermostat provides the airflow demand. The CTK02** thermostat may be configured for one of threecontinuous fan speed settings allow for 25%, 50% or 75% airflow, based on the furnaces’ maximum airflow capability. During continuous fan operation, the thermostat sends a fan request along with the continuous fan demand to the furnace. The furnace, in turn, sends the demand to the ECM motor. The ECM motor delivers the requested continu­ous fan airflow.
FOSSIL FUEL APPLICATIONS
This furnace can be used in conjunction with a ComfortNet™ compatible heat pump in a fossil fuel application. A fossil fuel application refers to a combined gas furnace and heat pump in­stallation which uses an outdoor temperature sensor to deter­mine the most cost efficient means of heating (heat pump or gas furnace). When used with the CTK0* thermostat, the fur­nace/heat pump system is automatically configured as a fossil fuel system. The balance point temperature may be adjusted via the CTK0* thermostat advanced user menus (see CTK0* instructions for additional information).
55
Page 56
OPERATION
CTK0* WIRING
NOTE: Refer to Electrical Connections for 115 volt line
connections to the furnace. NOTE: A removable plug connector is provided with the control
to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and replaced. Multiple wires imust be twisted together prior to inserting into the plug connector. Failure to do so may result in intermittent operation.
Typical 18 AWG thermostat wire may be used to wire the sys­tem components. One hundred (100) feet is the maximum length of wire between indoor unit and outdoor unit, or between indoor unit and thermostat. Wire runs over (100) feet require larger gauge wire.
FOUR-WIRE INDOOR AND OUTDOOR WIRING
Typical ComfortNet wiring will consist of four wires between the indoor unit and outdoor unit and between the indoor unit and ther­mostat. The required wires are: (a) data lines, 1 and 2; (b) ther­mostat “R” (24 VAC hot) and “C” (24 VAC common).
CTK0**
12RC
12RC
12RC
System Wiring using Four-Wires
Thermostat
ComfortNet Compatible Furnace Integrated Control Module
ComfortNet Compatible AC/HP Integrated Control Module
TWO-WIRE OUTDOOR, FOUR-WIRE INDOOR WIRING
Two wires can be utilized between the indoor and outdoor units. For this wiring scheme, only the data lines, 1 and 2, are needed between the indoor and outdoor units. A 40VA, 208/230 VAC to 24VAC transformer must be installed in the outdoor unit to pro­vide 24VAC power to the outdoor unit’s electronic control. The transformer is included with the CTK01AA kit. See kit instruc­tions for mounting and wiring instructions. If using a CTK02 or CTK01BA, an accessory transformer is available (TFK01). Four wires are required between the indoor unit and thermostat.
R powering Y1, O and G simultaneously
The compressor and condenser fan are energized di­rectly from the Y1 terminal from the thermostat.
The circulator is energized after cool fan on delay.
If the ‘2 Stage Cooling’ DIP switch is set to:
ON, then circulator will run at low cooling speed with Y1 request
OFF, then circulator will run at high cooling speed with Y1 request (a Y2 request will be ignored)
The circulator will operate according to one of the se­lectable ramping profiles.
When the cool request is satisfied, the circulator is de-energized per one of the selectable ramping pro­files.
2ND STAGE COOLING – CONVENTIONAL THERMOSTAT
The ‘2 Stage Cooling’ DIP switch on the IFC must be ON to enable 2 stage cooling control with a conven­tional thermostat.
A call for 2nd stage cooling is signaled by the shorting of R to Y2 while a valid call for first stage cooling ex­ists.
After the cool fan on delay, the circulator is energized at the low cooling speed when the 1st stage cool re­quest is detected and switches to high cooling speed immediately after the 2nd stage cool request is detected.
The circulator will be controlled according to the se­lected ramping profile.
When the cool requests are satisfied, the circulator is de-energized per the selected ramping profile.
COOLING OPERATION WITH A COMMUNICATING THERMOSTAT
CONVENTIONAL SINGLE STAGE A/C
AND
The call for cooling will be communicated via the ClimateTalk™ protocol.
The Y1 terminal of the IFC becomes an output via the on board Y1 relay
The IFC does not provide short cycle protection.
The circulator operates as commanded by the com­municating thermostat.
NOTE: Use of the CTK0* transformer is recommended if installing a dual fuel/fossil fuel system. Failure to use the transformer in the outdoor unit could result in over loading of the furnace transformer.
1ST STAGE COOLING – CONVENTIONAL THERMOSTAT
A call for cooling is signaled by:
R powering Y1 and O simultaneously
56
COOLING OPERATION WITH A COMMUNICATING THERMOSTAT
OUTDOOR UNIT
AND
The furnace receives the CFM demand from the com­municating outdoor unit.
CALL FOR COOL WITH CALL FOR HEAT PRESENT – DUAL FUEL DEFROST OPERATION
While in defrost, the standard light off sequence will be followed. The IFC will then fire at 100% for the remain­der of the defrost call.
While in defrost the circulator will use the selected heat speed.
Page 57
OPERATION
FAN MODE CONVENTIONAL THERMOSTAT
Two seconds after G request becomes active without Y1 re­quest, IFC will run the circulator at the appropriate speed (as selected by the DIP switches), unless circulator is running as a result of Heat or Cool mode. The circulator speed re­quired by the heat or cool demand always has priority over G speed.
COMMUNICATING THERMOSTAT
If a conventional G request is present without a heat or cool request from the communicating thermostat, the circulator will run at the selected fan speed.
HUMIDITY CONTROL HUMIDIFIER OUTPUT – CONVENTIONAL THERMOSTAT
One set of isolated relay contacts are wired to a pair of termi­nals for connection to a humidifier. When the inducer is on the IFC closes the humidifier relay contacts, except from the calibration routine where the humidifier relay contacts are always open.
HUMIDIFIER OUTPUT – COMMUNICATING THERMOSTAT
One set of isolated relay contacts are wired to a pair of termi­nals for connection to a humidifier. Upon receipt of a Humidi­fication Requested Demand the IFC will:
Close the humidifier relay contacts
Energize the circulator at the circulation speed (G speed) unless the circulator is commanded to a differ­ent speed by a heat demand.
Dehumidification – Conventional Thermostat
DEHUM functionality is enabled by a DIP switch set­ting.
The IFC varies circulator speed operation based on the DEHUM signal from the thermostat
If 24VAC (R) is not connected to DEHUM (through a Humidistat) and both Y1 and O terminals are ener­gized, then the IFC control reduces the cooling CFM by 15%.
If both Y1 and O terminals are not energized, the DEHUM signal is ignored
DEHUM is ignored during any heating request.
LEARN PUSH-BUTTON
Pressing the learn button re-sets the communicating net­work and allows the IFC to search for communicating equip­ment The press and release of the button starts the same learning process as during power-up of the system.
CLIMATETALK™ COMMUNICATION LEDS
The IFC has two LEDs :
Red communications LED – Indicates the status of the network
OFF is normal condition.
2 slow flashes on power-up: ON for ¼ second, OFF for ¾ second, ON for ¼ second, OFF.
Continuous slow flash indicates communication fail­ure: ON for ¼ second, OFF for ¾ second…
Green receive LED – Indicates network traffic
Fast, sporadic flashes indicates normal bus commu­nication.
ON solid indicates a Data 1 / Data 2 miswire.
Low
Model Tap
*CVM960604CX*
*CVM960805DX*
*CVM961005DX*
*MVM960603BX*
*MVM960805CX*
*MVM961005DX*
*MVM961155DX*
*100% CFM shown. CFM will vary proportionally with the g a s va lve BTU/H input.
Stage
Cool A 370 660 1220 B 540 860 1340
C 790 1150 1460 D 980 1470 1590
A 530 900 1600 B 730 1100 1710
C 930 1430 1800 D 1220 1880 1910
A 500 780 1730 B 740 1070 1770
C 920 1380 1840 D 1160 1780 1870
A 390 630 950 B 550 800 1050
C 680 1000 1170 D 800 1210 1270
A 540 830 1600 B 750 1090 1690
C 980 1460 1800 D 1210 1800 1890
A 510 790 1810 B 710 1100 1850
C 910 1410 1890 D 1160 1830 1940
A 510 790 1810 B 710 1100 1850
C 910 1410 1890 D 1160 1830 1940
Airflow Table
High
Stage
Cool
100%
Heat
*CFM
57
Page 58
ABBREVIATIONS & DEFINITIONS
7. Select the heating speed for your model from the heat­ing speed chart in the Specification Sheet. The “ad­just” setting (already established by the cooling speed selection) determines which set of speeds are avail­able. The selected speed must provide a temperature rise within the rise range listed with the particular model.
8. Select the desired “heating” speed tap by positioning switches 3 and 4 appropriately . Refer to figure above. V erify CFM by noting the number displayed on the dual 7-segment LED display .
In general lower heating speeds will: reduce electrical consump­tion, lower operating sound levels of the blower, and increase the outlet air temperature delivered to the home. The speeds avail­able allow the blower performance to be optimized for the particu­lar homeowner’s needs.
BLOWER HEAT OFF DELAY TIMINGS
The integrated control module provides a selectable heat off de­lay function. The heat off delay period may be set to 90, 120, 150, 180 seconds using the DIP switches or jumper provided on the control module. The delay is factory shipped at 150 seconds but may be changed to suit the installation requirements and/or ho­meowner preference.
The indoor unit, outdoor unit and thermostat comprising a ComfortNet system “communicate” digitally with one another, cre­ating a two-way communications path. The thermostat still sends commands to the indoor and outdoor units. However, the ther­mostat may also request and receive information from both the indoor and outdoor units. This information may be displayed on the ComfortNet thermostat. The indoor and outdoor units also interact with one another. The outdoor unit may send commands to or request information from the indoor unit. This two-way digital communications between the thermostat and subsystems (in­door/outdoor unit) and between subsystems is the key to unlock­ing the benefits and features of the ComfortNet system.
CTK0* Thermostat
ComfortNet Compatible Furnace Integrated Control Module
ComfortNet Compatible
RC
AC/HP Integrated Control Module
40V A Transformer
208/230 VAC
12RC
12RC
12
24 VAC
ComfortNet System
OVERVIEW
NOTE: DIP switch #13 MUST be set to match thermostat type. To use the CTK01 communicating thermostat, DIP switch #13 must be set to ON position. This is also the cor­rect setting for a non-communicating 2-stage thermostat. To use the CTK02** modulating thermostat, check to make sure DIP switch #13 is in the OFF position (factory position). This is also the correct position when using a non-communicating single stage thermostat.
The ComfortNet system is a system that includes a ComfortNet compatible furnace and air conditioner or heat pump with a CTK0* thermostat. A valid ComfortNet system could also be a compat­ible furnace, CTK0* thermostat and non-compatible, single stage air conditioner. Any other system configurations are considered invalid ComfortNet systems and must be connected as a tradi­tional (or non-communicating) system (see Electrical Connec- tions for wiring connections).
A ComfortNet heating/air conditioning system differs from a non­communicating/traditional system in the manner in which the indoor unit, outdoor unit and thermostat interact with one another. In a traditional system, the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals. It is a one­way communication path in that the indoor and outdoor units typically do not return information to the thermostat.
System Wiring using Two-Wires between Furnace and AC/HP
and Four-Wires between Furnace and Thermostat
COMFORTNET COMPATIBLE FURNACE WITH NON-COMFORTNET
COMPATIBLE
Four wires are required between the furnace and thermostat. Two wires are required between the furnace control and single stage air conditioner. For this system configuration, the “Y1” terminal on the integrated furnace control becomes an output rather than an input. The “Y1” connection to the outdoor unit is made using both 4-position thermostat connectors in the CTK0* kit. Re­move the red keying tabs from the on-board connector block and position both 4-position connector such that “1”, “2”, “R”, “C”, and “Y1” positions are filled.
12RC
12RC
SINGLE-STAGE AIR CONDITIONER
CTK0* Thermostat
G
C Y
4-Position Connectors from CTK0* Thermostat Kit
W1 W2 Y1 Y2
ComfortNet Compatible
O
Non-ComfortNet Compatible Single Stage AC
Furnace Integrated Control Module
58
System Wiring between Furnace and Non-Communicating
Compatible Single Stage Air Conditioner
Page 59
ABBREVIATIONS & DEFINITIONS
Pressure Switch Calibration Routine The modulating
furnace must go through a pressure switch calibration rou­tine before it can begin its first heat cycle. This is performed automatically by the furnace and requires no action on the part of the installer other than to have the system compo­nents installed completely and correctly. On the initial power up, or any time that power to the furnace is switched off then back on again and a call for heat is applied, the furnace will go through a calibration routine. During the calibration rou­tine the IFC runs the induced draft blower at different speeds to determine the opening and closing points of the pressure switches. It records this information and uses it as reference points for determining the draft inducer speeds for all gas input rates from 35% - 100%.
Before beginning a calibration routine, the IFC will check that both pressure switches are in the open position.
· The IFC powers the draft inducer at a predetermined speed and checks to see if the LPS has closed.
· If the LPS is not closed the IFC will increase the draft inducer RPM in small steps until it detects a closed LPS.
The IFC then begins to reduce RPM until it detects that the HPS is open.
It records the RPM point where the HPS went open.
The IFC then adds a predetermined amount of draft inducer RPM to both the recorded points.
These new RPM points are the draft inducer speed for 35% (lowest input rate) and 100% (highest input rate).
The IFC then is able to control draft inducer speed through the IFC-VFD throughout the entire range of modulating operation.
100% (Max)
RPM
Closed LPS
RPM 1
Time
35% (Minimum)
Inducer Calibration Routine
ABBREVIATIONS AND DEFINITIONS
IFC: Integrated furnace control
HSI: Hot surface element
Closed HPS
RPM 2
LPS: Low pressure switch
IDB: Induced draft blower
HPS: High pressure switch
Variable Frequency Drive (VFD): Control of the in­duced draft blower is carried out by Variable Frequency Drive. By varying the voltage and frequency to the draft inducer, the RPM can be controlled. A section of the IFC is dedicated to this task.
Trial for Ignition Period (TFI): The period of time between initiation of gas flow and the action to shut off the gas flow in the event of failure to establish proof of the supervised ignition source or the supervised main burner flame.
Gas Valve Sequence Period: The total period of time of gas flow starting from the first initiation of gas to the final action to shut off the gas before going to lockout.
Ignition Activation Period (IAP): The period between energizing the main gas valve and deactivation of the ignition source prior to the end of TFI.
Flame Recognition Period (FRP): The period be- tween deactivation of the ignition source and the expi­ration of the TFI.
Flame Failure Response Time (FFRT): The period between loss of the supervised main burner flame and the action to shut off the gas supply.
Igniter Warm-up Time: The length of time allowed for the hot surface igniter to heat up prior to the initia­tion of gas flow.
Pre-purge Time: The period of time intended to allow for the dissipation of any unburned gas or residual prod­ucts of combustion at the beginning of a furnace oper­ating cycle prior to initiating ignition. Beginning from the moment the pressure switch is sensed closed and lasting until the ignition source is energized.
Inter-purge Time: The period of time intended to al­low for the dissipation of any unburned gas or residual products of combustion, just prior to initiating ignition retries during the Ignition Retries sequence.
Post-purge Time: The period of time to allow for the dissipation of any unburned gas or residual products of combustion at the end of a furnace burner operating cycle. Post-purge begins at the loss of flame sense.
Ignition Stabilization Period – The period between sensing of the main burner flame and the transition from the Ignition Firing Rate to the Target Firing Rate.
Ignition Recycles: The additional attempts within the same thermostat cycle for ignition after loss of the su­pervised ignition source or the supervised main burner flame.
Ignition Retries: The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the Trial for Igni­tion Period.
59
Page 60
ABBREVIA TIONS & OPERATION
Low Fire Rate: The lowest firing rate the IFC controls to during a heating cycle.
High Firing Rate: The maximum firing rate that an installed appliance can attain based on manifold ori­fices and the high pressure switch setting.
Ignition Firing Rate: The target firing rate at which the appliance always lights off. The appliance stays at this firing rate until the Ignition Stabilization Period expires. It then moves to the target firing rate called for by the operating sequence.
Target Firing Rate: The firing rate that the IFC con- trols the inducer to attain at a given time in the operat­ing sequence.
Heat Fan On Delay: The period between proof of the supervised main burner flame and the activation of the blower motor at the low heat speed.
Heat Fan Off Delay: The period between the loss of supervised main burner flame after the call for heat has ended and the deactivation of the blower motor.
2nd Stage On Delay: This applies to systems config­ured for 1-stage thermostats. The length of time oper­ating in normal low fire mode before switching to mid fire mode.
Auto Restart Delay: The time delay waited before the control is able to perform a new trial for ignition in the case of Soft Lockout.
Soft Lockout: A state caused a system fault such as loss of flame or pressure switch failure .
Hard Lockout: A state caused by a failure internal to the control or by a system fault such as a flame rollout
Fault Debouncing Time: The period between a sys­tem fault occurring and the IFC recognizing the fault has occurred. This time varies depending on the spe­cific fault.
Factory Shared Data: Data used by a ClimateTalk™ device for specific configuration parameters. This data will be programmed in at the Goodman factory.
Heat Exchanger Prepurge 15 sec --­HSI Warm U p 17 sec Same for all trials Ignition Acti vation Per iod 3 sec --­Flame Recognition Period 1 sec --­Trial F or Ignition 4 sec TFI = IAP + FRP Gas Valve Sequence Period 12 sec --­I gni ti on Stab il iz ati on Per io d 10 sec ---
Flame Debounce Period 2 sec
Post-purge 29 sec --­Inter-purge 30 sec --­A uto Restart Delay 60 m in --­Ign ition Retries 2 3 trials total Ignition Recycles – Flame Failure 2 3 flame los ses total Flame Failure Response Time 2 sec max @ 1uA
Other Parameters
Low Fire Rate 35% % of target high fire rate Ignition Fire Rate 80% % of target high fire rate High Fire Rate 100% ---
Time it takes to debounce flame presence or failure
---
Ignition Activation Chart
Ignition Retries:
When flame is not sensed during the Trial for Ignition Period:
The valve is de-energized.
The inducer remains energized at ignition speed dur­ing the Inter-purge Period.
The circulator if already running remains energized at the current CFM for the circulator fan off delay period.
When the Inter-purge Period expires, the control pro­ceeds to the HSI Warm-up and then a new Trial for Ignition is started again for up to a maximum of two additional trials (3 attempts total). After the third Trial for Ignition has failed to light the burner the IFC pro­ceeds to Soft Lockout through the Post-purge where the inducer remains energized at the ignition speed. Error code “E0” is flashed during the Soft Lockout pe­riod.
The retry count is cleared if flame is sensed for longer than 10 seconds after exiting Trial for Ignition, or upon exit of Soft Lockout.
Ignition Recycles:
When flame is established during Trial for Ignition, and then
lost:
The gas valve is de-energized.
The inducer moves to the ignition speed and holds for the Inter-purge Period.
60
Page 61
SERVICE & OPERATION
The circulator if already running remains energized at the current CFM for the circulator fan off delay period.
When the Inter-purge Period expires, the control pro­ceeds to the HSI Warm-up and then a new Trial for Ignition is started.
A maximum of two recycles (3 flame losses) are al­lowed on a single call for heat before the control pro­ceeds to Soft Lockout through the Post-purge where the inducer remains energized at the current speed. Error code “E0” is flashed during the Soft Lockout pe­riod.
The recycle count is not cleared until the current de­mand for heat is satisfied or upon exit of Soft Lockout.
Rollout Circuit Operation
If the manual reset rollout switch circuit opens during a heat-
ing cycle:
The valve is immediately de-energized.
The inducer will run for the Post-purge period at its current speed
If the circulator fan is on it will run for the normal fan off delay at the current heat speed.
An error code is logged and displayed indicating the rollout switch circuit has opened.
All future thermostat heat requests are ignored.. The IFC will remain in this state until the rollout switch
closes. Once the manual rollout switch has been re­set the IFC will clear the error code and return to nor­mal operation.
If the rollout switch circuit opens in any mode, other than Heat, it will be ignored.
Limit Switch Operation
If the limit switch circuit is open during a heating cycle:
The valve is immediately de-energized.
The inducer will run for the Post-purge period at its current speed.
The circulator is immediately energized at high heat speed. The IFC will remain in this state until the limit switch circuit closes.
The IFC logs and displays an error code indicating the limit circuit is open.
Once the limit switch circuit closes and a call for heat is present, a new ignition sequence is started and the circulator will remain energized for the selected fan off delay. If the burner is lit before expiration of the se­lected fan off delay, the fan off timing is stopped and the circulator will adjust to the speed requested by the heating sequence.
Pressure Switch Configuration
The IFC monitors the contacts of a SPST (single pole single throw) low pressure switch with a set point that ensures the switch will be closed at approximately 35% of the firing rate of the furnace.
The IFC monitors the contacts of a SPST high pres­sure switch with a set point that ensures the switch will be closed at approximately 100% of the firing rate of the furnace.
H Fitting
The H-fi tting
“conditions”
the ne gative
pressure signal whic h is applied t o
the gas valve
Restrictin g Orifi ce
Restrictin g Orifice
"H" Fitting
The low pressure switch assembly includes an H fitting as­sembly and tubing that provides pressure signals to the Honeywell amplified gas/air gas valve. The H fitting contains an orifice which conditions the negative air pressure control­ling the gas valve. This has the effect of allowing only smooth changes in air pressure to reach the gas valve.
Low Pressure Switch Operation
If a call for heat exists and the low pressure switch is closed already (before the ignition sequence has be­gun), the IFC will wait 5 minutes. After the 5 minute delay, and if the LPS is still closed, the IFC will log and display an error code indicating the low pressure switch is stuck closed. When the LPS is sensed open, the IFC clears the error code and resumes normal op­eration.
If the ignition sequence has begun and the low pressure switch fails to close within 30 seconds, the IFC logs and displays an error code indicating the low pressure switch is stuck open. The inducer continues to run for a total of 5 minutes, at which time the IFC de-energizes the inducer and then at­tempts the Calibration routine immediately. If during the 5 minute interval LPS is sensed closed or call for heat is re­moved, the IFC clears the error code and resumes normal operation.
If the limit switch circuit opens in any mode, other than Heat, it will be ignored.
61
Page 62
SERVICE & OPERATION
High Pressure Switch Operation
High Pressure Switch action is used to determine the inducer speed required to achieve the 100% firing rate of the appliance. The determination is made by the IFC during the calibration process.
The HPS must remain closed during 100% fire opera­tion. If it opens during 100% fire operation, the IFC will increase the inducer speed at a rate of 1% per sec in an attempt to re-close the pressure switch up to the maximum allowed RPM. If the HPS is re-closed suc­cessfully, the IFC will complete the Heat mode and perform the Calibration routine on the next call for heat. If the HPS remains open, the IFC will end the Heat mode through the Post-purge and perform the Calibra­tion routine immediately (error code “E9” is flashed until calibration routine is successful).
High Pressure Switch check takes place during the Calibration routine. If the switch is stuck open or closed calibration will not be completed and the appropriate error code will be logged and displayed.
Hot Surface Igniter Operation
The IFC energizes a relay to control the line voltage Hot Sur­face Igniter. The HSI warm up time will be fixed for all ignition trials. Both the continuity of the igniter and the ability of the relay to energize the igniter are continuously monitored dur­ing the Igniter Warm-up and Ignition Activation Periods.
ECM Motor
An Emerson® UltraTech® four wire indoor fan motor provides supply air to the conditioned space. This is the same motor used on Goodman & Amana previous generation communi­cating furnaces.
The ECM motor consists of two sections;
1. A motor body containing 3 phase motor windings
2. An electronic control module (end bell). In the event of a non-operating motor; the following items
should be checked. There are two harnesses which connect the blower motor to the IFC. The line voltage (5 Pin) harness provides 115 volts directly off of the IFC L1 and neutral termi­nals on ½ hp ECM motors. On furnaces with ¾ and 1 HP ECM motors, L1 is fed to the motor through an inductor coil. The inductor coil conditions the power supply to the motor smoothing out spikes and electrical noise. The low voltage harness is a 4 wire harness that supplies 12 volts DC to terminals 1 & 4 of the motor and communicating signals on terminals 3 & 4.
W ARNING
THE
CONTROL MODULE CONTAINS COMPONENTS WHICH CAN HOLD AN ELECTRICAL CHARGE FOR SEVERAL MINUTES TAKEN APART, IT MUST BE ALLOWED TO DISSIPATE VOLTAGE BY WAITING FIVE MINUTES BEFORE IT IS INSPECTED INTERNALLY BELL CAN BE SEPARATED FROM THE MOTOR BODY BY REMOVING THE THREE SCREWS WHICH JOIN THEM THE INTERANL HARNESS CAN BE SEPARATED AND MOTOR CAN THEN BE INSPECTED SEPARATELY
. O
. B
EFORE THE MOTOR IS
. THE
END
NCE THE SCREWS ARE REMOVED
. THE
CONTROL MODULE
.
,
The motor contains three windings of equal resistance + / ­10%. Resistance between windings is generally less than 10 ohms and will vary between models. To take this read­ing; the ohm meter leads are placed in the wiring harness, previously disconnected from the internal control unit con­nector.
Inspect capacitors inside the control unit for bulging or swol­len caps. The end bell should be replaced if components appear swollen or bulging. A functioning control unit should have a phase to phase resistance of greater than 100K between any two pins. A separated control unit is shown below. To take this reading; the ohm meter leads are placed in the end bell socket and not in the wiring harness.
3 Wire Motor-to-Control Harness
3 Pin Connector
Motor Connector
Beyond basic visual checks and voltage / resistance checks; the Emerson ECM motor may be tested with an Emerson UltraCheck-EZ™ diagnostic tool (Goodman Part UTT-01). This tool will test the motor windings and also the commu­nicating module of the motor.
62
Page 63
OPERA TIONAL CHECKS
LED LED St a tus Indication Po ss ible Caus es Corrective Action(s)
Red
Com munications
LED
Green
Receive
LED
Off • Normal condition • None • None
2 Flashes • Out-of-bo x reset • None
Rapid Flashing • Normal network traffic • Control is “talking” on
On Solid • Data 1/ Data 2 miss-wire
Operational Checks
BURNER FLAME
The burner flames should be inspected with the burner compart­ment door installed. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.
• Control power up
• Learn button depressed
• None
network as expected
• Data 1 and data 2 wires reversed a t furn ac e , thermostat or communicati ng compatible outdoor AC/HP
• Sho r t betwee n dat a 1 and data 2 wires.
• Sho r t betwee n dat a 1 or data 2 wires and R (24VAC) or C (24 VAC common).
• Check commun icatio ns wiring (da ta 1/ data 2 wires).
• Check wire connections at terminal block
• Check data 1/ data 2 voltage s.
A memory chip is only required when all communicating com­ponents have been replaced with service parts containing no shared data. If either an existing control board or ECM motor needed to be replaced, the service part would upload the necessary data from the remaining communicating compo­nent. In a fully communicating system, this would include the communicating thermostat and communicating outdoor unit control board as the necessary data is stored in all com­municating devices.
Check the Burner Flames for:
1. Stable, soft and blue.
2. Not curling, floating or lifting off.
Burner Flame
MEMORY CHIPS
Memory chips are a service only item and are not sent out with new equipment. They are used only in the rare occur­rence where communicating equipment shared data needs to be restored.
Memory chips should not be routinely installed at the time of installation. A memory chip is not required when an individual control board or motor is replaced.
A furnace void of shared data will not function in a legacy or a fully communicating installation. The furnace display would show “d0” indicating that there is no shared data in the fur­nace control board. If it is ever necessary to use a memory chip, the specific memory chip for your furnace number must be used.
63
Page 64
OPERA TIONAL CHECKS
To use a memory chip;
1. Power down all HVAC equipment in the system.
2. As when handling any electronic components, discharge any static electricity you may be carrying by touching grounded metal.
3. Insert the memory card in the slot on the control board.
4. Power the system back up and allow a few minutes for the network to establish communication between all de­vices.
5. Furnace control board will display “OP” or ‘ON” (depend­ing on board part number).
6. Check operation.
7. Memory chip can be left on the control board (recom­mended) or removed once equipment is powered down again.
PRESSURE SWITCHES
The pressure switches are normally-open (closed during opera­tion) negative air pressure-activated switches. They monitor the airflow (combustion air and flue products) through the heat ex­changer via pressure taps located on the induced draft blower and the coil front cover. These switches guard against insuffi­cient airflow (combustion air and flue products) through the heat exchanger and/or blocked condensate drain conditions.
FLAME SENSOR
The flame sensor is a probe mounted to the burner/manifold as­sembly which uses the principle of flame rectification to deter­mine the presence or absence of flame.
T roubleshooting
WARNING
Safety Circuit Description
A number of safety circuits are employed to ensure safe and proper furnace operation. These circuits serve to control any potential safety hazards and serve as inputs in the monitoring and diagnosis of abnormal function. These circuits are continu­ously monitored during furnace operation by the integrated con­trol module.
INTEGRATED FURNACE CONTROL (IFC)
The integrated control module is an electronic device which, if a potential safety concern is detected, will take the necessary pre­cautions and provide diagnostic information through an LED dis­play.
PRIMARY LIMIT
The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is a nor­mally-closed (electrically), automatic reset, temperature-activated sensor. The limit guards against overheating as a result of insuf­ficient conditioned air passing over the heat exchanger.
AUXILIARY LIMIT
The auxiliary limit controls are located on or near the circulator blower and monitors blower compartment temperatures. They are a normally-closed (electrically), auto-reset sensors. These limits guard against overheating as a result of insufficient condi­tioned air passing over the heat exchanger.
ROLLOUT LIMIT
The rollout limit controls are mounted on the burner/manifold as­sembly and monitor the burner flame. They are normally-closed (electrically), manual-reset sensors. These limits guard against burner flames not being properly drawn into the heat exchanger.
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER
BEFORE
Refer to the Troubleshooting Codes for assistance in determin­ing the source of unit operational problems. The dual 7-segment LED display will display an error code that may contain a letter and number. The error code may be used to assist in trouble­shooting the unit.
PERFORMING ANY SERVICE OR MAINTENANCE
RESETTING FROM LOCKOUT
Furnace lockout results when a furnace is unable to achieve igni­tion after three attempts during a single call for heat. It is charac­terized by a non-functioning furnace and a E 0 code displayed on the dual 7-segment display. If the furnace is in “lockout”, it will (or can be) reset in any of the following ways.
1. Automatic reset. The integrated control module will auto­matically reset itself and attempt to resume normal opera­tions following a one hour lockout period.
2. Manual power interruption. Interrupt 115 volt power to the furnace.
3. Manual thermostat cycle. Lower the thermostat so that there is no longer a call for heat for 1 -20 seconds then reset to previous setting.
NOTE: If the condition which originally caused the lockout still exists, the control will return to lockout. Refer to the Troubleshooting Codes for aid in determining the cause.
.
64
Page 65
MAINTENANCE
Maintenance
FILTERS
WARNING
TO
AVOID ELECTRICAL SHOCK, INJURY OR DEATH DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE HANDLE WITH CARE WITH BARE FINGERS, ROUGH HANDLING OR VIBRATION COUL D DAMAGE THE IGNITER RESU LTING IN PREMATURE FAILURE HANDLE THE IGNITER
. IF
YOU MUST HANDLE THE IGNITER
. T
OUCHING THE IGNITER ELEMENT
. O
NLY A QUALIFIED SERVICER SHOULD EVER
.
,
,
ANNUAL INSPECTION
The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure that all fur­nace components are in proper working order and that the heating system functions appropriately. Pay particular attention to the following items. Repair or service as necessary.
Flue pipe system. Check for blockage and/or leakage. Check the outside termination and the connections at and internal to the furnace.
Heat exchanger. Check for corrosion and/or buildup within the heat exchanger passageways.
Burners. Check for proper ignition, burner flame, and flame signal.
Drainage system. Check for blockage and/or leakage. Check hose connections at and internal to furnace.
Wiring. Check electrical connections for tightness and/or corrosion. Check wires for damage.
Filters.
CAUTION
TO
ENSURE PROPER UNIT PERFORMANCE, ADHERE TO THE FILTER SIZES
GIVEN IN THE RECOMMENDED MINIMUM FILTER SIZE TABLE OR
PECIFICATION SHEET APPLICABLE TO YOUR MODEL
S
.
FILTER MAINTENANCE
Improper filter maintenance is the most common cause of inad­equate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as re­quired.
BURNERS
Visually inspect the burner flames periodically during the heating season. Turn on the furnace at the thermostat and allow several minutes for flames to stabilize, since any dislodged dust will alter the flames normal appearance. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). They should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.
INDUCED DRAFT AND CIRCULATOR BLOWERS
The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No fur­ther lubrication is required. Check openings on motor housing for accumulation of dust which may cause overheating. Clean as necessary.
CONDENSATE TRAP AND DRAIN SYSTEM (QUALIFIED SERVICER ONLY)
Annually inspect the drain tubes, drain trap, and field-supplied drain line for proper condensate drainage. Check drain system for hose connection tightness, blockage, and leaks. Clean or repair as necessary.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sense signal. If the flame sense signal drops too low the furnace will not sense flame and will lock out. The flame sensor should be carefully cleaned by a qualified servicer using steel wool.
65
Page 66
SERVICING
SERVICING
S-1 CHECKING VOL T AGE ................................. 67
S-2 CHECKING WIRING..................................... 67
S-3A THERMOSTA T AND WIRING ....................... 67
S-3B HEATING ANTICIP A TOR/ CYLCE RA TE....... 68
S-4 CHECKING TRANSFORMER
AND CONTROLCIRCUIT........................... 68
S-300 CHECKING PRIMARY LIMIT CONTROL ...... 68
S-30 CHECKING AUXILIARY LIMIT CONTROL..... 68
S-302 CHECKING FLAME ROLLOUT CONTROL... 69
S-303 INDUCED DRAFT BLOWER MOTOR ......... 69
S-304 CHECKING MODULATING GAS VALVE..... 69
S-304ACHECKING INDUCTOR COIL....................... 69
S-305 CHECKING MAIN BURNERS ...................... 71
S-306 CHECKING ORIFICES ................................. 71
S-307 CHECKING GAS PRESSURE ..................... 71
S-308 CHECKING HOT SURFACE IGNITOR.......... 72
S-309 CHECKING FOR FLASHBACK .................... 72
S-310 CHECKING PRESSURE CONTROL ............ 72
S-311 HIGH ALTITUDE APPLICA TION .................... 73
S-312 CHECKING FOR DELA YED IGNITION........ 73
S-313 CHECKING INTEGRATED
IGNITION CONTROL BOARDS ............... 73
S-314 CHECKING FLAME SENSOR ................... 7 4
66
Page 67
SERVICING
S-1 CHECKING VOLTAGE
WARNING
HIGH VOLTAGE D
ISCONNECT ALL POWER BEFORE SERVICI NG OR
CHANGING ANY E LECTRI CAL WI RING. SOURCES MAY BE PRESENT. PROPERTY DAMAGE, PERS ONAL INJURY OR DEATH.
MULTIPLE POWER
FAILURE TO DO SO MAY CAUSE
1. Remove the blower door to gain entry to the Junction Box.
2. Remove cover from the Junction Box and gain access to incoming power lines.
With Power ON:
WARNING
INE VOLTAGE NOW PRESENT
L
3. Using a voltmeter, measure the voltage across the hot and neutral connections. Line voltage should measure 115 +/- 10%. Measure from black (hot) to ground should also read 115 volts +/- 10%. Measuring from white (neu­tral) to ground should read 0 volts
NOTE: To energize the furnace, the Door Interlock Switch must be engaged at this point.
4. No reading - indicates open wiring, open line voltage
fuse, no power, or faulty Door Interlock Switch from unit to fused disconnect service. Repair as needed.
5. With proper voltage at line voltage connectors, ener-
gize the furnace blower motor by jumpering terminals R to G on the integrated ignition control.
6. With the blower motor in operation, the voltage should
be 1 15 volts ± 10 percent.
7. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company of the condition.
8. After completing check and/or repair , replace Junction
Box cover and reinstall the service panel doors.
9. Turn on electrical power and verify proper unit opera-
tion.
S-2 CHECKING WIRING
WARNING
DISCONNECT ALL POWER BEFORE SERVICING.
1. Check wiring visually for signs of overheating, damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected open wires.
3. If any wires must be replaced, replace with AWM, 105°C. 2/64 thick insulation of the same gauge or its equivalent.
CHECKING THERMOSTAT, WIRING AND ANTICIPATOR
S-3A THERMOSTAT AND WIRING
WARNING
DISCONNECT ALL POWER BEFORE SERVICING.
1. Remove the blower compartment door to gain access to the thermostat low voltage wires located at the furnace integrated control module terminals.
2. Remove the thermostat low voltage wires at the furnace control panel terminal board.
3. Jumper terminals R to W on the integrated ignition con­trol.
With Power On (and Door Interlock Switch closed): NOTE: For this test, DIP switch #13 must be in OFF posi-
tion.)
WARNING
LINE VOLTAGE NOW PRESENT
4. Induced Draft Motor must run and pull in pressure
switch.
5. If the hot surface ignitor heats and at the end of the ig-
nitor warm-up period the gas valve opens and the burners ignite, the trouble is in the thermostat or wir­ing.
6. With power off, check the continuity of the thermostat
and wiring. Repair or replace as necessary .
If checking the furnace in the air conditioning mode, pro-
ceed as follows.
7. With power off, Jumper terminals R to Y (or Y1 or Y2
for two-stage models) to G .
8. Turn on the power .
9. If the furnace blower motor starts and the condensing
unit runs, then the trouble is in the thermostat or wir­ing. Repair or replace as necessary .
10. After completing check and/or repair of wiring and
check and/or replacement of thermostat, reinstall blower compartment door.
1 1. Turn on electrical power and verify proper unit opera-
tion.
67
Page 68
SERVICING
S-3B HEATING ANTICIPATOR/ CYLCE RATE
Older heating thermostats may have an adjustable anticipa­tor. This is a wire wound adjustable heater which is ener­gized during the "ON" cycle to help prevent overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail for any reason, the thermostat must be replaced.
Other thermostats have a cycle rate adjustment to adjust cycles per hour. This should be set to match system type.
S-4 CHECKING TRANSFORMER AND CONTROL
CIRCUIT
A step-down transformer 120 volt primary to 24 volt second­ary, 40 VA (Heating and Cooling Models) supplies ample capacity of power for either operation.
WARNING
HIGH VOLTAGE D
ISCO NN E CT ALL POWER BEFORE SERVI CING OR
CHANGING ANY ELECTRICAL WIRING. SOURCES MAY BE PRESENT. PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULT IPLE POWER
FAILURE TO DO SO MAY CAUSE
1. Remove blower compartment door to gain access to the thermostat low voltage wires located at the furnace inte­grated control module.
2. Remove the thermostat low voltage wires at the furnace integrated control module terminals.
With Power On (and Door Interlock Switch closed
WARNING
S-300 CHECKING PRIMARY LIMIT CONTROL
All modulating furnaces use a nonadjustable, automatic re­set, bi-metal type limit control. The primary limit control is located on the front panel of the furnace between heat ex­changer tubes. This is a normally closed control.
WARNING
HIGH VOLTAGE
ISCO NN E CT ALL POWER BEFORE SERVI CING OR
D
CHANGING ANY ELECTRICAL WIRING. SOURCES MAY BE PRESENT. PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULT IPLE POWER
FAILURE TO DO SO MAY CAUSE
1. Turn off all voltage sources
2. Remove the two wires from the limit switch
3. Using an ohmmeter, check for a closed circuit across the two limit contacts (this will be the same reading that you see by touching your two meter leads to­gether)
S-301 CHECKING AUXILIARY LIMIT CONTROL
Automatic Reset Auxiliary Limit Located in Blower Hous­ing
Modulating furnaces use an auxiliary limit(s) (automatic re­set) control connected in series with the main limit switch. If its temperature should be exceeded, it will open, interrupt­ing the voltage in the limit circuit. The auxiliary limit is lo­cated on the side of the blower housing. This is a normally closed switch. To check auxiliary limits; perform the follow­ing steps.
LINE VOLTAGE NOW PRESENT
3. Use a voltmeter, check voltage across terminals R and C. Must read 24 V AC.
4. No voltage indicates faulty transformer, open fuse, bad wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line voltage connections, fuse, splices, and blower door in­terlock switch.
6. If line voltage is available to the primary side of trans­former and not at secondary side, the transformer is inoperative. Replace.
7. After completing check and/or replacement of trans­former and check and/or repair of control circuit, rein­stall blower compartment door .
8. Turn on electrical power and verify proper unit opera­tion.
68
WARNING
HIGH VOLTAGE D
ISCO NNECT ALL POWER BEFORE SERVI CING OR
CHANGING ANY ELECTRICAL WIRING. SOURCES MAY BE PRESENT. PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER
FAILURE TO DO SO MAY CAUSE
1. Turn off all power sources
2. Remove the two wires from the auxiliary limit switch
3. Using an ohmmeter, check for a closed circuit across the two limit contacts (this will be the same reading that you see by touching your two meter leads to­gether)
Page 69
SERVICING
AUXILIARY LIMIT CONTROL
BLOWER HOUSING
AUXILIARY LIMIT CONTROL
Auxiliary Limit Control Location
S-302 CHECKING FLAME ROLLOUT CON-
TROL
A temperature activated manual reset control is mounted to the manifold assembly on modulating furnace, as shown in the following illustration.
FLAME ROLLOUT SWITCHES
*
*
*
*
2
*
**
Flame Rollout Switch Location
(90% Upflow Furnace Shown, Counterflow Similar)
WARNING
HIGH VOLTAGE D
ISCO NN E CT ALL POWER BEFORE SERVI CING OR
CHANGING ANY ELECTRICAL WIRING. SOURCES MAY BE PRESENT. PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Turn off all power sources
2. Remove the two wires from the roll out switch
3. Using an ohmmeter, check for a closed circuit across the two roll out switch contacts (this will be the same reading that you see by touching your two meter leads together).
MULT IPLE POWER
FAILURE TO DO SO MAY CAUSE
S-303 INDUCED DRAFT BLOWER MOTOR
Induced Draft Blower (IDB)
All modulating furnace models use a three phase induced draft blower to draw flue gases through the heat exchanger . The inducer uses ball bearings and is permanently lubricated. This motor is driven at varying speeds by the VFD (variable frequency drive) section of the IFC. The IFC takes typical single phase power supplied to the furnace and converts it to a three phase supply to operate the draft inducer at the desired speed. The windings of the induced draft motor will have equal resistance +/- 5%. Normal resistance readings at room temperature will range from 14-17 ohms. The voltage supplied by the IFC to drive the induced draft blower will vary from 15-1 10 volts A/C between any two windings. This would be read between any two of the three power wires between the IFC and the induced draft blower . This voltage to the IBD will vary between furnace models and is dependant on what percentage of maximum fire is being called for. The power wires are colored red, white and black. A green colored ground wire is also present.
S-304 CHECKING MODULATING GAS VALVE
Gas ValveModulating furnaces use a 24 VAC pneumati­cally operatedgas valve by Honeywell. The valve is ener­gized by the inte-grated furnace control on a call for heat, wired in series through the front-cover pressure switch. The firing rate percentage is determined by the negative pres­sure created by the operation of the draft inducer. The gas valve is factory set and non-adjustable in the field. Do not remove the seal covering the regulator screws or attempt to adjust either of the regulator screws. Even though the modu­lating gas valve is non-adjustable in the field, gas industry procedure dictates that the installing / servicing technician should know that the appliance is operating as designed before leaving newly installed or serviced equipment. The gas valve is equipped with 1/8 NPT fittings to access both the inlet and manifold gas pressures. To do a manifold gas pressure check, the furnace can be operated in field test mode. This mode will quickly bring the furnace up to high fire. To enter field test mode; during a call for heat, press the fault recall button twice within a five second period; when the dual seven segment displays show Ft, press the fault recall button again to enter field test mode.The furnace will stay in field test for five minutes or until the call for heat is satisfied. Gas valve orientation must be such that the switch is facing out towards the front of the furnace.
S-304A CHECKING INDUCTOR COIL
Wired in series with ¾ and 1 HP ECM motors; the inductor coil conditions the power supply to the motor, smoothing out spikes and electrical noise. With voltage applied to one side of the inductor coil, the output voltage to the motor should be the same as incoming voltage.
69
Page 70
SERVICING
MODULATING FURNACE PNEUMATIC TUBING DIAGRAM
Front Cover
Pressur e Sw itch
Black Tee
MUST
be left open
Low & High Pressure Switch Assembly
with “H” Fitting
+ Port is Open
to the Atmosphere
Modulating
Gas Valve
Negative (-)
Port on Gas Valve
For representation only. Ac tual unit may vary in appearance.
70
Upflow Model Shown
Page 71
SERVICING
S-305 CHECKING MAIN BURNERS
The main burners are used to provide complete combustion of various fuels in a limited space, and transfer this heat of the burning process to the heat exchanger.
Proper ignition, combustion, and extinction are primarily due to burner design, orifice sizing, gas pressure, primary and secondary air, vent and proper seating of burners.
Depending on the size of the furnace, each furnace will havefrom three to five inshot burners. Burners are precisely constructed of aluminized steel and designed to provide proper ignition and flame stability. When converting a modu­lating furnace to L.P. gas, the factory installed burners must be replaced by burners that come in the L.P. kit.
WARNING
D
IS CONNECT
In checking main burners, look for signs of rust, oversized and undersized carry over ports restricted with foreign ma­terial, etc, refer to Beckett Burner drawing.
ALL G
AS AND ELECTRICAL POWER SUPPLY.
A
GAS STREAM
B
The length of Dimension "A" determines the angle of Gas Stream "B".
DENT OR BURR
GAS
STREAM
B
A dent or burr will cause a severe deflection of the gas stream.
S-307 CHECKING GAS PRESSURE
Gas Supply Pressure Measurement
CAUTION
Beckett Burner
S-306 CHECKING ORIFICES
A fixed gas orifice is used in all Goodman® brand & Amana brand furnaces. That is an orifice which has a fixed bore and position as shown in the following drawing.
No resizing should be attempted until all factors are taken into consideration such as inlet and manifold gas pressure, alignment, and positioning, specific gravity and BTU con­tent of the gas being consumed.
Orifices should be treated with care in order to prevent dam­age. They should be removed and installed with a box-end wrench in order to prevent distortion. In no instance should an orifice be peened over and redrilled.
T
O PREVENT UNRELIABL E OPERATI ON OR E QUIPMENT DAMAGE, T HE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.
Gas inlet and manifold pressures should be checked in ac­cordance to the type of fuel being consumed.
The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be mea­sured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must
®
be measured with the burners operating. To measure the gas supply pressure, use the following procedure.
WARNING
D
ISCONNECT ELECTRICAL POWER AND SHUT OFF GAS SUPPLY.
1. After turning off gas to furnace at the manual gas shutoff valve external to the furnace, remove burner compart­ment door to gain access to the gas valve.
2. Connect a calibrated water manometer (or appropriate gas pressure gauge) at either the gas valve inlet pres­sure tap or the gas piping drip leg as shown in the follow­ing figures.
71
Page 72
SERVICING
GAS LINE
GAS SHUTOFF VALVE
GAS LINE TO FURNACE
OPEN TO ATMOSPHERE
DRIP L E G CAP WITH FITTING
MANOMETER HOSE
MANOMETER
Measuring Inlet Gas Pressure
(Alternate Method)
3. Turn ON the gas and electrical power supply and oper­ate the furnace and all other gas consuming appliances on the same gas supply line.
4. Measure furnace gas supply pressure with burners fir­ing. Supply pressure must be within the range specified in the following table.
T o test manifold pressure the furnace must be put into “field test mode” to bring the furnace up to 100% input.
5. Disconnect manometer after turning off gas at manual shutoff valve. Reinstall plug before turning on gas to fur­nace.
6. Turn OFF any unnecessary gas appliances started in step 3.
7. Turn on gas to furnace and check for leaks. If leaks are found, repair and then reinstall burner compartment door.
8. Turn on electrical power and verify proper unit operation.
The gas valve is factory set and non-adjustable in the field. Do not remove the seal covering the regulator screws or attempt to adjust either of the regulator screws. Even though the modulating gas valve is non-adjustable in the field, gas industry procedure dictates that the installing / servicing tech­nician should know that the appliance is operating as de­signed before leaving newly installed or serviced equipment. The gas valve is equipped with 1/8 NPT fittings to access both the inlet and manifold gas pressures. To do a manifold gas pressure check the furnace can be operated in field test mode. This mode will quickly bring the furnace up to high fire. To enter field test mode; during a call for heat, press the fault recall button twice within a five second pe­riod; when the dual seven segment displays show Ft, press the fault recall button again to enter field test mode. The furnace will stay in field test for five minutes or until the call for heat is satisfied. Gas valve orientation must be such that the switch is facing out towards the front of the furnace.
Manifold pressure for natural gas is pre-set to be between
3.2” WC to 3.8”WC. If the furnace has been converted to LP gas, the manifold pressure will be 9.7”WC to 10.3”W.
Manifold Gas Pressure
Natural Gas
Propane Gas
3.5" w.c.
10.0" w.c.
S-308 CHECKING HOT SURFACE IGNITOR
Modulating furnaces use a 115 volt silicon nitride hot sur­face igniter. This is the familiar and reliable 0131F00008S igniter with 17 second warm up time. At room temperature the igniter has a resistance range of 37 - 68 ohms. The H.S.I. isconnected electrically to the IFC by a 3/16" push­on connection.
S-309 CHECKING FOR FLASHBACK
Flashback will also cause burning in the burner venturi, but is caused by the burning speed being greater than the gas­air flow velocity coming from a burner port.
Flashback may occur at the moment of ignition, after a burner heats up or when the burner turns off. The latter is known as extinction pop.
Since the end results of flashback and delayed ignition can be the same (burning in the burner venturi) a definite attempt should be made to determine which has occurred. If flash­back should occur, check for the following:
1. Improper gas pressure - adjust to proper pressure (See S-307 CHECKING GAS PRESSURE)..
2. Check burner for proper alignment and/or replace burner.
3. Improper orifice size - check orifice for obstruction.
S-310 CHECKING PRESSURE CONTROL
The pressure control is a safety device to prevent the com­bustion cycle from occurring with inadequate venting caused by a restricted or blocked vent pipe on the modulating fur­nace. Also on the modulating furnaces there is a pressure control that will prevent the combustion cycle from occur­ring with inadequate condensate drainage due to a partial or blocked recuperator coil or drain.
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVI CING OR
D
INSTALLI NG THIS UNIT. BE PRESENT. DAMAGE, PERS ONAL I NJURY OR D EATH.
1. Remove burner compartment door to gain access to pres­sure switch(es).
2. Remove wires from the pressure switch(es) electrical ter­minals.
3. Using a VOM check from common terminal to NO (Nor­mally Open) - should read open.
MULTIPLE POWER SOURCES MAY
FAILURE TO DO SO MAY CAUSE PROPERTY
72
Page 73
SERVICING
If switch reads as above proceed to Step 4, otherwise re­place control.
4. Remove the pressure control hose from the control and interconnect with an inclined manometer as shown in the following figures.
MODULATING FURNACE PNEUMATIC TUBING DIAGRAM
Front Cover
Pressure Switch
be left open
Low & High Pressure Switch Assembly
Black Tee
MUST
with “H” Fitting
+ Port is Open
to the Atmosphere
Modulating
Gas Valve
Negative (-)
Port on Gas Valve
S-313 CHECKING INTEGRATED IGNITION
CONTROL BOARDS
NOTE: Failure to earth ground the furnace, reversing the
neutral and hot wire connection to the line (polarity), or a high resistance connection in the neutral line may cause the control to lockout due to failure to sense flame.
WARNING
T
O AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. BEFORE PERFORMING SERVICE LISTED BELOW.
The ground wire must run from the furnace all the way back to the electrical panel. Proper grounding can be confirmed by disconnecting the electrical power and measuring resis­tance between the neutral (white) connection and the burner closest to the flame sensor. Resistance should be less than 10 ohms.
The ignition control is a combination electronic and electro­mechanical device and is not field repairable. Complete unit must be replaced.
D
ISCONNECT POWER
Upflow Model Shown
For represent atio n onl y. Actual unit may vary in app ear a nce .
S-311 HIGH ALTITUDE APPLICATION
Modulating furnaces are approved up to 10,000 ft alti­tude. No kit or changes are needed.
S-312 CHECKING FOR DELAYED IGNITION
Delayed ignition is a delay in lighting a combustible mix­ture of gas and air which has accumulated in the combus­tion chamber.
When the mixture does ignite, it may explode and/or rollout causing burning in the burner venturi.
If delayed ignition should occur, the following should be checked:
1. Improper gas pressure - adjust to proper pressure (See S-307 CHECKING GAS PRESSURE).
2. Improper burner positioning - burners should be in lo­cating slots, level front to rear and left to right.
3. Carry over (lighter tube or cross lighter) obstructed ­clean.
4. Main burner orifice(s) deformed, or out of alignment to burner - replace.
WARNING
INE VOLTAGE NOW PRESENT
L
These tests must be completed within a given time frame due to the operation of the ignition control.
The ignition control is capable of diagnosing many furnace failures to help in troubleshooting. The PCBKF200 and PCBKF201 controls utilize a dual, 7-segment LED display to indicate diagnostic codes.
When the control is powered up normally the light will be on continuously. The PCBKF200 and PCBKF201displays will indicate "ON" when powered and in standby mode.
This can be used to test for 120 volts and 24 volts to the control since both must be present for the light to be on. If this step fails, check for 120 volts to the control and check the transformer and its associated wiring. If this step is suc­cessful give the control a call for heat and wait five (5) sec­onds or until the furnace goes into lockout. If the control detects a failure it will now be shown on the diagnostic indi­cator light/display. Refer to the Abnormal Operation section in the Sequence of Operation section of this manual for more detail on failure codes
The indicator light/display may be viewed by looking through the sight glass in the blower compartment door. The failure codes are retrieved via an on-board, momentary push button switch. Pressing the button for 2-5 seconds will force the failure codes to be displayed on the diagnostic indicator.
73
Page 74
SERVICING
S-314 CHECKING FLAME SENSOR
A flame sensing device is used in conjunction with the igni­tion control module to prove combustion. If proof of flame is not present the control will de-energize the gas valve and "retry" for ignition or lockout.
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVI CING OR
D
INSTALLI NG THIS UNIT. BE PRESENT. DAMAGE, PERSONAL INJURY OR DEATH.
Flame signal is continuously monitored by the IFC. The flame rod, flame rod wire, and proper grounding are all critical to proving the presence of flame. Because of the design of the Honeywell flame proving system, reading flame signal with a microamp meter will not provide reliable and consistent re­sults and is therefore not a recommended practice. The IFC has a built in warning (E6) if flame signal is approaching the low threshold.
MULTIPLE POWER SOURCES MAY
FAILURE TO DO SO MAY CAUSE PROPERTY
NOTE: Contaminated fuel or combustion air can create a
nearly invisible coating on the flame sensor. This coating works as an insulator causing a loss in the flame sense signal. If this situation occurs the flame sensor must be cleaned with steel wool.
74
Page 75
Troubleshooting
O
E0
E1
E2
Notes & Cautions
repair.
“Electrostatic Discharge”
section of manual.
x Turn power OFF prior to
x Read precautions in
module with current
x Replace integrated control
replacement parts.
x Turn power OFF prior to
repair.
with care.
x Igniter is fragile, handle
wool.
section for piping details.
x Clean flame rod with steel
x See “Vent/Flue Pipe”
x Turn power OFF prior to
repair.
with correct replacement
x Replace pressure switch
part.
repair.
with correct replacement
part.
blower with correct
replacement part.
assemble/install H fitting
x Turn power OFF prior to
x Replace pressure switch
x Replace induced draft
in factory configuration.
x Take care to
Corrective Actions
interruption.
switch operation (hose, wiring,
contact operation). Correct if
necessary. Make sure furnace is
draining properly.
sensor if coated and/or oxidized.
proper length, elbows, and
termination.
x Assure proper wiring to furnace
blower performance.
and integrated control module.
x Verify power to the furnace and
integrated control module is
stable and within specifications.
x Replace bad integrated control
module.
x Locate and correct gas
x Check front cover pressure
x Replace or realign igniter.
x Check flame sense signal. Sand
x Check flue piping for blockage,
x Verify proper induced draft
x Replace low stage pressure
switch.
x Repair short in wiring.
Repair/replace if necessary.
piping for blockage, proper
length, elbows, and termination.
necessary.
performance. Correct as
necessary.
or contact motion.
x Inspect pressure switch hose.
x Inspect flue and/or inlet air
x Check drain system. Correct as
x Check induced draft blower
connection.
x Correct pressure switch set point
x Tighten or correct wiring
x Clean H fitting.
Possible Causes
may be no gas to burners, front
cover pressure switch stuck open,
bad igniter or igniter alignment,
improper orifices, or
coated/oxidized or improperly
connected flame sensor.
Cause may be interrupted gas
supply, lazy burner flames
(improper gas pressure or
restriction in flue and/or
combustion air piping), front
cover pressure switch opening, or
improper induced draft blower
performance.
contacts sticking.
x Failure to establish flame. Cause
x Improper wiring to the furnace
or integrated control module.
EE
x Normal operation x None x Normal operation
x Loss of flame after establishment.
wiring.
x Low stage pressure switch
x Shorts in pressure switch circuit
E1
pinched, or connected improperly.
blocked drain system or weak
induced draft blower.
or malfunctioning switch
contacts.
wiring.
x Pressure switch hose blocked
x Blocked flue and/or inlet air pipe,
x Incorrect pressure switch set point
x Loose or improperly connected
blocked.
x Inducer not running.
x H fitting atmospheric port
ComfortNet
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
FAULT
Message Code
INTERNAL
module has an internal
x Integrated control
if
Thermostat)
None None
LOCKOUT E0
an excessive number of
ignition “retries” or
flame “recycles” (3
fault
x Normal operation
n
O
n
x Furnace lockout due to
total).
E0
error code.
PS1
CLOSED
switch circuit is closed at
x Low stage pressure
E1
start of heating cycle.
error code.
PS1 OPEN E2
switch circuit is not
closed.
x Low stage pressure
E2
error code.
Symptoms of Abnormal Operation
(Non-communicating & ComfortNet™
provides IF error code..
icon illuminated
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message
x LED display indicates
x Furnace fails to operate
x Furnace fails to operate
x Integrated control module LED display
icon illuminated.
provides
x ComfortNet thermostat “Call for Service”
x Integrated control module LED display
x ComfortNet thermostat scrolls “Check
Furnace” message.
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
with no further furnace operation.
x Induced draft blower runs continuously
provides
x Furnace fails to operate.
x Integrated control module LED display
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
provides
x Integrated control module LED display
75
Page 76
Troubleshooting
E3
E4
E
E5
E6
Notes & Cautions
repair.
applicable to your model
for allowable rise range
and proper circulator
x Turn power OFF prior to
x See Specification Sheet
speed.
repair.
x Turn power OFF prior to
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair.
automotive type
x Replace fuse with 3-amp
x Turn power OFF prior to
repair.
steel wool.
x Clean flame sensor with
x See "Vent/Flue Pipe"
section for piping details.
gas pressure.
x See rating plate for proper
Corrective Actions
blockage. Clean filters or
remove obstruction.
and performance. Correct speed
or replace blower motor if
necessary.
connection.
x Check filters and ductwork for
x Check circulator blower speed
x Tighten or correct wiring
in flame sensor wiring.
x Correct short at flame sensor or
x Check for lingering flame.
x Verify proper operation of gas
valve. Replace if necessary.
x Reset system power and verify
inducer is running properly.
x Replace inducer or integrated
control module, if necessary.
exchanger.
x Line up burners.
x Check for flame disturbance on
roll out when blower comes on.
x Install jumper.
x Inspect float switch.
x Line up orifice plate.
x Remove Blockage from heat
voltage wiring
coated/oxidized.
alignment.
blockage, proper length, elbows,
and termination.
x Clean flame sensor if
x Inspect for proper sensor
x Check inlet air piping for
rating plate. Adjust as needed.
x Compare current gas pressure to
Possible Causes
the heat exchanger. Blocked
filters, restrictive ductwork,
improper circulator blower speed,
or failed circulator blower motor.
x Insufficient conditioned air over
E3
wiring.
x Loose or improperly connected
circuit.
x Short to ground in flame sense
x Lingering burner flame.
x Slow closing gas valve.
E4
x Lingering Inducer motor
EC
overcurrent detected.
x Orifice plate out of position.
x Blocked heat exchanger.
Ed
x Burners out of alignment.
x Defective heat exchanger.
aux out.
x Open circuit between aux in or
EF
x Missing jumper.
x Open float switch..
x Short in low voltage wiring x Locate and correct short in low
Not
Displayed
.positioned in burner flame.
improper gas pressure or
x Lazy burner flame due to
combustion air.
x Flame sensor is coated/oxidized.
x Flame sensor incorrectly
E6
ComfortNet
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Message Code
Thermostat)
HIGH
LIMIT
x Primary limit.
E3
OPEN
error code.
IMPROPER
x Flame sensed when it
E4
FLAME
should not be present.
error code.
OR
FAULT
INDUCER
x Inducer motor
overcurrent fault.
EC
INDUCER
LOCKOUT
OPEN
ROLLOUT
switch is open
x Manual reset rollout
Ed
d error code.
OPEN
AUXILIARY
x Open auxiliary input.
EF
Not
Displayed
x Open Fuse
E5
error code.
WEAK
x Flame sense micro amp
E6
FLAME
signal is low
error code.
Symptoms of Abnormal Operation
(Non-communicating & ComfortNet™
furnace operation.
provides
x Circulator blower runs continuously. No
icon illuminated.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
runs continuously. No furnace operation.
provides
icon illuminated.
x Induced draft blower and circulator blower
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate
76
provides EC error code.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
icon illuminated.
x ComfortNet thermostat scrolls “Check
Furnace” message.
provides
x No furnace operation.
x Integrated control module LED display
provides Ef error code.
x No furnace operation.
x Integrated control module LED display
provides
x No furnace operation.
Power”.
x Integrated control module LED display
x ComfortNet thermostat displays “Battery
provides
x Normal furnace operation.
x Integrated control module LED display
Page 77
E8
E9
EA
0
Troubleshooting
Notes & Cautions
repair.
with correct replacement
x Turn power OFF prior to
part.
x Replace pressure switch
x Turn power OFF prior to
repair.
with correct replacement
part.
x Replace pressure switch
x Replace induced draft
blower with correct
replacement part.
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair
specific model.
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
removing memory card.
x Use memory card for the
x Insert memory card
x Turn power OFF before
x Error code will be cleared
once data is loaded.
Corrective Actions
Repair/replace if necessary.
piping for blockage, proper
length, elbows, and termination.
Check drain system. Correct as
necessary.
performance. Correct as
necessary.
or contact motion.
switch.
x Replace high stage pressure
x Inspect pressure switch hose.
x Repair short in wiring
x Inspect flue and/or inlet air
x Check induced draft blower
connection.
correct polarity.
x Correct pressure switch set point
x Tighten or correct wiring
necessary.
x Review wiring diagram to
x Verify proper ground. Correct if
x Check and correct wiring.
x Populate shared data set using
memory card.
Possible Causes
pinched, or connected
improperly.
blocked drain system or weak
induced draft blower.
point or malfunctioning switch
contacts.
contacts sticking.
wiring.
x High stage pressure switch
x Shorts in pressure switch circuit
E8
x Pressure switch hose blocked
x Blocked flue and/or inlet air pipe,
x Incorrect pressure switch set
wiring.
x Loose or improperly connected
x Polarity of 115 volt AC power to
EA
furnace or integrated module is
reversed.
x Reversed unit ground.
x Furnace does not contain any
d0
shared data.
ComfortNet
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Thermostat)
Message Code
PS2
CLOSED
switch circuit is closed at
x High stage pressure
E8
PS2 OPEN E9
switch circuit is not
closed.
operating.
start of heating cycle.
operating.
low stage only
x Furnace is operating on
x High stage pressure
x Induced draft blower is
low stage only
x Induced draft blower is
x Furnace is operating on
E9
error code.
error code.
REVERSED
x Polarity of 115 volt AC
PLTY
is reversed
EA
error code.
DATA
NO NET
x Data not yet on network.
d0
error code.
Symptoms of Abnormal Operation
(Non-communicating & ComfortNet™
furnace operates normally on low stage.
x Furnace fails to operate on high stage;
x Integrated control module LED display
provides
furnace operates normally on low stage.
provides
x Furnace fails to operate on high stage;
x Integrated control module LED display
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
provides d
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
x Integrated control module LED display
provides
x Furnace fails to operate.
x Integrated control module LED display
77
Page 78
Troubleshooting
4
0
1
2
3
Notes & Cautions
Corrective Actions
Possible Causes
Only
ComfortNetThermostat
repair
x Turn power OFF prior to
for the specific model. Re-
populate data using correct
x Verify shared data set is correct
has been rejected by integrated
control module
x Shared data set on memory card
d4
DATA
Message Code
INVALID MC
x Use memory card for the
specific model.
x Insert memory card
memory card if required.
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
removing memory card.
once data is loaded.
repair
correct replacement part.
with correct replacement
part.
repair
with correct replacement
part.
module with correct
replacement part.
repair
correct replacement part.
specific model
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
x Turn power OFF before
x Error code will be cleared
x Turn power OFF prior to
x Replace inductor with
connection.
through inductor. Replace if
circulator motor power leads or
RUN
open or short circuit.
x Verify continuous circuit
circulator motor power leads
disconnected.
x Open circuit in inductor or loose
x Tighten or correct wiring
x Loose wiring connection at
b0
MOTOR NOT
x Replace circulator motor
x Turn power OFF prior to
x Replace circulator motor
x Replace integrated control
x Turn power OFF prior to
x Replace motor with
x Use memory card for the
x Insert memory card
Replace if necessary.
connection.
01 Emerson tester
x Check circulator blower motor.
x Tighten or correct wiring
wiring connection at inductor
(3/4 Hp and 1 Hp models only).
circulator motor control leads.
x Failed circulator blower motor.
x Loose wiring connection at
b1
COMM
MOTOR
x Check blower motor with UTT-
x Failed circulator blower motor.
x Failed integrated control module.
module. Replace if necessary.
x Check integrated control
horse power is the same
specified for the specific furnace
x Verify circulator blower motor
in furnace.
x Incorrect circulator blower motor
b2
MOTOR
MISMATCH
model. Replace if necessary.
integrated control module.
x Incorrect shared data set in
x Verify shared data set is correct
for the specific model. Re-
populate data using correct
memory card if required.
x Turn power OFF before
removing memory card.
x Error code will be cleared
once shared data and
motor horse power match.
x Turn power OFF prior to
x Check filters for blockage.
x Blocked filters.
b3
MOTOR
repair.
Clean filters or remove
obstruction.
x Restrictive ductwork.
x Undersized ductwork.
LIMITS
Remove obstruction. Verify all
x Check ductwork for blockage.
x High ambient temperatures.
registers are fully open.
sized for system. Resize/replace
ductwork if necessary.
"Location Requirements &
Considerations" for furnace
x Verify ductwork is appropriately
installation requirements.
x See "Product Description" and
78
Fault Description
LED Codes
Diagnostic/Status
Symptoms of Abnormal Operation
(Non-communicating & ComfortNet™
Thermostat)
data.
x Invalid memory card
d4
error code.
operation.
provides d
icon illuminated.
x Operation different than expected or no
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
is not running when it
should be running.
x Circulator blower motor
b0
error code.
provides b
x Furnace fails to operate.
icon illuminated.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
module has lost
communications with
circulator blower motor.
x Integrated control
b1
error code.
provides b
x Furnace fails to operate.
icon illuminated.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
horse power in shared
data set does not match
circulator blower motor
x Circulator blower motor
horse power.
b2
error code.
provides b
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
x Integrated control module LED display
x Circulator blower motor
b3
x Furnace operates at reduced performance.
is operating in a power,
temperature, or speed
limiting condition.
error code.
provides b
x Airflow delivered is less than expected.
x Integrated control module LED display
Page 79
4
5
6
7
9
Troubleshooting
Notes & Cautions
repair.
x Turn power OFF prior to
Corrective Actions
grills/registers, duct system, and
furnace air inlet/outlet for
blockages.
x Check filters, filter
x Turn power OFF prior to
x Check circulator blower for
repair
obstructions. Remove and
replacement part.
x Replace motor with correct
repair/replace wheel/motor if
necessary.
x Replace wheel with correct
x Check circulator blower motor
replacement part.
shaft rotation and motor.
Replace motor if necessary.
x Turn power OFF prior to
x Check power to furnace. Verify
repair.
line voltage to furnace is within
the range specified on the
furnace rating plate.
x See "Product Description" and
"Location Requirements &
Considerations" for furnace
installation requirements.
x Turn power OFF prior to
x Check integrated control module.
repair.
Verify control is populated with
replacement part(s).
x Replace with correct
correct shared data set. See data
errors above for details.
x Use memory card for the
x Check for locked rotor condition
specific model.
(see error code above for
details).
x Turn power OFF prior to
x Check filters for blockage.
repair.
Clean filters or remove
obstruction.
Remove obstruction. Verify all
registers are fully open.
sized for system. Resize/replace
x Check ductwork for blockage.
ductwork if necessary.
x Verify ductwork is appropriately
Possible Causes
ComfortNet
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
x Abnormal motor loading, sudden
b4
MOTOR
Message Code
x Circulator blower motor
change in speed or torque, sudden
TRIPS
senses a loss of rotor
b4
blockage of furnace air inlet or
outlet.
filters, very restrictive ductwork,
blockage of furnace air inlet or
outlet.
housing.
x High loading conditions, blocked
control.
senses high current.
x Circulator blower motor
bearings.
x Obstruction in circulator blower
x Seized circulator blower motor
b5
ROTOR
MTR LCKD
fails to start 10
consecutive times.
x Circulator blower motor
b5
x High AC line voltage to furnace.
x Failed circulator blower motor.
x Low AC line voltage to furnace.
x High ambient temperatures.
b6
VOLTS
MOTOR
shuts down for over or
under voltage condition.
x Circulator blower motor
x Circulator blower motor
shuts down due to over
temperature condition on
b6
power module.
module.
x Error with integrated control
x Motor has a locked rotor
b7
MOTOR
PARAMS
does not have enough
information to operate
x Circulator blower motor
b7
condition.
properly.
x Blocked filters.
x Restrictive ductwork.
x Undersized ductwork.
b9
LOW ID
AIRFLOW
consecutive times.
x Airflow is lower than
demanded.
x Motor fails to start 40
b9
Thermostat)
error code.
Symptoms of Abnormal Operation
(Non-communicating & ComfortNet™
provides b
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
x Integrated control module LED display
error code.
provides b
x Furnace fails to operate.
icon illuminated.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
error code.
error code.
error code.
provides b
icon illuminated.
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
x Integrated control module LED display
provides b
x Furnace fails to operate.
icon illuminated.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check
Furnace” message.
x Furnace operates at reduced performance.
provides b
x Integrated control module LED display
79
Page 80
Status Codes
80
NO POWER NORMAL OPERATIO N
On
INDICATES AIRFL OW, FO LL OWED BY CFM
A
BLOWER MO TO R NOT RUNNING
b0
BLOWE R CO M M UNICATION ERROR
b1
BLOWER HP MIS-MATCH
b2
BLOWER MO TO R O PERATING IN POWER, TEMPERATURE, OR SPEED LIMIT
b3
BLOWER M OTOR CURRENT TRIP O R L O ST ROTOR
b4
BLOWER MO TO R LO CKED ROTOR
b5
BLOWER OVER/ UNDER VOLTAGE TRIP OR OVER TEM PERATURE TRIP
b6
INCOMPLETE PARAMETERS SENT TO MOTOR
b7
LOW INDO OR AIRFLOW
b9
CLIMATETALK COMPRESSOR COOLING / CONVENTIO NAL COMPRESSOR COOLI NG
C
WHEN 1-STAG E CO MPRESSOR I S SE T UP LOW STAGE CO OL
C1
HIGH STAGE COOL
C2
CLIMA TETAL K CO M PRESSOR COOLING W I TH DEHUM I FICATION / CONVENTIONAL COMP RESSOR COOLING W ITH DEHUMIDIF I CA TION WHEN 1-STA GE
d
COMPRESSOR IS SET UP DATA NOT YET ON NETWORK
d0
CONVENTIONAL 1-STAGE COMPRESSOR COOLING WITH DEHUM I DI FI CAT ION WHEN
d1
2-STAGE COMPRESSOR I S SET UP CONVENTIONAL 2-STAGE COMPRESSOR COOLING WITH DEHUM I DI FI CAT ION WHEN
d2
2-STAGE COMPRESSOR I S SET UP INVALID MEMORY CARD DATA
d4
DEFROST DEM AND
dF
LOCKO UT DUE TO EXCESSIVE RETRIES O R RECY CL ES
E0
LOW STAGE PRESSURE SWITCH STUCK CLOSED AT START OF HEATING CYCLE
E1
LOW STAGE PRESSURE SWITCH STUCK OPEN
E2
OPEN HIG H LIMI T SWI TCH
E3
FLAM E DET ECT ED W HEN NO FLAME SHOULD BE PRESE NT
E4
OPEN FUSE
E5
LOW FLAM E SIGNAL
E6
IGNITER FAULT OR IMPROPER GROUNDING
E7
HIGH STAGE PRESSURE SWITCH STUCK CLOSED AT START OF HEATING CY CLE
E8
HIGH STAGE PRESSURE SWITCH STUCK OPEN
E9
REVERSED 115 VAC POLARITY
EA
INDUCER MOTOR O VERCURRENT FAULT
EC
ROLLO UT SWI TCH OPEN
Ed
AUXILIARY INPUT OPEN
EF
CONTINUOUS F AN
F
FIELD TEST MODE
Ft
INDICATES GAS HEAT, FO L LOWED BY PERCENTAGE OF DEM AND
H
HIGH HEAT = 100%
HI
INTERNAL FAULT
IF
CLIMATETALK COMPRESSOR HEATING / CONVENTI O NAL COMPRESSOR HEATING
P
WHEN 1-STAG E CO MPRESSOR I S SE T UP CONVENTIO NAL 1-STAGE COM PRESSOR HEATING
P1
WHEN 2-STAG E CO MPESSOR I S SE T UP CONVENTIO NAL 2-STAGE COM PRESSOR HEATING
P2
WHEN 2-STAG E CO MPESSOR I S SE T UP % OF HI GH HEA T
50
Page 81
Wiring Diagram
T
O
H
A
F
R
U
S
E
T
I
N
G
I
1
2
RD
WH
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
C
E
A
H
WH
WH
WH
:
S
E
T
O
N
A
E
H
T
E
S
.
1
A
M
.
2
A
F
U
N
W
D
E
S
U
O
Y
N
A
F
I
.
3
N
R
U
F
C
A
G
N
I
R
I
W
1
T
S
A
E
L
U
M
T
I
N
U
.
4
N
A
.
C
.
E
.
N
A
C
E
R
O
T
.
5
T
N
E
C
E
R
D
N
A
T
S
N
I
0140F00863-B
*MVM96_A*, *CVM96_A*
O
L
A
F
E
S
N
)
U
T
O
N
R
T
I
R
F
E W
.
S
S
)
(
4
)
4
(
)
(
1
)
H
U
M
OPTIONAL
G
L
E
I
A
OPTIONAL
H
OPTIONAL
H
O
M
E O
S
R
E
S
O
L
N
I
T
C
D
I
I
T
D
N
L
N
G
J
I
O
U
T
N
C
I
N
D
O
A
I
R
C
C
U
R
A
I
L
W
B
L
L
E
C
R
T
O
N
L
E
R
N
C
A
D
I
Ø
3
R
W
L
B
I
I
F
U
D
M
I
T
S
U
R
A
F
R
I
G
N
E
T
I
R
5
1
1 A
V
C
2
4
E
U
A
T
X
S
O
C
H
I
C
I
R
R
E
I
F
U
Q
E
L
E
I
F
L
E
I
F
W
S
I
N
G
I
W
S
E
V
O
O
R
P
5
1
1
W
O
P
E
V
O
O
R
P
V
E
D
A
W
O
P
E
S
O
T
R
P
N
A
D
N
N
X
B
O
O
R
O
R
T R
G
C
I
E
R
R
E
E
C
V
A
C
Y
R
I
A
I
L
NO
N
FRONT COVER PRESS. SWITCH
N
D
O
O
R
I
R
A
C
O
U
T
A
L
B
L
W
R
M
P
I
E
N
G
D
P
S
D
H
C
T
I
R
E
T
H
C
T
I
R
U
C
R
E
D
.
T
Ø
0
6
V
/
1
/
C
Z
H
A
E
C
R
E
T
E
C
I
N
R
W
V
R
U
P
O
D
G
H
T
I
W
Y
L
P
P
U
S
R
T
N
E
R
R
U
N
O
I
T
C
T
C
E
N
N
O
C
S
I
D
:
G
N
I
E
R
O
F
E
B
R
E
.
G
N
I
G
R
I
N
I
W
C
I
E
B
T
S
U
M
T
I
N
E R
D
E
Z
I
R
A
L
O
P
Y
L
R
.
D
E
D
N
U
O
N
D
I
S
N
C
N
C
O
E
T
U
E
R
T
A
N
L
N
D
N
E
U
E
U
N
T
N
E
U
T
N
E
A
V
4
0
N
R
A
T
S
O
F
O
U
T
A
M
I
T
I
L
INT EGRATED CO NTROL MODULE
L
R
T
A
R
L
A
R
L
A
U
R
T
A
L
R
R
E
M
R
E
E
R
S
P
M
T
A
I
R
Y
C
L
T
I
M
N
I
O
R
T
O
L
O
L
W
R
F
I
P
E
R
S
E
.
S
S
T
C
I
W
H
C
C
M
A
N
U
R
S
U
R
A
L
E
T
T
E
O
O
L
L
C
L
T
I
M
I
O
N
T
R
O
S
L
O
G
R
G
T
N
D
E
C
I
L
M
E
T
(
S
E
R
P
N
E
R
E
C
I
V
M
P
C
A
G
S
V
A
L
V
E
D
N
D
N
)
P
E
R
U
S
T
V
4
2
.
M
U
H
E
R
U
S
S
E
E
G
R
A
P
T
S
-
O
W
T
R
E
W
O
L
B
D
I
I
W
E
C
R
F
W
O
L
S
E
R
P
C
T
I
W
S
T
I
U
C
R
I
C
2
R
O
T
C
E
N
N
O
C
G
N
I
T
A
L
U
D
O
M
A
G
V
S
A
Y
E
N
O
H
(
U
P
WH
BK
RD
C
E
V
L
)
W
L
L
E
M
P
L
A
U
N
A
M
L
G
N
I
S
(
U
P
T
U
A
T
E
S
E
R
O
N
O
C
T
I
M
I
L
R
O
3
H
W
2
D
R
B
1
K
T
R
A
P
M
O
C
R
E
N
R
U
B
O
L
B
T
R
A
P
M
O
C
R
E
W
O
T
U
A
I
X
U
A
T
I
M
I
L
S
R
I
E
C
E
R
U
S
H
2
1
E
R
C
E
R
P
R
T
E
M
E
M
R
A
I
L
O
C
N
R
B
Y
G
N
O
L
T
U
O
L
L
O
R
T
E
S
N
O
5
4
L
O
R
T
N
O
K
P
Y
R
A
M
I
L
O
T
N
T
N
T
E
S
E
Y
R
L
O
R
T
N
Y
L
B
M
E
S
S
A
H
C
T
R
O
O
L
Y
C
Y
G
N
O
R
F
U
S
S
E
R
P
L
O
R
T
N
O
C
T
I
M
I
)
U
T
B
k
C
U
D
N
I
A
R
D
W
O
L
B
D
N
G
U
P
L
Y
BR
I
F
H
G
I
H
U
S
S
E
R
P
C
T
I
W
C
O
C
T
S
E
R
S
D
E
T
F
R
E
S
O
N
R
O
R
E
V
C
T
I
W
R
O
BR
H
OR
OR
PU
ID BLOWER
CONNECTOR
1 2
3
BL
FLAME
SENSOR
FURNACE CONTROL MODULE
D
I
COOL TAPS
HEAT TAPS
FAN TAPS
RAMPING
ADJUST
DELAY
COOL SETUP
HEAT SETUP
PULL U P
DEHUM
BIAS
E
S
U
F
V
4
A
2
3
R
T
M
M
K
B
S
S
E
N
R
T C
H
F E M
5
0 S
D
L ,
B
L
B
D
R
Y
G
4
3
2
1
O
T
A
L
U
C
R
I
C
O
R
N
O
R
O
T
A
P
I
C
I
T
N
A
R
U
T
S
N
E
E
H
T
S
U
M
E
T
A
.
C
°
E
B
T
O
L
H
T
L
R
P
E
D
N
(
Y
D
E
I
F
I
C
E
P
S
S
'
R
E
.
G
N
I
C
I
V
R
E
R U
C
E
O
E
R
I
W
L
A
N
I
G
I
R
O
D
E
C
A
L
P
E
R
E
B
T
T
A
G
N
I
V
A
H
L
A
I
O
C
R
E
P
P
O
C
E
S
Y
L
T
N
E
N
A
M
R
E
P
.
S
E
D
O
C
L
A
E
T
L
U
A
F
0
1
T
S
A
L
O
F
H
C
T
I
W
S
S
S
T
A
T
S
O
M
R
E
H
T
MODULATING INTE RGRATED
G
N
A
O
S
C
I
T
L
E
D
'
S
HEAT OFF
DIP SW IT C HES
PULL DOWN
R
2Y11
T
H
4
V
2
5 4
3 2 1
R
E
W
O
L
B
R
O
M
R
M
E
O
H
T
N
E
M
E
C
A
L
P
E
R
D
E
I
L
P
P
U
S
S
A
E
B
T
S
U
M
T
I
,
R
U
T
A
R
E
P
M
E
O
S
R
O
T
C
U
D
N
A
D
E
D
N
U
O
R
G
C
E
R
T
S
O
M
,
S
H
T
E
R
O
M
R
A
)
S
T
U
P
N
I
1
GY
1
2
OR
3
W1
W2
G
C
R
E
A
M
T
O
C
S
T
N
O
N
K
B
H
W
R
G
K
P
WH
A
7
.
0
T
A
T
A
T
S
S
U
M
S
T
R
A
P
T
E
H
T
H
T
I
W
I
W
D
E
C
A
L
P
E
R
A
F
O
G
N
I
T
A
R
E
.
Y
L
N
M
R
O
F
N
O
C
D
N
S
A
E
L
O
T
T
N
E
S
D
N
O
C
E
S
2
N
2
OR
45
6
OR
Y2
C
E
O
T
I
G
.
S
P
M
E
B
T
H
T T
O
T
T
L
I
H
W
LINE
H
S
I
E
C
A
HUM
3
7
89
DEH UM
O
N
S
D
N
E
NEUTRAL
RD
BK
4
BR
BR
10
11
12
A
U
X
YL
BL
RD
BK
GY
BK
L
I
O
C
R
O
T
C
U
D
N
I 7
1
1
,
U
T
B
k
0
9
,
U
T
B
k
0
D
O
M
U
T
B
k
5
S
L
E
Y
L
N
O
D
O
C
R
O
L
O
C
K
N
I
P
K
P
W
O
R
B
R
B
I
H
W
H
W
E
U
L
B
L
B
Y
A
R
G
Y
G
D
E
R
D
R
O
L
L
E
Y
L
Y
N
A
R
O
R
O
R
U
P
U
P
P E
E
R
G
R
G
C
A
L
B
K
B
JUNCTION BOX
K
E
R
E
R
H
F
S
B
H
W
A
E
M
A
L
R
O
S
N
E
CHASSIS
GROUND
BL
W
DISCONNECT POWER BEFORE SERVICING WIRING TO UNIT MUST BE PROPERLY POLARIZED AND
N
U
O
R
G
T
C
E
N
N
O
C
S
I
D
Ø /60 HZ PO WER SUPPLY WITHTO 11 5VAC/1
OVERCURRENT PROTECT ION DEVICE
:
G
N
I
N
R
.
D
E
D
O
O
R
D
T
H
W
C
S
I
R
I
N
C
O
C
T
I
D
O
U
L
U
T
U
0
k
7
k
B
T
9
0
,
,
B
5
1
k
1
B
T
U
M
O
D
S
L
E
Y
L
O
N
GR
E
N
L
INTEGRATED CONTROL MODULE
I
C
A
E
3
2
1
U
M
H
G
N
I
S
F
BK
I
L
N
E
40 VA
TRANSFORMER
4
2
C
A
V
GY
5
1
1
C
A
V
H
W
H
W
K
B
R
E
W
O
L
B
T
N
E
M
T
R
A
P
M
O
C
H
C
T
I
W
S
R
O
O
D
N
E
H
W
N
E
P
O
(
)
N
E
P
O
R
O
O
D
:
S
E
N
E
T
W
E
G
E
L N
K
A
T
L
W
O
O
V
L
A
T
L
W
O
O
L
V
E
G
A
T
L
O
V
I
H
E
G
A
T
L
O
V
I
H
N
O
I
T
C
N
U
J
L
A
N
I
M
R
E
T
T
L
A
N
R
E
T
N
I N
E
T
A
R
G
E
T
I
N
N
O
C
G
U
L
P
3
U
A
F
S
E
R
T
5
R
24V THERMOSTAT CONNECTIONS
1
Y
W
1
W
2
T M
2
Y
G
O
DEHUM
24V HUM.
C
O
T
R
O
T
M
I
C
R
I
N
E
T
G
R
M
O
D
U
E
L
D
L
E
I
F
E
G
)
V
4
2
(
E
G
)
V
5
1
1
(
E
I
F
D
L
O
O
R
T
N
O
C
D
N
O
I
T
C
E
(
A C
O
O
D
T
V
+
C
3
)
(
(
6
)
2
)
(
1
)
2
(
O
H
I
G
H
O
C
R
I
P
R
S
E
1
1
)
(
8
)
(
7
)
(
0
1
)
( G
N
D
TR (9)
G
N
D
D
V
+
C
R
X
(
2
T
3
(
)
X
O
E
T
A
D
C
O
N
R
O
T
L
L
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
81
Loading...