This SERVICE MANUAL provides various service information, including the mechanical and electrical
parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
1. When servicing the unit, turn off the air conditioner
and unplug the power cord.
2. Observe the original lead dress.
If a short circuit is found, replace all parts which
have been overheated or damaged by the short
circuit.
3. After servicing the unit, make an insulation
resistance test to protect the customer from being
exposed to shock hazards.
Push this button to shift mode of operation from COOL
→ MONEY SAVER → FAN.
- COOL :
• Fan runs continually for normal cooling operation.
- MONEY SAVER:
• The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check
the room air to determine if cooling is needed.
- FAN :
• Fan-only operation.
TIMER
- SHUT-OFF TIME
• You will usually use shut-off time while you sleep.
• If unit is running, use Timer to set number of
hours until shut-off.
• For your sleeping comfort, once Time is set, the
Temperature setting will raise 2°F after 30 min.,
and once again after another 30 min.
• Push Timer button to advance setting from 1 Hour
→
2 Hours
→
....
→
12 Hours maximum.
- START TIME
• If unit is off, use Timer to set number of hours before unit starts.
• Push Timer button to advance setting from 1 Hour
→
2 Hours
→
.....
→
12 Hours maximum.
TEMPERATURE SETTING
• Use this button to automatically control the temperature of the room.
The temperature can be set within a range of 60°F to 86°F by
increments of 1°F.
• The setting appears in the display.
• To turn the air conditioner ON, push this button.
To turn the air conditioner OFF, push the button again.
• This button takes priority over any other button.
• When you first turn it on, the unit is in cool mode, at High fan
speed, and set at a temperature setting of 72°F.
FAN SPEED
• Every time you push this button, it advances the setting as follows:
{High → Low → Med → High}
• Designed for cooling only.
• Powerful and quiet cooling.
• Top-down chassis for the simple installation and service.
1.5 CONTROL LOCATIONS
1.5.1 COOLING ONLY MODEL
• OPERATION
• Built in adjustable THERMISTOR and THERMOSTAT.
• Washable one-touch filter.
• Compact size.
• VENTILATION
Push the lever to the "CLOSE" position to cool, heat or recirculate room air only.
Pull the lever to the "OPEN" position to exhaust smoke or stale air from the room.
This feature is best used in conjunction with the FAN ONLY position.
CAUTION
When the air conditioner has been operating in the
cooling and is turned off or set to the fan only position,
wait at least 3 minutes before resetting to the cooling
operation again.
— Prior to disassembling the unit, make sure that the POWER is off and the power cord is unplugged from the
wall receptacle.
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Open the inlet grille downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille. (See Fig. 1)
5. Re-install the component by referring to the
removal procedure.
Figure 1
2.1.2 CABINET
1. After disassembling the FRONT GRILLE, remove
the 6 screws which fasten the cabinet at the both
sides and the top. (See Fig. 2)
Keep these for later use.
2.1.3 CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the screw which fasten the control
box. (See Fig. 3)
3. Pull the control box from the barrier.(See Fig.3)
4. Discharge the capacitor by placing a 20,000 ohm
resistor across the capacitor terminals.
5. Disconnect two wire housings in the control box.
6. Pull the control box forward completely.
7. Re-install the components by referring to the
removal procedure. (See Fig. 3)
(Refer to the circuit diagram found on pages