Goldstar DH300E, DH304, LD40, GD40E, DH404E Service Manual

...
Page 1
Dehumidifier
SERVICE MANUAL
MODELS: DH300E/DH304
LD40/DH400M/GD40E DH404E/DH400E/LD40E DH504EL/LD50EL LD65EL
CAUTION
- BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
- ONLY FOR AUTHORIZED SERVICE.
Page 2
—2—
1. PREFACE
1.1 SAFETY PRECAUTIONS...........................................................................................................................3
1.2 FEATURES AND DIMENSIONS ................................................................................................................3
1.2.1 FEATURES........................................................................................................................................3
1.2.2 DIMENSIONS....................................................................................................................................3
1.3 MODEL NAMES .........................................................................................................................................4
1.4 SPECIFICATIONS......................................................................................................................................4
1.5 CONTROL TYPE........................................................................................................................................5
1.5.1 MECHANICAL TYPE.........................................................................................................................5
1.5.2 ELECTRONIC TYPE.........................................................................................................................5
1.6 HOW TO OPERATE DEHUMIDIFIER........................................................................................................6
1.6.1 HOW DOES THE DEHUMIDIFIER WORK? .....................................................................................6
1.6.2 LOCATION FOR THE DEHUMIDIFIER.............................................................................................6
1.6.3 MICRO SWITCH................................................................................................................................6
1.6.4 AUTO DEFROST...............................................................................................................................6
1.6.5 HUMIDITY CONTROLLER................................................................................................................7
1.6.6 DRYER .............................................................................................................................................7
2. CIRCUIT DIAGRAM............................................................................................................................8
3.
DISASSEMBLY INSTRUCTIONS
3.1 MECHANICAL PARTS .............................................................................................................................13
3.1.1 BUCKET AND AIR FILTER.............................................................................................................13
3.1.2 FRONT CASE AND TOP COVER...................................................................................................13
3.1.3 CABINET AND CONTROL BOX .....................................................................................................13
3.2 CONTROL PARTS ..................................................................................................................................14
3.2.1 POWER CORD ASSEMBLY...........................................................................................................14
3.2.2 SENSOR ASSEMBLY.....................................................................................................................14
3.2.3 PWB(PCB) ASSEMBLY, MAIN .......................................................................................................14
3.2.4 CAPACITOR....................................................................................................................................14
3.2.5 MICRO SWITCH ASSEMBLY.........................................................................................................14
3.2.6 COIL ASSEMBLY, SOLENOID .......................................................................................................15
3.2.7 CONTROL PANEL ..........................................................................................................................15
3.2.8 FAN AND MOTOR...........................................................................................................................16
3.2.9 DRAIN PAN.....................................................................................................................................16
3.3 REFRIGERATING CYCLE .......................................................................................................................17
3.3.1 CONDENSER, EVAPORATOR AND CAPILLARY TUBE...............................................................17
3.3.2 PTC OR OVERLOAD PROTECTOR (OLP) FOR RECIPROCATING COMPRESSOR .................17
3.3.3 ROTARY COMPRESSOR ..............................................................................................................17
3.4 HOW TO REPLACE REFRIGERATION SYSTEM...................................................................................18
4. TROUBLESHOOTING GUIDE...................................................................................................20
5. EXPLODED VIEWS..........................................................................................................................22
6. REPLACEMENT PARTS LIST...................................................................................................28
CONTENTS
Page 3
—3—
1. PREFACE
This Service Manual provides various service information, including the mechanical and electrical parts. This dehumidifier was manufactured and assembled under the strict quality control procedures.
The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
• Disconnect the power supply before servicing or replacing any component.
• Do not cut off the grounding prong or alter the plug in any manner.
1.2 FEATURES AND DIMENSIONS
1.2.1 FEATURES
• Quiet operation
• High efficiency
• Adjustable humidistat
• Automatic defrost
• Automatic shut-off
• Bucket-full indicator light
• Easy roll casters
• Removable & large capacity bucket.
• Washable air filter
• Two-speed fan
• Drain hose connection.
• Low temperature operation (DH504EL/LD50EL/LD65EL)
1.2.2 DIMENSIONS (mm/in)
Figure 1
385 (15
5
/
32
)
FAN
SPEED
TIMER
High Low
Continuous On. 4Hr. On/Off 2Hr. On/Off
HUMIDITY CONTROL
BUCKET
FULL
POWER
AUTO RESTART
HUMIDITY SETTING
340 (13
3
/
8
)
540 (21
1
/
4
)
ENERGY STAR
Page 4
4
1.4 SPECIFICATIONS
1.3 MODEL NAMES
MODEL NAME
CAPACITY (Pints/24hrs) 30 40 50 65
MECHANICAL TYPE
ELECTRONIC TYPE
CONTROL
PANEL
DH304, DH300M DH400M,LD40 - -
DH300E GD40E,DH404E DH504EL LD65EL
DH400E,LD40E LD50EL
*NOTE:Specifications are subject to minor change without notice for further improvement.
DH304, DH300M DH300E
DH400M, LD40 GD40E, DH404E DH400E, LD40E
DH504EL* LD50EL*
LD65EL*
POWER SUPPLY(Phase,V,Hz) INPUT(W) 480 580 630 830 RUNNING CURRENT(A) 5.9 5.7 5.7 8.4 ENERGY FACTOR(L/kw.h) 1.23 1.36 1.56 1.54 REFRIGERANT R134a REFRIGERANT CHARGE, oz(g) 5.29(150) 4.94(140) 7.23(205) 8.82(250)
OPEN CLOSE
SOLENOID VALVE*
Using Temp/Humid.:-4~122°F(-20~50°C)/95%RH Rating:7W/90mA
COMPRESSOR MODEL No. LX86HAQG QS075CBA QA084CBC QA114CBD
P6R8MC
WORKING TIME:0.3~1.3sec RETURN TIME:65sec
AMPERE 10A VOLTAGE 200V
PROTECTOR
CAPACITOR - 40µF, 270VAC 35µF, 270VAC 35µF, 270VAC MOTOR ASSEMBLY,SINGLE Shaded pole motor, 72W/1.4A, Thermal cutoff:266°F/130°C
Shaded pole motor, 91W/1.8A,
Thermal cutoff:266°F/130°C
SWITCH ASSEMBLY,MICRO OUTSIDED MENSIONS WxHxD,mm(in) NET WEIGHT,kg(lbs) 23.1(51) 17.7(39) 20.4(45) 22.2(49)
OVERLOAD PROTECTOR FOR COMPRESSOR
INTERNAL PROTECTOR(FUSE)FOR MOTOR
1Ø, 115V,60Hz
R22
THERMISTOR
33.8°F(1±0.5°C) 50°F(10±0.5°C)
-
15A/250VAC
385X540X340(15 5/32 x 21 1/4 x 13 3/8)
P.T.C
ASSEMBLY
TYPE
-
TIME
MAXIMUM
MODELS
ITEMS
Page 5
5
1
2
3
4
5
6
7
8
9
Off
Max
High
Low
Fan Speed
Humidity Control
Auto
Shut-Off
Constantly On.
FAN
SPEED
TIMER
High Low
4hr. On/Off 2hr. On/Off
HUMIDITY CONTROL
BUCKET
FULL
POWER
AUTO RESTART
HUMIDITY
SETTING
Humidity Control
When you first use the dehumidifier, turn the humidity control to 5 or 6. If you still have moisture, turn the humidity control to a higher setting. MAX is the highest setting.
When excess moisture and dampness odors are gone, adjust the control to a lower setting. Use the dehumidifier as long as excess moisture is present.
Fan Speed
The fan control adjusts the fan speed. Set the fan control to HIGH for maximum moisture removal. When the humidity has been reduced and quiet operation is preferred, set the fan control to
LOW.
Bucket Full Indicator
This light glows when the water bucket is full and needs to be emptied.
Power
Operation starts when this button is pressed and stops when the button is pressed again.
Auto Shut-Off
This light glows when the bucket is full, or when the bucket is removed or not placed in the proper position. In these cases the Water Level Control Switch shuts off the dehumidifier.
When the light glows, check the bucket condition.
Fan Speed
This controls the speed of the airflow.
High: Fan speed is set to high.
Low: Fan speed is set to low.
When Fan Speed button is pressed, the fan speed
mode is changed.
Timer
Press this button to select type of operation.
Select continuous On for uninterrupted operation.
Select either 2 or 4 hr. On/Off for cycled operation:
The unit will operate for 2 or 4 hours, and then shut off completely for 2 or 4 hours. The cycle repeats until you change the setting.
When Timer button is pressed, the Timer indicator lights shift as follow from 2hr.On/Off to 4hr.On/Off.
Auto Restart
Once power is restored after a power outage, the unit returns to its previous operation setting after a 2 minute delay. The fan runs immediately when the power is restored.
Figure 2
Figure 3
Humidity Control
This button controls the humidity in the room.
Press button to raise the humidity setting.
Press button to lower the humidity setting.
The humidity setting can be set to a permanent "On"
setting or to a specific humidity setting between 35% and 70% in 5% increments.
"On" setting: Dehumidifier runs continuously regardless of humidity condition.
35% - 70% setting: Dehumidifier runs on and off according to surrounding humidity conditions.
1.5 CONTROL TYPE
1.5.1 Mechanical type
1.5.2 Electronic type
Page 6
6
1.6.1 HOW DOES THE DEHUMIDIFIER WORK?
Moist, humid air is drawn over a cold refrigerated dehumidifying coil. Moisture in the air condenses on this coil and drains into a bucket (or through the bucket into a hose and drain).
Dry, clean air is drawn over the condenser where it is actually heated several degrees and discharged out the rear grill into the room. (See Figure 4)
It is normal for the surrounding air to become slightly warmer as the dehumidifier operates.
This warming effect further reduces the relative humidity of the surrounding air.
1.6.2 LOCATION FOR THE DEHUMIDIFIER
Allow at least 12 inches of space on all sides of the unit for good air circulation. (See Figure 5)
The dehumidifier must be operated in an enclosed area to be most effective.
Close all doors, windows and other outside openings to the room.
Place the dehumidifier in a location that does not restrict air flow into the front grille or out the rear grille.
The operation of dehumidifier in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet, unless there is adequate circulation of air in and out of the area.
Fan
Side View
Condenser
Evaporator
Motor
Compressor
Rear Grille
Bucket
Dry
Air Out
Humid
Air In
12"
12"
Figure 4
Figure 5
1.6 HOW TO OPERATE DEHUMIDIFIER
1.6.3 MICRO SWITCH
The micro switch assembly, which is located on the drain pan of inside unit, automatically shuts off the dehumidifier when the bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again turns itself on.
1.6.4 AUTO DEFROST
When frost builds up on the cooling coils, the unit will automatically cycle off until the frost disappears. The fan continues to run.
NOTE: The unit will not operate satisfactorily if the room temperature is below 65˚F(18˚C). If the dehumidifier is
operated in low temperature conditions frost can form in the evaporator coil and the unit will cycle ON/OFF repeatedly. In this case, please check your room temperature conditions and stop the unit.
NOTE:
The low temperature operation feature in the DH504EL, DH50EL and DH65EL models will continuously cycle up to a temperature of 42°F(6°C).
Page 7
7
1.6.5 HUMIDITY CONTROLLER
1.6.5.1 Mechanical Type
The humidity control can be set anywhere between Off and Max for normal operation.
If you need more dehumidification, turn the Humidity Control toward Max. If you need less dehumidification, turn the Humidity Control toward Off.
The relative humidity range is from 20% to 80%. (See Figure 6)
Turn the Humidity Control to Off to stop the unit manually.
1.6.5.2 Electronic Type
The humidity control can be set 'on' or 35%-70% RH(Relative Humidity) for normal operation. (See Figure 7)
If you need drier air, press the Humidity Control button. If you need moister air, press the Humidity Control
button. Press the Power button to stop the unit manually.
1.6.6 DRYER (DH304, DH300M, DH300E)
Dryer is used to prevent capillary blockage from moisture in the refrigerant system and H/E, condenser and evaporator. Also, dryer is used to remove corrosion of the components.
NOTE: When dryer is replaced, proper injection to
capillary is needed. On opening the dryer, it should be welded instantly. The oxidization of dryer inside and all tubes inside after welding can be prevented.
Dryer
HUMIDITY
CONTROL
HUMIDITY
SETTING
42% R.H
40%
7(30%)
6(35%)4(50%)
3(60%)
2(70%)
1(80%)
5(42%)
8(25%)
9(20%)
Max.Off
DEAD DIAL
Figure 6
Figure 7
Figure 8
Page 8
8
2. CIRCUIT DIAGRAM
MODEL : DH304, DH300M
Q'TY
PER SET
1 1 1 1 1 1 1 1 1 1 1
RE-
MARKS
S S S S S S S S S S S
1 2 3 4 5 6 7 8
9 10 11
DESCRIPTION
POWER CORD ASSEMBLY SWITCH, ROCKER MOTOR ASSEMBLY PTC ASSEMBLY RE-COMPRESSOR, SET OLP PWB(PCB) ASSEMBLY, DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY, ROTARY SWITCH ASSEMBLY, MICRO PWB(PCB) ASSEMBLY, MAIN
DH304, DH300M
6411A20001Z
6600FX5001G
4681A20040J 6748C-0003D 2521C-A8626 6750C-0009E 6871A20289B 6877A30013L 6601A30001B
6600A30003C
6871A10142A
PART NO.
NO.
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
Page 9
9
MODEL : DH300E
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
Q'TY
PER SET
1 1 1 1 1 1 1 1 1
RE-
MARKS
S S S S S S S S S
1 2 3 4 5 6 7 8 9
DESCRIPTION
POWER CORD ASSEMBLY MOTOR ASSEMBLY PTC. ASSEMBLY RE-COMPRESSOR, SET OLP PWB(PCB) ASSEMBLY, DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY, MICRO PWB(PCB) ASSEMBLY, MAIN
DH300E
6411A20001Z 4681A20040J 6748C-0003D 2521C-A8626 6750C-0009E 6871A20482A 6877A30013L 6600A30003C 6871A10141A
PART NO.
NO.
Page 10
10
MODEL : DH400M/LD40
Q'TY
PER SET
1 1 1 1 1 1 1 1 1 1 1
RE-
MARKS
S S S S S S S S S S S
1 2 3 4 5 6 7 8
9 10 11
DESCRIPTION
POWER CORD ASSEMBLY SWITCH, ROCKER MOTOR ASSEMBLY CAPACITOR COMPRESSOR (ROTARY), SET OLP (ASSEMBLY) PWB(PCB) ASSEMBLY, DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY, ROTARY SWITCH ASSEMBLY, MICRO PWB(PCB) ASSEMBLY, MAIN
DH400M/LD40
6411A20001Z
6600FX5001G
4681A20040J 0CZZA20005N 2520UCAS003
6750U-L103A
6871A20289B 6877A30013M 6601A30001C 6600A30003C
6871A10142A
PART NO.
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
NO.
Page 11
11
MODEL : GD40E/DH404E/DH400E/LD40E
Q'TY
PER SET
1 1 1 1 1 1 1 1 1
RE-
MARKS
S S S S S S S S S
1 2 3 4 5 6 7 8 9
DESCRIPTION
POWER CORD ASSEMBLY MOTOR ASSEMBLY CAPACITOR COMPRESSOR,SET OLP PWB(PCB) ASSEMBLY,DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY,MICRO PWB(PCB) ASSEMBLY,MAIN
GD40E/DH404E/DH400E
LD40E
6411A20001Z
4681A20040J 0CZZA20005N 2520UCAS003
6750U-L013A
6871A20482A 6877A30013M 6600A30003C 6871A10141A
PART NO.
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
NO.
Page 12
12
MODEL : DH504EL/LD50EL/LD65EL
Q'TY
PER SET
1 1 1 1 1 1 1 1 1 1
RE-
MARKS
S S S S S S S S S S
1 2 3 4 5 6 7 8 9
10
DESCRIPTION
POWER CORD ASSEMBLY MOTOR ASSEMBLY CAPACITOR COMPRESSOR (ROTARY), SET OLP. PWB(PCB) ASSEMBLY, DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY, MICRO PWB(PCB) ASSEMBLY, MAIN COIL ASSEMBLY, SOLENOID
DH504EL/LD50EL LD65EL
6411A20001Z
4681A20040J 4681A20040K 0CZZA20001R 0CZZA20005J 2520UCAA014 2520UCBA007
6750U-L058A 6750U-L048A
6871A20482A
6877A30013L 6600A30003C 6871A10141C 6421A20003V
PART NO.
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
NO.
Page 13
3.1 MECHANICAL PARTS
3.1.1 BUCKET AND AIR FILTER
1. Turn the Humidity Control off(Mechanical type) or press the power button off. (Electronic type)
2. Disconnect the power supply.
3. Remove the bucket. (See Figure 9)
4. Pull out the air filter. (See Figure 10)
3.1.2 FRONT CASE AND REAR GRILLE
1. Remove 2 screws which fasten the front grille.
2. Pull the front grille forward and upward. (See Figure 11)
3. Remove 6 screws that secure the rear grille.
4. Remove the rear grille. (See Figure 12)
3.1.3.
CABINET AND CONTROL BOX
1. Remove the Bucket, the Air filter and Front grille according to the procedure above.
2. Remove 1 screws that fasten Control box. (See Figure 13)
3. Remove 8 screws on all sides of the cabinet.
4. Lift the Cabinet from the base.(See Figure 13)
5. Remove a screw fasten the earth wire on the inside of control box.
6. Remove 1 screw that fasten control box and unhook control box from hook on the shroud. (See Figure 14)
13
3. DISASSEMBLY INSTRUCTIONS
Figure 9 Figure 10
Figure 11 Figure 12
Figure 13 Figure 14
Page 14
3.2 CONTROL PARTS
3.2.1 POWER CORD ASSEMBLY
1. After opening the control box, remove the screw
that holds the ground wire. (See Figure 15)
2. Disconnect the remaining leads of the power cord
from the PWB(PCB) ASSEMBLY, MAIN, then remove it from the control box.
3.2.2 SENSOR ASSEMBLY
1. Disconnect the sensor assembly from the
PWB(PCB) ASSEMBLY, MAIN.
2. Remove the screw which fastens the humidity
sensor. (See Figure 16)
3. Remove the thermistor from the holder.
(See Figure 16)
4. Disconnect the switch wires from the micro switch
assembly. (See Figure 16)
3.2.3 PWB(PCB) ASSEMBLY, MAIN
1.
Disconnect all leads of the motor and the compressor from PWB(PCB) ASSEMBLY, MAIN.
2. Remove the screw which fastens the PWB(PCB)
ASSEMBLY, MAIN and pull it out after unhooking from 2 rectangular holes of the control box (lower). (See Figure 17)
3.2.4 CAPACITOR
(Except DH304/DH300M/DH300E)
1. Remove the screw that fastens the capacitor.
(See Figure 17)
2. Disconnect all leads from the capacitor and then
remove it from control box.
3.2.5 MICRO SWITCH ASSEMBLY
1. Turn the nut counterclockwise and pull out the
micro switch from the drain pan. (See Figure 18)
14
Figure 17
Figure 16
Figure 18
Figure 15
Page 15
15
3.2.6 COIL ASSEMBLY, SOLENOID (DH504EL, LD50EL, LD65EL)
1. Disconnect the housing of the COIL ASSEMBLY,
SOLENOID from the PCB(PWB) ASSEMBLY, MAIN.
2. Remove the screw that fastens the COIL
ASSEMBLY, SOLENOID. (See Figure 19)
3. Pull it out upwards.
3.2.7 CONTROL PANEL
3.2.6.1 CONTROL PANEL - Mechanical Type
(DH304/DH300M/DH400M/LD40)
1. Disconnect housing and all leads of the rocker
switch, SWITCH ASSEMBLY, ROTARY and PWB(PCB) ASSEMBLY, DISPLAY from PWB(PCB) ASSEMBLY, MAIN (3.1.3)
2. Pull out the knob assembly.
3. Remove the nut which fastens the SWITCH
ASSEMBLY, ROTARY.
4. Remove the knob of the rotary switch by pulling it
upward.
5. Pull out the rocker switch by pushing the hooks on
the both sides of rocker switch.
6. Pull out the PWB(PCB) ASSEMBLY, DISPLAY after
turning over both hooks of the display cover.
1. Disconnect the housing of the PWB(PCB)
ASSEMBLY, DISPLAY from PWB(PCB) ASSEMBLY, MAIN (3.1.3).
2. Remove 6 screws that secure the PWB(PCB)
ASSEMBLY, DISPLAY to the display cover.
Figure 19
Figure 20
H
i g
h
L
o w
Fan Speed
H
um
idity Control
Auto
Shut-O
ff
E N
E R
G Y
S T
A R
M
a
x
O
f
f
Figure 21
3.2.6.2 CONTROL PANEL - Electronic Type
(DH300E/GD40E/DH404E/DH400E/LD40E/DH504EL/
LD50EL/LD65EL)
Page 16
3.2.8
FAN AND MOTOR
1. Turn the nut left and full out the Fan by hands carefully.
2. Remove 2 screws that fasten Heat Exchange.
3. Lift the H/E and open the H/E around 45 degree clockwise carefully. (See Figure 22)
4. Unfasten 3 screws that secure the Motor and earth wire. (See Figure 23)
5. Remove the Motor.
3.2.9
SHROUD AND DRAIN PAN
1. Discharge the refrigerant by using a refrigerant Recovery System.
2. After purging the unit completely, unbrace the Discharge and the Suction tube connected compressor carefully.
3. Remove 2 screws that fasten the H/E.
4. Unfasten 2 screws that secure the shroud on the sides and then lift shroud from the drain pan. (See Figure 24)
5. Unfasten 2 screws that secure the drain pan to base pan. (See Figure 25)
6. Pull the drain pan backward then take it up from the base. (See Figure 25)
16
Figure 25
Figure 22
Figure 23
Figure 24
Page 17
17
3.3 REFRIGERATING CYCLE
3.3.1 CONDENSER, EVAPORATOR AND
CAPILLARY TUBE
1. Remove the insulation on the Heater/Evaporator (H/E) assembly
2. Pierce the pinch-off tube to discharge the refrigerant, using a refrigerant recovery system.
3. After discharging the refrigerant completely, remove 2 screws between the housing assembly and the H/E. (See Figure 26)
4. Lift the H/E and open the H/E around 45 degree counterclockwise carefully.
5. Unbraze each of interconnecting tubes of the evaporator and condenser carefully.
6. Remove the H/E assembly from the orifice. (See Figure 27)
7. Unbraze the capillary tube at the connections of the condenser and evaporator. (See Figure 28)
8. Remove 4 screws between the condenser and evaporator. (See Figure 28)
3.3.2 PTC OR OVERLOAD PROTECTOR
(OLP) FOR RECIPROCATING COMPRESSOR (DH304/DH300M/DH300E)
1. Discharge the refrigerant by using a refrigerant Recovery System.
2. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
3. Remove the screw or nut which fastens the terminal cover
4. Disconnect the lead wire from the overload protector or PTC assembly.
5. Remove the overload protector(OLP) or PTC assembly. (See Figure 29)
3.3.3 COMPRESSOR
1. Discharge the refrigerant by using a refrigerant Recovery System.
2. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
3. Remove the nuts and washers which fasten the compressor. (See Figure 30)
4. Remove the compressor. (See Figure 30)
Figure 26
Figure 27
Figure 28
Using Rotary
Compressor models
Figure 30
Figure 29
Using Recipro Compressor model
Page 18
18
1. When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system.
2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.
6. Evacuate as follows.
1) Connect the vacuum pump, as illustrated in Figure 31A.
2) Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.
3) Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
7. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2) Connect the charging cylinder as shown in Figure 31B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
CAUTION
3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM
NOTE:
REFRIGERANT R134a IS USED IN SOME MODELS. CHECK THE SPECIFICATION LABEL ON THE CABINET.
When discharging refrigerant R134a, purging instrument should be used only for R134a, without mixing that of refrigerant R22.
When checking the leakage of refrigerant R134a, leakage test tool should be used only for R134a.
The pump for discharging should be high efficiency. Final discharging value must be managed below 0.5 Torr.
Maximum water should be less than 150mg in the cycle­all tubes and H/E assembly-system. If water quantity is over 150mg, it causes acid or corrosion in the cycle system and the capillary tube to be clogged by water and harmful materials.
Models charged with refrigerant R134a should be used dryer to prevent water from overflowing.
Page 19
19
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.
B
A
COMPRESSOR
COMPOUND GAUGE
MANIFOLD GAUGE
SEE INSETS
BELOW
EXTERNAL VACUUM PUMP
CHARGING CYLINDER
HILOW
A
B
A
B
C
CONDENSER ASSEMBLY
(HIGH PRESSURE SIDE)
EVAPORATOR ASSEMBLY
(LOW PRESSURE SIDE)
CAPILLARY
TUBE
Figure 31A-Pulling Vacuum
Figure 31B-Charging
Page 20
CONDITION
1. Dehumidifier does not start. (Both compressor and fan motor do not operate.)
2. Motor runs but compressor does not run.
3. Does not defrost control.
4. Insufficient dehumidification
CAUSE
No power
Poor plug contact at outlet. Bucket is full.
Humidity control is at Off position
Wire disconnected or loose
Capacitor. (Discharge capacitor before testing.)
Voltage (115V ± 10%)
Wiring
Rotary switch
Defrost control
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload protector (OLP)
Defrost control is defective. Low relative humidity Poor air circulation
H/E clogged with dust and dirt Air filter is dirty. Motor is not operating.
REMEDY
C
heck power supply at outlet.
Correct if none. Install plug properly or replace it. If Auto Shut Off lights, empty the bucket
and replace properly. Turn the humidity control switch toward
Max. Connect wire. Refer to wiring diagram for
terminal identification. Repair or replace loose terminal.
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
It must be between 103.5V and 126.5V. If not within limits, call an electrician
Check the wire connections; If loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open.
The Defrost Control senses frost build-up on the evaporator coil and automatically shuts off the compressor. The fan continues to run, drawing air across the coil, and melting the frost. When the coil is defrosted, the compressor automatically restarts, and dehumidifying resumes.
Check the capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor OLP if externally mounted. Replace if open. (If the compressor temperature is high, remove OLP, cool, and retest.)
Check defrost control, replace it. Turn dehumidifier off. Move dehumidifier to obtain free and
unobstructed air circulation. Clean evaporator and/or condenser assembly Clean it. Check Motor, repair or replace it.
20
4. TROUBLESHOOTING GUIDE
Page 21
21
CONDITION
5. Noisy operating
6. Water drips
7. Compressor cycles on overload protector. (OLP)
CAUSE
Fan
Loose foreign material inside the housing. Tube hits frame. Fan blade hits frame Internal compressor noise. Loose set screws Worn bearings of Motor Assembly
The bucket is not installed properly.
Connection may be loose. Leak in bucket Water drips when bucket removed for
emptying. Bucket overflows. High or low line voltage. (115V ± 10%)
Poor air circulation.
Heat Exchange clogged with dust or dirt. Motor
Bad PTC assembly (if assembled) Short circuit or ground in electrical circuit Unit pressures not equalized
Capacitor Wiring
Refrigeration system Stuck compressor Overload protector (OLP)
REMEDY
If cracked, out of balance, or partially missing, replace it
Remove it. Adjust tubing routine carefully. Check Motor Mount. If loose, tighten it. Replace compressor. Tighten them. If knocking sounds continue when running
or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor assembly.
The bucket should be properly positioned on the hangers of the drain pan.
Check connection and repair. Replace bucket. Before removing bucket, the unit should
be turned off. Check micro switch and float. Check line voltage. It must be between
103.5V and 126.5V volts. If intermittent, provide new supply.
Move dehumidifier for free and unobstructed air flow.
Clean dust or dirt on the Heat Exchange. If not running, determine the cause.
Replace if required. Check PTC, Repair. Check electrical circuit. Repair. Allow 2 or 3 minutes for pressure to
equalize before starting compressor. Test the capacitor. Check the terminals. If loose, repair or
replace. Check the system for a restriction. Check compressor, replace compressor Check OLP, if externally mounted.
Replace if open. (If the compressor temperature is high, remove the OLP, cool, and retest.)
Page 22
22
5. EXPLODED VIEWS
MODEL: DH304/DH300M
354210
554030
130900
349600
149980
162615
346811
359012
268714
264110
148390
144410
752140
152302
436500
249950
266011
130411
235512
149410
435300
330870
266003
238310
135312
268712
266002
667482
558511
35211A
352113
552111
550140 554160 567502
H
i g h
L o
w
Fan Speed
Hum
idity Control
Au
to
Shut-Off
E N
E R
G
Y S
T A
R
M
a
x
O
ff
Page 23
23
MODEL: DH300E
354210
554030
135312
130900
349600
149980
346811
359012
148390
144410
752140
152302
436500
130401
268712
266011
238310
667482
550140 554160 567502
558511
35211A
352113
552111
435300
162615
268714
264110
249950
330870
Page 24
24
MODEL: DH400M/LD40
W0CZZ
162615
268714
264110
249950
35211A
352113
552111
550140
567502
554160
354210
554030
130900
349600
149980
346811
359012
148390
144410
752140
152302
436500
266011
130411
235512
149410
435300
330870
266003
238310
135312
268712
266002
H
i g
h
L o
w
Fan Speed
Hum
idity Co
ntrol
Auto
Shut-O
ff
E N
E R
G Y
S T A
R
M
a
x
O
f
f
Page 25
25
MODEL: GD40E/DH404E/DH400E/LD40E
W0CZZ
162615
268714
264110
249950
35211A
352113
552111
550140
567502
554160
354210
554030
135312
130900
349600
149980
346811
359012
148390
144410
752140
152302
436500
130401
268712
266011
238310
435300
330870
Page 26
26
MODEL: DH504EL/LD50EL
W0CZZ
162615
268714
264110
249950
35211A
352113
552204
567502
554160
550140
354210
554030
135312
130900
349600
149980
346811
359012
148390
144410
752140
152302
436500
130401
268712
266011
238310
435300
330870
Page 27
27
MODEL: D65EL
W0CZZ
162615
268714
264110
249950
35211A
552204
352113
567502
554160
550140
354210
135312
554030
130900
349600
149980
346811
359012
148390
144410
752140
152302
436500
130401
268712
266011
238310
435300
330870
Page 28
28
6. REPLACEMENT PARTS LIST
MODEL: DH304/DH300M
130411 BASE ASSEMBLY 3041A10042C 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10285C 330870 DRAIN PAN ASSEMBLY 3087A10019B 148390 TANK ASSEMBLY,BUCKET 4839A10002A 149410 KNOB ASSEMBLY 4941A30019B 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013L 249950 CONTROL BOX,ASSEMBLY 4995A20359J 264110 POWER CORD,ASSEMBLY 6411A20001Z 266002 SWITCH,ROCKER 6600FX5001G 266003 SWITCH ASSEMBLY,ROTARY 6601A30001B 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20289B 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10142A 346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY,SUCTION 5211A10464A
352113 TUBE ASSEMBLY,DISCHARGE 5211A11019A 552111 TUBE ASSEMBLY,CAPILLARY 5211A30720A 354210 EVAPORATOR,ASSEMBLY 5421A10009P 554030 CONDENSOR ASSEMBLY 5403A10008N 558511 DRIER ASSEMBLY 5851A30001A 554160 COMPRESSOR ,SET 2521C-A8626 359012 FAN,TURBO 5900A20007A 567502 OLP 6750C-0009E 349600 MOUNT,MOTOR 4960A20009B 667482 PTC ASSEMBLY 6748C-0003D 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079M 235512 COVER ASSEMBLY,DISPLAY 3551A20122A 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 5040AR4195A 149980 SHROUD 4998A10034A 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
DH304/DH300M
Page 29
29
MODEL: DH300E
130411 BASE ASSEMBLY 3041A10042C 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10254F 330870 DRAIN PAN ASSEMBLY 3087A10019B 148390 TANK ASSEMBLY,BUCKET 4839A10002A 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013L 249950 CONTROL BOX,ASSEMBLY 4995A20359G 264110 POWER CORD,ASSEMBLY 6411A20001Z 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20482A 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10141A 346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY,SUCTION 5211A10464A
352113 TUBE ASSEMBLY,DISCHARGE 5211A11019A 552111 TUBE ASSEMBLY,CAPILLARY 5211A30720A 354210 EVAPORATOR,ASSEMBLY 5421A10009P 554030 CONDENSOR ASSEMBLY 5403A10008N 558511 DRIER ASSEMBLY 5851A30001A 554160 COMPRESSOR ,SET 2521C-A8626 359012 FAN,TURBO 5900A20007A 567502 OLP 6750C-0009E 349600 MOUNT,MOTOR 4960A20009B 667482 PTC ASSEMBLY 6748C-0003D 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079L 235512 COVER ASSEMBLY,DISPLAY 3551A20109B 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 5040AR4195A 149980 SHROUD 4998A10034A 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
DH300E
Page 30
30
MODEL: DH400M/LD40
130411 BASE ASSEMBLY 3041A10042B 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10285B / 3531A10254A "B:LG/A:Goldstar" 330870 DRAIN PAN ASSEMBLY 3087A10019A 148390 TANK ASSEMBLY,BUCKET 4839A10002A 149410 KNOB ASSEMBLY 4941A30019B 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013M
W0CZZ CAPACITOR 0CZZA20005N
249950 CONTROL BOX,ASSEMBLY 4995A20359H 264110 POWER CORD,ASSEMBLY 6411A20001Z 266002 SWITCH,ROCKER 6600FX5001G 266003 SWITCH ASSEMBLY,ROTARY 6601A30001B 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20289B 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10142A 346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY,SUCTION 5211A10460A
352113 TUBE ASSEMBLY,DISCHARGE 5211A10463A 552111 TUBE ASSEMBLY,CAPILLARY 5211A31003B 354210 EVAPORATOR,ASSEMBLY 5421A10009N 554030 CONDENSOR ASSEMBLY 5403A10008M 554160 COMPRESSOR ,SET 2520UCAS003 359012 FAN,TURBO 5900A20007A 567502 OLP 6750U-L103A 349600 MOUNT,MOTOR 4960A20009B 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079E/K "E:Goldstar/K:LG" 235512 COVER ASSEMBLY,DISPLAY 3551A20122A 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 4830A30005A 149980 SHROUD 4998A10034A 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
DH400M/LD40
Page 31
31
MODEL: GD40E/DH404E/DH400E/LD40E
130411 BASE ASSEMBLY 3041A10042B 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10254A/E "A:Goldstar/E:LG" 330870 DRAIN PAN ASSEMBLY 3087A10019A 148390 TANK ASSEMBLY,BUCKET 4839A10002A 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013M
W0CZZ CAPACITOR 0CZZA20005N
249950 CONTROL BOX,ASSEMBLY 4995A20359F 264110 POWER CORD,ASSEMBLY 6411A20001Z 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20482A 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10141A 346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY,SUCTION 5211A10460A
352113 TUBE ASSEMBLY,DISCHARGE 5211A10463A 552111 TUBE ASSEMBLY,CAPILLARY 5211A31003B 354210 EVAPORATOR,ASSEMBLY 5421A10009N 554030 CONDENSOR ASSEMBLY 5403A10008M 554160 COMPRESSOR ,SET 2520UCAS003 359012 FAN,TURBO 5900A20007A 567502 OLP 6750U-L103A 349600 MOUNT,MOTOR 4960A20009B 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079A/J
"A:Goldstar/J:LG" 235512 COVER ASSEMBLY,DISPLAY 3551A20109B 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 4830A30005A 149980 SHROUD 4998A10034Y 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
GD40E/DH404E/DH400E/LD40E
Page 32
32
MODEL: DH504EL/LD50EL
130411 BASE ASSEMBLY 3041A10042A 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10254A/E "A:Goldstar/E:LG" 330870 DRAIN PAN ASSEMBLY 3087A10019A 148390 TANK ASSEMBLY,BUCKET 4839A10002A 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013L
W0CZZ CAPACITOR 0CZZA20001R
249950 CONTROL BOX,ASSEMBLY 4995A20359E 264110 POWER CORD,ASSEMBLY 6411A20001Z 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20482A 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10141C 346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY,SUCTION 5211A10428A
352113 TUBE ASSEMBLY,DISCHARGE 5211A11016A 552204 COIL ASSEMBLY,SOLENOID 6421A20003K 354210 EVAPORATOR,ASSEMBLY 5421A10009J 554030 CONDENSOR ASSEMBLY 5403A10008A 554160 COMPRESSOR ,SET 2520UCAA014 359012 FAN,TURBO 5900A20007A 567502 OLP 6750U-L058A 349600 MOUNT,MOTOR 4960A20009B 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079A/J
"A:Goldstar/J:LG" 235512 COVER ASSEMBLY,DISPLAY 3551A20109B 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 4830A30005A 149980 SHROUD 4998A10034A 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
DH504EL/LD50EL
Page 33
33
MODEL: LD65EL
130411 BASE ASSEMBLY 3041A10042A 130900 CABINET 3090A10042A 135312 FRONT GRILLE,ASSEMBLY 3531A10254E 330870 DRAIN PAN ASSEMBLY 3087A10019A 148390 TANK ASSEMBLY,BUCKET 4839A10002A 152302 FILTER(MECH),AIR 5230A20040A 162615 SENSOR ASEMBLY 6877A30013L
W0CZZ CAPACITOR 0CZZA20005J
249950 CONTROL BOX,ASSEMBLY 4995A20359L 264110 POWER CORD,ASSEMBLY 6411A20001Z 266011 SWITCH ASSEMBLY,MICRO 6600A30003C 268712 PWB(PCB)ASSEMBLY,DISPLAY 6871A20482A 268714 PWB(PCB)ASSEMBLY,MAIN 6871A10141C 346811 MOTOR ASSEMBLY 4681A20040K
35211A TUBE ASSEMBLY,SUCTION 5211A10454A
352113 TUBE ASSEMBLY,DISCHARGE 5211A10455A 552204 COIL ASSEMBLY,SOLENOID 6421A20003K 354210 EVAPORATOR,ASSEMBLY 5421A10009H 554030 CONDENSOR ASSEMBLY 5403A10008L 554160 COMPRESSOR ,SET 2520UCBA007 359012 FAN,TURBO 5900A20007A 567502 OLP 6750U-L048A 349600 MOUNT,MOTOR 4960A20009B 436500 HANDLE 3650A20004A 144410 CASTER ASSEMBLY,ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20079J 235512 COVER ASSEMBLY,DISPLAY 3551A20109B 752140 HOSE,CONNECTOR 5214A20027A 550140 ISOLATOR,COMP 4830A30005A 149980 SHROUD 4998A10034A 435300 REAR GRILLE 3530A10193A
LOCATION
NO.
DESCRIPTION
REMARK
PART NO.
LD65EL
Page 34
P/No : 3828A31001A
January, 2004
Printed in China
Loading...