Golden Anderson Valve 920, 920H Installation Manual

INSTALLATION, OPERATION AND
MAINTENANCE MANUAL
Figure 920
1” & 2” Compound Lever
Air Release Valves
Drawing EAR-7003
234 Clay Avenue Mars, PA 16046 USA
Telephone (724) 776-1020 Fax (724) 776-1254
E-mail: info-ga@vag-group.com
Manual Number 920-IOM 022420
INSTALLATION, OPERATION
INSTALLATION, OPERATION and
MAINTENANCE
Figure 920 Air Release Valves
INTRODUCTION
This manual will provide the information to properly install, operate and maintain the valve to ensure a long service life. The Air Release Valve is ruggedly constructed to provide years of trouble-free operation with minimal maintenance.
These Air Release Valves are not intended for use with fluids containing suspended solids such as wastewater and sewage. The GA Industries Figure 925, 927 or 929 Air Release Valves are recommended for such applications.
CAUTION
The valve is NOT recommended for use with toxic fluids, fuels or fluids containing hazardous gases
CAUTION
The valve will not function if used at a pressure higher than the maximum working pressure indicated on the nameplate.
The Shop Order (SO) Number, Figure Number, size and pressure rating are stamped on a nameplate attached to the valve. Please refer to the SO number when ordering parts.
DESCRIPTION OF OPERATION The Air Release Valve is designed to automatically vent air that has accumulated within the valve. These valves are usually installed at high points in the system where air tends to collect. The valve as shipped is
”normally open” and will vent air through its
orifice at the top of the valve. The float rises when water enters the valve and closes the orifice. Air from the system accumulates in the valve forcing the water level down until the float drops and opens the venting orifice. As air is released the water level rises lifting the float and re-closing the valve.
This sequence occurs as often as necessary to release air that has collected in the valve.
RECEIVING AND STORAGE
Inspect the valve upon receipt for damage during shipment. Carefully unload all valves to the ground without dropping.
The valves should remain in a clean, dry and weather protected area until installed. For long term storage (greater than 6 months) the rubber surfaces of the seat should be coated with a non-toxic lubricant such as "SuperLube" made by Synco Chemical. Do not expose the rubber parts to sunlight or ozone.
INSTALLATION
The Figure 920 is standard with NPT screwed connections. An optional flange pipeline connection is available on special order.
Consult the drawings of record to verify the configuration supplied and installed.
The valve must be installed in an upright vertical orientation, normally at a high point in the system.
If installed outdoors, below ground in a vault or in an unheated area, adequate freeze protection must be provided. Some discharge of water may occur during operation so the valve outlet should be piped to an adequate drain.
An isolating valve should be installed between the valve and the pipeline or system to facilitate maintenance.
Carefully screw threaded end valves onto pipe nipple using compatible thread sealant. Tighten valve using wrench flats. DO NOT OVER­TIGHTEN.
Flat-faced flanged valves should be mated with flat-faced flanges and full-face gaskets. If ring gaskets are used the bolt material shall be ASTM A307 Grade B (or equivalent). Higher strength bolting should only be used with full­face gaskets.