GOK GS Pro-Fi 3 Assembly And Operating Manual

Assembly and operating manual
Combined heating oil filter breather type GS Pro-Fi® 3
installation guidelines.
Breather device with filter and shut-off fitting according to EN 12514-2
2Y115
CONTENTS
ABOUT THE MANUAL ............................................................................................................................. 1
GENERAL PRODUCT INFORMATION .................................................................................................... 2
INAPPROPRIATE USE ............................................................................................................................ 3
ADVANTAGES AND EQUIPMENT .......................................................................................................... 3
DESIGN ................................................................................................................................................... 4
CONNECTIONS ....................................................................................................................................... 5
DETERMINATION OF THE FLOW RATE, THE PIPE DIAMETER, AND THE PRESSURE LOSS ........... 5
ASSEMBLY .............................................................................................................................................. 6
LEAK CHECK .......................................................................................................................................... 8
START-UP ............................................................................................................................................... 9
OPERATION ............................................................................................................................................ 9
MAINTENANCE ..................................................................................................................................... 10
REPLACEMENT .................................................................................................................................... 10
RESTORATION ..................................................................................................................................... 10
SHUT-DOWN ......................................................................................................................................... 11
DISPOSAL ............................................................................................................................................. 11
TECHNICAL DATA ................................................................................................................................ 11
LIST OF ACCESSORIES ....................................................................................................................... 12
WARRANTY .......................................................................................................................................... 12
TECHNICAL CHANGES ........................................................................................................................ 12
NOTES .................................................................................................................................................. 13
APPROVAL ............................................................................................................................................ 14
ABOUT THE MANUAL
This manual is part of the product.
This manual must be observed and handed over to the operator to ensure that
the component operates as intended and to comply with the warranty terms.
Keep it in a safe place while you are using the product.
In addition to this manual, please also observe national regulations, laws and
Translation of original / Item No. 13 512 53 Version 01.2016
Combined heating oil filter breather type GS Pro-Fi® 3
Your safety and the safety of others are very important to us. We have provided many important safety messages in this assembly and operating manual.
Always read and obey all safety messages.
This is the safety alert symbol.
“DANGER”, “WARNING”, or “CAUTION”. These words mean:
May result in death or serious injury.
May result in death or serious injury.
May result in minor or moderate injury.
Has an effect on ongoing operation.
Capture fuels during maintenance work.
SAFETY ADVICE
This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word
describes a personal hazard with a high degree of risk.
describes a personal hazard with a medium degree of risk.
describes a personal hazard with a low degree of risk.
describes material damage.
Escaping, liquid fuels:
are hazardous for water
are inflammable category 1, 2 or 3 liquids
can ignite and cause burning
can cause injury through people falling or slipping
GENERAL PRODUCT INFORMATION
The combined heating oil filter breather type GS Pro-Fi® 3 is a professional filter breather system of the 3rd generation as “closed system” (GS). The GS Pro-Fi
®
3 meets the requirements of EN 12514-2, E DIN EN 12514-3, the technical regulation for oil firing installations DIN 4755:2004-11, the technical regulation for oil systems TRÖl and TRÖL (AT), respectively, as well as worksheet DWA-A 791 part 1 “Erection, operational requirements, and shut-down of fuel oil consumer systems”. The GS Pro-Fi
®
3 is a combination of a breather device, a filter, and an upstream shut-off fitting. It ensures that the liquid fuel oil is filtered and the gases released during the suction process are discharged at the same time. The gas is not discharged into the environment, but within the closed system via the burner nozzle in the combustion chamber, which is why the system works without producing any smell. The GS Pro-Fi according to the single string system with return supply.
®
3 is only installed into the suction lines of supply/oil systems designed
2 / 16 Item No. 13 512 53
Combined heating oil filter breather type GS Pro-Fi® 3
www.gok-online.de/de/downloads/technische-dokumentation.
INTENDED USE
Operating media
Diesel fuel
Kerosene
FAME
Fuel oil
Bio fuel oil, 30% (V/V) FAME
You will find a list of operating media with descriptions, the
relevant standards and the country in which they are used in the Internet at
Installation location
for being installed in oil systems designed as single string system with return supply
above and below the tank crown, respectively
INAPPROPRIATE USE
All uses that are not appropriate:
e.g. operating with different media,
different inlet or outlet pressures
installation against the flow direction
USER QUALIFICATION
This product may be installed only by qualified experts. These are personnel who are familiar with setting up, installing, starting up, operating and maintaining this product. "Equipment and systems requiring supervision may be operated only by persons aged at least 18, who are physically capable and who have the necessary specialist knowledge or who have been instructed by a competent person. Instruction at regular intervals, but at least once per year, is recommended."
ADVANTAGES AND EQUIPMENT
Combined heating oil filter breather type GS Pro-Fi® 3:
guaranteed smell-tight, without any further accessories
no escaping oil and oil foam, respectively
safety function in the event of hose rupture
integrated ball cock as required shut-off fitting upstream of the consumption equipment
connection hose for oil suction pump
version with vacuum pressure gauge -1.0 to +0.6bar, for controlling the vacuum in the
suction line and therefore the operating states
Item No. 13 512 53 3 / 16
Combined heating oil filter breather type GS Pro-Fi® 3
vent screw
Anti-siphon device
Withdrawal valve Typ VTK-3
Aspiration line
type GS Pro-Fi® 3
DESIGN
vent tray holding plate for wall assembly connection burner return line connection burner supply line clamping ring filter insert filter tray vacuum pressure gauge connection for tank line shut-off fitting screws for accepting the holding plate
Fuel oil consumer installation in single conduit system
Pressure compensation valve Typ DAV
4 / 16 Item No. 13 512 53
Combined heating oil filter breather
CONNECTIONS
Inlet,
Trading name and dimensions
Installation notes
screw-in fitting
compression fitting RVS
Outlet,
Trading name and dimensions
Installation notes
ball-cone connector
torque 15Nm
Single string system
Double string system
Conveyor system
Calculation
.
V
Operating medium (L/h)
= Gear output of the
=
.
V
Suction: (0.2 ÷ 0.5) m/s
Discharge: (1.0 ÷1.5) m/s
Taking into account the length of the suction
.
V
x t
Copper pipe
1 ÷ 10L/h
6 x 1mm
8 ÷ 45L/h
8 x 1mm
25 ÷ 130L/h
10 x 1mm
90 ÷ 170L/h
12 x 1mm
Lower flow rates in suction mode will result in an undesired formation of bubbles.
Piping with inner diameters of less than 4mm is not recommended!
Maximum total pressure loss of all fittings in the suction line = 0.4bar
Combined heating oil filter breather type GS Pro-Fi® 3
optional
acc. to standard
IG G 3/8 For accepting a screw-in fitting with O-ring
compr. fit. 6
optional
acc. to standard
thread AG G 3/8-KN
DETERMINATION OF THE FLOW RATE, THE PIPE DIAMETER, AND THE PRESSURE LOSS
Flow rate
The outlet pipe must be dimensioned pursuant to DIN 4755 in such a way that the mean flow rate of the fuel oil is between (0.2 and 0.5) m/s. In the event of too large a pipe diameter with low flow rates, undesired formation of gas bubbles may occur.
Determination of the flow rate w in m/s
Installation in ⇒
=
Volume flow rate
Heat input in kW / 10
Oil burner pump
Delivery rate of the booster pump
w = 0.3537
ID=inner pipe
diameter (mm)
For supply / oil systems, the following mean flow rate is applicable pursuant to DIN 4755:
line, the geodesic height, the suction height,
Fuel oil
and the fuel oil volume flow rate, the following can be recommended for selecting the piping:
Item No. 13 512 53 5 / 16
/ ID2
Combined heating oil filter breather type GS Pro-Fi® 3
NOTICE ON THE FILTER INSERT :
Female thread G 3/8 acc. to EN ISO 228-1, as
prEN 12514-4:2009 Figure D.1
O-ring dimensions 14x2 mm, included with delivery
Screw-in connectors, type B acc. to EN ISO 1179-
screw-in connector is 15 Nm
The pressure loss of the GS Pro-Fi® 3 depending on the fuel oil volume flow rate and the filter insert used can be found in the diagram:
There is no such thing as a universal filter insert. The filter insert should be selected based on the specifications of the burner manufacturer according to filter mesh and the present operating conditions. According to the recommendation of the IWO Institut für Wärme- und Öltechnik e.V, filter inserts made of sintered plastic materials with a mesh width of 30-75μm should be used. Regarding oil systems with so-called “Low-NOx burners” and burners with lower heat outputs, the GOK filter inserts FEINFILTERUNG (fine filtration) with a mesh width of < 35μm are recommended.
ASSEMBLY
Before assembly, check that the product is complete and has not suffered any damage during transport. Installation, maintenance and start-up may only be carried out by companies that are specialist companies for this work in terms of Section 3 of the German Ordinance on Facilities Handling Substances Hazardous to Water (VAwS) from 31 March 2010 (Federal Law Gazette, P. 377).
Connection assembly
screw-in opening G 3/8-UA-O acc. to
4 or prEN 12514-4 Annex C (adequate with type A acc. to DIN 3852-2) The recommended maximum torque with steel
6 / 16 Item No. 13 512 53
Combined heating oil filter breather type GS Pro-Fi® 3
The female thread can also take the GOK universal
The housing is made from a zinc die-cast alloy:

Flexible pipe assembly

www.gok-online.de/de/downloads/technische-dokumentation.
pipes and with soft pipe materials.
pipe. Risk of corrosion!
instructions - Compression fittings.
Universal connection set (UA):
connection set type UA, which corresponds to a compression joint type G acc. to prEN 12514-4:2009 Annex D.
Piping used:
Copper pipe with outer diameter 6, 8 or 10 mm, e.g. acc. to EN 1057
Do not use a conical pipe thread acc. to EN 10226-1.
The following connections may be used in addition for flexible oil lines and their pendant:
cap nut G 3/8 with inside taper 60° pursuant to prEN 12514-4 Appendix B
More information about Universal connection fitting type UA can be found at
A reinforcement ring must be used with all thin-walled
Brass reinforcement rings may not come into contact with aluminium
More information about compression fittings can be found at
www.gok-online.de/en/downloads/technical
-documentation/Assembly
Installation position and mounting
Installation position vertical as a matter of principle,
filter tray with filter insert at the bottom
vent tray at the top.
The GS Pro-Fi 3
®
is delivered with pre-mounted holding plate for wall assembly. It can be
mounted on both sides of the housing.
Pull down the holding plate, remove the holding plate, suspend it with the screws on the opposite side of the housing, and push it upwards.
The specialised company and the operator must observe, comply with and understand all of the following instructions in this assembly and operating manual. For the system to function as intended, it must be installed professionally in compliance with the technical rules applicable to the planning, construction and operation of the entire system.
Item No. 13 512 53 7 / 16
Combined heating oil filter breather type GS Pro-Fi® 3
It is important that metal chips or other residues are blown out.
Do not use unsuitable tools, such as pliers.
NOTICE FOR LEAK TESTING
type UPE-300 item no. 13 602 00 for leak testing.
NOTICE
Please find comprehensive information on leak testing pursuant to TRÖI and worksheet DWA-A 791 on the Internet.
Pursuant to TRÖl chapter 4.10.4.2. “Vacuum
Malfunctions caused by residues.
Proper functioning is not guaranteed.
Visually check that there are no metal chips or other residues in the connections.
Install with suitable tools, if required.
Regarding screw connections, use a second spanner to brace against the connection nozzle.
Option assembly metal filter tray PS 16bar instead of plastic filter tray
Loosen the clamping ring by anti-clockwise rotation, hold and remove the filter tray
Do not damage the O-ring, refurbish if required (oil new O-ring!)
Fit the metal filter tray and the O-ring and manually tighten by rotating the clamping ring
in a clockwise direction
Perform leak testing activities!
LEAK CHECK
Check the condition of the system:
before initial start-up,
after major changes,
after repairs,
after the system has been out of operation for more than one year.
Check the system with 1.1 x the operating pressure using air or an inert gas. The system is leakproof if the test pressure does not drop after 10 minutes. Prior to start-up, the oil system with GS Pro-Fi® 3, including the connections, must be subjected to leak testing. This may be performed within the framework of leak testing pursuant to TRÖI and worksheet DWA-A 791, as well as function check of the oil system. In the event of possible leaks, these must be eliminated, e.g. repeated assembly of the connections using new gaskets, tightening of the screwed connections. Observe the notice in MAINTENANCE!
We recommend using the vacuum test device for oil systems pursuant to TRÖl
leak testing”, the test time is:
10 minutes plus the time required for temperature equalisation.
The oil line is deemed tight if the pressure increase during the specified test time is not higher than 30mbar. If this requirement is not met, the leak must be found applying a slight over-pressure and foam-forming substances and the error must be eliminated. Thereafter, the oil system must be re-checked.
8 / 16 Item No. 13 512 53
Combined heating oil filter breather type GS Pro-Fi® 3
Once leak testing is completed and the system is leak-tight, only the toggle valve of
immediately. If required, re-pump.
Fault cause
Action
Hose rupture in the supply or return line
Burner switches to failure due to the sucked in ambient air Restore the leak-tightness of the system
Released air in the vent tray
Burner switches to failure due to the sucked in ambient air Restore the leak-tightness of the system
Strong noise generation of the burner pump
Filter insert is clogged For replacing the filter insert, see MAINTENANCE
Level in the filter tray decreases
System has a leak
Restore the leak-tightness of the system
Filter tray runs empty,
System has a leak
Restore the leak-tightness of the system
START-UP
the tank discharge fitting or, for systems without toggle valve, the shut-off safety device must be opened. The vacuum still present in the line will suck fuel oil
Unless specified differently in the burner/boiler manufacturer’s manual, the procedure is as follows:
bleed the installed oil lines (burner supply and return lines) and the fittings using a suction pump and fill in fuel oil
open the shut-off fitting and the vent screw
connect the suction pump directly at the vent screw
using the supplied adapter item no. 13610-60
only stop the suction process once the vent tray is filled with oil as well
close the vent screw in a leak-tight manner
OPERATION
During ongoing operation of the oil system, the GS Pro-Fi® 3 does not require any operation. The integrated shut-off fitting must be opened. For this, the rotary handle must be rotated in the flow Due to the design of the GS Pro-Fi® 3, the full fuel oil column without any noticeable shares of air is available when starting the burner.
TROUBLESHOOTING
direction.
Item No. 13 512 53 9 / 16
Combined heating oil filter breather type GS Pro-Fi® 3
Replacing the filter insert:
Switch off the burner and prevent the return of the oil column into the tank
without replacement filter
with replacement filter
Loosen the clamping ring by anti-
clockwise direction
Loosen the replacement filter by anti-
MAINTENANCE
The following is recommended within the framework of annual maintenance or after extended periods of non-use:
leak testing of the fitting, including the connections
visual inspection of the plastic filter tray and the vent tray for possible damage: cracks
or deformation
replacement of the filter insert
after flooding, clean the external contamination on the filter using a commercially available
domestic cleaning agent
When using solvent-containing cleaning agents, the plastic filter trays or other plastic parts may be destroyed
REPLACEMENT
If there is any sign of wear or if the product or parts thereof are damaged, it must be replaced. When the product has been replaced, observe the steps ASSEMBLY, LEAK TESTING and START-UP.
Close the shut-off fitting
Use a collector
Clean the line sections downstream of the filter particularly carefully prior to re-installation
clockwise rotation, hold and remove the filter tray
Do not damage the O-ring, refurbish if required (oil new O-ring!) Use red GOK O-ring only!
clockwise rotation, hold adapter using a jaw spanner SW 70
Oil the gasket of the new replacement filter
Fit new replacement filter and tighten
through clockwise rotation
Unscrew the old filter insert
Clean the sealing surface and the O-ring
Insert the new filter insert firmly
Fit the filter tray and the O-ring and tighten by rotating the clamping ring in a
If the filter tray is damaged or destroyed, it must be replaced by a new one, the approach is identical to the procedure of replacing the filter insert. The vent tray can only be replaced completely with the vent screw .
RESTORATION
If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is no dimensioning problem, the product must be sent to the manufacturer to be checked. Our warranty does not apply in cases of unauthorised interference.
10 / 16 Item No. 13 512 53
Combined heating oil filter breather type GS Pro-Fi® 3
In order to protect the environment, products contaminated with water-
The product must be disposed of via local collection stations or a recycling station.
Maximum admissible pressure PS
PS 6bar with plastic tray PS 10bar with replacement filter insert
PS 16bar with metal tray
Housing material Pressure resistance housing
Zinc die cast ZP0410 PS 16bar
Nominal flow rate Vn
110L/h
Pressure loss Siku 70μm
MC 7, 5 - 20μm
110mbar
120mbar
Ventilation output
10L/h
Flow rate V
difference
Ambient temperature
SHUT-DOWN
During extended periods of non-use or MAINTENANCE work, the rotary handle of the shut-off fitting must be rotated to the position perpendicular to the flow direction - the shut-off fitting is closed. When using the product the next time, observe the steps LEAK TESTING and START-UP!
DISPOSAL
hazardous substances or that have come in contact with such substances must not be disposed of in the domestic waste, to public waters or channels.
TECHNICAL DATA
Pressure loss Siku 70μm Pressure loss Siku 70μm
n,R
210mbar 105mbar
return line – supply line at maximum pressure
Δp
o,d,max
= 1.3bar
-10°C to +60°C
Item No. 13 512 53 11 / 16
LIST OF ACCESSORIES
Product name
Item no.
Vacuum test device Typ UPE-300
13 602 00
Oil suction pump with suction and discharge hoses
13 610 00
Spare parts for filters
Filter tray 500 plastic blue-transparent 79mm (PS 6bar)
13 850 22
Filter tray 500 plastic blue-transparent 170mm (PS 6bar)
13 850 23
Filter tray 500 metal zinc die cast (PS 16bar)
13 850 25
Clamping ring 500 metal zinc die cast
13 850 60
O-ring 500 NBR
13 850 24
O-ring 500 FKM
25 521 64
Adapter for replacement filter metal zinc die cast
13 851 65
Sealing ring for adapter NBR
13 851 68
Retrofit kit replacement filter consisting of: Adapter, sealing ring for adapter
type
Filter tray 500 plastic blue-transparent 79mm with ventilation valve (PS 6bar)
Filter tray 500 metal zinc die cast with ventilation valve
13 514 26
Accessories for filter assembling
Installation wrench clamping ring 500 plastic
13 850 88
Changeover kits for filter type GS Pro-Fi® 3
to filter insert long Siku 70μm
13 852 53
to filter insert long Siku 35μm
13 852 54
to replacement filter 25µm
13 851 62
We guarantee that the product will function as intended and will not leak during
of our terms and conditions of delivery and payment.
Combined heating oil filter breather type GS Pro-Fi® 3
and O-ring 500 NBR, without replacement filter (PS 10bar) for GS Pro-Fi® 3
13 851 67
13 514 25
WARRANTY
the legally specified period. The warranty term begins when the product is handed over to the customer. The scope of our warranty is based on Section 8
TECHNICAL CHANGES
All the information contained in this assembly and operating manual is the result of product testing and corresponds to the level of knowledge at the time of testing and the relevant legislation and standards at the time of issue. We reserve the right to make technical changes without prior notice. Errors and omissions excepted. All figures are for illustration purposes only and may differ from actual designs.
12 / 16 Item No. 13 512 53
NOTES
Combined heating oil filter breather type GS Pro-Fi® 3
Item No. 13 512 53 13 / 16
Combined heating oil filter breather type GS Pro-Fi® 3
APPROVAL
DoCMR pursuant to Building Rules List according to EN 12514-2
14 / 16 Item No. 13 512 53
Combined heating oil filter breather type GS Pro-Fi® 3
Item No. 13 512 53 15 / 16
Combined heating oil filter breather type GS Pro-Fi® 3