goClima AWR518CL, FCR518CL, AER518SC Technical Data & Service Manual

TECHNICAL DATA & SERVICE MANUAL
Indoor Unit Outdoor Unit
AWR518CL AER518SC FCR518CL
SPLIT SYSTEM AIR CONDITIONER
0.8180.218.0 07/2001
®
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1 OPERATING RANGE 1 2 SPECIFICATIONS
2-1 Unit Specification 2 2-2 Major Component Specifications 4
2-3 Other Component Specifications 7 3 DIMENSIONAL DATA 9 4 REFRIGERANT FLOW DIAGRAM 12 5 PERFORMANCE DATA
5-1 Performance Charts 13 5-2 Air Throw Distance Chart 14 5-3 Cooling Capacity 16
6 ELECTRICAL DATA
6-1 Electrical Characteristic 18
6-2 Electric Wiring Diagrams 19 7 INSTALLATION INSTRUCTIONS
7-1 Installation Site Selection 21 7-2 Remote Control Unit Installation Position 23 7-3 Recommended Wire Length and Diameter 24
8 FUNCTION 8-1 Room Temperature Control 25 8-2 Dry Operation 26 8-3 Freeze prevention 26 8-4 Outdoor Fan Speed Control 27
9 REFRIGERANT R407C:SPECIAL PRECAUTION WHEN SERVICING UNIT 9-1 Characteristics of new refrigerant R407c 28 9-2 Checklist before servicing 28 9-3 Tools specifically for R407c 29 9-4 For tubing installation procedures 29 9-5 In case of compressor malfunction 30 9-6 In case refrigerant is leaking 31 9-7 Charging additional refrigerant 34 9-8 Retro-fitting existing system 34
10 TROUBLESHOOTING
10-1 Check before and after troubleshooting 35
10-2 Air Conditioner Does not operate 36
10-3 Some Parts of Air Conditioner does not operate 40 10-4 Air Conditioner Operates, but abnormalities are observed 42 10-5 If a sensor is defective 43
ii
11 CHECKING ELECTRICAL COMPONENTS 11-1 Measurements of insulation resistance 44 11-2 Checking continuity of fuse on PCB ass’y 45 11-3 Checking motor capacitor 46
12 DISASSEMBLY PROCEDURE FOR INDOOR UNIT 12-1 Removing air intake grille 46 12-2 Removing side panels 47 12-3 Access and removal of electrical components box 47 12-4 Removing flap motor 48 12-5 Removing evaporator 48 12-6 Removing fan and fan motor 50
iii
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 230 V Single phase 50Hz Voltage rating V 230
Cooling
Capacity
kW 4.80
BTU/h 16400
Air circulation (High) m
3
/h 760 Moisture removal (High) Liters/h 2.2 Available voltage range V 198 to 264 Running amperes A 9.1 Power input W 1950 Power factor % 93 C.O.P. W/W 2.50 Compressor locked rotor amperes A 43 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 1840 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 55 / 51/ 49
Outdoor – Hi dB-A 62 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 830
Depth mm 206 305 Package dimensions Height mm 276 713
Width mm 1,070 994
Depth mm 363 413
Weight Net
kg 12.0 52.0
Shipping
kg 15.0 57.0
Shipping volume m
3
0.11 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit AWR518CL Outdoor Unit AER518SC
2
2. SPECIFICATIONS
2-1. Unit Specifications
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 230 V Single phase 50Hz Voltage rating V 230
Cooling
Capacity
kW 4.80
BTU/h 16400
Air circulation (High) m
3
/h 800 Moisture removal (High) Liters/h 2.3 Available voltage range V 198 to 264 Running amperes A 9.1 Power input W 1950 Power factor % 93 C.O.P. W/W 2.5 Compressor locked rotor amperes A 43 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 1840 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 58 / 55 / 52
Outdoor – Hi dB-A 62 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 630
Width mm 900 830
Depth mm 190 305 Package dimensions Height mm 813 713
Width mm 1011 994
Depth mm 296 413
Weight Net
kg 23.5 52.0
Shipping
kg 30.0 57.0
Shipping volume m
3
0.24 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit FCR518CL Outdoor Unit AER518SC
4
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K188E Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–8PS3E
Type Cross-flow Q´ty ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Q´ty UF2– 31A5PA–S ... 1 No. of poles ... rpm (High) 2 ... 1,305 Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN : 130.4
WHT – PNK : 169.8
– : – – : – – :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 20°C) Each terminals (1–2, 1–3, 1–4, 1–5) 400 : ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m2 0.250
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit AWR518CL
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K185GS–N Controls Microprocessor Control circuit fuse 250 V – 3 A
Remote Control Unit RCS – 5PN3E
Type Centrifugal Number ... Dia. and length mm 2 ... ø 130 / L 180 Fan motor model ... Number K48410–M01417 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,140 Nominal output W 27 Coil resistance (Ambient temp. 20°C) GRY – WHT : 215 ± 7%
WHT – VLT : 87 ± 7%
VLT – YEL : 87 ± 7%
WHT – PNK : 273 ± 7%
Safety
Type Internal thermal fuse
devices
Operating temp.
Open °C 145 ± 5 Close Automatic reclosing
Run capacitor
µF 2.0
VAC 440 Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ±15%
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area m
2
0.192
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit FCR518CL
6
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Controller PCB
Type Rotary (Hermetic) Compressor model C–2RN150H5W 80805045 Nominal output W 1500 Compressor oil ... Amount cc DAPHNE FV68S ... 750 Coil resistance (Ambient temp. 25°C) Ω C – R : 1.42
C – S : 4.12
Type Internal protector
Safety
Overload relay —
devices Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C) —
Run capacitor µF 40.0
VAC 450 Crank case heater Type Propeller Number ... Dia. mm 1 ... ø 400 Fan motor model ... Number Smen 19TFB6055 ... 1 No. of poles ... rpm (230 V, High) 6 ... 910 Nominal output W 43
Coil resistance (Ambient temp. 20°C) Ω WHT – BRN : 77.7 ± 7%
WHT – YEL : 366.0 ± 7%
WHT – PNK : 211.0 ± 7%
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 5.2
VAC 440 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area m
2
0.508
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
Outdoor Unit AER518SC
2-3. Other Component Specifications
7
Thermistor (Room sensor) DTN-TKS142B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit AWR518CL
Indoor Unit FCR518CL
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance k 10°C 10.0 ± 4% 30°C 4.0 ± 4%
15°C 7.9 ± 4% 35°C 3.3 ± 4% 20°C 6.3 ± 4% 40°C 2.7 ± 4% 25°C 5.0 ± 4% 50°C 1.8 ± 4%
Thermistor (Coil sensor TH1) PBC-41E-S14
Resistance k –20°C 40.1 ± 5% 20°C 6.5 ± 5%
–10°C 24.4 ± 5% 30°C 4.4 ± 5%
0°C 15.3 ± 5% 40°C 3.0 ± 5%
10°C 9.9 ± 5% 50°C 2.1 ± 5%
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50/60Hz
Secondary 11V, 0.727A Capacity 8VA
Coil resistance (at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
Thermostat (Fan Speed Control 23S) MQT5S-27YZJ
Switching temp. °C
high LOW 23.5°C
+0 –2.5
low HIGH 27.0°C
+0 –3
Contact rating AC 220V, 3A
Power Relay G7L-2A-TUB
Coil rating AC 200–240V, 50/60Hz Coil resistance k(at 23°C) ( 21 ± 15% ) Contact rating AC 220V, 25A
Outdoor Unit AER518SC
8
9
3. DIMENSIONAL DATA
Indoor Unit AWR518CL
28545
995
45
147.5 147.5
206 (3)
Remote control unit
Center of tubing hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2") KR188E
61
18.5
172.5
Unit : mm
Indoor Unit FCR518CL
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2")
Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
FCR518CL
Dimensions : mm
10
61
18.5
172.5
11
Outdoor Unit AER518SC
Air discharge
Air intake
538 146
307
337
4 – ø12 holes
830
19
630
305
61 95
Wide tube service valve ø12.7 (1/2")
Narrow tube service valve ø6.35 (1/4")
Unit : mm
4. REFRIGERANT FLOW DIAGRAM
12
Capillary tube
Compressor
Accumulator
Wide tube service valve
Wide tube
O.D. ø12.7 mm (1/2 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Condenser
Indoor Unit Outdoor Unit
Evaporator
Strainer
Indoor Unit AWR518CL Outdoor Unit AER518SC
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
FCR518CL
13
5. PERFORMANCE DATA
5-1. Performance charts
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B.
Outdoor air temperature 35°C D.B./24°C W.B.
NOTE
Indoor Unit AWR518CL
Outdoor Unit AER518SC
Cooling Characteristics
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
0.29 ( 2 )
0.19 ( 1 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Outdoor fan speed
HighLow
15 14 13 12 11 10
9 8 7
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
16
Outdoor fan speed
HighLow
32 27
21
32 27 21
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)