TECHNICAL DATA & SERVICE MANUAL
Indoor Unit Outdoor Unit
AWR518CL AER518SC
FCR518CL
SPLIT SYSTEM AIR CONDITIONER
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg2.png)
i
Important!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person,
it is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
●Carefully read this instruction booklet before
beginning.
●Follow each installation or repair step exactly as
shown.
●Observe all local, state, and national electrical codes.
●Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or
death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help
for a special problem, contact our sales/service outlet
or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD
ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can
cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
units weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to
prevent “sweating” that can cause dripping and water
damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to
provide a solid, level foundation for the outdoor unit.
This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces
of the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leakfree connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any
moving parts.
• Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or
testing the refrigeration system. Escaped refrigerant
gas, on contact with fire or heat, can produce
dangerously toxic gas.
• Confirm upon completing installation that no
refrigerant gas is leaking. If escaped gas comes in
contact with a stove, gas water heater, electric room
heater or other heat source, it can produce
dangerously toxic gas.
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg3.png)
Table of Contents
Page
1 OPERATING RANGE 1
2 SPECIFICATIONS
2-1 Unit Specification 2
2-2 Major Component Specifications 4
2-3 Other Component Specifications 7
3 DIMENSIONAL DATA 9
4 REFRIGERANT FLOW DIAGRAM 12
5 PERFORMANCE DATA
5-1 Performance Charts 13
5-2 Air Throw Distance Chart 14
5-3 Cooling Capacity 16
6 ELECTRICAL DATA
6-1 Electrical Characteristic 18
6-2 Electric Wiring Diagrams 19
7 INSTALLATION INSTRUCTIONS
7-1 Installation Site Selection 21
7-2 Remote Control Unit Installation Position 23
7-3 Recommended Wire Length and Diameter 24
8 FUNCTION
8-1 Room Temperature Control 25
8-2 Dry Operation 26
8-3 Freeze prevention 26
8-4 Outdoor Fan Speed Control 27
9 REFRIGERANT R407C:SPECIAL PRECAUTION WHEN SERVICING UNIT
9-1 Characteristics of new refrigerant R407c 28
9-2 Checklist before servicing 28
9-3 Tools specifically for R407c 29
9-4 For tubing installation procedures 29
9-5 In case of compressor malfunction 30
9-6 In case refrigerant is leaking 31
9-7 Charging additional refrigerant 34
9-8 Retro-fitting existing system 34
10 TROUBLESHOOTING
10-1 Check before and after troubleshooting 35
10-2 Air Conditioner Does not operate 36
10-3 Some Parts of Air Conditioner does not operate 40
10-4 Air Conditioner Operates, but abnormalities are observed 42
10-5 If a sensor is defective 43
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg4.png)
11 CHECKING ELECTRICAL COMPONENTS
11-1 Measurements of insulation resistance 44
11-2 Checking continuity of fuse on PCB ass’y 45
11-3 Checking motor capacitor 46
12 DISASSEMBLY PROCEDURE FOR INDOOR UNIT
12-1 Removing air intake grille 46
12-2 Removing side panels 47
12-3 Access and removal of electrical components box 47
12-4 Removing flap motor 48
12-5 Removing evaporator 48
12-6 Removing fan and fan motor 50
iii
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg5.png)
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg6.png)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 230 V Single phase 50Hz
Voltage rating V 230
Cooling
Capacity
kW 4.80
BTU/h 16400
Air circulation (High) m
3
/h 760
Moisture removal (High) Liters/h 2.2
Available voltage range V 198 to 264
Running amperes A 9.1
Power input W 1950
Power factor % 93
C.O.P. W/W 2.50
Compressor locked rotor amperes A 43
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407c / 1840
Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 55 / 51/ 49
Outdoor – Hi dB-A 62
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 12.7 (1/2)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 830
Depth mm 206 305
Package dimensions Height mm 276 713
Width mm 1,070 994
Depth mm 363 413
Weight Net
kg 12.0 52.0
Shipping
kg 15.0 57.0
Shipping volume m
3
0.11 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit AWR518CL
Outdoor Unit AER518SC
2
2. SPECIFICATIONS
2-1. Unit Specifications
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg7.png)
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 230 V Single phase 50Hz
Voltage rating V 230
Cooling
Capacity
kW 4.80
BTU/h 16400
Air circulation (High) m
3
/h 800
Moisture removal (High) Liters/h 2.3
Available voltage range V 198 to 264
Running amperes A 9.1
Power input W 1950
Power factor % 93
C.O.P. W/W 2.5
Compressor locked rotor amperes A 43
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407c / 1840
Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 58 / 55 / 52
Outdoor – Hi dB-A 62
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 12.7 (1/2)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 630
Width mm 900 830
Depth mm 190 305
Package dimensions Height mm 813 713
Width mm 1011 994
Depth mm 296 413
Weight Net
kg 23.5 52.0
Shipping
kg 30.0 57.0
Shipping volume m
3
0.24 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit FCR518CL
Outdoor Unit AER518SC
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg8.png)
4
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K188E
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–8PS3E
Type Cross-flow
Q´ty ... Dia. and length mm 1 ... ø88 / L746
Fan motor model ... Q´ty UF2– 31A5PA–S ... 1
No. of poles ... rpm (High) 2 ... 1,305
Nominal output W 30
Coil resistance (Ambient temp. 20°C) Ω WHT – BRN : 130.4
WHT – PNK : 169.8
– : –
– : –
– : –
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440
Type Stepping motor
Model MP24GA2
Rating DC 12 V
Coil resistance (Ambient temp. 20°C) Ω Each terminals (1–2, 1–3, 1–4, 1–5) 400 : ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m2 0.250
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit AWR518CL
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg9.png)
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K185GS–N
Controls Microprocessor
Control circuit fuse 250 V – 3 A
Remote Control Unit RCS – 5PN3E
Type Centrifugal
Number ... Dia. and length mm 2 ... ø 130 / L 180
Fan motor model ... Number K48410–M01417 ... 1
No. of poles ... rpm (230 V, High) 4 ... 1,140
Nominal output W 27
Coil resistance (Ambient temp. 20°C) Ω GRY – WHT : 215 ± 7%
WHT – VLT : 87 ± 7%
VLT – YEL : 87 ± 7%
WHT – PNK : 273 ± 7%
Safety
Type Internal thermal fuse
devices
Operating temp.
Open °C 145 ± 5
Close Automatic reclosing
Run capacitor
µF 2.0
VAC 440
Model M2LJ24ZE31
Rating AC 208 / 230 V, 50 / 60 Hz
No. of poles ... rpm 8 ... 2.5 / 3.0
Nominal output W 3 / 2.5
Coil resistance (Ambient temp. 20°C) kΩ 16.45 ±15%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.8
Face area m
2
0.192
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit FCR518CL
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bga.png)
6
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Controller PCB —
Type Rotary (Hermetic)
Compressor model C–2RN150H5W 80805045
Nominal output W 1500
Compressor oil ... Amount cc DAPHNE FV68S ... 750
Coil resistance (Ambient temp. 25°C) Ω C – R : 1.42
C – S : 4.12
Type Internal protector
Safety
Overload relay —
devices Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C) —
Run capacitor µF 40.0
VAC 450
Crank case heater
Type Propeller
Number ... Dia. mm 1 ... ø 400
Fan motor model ... Number Smen 19TFB6055 ... 1
No. of poles ... rpm (230 V, High) 6 ... 910
Nominal output W 43
Coil resistance (Ambient temp. 20°C) Ω WHT – BRN : 77.7 ± 7%
WHT – YEL : 366.0 ± 7%
WHT – PNK : 211.0 ± 7%
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 5.2
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.8
Face area m
2
0.508
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
Outdoor Unit AER518SC
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bgb.png)
2-3. Other Component Specifications
7
Thermistor (Room sensor) DTN-TKS142B
Resistance kΩ 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance kΩ 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance Ω (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance kΩ 10°C 10.0 ± 4% 30°C 4.0 ± 4%
15°C 7.9 ± 4% 35°C 3.3 ± 4%
20°C 6.3 ± 4% 40°C 2.7 ± 4%
25°C 5.0 ± 4% 50°C 1.8 ± 4%
Thermistor (Coil sensor TH1) PBC-41E-S14
Resistance kΩ –20°C 40.1 ± 5% 20°C 6.5 ± 5%
–10°C 24.4 ± 5% 30°C 4.4 ± 5%
0°C 15.3 ± 5% 40°C 3.0 ± 5%
10°C 9.9 ± 5% 50°C 2.1 ± 5%
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50/60Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance Ω (at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bgc.png)
Thermostat (Fan Speed Control 23S) MQT5S-27YZJ
Switching temp. °C
high ➞ LOW 23.5°C
+0
–2.5
low ➞ HIGH 27.0°C
+0
–3
Contact rating AC 220V, 3A
Power Relay G7L-2A-TUB
Coil rating AC 200–240V, 50/60Hz
Coil resistance kΩ (at 23°C) ( 21 ± 15% )
Contact rating AC 220V, 25A
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bgd.png)
9
3. DIMENSIONAL DATA
Indoor Unit AWR518CL
28545
995
45
147.5 147.5
206 (3)
Remote control unit
Center of tubing
hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2") KR188E
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bge.png)
86
74 74
Center of tubing hole
ø75 (4 places)
Wide tube ø12.7 (1/2")
Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
FCR518CL
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bgf.png)
Air discharge
Air intake
538 146
307
337
4 – ø12 holes
830
19
630
305
61
95
Wide tube service valve
ø12.7 (1/2")
Narrow tube service valve
ø6.35 (1/4")
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg10.png)
4. REFRIGERANT FLOW DIAGRAM
12
Capillary tube
Compressor
Accumulator
Wide tube
service
valve
Wide tube
O.D.
ø12.7 mm
(1/2 ")
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Condenser
Indoor Unit Outdoor Unit
Evaporator
Strainer
Indoor Unit AWR518CL Outdoor Unit AER518SC
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
![](/html/16/1610/1610d808bf6367d6447c7bf82e710f2f46a47c1503904b3d139bcecca6bef062/bg11.png)
13
5. PERFORMANCE DATA
5-1. Performance charts
● ...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B.
Outdoor air temperature 35°C D.B./24°C W.B.
■ Cooling Characteristics
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
0.29 ( 2 )
0.19 ( 1 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Outdoor
fan speed
HighLow
15
14
13
12
11
10
9
8
7
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
16
Outdoor
fan speed
HighLow
32
27
21
32
27
21
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)