Gneub TMV V2LC 3 Operating Instructions Manual

Tel/26.07.99 Seite - 1 -
Measurement technology for extrusion
Operating instructions
Pressure Measurement Amplifier
Please read these instructions carefully before connecting or operating the equipment.
Certified acc. to
ISO 9001
Tel/26.07.99 Seite - 2 -
Index:
1. General description 6. Display and operating elements
2. Technical data 7. Programme access – locking functions
3. Assembly 8. Commissioning
4. Electrical connection 9. Additional functions
5. Setting possibilities
1. General description:
The Gneuß temperature measurement amplifier type TMV V2LC 3 is a measurement amplifier for temperature sensors with thermocouples or PT-100 measuring rheostats. Universal setting possibilities guarantee that all market-usual temperature sensors can be connected. Furthermore, two freely-adjustable limit contacts and one analog signal 0-10 V or 0-20 mA or 4-20 mA can be processed. A peak-value memory, simple operation via touch-sensitive keyboard and extreme sturdiness guarantee a high ease of operation. The unit can be protected against unauthorized use via possible software settings and/or via jumpers (bridges).
2. Technical data:
Dimensions : Housing 96 x 48 x 134 incl. terminal block with quick lock
by means of plastic clamps for wall thicknesses of up to 50 mm. Material PC/ABS blend, black colour, weight approx. 0.450 kg. Cut-out size: 92,0
+0,8
x 45,0
+0,6
Insulation class : Front IP 54, connection IP 00 Input : Thermoco uple Type L / DIN 43710 -100 up to +900 °C
Thermocouple Type J / IEC 584 -200 up to +1200 °C Thermocouple Type K / IEC 584 -250 up to 1350 °C Measuring rheostat Pt-100 IEC 751 in 2, 3 or 4 conductors –
100 up to +600 °C Limit value relais : Freely adjustable over the whole measurement range
Switching capacity: 230 VAC = 2Amp. / 120 VDC = 0,5 Amp. Sensor break : Circuit-break control sensor connection Accuracy : 1 °C +/- 1digit
Temperature co -efficient 50ppm/K Power supply : Supply voltage 230 VAC +/- 10 %, 50 - 60 Hz. Power input
approx. 5VA optionally 120 VAC or 24 VDC Display : Seven-segment LED, 14 mm high
4 digits = display 9999 Overflow and (or) wire break displayed by 4 horizontal bars
Connection : Via 15-pole terminal block up to 2.5 mm
2
at the rear
Ambient conditions : Operating temperature 0-60 °C / Storing temperature
from -20 up to + 80 °C