GMW TG basic 1 User guide

TG basic 1
Appliance tester for testing protective measures in accordance with DIN VDE 0701-0702 (DIN EN 62638)
Operating manual (Version 1.00.8 or higher)
Operating manual for the TG basic 1 appliance tester
Table of contents Page
6.1. Initial equipping or battery replacement 8
6.2. Switching the tester on and off Selecting the measuring sequences 8
7. Explanation of terminology 11
7.1. Protection class I (PC I) 11
7.2. Protection class II (PC II) 11
7.3. Protection class III (PC III) 11
7.4. Protective conductor resistance (RPE)11
7.5. Insulation resistance (R
7.6. Substitute leakage current (IEA)12
)11
ISO
7.7. Visual inspection 12
8. Conducting tests in accordance with DIN VDE 0701-0702; Definition of standards 13
8.1. Visual inspection 13
8.2. Measuring the protective conductor resistance 13
8.3. Measuring the insulation resistance 13
8.4. Measuring the substitute leakage current for devices of protection class I 14
8.5. Measuring the substitute leakage current for devices of protection class II 15
8.6. Inspecting the inscriptions 15
9. Test procedures 16
9.1. Testing devices of protection class I 16
9.1.1. Measuring the protective conductor resistance 16
9.1.2. Measuring the insulation resistance 18
9.1.3. Measuring the substitute leakage current 19
9.1.4. Test assessment 19
9.2. Testing devices of protection class II 20
9.2.1. Measuring the insulation resistance 20
9.2.2. Measuring the substitute leakage current 20
9.2.3. Test assessment 21
9.3. Cable test 21
9.3.1. Protective conductor resistance 22
9.3.2. Insulation resistance 22
9.3.3. Cable test 22
9.4. Measuring the voltage at an external earthed mains socket 23
10. Checking the battery voltage 24
11. Technical data 24
12. Notes on cleaning 25
13. Calibrating the tester 25
14. Manufacturer’s guarantee conditions 26
GOSSEN Müller & Weigert
Operating manual for the TG basic 1 appliance tester
1. Safety information
Tests on the electrical safety of electrical appliances may only be carried out by qualified electricians or under their supervision. Carefully read through the following safety information before starting up the TG Basic appliance tester.
Symbols used in the operating manual and on the appliance tester:
Warning of a hazardous situation. Follow the operating manual.
Caution! Dangerous voltage, danger of electric shock.
Note: Please be sure to follow the manual!
&&
&
&&
CE mark of conformity
The operating manual contains information and notes
&&
&
&&
which are necessary for the safe operation and use of the appliance tester. Before using (starting up) the appliance tester, the operating manual should be carefully read through and followed in all points.
If the manual is not observed or if you fail to observe the
&&
&
&&
warnings and notes, serious injury to the user and damage to the appliance tester can occur.
All the technical data and quoted standards in this manual
&&
&
&&
are up-to-date at the time of going to press and have been determined to the best of our knowledge, nevertheless this data may be subject to errors and printing errors. Therefore no legal responsibility or any other liability can be accepted for incorrect information or the consequences of this information.
The respective provisions, regulations and standards are the authorities defining the procedures to be followed when conducting tests.
There is no intention to infringe on any existing patents and other property rights with this publication.
GOSSEN Müller & Weigert
3
Operating manual for the TG basic 1 appliance tester
2. Introduction
You have acquired a high-grade device from the company Gossen Müller & Weigert with which you can carry out repeatable measurements over a very long period of time. The product was calibrated during the manufacturing process in accordance with the specified operating procedures.
The TG basic 1 appliance tester, hereafter referred to as the tester, has been developed for carrying out the following measurements for testing the safety of electrical appliances in accordance with DIN VDE 0701-0702 (BGV A3):
- Measuring the protective conductor resistance
- Measuring the insulation resistance
- Measuring the substitute leakage current
- Testing of IEC and extension cables
- Measuring the power socket voltage Scope of delivery 1 qty TG basic 1 appliance tester
1 qty set of measuring accessories with safety test line, safety
crocodile clip and safety test tip 6 qty batteries of type AA (Mignon) 1 qty IEC connection cable, 0.5 m 1 qty carrying bag 1 qty operating manual
Transport and storage Please retain the original packaging for dispatch at a later date,
e.g. for calibration. Transport damage that occurs due to inadequate packaging is not covered by the manufacturer’s guarantee. The appliance tester must be stored in a dry, closed room. If the device is transported in extreme temperatures, it requires at least 2 hours acclimatisation before being switched on.
GOSSEN Müller & Weigert
4
Operating manual for the TG basic 1 appliance tester
3. Safety instructions
The appliance tester was constructed and tested in accordance with the applicable safety regulations and left the factory in a faultless safety condition. In order to maintain this condition and ensure safe operation, the user must observe the instructions and warnings contained in this operating manual.
With all work, the applicable accident prevention
&&
&
&&
regulations of the trade associations for electrical systems
and equipment must be observed.
To avoid electric shock, the applicable safety regulations
and DIN-VDE regulations regarding high touch voltage
must be observed without fail when working with voltages
greater than 120 V DC or 50 V AC. Measuring at a dangerous proximity to electrical systems should
only be carried out under the instruction of a responsible electrician, and never alone.
Check the appliance tester and the connecting cables for external damage before every new operation.
Make sure that the appliance tester and the cable connections are in faultless condition. The appliance tester may not be used if one or more functions fail or if functional readiness is not evident.
The measuring lines and the measuring accessories may
only be touched in the designated handling areas.
Touching measuring connections, e.g. test tips, must be
avoided under all circumstances.
If the safety of the operator is no longer guaranteed the
&&
&
&&
appliance tester must be decommissioned and secured
against unwanted use. This is the case if the device:
– Shows obvious signs of damage
– No longer carries out the required measurements
– Has been stored under adverse conditions for too long
GOSSEN Müller & Weigert
5
Operating manual for the TG basic 1 appliance tester
4. Appropriate usage
The tester may only be used under the conditions and for the purposes for which it has been designed. It is particularly important to observe the safety instructions and the technical data regarding ambient conditions and usage in a dry environment.
The appliance tester may not be used for measuring in electrical systems.
Operational safety is no longer guaranteed in the case of modifications or conversions that have not been carried out by the manufacturer.
Maintenance or calibration work may only be carried out by the manufacturer.
Subject the appliance tester to an electromagnetic field can impair the function of the appliance tester.
In order to avoid damaging the appliance tester, the test socket and the test line may not be connected to an external voltage source.
Only the supplied original measuring lines or equivalent safety measuring accessories may be used!
GOSSEN Müller & Weigert
6
Operating manual for the TG basic 1 appliance tester
5. Operating elements
Explanation of the appliance tester’s connections, operating elements and displays.
In-case socket for IEC appliances, for testing connection and extension cables/ measuring the mains voltage at a protective earth mains socket.
T est socket for connecting test objects
„Probe“ connection socket (red) for the test line
LC display
Briefly pressing the „START“ button: start measuring, press and hold for 2 s: Help function
GOSSEN Müller & Weigert
Rotary switch for selecting the type of measurement
7
Operating manual for the TG basic 1 appliance tester
6. Starting up
6.1. Initial equipping or battery replacement
The tester is operated using 6 x 1.5 V type AA batteries (IEC LR6) or six type AA rechargeable batteries. The six batteries supplied must be inserted into the tester before starting the device. Proceed as follows to insert the batteries:
- Switch off the device (rotary switch in the „OFF“ position)
- Release the screw from the battery cover
- Lift the cover from the lower part of the case
- Remove the old batteries if necessary
- Insert the batteries into the correct locations in the
battery compartment (taking care to ensure correct
polarity)
- Click the battery cover into place in the lower part of the
case and secure it by tightening the screw
6.2. Switching the tester on and off – Selecting the
measuring sequences
The tester is operated via a rotary switch and a „Start“ button.
EIN
ON
AUS
OFF
Measurements for devices with protective conductor (PC I)
Measurements for devices without protective conductor (PC II)
Measurements for testing the device connection and extension cable (LPR)
GOSSEN Müller & Weigert
8
Operating manual for the TG basic 1 appliance tester
„OFF“ switch position: Turning the rotary switch to the „OFF“ position switches off the
device. Turn the rotary switch to the „ON“ position to switch on the tester. The device performs a self-test. If the device is OK, the following switch-on message appears in the display:
Note that no other functions are available until the switch-
&&
&
&&
on message is displayed!
Selecting the menu language To select the menu language, turn the rotary switch to the „ON“
position and press the „Start“ button. The display shows the following menu. The desired language is selected by briefly pressing the „Start“ button (< 2 s). The respective number before the language designation blinks to indicate the currently selected language. Pressing the „Start“ button for a longer time (> 2 s) confirms the currently selected
language and exits the language selection.
GOSSEN Müller & Weigert
9
Operating manual for the TG basic 1 appliance tester
After the switch-on message has been displayed, the desired operating mode PC I, PC II or cable test can be selected. The „Measuring sequence“ window is displayed depending on the setting of the rotary switch.
Briefly pressing the „START“ button starts the selected measuring sequence.
Pressing the „START“ button for a longer time (> 2 s) calls up a quick guide for the select measurement type. Briefly pressing the „START“ button pages forwards through this quick guide. The scrollbar at the left provides an indication of how many pages are available in the quick guide.
Help window (example)
Pressing the „START“ button for a longer period of time returns you to the „Measuring sequence“ window.
If a measuring sequence is not started within a period of 3 minutes then the tester automatically switches off. To switch the tester on again, the rotary switch must first be set to the „OFF“ position and then back to the „ON“ position (normal switch-on procedure).
GOSSEN Müller & Weigert
10
Operating manual for the TG basic 1 appliance tester
7. Explanation of terminology
7.1. Protection class I (PC I)
The active parts of the device are protected against direct touching by the basic insulation. Through connection of the touchable conductive housing parts to the protective conductor, these are included in the protective measure in the case of direct touching (fault protection) with the system. The device has a protective conductor connection (earthed plug).
7.2. Protection class II (PC II)
The active parts are separated by strengthened or double insulation (basic insulation and additional insulation). This ensures protection against direct contact. Protection against indirect contact also exists, since an insulation fault is practically impossible. Such devices can nevertheless have touchable metallic housing parts. Devices of protection class II have a mains plug without an earth contact.
7.3. Protection class III (PC III)
Devices of protection class III are exclusively connected to protective extra-low voltage electric circuits. The protection against dangerous body currents is achieved by the low voltage and the safe separation from other electric circuits.
7.4. Protective conductor resistance (RPE)
Resistance between any conductive touchable parts, connected to the protective conductor for protective purposes, and the earthed contact of the mains plug, the device plug or the protective conductor, which is constantly connected to the mains power supply.
See also the measuring principle circuit under point 8.2.
&&
&
&&
7.5. Insulation resistance (R
This is the Ohmic resistance between conductive parts separated by insulation. Measurements are taken between the active parts and the body as well as touchable conductive parts that are not connected to the protective conductor.
See also the measuring principle circuit under point 8.3.
&&
&
&&
GOSSEN Müller & Weigert
)
ISO
11
Operating manual for the TG basic 1 appliance tester
7.6. Substitute leakage current (IEA)
Current that would flow through the interconnected active conductors of the device (test object) and the protective conductor or the touchable conductive parts at rated voltage and rated frequency of the device. This measuring method determines the leakage current without mains voltage. It is an alternative measuring method for determining protective conductor current or touch current.
See also the measuring principle circuit under point 8.4.
&&
&
&&
7.7. Visual inspection
Testing in accordance with DIN VDE 0701-0702 requires a visual inspection of the device. According to the standard, the devices should be inspected for external defects (without opening the device) and, as far as possible, for suitability to the place of installation. (More details are provided in the DIN VDE 0701-0702 standard).
GOSSEN Müller & Weigert
12
Operating manual for the TG basic 1 appliance tester
8. Conducting tests in accordance with
DIN VDE 0701-0702 Definition of standards
The sequence of tests is specified in the standard.
8.1. Visual inspection
The test objects are inspected for externally visible defects.
8.2. Measuring the protective conductor resistance
(for devices of protection class I)
The limit value is:
≤≤
Ω Ω
0.3
Ω for devices with connecting cables up to 5 m,
≤≤
Ω Ω
plus 0.1
1.0
Measuring principle circuit Protective conductor resistance PC I
Ω Ω
Ω for every extra 7.5 m, up to a maximum of
Ω Ω
ΩΩ
Ω.
ΩΩ
Appliance tester
´Probe´ socket
Test line
Test socket
8.3 Measuring the insulation resistance
The limit value is:
ΩΩ
1 M
Ω for devices of protection class I
ΩΩ ΩΩ
2 M
Ω for devices of protection class II
ΩΩ
ΩΩ
0.3 M
Ω for devices of protection class I (with switched-on
ΩΩ
heating elements)
1)
Also applies to touchable conductive parts of test objects in protection class I that are not connected to the protective conductor.
2)
If the required insulation resistance is not achieved in the case of test objects in protection class I with heating elements with a total capacity nevertheless rated as faultless if the protective conductor current does not exceed the limit values.
GOSSEN Müller & Weigert
2)
3.5 kW, the test object is
13
1)
Test object
Operating manual for the TG basic 1 appliance tester
Measuring principle circuit Insulation resistance PC I PC II
Appliance tester
Test object
´Probe´ socket
T est line
Test socket
´Probe´ socket
T est line
T est socket
8.4. Measuring the substitute leakage current for devices of protection class I
The substitute leakage current procedure is an alternative method for measuring the protective conductor current.
The limit value is 3.5 mA.
The substitute leakage current for test objects with heating elements having a total connected power greater than 3.5 kW must not be greater than 1 mA/kW heating power, up to a maximum value of 10 mA.
Measuring principle circuits Substitute leakage current procedure PC I
GOSSEN Müller & Weigert
Appliance tester
T est socket
T est object
14
Operating manual for the TG basic 1 appliance tester
8.5. Measuring the substitute leakage current for devices of protection class II
The substitute leakage current procedure is an alternative method for measuring the touch current.
The limit value is 0.5 mA.
Measuring principle circuits Substitute leakage current procedure PC II
Appliance tester
´Probe´ socket
T est line
Test socket
Test object
8.6. Inspecting the inscriptions
Safety-related inscriptions must be controlled and, where necessary, renewed or supplemented in suitable form.
GOSSEN Müller & Weigert
15
Operating manual for the TG basic 1 appliance tester
9. Test procedures
9.1. Testing devices of protection class I
Rotary switch position: Test object connection:
The test procedure occurs automatically in the sequence specified below:
- Protective conductor resistance
- Insulation resistance
- Substitute leakage current
Please note: The test object must be switched on.
&&
&
&&
The test sequence is started by pressing the „Start“ button for < 2 s.
9.1.1. Measuring the protective conductor resistance
The protective conductor resistance is measured using a measuring current > 200 mA DC. The direction of current is automatically reversed by the tester. The measuring sequence is indicated on the display as follows:
Exceeding of the limit value is indicated as follows:
- The momentary measurement value blinks
- An audio signal is emitted
33
A „
3“ is shown in the assessment field if the measurement does
33
not reach the limit value.
GOSSEN Müller & Weigert
16
Operating manual for the TG basic 1 appliance tester
At the start of measuring, the tester checks to see if the measuring current is greater than 200 mA. If this is not the case, the test is aborted. This can occur for the following reasons:
- The test object is not of protection class I
- The test object is not connected to the tester or the test line is not connected
- The protective conductor has an open-circuit This is indicated by a scrolling message in the status line. The tester performs the following checks:
a)Check of the test wiring!
The measurement procedure is continued when the missing connection to the test line or test object is restored and the measuring current is > 200 mA.
b)Check that the appliance conforms to
protection class I! If the tester detects that the appliance does not conform to protection class I, then the test must be aborted by pressing the „START“ button.
If the test wiring is „OK“ and the test object conforms to protection class I, then the protective conductor connection has an open­circuit or high resistance. The test must be aborted by pressing the „START“ button. When the test is aborted, the assessment window is shown in the display. Measurement of the insulation resistance and substitute leakage current is not performed. This also applies when the measured protective conductor resistance is > 1 Ω .
GOSSEN Müller & Weigert
17
Operating manual for the TG basic 1 appliance tester
When performing the protective conductor resistance measurement, the automatic test sequence can also be switched to a permanent measurement (max. 3 min).
When the tester is in the normal measuring mode, pressing the „START“ button switches the tester into the permanent measurement mode. The bar graph is then no longer shown in the display.
Pressing the button again continues the measurement with a reversed test current polarity. Pressing the button again ends the protective current measurement and continues with the next measurement in the measuring sequence.
During permanent measurement, the connecting cable of the test object should be moved, section by section, along its whole length, in order to find broken conductors or weak points. The momentary measurement values are continuously acquired and displayed by the tester. The maximum measurement value is stored and displayed in the assessment window at the end of the measuring sequence.
9.1.2. Measuring the insulation resistance
The insulation resistance is measured automatically. Switching to permanent measurement is not possible.
Failure to reach the limit value is indicated as follows:
- The momentary measurement value blinks
- An audio signal is emitted
33
A „
3“ is shown in the assessment field if the measurement
33
exceeds the limit value.
GOSSEN Müller & Weigert
18
Operating manual for the TG basic 1 appliance tester
9.1.3. Measuring the substitute leakage current
The substitute leakage current is measured automatically. Switching to permanent measurement is not possible.
Exceeding of the limit value is indicated as follows:
- The momentary measurement value blinks
- An audio signal is emitted
33
A „
3“ is shown in the assessment field if the measurement does
33
not reach the limit value.
9.1.4. Test assessment
When the automatic test sequence finishes, an assessment window is displayed.
The measurements and their assessments („X“ or „ displayed here. The status bar displays „Test OK“ or „Test n. OK“ depending on the result.
Briefly pressing the „START“ button will repeat the test or perform a new test if a new test object has been connected. Pressing the „START“ button for longer than 2 s will display the quick guide (see point 6.2.)
GOSSEN Müller & Weigert
19
33
3“) are
33
Operating manual for the TG basic 1 appliance tester
9.2. Testing devices of protection class II
- Testing devices without a protective conductor and with touchable conductive parts
- Testing devices with a protective conductor and with touchable conductive parts that are not connected to the protective conductor
Caution:
With these appliances, this test can only check the
&&
&
&&
insulation resistance and the substitute leakage current between the touchable electrical components that are not connected to the protective conductor and the L and N connections. Testing of the protective conductor resistance and the substitute leakage current relating to the protective conductor must first be performed after the measuring
sequence for protection class I appliances. Rotary switch position: Test object connection:
The test procedure occurs automatically in the sequence specified below:
- Insulation resistance
- Substitute leakage current
The test object must be switched on (mains switch).
&&
&
&&
The test sequence is started by pressing the „Start“ button
for 2 s.
9.2.1. Measuring the insulation resistance
The same statements apply as in point 9.1.2.
9.2.2. Measuring the substitute leakage current
The same statements apply as in point 9.1.3.
GOSSEN Müller & Weigert
20
Operating manual for the TG basic 1 appliance tester
9.2.3. Test assessment
The measurements and their assessments („X“ or „ displayed here. The status bar displays „Test OK“ or „Test n. OK“ depending on the result.
Briefly pressing the „START“ button will repeat the test or perform a new test if a new test object has been connected. Pressing the „START“ button for longer than 2 s will display the quick guide.
9.3. Cable test
The cable test allows testing of IEC cables (appliance connection cables with non-heating device connections), distribution boxes and extension cables.
Rotary switch position:
33
3“) are
33
The IEC connection line The test procedure occurs automatically in the sequence
specified below:
- Measuring the protective conductor resistance
- Measuring the insulation resistance
- Cable test
GOSSEN Müller & Weigert
21
Operating manual for the TG basic 1 appliance tester
9.3.1. Protective conductor resistance
The same statements apply as in point 9.1.2.
9.3.2. Insulation resistance
The same statements apply as in point 9.1.3.
9.3.3. Cable test
This test provides an additional function that is not part of the DIN VDE 0701-0702 standard. This test checks a connection cable or extension cable for open­circuits in the live (L) and neutral (N) conductors and for short­circuits between L and N.
Cable test assessment window:
Line open­circuit
Line short­circuit
Line OK
Briefly pressing the „START“ button will repeat the test or perform a new test if a new test object has been connected. Pressing the „START“ button for longer than 2 s will display the quick guide.
GOSSEN Müller & Weigert
22
Operating manual for the TG basic 1 appliance tester
9.4. Measuring the voltage at an external earthed mains
socket
The test allows checking of the voltage potentials between the LN, LPE and NPE terminals. The LPE and NPE display depends on the position of the live conductor in the
earthed mains socket (right or left). To perform the measurement, plug the IEC line provided with the tester into the IEC socket of the tester. The rotary switch must be in one of the following positions.
The measuring process starts automatically if voltage is present at the socket.
EIN
ON
The measuring process starts automatically if voltage is present at the socket.
Only the voltage potentials between the connection
&&
&
&&
terminals are measured. The measurement provides no information as to whether the earthed mains socket has been correctly installed.
No warning message is provided if a dangerous touch
&&
&
&&
voltage exists on the PE conductor.
GOSSEN Müller & Weigert
23
Operating manual for the TG basic 1 appliance tester
10. Checking the battery voltage
Before each measurement, the tester automatically checks that the charge level of the batteries is sufficient for correct execution of the respective measurement. If this is not the case, the following information is displayed:
In this case the tester must be switched off and the batteries replaced as described in point 6.1.
11. Technische Daten
Protective conductor resistance: Measuring range: 0.1…2.000 Display range: 0.05…2 Resolution: 0.001 Tolerance:
±±
± (5% + 2 digits)
±±
Measuring current/voltage: min.
ΩΩ
Ω
ΩΩ
ΩΩ
Ω
ΩΩ
ΩΩ
Ω
ΩΩ
±±
± 200 mA DC / > 4 V
±±
Insulation resistance: Measuring range: 0.1…20 M Display range: 0.1…20 M
ΩΩ
Ω
ΩΩ ΩΩ
Ω
ΩΩ
Resolution: im Bereich 0.1…9.999 M
ΩΩ
Ω
ΩΩ
im Bereich 10.00…20.00 M Tolerance:
ΩΩ
Ω
ΩΩ
≥≥
0.001 M
≥≥ ≥≥
0.01 M
≥≥ ±±
± (5% + 2 Digit)
±±
ΩΩ
Ω
ΩΩ
ΩΩ
Ω
ΩΩ
Measuring voltage/current: min. 500 V DC / >1 mA Substitute leakage current:
Measuring range: 0.1...20 mA Display range: 0.1...20 mA Resolution: Range 0.1…9.999 mA Range 10.0 …20.00 mA Tolerance:
≥≥
0.001 mA
≥≥ ≥≥
0.01 mA
≥≥ ±±
± (5% + 2 Digit)
±±
Measurement voltage: approx. 32 V AC
GOSSEN Müller & Weigert
24
Operating manual for the TG basic 1 appliance tester
Spannungsmessung an externer Schutzkontaktsteckdose: Measuring range: 50…270 V AC
Display range: 50...270 V AC Resolution: 1 V Tolerance:
±±
± 5 %
±±
General technical data:
Power supply: 6 x 1.5 V batteries
Typ IEC LR6 (AA) 6 x 1.2 V NiMH
rechargeable batteries Degree of pollution: 2 Overvoltage category: CAT II 300 V Protection degree: IP40 Protection class: II
Electrical safety: EN61010-1/VDE0411
DIN VDE 0404 Parts 1,2
DIN VDE 0413, Parts 1,2,4 EMC emission: EN61000-6-3 EMC interference resistance: EN61326-1
Dimensions (L x W x H): Approx. 265 x 110 x 50 mm Weight: Approx. 700 g
12. Notes on cleaning
When dirty, the tester is to be cleaned with a dry cloth (no solvents) or an anti-static cloth. The tester must be protected from shock and impacts.
13. Calibrating the tester
According to the DIN VDE 0701-0702:2008-06 standards:
„Measuring devices used for testing must be regularly checked and calibrated.“
We recommend a calibration interval of one year. Shorter periods are recommended if the tester is frequently used or used under tough conditions. If the tester is seldom used then the calibration interval can be extended up to a maximum of 3 years.
GOSSEN Müller & Weigert
25
Operating manual for the TG basic 1 appliance tester
GOSSEN Müller & Weigert
26
Operating manual for the TG basic 1 appliance tester
GOSSEN Müller & Weigert
27
Operating manual for the TG basic 1 appliance tester
14. Manufacturer’s guarantee conditions
The TG basic 1 appliance tester is subject to a strict quality inspection. Nevertheless, we grant a 24-month manufacturer’s guarantee in the case of malfunctions during normal daily usage. Manufacturing or material faults will be remedied, free of charge, as long as the tester shows no signs of third party actions and is unopened before it is sent back to us. Damage resulting from the device being dropped or mishandled is excluded from guarantee claims.
GOSSEN Müller & Weigert
GOSSEN Müllert & Weigert Kleinreuther Weg 88 D-90408 Nuremberg, Germany Phone +49(0)911 / 3502-0 FAX +49(0)911 / 3502-307
info@g-mw.de www .g-mw.de
Item: 2786688238 10.2011
Loading...