GMV NGV A3 Installation, Use And Maintenance Manual

GMV SPA
FLUID DYNAMICS EQUIPMENTS AND COMPONENTS FOR LIFTS
UNI EN ISO 9001 Certified Company
1.05
ENG
English
NGV A3 VALVE
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANACE
1 0991 483 EN
AVAILABLE WITH TANK TYPE
GL, F1, T2, T3, T4, MRL-T, MRL-H
1 0991 483 EN - 21.12.2011
ENG
1.05
2 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
INDEX
0 GENERAL SECTION 5
0.1 INTRODUCTION INFORMATIONS 5
0.1.1 DEFINITIONS 5
0.1.2 TERMS AND SYMBOLS USED 5
0.1.3 RULES REFERENCE 5
0.2 DOCUMENTS RELATED WITH INSTALLATION 5
0.3 SAFETY PRECAUTION DURING INSTALLATION 5
0.4 TOOLING 5
0.5 GENERAL ORDERS 6
1 FEATURES AND REQUIREMENTS 7
1.1 THE NGV A3 VALVE 7
1.2 THE FLUID 7
1.3 HOW THE NGV A3 WORKS 8
1.4 THE DOUBLE SAFETY 9
1.5 MAIN FEATURES 9
2 INSTALLATION OPERATIONS 10
2.1 HYDRAULIC CONNECTIONS 10
2.1.1 MINIMUM DIMENSIONS AND HOLES FOR POWER UNIT 10
2.1.2 INPUT AND OUTPUT -POWER UNIT SIDE 11
2.2 HYDRAULIC CIRCUIT 11
2.3 ELECTRICAL CONNECTIONS 12
2.3.1 CONTROL PANEL REQUIREMENTS 12
2.3.2 INTERVENTION TIME 12
2.3.3 FAULT SCHEMAS 13
2.4 OPERATIONS PRELIMINARY TO CONNECTION 13
2.5 SCHEMAS OF THE CONNECTIONS TO CONTROL PANELS 14
2.5.1 MAIN SCHEMA 14
2.5.2 CONNECTION SCHEMAS FOR SIGNALS 15
2.5.3 CONNECTION SCHEMAS FOR POWER 15
2.6 CONNECTIONS TO THE TERMINAL 16
2.7 CONNECTIONS TO THE CARD 16
2.8 CONNECTION OF HYDRAULIC PIPES 17
2.8.1 CONNECTION WITH FLEXIBLE HOSE 17
2.8.2 CONNECTION WITH A RIGID PIPE 17
3 NGV A3 CONTROL BOARD 18
3.1 ELECTRICAL FEATURES 18
3.2 PERFORMANCES 18
3.2.1 SIGNALLERS 18
3.3 CONNECTIONS 19
3.3.1 CONTROL PANEL INTERFACE 19
3.3.2 VALVE INTERFACE 20
3.3.3 USER INTERFACE 21
3.4 SIGNALS AND COMMANDS SEQUENCE 22
3.4.1 UPWARD DIAGRAM 22
3.4.2 DOWNWARD DIAGRAM 23
3.5 DECELERATION DISTANCES 24
4 ADJUSTMENTS AND TEST 25
4.1 ADJUSTMENT OF THE OVERPRESSURE VALVE (OPP/MPS) 25
4.2 RAM PRESSURE ON THE VSMA ADJUSTMENT 26
4.3 PIPE RUPTURE VALVE (VC) TEST 26
4.4 TEST OF DEVICES THAT PREVENT UNCONTROLLED MOVEMENT 26
4.4.1 PREREQISITES 26
0.1.1 26
4.4.2 TEST IN UP DIRECTION 27
4.4.3 TEST IN DOWN DIRECTION 27
4.5 TEST OF THE DOUBLE SAFETY SYSTEM 28
4.5.1 SIMULATION OF THE VRP FAULT 28
4.5.2 SIMULATION OF THE VB FAULT 29
4.5.3 TEST OF THE MONITORING SYSTEM 29
4.6 FAULT SIMULATION ON OUTPUT RDY AND RUN 30
4.6.1 TEST RUN ALWAYS ON 30
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
3 / 46
1.05
ENG
4.6.2 TEST RDY ALWAYS OFF 30
4.6.3 TEST RUN ALWAYS OFF 30
4.6.4 TEST RDY ALWAYS ON 30
4.6.5 EXIT RUN-RDY TEST 30
5 PROGRAMMING 31
5.1 SYSTEM PARAMETERS 31
5.2 COMPLETE MENÙ 32
5.3 MENÙ 33
- 1 - DIAGNOSTICS 33
- 2 - ALLARM 33
- 3 - ALARM AND FAULT RESET 33
- 4 - ADJUSTMENTS 34
- 5 - SETTINGS 35
- 6 - UPWARD PARAMETERS 36
- 7 - DOWNWARD PARAMETERS 36
- 8 - OUTPUT FUNCTIONS 37
- 9 - TEST 37
- 10 - ADVANCED PROGRAMMING 38
5.4 CHART OF OUTPUT PROGRAMMABLE FUNCTIONS 38
5.5 CHART OF FAILURES 39
5.6 ACCESSORIES 39
6 MAINTENANCE AND FAULT ANALYSIS 40
6.1 PROGRAMMED MAINTENANCE 40
6.2 PERIODICAL MAINTENANCE AND CHECKS TABLE 40
6.3 MAINTENANCE SCHEDULES 40
6.4 FAULT ANALYSIS 42
6.4.1 TROUBLESHOOTING 43
6.5 ADJUSTING THE SENSORS 45
6.5.1 SENSOR S1 45
6.5.2 SENSOR S2 45
6.5.3 SENSOR S3 45
7 CERTIFICATES 46
ENG
All rights reserved. Any kind of exploitation in any form and by any means is forbidden without a written permission of GMV Spa. GMV Spa, within technical or manufacturing progress, reserves the right to modify parts or this manual without notice. Drawings, descriptions and data included in this manual are indicatives. For all the data not included in this manual refer to the documents of any single part. To guarantee the products security, do not use spare parts not genuine or not approved by GMV Spa. GMV Spa will not assume any responsibility if the instructions included in this manual are not observed.
/c2
DT 21/12/2011
2C
CR 21/12/2011
2c6
GF 21/12/2011
Information and support:
FLUID DYNAMICS EQUIPMENTS AND COMPONENTS FOR LIFTS
UNI EN ISO 9001 Certified Company
GMV SPA
Via Don Gnocchi, 10 - 20016 PERO – Milano (Italy) TEL. +39 02 33930.1 - FAX +39 02 3390379
http://www.gmv.it - e-mail: info@gmv.it
1 0991 483 EN - 21.12.2011
ENG
1.05
4 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
Main acronyms and abbreviations
# Description
1
Pressure safety valve adjustment (pressure limiter)
2
Pressure safety valve adjustment (hand pump)
3
Ram pressure adjustment (only 2:1 acting jacks)
4
Shut-off valve for pressure gauge exclusion
5
Screw for rupture valve test
AF
Valve to prevent ropes slacking
BOX
Interface box (NGVA3 / Control panel)
C1
Chamber of the VRP
C2
Inlet chamber
C3
VB outlet chamber
C4
Chamber of the VRP pilot spool
CARD
NGV A3 control card
D
Downward signal
DN
Downward
FLT
Filter
ISP
Inspection gauge fitting
J
Jack
K
Non-return valve
M1
Spool of the VRP
MAN
Pressure gauge
ML
Manual lowering button
M, MP
Motor / pump
MPS
Maximum pressure spool
NGV-A3
NGV A3 Valve (Complete)
OFF
Not powered
ON
Powered
OPP
MPS pilot valve
P
VRP pilot spool
PAM
Hand pump
PT
Pressure transducer
RDY
Ready - Ready signal (card output to control panel)
RO
Oil heating resistance
RT
Motor thermistors
RUN
Run - Start signal (card output to control panel)
S1 (VRP)
Sensor to control the VRP closing
S2 (VBC)
Sensor to control the VB closing
S3 (VBO)
Sensor to control the VB opening
SM
Stepping motor
TO
Oil thermostat
TT
Temperature transducer
UP
Upward / Up - command of starting upward (card to control panel)
V0
Speed : high
V1
Speed : medium
V2
Speed : inspection
VAL
Valve NGVA3 (Valve only)
VB
Main flow adjustment valve
VC
Rupture valve
VMD
Downward solenoid valve
VR
Non-return valve (flow)
VR1
Non-return valve (inlet)
VR2
Non-return valve (outlet)
VRP
Non-return valve - controlled
VS
Upward signal
VS1, VS2
Pressure safety valve
VSMA
Lowering valve manual / electrical
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
5 / 46
1.05
ENG
0 GENERAL SECTION
0.1 INTRODUCTION INFORMATIONS
0.1.1 DEFINITIONS
In this manual are used the definitions in EN81-1, EN81-2: Safety rules for the construction and installation of lifts, EN81-28: Remote alarms on passenger lifts, EN1050: Safety of machinery - Principles for risk assessment, ISO3864: Safety colours and safety signs, and the following apply:
0.1.2 TERMS AND SYMBOLS USED
NOTE
Indicates information which contents must be seriously taken in consideration.
WARNING
Indicates that the described operation is likely to cause, damages to the system or physical damages if performed without complying with the safety standards.
0.1.3 RULES REFERENCE
For all definitions not included in this manual please refer to rules and local laws in force, following, particularly: EN 81-2: Safety rules for the construction and installation of lifts, EN 1050: Safety of machinery - Principles for risk assessment, ISO 3864: Safety colours and safety signs.
0.2 DOCUMENTS RELATED WITH INSTALLATION
The documents to use for the installation are those required by the EN81-2:1998 and by the rules in force, particularly the following:
- THIS INSTALLATION MANUAL
- WIRING AND HYDRAULIC DIAGRAMS (EN81-2:1998 16.2 A) 6 AND 7). All the documentation for a correct and safe installation, must be stored by the installation responsible. Please remember that this documentation is considered part of the plant and must be complete, well stored and unabridged in every part. In order to maintain the readability, the documentation shouldn’t be damaged and shouldn’t have missing parts. Moreover, do not tear or deteriorate sheets during consulting.
0.3 SAFETY PRECAUTION DURING INSTALLATION
WARNING
Before start all kind of installation operation. ALWAYS verify that al the safety devices, mechanical or electrical, are active and working properly.
0.4 TOOLING
Use standard building-yard tooling for the installation.
1 0991 483 EN - 21.12.2011
ENG
1.05
6 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
0.5 GENERAL ORDERS
The valves shall be maintained in good working order in accordance with the European Standards. To this effect, regular maintenance of the installation shall be carried out, to ensure, in particular, the safety of the installation. The safety of an installation shall take into account the ability to be maintained without causing injury or damage to health. Regular maintenance of the installation shall be carried out to ensure the reliability of the installation. The access and the associated environment shall be maintained in good working order. The competence of the maintenance person within the maintenance organization shall be continuously updated.
NOTE
We inform the owner of the installation that the qualification of the maintenance organization needs to be in conformity with the rules applicable in the country in which the installation operates; if no rules exist, the qualification can be ensured by a certified EN ISO 9001 quality system supplemented if necessary to take into account the specific features of the installation.
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
7 / 46
1.05
ENG
1 FEATURES AND REQUIREMENTS
1.1 THE NGV A3 VALVE
The NGV A3 Valve with:
· the new Fluitronic digital technology.
· the “Stepping System” device
· the possibility to use ecological fluid or traditional mineral oil
· the working pressure between 12 and 45 bar
Guarantees :
- Increased reliability of the control system
- Best performance
- Reduction of costs
- Reduction of the installed power (up to 20%)
- Reduction of consumptions up to 40% (*)
- Reduction of the travel time
- Reduced use of heat exchangers
- Constant downward speed regardless of the load
- Compliance with various regulatory and environmental requirements
(Ex. compliance with the Directive 2006/118/EC on the environment)
- More safety thanks to double lock, already integrated in the product conforms to the rule EN 81-2:2010
Offer:
- Ideal solution for renovation and MRL systems
- The most advanced system of control for lift
- Technology in line with the latest trends in the control field
- Speed up to 1 m/s
- Downward speed greater than the upward up to +20%
- Ride comfort comparable to a VVVF electric and no consumption in standby mode
- Maintenance speed adjustable
(*) Maximum value reached under optimal conditions and in combination with other products GMV
- The driving option
INTERNAL FEED BACK (CAR LOAD / TEMPERATURE)
The choice to immediate savings, interfaced with all, existing and new systems Not require encoder, reduce consumption up to 20% * The valve, stored the operating characteristics, reading changing of pressure and temperature, make the appropriate corrections to obtain car speed profiles with low deviations from the ideal profile.
* Compared to a traditional valve
1.2 THE FLUID
GMV use and recommend an hydraulic fluid ISO VG 46 that :
· Thanks to classification as category HEES, as rule ISO-UNI 6743-4 and its biodegradability index > 90%, according to standard CEC L33-A­93, is acceptable from an environmental point of view.
· Thanks to the synthetic base (ISO VG 46 ) and its viscosity index (>140), higher than the traditional mineral oil, allowing greater stability, ensuring better performance against wear and aging on systems as lifts for persons and goods, in accordance with the environmental directive 2006/118/EC.
· Thanks to a flash point above 220°C compared to the 140°C of the traditional mineral oil it is safer and reduces the risk of fire.
1 0991 483 EN - 21.12.2011
ENG
1.05
8 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
1.3 HOW THE NGV A3 WORKS
The valve NGV is made with a non-return valve VR, a control spool VB controlled by a stepping motor and by a system with pilot operated non-return valve VRP - P (moved in opening by the electro-valve VMD)
Valve VR
It is a valve that prevent , during the downward, the oil inlet to the pump. It forces the oil that comes from the VRP C2 to pass through the spool VB and then in the C3 and in the tank T1.
Valve VRP-P
It is the pilot operated non-return valve, requested by rules. During upward the valve works only as ON/OFF, the spool VRP opens or closes depending on the oil that comes. Its position is determined by the ratio between the pressure that develops in the chamber C2 and the one that occurs in chamber C1 During downward, instead, it opens the oil way to the valve block (chamber C2). Its opening is made by the pushing of the piston P that is opened by the pilot operated valve VMD
Spool VB
It’s the main part of the control block. It adjusts the oil quantity that should be discharged and determines all the movements of the car Its movement is controlled by a stepping motor coupled to the spool VB, through a screw­nut coupling (necessary to transform the rotatory motion into translatory). The spool adjusts both the upward phase (with a direct control of the oil that should be discharged and, indirectly the oil for the cylinder) than that of downward (directly)
All the other valves have features of safety, pilotage, etc. For example :
MPS+OPP
Maximum pressure valve with pilot
5
Overspeed screw
VSMA
Emergency lovering valve
S1
S3
VMD
J
VB
VSMA
3
PT
FLT
VR
P
C4
C2
S2
C1
M1
OPP
MPS
C3
T1
VRP
5
BHBLS
505152
V-VSV0V1V2V3V+
A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP VMD
D-E+E-
111221223132
4142
X14
X15
X12 X11 X10 X9 X8
X7
X13
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4 X6X5
X2
J2 J3
J6
J1
131
3
SM
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
9 / 46
1.05
ENG
1.4 THE DOUBLE SAFETY
For the double safety the system has two spools in series, the VRP and the VB. Both work together to stop the car in different ways between upvward and downward
UPWARD
The spool VB controls acceleration and deceleration. During the approach to the landing, the spool VB, will be almost fully open to discharge a quantity of oil equal to:
Qt = Qp - Qc
where
Qt = Oil sent to the drain through the VB, Qp= Pump flow
Qc= Flow to the cylinder, corresponding to the car speed
The car stop at the landing is made by opening completely the VB and bringing the value of Qt = Qp. As a result Qc becomes zero. The car stops when the pressure of the chamber C2 become equal to the pressure of the chamber C1 (Static pressure of the system). In this case,
the VRP spool closes, because is pushed by the pressure and
by the spring, and the car stops at the landing.
DOWNWARD
The downward phase is simpler and, after the opening of the VRP spool, the car speed is controlled by the VB spool. To a more opening of the spool corresponds an higher speed of the car The phase of arrival at the landing is determined by the following events:
The VRP spool is opened by the push of the spools P, controlled by the VMD pilot valve The VB spool closes to stop the car
The VMD valve, raised the landing, is de-energized and consequently the VRP spool closes. During standard operation of the system, both upward and downward, the proper working of the two spools (VRP and VB) acting in series, is controlled by three switches :
One, (S1) installed on the VRP, to control the full close position.
Two (S2, S3) installed on the VB, to control the full close and the full open positions
During all phases the system control that the spools reach the correct open and close position. If this do not happen, the system send an alarm to the control panel, which must turn the system into the out of service status
WARNING
Needful prerequisite of the control panel, when the system is outside of the doors unlocking zone, is that it does not send commands to the card and/or the motor / pump.
1.5 MAIN FEATURES
Valve Type
NGV A3
Minimum operating pressure
12 bar
Maximum operating pressure
45 bar
Test speed
1 m/s
Temperature operating range
5°C - 70°C
Rated pump flow range
55 - 300 l/min
¥"
1 0991 483 EN - 21.12.2011
ENG
1.05
10 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
2 INSTALLATION OPERATIONS
ATTENTION
During the installation never exclude the safety devices and never connect the motor/pump directly to the power supply
2.1 HYDRAULIC CONNECTIONS
2.1.1 MINIMUM DIMENSIONS AND HOLES FOR POWER UNIT
135
113
8352
131
18
14
105
137
15
10
1557
Ø9 x 4 fori
35
61.5
Ø28
M6
M6
16.5 41.5
19
24
48
74
1"1/4 G IN
1"1/4 G OUT
11.5
54.5
43.577.5
6
6
310
340
393
310
400
1"
1
4
IN
1"
1
4
OUT
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
11 / 46
1.05
ENG
2.1.2 INPUT AND OUTPUT -POWER UNIT SIDE
1"
1
4
OUT
M8
OUT
1"
1
4
IN
M8
OUT
M8
OUT
M8
OUT
M8
OUT
3
4
"
OUT
12x8 PAM
PAM 12x8 IN 1” ¼ OUT 1” ¼ OUT ¾” OUT M8
2.2 HYDRAULIC CIRCUIT
M
VS1
VB
VR1
VR
ML
VSMA
PAM
VR2
VS2
VC 3006/B
ISP
MAN
PT
4
2
1
5
3
SM
TT
VAL
CARD
J
NGV A3
VRP
K
VMD
1 0991 483 EN - 21.12.2011
ENG
1.05
12 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
2.3 ELECTRICAL CONNECTIONS
2.3.1 CONTROL PANEL REQUIREMENTS
The control panel must send to the power unit at least the following signals:
Mark Signal/comand Features VS
Upward signal
10…40mA 12…48Vdc
V0
Speed : High
10…40mA 12…48Vdc
V1
Speed : Medium
10…40mA 12…48Vdc
V2
Speed : Inspection
10…40mA 12…48Vdc
D+
Downward signal
12…48Vdc, 60…180Vdc
D-
Downward negative pole
12…48Vdc, 60…180Vdc
The control panel must to receive and to understand correctly at least the following signals:
Mark Signal/comand Features RDY
Ready
10mA…2A
RUN
Run
10mA…2A
UP*
Up
10mA…2A
OVL
Overload
10mA…2A
*Command used only to interface control panels that need different signals to start upward or doward travels
Outputs RDY, RUN and UP
- report to control panel about the system state,
- determine when the control panel must start or stop the motor /pump
WARNING
The control panel, when receive a FAULT signal from the NGV-A3 card (RUN and RDY output), should not send commando to the valve and/or the motor/pump In FAULT condition the motor/pump group should NOT be active
WARNING
To detect the unintended movement of the car the system use the circuit required by paragraph 7.7.1 and 14.2.1.2 of the rule EN 81-2:2010. This circuit, if it detects a movement of the car, with doors not closed, outside the unlocking zone, prevents the control panel to send any command to the valve. The system restore should be performed only by an authorized and properly trained person.
· Distance of setting: ± 200 mm
· Maximum time for the intervention of the circuit 270 ms
For other data or signals sequence see next paragraphs of this manual
2.3.2 INTERVENTION TIME
0
Origin
1
Car speed in the instant of intervention of the bracking device 1,3 m/s
2
Speed
3
Response time of the device that detects the unintended movement of the car 270 ms
4
Response time of the braking devices 200 ms
5
Time
6
Time from start of the unintended movement to the instant in which the car sensor leaves the doors area (dimension = ± 200 mm)
7
Stoping time of the car 500 ms
8
Point in which the car stops
0-8 between 0 and 8 the maximum
distance travelled is 100 cm
2
3
6
0
8
745
1
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
13 / 46
1.05
ENG
2.3.3 FAULT SCHEMAS
A control panel installed with the valve NGV A3 must continuously monitor the signals RDY and RUN (UP) that it receives from the card NGVA3-xx. The control panel should go in error status, stop the system and do not send commands to the valve and / or the motor / pump when, for more than 2s, signals RDY and RUN are simultaneously in the same condition. The contemporary of the ON or OFF status require different behaviours, in particular: If RDY and RUN are both in ON status, the control panel must detect the error, move the car to the nearest landing and stop the system without allowing more travels; If RDY and RUN are both in OFF status, the control panel must stop immediately the system and prevent any further movement with the exception of the manual emergency operation.
FAULT
ALLOWED
ALLOWED
OK
OK
2s
2s
2s
2s
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OUT : RDY
OUT : RDY
OUT : RDY
OUT : RUN
OUT : RUN
OUT : RUN
IN : VS / D
OK
RDY FAULT
RUN FAULT
2.4 OPERATIONS PRELIMINARY TO CONNECTION
0 - OFF
0 - OFF
+
1 0991 483 EN - 21.12.2011
ENG
1.05
14 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
2.5 SCHEMAS OF THE CONNECTIONS TO CONTROL PANELS
In the following pages the schemas of the connections between valve / NGVA3 card and control panels
2.5.1 MAIN SCHEMA
T
TT C°
BOX
QM
VAL
A3-Sxx-Wxx
UP
OVL
PMAX
PMIN
RUN
RDY
2A max
VSMA
VMD
PT
MAN
B
S1
SM
S3ò
S2ñ
3
5
1
4
ISP
PAMï
ML
BHBLS
505152
A+PEA-A-
D+D-E+E-
NGV-A3-01
EXP
µSD
COMM
PT01
111221223132
4142
X14
X15
X12 X11 X10 X9
X8
X7
X13
+ - T+ T- P+ P-+ -+ -
X1
X3
X4
X6
X5
X2
CAN BUS
D-D+ E+E-
VMD
X7
(1)
X6
D-E+E-
NGV-A3
S00 / S48 W25 / W50
CARD
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
15 / 46
1.05
ENG
2.5.2 CONNECTION SCHEMAS FOR SIGNALS
Schema S00 Schema S48
V2
V1
V0
VS
QM
A+PEA-A-
D+D-E+E-
X4 X6
X5
CARD
S00
V+
J6
V2
V1
V0
VS
QM
A+PEA-A-
D+D-E+E-
X4 X6
X5
CARD
S48
J6
10...48 VDC
-
+
2.5.3 CONNECTION SCHEMAS FOR POWER
Schema W50 Schema W25
QM
A+PEA-A-
D+D-E+E-
X4
X6
X5
CARD
W50
J6
24 VDC = +/- 10% 50W
-
+
PE
EN81-2
J6=1-2 12- 48 VDC
QM
A+PEA-A-
D+D-E+E-
X4
X6
X5
CARD
W25
J6
-
+
24 VDC = +/- 10% 25W
PE
EN81-2
12- 48 VDC J6=1-2 60-180 VDC J6=2-3
VAL
NGV valve
QM
Control panel
BOX
NGV interface box
VSMA
Emergency downward valve
VS
Upward signal
CARD
NGV control card
VMD
Downward solenoid valve
V0
High speed
S1,S2,S3
Sensors (VRP,VBO, VBC)
SM
Stepping motor
V1
Medium speed
PT
Pressure transducer
D
Downward signal
V2
Inspection speed
(1)
Schema of the connections between D+D-E+E-VMD
TT
Temperature transducer
¥"
1 0991 483 EN - 21.12.2011
ENG
1.05
16 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
2.6 CONNECTIONS TO THE TERMINAL
A
U1
V1
W1
3 x
U1 V1
W1
U1-W2
V1-U2
W1-V2
U1
W2
V1
U2
W1
V2
U1
W2
V1
U2
W1
V2
RO2
RO1
TO1
TO2
RT1
RT2
RO2
RO1
TO1
TO2
RT1
RT2
T
M
3~
TORO
RT
150 mm
B
U1
W2
V1
U2
W1
V2
6 x
U1
W2
V1
U2
W1
V2
U1
W2
V1
U2
W1
V2
U1
W2
V1
U2
W1
V2
RO2
RO1
TO1
TO2
RT1
RT2
RO2
RO1
TO1
TO2
RT1
RT2
T
M
3~
TORO
RT
150 mm
2.7 CONNECTIONS TO THE CARD
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP VMDD-E+E-
1112212231324142
X14
X15
X12 X11 X10 X9 X8
X7
X13
A-
+ -T+ T- P+ P-+ -+ -
X1
X3
X4 X6X5X2
J2 J3
J6
J1
131
3
ò
X1-X2-X3
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP
VMD
D-E+
E-
111221223132
4142
X14
X15
X12 X11 X10 X9
X8
X7
X13
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4 X6
X5
X2
J2 J3
J6
J1
131
3
÷÷
÷
§ 2.7
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP VMDD-E+E-
1112212231324142
X14
X15
X12 X11 X10 X9 X8
X7
X13
A-
+ -T+ T- P+ P-+ -+ -
X1
X3
X4 X6X5X2
J2 J3
J6
J1
131
3
ô
X4-X5-X6
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP
VMD
D-E+
E-
111221223132
4142
X14
X15
X12 X11 X10 X9
X8
X7
X13
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4 X6
X5
X2
J2 J3
J6
J1
131
3
ø
ø
ø
§ 2.7
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP VMDD-E+E-
1112212231324142
X14
X15
X12 X11 X10 X9 X8
X7
X13
A-
+ -T+ T- P+ P-+ -+ -
X1
X3
X4 X6X5X2
J2 J3
J6
J1
131
3
J6
VMD
1
2
3
=
12-48 Vdc
1
2
3
=
60-180
Vdc
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP
VMD
D-E+
E-
111221223132
4142
X14
X15
X12 X11 X10 X9
X8
X7
X13
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4 X6
X5
X2
J2 J3
J6
J1
131
3
ø
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
17 / 46
1.05
ENG
2.8 CONNECTION OF HYDRAULIC PIPES
ñ
8 ÷ 36 3/4" x 3/4" 3/4" - 3/4" x 3/4" 3/4"
42 ÷ 52
3/4" 3/4"
3/4" x M36" - 3/4" x M36
55 ÷ 100 1” x M36
1”
- 1” x M36
1”
100 ÷ 150
1”
1” x M45 1” x M45
180 ÷ 216 1”1/4
-
1”1/4 x M45
1”1/4 35
1”1/4 x M45
1”1/4
250 ÷ 300
1”1/4
1”1/4
1”1/4GM x 1”1/2GF
+ 1”1/2 x M52
360 ÷ 432 1”1/2 1”1/2 x M52
1”1/2 42 1”1/2 x M52 1”1/2
500 ÷ 600
1”1/2
-
2” 2” x 2” 2” - 2” x 2” 2”
2.8.1 CONNECTION WITH FLEXIBLE HOSE
· Remove the gear and the cutting ring from the terminal connection of the silencer.
· Ensure that the terminal connection is well fixed on the silencer.
· Clean and oil the threading and their seats.
· Fix the flexible hose verifying it is thoroughly tightened.
WARNING
Ensure that there is no dirty inside the tube. These impurities could damage the sealing of the piston and of the valve block and inhibit the correct operation of the system.
2.8.2 CONNECTION WITH A RIGID PIPE
· Cut at 90° the head of the tube with a saw (do not use a tube-cutter)
· Do not let metal residuals fall into the tube and eliminate the burrs internally and externally.
· Remove the gear and the cutting ring of the terminal connection and insert it on the pipe.
· Ensure that the cutting ring is inserted as indicated in image
· Ensure that the terminal connection is well fixed on the silencer.
· Clean and lubricate the threading and the connection seat with
a slight oil veil.
· Insert the pipe into the cone at 24° up to lay it on the stop limit of the cone itself.
· Screw thoroughly the gear by hand until it is felt that the cutting gear lays perfectly to the nut.
· Then screw the nut using a wrench until the cutting edge of the ring is in contact with the tube and prevents it from rotating.
· Keep the tube against its stop to avoid it rotates, screw the fixing nut by 3/4 rev. In doing so the ring engraves with the necessary depth the external part of the tube and rises a border in front of its cutting edge.
· Loose the nut and check that the tube has all around a well risen border. The border must cover 70% of the front part of the cutting ring.
· Fix the tube, close the nut with a wrench until a certain resistance is felt; from this moment on screw for a further 1/4 turn, contrasting wrench against wrench.
WARNING
Ensure that there is no dirty inside the tube. These impurities could damage the sealing of the piston and of the valve block and inhibit the correct operation of the plant.
1 0991 483 EN - 21.12.2011
ENG
1.05
18 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
3 NGV A3 CONTROL BOARD
3.1 ELECTRICAL FEATURES
The hardware features of the card NGV-A3 are:
# DESCRIPTION VALUE
01 Standard supply voltage 24V=, ±10% 02 Extended supply voltage 12...42Vdc 03 Maximum consumption 25W 04 Voltage input VS-V0-V1-V2-V3 10...48Vdc (70Vp) 05 Voltage input D+ (VMD), two range selectable by jumper 12...48Vdc / 60...180Vdc 06 Power voltage sensors VRP and VB 12Vdc 07 Power voltage pressure transducer 12Vdc
08
Relays output, Volt free contact according with EN81-2 for distances and insulation up to 250V
10mA@20Vdc / 2A@250Vac
3.2 PERFORMANCES
The card NGV-A3-01 has 3 different versions:
-01 Standard version : with power supply 24VDC
-02 Extended version : with all the available functions
-03 Reduced version : with power supply 24VDC and only serial connection on can bus
VERSION
# FUNCTION DESCRIPTION
01 02 03
01
Power supply Standard, 24V=, ±10% / Extended, 12...42Vdc
S E S 02 Opto-isolated inputs to command upward and speed level 5 5 ­03 Opto-isolated input to command downward (separate) 1 1 1
04
Relay output with voltage free contact according to EN81-2 for distances and isolation up to 250V
7 7 -
05
Step Motor Command 12...52Vdc, 1,5Arms with the possibility of monitoring the rated current and the connection breaking.
1 1 1
06 Input for pressure transducer interface, range 0...100 bar 1 1 1 07 Input for oil temperature transducer interface, range 0...100°C 1 1 1 08 Input for sensor ON/OFF 12V or linear sensor 0...5V (power supply 12V) 2 2 2 09 Input for sensor ON/OFF 12V 1 1 1 10 Rj45 port for PT01 / Pc / remote 2 2 1 11 Slot for µSD card - 1 ­12 Calendar watch with CR2030 battery 1 1 ­13 Can bus serial socket - 1 1 14 I/O extender connector 1 1 1
3.2.1 SIGNALLERS
GREEN LED OFF Not powered
FLASHING Power out of range
BHBLS
505152
1112212231324142
X14
X15
A-
X1
X3
X2
Power supply status
ON Correctly powered
RED LED OFF No alarm
FLASHING Alarm that stops the system work
BHBLS
505152
1112212231324142
X14
X15
A-
X1
X3
X2
Alarm status
ON Alarm that do not stops the system work
PT01
Card status DISPLAY Show errors and settings
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
19 / 46
1.05
ENG
3.3 CONNECTIONS
3.3.1 CONTROL PANEL INTERFACE
The input circuits are divided in two groups, both isolated from the card power supply:
· V0,V1,V2,VS with common V- · D+ with common D­Each group can be powered or by an external source within established limits, or directly by the card power, connecting the commons (V- and/or D-) to the A-. The interfacing with the control panel is made via removable terminal connectors defined as follows:
Connector X1, step 3,5 mm Pos. Mark Features Description
1 BH Bus Can bus H 2 BL Bus Can bus L 3 SH Shield Shield
BHBLS
505152
111221223132
4142
X14
X15
X1
X3
X2
÷
Connector X2, step 5,0 mm Pos. Mark Features Description
1 11 2 12
10mA...2A
20...250V
Programmable output relay (refer to programming
menu and programmable functions chart) 3 21 4 22
10mA...2A
20...250V
Programmable output relay (refer to programming
menu and programmable functions chart) 5 31 6 32
10mA...2A
20...250V
Programmable output relay (refer to programming
menu and programmable functions chart) 7 41 8 42
10mA...2A
20...250V
Programmable output relay (refer to programming
menu and programmable functions chart)
BHBLS
505152
111221223132
4142
X14
X15
X1
X3
X2
÷
Connector X3 step 3,5 mm Pos. Mark Features Description
1 50
10mA...2A
20...250V
Output: RUN (NO)
2 51
10mA...2A
20...250V
Output: RDY (NO)
3 52
10mA...2A
20...250V
Common
BHBLS
505152
1112212231324142
X14
X15
A-
X1
X3
X2
Connector X4, step 3,5 mm Pos. Mark Features Description
1 A- Power : negative (-)
2 V-
Inputs : negative
Make a short circuit with A- if you use V+ as power
or connect to input negative pole. 3 VS Input command : upward 4 V0 Input command : speed : high (nominal speed) 5 V1 Input command : speed : medium 6 V2 Input command : speed : inspection 7 V3
12...48Vdc,
10...40mA
Aux, not assigned
8 V+
Power : positive common.
For input command circuits without voltage.
Do NOT use if input commands are under voltage
52
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
A-
X3
X4 X6
X5
J6
ø
Connector X5, step 3,5 mm Pos. Mark Features Description
1 A+ Power : positive 2 PE PE, ground 3 A- Power : negative 4 A- Power : negative
52
V-VSV0V1V2V3V+
A+PEA-A-
D+D-E+E-
1
3
A-
X3
X4 X6X5
J6
ø
Connector X6, step 5,0 mm Pos. Mark Features Description
1 D+ Input command : downward 2 D-
12...48Vdc,
60...180Vdc
Input downward : negative 3 E+ Input command : emergency solenoid valve 4 E-
Input emergency solenoid valve : negative
52
V-VSV0V1V2V3V+
A+PEA-A-
D+D-E+E-
1
3
A-
X3
X4 X6X5
J6
ø
1 0991 483 EN - 21.12.2011
ENG
1.05
20 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
Jumper J6 (to set connector X6 D+ D-) Pos. Description
1-2
1
2
3
Input and downward command VMD 12…48Vdc
2-3
1
2
3
Input and downward command VMD 60…180Vdc
52
V-VSV0V1V2V3V+
A+PEA-A-
D+D-E+E-
1
3
A-
X3
X4 X6X5
J6
3.3.2 VALVE INTERFACE
The valve interfacing is made by these connections:
Connector X7, step 5,0 mm Pos. Mark Features Description
1 VMD 2 D-
Downward command VMD
3 E+ 4 E-
Emergency solenoid valve
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
ö
Connector X8, step 2,0 mm Pos. Mark Features Description
1 PHA1 2 PHA2
Winding of motor phase 1
3 PHB1 4 PHB2
Winding of motor phase 2
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
ö
Connector X9, step 3,5 mm Pos. Mark Features Description
1 T+ +Ref 2 T-
2KW max.
Temperature transducer PTC, 1K a 25°C
3 P+ +12Vdc 4 P- 4…20mA return
Pressure transducer
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
Connector X10, step 3,5 mm - (SensorS1 VRP - Settable) Pos. Mark Features Description
1 + +12Vdc 2 0…12Vdc / 0…5V 3 - 0V
Sensor ON/OFF (12Vdc) / Linear sensor 0…5V
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
Jumper J3 (to set connector X10) Pos. Description
1-2
1
2
3
Sensor S1 VRP (ON/OFF)
2-3
1
2
3
Linear Sensor 0…5V
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
Connector X11, step 3,5 mm - (Sensor S2 VB Close - Settable) Pos. Mark Features Description
1 + +12Vdc 2 0…12Vdc / 0…5V 3 - 0V
Sensor ON/OFF (12Vdc) / Linear sensor 0…5V
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
Jumper J2 (to set connector X11) Pos. Description
1-2
1
2
3
Sensor S2 VB (ON/OFF)
2-3
1
2
3
Linear Sensor 0…5V
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
Connector X12, step 3,5 mm - (SensorS1 VB Open) Pos. Mark Features Description
1 + +12Vdc 2 0…12Vdc 3 - 0V
Sensor ON/OFF (12Vdc)
NGV-A3-01
VMD
D-E+E-
X12 X11 X10 X9
X8
X7
+ - T+ T- P+ P-+ -+ -
J2 J3
131
3
õ
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
21 / 46
1.05
ENG
3.3.3 USER INTERFACE
Connector X13, step 2,54 mm - (AUX 2 x 13)
Connector for extensions (Encoder, …)
EXP
X14
X12
X13
+ -
J2
J1
1
3
õ
Slot J1, µSD (serial SPI)
Slot for µSD memory cards (serial SPI)
EXP
X14
X12
X13
+ -
J2
J1
1
3
õ
Connector X14, RJ45 (PT01)
Socket RS232 for programmer PT01
Pos. Mark Features Description
1 +12 Power : 12Vdc 2 +12 Power : 12Vdc 3 RxD Data output (to PT01) 4 TxD
Data input (from PT01)
5
Not in use
6
Not in use
7 0V
Power : negative
8 0V Power : negative
EXP
X14
X12
X13
+ -
J2
J1
1
3
÷
Connector X15, RJ45 (COMM)
Socket RS232 for PC, Modem, …
Pos. Mark Features Description
1 +12 Power : 12Vdc 2 +12 Power : 12Vdc 3 RxD Data output (to Pc, Modem,…) 4 TxD
Data input (from Pc, modem,..)
5
Not in use
6
Not in use
7 0V
Power : negative
8 0V Power : negative
BHBLS
505152
111221223132
4142
X14
X15
A-
X1
X3
X2
÷
BHBLS
505152
V-VSV0V1V2V3V+
A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP
µSD
COMM
PT01
LED RED
LED GREEN
VMD
D-E+
E-
VB OPEN TT PT
CAN BUS
AUX OUT
RUN
RDY
COM
111221223132
4142
X14
X15
X12 X11 X10 X9
X8
X7
X13
VB CLOSE VRP
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4
X6
X5
X2
J2 J3
J6
J1
1
3
1
3
1 0991 483 EN - 21.12.2011
ENG
1.05
22 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
3.4 SIGNALS AND COMMANDS SEQUENCE
3.4.1 UPWARD DIAGRAM
15
D
RAL,S
14
13
9 10
11
12
8
7
6
3
4
5
2
0
1
MP
VS
VX
RDY
RUN
UP
16
17
(0)
18
V
[m/s]
C
[mm]
VN
Close
0
Open
VB/SM
ппчшш
N G V
-
A 3
-
0 1
E X P
µ S D
R J 4 5
P T 0 1
L E D R E D
L E D G R E E N
V B
O P E N
V B
C L O S E
V R P
T T
P T
C A N
B U S
A U X O U T
READY RUN CO
M
3.4.1.1 UPWARD SIGNALS AND COMMANDS SEQUENCE
Start travel sequence : RDY=ON + RUN=OFF ð (Vx=ON ð) VS=ON ð RDY=OFF – VB/SM=OPEN ð
RUN/UP=ON (ð MP=ON)
End travel sequence : (Vx=OFF ð VS=OFF ð) VB/SM=OPEN ð RUN/UP=OFF ð (MP=OFF ð)
VB/SM=CLOSE ð RDY=ON
MP Motor / pump Vx = V0, V1, V2 Speed (High, Intermediate, Inspection) SM Stepping Motor VS Upward command
VS V0 V1 V2
Speed : High 1 1 0 0 1 Powered Speed : Medium 1 X 1 0 0 Not powered Speed : Inspection 1 X X 1 X Anything Speed : levelling / re-levelling 1 0 0 0
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
23 / 46
1.05
ENG
3.4.2 DOWNWARD DIAGRAM
D
RAL,D
VMD
D
VX
RDY
RUN
(0)
9
10
11
12
8
7
6
3
4
5
201
V
[m/s]
C
[mm]
VN
Close
0
Open
VB/SM
ппрчш
N G V
-
A 3
­0 1
E X P
µ S D
R J 4 5
P T 0 1
L E D R E D
L E D G R E E N
V B
O P E N
V B
C L O S E
V R P
T T
P T
C A N
B U S
A U X O U T
READY RUN CO
M
3.4.2.1 DOWNWARD SIGNALS AND COMMANDS SEQUENCE
Start travel sequence :
RDY=ON+RUN=OFF ð Vx=ON ð D=ON ð RDY=OFF ð RUN=ON (ðVMD=ON)
End travel sequence :
(Vx=OFF ð) D=OFF ð VB/SM=CLOSE ð RUN=OFF ð RDY=ON
D Downward command SM Stepping motor MP Motor / pump VMD Downward solenoid valve Vx = V0, V1, V2 Speed (High, Intermediate, Inspection)
D V0 V1 V2
Speed : High 1 1 0 0 1 Powered Speed : Medium 1 X 1 0 0 Not powered Speed : Inspection 1 X X 1 X Anything Speed : levelling / re-levelling 1 0 0 0
1 0991 483 EN - 21.12.2011
ENG
1.05
24 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
3.5 DECELERATION DISTANCES
ON
UP
DN
OFF
V2
VS
MP
V1
V0
V0
V1
D
V2
1s
DRAL,D
DR
AL,
S
VN [m/s] D
RAL,S
[m]
Upward Extra Slow Slow Standard Fast
0,00 < V 0,15 0,19 0,15 0,13 0,12
0,15 < V 0,40 0,43 0,39 0,37 0,32
0,40 < V 0,65 0,81 0,71 0,63 0,61
0,65 < V 0,85 1,16 0,99 0,92 0,89
0,85 < V 1,00 1,40 1,27 1,17 1,10
VN [m/s] D
RAL,D
[m]
Downward Extra Slow Slow Standard Fast
0,00 < V 0,15 0,15 0,13 0,12 0,12
0,15 < V 0,40 0,41 0,36 0,34 0,31
0,40 < V 0,65 0,78 0,67 0,62 0,58
0,65 < V 0,85 1,14 0,98 0,88 0,83
0,85 < V 1,00 1,36 1,18 1,11 1,05
EXTRA SLOW SLOW STANDARD FAST
The distance between the deceleration sensor (D
RAL
) and the floor must be regulated according to the chart
above. If the levelling space is greater is possible to make an adjustment using the programmer as shown in the chapter Programming.
D Downward command ON Powered DN Downward UP Upward M, MP Motor / pump V0, V1, V2 Speed (high, medium, inspection) OFF Not powered VS Upward command
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
25 / 46
1.05
ENG
4 ADJUSTMENTS AND TEST
4.1 ADJUSTMENT OF THE OVERPRESSURE VALVE (OPP/MPS)
VALVE NGVA3
VSMA
VMD
PT
MAN
B
S1
SM
S3
S2
3
5
1
4
ISP
PAMï
ML
To adjust the overpressure valve:
1. Refer to the hydraulic circuit of the NGV valve
2. Close the ball valve (B), the lever must be found to 90° regarding the ball valve
3. Open the manometer shut-off valve (4)
4. Unscrew and remove the protection cap of the adjusting screw of the overpressure valve (1)
5. Loosen the locknut (1)
6. Start the motor-pump group
7. Start the 9.1 Overpressure Value control procedure on the PT01 programmer (please refer to the Programming chapter)
8. Read the pressure on the programmer PT01
9. If the read value is different then the calibration one:
· Press the manual lowering button (ML) in order to decrease the pressure on the valve block
· Screw the adjustment screw 1 for increase the pressure on the MPS; unscrew the adjustment screw 1 for
reduce the pressure.
· Start the motor-pump group
· Start the Overpressure Value control procedure on the PT01 programmer
· Read the pressure on the programmer
· Repeat this procedure until the pressure value on the programmer is the same than the calibration one
10. Tighten the locknut 1
11. Put back and tighten the protection cap of the adjusting screw (1)
12. Re-open the ball valve (B)
PROGRAMMER PT01
1 0991 483 EN - 21.12.2011
ENG
1.05
26 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
4.2 RAM PRESSURE ON THE VSMA ADJUSTMENT
NOTE
Adjustment possible only with systems 2:1
To adjust the ram pressure on the VSMA :
1. Close the ball valve (B), the lever must be found to 90° regarding the ball valve
2. Unscrew and remove the protection cap of the adjusting screw of the VSMA valve (3)
3. Press the manual lowering button (ML)
4. Check the pressure gauge on the manometer (MAN) is around 5 bar. If it is 5 bar go to point 6, if it is less then 5 bar go to point 5
5.
· Re-open the ball valve B
· Loosen the locknut (3)
· Tighten the screw (3) – one turn
· Tighten the locknut (3)
· Close the ball valve B
· Press the manual lowering button (ML)
· Repeat this procedure until the pressure is close to 5 bar
· Go to point 6
6. Put back and tighten the protection cap of the adjusting screw (3)
7. Re-open the ball valve (B)
4.3 PIPE RUPTURE VALVE (VC) TEST
WARNING
Before testing the pipe rupture valve, adjust this valve on the cylinder (refer to the technical data on the plant and instructions of the rupture valve)
To test the pipe rupture valve follow the next procedure:
1. Move the car to the highest floor at full load (refer to system use manual)
2. After the car comes to a full stop loosen the locknut (5) and unscrew the screw (5) – 3 turns
3. Start the 9.2 Pipe Rupture test procedure on the PT01 programmer (please refer to the Programming chapter)
4. Move the car to the lower floor. The valve, during downward, should be stop the car.
WARNING
If the valve do not stop the car, verify the settings of the rupture valve on the cylinder
5. At the end of the test fully tighten the screw (5) and tighten the locknut (5)
6. Use the hand pump to release / unlock the rupture valve
7. Exit from the 9.2 Pipe Rupture test procedure
4.4 TEST OF DEVICES THAT PREVENT UNCONTROLLED MOVEMENT
WARNING
Perform these tests only after the previous ones.
To verify that the devices that prevent uncontrolled movement work correctly, you must proceed with the test required at point zc) of Appendix D of the rule EN81-2 checking that the control panel and the system work according to the rule. (EN81-2 §9.13.5).
4.4.1 PREREQISITES
To be according to the rule EN81-2 the following points must be respected:
- The system shall be provided with a means /switch able to detect unintended car movement
- The control panel, should NOT send commands to the valve and to the motor / pump when the system is located, with open doors, outside the doors unlocking zone.
NOTE
Before proceeding check on the installation manual of the electrical part which operations, required for the test, should be performed
ò
ñ
P 1000
mm
O 1200
mm
O 200 mm
P 1000
mm
O 1200
mm
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
27 / 46
1.05
ENG
4.4.2 TEST IN UP DIRECTION
Cod.10911309
E00.001
Cod.10911309
E00.001
For safety it’s required that the test take place behind closed doors. Then proceed as follows:
1. Put at all landings the sign “Out of service”
8. Move the empty car to the floor below the top floor
9. Wait for the closing of the door
10. Start on the valve card NGVA3 the procedure 9.3 UCM UP TEST using the programmer PT01.
11. Start on the control panel the UP direction test procedure. This procedure must :
- To exclude the possibility to call the car form the landings
- Open the electrical safety chain at the landing doors level (for the system the doors must be open even if physically closed)
12. Open, manually or electrically, the emergency lowering valve , moving in down direction the car until the intervention of the re-levelling.
When the re-levelling occurs, the system start to move in up direction at rated speed and the switch intended to detect unintended car movement must be activated and the car must stopped.
13. Verify that the car stops according to the rule EN 81-2.
14. Exit from the procedure 9.3 UCM UP TEST pushing the ESC key
15. Close the landing doors level of the electrical safety chain
16. Remove the signs “Out of service”
17. Restore the normal working status of the system.
NOTE
The switch to detect unintended car movement can be the same used to detect the movement of the car, away from the landing unlocking zone with doors not in the locked and closed position,
4.4.3 TEST IN DOWN DIRECTION
Cod.10911309
E00.001
Cod.10911309
E00.001
For safety it’s required that the test take place behind closed doors. Then proceed as follows:
1. Put at all landings the sign “Out of service”
18. Move the fully loaded car to the floor below the top floor
19. Wait for the closing of the door
20. Start on the valve card NGVA3 the procedure 9.4 UCM DN TEST using the programmer PT01.
21. Start on the control panel the DOWN direction test procedure. This procedure must :
- To exclude the possibility to call the car form the landings
- Open the electrical safety chain at the landing doors level (for the system the doors must be open even if physically closed)
22. Using the hand pump, moving in up direction the car until the intervention of the re-levelling. When the re-levelling occurs, the system start to move in down direction at rated speed and the switch intended to detect unintended car movement must be activated and the car must stopped.
23. Verify that the car stops according to the rule EN 81-2.
24. Exit from the procedure 9.4 UCM DN TEST pushing the ESC key
25. Close the landing doors level of the electrical safety chain
26. Remove the signs “Out of service”
2. Restore the normal working status of the system.
NOTE
The switch to detect unintended car movement can be the same used to detect the movement of the car, away from the landing unlocking zone with doors not in the locked and closed position,
1 0991 483 EN - 21.12.2011
ENG
1.05
28 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
4.5 TEST OF THE DOUBLE SAFETY SYSTEM
4.5.1 SIMULATION OF THE VRP FAULT
This test allow to verify that the system stay stopped in event of failure of the VRP. To perform the test you must simulate the failure of the VRP as follows:
4.5.1.1 POWER UNITS OUTSIDE THE WELL
1. Remove the VMD protection cap by turning it counterclockwise
2. [DOWN DIRECTION] Move the fully loaded car in down direction in the lower part of the well
3. During the travel, by turning clockwise, completely screw the test cap on the VMD (this operation open the VRP and does not allow it to close).
4. Verify that the car stops at the target landing correctly and in compliance with the rule
5. Remove from the VMD the test cap by turning it counterclockwise (the VRP return in the normal working condition and allow it to close)
6. Verify that in the menu (2.1 Alarm), at the end of the travel in down direction, is reported the fault nr.16
7. Reset all faults (3 Al/Flt reset)
8. [UP DIRECTION] Repeat the test moving the car empty in up direction in the upper part of the well.
9. During the travel, by turning clockwise, completely screw the test cap on the VMD
10. Verify that the car stops at the target landing correctly and in compliance with the rule
ATTENTION
During the test in up direction it is possible that the final limit switch is activated.
11. Remove from the VMD the test cap by turning it counterclockwise and put protection cap on VMD by turning it clockwise
12. Verify that in the menu (2.1 Alarm), at the end of the travel in down direction, is reported the fault nr.22
13. Reset all faults (3 Al/Flt reset)
The test is ended.
4.5.1.2 POWER UNITS IN THE SHAFT (MRL)
Perform the test in down direction and after in up direction
1. Rotate counterclockwise and remove the VMD cap
27. Remove the coil from the VMD
28. Remove the coil from the solenoid emergency valve ML and insert it on the VMD
29. [DOWN DIRECTION] Move the fully loaded car in down direction in the lower part of the well [UP DIRECTION] Move the empty car in up direction in the upper part of the well …
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
29 / 46
1.05
ENG
30. During the travel, push and hold the remote emergency button (this operation open the VRP and does not allow it to close)
31. Verify that the car stops at the target landing correctly and in compliance with the rule
32. Release the remote emergency button (the VRP return in the normal working condition and allow it to close)
33. Verify that in the menu (2.1 Alarm), at the end of travel, is reported the fault nr. 16 [DOWN DIRECTION] or nr. 22 [UP DIRECTION].
34. Reset all faults (3 Al/Flt reset)
The test is ended
4.5.2 SIMULATION OF THE VB FAULT
This test allow to verify that the system stay stopped in event of failure of the VB. To perform the test you must simulate the failure of the VB as follows:
4.5.2.1 SIMULATION OF THE VB FAULT IN DOWN DIRECTION
1. Connect the programmer PT01 to the card NGV-A3
2. Move the fully loaded car to the upper landing
3. Start the test procedure 9.5 VB TEST DOWN (Enter=Start)
4. Move the car in down direction
5. Verify that the car stops at the target landing correctly
6. End the test procedure 9.5 VB TEST DOWN (ESC=End)
7. Verify that are reported the fault nr. 17. (2.1 Alarm)
8. Reset all faults (3 Al/Flt reset)
The test is ended
4.5.2.2 SIMULATION OF THE VB FAULT IN UP DIRECTION
1. Connect the programmer PT01 to the card NGV-A3
2. Move the empty car to the lower landing
3. Start the test procedure 9.6 VB TEST UP (Enter=Start)
4. Move the car in up direction
5. Verify that the car stops at the target landing correctly
6. End the test procedure 9.6 VB TEST UP (Enter=End)
7. Verify that are reported the fault nr. 13 and nr. 14 (2.1 Alarm).
8. Reset all faults (3 Al/Flt reset)
The test is ended
4.5.3 TEST OF THE MONITORING SYSTEM
The NGV A3 card, each travel, automatically perform a check of the monitoring system and in event of fault goes into alarm/fault. To test of the monitoring system is therefore sufficient, at the end of any travel, make sure that (2.1 Alarm) there is no one among the following faults: 06, 07, 13 ÷ 22
NOTE
If requested, it is possible to simulate a fault of the sensors removing from the card or the connector X10 (FAULT 06) or the X11 (FAULT 14). During this event the card must go into alarm. Using the programmer PT01, verify that an alarm is active (2.1 Alarm), insert the connector previously removed (the alarm end) and reset the alarms (3.1 Al/Flt Reset)
¥"
1 0991 483 EN - 21.12.2011
ENG
1.05
30 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
4.6 FAULT SIMULATION ON OUTPUT RDY AND RUN
The test verifies the correct behaviour of the control panel when it receives signals RUN and/or RDY not corrects. It is possible to simulate the failure when the system is stopped a), or during a travel of the system b). To perform the test you must connect the programmer PT01 to the card NGV-A3 and continue simulating faults as follow:
4.6.1 TEST RUN ALWAYS ON
1. Select 9.7 RUN-RDY TEST and push ENT
2. Select using keys Þ/Ý : RUN always ON
3. a) Push ENT with the system stopped .The control panel must recognize the error and to prevent any
movement of the system. b) Make a call in up or down direction and push ENT during the travel. The control panel, after the arrival at landing, after 2 sec, must recognize the error and to prevent any movement of the system.
4. At the end push ENT, Select using keys Þ/Ý : NO TEST and press ENT to restore the initial condition.
4.6.2 TEST RDY ALWAYS OFF
1. Select 9.7 RUN-RDY TEST and push ENT
5. Select using keys Þ/Ý : RDY always OFF
6. a) Push ENT with the system stopped and call the car in up or in down direction. The control panel must
recognize the error and to prevent any movement of the system. b) Make a call in up or down direction and push ENT during the travel. The control panel, after the arrival at landing, after 2 sec, must recognize the error and to prevent any movement of the system.
7. At the end push ENT, Select using keys Þ/Ý : NO TEST and press ENT to restore the initial condition.
4.6.3 TEST RUN ALWAYS OFF
1. Select 9.7 RUN-RDY TEST and push ENT
2. Select using keys Þ/Ý : RUN always OFF
3. a) Push ENT with the system stopped and call the car in up or in down direction. The control panel, after
2 sec, must recognize the error and to prevent any movement of the system. b) Make a call in up or down direction and push ENT during the travel. The control panel, after 2 sec, must recognize the error, to stop the system and to prevent any further movement.
4. At the end push ENT, Select using keys Þ/Ý : NO TEST and press ENT to restore the initial condition.
4.6.4 TEST RDY ALWAYS ON
1. Select 9.7 RUN-RDY TEST and push ENT
2. Select using keys Þ/Ý : RDY always ON
3. a) Push ENT with the system stopped and call the car in up or in down direction. The control panel, after
2 sec, must recognize the error and to prevent any movement of the system. b) Make a call in up or down direction and push ENT during the travel. The control panel, after 2 sec, must recognize the error and after the arrival at landing, to stop the system and to prevent any further movement.
4. At the end push ENT, Select using keys Þ/Ý : NO TEST and press ENT to restore the initial condition
4.6.5 EXIT RUN-RDY TEST
Before to exit 9.7 RUN-RDY TEST verify that NO TEST is set as parameter value.
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
31 / 46
1.05
ENG
5 PROGRAMMING
It is possible to dialog with the NGV01 control board by the programmer PT01. The connection between the programmer and the board is made by a network UTP RJ45 straight cable. The programmer power supply comes from the control board through the connection cable.
It is possible to navigate into the menus and change the numeric values using the arrow keys Ý Þ, it is
possible to enter into the sub-menus and confirm the input data by the ENT key and finally it’s possible exit and move the cursor left side by the ESC key.
Network cord UTP RJ45
WARNING MIN = Car empty MAX = Car with full
load
BHBLS
505152
V-VSV0V1V2V3V+ A+PEA-A-
D+D-E+E-
1
3
NGV-A3-01
EXP VMD
D-E+
E-
111221223132
4142
X14
X15
X12 X11 X10 X9 X8
X7
X13
A-
+ - T+ T- P+ P-+ -+ -
X1
X3
X4 X6
X5
X2
J2 J3
J6
J1
131
3
5.1 SYSTEM PARAMETERS
NOTE
It is recommended to indicate in the table below the parameters of your system To write your parameters make easy future maintenance and repairs.
4 ADJUSTMENTS 6 UP PARAMETERS
4.1 Start UP min
6.2 Int. Speed V1
4.2 Slow UP min
6.3 Ins.Speed V2
4.3 High DN min
6.4 Slow Speed
4.4 Slow DN min
6.5 Relev. Speed
4.5 Start UP max
6.6 Acc.Profile
4.6 Slow UP max
6.7 Dec.Profile
4.7 High DN max
6.8 Start Delay
4.8 Slow DN max
7 DN PARAMETERS
4.9 Offset V0 UP
7.1 Nom. Speed V0
4.10 Offset V0 DN
7.2 Int.Speed V1
4.11 Offset V1 UP
7.3 Insp. Speed V2
4.12 Offset V1 DN
7.4 Slow Speed
5 SETTING
7.5 Relev. Speed
5.1 Lift Ratio
7.6 Acc.Profile
5.2 Jack Diam
7.7 Dec.Profile
5.3 Pump Flow
8 OUTPUT FUNC
5.5 Pstat. min
8.1 Output 11-12
5.6 Pstat.max
8.2 Output 21-22
8.3 Output 31-32
8.4 Output 41-42
1 0991 483 EN - 21.12.2011
ENG
1.05
32 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
5.2 COMPLETE MENÙ
1
NGV-A3 VX.XRXXHX DIAGNOSTICS
5
NGV-A3 VX.XRXXHX SETTINGS
8
NGV-A3 VX.XRXXHX OUTPUT FUNC
1.1 Pressure // xx.x bar 5.1 Lift Ratio // x:x 8.1 Output 11-12 // FUN xx Nx
1.2 Temperature // xx.x C° 5.2 Jack Diam // xxx mm 8.2
Output 21-22 // FUN xx Nx
1.3 Ref.Speed // x.xx m/s 5.3 Pump Flow // xxx l/min 8.3
Output 31-32 // FUN xx Nx
1.4
In: S0123DICA // 000000000
5.4 Map // xx 8.4
Output 41-42 // FUN xx Nx
1.5
Out: 1234YND // 0000000
5.5 Pstat. min // xx.x bar
1.6 Supply // xx.x Vdc 5.6 Pstat.max // xx.x bar
1.7 Fly Time // 5.7 P min // xx.x bar
1.7.1 Total //xxx.x s 5.8 P full load // xx.x bar
1.7.2 Start -> Dec. // XXX.X s 5.9 P overload // xx.x bar
1.7.3 Dec. -> Stop //XXX.X s 5.10 P max // xx.x bar
5.11 Cool Temp // xx °C
5.12 Mode: Normal-Installation
2
NGV-A3 VX.XRXXHX ALLARMS
6
NGV-A3 VX.XRXXHX UP PARAMETERS
9
NGV-A3 VX.XRXXHX TEST…
2.1 Alarm 01 // 00: No Alarm 6.1 Nom.Speed V0 // x.xx m/s 9.1 OverP. Value // Ent = Start
... ... 6.2 Int. Speed V1 // x.xx m/s 9.2 Pipe Rupture // Ent = Start
2.8 Alarm 08 // 00: No Alarm 6.3 Ins.Speed V2 // x.xx m/s 9.3 UCM UP test // Ent = Start
6.4 Slow Speed // x.xxx m/s 9.4 UCM Test up // Ent = Start
6.5 Relev. Speed // x.xxx m/s 9.5 VB test down // Ent = Start
3
NGV-A3 VX.XRXXHX AL/FLT RESET
6.6 Acc. Profile // XS,S,ST,F,C 9.6 VB test down // Ent = Start
3.1 Reset ? ESC=NO ENT=YES 6.7 Dec.Profile // XS,S,ST,F,C 9.7 Run-Rdy test // No test
6.8 Start Delay // x.x s 9.8 S3 tuning // Ent =Start
4
NGV-A3 VX.XRXXHX ADJUSTMENTS
7
NGV-A3 VX.XRXXHX DN PARAMETERS
10
NGV-A3 VX.XRXXHX ADVANCED
4.1 Start UP min // ±xx 7.1 Nom. Speed V0 // x.xx m/s 10.1 Password // -00000
4.2 Slow UP min // ±xx 7.2 Int.Speed V1 //x.xx m/s
4.3 High DN min // ±xx 7.3 Ins.Speed V2 // x.xx m/s
4.4 Slow DN min // ±xx 7.4 Slow Speed // x.xxx m/s
4.5 Start UP max // ±xx 7.5 Relev. Speed // x.xxx m/s
4.6 Slow UP max // ±xx 7.6 Acc. Profile // XS,S,ST,F,C
4.7 High DN max // ±xx 7.7 Dec.Profile // XS,S,ST,F,C
4.8 Slow DN max // ±xx
4.9 Offset V0 UP // xxx mm
4.10 Offset V0 DN // xxx mm
4.11 Offset V1 UP // xxx mm
4.12 Offset V1 DN // xxx mm
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
33 / 46
1.05
ENG
5.3 MENÙ
- 1 - DIAGNOSTICS
NGV VER XX.XXX
1-DIAGNOSTICS
Ý Þ
1.1 PRESSURE
XX.X bar
Pressure gauge [bar] read by the pressure transducer
Ý Þ
1.2 TEMPERATURE
XX.X °C
Temperature gauge [°C] read by the temperature transducer
Ý Þ
1.3 REF. SPEED
X.XXX m/s
Set point speed [m/s]
Ý Þ
State of the input signals: S0123DICA
1.4 INPUT S0123DICA
000000000
100000000=VS 010000000=V0 001000000=V1 000100000=V2 000010000=V3 000001000=D
000000100=IND 000000010=VBC 000000001=VBO
Ý Þ
State of the output signals: 1234YND
1.5 OUTPUT 1234YND
0000000
1000000=Out1 0100000=Out2 0010000=Out3 0001000=Out4 0000100=RDY 0000010=RUN 0000001=VMD
Ý Þ
1.6 SUPPLY
XX.X V
Supply voltage [V] of the control board
Ý Þ
1.7 FLY TIME
Fly time of the lift
ENT
1.7.1 TOTAL
XXX.X s
Total time of the lift travel [s]
Ý Þ
1.7.2 START->DEC
XXX.X s
Ý Þ
Time between the start of the lift end the start of the deceleration phase [s]
1.7.3 DEC->STOP
XXX.X s
Time between the start of the deceleration phase and the stop of the lift [s]
V0
Vs/D
Start->Dec
Total
Dec->Stop
OFF ON
- 2 - ALLARM
NGV VER XX.XXX
2-ALARM
Ý Þ
2.1 ALARM
00:No Alarm
Active alarms. Each alarm is identified by a code explained in the Failure Chart. Last 8 alarms are stored in memory
- 3 - ALARM AND FAULT RESET
NGV VER XX.XXX
3-AL/FLT RESET
Ý Þ
3.1 FAULT RESET
Pressing the ENT key on the programmer all the faults and the alarms are deleted
1 0991 483 EN - 21.12.2011
ENG
1.05
34 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
- 4 - ADJUSTMENTS
NGV VER XX.XXX
4-ADJUSTMENTS
Optimal car motion
Real car motion
Ý Þ
A B
C
4.1 START UP MIN
±XX.X
UPWARD start adjustment (-99 ÷ +99)
A
+Ý -Þ
4.2 SLOW UP MIN
±XX.X
UPWARD levelling speed adjustment (-99 ÷ +99)
B
+Ý -Þ
4.3 HIGH DN MIN
±XX.X
DOWNWARD high speed adjustment (-99 ÷ +99)
C
+Ý -Þ
4.4 SLOW DN MIN
±XX.X
DOWNWARD levelling speed adjustment (-99 ÷ +99)
B
+Ý -Þ
4.5 START UP MAX
±XX.X
UPWARD start adjustment (-99 ÷ +99)
A
+Ý -Þ
4.6 SLOW UP MAX
±XX.X
UPWARD levelling speed adjustment (-99 ÷ +99)
B
+Ý -Þ
4.7 HIGH DN MAX
±XX.X
DOWNWARD high speed adjustment (-99 ÷ +99)
C
+Ý -Þ
4.8 SLOW DN MAX
±XX.X
DOWNWARD levelling speed adjustment (-99 ÷ +99)
B
+Ý -Þ
4.9 OFFSET V0 UP
XXX mm
+Ý -Þ
UPWARD levelling space adjustment in NOMINAL speed (0 ÷ 600 mm)
4.10 OFFSET V0 DN
XXX mm
+Ý -Þ
DOWNWARD levelling space adjustment in NOMINAL speed (0 ÷ 600 mm)
4.11 OFFSET V1 UP
XXX mm
+Ý -Þ
UPWARD levelling space adjustment in INTERMEDIATE speed (0 ÷ 600 mm)
4.12 OFFSET V1 DN
XXX mm
+Ý -Þ
DOWNWARD levelling space adjustment in INTERMEDIATE speed (0 ÷ 600 mm)
D
D
RAL
600 0
OFFSET
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
35 / 46
1.05
ENG
- 5 - SETTINGS
Data entered by GMV, run control during the installation of the system
NGV VER XX.XXX
5-SETTINGS
Ý Þ
5.1 LIFT RATIO
X:X
Ratio of the lift system (1:1; 2:1; 3:1)
Ý Þ
5.2 JACK DIAM.
XXX mm
Diameter or correspondent diameter of the jack [mm] (see data on technical catalogue tables)
Ý Þ
5.3 PUMP FLOW
XXX l/min
Flow rate of the pump [l/min]
Ý Þ
5.4 MAP
XXXX
Map code of the power unit (not active)
Ý Þ
5.5 PSTAT MIN
XX.X bar
Minimum static pressure (5.0 ÷ 45.0 bar)
Ý Þ
5.6 PSTAT MAX
XX.X bar
Maximum static pressure (Pstat Min. ÷ 45.0 bar)
Ý Þ
5.7 P MIN
XX.X bar
Minimum pressure (1.0 ÷ 10.0 bar) medium value ±5 bar
Ý Þ
5.8 P FULL LOAD
XX.X bar
Full load pressure, 80% of nominal load (12.0 ÷ 45.0 bar)*
Ý Þ
5.9 P OVERLOAD
XX.X bar
Overload pressure, 110% of nominal load (12.0 ÷ 50.0 bar)*
Ý Þ
5.10 P MAX
XX.X bar
Pressione di massima, 140% del carico nominale (15.0 ÷ 70.0 bar)*
Ý Þ
* Re-calculated value when the P
stat,MIN
value (parameter 5.5) or the
P
stat,MAX
value (parameter 5.6) are modified
5.11 COOL TEMP.
XX °C
Maximum allowable fluid temperature (5.0 ÷ 70.0 °C) set value 70°C
Ý Þ
5.12 MODE:
XX - XX
Mode: NORMAL Mode:INSTALLATION
NOTE
If the mode set is : NORMAL, the valve works as shown into the manual. If the mode set is : INSTALLATION, the valve works at V2 speed regardless of signal it receives from the control panel. The installation mode is used routinely during the installation of the system.
¥"
1 0991 483 EN - 21.12.2011
ENG
1.05
36 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
- 6 - UPWARD PARAMETERS
NGV VER XX.XXX
6-UP PARAMETERS
Ý Þ
6.1 NOM.SPEED V0
X.XX m/s
Nominal speed [m/s] referred to the nominal pump flow, piston diameter and size, value not modifiable.
Ý Þ
6.2 INT.SPEED V1
X.XX m/s
Intermediate speed [m/s] (15 ÷ 75 % x Nominal Speed)
Ý Þ
6.3 INS.SPEED V2
X.XX m/s
Inspection speed (0.15 ÷ 0.63 m/s)
Ý Þ
6.4 SLOW SPEED
X.XX m/s
Levelling speed (0.01 ÷ 0.15 m/s, recommended 0.06 m/s)
Ý Þ
6.5 RELEV.SPEED
X.XX m/s
Re-levelling speed (0.01 ÷ 0.15 m/s, recommended 0.04 ÷ 0.06 m/s)
Ý Þ
6.6 ACC.PROFILE
XXXXXXXX
Acceleration profile (Fast – Standard – Slow – Extra Slow - Custom)
Ý Þ
6.7 DEC.PROFILE
XXXXXXXX
Deceleration profile (Fast – Standard – Slow – Extra Slow - Custom)
Ý Þ
6.8 START DELAY
X.X s
Delay start closing VB / Time to start the motor/pump (0,2…5,0 s)
- 7 - DOWNWARD PARAMETERS
NGV VER XX.XXX
7-DN PARAMETERS
Ý Þ
7.1 NOM.SPEED V0
X.XX m/s
Enter required nominal downward speed (m/s…) . es: 0,63
Ý Þ
7.2 INT.SPEED V1
X.XX m/s
Indicates the Intermediate speed [m/s] (15 ÷ 75 % x Nominal Speed)
Ý Þ
7.3 INS.SPEED V2
X.XX m/s
Inspection speed (0.15 ÷ 0.63 m/s)
Ý Þ
7.4 SLOW SPEED
X.XXX m/s
Levelling speed (0.01÷ 0.15 m/s, recommended 0.04 m/s)
Ý Þ
7.5 RELEV. SPEED
X.XXX m/s
Re-levelling speed (0.01÷ 0.15 m/s, recommended 0.02 ÷ 0.04 m/s)
Ý Þ
7.6 ACC.PROFILE
XXXXXXXX
Acceleration profile (Fast – Standard – Slow – Extra Slow - Custom)
Ý Þ
7.7 DEC.PROFILE
XXXXXXXX
Deceleration profile (Fast – Standard – Slow – Extra Slow - Custom)
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
37 / 46
1.05
ENG
- 8 - OUTPUT FUNCTIONS
NGV VER XX.XXX
8-OUTPUT FUNC.
Ý Þ
8.1 OUTPUT 11-12
FUNXXXX
Active function on output 11-12. Every function is identified by a code described into Output Programmable Functions Chart
Ý Þ
8.2 OUTPUT 21-22
FUNXXXX
Active function on output 21-22. Every function is identified by a code described into Output Programmable Functions Chart
Ý Þ
8.3 OUTPUT 31-32
FUNXXXX
Active function on output 31-32. Every function is identified by a code described into Output Programmable Functions Chart
Ý Þ
8.4 OUTPUT 41-42
FUNXXXX
Active function on output 41-42. Every function is identified by a code described into Output Programmable Functions Chart
As default the output are set up with this functions:
· Output 11-12: Minimum pressure (01NC)
· Output 21-22: Maximum pressure (02NC)
· Output 31-32: Overload (08NO)
· Output 41-42: Up (09NO)
- 9 - TEST
NGV VER XX.XXX
9-TEST…
Ý Þ
9.1 OVERP. VALUE
ENT=Start
Start the routine for the control of the adjusted pressure on the overpressure valve. For the overpressure value test please refer to the Overpressure Valve (VS) Adjustment chapter. This routine needs VS and V0 input signals for working. Press ENT to start the routine. The display blinks while the routine is working, at the end of the routine the fixed value is the adjustment value of the overpressure valve. Press ESC to exit and ENT to start again.
Ý Þ
9.2 PIPE RUPTURE
ENT=Start
Start the routine for the test of the pipe rupture valve. For the pipe rupture valve test please refer to the Pipe Rupture (VC) Test chapter. This routine needs D and V0 input signals for working. Press ENT to start the routine. The routine is ended when the D signal falls down. Press ESC to exit and ENT to start again.
Ý Þ
9.3 UCM UP TEST
ENT=Start
Start the routine that allows to simulate the unintended car movement in up direction To use this function see the chapter Test in Up direction This routine needs that the control panel works in normal mode (not inspection) Press ENT to start the routine. Press ESC to end/exit.
Ý Þ
9.4 UCM DN TEST
ENT=Start
Start the routine that allows to simulate the unintended car movement in down direction To use this function see the chapter Test in Down direction This routine needs that the control panel works in normal mode (not inspection) Press ENT to start the routine. Press ESC to end/exit.
Ý Þ
1 0991 483 EN - 21.12.2011
ENG
1.05
38 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
9.5 VB TEST DOWN
ENT=Start
Start the routine to check if the VRP working well in event of VB breaking at downward end. To use this function see chapter Simulation of the
VB fault.
This routine needs D and V0 input signals for working. Press ENT to start the routine. During downward the VB will work in a not correct way to allow the test. Press ESC to exit and ENT to start again the routine
Ý Þ
9.6 VB TEST UP
ENT=Start
Start the routine to check if the system working well in event of RUN/RDY breaking. To use this function see chapter Simulation of the
VB fault.
This routine needs VS and V0 input signals for working. Press ENT to start the routine. During downward the VB will work in a not correct way to allow the test. Press ESC to exit and ENT to start again the routine
Ý Þ
9.7 RUN-RDY TEST
ENT=Start
Start the routine to check if the VRP working well in event of VB breaking at upward end. To use this function see chapter Fault simulation on output RDY and RUN. Press ENT , select the fault that you want simulate, push ENT to activate the fault. The fault condition that you can choose are: RUN always ON,, RDY always OFF, RUN always OFF, RDY always ON.
NOTE
Exit from test using the ESC key, do not restore the NO TEST condition necessary for the normal working of the sysstem. To return to normal operating condition parameter, you should select NO TEST and press ENT to confirm the codition change, before to exit pushing ESC.
Ý Þ
9.8 S3 TUNING
ENT=Start
Start the routine that allows to place the sensor S3 in the correct position. The routine open the VB allowing to move the sensor in the exact lighting position. To use this function see chapter 6 Adjusting of the sensors. Press ESC to end
- 10 - ADVANCED PROGRAMMING
NGV VER XX.XXX
10-ADVANCED
Ý Þ
10.1 PASSWORD
00000
Entering the password it’s possible to read and modify the entire parameters of the NGV valve
5.4 CHART OF OUTPUT PROGRAMMABLE FUNCTIONS
The outputs 11-12; 21-22; 31-32; 41-42 are programmable with a specific function. Each function could be defined active as NO (Normally Open) or as NC (Normally Close)
Function Description PT01 Code
0 No function, output OFF FUN00
1
Minimum pressure (see parameter 5.7 into the Programming section)
FUN01NC FUN01NO
2
Maximum pressure (see parameter 5.10 into the Programming section)
FUN02NC FUN02NO
3 Maximum pressure or minimum pressure FUN03NC FUN03NO 4 Minimum temperature (<5°C) FUN04NC FUN04NO
5
Maximum temperature (see parameter 5.11 into the Programming section)
FUN05NC FUN05NO
6 Maximum temperature or minimum temperature FUN06NC FUN06NO 7
Full load (see parameter 5.8 into the Programming section)
FUN07NC FUN07NO
8
Overload (see parameter 5.9 into the Programming section)
FUN08NC FUN08NO
9 Signal UP FUN09NC FUN09NO
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
39 / 46
1.05
ENG
5.5 CHART OF FAILURES
S1 (VRP)
S2 (VB Close)
S3 (VB Open)
Fault Description
00: NO ALARM
No alarm
01: SUPPLY LOW
Low power supply < Vdc - 15%
02: SUPPLY HIGH
High power supply > 40 Vdc
03: PRESS. FAULT
Pressure transducer PT short circuit
04: TEMP. FAULT
Temperature transducer TT short circuit
05: STEP MOTOR
Stepping motor driver SM overheated
06: S1 VRP OPEN
Contact S1 (VRP) open with lift stopped
07: S1 VRP OPEN
Contact S1 (VRP) open at the end of a downward travel
08: VS-VD INPUT
Signals VS and D contemporaneous
09: PRESS. MAX
Maximum pressure > 5.10 PSTAT MAX
10: PRESS. MIN
Minimum pressure < 5.7 PSTAT MIN
11: OIL TEMP LOW
Minimum oil temperature < 5°C
12: OIL TEMP HI
Maximum oil temperature > 5.11 COOL TEMP
13: S3 CLOSED
Contact S3 (VBO) closed with lift stopped
14: S3 OPENED
Contact S2 (VBC) opened with lift stopped
15: S1 NOT OPEND
Contact S1 (VRP) did not opened during starting downward travel
16: S1 NOT CLOSD
Contact S1 (VRP) did not closed during end of downward travel
17: S2 NOT CLOSD
Contact S2 (VBC) did not closed during end of downward travel
18: S3 NOT CLOSD
Contact S3 (VBO) did not closed when VB opens
19: S2 NOT OPEND
Contact S2 (VBC) did not opened when VB opens
20: S1 ALRDY OPN
Contact S1 (VRP) open before starting upward travel
21: S1 NOT OPEND
Contact S1 (VRP) did not opened during starting or in high speed
22: S1 NOT CLOSD
Contact S1 (VRP) did not closed during end of upward travel
5.6 ACCESSORIES
Box MR Box MRL NGVA3-XX Morsettiera PT01
40370007 + 00000000
01: 70200334
00000000 70205360
61000010 +
02: 70200335
24VDC:80395002C
40990003
03: 70200336
12VDC:80395002C
1 0991 483 EN - 21.12.2011
ENG
1.05
40 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
6 MAINTENANCE AND FAULT ANALYSIS
6.1 PROGRAMMED MAINTENANCE
For a correct and safe lift use, it is necessary to make a preventive programmed maintenance, following a fixed plan. To define the periodical maintenance frequency, you should consider more events, particularly :
- Number of travel per year
- Travelling and stopping periods
- Age and condition of the lift
- Site and type of the building in which the lift travel
- Passengers and goods demand
- Inside and outside working condition (climate, vandalism, etc.) In the next table, parts are shared in groups and for each group is shown the type of check and its longest frequency recommended. Checks operative instructions are detailed in the maintenance schedules on chapter. Please, note that all checks are applicable only if the part is really installed..
6.2 PERIODICAL MAINTENANCE AND CHECKS TABLE
Operation checks Recommended maximal Frequency
INSTALLAZIONE MESI ANNI
Valve gaskets seal
þ
6
Oil level check up
þ
6
Characteristics of the oil
þ
6
Motor protection operation
þ
6
Filters
þ
1
Pressure check
þ
6
Pressure gauge shut off (4)
þ
6
Pressure test (static pressure x2)
þ
6
Ball valve seal
6
Labels, signs and schemes
þ
6
Overall check-up
5
6.3 MAINTENANCE SCHEDULES
What to do: (see image) Valve gaskets seals
- At the end of installation, and during check-
ups, verify the gasket seals, in the following way: with the oil at room temperature close the ball valve (B) and open the pressure gauge shut off (4). Check that the pressure gauge reading on pressure gauge should not drop more than 4 bar in 5 minutes.
Oil level check-up.
- With the elevator at the highest floor, check,
using dipstick (F) or level indicator (L), that the oil level is above the minimum level and (the motor should be fully covered in oil).
VSMA
VMD
PT
MAN
B
S1
SM
S3
S2
3
5
1
4
ISP
PAMï
ML
Oil Characteristics
- Check visually that no change are occurred in the oil conditions. Perform this check after leaving the
system down for a few hours. Once every year it should be better to discharge a little amount of oil from cap (J) and to check if it’s clean. If oil is not clean keep on discharging oil until you see to flow clean oil.
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
41 / 46
1.05
ENG
Motor protection functionality
- Disconnect one terminal of the thermistors, and check that the motor protection working properly.
Filter
- Check the main filter (FIL) mounted inside the silencer and clean it if is necessary.
Pressures check
- Check static and dynamic (working) pressure at the end of installation. Check regularly that all values of these parameters remain unchanged.
Pressure gauge shut off (4)
- Close the ball valve (B), open the pressure gauge shut off (4) and fully discharge the pressure using electro-valve (VMD). Close the pressure gauge shut off (4) open the ball valve (B) and check that the level shown on pressure gauge is zero.
Pressure test (static pressure x2)
· This test assures you about the integrity of parts under pressure, including those which can not be visually checked.
· To correctly carry out this test follow these instructions and make reference to the images:
- Close the pressure gauge valve (4).
- Close the ball valve (B). Remove the pressure gauge (MAN).
- Connect the hand pump (M) in place of the pressure gauge (G1/4) as shown in the image on the right side
- Open the pressure gauge valve (4).
- Open the ball valve (B).
- Open the hand pump valve (N) for about 1 minute.
- Close the hand pump valve (N).
- Close the ball valve (B).
- Operate the hand pump (M) until the required pressure is reached, checking it on hand pump pressure gauge (O).
- At the end of the test, discharge the pressure to zero by pressing the push-button on (VMD) (see image up).
- Close the pressure gauge shut off (4).
- Disconnect the hand pump (M)
- Mount the pressure gauge (MAN).
Ball valve seal
- Close the ball valve (B) and open the pressure gauge shut off (4). Fully discharge the pressure-using valve (VMD). check that the level shown on pressure gauge (MAN) is zero.
LEGEND:
M – Test hand pump N – Shut off valve for H-pump O – Pump pressure gauge P – Pump fitting Q – Cupper washer
Labels, signs and schemes
- Check that all the tags and diagrams are in place and legible (oil data label, emergency operation manual, electrical diagram and hydraulic power unit schemes).
Overall check-up
- Perform an overall check up of the power unit. When the overall check-up ends, check all the settings for the power unit start-up.
· Replace or restore all the components not correctly working. NOTE
In case of oil replacement, do not throw the oil away in the environment, but give it to oil recycling company.
NOTE
When the power unit in no longer required, don’t throw it away, but give it to a recycling company or to the manufacturer.
¥"
1 0991 483 EN - 21.12.2011
ENG
1.05
42 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
6.4 FAULT ANALYSIS
Fault Possible cause Possible solution
01: SUPPLY LOW
Low power supply
Increase power voltage by adjustment or replace power supply
02: SUPPLY HIGH
High power supply
Decrease power voltage by adjustment or replace power supply
03: PRESS. FAULT
Pressure transducer PT failure Replace transducer PT
04: TEMP. FAULT
Temperature transducer TT failure Replace transducer TT
05: STEP MOTOR
Stepping motor (SM) overheated
Wait for motor cooling. If the problem recurs after a short time, replace stepping motor.
06: S1 VRP OPEN
Contact S1 (VRP) open with lift stopped
See 13-22
07: S1 VRP OPEN
Contact S1 (VRP) open at the end of a downward travel
See 13-22
08: VS-VD INPUT
Signals VS and D contemporaneous
Verify that the control panel sends signals correctly
09: PRESS. MAX
Maximum pressure > 5.10 PSTAT MAX
Verify that the parameter is equal to the system value. If it is not equal, set parameter equal to the system, if equal to find the cause of overpressure.
10: PRESS. MIN
Minimum pressure < 5.7 PSTAT MIN
Find and correct the cause that does not allow to the pressure to reach the minimum value required.
11: OIL TEMP LOW
Minimum oil temperature < 5°C
Verifiy that the sensor works crrectly or install an oil heater.
12: OIL TEMP HI
Maximum oil temperature > 5.11 COOL TEMP
If the parameter 5.11 COOL TEMP is < 70°C set the value up to 70°C If the parameter 5.11 COOL TEMP is = 70°C probably you must install an heat exchanger
13: S3 CLOSED
Contact S3 (VBO) closed with lift stopped
14: S2 OPENED
Contact S2 (VBC) opened with lift stopped
15: S1 NOT OPEND
Contact S1 (VRP) did not opened during starting downward travel
16: S1 NOT CLOSD
Contact S1 (VRP) did not closed during end of downward travel
17: S2 NOT CLOSD
Contact S2 (VBC) did not closed during end of downward travel
18: S3 NOT CLOSD
Contact S3 (VBO) did not closed when VB opens
19: S2 NOT OPEND
Contact S2 (VBC) did not opened when VB opens
20: S1 ALRDY OPN
Contact S1 (VRP) open before starting upward travel
21: S1 NOT OPEND
Contact S1 (VRP) did not opened during starting or in high speed
22: S1 NOT CLOSD
Contact S1 (VRP) did not closed during end of upward travel
Verify that the sensor works correctly placing a magnet near to its white side. If the led does not change status (Led not turn on if it is in off status or led not turn off if it is in on status) the sensor is broken and you must replace it. If the led changes status (Led turn on if it is in off status or led turn off if it is in on status) the sensor works correctly. You should try to move the sensor to the correct position. (see
6.5). If the problem persist on the sensor S1 probably the VRP does not work correctly (verify and/or contact support). If the problem persist on the sensors S2 e S31 probably the stepping motor does not work correctly (verify and eventually replace) or not work correctly the VB (verify and/or contact support)
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
43 / 46
1.05
ENG
6.4.1 TROUBLESHOOTING
Fault Possible cause Possible solution
1
The system
- do not start but the pump works
The card do not receive the signal VS from the control panel. The control panel do not receive/recognize the RUN signal from the card.
Verify in the Menu 1.4 if the card receive the signal VS from control panel. Verfy that signals RDY and RUN are according to the schema 2.3.3
2
The system
- run slowly in up and down direction
- stops immediately without deceleration
The Menu 5.12 is set on “Install” and the system run only in inspection speed.
The default parameter is “Install”. At the end of the installation you must set the parameter 5.12 = “Normal”
3
The system
- run only with low speed
The card
- do not receive the speed signal (V0, V1, V2)
- receive the speed signal after the direction signal (VS, D)
Verify (menu 1.4 S0123DICA) that the card receives the speed and the direction signals. If the card do not receives any signal check the signal flow from the control panel and repair the error.
4
The system
- has an abrupt departure in up direction (run fast for piece of the travel, slows, and return to the correct speed.
The motor starts before of the RUN signal
Verify that the signals RUN and RDY are in compliance with § 2.3.3. Verify (menù 1.4 S0123DICA) that all signals are received and (menù 1.5 1234YND) send correctly to/from the card. The motor do not must start before:
- VS, up command
- RUN
- Out 4=UP if used
5
The system
- starts in up direction with an not regular acceleration (it starts with a little burst and immediately return to the correct acceleration)
The starting time is not correct, the oil output line was open in advance and the oil reach the piston until the motor is at full.
Increase the value of the menu point 6.8 to delay the oil output line opening.
6
The system
- run irregularly and inaccurate
The basic parameters are not corrects
Verify (menu 5) that the values set are in compliance with the effective system data. Particularly, verify values 5.5 Pstat MIN e
5.6 Pstat MAX
7
The system
- stops over/under the landing level when the system has a reduced floor distance (< 1,8m)
The system arrive at landing in nominal speed (Vo) instead of intermediate speed V1. The intermediate speed set is too high
Verify that the card receives the speed signal V1 (menu 1.4 S0123DICA). If the card do not receive the signal check the signal flow from the control panel and repair the error. If the card receive the signal you must decrease the intermediate speed V1 parameter (in up direction menu 6.2, in down direction menu 7.2 recommended value 0,3 m/s) and/or increase the deceleration distance.
8
The system
- do not decelerate correctly
The speed signals (V0, V1 o V2) are not according with §
3.5 or the magnet position is not correct
Verify (menù 1.4 S0123DICA) that the status of the speed signal V0 changes from 1 to 0 when the car comes in the deceleration zone. Verify that the parameters 4.9, 4.10, 4.11 e
4.12 are correctly set (default = 0) and otherwise, set the correct value. Verify that the magnets are at the correct distance from the floor If the problem persist, please, contact the technical support.
1 0991 483 EN - 21.12.2011
ENG
1.05
44 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
9
The system
- do not stops at landing
The signal VS or D do not switch off or is switched off too late (up to 1-2 cm from floor) The deceleration speed or the levelling speed is too high.
Verify (menu 1.4 S0123DICA) that the signal VS or D is switched off before that the car arrives at floor, at the beginning of the deceleration zone. If the signal do not change status check the signal flow from the control panel and repair the error. If the problem persist, verify the parameters set in Menu: 4.2, 4.4, 4.6 e 4.8 and if are not the default value set to default (default = 0). Verify that the value of parameters 6.4, 6.5, 7.4 e 7.5 is the recommended value. (see § 5.3) If setting parameter to the default values do not solve the problem, you should personalize the value set in the Menu: 4.2,
4.4 (min = car empty), 4.6 e 4.8 (max = car with full load).
10
The system stops during the switching from nominal speed to slow speed; with the car empty or full loaded.
If the basic settings are correct (Menu 5) the slow speed (6.4 and 7.4) or the low speed offsets (4.2, 4.4,
4.6 e 4.8) should be too low.
Input the recommended values for the menu points 6.4 e 7.4 or increase the offsets of the slow speed (4.2, 4.4, 4.6 e
4.8)
11
The control panel detects an insufficient minimum pressure
The system minimum pressure is below the minimum allowed or control panel and card do not work with the same type of signal. (the card send a normally close (NC) signal and the control panel works with a normally open (NO) signal).
Control (Menu 1.1) the pressure value of the system, if the value is below the minimum (5.7 bar) and the red led is switch on, you must increase the minimum pressure of the system. If you have no error on the card and the minimum pressure is higher than 5.7 bar you must verify that the card and the control panel have the same type of signal (both NC or both NO)
¥"
1 0991 483 EN - 21.12.2011
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
45 / 46
1.05
ENG
6.5 ADJUSTING THE SENSORS
The adjusting of the sensors should be done with the system stopped.
S1 (VRP)
S2 (VB Close)
S3 (VB Open)
6.5.1 SENSOR S1
ò12
3
1/4
6.5.2 SENSOR S2
õ12
3
1/4
6.5.3 SENSOR S3
8. Using the programmer PT01 select the function
9.8 S3 tuning and activate it pressing ENT
9. Proceed as show in the image
10. deacrivate the function
9.8 S3 tuning by pressing ESC
ö
1
2
3
P
1/4
1 0991 483 EN - 21.12.2011
ENG
1.05
46 / 46
NGV A3 VALVE MANUAL
INSTALLATION, USE AND MAINTENANCE
7 CERTIFICATES
¥"
¥"
APPARECCHIATURE FLUIDODINAMICHE
E COMPONENTI PER ASCENSORI
GMV SPA
VIA DON GNOCCHI, 10 - 20016 PERO – MILANO (ITALY) TEL. +39 02 33930.1 - FAX +39 02 3390379
HTTP://WWW.GMV.IT - E-MAIL: INFO@GMV.IT
Azienda CERTIFICATA UNI EN ISO 9001
Doc. n° 1 0991 483 Rev. 1.05 - 21.12.2011 File: NGVA3-MI-02-10991483EN.doc - (J2)
Loading...