D6036S - D6036D
INSTRUCTION MANUAL
SIL 2 Switch/Proximity Detector Repeater,
Relay Output DIN-Rail
Models D6036S, D6036D
D6036 - SIL 2 Switch/Proximity Detector Repeater, Relay Output G.M. International ISM0407-0

Characteristics
General Description: The single and dual channel Switch/Proximity Detector Repeater, D6036S and D6036D module is a unit suitable for applications requiring SIL 2 level (according to
IEC 61508:2010 Ed. 2) in safety related systems for high risk industries.
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NE or ND SPST (D6036D) or SPDT (D6036S) relay output contact.
Each channel enables a load to be controlled by a switch, or a proximity detector.
A fault detection circuit (DIP switch enabled) is available for both proximity sensor and switch equipped with end of line resistors. In case of fault, when enabled, it de-energizes the
corresponding output relay and turns the fault LED on; when disabled the corresponding output relay repeats the input line open or closed status as configured.
Mounting on standard DIN-Rail, with or without Power Bus.
Functional Safety Management Certification:
G.M. International is certified by TÜV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
FSM
SIL 3
Supply: 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits 5 Vpp, 2 A time lag fuse internally protected.
Technical Data
Current consumption @ 24 V: 35 mA for 2 channels D6036D, 18 mA for 1 channel D6036S with short circuit input and relay energized, typical.
Power dissipation: 0.85 W for 2 channels D6036D, 0.45 W for 1 channel D6036S with 24 V supply voltage, short circuit input and relay energized, typical.
Isolation (Test Voltage): In/Out 1.5 KV; In/Supply 1.5 KV; In/In 500 V; Out/Supply 1.5 KV; Out/Out 1.5 KV.
Input switching current levels: ON 2.1 mA (1.9 to 6.2 mA range), OFF 1.2 mA (0.4 to 1.3 mA range), switch current 1.65 mA ± 0.2 mA hysteresis.
Fault current levels: open fault 0.2 mA, short fault 6.8 mA.
Input equivalent source: 8 V 1 K typical (8 V no load, 8 mA short circuit).
Output: voltage free SPST (D6036D) or SPDT (D6036S) relay contact.
Contact material: Ag Alloy (Cd free), gold plated.
Contact rating: 4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W (resistive load). Min. switching current 1 mA.
DC Load breaking capacity:
V (V)
300
250
200
Resistive
100
50
40
30
20
10
0.3 0.4 0.5 1 2 3
0.20.0
0.1
Load
I (A)
4
6
Mechanical / Electrical life: 5 * 10
/ 3 * 104 operation, typical.
Operate / Release time: 8 / 4 ms typical.
Bounce time NO / NC contact: 3 / 8 ms typical.
Frequency response: 10 Hz maximum.
Compatibility:
CE mark compliant, conforms to Directive: 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage: temperature limits – 45 to + 80 °C.
Approvals:
TÜV Certificate No. C-IS-722134640-01, SIL 2 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
Mounting:
T35 DIN-Rail according to EN50022, with or without Power Bus.
Weight: about 135 g D6036D, 120 g D6036S.
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm
2
.
Protection class: IP 20.
Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
2
D6036 - SIL 2 Switch/Proximity Detector Repeater, Relay Output G.M. International ISM0407-0

Ordering Information
Model: D6036
1 channel S
2 channels
D
Front Panel and Features
Power Bus and DIN-Rail accessories:
Connector JDFT049 Cover and fix MCHP196
Terminal block male MOR017 Terminal block female MOR022
SIL 2 according to IEC 61508:2010 Ed. 2
for Tproof = 4 / 20 years (10% / >10 % of total SIF) for D6036S and D6036D.
PFDavg (1 year) 2.25 E-04, SFF 70.87 % for D6036S.
PFDavg (1 year) 2.25 E-04, SFF 71.76 % for D6036D.
Systematic capability SIL 3.
NO/NC switch/proximity Detector Input, NE/ND relay actuation mode.
Field open and short circuit detection.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
In-field programmability by DIP Switch.
TÜV Certification.
TÜV Functional Safety Certification.
High Density, two channels per unit.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus.
+ Input Ch 1 for Proximity or Voltage free Contact
7
Terminal block connections
7 8
9 10
Output Ch 1
1
1
2
4 3
6 5
- Input Ch 1 for Proximity or Voltage free Contact
8
+ Input Ch 2 for Proximity or Voltage free Contact
9
- Input Ch 2 for Proximity or Voltage free Contact
10
Output Ch 1
2
Output Ch 2
3
Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
D6036 - SIL 2 Switch/Proximity Detector Repeater, Relay Output G.M. International ISM0407-0
3