GMI D5031, D5030, D5032, D5034, D5036 Safety Instructions

...
Note: This manual contains only safety instructions.
For the complete installation and user manuals, certifications and data sheets, please refer to www.gmintsrl.com.
D5000 Safety Instruction Manual ISM0156-9
SAFETY INSTRUCTIONS
D5000 series
PSD5000 Series Power Supplies
ISM0156-9 Page 2
ISM0156-9 Page 3
SUMMARY
D5011 .................................................................................................................. 4
D5014 .................................................................................................................. 5
D5020 .................................................................................................................. 7
D5030 .................................................................................................................. 9
D5031 ................................................................................................................ 10
D5032 ................................................................................................................ 12
D5034 ................................................................................................................ 13
D5036 ................................................................................................................ 15
D5037 ................................................................................................................ 16
D5040 ................................................................................................................ 18
D5048 ................................................................................................................ 21
D5049 ................................................................................................................ 23
D5062 ................................................................................................................ 25
D5072 ................................................................................................................ 27
D5072-087 ......................................................................................................... 29
D5090 ................................................................................................................ 31
D5090-086 ......................................................................................................... 32
D5091 ................................................................................................................ 33
D5093 ................................................................................................................ 34
D5094 ................................................................................................................ 35
D5095 ................................................................................................................ 36
D5096 ................................................................................................................ 37
D5097 ................................................................................................................ 38
D5098 ................................................................................................................ 39
D5202 ................................................................................................................ 40
D5231 ................................................................................................................ 41
D5240 ................................................................................................................ 42
D5244 ................................................................................................................ 49
D5254 ................................................................................................................ 51
D5263 ................................................................................................................ 53
D5264 ................................................................................................................ 55
D5273 ................................................................................................................ 56
D5290 ................................................................................................................ 58
D5290-078 ......................................................................................................... 59
D5291 ................................................................................................................ 60
D5293 ................................................................................................................ 61
D5294 ................................................................................................................ 62
D5295 ................................................................................................................ 63
PSD5201 ........................................................................................................... 64
ISM0156-9 Page 4
D5011
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5011 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 92 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 594 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 4.2 mH IIC (A, B) Lo / La = 16.8 mH IIB (C) Lo / La = 33.7 mH IIA (D) Lo / La = 55.2 mH I Lo / La = 16.8 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.9 μH/Ω IIC (A, B) Lo/Ro = 239.7 μH/Ω IIB (C) Lo/Ro = 479.4 μH/Ω IIA (D) Lo/Ro = 786.6 μH/Ω I Lo/Ro = 239.7 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5011 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5011 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
ISM0156-9 Page 5
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5011 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN­Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5011 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5011 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5011 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0124, datasheet and certifications please refer to our website www.gmintsrl.com.
D5014
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 8-11, 10-12. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 8-11, 10-12. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5014 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V
Ui / Vmax
Ch1, Ch2 8-11, 10-12 Uo / Voc = 1.1 V Ch1, Ch2 7-8, 9-10 Io / Isc = 92 mA
Ii / Imax
Ch1, Ch2 8-11, 10-12 Io / Isc = 56 mA Ch1, Ch2 7-8, 9-10 Po / Po = 594 mW
Pi / Pi
Ch1, Ch2 8-11, 10-12 Po / Po = 16 mW
ISM0156-9 Page 6
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 8-11, 10-12
Co / Ca = 100 μF IIC (A, B) Co / Ca = 1000 μF IIB (C) Co / Ca = 1000 μF IIA (D) Co / Ca = 1000 μF I Co / Ca = 1000 μF IIIC (E, F, G)
Ch1, Ch2 7-8, 9-10
Lo / La = 3 mH IIC (A, B) Lo / La = 16.8 mH IIB (C) Lo / La = 33.7 mH IIA (D) Lo / La = 55.2 mH I Lo / La = 16.8 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 8-11, 10-12
Lo / La = 11.3 mH IIC (A, B) Lo / La = 45.3 mH IIB (C) Lo / La = 90.7 mH IIA (D) Lo / La = 151.1 mH I Lo / La = 45.3 mH IIIC (E, F, G)
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.9 μH/Ω IIC (A, B) Lo/Ro = 239.7 μH/Ω IIB (C) Lo/Ro = 479.4 μH/Ω IIA (D) Lo/Ro = 786.6 μH/Ω I Lo/Ro = 239.7 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1, Ch2 8-11, 10-12
Lo/Ro = 2327.2 μH/Ω IIC (A, B) Lo/Ro = 9309 μH/Ω IIB (C) Lo/Ro = 18618.1 μH/Ω IIA (D) Lo/Ro = 30545.4 μH/Ω I Lo/Ro = 9309 μH/Ω IIIC (E, F, G)
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5014 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1, Ch2 8-11, 10-12 Ui / Vmax = 30 V Uo / Voc Ch1, Ch2 8-11, 10-12 Ii / Imax = 128 mA Io / Isc Ch1, Ch2 8-11, 10-12 Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5014 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5014 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
ISM0156-9 Page 7
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5014 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN­Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5014 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5014 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5014 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0103, datasheet and certifications please refer to our website www.gmintsrl.com.
D5020
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 93 mA, Po/Po = 595 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5020 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 93 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 595 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
ISM0156-9 Page 8
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10
Lo / La = 2 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 54.9 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.7 μH/Ω IIC (A, B) Lo/Ro = 239 μH/Ω IIB (C) Lo/Ro = 478.1 μH/Ω IIA (D) Lo/Ro = 784.5 μH/Ω I Lo/Ro = 239 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5020 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5020 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5020 series are isolating driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5020 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5020 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5020 unit must be connected to SELV or SELV-E supplies.
ISM0156-9 Page 9
For the complete instruction manual ISM0118, datasheet and certifications please refer to our website www.gmintsrl.com.
D5030
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5030 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5030 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5030 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
ISM0156-9 Page 10
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5030 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5030 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5030 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5030 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0106, datasheet and certifications please refer to our website www.gmintsrl.com.
D5031
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5031 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device
ISM0156-9 Page 11
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5031 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5031 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5031 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5031 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
ISM0156-9 Page 12
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5031 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5031 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0107, datasheet and certifications please refer to our website www.gmintsrl.com.
D5032
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5032 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
ISM0156-9 Page 13
WARNING
D5032 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5032 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5032 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5032 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output relay contacts checking the load rating to be within the contact maximum rating (100 mA 50 Vac 5 VA, 100 mA 50 Vdc 5 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5032 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5032 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
For the complete instruction manual ISM0108, datasheet and certifications please refer to our website www.gmintsrl.com.
D5034
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 10.5 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
ISM0156-9 Page 14
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5034 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 15 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 39 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 163 mH IIC (A, B) Lo / La = 652 mH IIB (C) Lo / La = 1.3 H IIA (D) Lo / La = 2.14 H I Lo / La = 652 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 918.2 μH/Ω IIC (A, B) Lo/Ro = 3672.9 μH/Ω IIB (C) Lo/Ro = 7345.8 μH/Ω IIA (D) Lo/Ro = 12051.8 μH/Ω I Lo/Ro = 3672.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5034 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5034 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5034 series are switch/proximity interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5034 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant
ISM0156-9 Page 15
national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5034 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5034 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0113, datasheet and certifications please refer to our website www.gmintsrl.com.
D5036
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5036 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635 μH/Ω IIC (A, B) Lo/Ro = 2543 μH/Ω IIB (C) Lo/Ro = 5087 μH/Ω IIA (D) Lo/Ro = 8347 μH/Ω I Lo/Ro = 2543 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
ISM0156-9 Page 16
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5036 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5036 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5036 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5036 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5036 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5036 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0269, datasheet and certifications please refer to our website www.gmintsrl.com.
D5037
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
ISM0156-9 Page 17
IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5037 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635 μH/Ω IIC (A, B) Lo/Ro = 2543 μH/Ω IIB (C) Lo/Ro = 5087 μH/Ω IIA (D) Lo/Ro = 8347 μH/Ω I Lo/Ro = 2543 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5037 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5037 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
ISM0156-9 Page 18
INSTALLATION
D5037 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5037 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5037 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5037 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0270, datasheet and certifications please refer to our website www.gmintsrl.com.
D5040
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.2 V, Io/Isc = 146 mA, Po/Po = 916 mW at terminals 7-8, 10-11 Out A. Uo/Voc = 25.2 V, Io/Isc = 108 mA, Po/Po = 676 mW at terminals 7-9, 10-12 Out B. Uo/Voc = 25.2 V, Io/Isc = 292 mA, Po/Po = 1831 mW at terminals 7//10-8//11 Out A+A. Uo/Voc = 25.2 V, Io/Isc = 216 mA, Po/Po = 1352 mW at terminals 7//10-9//12 Out B+B. Uo/Voc = 25.2 V, Io/Isc = 254 mA, Po/Po = 1592 mW at terminals 7//10-8//12, 7//10-9//11 Out A+B. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 14 ATEX E 159 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 14.0111X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5040 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11
Uo / Voc = 25.2 V Ui / Vmax
Ch1, Ch2 7-9, 10-12
Ch1//2 7//10-8//11 Ch1//2 7//10-9//12
Ch1//2
7//10-8//12,
7//10-9//11
ISM0156-9 Page 19
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11 Io / Isc = 146 mA
Ii / Imax
Ch1, Ch2 7-9, 10-12 Io / Isc = 108 mA
Ch1//2 7//10-8//11 Io / Isc = 292 mA Ch1//2 7//10-9//12 Io / Isc = 216 mA
Ch1//2
7//10-8//12,
7//10-9//11
Io / Isc = 254 mA
Ch1, Ch2 7-8, 10-11 Po / Po = 916 mW
Pi / Pi
Ch1, Ch2 7-9, 10-12 Po / Po = 676 mW
Ch1//2 7//10-8//11 Po / Po = 1831 mW Ch1//2 7//10-9//12 Po / Po = 1352 mW
Ch1//2
7//10-8//12,
7//10-9//11
Po / Po = 1592 mW
Ch1, Ch2 7-8, 10-11 Co / Ca = 107 nF IIC (A, B)
Co / Ca = 820 nF IIB (C) Co / Ca = 2.9 μF IIA (D) Co / Ca = 4.8 μF I Co / Ca = 820 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-9, 10-12
Ch1//2 7//10-8//11
Co / Ca = 820 nF IIB (C) Co / Ca = 2.9 μF IIA (D) Co / Ca = 4.8 μF I Co / Ca = 820 nF IIIC (E, F, G)
Ch1//2 7//10-9//12
Ch1//2
7//10-8//12,
7//10-9//11
Ch1, Ch2 7-8, 10-11
Lo / La = 1.67 mH IIC (A, B) Lo / La = 6.7 mH IIB (C) Lo / La = 13.4 mH IIA (D) Lo / La = 22 mH I Lo / La = 6.7 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-9, 10-12
Lo / La = 3 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 40 mH IIA (D) Lo / La = 12.3 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1//2 7//10-8//11
Lo / La = 1.67 mH IIB (C) Lo / La = 3.3 mH IIA (D) Lo / La = 5.5 mH I Lo / La = 1.67 mH IIIC (E, F, G)
Ch1//2 7//10-9//12
Lo / La = 3 mH IIB (C) Lo / La = 6.1 mH IIA (D) Lo / La = 10.09 mH I Lo / La = 3 mH IIIC (E, F, G)
Ch1//2
7//10-8//12,
7//10-9//11
Lo / La = 2.2 mH IIB (C) Lo / La = 4.4 mH IIA (D) Lo / La = 7.28 mH I Lo / La = 2.2 mH IIIC (E, F, G)
ISM0156-9 Page 20
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11
Lo/Ro = 38.8 μH/Ω IIC (A, B) Lo/Ro = 155.3 μH/Ω IIB (C) Lo/Ro = 310.7 μH/Ω IIA (D) Lo/Ro = 509.8 μH/Ω I Lo/Ro = 155.3 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1, Ch2 7-9, 10-12
Lo/Ro = 52.6 μH/Ω IIC (A, B) Lo/Ro = 210.4 μH/Ω IIB (C) Lo/Ro = 420 μH/Ω IIA (D) Lo/Ro = 690.3 μH/Ω I Lo/Ro = 210.4 μH/Ω IIIC (E, F, G)
Ch1//2 7//10-8//11
Lo/Ro = 77.6 μH/Ω IIB (C) Lo/Ro = 155.3 μH/Ω IIA (D) Lo/Ro = 254.9 μH/Ω I Lo/Ro = 77.6 μH/Ω IIIC (E, F, G)
Ch1//2 7//10-9//12
Lo/Ro = 105.2 μH/Ω IIB (C) Lo/Ro = 210.4 μH/Ω IIA (D) Lo/Ro = 345.1 μH/Ω I Lo/Ro = 105.2 μH/Ω IIIC (E, F, G)
Ch1//2
7//10-8//12,
7//10-9//11
Lo/Ro = 89.3 μH/Ω IIB (C) Lo/Ro = 178.7 μH/Ω IIA (D) Lo/Ro = 293.2 μH/Ω I Lo/Ro = 89.3 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5040 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIB, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5040 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5040 series are digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5040 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of
ISM0156-9 Page 21
protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5040 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
For the complete instruction manual ISM0187, datasheet and certifications please refer to our website www.gmintsrl.com.
D5048
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 7-10 Out A. Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 8-10 Out B. Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 9-10 Out C. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5048 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Uo / Voc = 24.8 V Ui / Vmax
Ch1 8-10 Ch1 9-10 Ch1 7-10 Io / Isc = 147 mA
Ii / Imax
Ch1 8-10 Io / Isc = 108 mA Ch1 9-10 Io / Isc = 93 mA Ch1 7-10 Po / Po = 907 mW
Pi / Pi
Ch1 8-10 Po / Po = 667 mW Ch1 9-10 Po / Po = 571 mW
Ch1 7-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 8-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.32 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 9-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
ISM0156-9 Page 22
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Lo / La = 40 μH IIC (A, B) Lo / La = 6.63 mH IIB (C) Lo / La = 13.27 mH IIA (D) Lo / La = 21.78 mH I Lo / La = 6.63 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 8-10
Lo / La = 1.42 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.35 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1 9-10
Lo / La = 2.54 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 55.09 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Ch1 7-10
Lo/Ro = 39.2 μH/Ω IIC (A, B) Lo/Ro = 156.8 μH/Ω IIB (C) Lo/Ro = 313.6 μH/Ω IIA (D) Lo/Ro = 514.6 μH/Ω I Lo/Ro = 156.8 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 8-10
Lo/Ro = 53.3 μH/Ω IIC (A, B) Lo/Ro = 213.5 μH/Ω IIB (C) Lo/Ro = 427 μH/Ω IIA (D) Lo/Ro = 700.6 μH/Ω I Lo/Ro = 213.5 μH/Ω IIIC (E, F, G)
Ch1 9-10
Lo/Ro = 62.3 μH/Ω IIC (A, B) Lo/Ro = 249.4 μH/Ω IIB (C) Lo/Ro = 498.9 μH/Ω IIA (D) Lo/Ro = 818.5 μH/Ω I Lo/Ro = 249.4 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5048 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5048 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5048 is a digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5048S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks
ISM0156-9 Page 23
which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
NOTE: Use only one output at a time (Out A or Out B or Out C).
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5048 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
For the complete instruction manual ISM0119, datasheet and certifications please refer to our website www.gmintsrl.com.
D5049
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 7-10 Out A. Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 8-10 Out B. Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 9-10 Out C. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5049 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Uo / Voc = 24.8 V Ui / Vmax
Ch1 8-10 Ch1 9-10 Ch1 7-10 Io / Isc = 147 mA
Ii / Imax
Ch1 8-10 Io / Isc = 108 mA Ch1 9-10 Io / Isc = 93 mA Ch1 7-10 Po / Po = 907 mW
Pi / Pi
Ch1 8-10 Po / Po = 667 mW Ch1 9-10 Po / Po = 571 mW
ISM0156-9 Page 24
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 8-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.32 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 9-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 7-10
Lo / La = 40 μH IIC (A, B) Lo / La = 6.63 mH IIB (C) Lo / La = 13.27 mH IIA (D) Lo / La = 21.78 mH I Lo / La = 6.63 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 8-10
Lo / La = 1.42 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.35 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1 9-10
Lo / La = 2.54 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 55.09 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Ch1 7-10
Lo/Ro = 39.2 μH/Ω IIC (A, B) Lo/Ro = 156.8 μH/Ω IIB (C) Lo/Ro = 313.6 μH/Ω IIA (D) Lo/Ro = 514.6 μH/Ω I Lo/Ro = 156.8 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 8-10
Lo/Ro = 53.3 μH/Ω IIC (A, B) Lo/Ro = 213.5 μH/Ω IIB (C) Lo/Ro = 427 μH/Ω IIA (D) Lo/Ro = 700.6 μH/Ω I Lo/Ro = 213.5 μH/Ω IIIC (E, F, G)
Ch1 9-10
Lo/Ro = 62.3 μH/Ω IIC (A, B) Lo/Ro = 249.4 μH/Ω IIB (C) Lo/Ro = 498.9 μH/Ω IIA (D) Lo/Ro = 818.5 μH/Ω I Lo/Ro = 249.4 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5049 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5049 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres -