GMI D5031, D5030, D5032, D5034, D5036 Safety Instructions

...
Page 1
Note: This manual contains only safety instructions.
For the complete installation and user manuals, certifications and data sheets, please refer to www.gmintsrl.com.
D5000 Safety Instruction Manual ISM0156-9
SAFETY INSTRUCTIONS
D5000 series
PSD5000 Series Power Supplies
Page 2
ISM0156-9 Page 2
Page 3
ISM0156-9 Page 3
SUMMARY
D5011 .................................................................................................................. 4
D5014 .................................................................................................................. 5
D5020 .................................................................................................................. 7
D5030 .................................................................................................................. 9
D5031 ................................................................................................................ 10
D5032 ................................................................................................................ 12
D5034 ................................................................................................................ 13
D5036 ................................................................................................................ 15
D5037 ................................................................................................................ 16
D5040 ................................................................................................................ 18
D5048 ................................................................................................................ 21
D5049 ................................................................................................................ 23
D5062 ................................................................................................................ 25
D5072 ................................................................................................................ 27
D5072-087 ......................................................................................................... 29
D5090 ................................................................................................................ 31
D5090-086 ......................................................................................................... 32
D5091 ................................................................................................................ 33
D5093 ................................................................................................................ 34
D5094 ................................................................................................................ 35
D5095 ................................................................................................................ 36
D5096 ................................................................................................................ 37
D5097 ................................................................................................................ 38
D5098 ................................................................................................................ 39
D5202 ................................................................................................................ 40
D5231 ................................................................................................................ 41
D5240 ................................................................................................................ 42
D5244 ................................................................................................................ 49
D5254 ................................................................................................................ 51
D5263 ................................................................................................................ 53
D5264 ................................................................................................................ 55
D5273 ................................................................................................................ 56
D5290 ................................................................................................................ 58
D5290-078 ......................................................................................................... 59
D5291 ................................................................................................................ 60
D5293 ................................................................................................................ 61
D5294 ................................................................................................................ 62
D5295 ................................................................................................................ 63
PSD5201 ........................................................................................................... 64
Page 4
ISM0156-9 Page 4
D5011
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5011 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 92 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 594 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 4.2 mH IIC (A, B) Lo / La = 16.8 mH IIB (C) Lo / La = 33.7 mH IIA (D) Lo / La = 55.2 mH I Lo / La = 16.8 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.9 μH/Ω IIC (A, B) Lo/Ro = 239.7 μH/Ω IIB (C) Lo/Ro = 479.4 μH/Ω IIA (D) Lo/Ro = 786.6 μH/Ω I Lo/Ro = 239.7 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5011 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5011 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Page 5
ISM0156-9 Page 5
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5011 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN­Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5011 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5011 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5011 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0124, datasheet and certifications please refer to our website www.gmintsrl.com.
D5014
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 8-11, 10-12. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 8-11, 10-12. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5014 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V
Ui / Vmax
Ch1, Ch2 8-11, 10-12 Uo / Voc = 1.1 V Ch1, Ch2 7-8, 9-10 Io / Isc = 92 mA
Ii / Imax
Ch1, Ch2 8-11, 10-12 Io / Isc = 56 mA Ch1, Ch2 7-8, 9-10 Po / Po = 594 mW
Pi / Pi
Ch1, Ch2 8-11, 10-12 Po / Po = 16 mW
Page 6
ISM0156-9 Page 6
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 8-11, 10-12
Co / Ca = 100 μF IIC (A, B) Co / Ca = 1000 μF IIB (C) Co / Ca = 1000 μF IIA (D) Co / Ca = 1000 μF I Co / Ca = 1000 μF IIIC (E, F, G)
Ch1, Ch2 7-8, 9-10
Lo / La = 3 mH IIC (A, B) Lo / La = 16.8 mH IIB (C) Lo / La = 33.7 mH IIA (D) Lo / La = 55.2 mH I Lo / La = 16.8 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 8-11, 10-12
Lo / La = 11.3 mH IIC (A, B) Lo / La = 45.3 mH IIB (C) Lo / La = 90.7 mH IIA (D) Lo / La = 151.1 mH I Lo / La = 45.3 mH IIIC (E, F, G)
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.9 μH/Ω IIC (A, B) Lo/Ro = 239.7 μH/Ω IIB (C) Lo/Ro = 479.4 μH/Ω IIA (D) Lo/Ro = 786.6 μH/Ω I Lo/Ro = 239.7 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1, Ch2 8-11, 10-12
Lo/Ro = 2327.2 μH/Ω IIC (A, B) Lo/Ro = 9309 μH/Ω IIB (C) Lo/Ro = 18618.1 μH/Ω IIA (D) Lo/Ro = 30545.4 μH/Ω I Lo/Ro = 9309 μH/Ω IIIC (E, F, G)
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5014 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1, Ch2 8-11, 10-12 Ui / Vmax = 30 V Uo / Voc Ch1, Ch2 8-11, 10-12 Ii / Imax = 128 mA Io / Isc Ch1, Ch2 8-11, 10-12 Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5014 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5014 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Page 7
ISM0156-9 Page 7
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5014 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN­Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5014 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5014 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5014 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0103, datasheet and certifications please refer to our website www.gmintsrl.com.
D5020
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 93 mA, Po/Po = 595 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5020 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 25.9 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 93 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 595 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Page 8
ISM0156-9 Page 8
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10
Lo / La = 2 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 54.9 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 59.7 μH/Ω IIC (A, B) Lo/Ro = 239 μH/Ω IIB (C) Lo/Ro = 478.1 μH/Ω IIA (D) Lo/Ro = 784.5 μH/Ω I Lo/Ro = 239 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5020 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5020 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5020 series are isolating driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5020 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5020 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5020 unit must be connected to SELV or SELV-E supplies.
Page 9
ISM0156-9 Page 9
For the complete instruction manual ISM0118, datasheet and certifications please refer to our website www.gmintsrl.com.
D5030
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5030 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5030 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5030 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
Page 10
ISM0156-9 Page 10
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5030 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5030 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5030 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5030 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0106, datasheet and certifications please refer to our website www.gmintsrl.com.
D5031
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5031 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device
Page 11
ISM0156-9 Page 11
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5031 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5031 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5031 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5031 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
Page 12
ISM0156-9 Page 12
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5031 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5031 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0107, datasheet and certifications please refer to our website www.gmintsrl.com.
D5032
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5032 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635.9 μH/Ω IIC (A, B) Lo/Ro = 2543.9 μH/Ω IIB (C) Lo/Ro = 5087.9 μH/Ω IIA (D) Lo/Ro = 8347.4 μH/Ω I Lo/Ro = 2543.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
Page 13
ISM0156-9 Page 13
WARNING
D5032 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5032 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5032 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5032 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output relay contacts checking the load rating to be within the contact maximum rating (100 mA 50 Vac 5 VA, 100 mA 50 Vdc 5 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5032 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5032 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
For the complete instruction manual ISM0108, datasheet and certifications please refer to our website www.gmintsrl.com.
D5034
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 10.5 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 7-8, 9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
Page 14
ISM0156-9 Page 14
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5034 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 15 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 39 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 163 mH IIC (A, B) Lo / La = 652 mH IIB (C) Lo / La = 1.3 H IIA (D) Lo / La = 2.14 H I Lo / La = 652 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 918.2 μH/Ω IIC (A, B) Lo/Ro = 3672.9 μH/Ω IIB (C) Lo/Ro = 7345.8 μH/Ω IIA (D) Lo/Ro = 12051.8 μH/Ω I Lo/Ro = 3672.9 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5034 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5034 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5034 series are switch/proximity interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5034 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant
Page 15
ISM0156-9 Page 15
national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5034 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5034 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0113, datasheet and certifications please refer to our website www.gmintsrl.com.
D5036
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5036 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635 μH/Ω IIC (A, B) Lo/Ro = 2543 μH/Ω IIB (C) Lo/Ro = 5087 μH/Ω IIA (D) Lo/Ro = 8347 μH/Ω I Lo/Ro = 2543 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
Page 16
ISM0156-9 Page 16
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5036 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5036 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5036 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5036 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5036 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5036 unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0269, datasheet and certifications please refer to our website www.gmintsrl.com.
D5037
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
Page 17
ISM0156-9 Page 17
IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment. Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C Ta 70 °C. Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5037 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 9-10 Uo / Voc = 10.5 V Ui / Vmax Ch1, Ch2 7-8, 9-10 Io / Isc = 22 mA Ii / Imax Ch1, Ch2 7-8, 9-10 Po / Po = 56 mW Pi / Pi
Ch1, Ch2 7-8, 9-10
Co / Ca = 2.4 μF IIC (A, B) Co / Ca = 16.8 μF IIB (C) Co / Ca = 75 μF IIA (D) Co / Ca = 66 μF I Co / Ca = 16.8 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-8, 9-10
Lo / La = 78.3 mH IIC (A, B) Lo / La = 313.4 mH IIB (C) Lo / La = 626.9 mH IIA (D) Lo / La = 1.0286 H I Lo / La = 313.4 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-8, 9-10
Lo/Ro = 635 μH/Ω IIC (A, B) Lo/Ro = 2543 μH/Ω IIB (C) Lo/Ro = 5087 μH/Ω IIA (D) Lo/Ro = 8347 μH/Ω I Lo/Ro = 2543 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5037 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5037 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Page 18
ISM0156-9 Page 18
INSTALLATION
D5037 series are switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5037 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5037 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5037 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0270, datasheet and certifications please refer to our website www.gmintsrl.com.
D5040
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.2 V, Io/Isc = 146 mA, Po/Po = 916 mW at terminals 7-8, 10-11 Out A. Uo/Voc = 25.2 V, Io/Isc = 108 mA, Po/Po = 676 mW at terminals 7-9, 10-12 Out B. Uo/Voc = 25.2 V, Io/Isc = 292 mA, Po/Po = 1831 mW at terminals 7//10-8//11 Out A+A. Uo/Voc = 25.2 V, Io/Isc = 216 mA, Po/Po = 1352 mW at terminals 7//10-9//12 Out B+B. Uo/Voc = 25.2 V, Io/Isc = 254 mA, Po/Po = 1592 mW at terminals 7//10-8//12, 7//10-9//11 Out A+B. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 14 ATEX E 159 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 14.0111X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5040 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11
Uo / Voc = 25.2 V Ui / Vmax
Ch1, Ch2 7-9, 10-12
Ch1//2 7//10-8//11 Ch1//2 7//10-9//12
Ch1//2
7//10-8//12,
7//10-9//11
Page 19
ISM0156-9 Page 19
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11 Io / Isc = 146 mA
Ii / Imax
Ch1, Ch2 7-9, 10-12 Io / Isc = 108 mA
Ch1//2 7//10-8//11 Io / Isc = 292 mA Ch1//2 7//10-9//12 Io / Isc = 216 mA
Ch1//2
7//10-8//12,
7//10-9//11
Io / Isc = 254 mA
Ch1, Ch2 7-8, 10-11 Po / Po = 916 mW
Pi / Pi
Ch1, Ch2 7-9, 10-12 Po / Po = 676 mW
Ch1//2 7//10-8//11 Po / Po = 1831 mW Ch1//2 7//10-9//12 Po / Po = 1352 mW
Ch1//2
7//10-8//12,
7//10-9//11
Po / Po = 1592 mW
Ch1, Ch2 7-8, 10-11 Co / Ca = 107 nF IIC (A, B)
Co / Ca = 820 nF IIB (C) Co / Ca = 2.9 μF IIA (D) Co / Ca = 4.8 μF I Co / Ca = 820 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2 7-9, 10-12
Ch1//2 7//10-8//11
Co / Ca = 820 nF IIB (C) Co / Ca = 2.9 μF IIA (D) Co / Ca = 4.8 μF I Co / Ca = 820 nF IIIC (E, F, G)
Ch1//2 7//10-9//12
Ch1//2
7//10-8//12,
7//10-9//11
Ch1, Ch2 7-8, 10-11
Lo / La = 1.67 mH IIC (A, B) Lo / La = 6.7 mH IIB (C) Lo / La = 13.4 mH IIA (D) Lo / La = 22 mH I Lo / La = 6.7 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2 7-9, 10-12
Lo / La = 3 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 40 mH IIA (D) Lo / La = 12.3 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1//2 7//10-8//11
Lo / La = 1.67 mH IIB (C) Lo / La = 3.3 mH IIA (D) Lo / La = 5.5 mH I Lo / La = 1.67 mH IIIC (E, F, G)
Ch1//2 7//10-9//12
Lo / La = 3 mH IIB (C) Lo / La = 6.1 mH IIA (D) Lo / La = 10.09 mH I Lo / La = 3 mH IIIC (E, F, G)
Ch1//2
7//10-8//12,
7//10-9//11
Lo / La = 2.2 mH IIB (C) Lo / La = 4.4 mH IIA (D) Lo / La = 7.28 mH I Lo / La = 2.2 mH IIIC (E, F, G)
Page 20
ISM0156-9 Page 20
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2 7-8, 10-11
Lo/Ro = 38.8 μH/Ω IIC (A, B) Lo/Ro = 155.3 μH/Ω IIB (C) Lo/Ro = 310.7 μH/Ω IIA (D) Lo/Ro = 509.8 μH/Ω I Lo/Ro = 155.3 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1, Ch2 7-9, 10-12
Lo/Ro = 52.6 μH/Ω IIC (A, B) Lo/Ro = 210.4 μH/Ω IIB (C) Lo/Ro = 420 μH/Ω IIA (D) Lo/Ro = 690.3 μH/Ω I Lo/Ro = 210.4 μH/Ω IIIC (E, F, G)
Ch1//2 7//10-8//11
Lo/Ro = 77.6 μH/Ω IIB (C) Lo/Ro = 155.3 μH/Ω IIA (D) Lo/Ro = 254.9 μH/Ω I Lo/Ro = 77.6 μH/Ω IIIC (E, F, G)
Ch1//2 7//10-9//12
Lo/Ro = 105.2 μH/Ω IIB (C) Lo/Ro = 210.4 μH/Ω IIA (D) Lo/Ro = 345.1 μH/Ω I Lo/Ro = 105.2 μH/Ω IIIC (E, F, G)
Ch1//2
7//10-8//12,
7//10-9//11
Lo/Ro = 89.3 μH/Ω IIB (C) Lo/Ro = 178.7 μH/Ω IIA (D) Lo/Ro = 293.2 μH/Ω I Lo/Ro = 89.3 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5040 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIB, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5040 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5040 series are digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5040 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of
Page 21
ISM0156-9 Page 21
protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5040 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
For the complete instruction manual ISM0187, datasheet and certifications please refer to our website www.gmintsrl.com.
D5048
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 7-10 Out A. Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 8-10 Out B. Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 9-10 Out C. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5048 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Uo / Voc = 24.8 V Ui / Vmax
Ch1 8-10 Ch1 9-10 Ch1 7-10 Io / Isc = 147 mA
Ii / Imax
Ch1 8-10 Io / Isc = 108 mA Ch1 9-10 Io / Isc = 93 mA Ch1 7-10 Po / Po = 907 mW
Pi / Pi
Ch1 8-10 Po / Po = 667 mW Ch1 9-10 Po / Po = 571 mW
Ch1 7-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 8-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.32 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 9-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Page 22
ISM0156-9 Page 22
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Lo / La = 40 μH IIC (A, B) Lo / La = 6.63 mH IIB (C) Lo / La = 13.27 mH IIA (D) Lo / La = 21.78 mH I Lo / La = 6.63 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 8-10
Lo / La = 1.42 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.35 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1 9-10
Lo / La = 2.54 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 55.09 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Ch1 7-10
Lo/Ro = 39.2 μH/Ω IIC (A, B) Lo/Ro = 156.8 μH/Ω IIB (C) Lo/Ro = 313.6 μH/Ω IIA (D) Lo/Ro = 514.6 μH/Ω I Lo/Ro = 156.8 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 8-10
Lo/Ro = 53.3 μH/Ω IIC (A, B) Lo/Ro = 213.5 μH/Ω IIB (C) Lo/Ro = 427 μH/Ω IIA (D) Lo/Ro = 700.6 μH/Ω I Lo/Ro = 213.5 μH/Ω IIIC (E, F, G)
Ch1 9-10
Lo/Ro = 62.3 μH/Ω IIC (A, B) Lo/Ro = 249.4 μH/Ω IIB (C) Lo/Ro = 498.9 μH/Ω IIA (D) Lo/Ro = 818.5 μH/Ω I Lo/Ro = 249.4 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5048 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5048 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5048 is a digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5048S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks
Page 23
ISM0156-9 Page 23
which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
NOTE: Use only one output at a time (Out A or Out B or Out C).
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5048 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
For the complete instruction manual ISM0119, datasheet and certifications please refer to our website www.gmintsrl.com.
D5049
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 7-10 Out A. Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 8-10 Out B. Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 9-10 Out C. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5049 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Uo / Voc = 24.8 V Ui / Vmax
Ch1 8-10 Ch1 9-10 Ch1 7-10 Io / Isc = 147 mA
Ii / Imax
Ch1 8-10 Io / Isc = 108 mA Ch1 9-10 Io / Isc = 93 mA Ch1 7-10 Po / Po = 907 mW
Pi / Pi
Ch1 8-10 Po / Po = 667 mW Ch1 9-10 Po / Po = 571 mW
Page 24
ISM0156-9 Page 24
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 8-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.32 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 9-10
Co / Ca = 113 nF IIC (A, B) Co / Ca = 860 nF IIB (C) Co / Ca = 3.05 μF IIA (D) Co / Ca = 4.35 μF I Co / Ca = 860 nF IIIC (E, F, G)
Ch1 7-10
Lo / La = 40 μH IIC (A, B) Lo / La = 6.63 mH IIB (C) Lo / La = 13.27 mH IIA (D) Lo / La = 21.78 mH I Lo / La = 6.63 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 8-10
Lo / La = 1.42 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.35 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1 9-10
Lo / La = 2.54 mH IIC (A, B) Lo / La = 16.7 mH IIB (C) Lo / La = 33.5 mH IIA (D) Lo / La = 55.09 mH I Lo / La = 16.7 mH IIIC (E, F, G)
Ch1 7-10
Lo/Ro = 39.2 μH/Ω IIC (A, B) Lo/Ro = 156.8 μH/Ω IIB (C) Lo/Ro = 313.6 μH/Ω IIA (D) Lo/Ro = 514.6 μH/Ω I Lo/Ro = 156.8 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 8-10
Lo/Ro = 53.3 μH/Ω IIC (A, B) Lo/Ro = 213.5 μH/Ω IIB (C) Lo/Ro = 427 μH/Ω IIA (D) Lo/Ro = 700.6 μH/Ω I Lo/Ro = 213.5 μH/Ω IIIC (E, F, G)
Ch1 9-10
Lo/Ro = 62.3 μH/Ω IIC (A, B) Lo/Ro = 249.4 μH/Ω IIB (C) Lo/Ro = 498.9 μH/Ω IIA (D) Lo/Ro = 818.5 μH/Ω I Lo/Ro = 249.4 μH/Ω IIIC (E, F, G)
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5049 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5049 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres -
Page 25
ISM0156-9 Page 25
Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5049 is a digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5049S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
NOTE: Use only one output at a time (Out A or Out B or Out C).
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc ( 1.5 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5049 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5049S unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0120, datasheet and certifications please refer to our website www.gmintsrl.com.
D5062
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 27 V, Io/Isc = 90 mA, Po/Po = 576 mW at terminals 7-8, 8-9 (when used with 2 wire constant current supply mode). Uo/Voc = 25.9 V, Io/Isc = 90 mA, Po/Po = 576 mW at terminals 7-10, 9-10 (when used with 3 wires transducer). Uo/Voc = 27 V, Io/Isc = 90 mA, Po/Po = 576 mW at terminals 7-8, 8-9 (when used with 2 wires AC sensor). Ui/Vmax = 30 V, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 7-8, 8-9 (when used with 2 wires AC sensor). Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 14 ATEX E 073 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 14.0044X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5062 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device
Page 26
ISM0156-9 Page 26
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7/9-10 Uo / Voc = 25.9 V
Ui / Vmax
Ch1 7/9-8
Uo / Voc = 27 V
Ch1 7/9-8 Ch1 7/9-10
Io / Isc = 90 mA Ii / Imax
Ch1 7/9-8 Ch1 7/9-8 Ch1 7/9-10
Po / Po = 576 mW Pi / Pi
Ch1 7/9-8 Ch1 7/9-8
Ch1 7/9-10
Co / Ca = 100 nF IIC (A, B) Co / Ca = 770 nF IIB (C) Co / Ca = 2.63 μF IIA (D) Co / Ca = 4.02 μF I Co / Ca = 770 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 7/9-8 Co / Ca = 90 nF IIC (A, B)
Co / Ca = 705 nF IIB (C) Co / Ca = 2.3 μF IIA (D) Co / Ca = 3.75 μF I Co / Ca = 705 nF IIIC (E, F, G)
Ch1 7/9-8
Ch1 7/9-10
Lo / La = 4.4 mH IIC (A, B) Lo / La = 17.9 mH IIB (C) Lo / La = 35.8 mH IIA (D) Lo / La = 58.7 mH I Lo / La = 17.9 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 7/9-8 Lo / La = 4.1 mH IIC (A, B)
Lo / La = 16.4 mH IIB (C) Lo / La = 33.9 mH IIA (D) Lo / La = 54 mH I Lo / La = 16.4 mH IIIC (E, F, G)
Ch1 7/9-8
Ch1 7/9-10
Lo/Ro = 61.7 μH/Ω IIC (A, B) Lo/Ro = 247.1 μH/Ω IIB (C) Lo/Ro = 494.3 μH/Ω IIA (D) Lo/Ro = 811 μH/Ω I Lo/Ro = 247.1 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 7/9-8 Lo/Ro = 56.8 μH/Ω IIC (A, B)
Lo/Ro = 227.3 μH/Ω IIB (C) Lo/Ro = 459.7 μH/Ω IIA (D) Lo/Ro = 746.1 μH/Ω I Lo/Ro = 227.3 μH/Ω IIIC (E, F, G)
Ch1 7/9-8
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5062 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1 7/9-8 Ui / Vmax = 30 V Uo / Voc Ch1 7/9-8 Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5062 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of
Page 27
ISM0156-9 Page 27
250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5062 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5062 is a vibration transducer interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5062S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5062 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5062S unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0184, datasheet and certifications please refer to our website www.gmintsrl.com.
D5072
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 7.2 V, Io/Isc = 23 mA, Po/Po = 40 mW at terminals 7-8-9-10 (only for D5072S). Uo/Voc = 7.2 V, Io/Isc = 16 mA, Po/Po = 27 mW at terminals 7-8-9, 10-11-12 (only for D5072D). Ui/Vmax = 12.8 V, Ii/Imax = 28.7 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 7-8-9-10 (only for D5072S). Ui/Vmax = 12.8 V, Ii/Imax = 28.7 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 7-8-9, 10-11-12 (only for D5072D). Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 12 ATEX E 053 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 12.0050X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5072 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device
Page 28
ISM0156-9 Page 28
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
D5072S Ch1: 7-8-9-10
Uo / Voc = 7.2 V Ui / Vmax
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
D5072S Ch1: 7-8-9-10 Io / Isc = 23 mA
Ii / Imax
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
Io / Isc = 16 mA
D5072S Ch1: 7-8-9-10 Po / Po = 40 mW
Pi / Pi
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
Po / Po = 27 mW
D5072S Ch1: 7-8-9-10
Co / Ca = 13.5 μF IIC (A, B) Co / Ca = 240 μF IIB (C) Co / Ca = 1000 μF IIA (D) Co / Ca = 1000 μF I Co / Ca = 240 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
D5072S Ch1: 7-8-9-10
Lo / La = 67.2 mH IIC (A, B) Lo / La = 268 mH IIB (C) Lo / La = 537 mH IIA (D) Lo / La = 882 mH I Lo / La = 268 mH IIIC (E, F, G)
Li / Li device
+ L cable
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
Lo / La = 138 mH IIC (A, B) Lo / La = 555 mH IIB (C) Lo / La = 1.111 H IIA (D) Lo / La = 1.822 H I Lo / La = 555 mH IIIC (E, F, G)
D5072S Ch1: 7-8-9-10
Lo/Ro = 875 μH/Ω IIC (A, B) Lo/Ro = 3500 μH/Ω IIB (C) Lo/Ro = 7000 μH/Ω IIA (D) Lo/Ro = 11480 μH/Ω I Lo/Ro = 3500 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
Lo/Ro = 1290 μH/Ω IIC (A, B) Lo/Ro = 5160 μH/Ω IIB (C) Lo/Ro = 10330 μH/Ω IIA (D) Lo/Ro = 16950 μH/Ω I Lo/Ro = 5160 μH/Ω IIIC (E, F, G)
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5072 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
D5072S Ch1: 7-8-9-10
Ui / Vmax = 12.8 V Uo / Voc
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
D5072S Ch1: 7-8-9-10
Ii / Imax = 28.7 mA Io / Isc
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
D5072S Ch1: 7-8-9-10
Ci = 0 μF, Li = 0 mH
D5072D
Ch1, Ch2: 7-8-9,
10-11-12
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5072 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified
Page 29
ISM0156-9 Page 29
operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5072 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5072 series are temperature signal converter housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5072 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect alarm transistors checking the load rating to be within the maximum rating (100 mA at 60 Vdc ( 1 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5072 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5072 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0156, datasheet and certifications please refer to our website www.gmintsrl.com.
D5072-087
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 7.2 V, Io/Isc = 23 mA, Po/Po = 40 mW at terminals 7-8-9-10. Ui/Vmax = 12.8 V, Ii/Imax = 28.7 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 7-8-9-10. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 12 ATEX E 053 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 12.0050X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5072-087 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device
Page 30
ISM0156-9 Page 30
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 7-8-9-10 Uo / Voc = 7.2 V Ui / Vmax Ch1 7-8-9-10 Io / Isc = 23 mA Ii / Imax Ch1 7-8-9-10 Po / Po = 40 mW Pi / Pi
Ch1 7-8-9-10
Co / Ca = 13.5 μF IIC (A, B) Co / Ca = 240 μF IIB (C) Co / Ca = 1000 μF IIA (D) Co / Ca = 1000 μF I Co / Ca = 240 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 7-8-9-10
Lo / La = 67 mH IIC (A, B) Lo / La = 268 mH IIB (C) Lo / La = 537 mH IIA (D) Lo / La = 882 mH I Lo / La = 268 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 7-8-9-10
Lo/Ro = 875 μH/Ω IIC (A, B) Lo/Ro = 3500 μH/Ω IIB (C) Lo/Ro = 7000 μH/Ω IIA (D) Lo/Ro = 11480 μH/Ω I Lo/Ro = 3500 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5072-087 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1 7-8-9-10 Ui / Vmax = 12.8 V Uo / Voc Ch1 7-8-9-10 Ii / Imax = 28.7 mA Io / Isc Ch1 7-8-9-10 Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5072-087 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5072-087 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5072-087 is a resistance isolating repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5072S-087 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
Page 31
ISM0156-9 Page 31
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5072-087 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5072S-087 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0178, datasheet and certifications please refer to our website www.gmintsrl.com.
D5090
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5090 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5090 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5090 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5090S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
Page 32
ISM0156-9 Page 32
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5090 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0109, datasheet and certifications please refer to our website www.gmintsrl.com.
D5090-086
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5090-086 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5090-086 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5090-086 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5090S-086 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific
Page 33
ISM0156-9 Page 33
installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5090-086 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0267, datasheet and certifications please refer to our website www.gmintsrl.com.
D5091
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5091 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5091 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5091 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5091S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Page 34
ISM0156-9 Page 34
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5091 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0110, datasheet and certifications please refer to our website www.gmintsrl.com.
D5093
SAFETY DESCRIPTION
ATEX: II 3G Ex nA IIC T4 Gc IECEx: Ex nA IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5093 series are electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5093 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5093 series are 24 to 220 vac/vdc switch repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5093 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (50 mA at 35 Vdc ( 1 Vdc voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5093 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
Page 35
ISM0156-9 Page 35
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0175, datasheet and certifications please refer to our website www.gmintsrl.com.
D5094
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
WARNING
D5094 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5094 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5094 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5094S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5094 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
Page 36
ISM0156-9 Page 36
For the complete instruction manual ISM0299, datasheet and certifications please refer to our website www.gmintsrl.com.
D5095
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
WARNING
D5095 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5095 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5095 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5095S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5095 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0300, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 37
ISM0156-9 Page 37
D5096
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
WARNING
D5096 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5096 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5096 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5096S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 V ( 1.0 V voltage drop)). The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA
Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5096 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0301, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 38
ISM0156-9 Page 38
D5097
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
WARNING
D5097 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5097 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5097 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5097S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
Connect fault transistors checking the load rating to be within the maximum rating (100 mA at 35 V ( 1.0 V voltage drop)). The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA
Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5097 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0302, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 39
ISM0156-9 Page 39
D5098
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
IMQ 17 ATEX 009 X conforms to EN60079-0, EN60079-15. IECEx IMQ 17.0006X conforms to IEC60079-0, IEC60079-15.
WARNING
D5098 series are electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5098 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5098 series are relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5098 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5098 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0305, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 40
ISM0156-9 Page 40
D5202
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 14 ATEX E 031 X conforms to EN60079-0, EN60079-15. IECEx BVS 14.0025X conforms to IEC60079-0, IEC60079-15.
WARNING
D5202 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C.
D5202 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5202 is a power distribution and diagnostic module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5202S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect fault relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5202 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5202S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0177, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 41
ISM0156-9 Page 41
D5231
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 11.2 V, Io/Isc = 12 mA, Po/Po = 34 mW at terminals 21-13, 21-14, 22-15, 22-16, 23-17, 23-18, 24-19, 24-20. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 12 ATEX E 122 X conforms to EN60079-0, EN60079-11, EN60079-15, EN60079-26, EN50303.
IECEx BVS 12.0090X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5231 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Uo / Voc = 11.2 V Ui / Vmax
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Io / Isc = 12 mA Ii / Imax
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Po / Po = 34 mW Pi / Pi
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Co / Ca = 1.83 μF IIC (A, B) Co / Ca = 12.6 μF IIB (C) Co / Ca = 54 μF IIA (D) Co / Ca = 58 μF I Co / Ca = 12.6 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Lo / La = 246 mH IIC (
A
, B) Lo / La = 987 mH IIB (C) Lo / La = 1.9 H IIA (D) Lo / La = 3.2 H I Lo / La = 987 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2, Ch3, Ch4, Ch5, Ch6,
Ch7, Ch8
21-13, 21-14, 22-15, 22-16, 23-17, 23-18,
24-19, 24-20
Lo/Ro = 1070 μH/Ω IIC (A, B) Lo/Ro = 4280 μH/Ω IIB (C) Lo/Ro = 8550 μH/Ω IIA (D) Lo/Ro = 14030 μH/Ω I Lo/Ro = 4280 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5231 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
Page 42
ISM0156-9 Page 42
D5231 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5231 is a switch/proximity detector repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5231E unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect output transistors checking the load rating to be within the maximum rating (100 mA at 35 V ( 1.0 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5231 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5231E unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0172, datasheet and certifications please refer to our website www.gmintsrl.com.
D5240
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.2 V, Io/Isc = 146 mA, Po/Po = 916 mW at terminals 13-14, 17-18, 21-22 Out A. Uo/Voc = 25.2 V, Io/Isc = 108 mA, Po/Po = 676 mW at terminals 13-15, 17-19, 21-23 Out B. Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 580 mW at terminals 13-16, 17-20, 21-24 Out C. Uo/Voc = 25.2 V, Io/Isc = 185 mA, Po/Po = 1160 mW at terminals 13//17-16//20, 13//21-16//24, 17//21-20//24 Out C+C. Uo/Voc = 25.2 V, Io/Isc = 216 mA, Po/Po = 1352 mW at terminals 13//17-15//19, 13//21-15//23, 17//21-19//23 Out B+B. Uo/Voc = 25.2 V, Io/Isc = 238 mA, Po/Po = 1496 mW at terminals 13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21­18//24, 21//13-22//16, 21//17-22//20 Out A+C. Uo/Voc = 25.2 V, Io/Isc = 277 mA, Po/Po = 1740 mW at terminals 13//17//21-16//20//24 Out C+C+C. Uo/Voc = 25.2 V, Io/Isc = 323 mA, Po/Po = 2028 mW at terminals 13//17//21-15//19//23 Out B+B+B. Uo/Voc = 25.2 V, Io/Isc = 361 mA, Po/Po = 2138 mW at terminals 13//17//21-14//19//23, 17//13//21-18//15//23, 21//13//17­22//15//19 Out A+B+B. Uo/Voc = 25.2 V, Io/Isc = 384 mA, Po/Po = 2138 mW at terminals 13//17//21-14//18//24, 13//21//17-14//22//20, 17//21//13­18//22//16 Out A+A+C. Uo/Voc = 25.2 V, Io/Isc = 437 mA, Po/Po = 2138 mW at terminals 13//17//21-14//18//22 Out A+A+A. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals:
Page 43
ISM0156-9 Page 43
BVS 14 ATEX E 159 X conforms to EN60079-0, EN60079-11, EN60079-15. IECEx BVS 14.0111X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5240 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22
Uo / Voc = 25.2 V Ui / Vmax
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Ch1//2//3
13//17//21,
16//20//24
Ch1//2//3
13//17//21,
15//19//23
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Ch1//2//3
13//17//21,
14//18//22
Page 44
ISM0156-9 Page 44
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22 Io / Isc = 146 mA
Ii / Imax
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23 Io / Isc = 108 mA
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24 Io / Isc = 93 mA
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Io / Isc = 185 mA
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Io / Isc = 216 mA
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Io / Isc = 238 mA
Ch1//2//3
13//17//21,
16//20//24
Io / Isc = 277 mA
Ch1//2//3
13//17//21,
15//19//23
Io / Isc = 323 mA
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Io / Isc = 361 mA
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Io / Isc = 384 mA
Ch1//2//3
13//17//21,
14//18//22
Io / Isc = 437 mA
Page 45
ISM0156-9 Page 45
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22 Po / Po = 916 mW
Pi / Pi
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23 Po / Po = 676 mW
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24 Po / Po = 580 mW
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Po / Po = 1160 mW
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Po / Po = 1352 mW
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Po / Po = 1496 mW
Ch1//2//3
13//17//21,
16//20//24
Po / Po = 1740 mW
Ch1//2//3
13//17//21,
15//19//23
Po / Po = 2028 mW
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Po / Po = 2138 mW
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Ch1//2//3
13//17//21,
14//18//22
Page 46
ISM0156-9 Page 46
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22
Co / Ca = 96 nF IIC (A, B) Co / Ca = 809 nF IIB (C) Co / Ca = 2.8 μF IIA (D) Co / Ca = 4.78 μF I Co / Ca = 809 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Co / Ca = 798 nF IIB (C) Co / Ca = 2.8 μF IIA (D) Co / Ca = 4.77 μF I Co / Ca = 798 nF IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Ch1//2//3
13//17//21,
16//20//24
Co / Ca = 787 nF IIB (C) Co / Ca = 2.8 μF IIA (D) Co / Ca = 4.76 μF I Co / Ca = 787 nF IIIC (E, F, G)
Ch1//2//3
13//17//21,
15//19//23
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Co / Ca = 2.8 μF IIA (D) Co / Ca = 4.76 μF I
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Ch1//2//3
13//17//21,
14//18//22
Page 47
ISM0156-9 Page 47
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22
Lo / La = 1.67 mH IIC (A, B) Lo / La = 6.7 mH IIB (C) Lo / La = 13.4 mH IIA (D) Lo / La = 22 mH I Lo / La = 6.7 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23
Lo / La = 3 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.37 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24
Lo / La = 3.07 mH IIC (A, B) Lo / La = 12.3 mH IIB (C) Lo / La = 24.6 mH IIA (D) Lo / La = 40.37 mH I Lo / La = 12.3 mH IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Lo / La = 4.1 mH IIB (C) Lo / La = 8.3 mH IIA (D) Lo / La = 13.72 mH I Lo / La = 4.1 mH IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Lo / La = 3 mH IIB (C) Lo / La = 6.1 mH IIA (D) Lo / La = 10.09 mH I Lo / La = 3 mH IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Lo / La = 2.5 mH IIB (C) Lo / La = 5 mH IIA (D) Lo / La = 8.25 mH I Lo / La = 2.5 mH IIIC (E, F, G)
Ch1//2//3
13//17//21,
16//20//24
Lo / La = 1.85 mH IIB (C) Lo / La = 3.71 mH IIA (D) Lo / La = 6.09 mH I Lo / La = 1.85 mH IIIC (E, F, G)
Ch1//2//3
13//17//21,
15//19//23
Lo / La = 1.36 mH IIB (C) Lo / La = 2.73 mH IIA (D) Lo / La = 4.48 mH I Lo / La = 1.36 mH IIIC (E, F, G)
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Lo / La = 2.1 mH IIA (D) Lo / La = 3.58 mH I
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Lo / La = 1.9 mH IIA (D) Lo / La = 3.17 mH I
Ch1//2//3
13//17//21,
14//18//22
Lo / La = 1.49 mH IIA (D) Lo / La = 2.44 mH I
Page 48
ISM0156-9 Page 48
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2,
Ch3
13-14, 17-18, 21-22
Lo/Ro = 38.8 μH/Ω IIC (A, B) Lo/Ro = 155.3 μH/Ω IIB (C) Lo/Ro = 310.7 μH/Ω IIA (D) Lo/Ro = 509.8 μH/Ω I Lo/Ro = 155.3 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1, Ch2,
Ch3
13-15, 17-19, 21-23
Lo/Ro = 52.6 μH/Ω IIC (A, B) Lo/Ro = 210.4 μH/Ω IIB (C) Lo/Ro = 420 μH/Ω IIA (D) Lo/Ro = 690.3 μH/Ω I Lo/Ro = 210.4 μH/Ω IIIC (E, F, G)
Ch1, Ch2,
Ch3
13-16, 17-20, 21-24
Lo/Ro = 61.3 μH/Ω IIC (A, B) Lo/Ro = 245.3 μH/Ω IIB (C) Lo/Ro = 490.6 μH/Ω IIA (D) Lo/Ro = 804.9 μH/Ω I Lo/Ro = 245.3 μH/Ω IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-16//20, 13//21-16//24,
17//21-20//24
Lo/Ro = 122.6 μH/Ω IIB (C) Lo/Ro = 245.3 μH/Ω IIA (D) Lo/Ro = 402.4 μH/Ω I Lo/Ro = 122.6 μH/Ω IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-15//19, 13//21-15//23,
17//21-19//23
Lo/Ro = 105.2 μH/Ω IIB (C) Lo/Ro = 210.4 μH/Ω IIA (D) Lo/Ro = 345.1 μH/Ω I Lo/Ro = 105.2 μH/Ω IIIC (E, F, G)
Ch1//2, Ch2//3,
Ch1//3
13//17-14//20, 13//21-14//24, 17//13-18//16, 17//21-18//24, 21//13-22//16,
21//17-22//20
Lo/Ro = 95.1 μH/Ω IIB (C) Lo/Ro = 190.2 μH/Ω IIA (D) Lo/Ro = 312.1 μH/Ω I Lo/Ro = 95.1 μH/Ω IIIC (E, F, G)
Ch1//2//3
13//17//21,
16//20//24
Lo/Ro = 81.7 μH/Ω IIB (C) Lo/Ro = 163.5 μH/Ω IIA (D) Lo/Ro = 268.3 μH/Ω I Lo/Ro = 81.7 μH/Ω IIIC (E, F, G)
Ch1//2//3
13//17//21,
15//19//23
Lo/Ro = 70.1 μH/Ω IIB (C) Lo/Ro = 140.2 μH/Ω IIA (D) Lo/Ro = 230.1 μH/Ω I Lo/Ro = 70.1 μH/Ω IIIC (E, F, G)
Ch1//2//3
13//17//21, 14//19//23, 17//13//21, 18//15//23, 21//13//17,
22//15//19
Lo/Ro = 125.4 μH/Ω IIA (D) Lo/Ro = 205.8 μH/Ω I Lo/Ro = 62.7 μH/Ω IIIC (E, F, G)
Ch1//2//3
13//17//21, 14//18//24, 13//21//17, 14//22//20, 17//21//13,
18//22//16
Lo/Ro = 118 μH/Ω IIA (D) Lo/Ro = 193.6 μH/Ω I Lo/Ro = 59 μH/Ω IIIC (E, F, G)
Ch1//2//3
13//17//21,
14//18//22
Lo/Ro = 103.5 μH/Ω IIA (D) Lo/Ro = 169.9 μH/Ω I
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
Page 49
ISM0156-9 Page 49
WARNING
D5240 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIA, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5240 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5240 is a digital output driver housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5240T unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5240 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5240T unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0209, datasheet and certifications please refer to our website www.gmintsrl.com.
D5244
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 0 mV, Io/Isc = 0 μA, Po/Po = 0 μW at terminals 13-14-15/16, 17-18-19/20.
Ui/Vmax = 40 V, Ii/Imax = 2 A, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 13-14-15/16, 17-18-19/20. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 16 ATEX E 109 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 16.0071X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations
Page 50
ISM0156-9 Page 50
and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5244 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1, Ch2
13-14-15/16,
17-18-19/20
Uo / Voc = 0 V Ui / Vmax
Ch1, Ch2
13-14-15/16,
17-18-19/20
Io / Isc = 0 mA Ii / Imax
Ch1, Ch2
13-14-15/16,
17-18-19/20
Po / Po = 0 mW Pi / Pi
Ch1, Ch2
13-14-15/16,
17-18-19/20
Co / Ca = - IIC (A, B) Co / Ca = - IIB (C) Co / Ca = - IIA (D) Co / Ca = - I Co / Ca = - IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1, Ch2
13-14-15/16,
17-18-19/20
Lo / La = - IIC (A, B) Lo / La = - IIB (C) Lo / La = - IIA (D) Lo / La = - I Lo / La = - IIIC (E, F, G)
Li / Li device
+ L cable
Ch1, Ch2
13-14-15/16,
17-18-19/20
Lo/Ro = - IIC (A, B) Lo/Ro = - IIB (C) Lo/Ro = - IIA (D) Lo/Ro = - I Lo/Ro = - IIIC (E, F, G)
Li/Ri device
and L cable/R cable
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5244 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1, Ch2
13-14-15/16,
17-18-19/20
Ui / Vmax = 40 V Uo / Voc
Ch1, Ch2
13-14-15/16,
17-18-19/20
Ii / Imax = 2 A Io / Isc
Ch1, Ch2
13-14-15/16,
17-18-19/20
Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5244 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5244 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Page 51
ISM0156-9 Page 51
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5244 series are digital relay output loop powered housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5244 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (40 Vdc, 2 A for use in Intrinsic Safety applications, 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W, resistive load, for non Intrinsic Safety applications).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5244 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM271, datasheet and certifications please refer to our website www.gmintsrl.com.
D5254
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 26 V, Io/Isc = 91 mA, Po/Po = 588 mW at terminals 13-14.
Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 14-16. Uo/Voc = 1.1 V, Io/Isc = 12 μA, Po/Po = 4 μW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci/Ci = 2.1 nF, Li/Li = 0 mH, at terminals 14-16. Ui/Vmax = 30 V, Ci/Ci = 2.1 nF, Li/Li = 0 mH, at terminals 15-16. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 16 ATEX E 066 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 16.0043X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5254 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Page 52
ISM0156-9 Page 52
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13-14 Uo / Voc = 26 V
Ui / Vmax
Ch1 14-16
Uo / Voc = 1.1 V
Ch1 15-16 Ch1 13-14 Io / Isc = 91 mA
Ii / Imax
Ch1 14-16 Io / Isc = 56 mA Ch1 15-16 Io / Isc = 12 μA Ch1 13-14 Po / Po = 588 mW
Pi / Pi
Ch1 14-16 Po / Po = 16 mW Ch1 15-16 Po / Po = 4 μW
Ch1 13-14
Co / Ca = 96 nF IIC (A, B) Co / Ca = 767 nF IIB (C) Co / Ca = 2.597 μF IIA (D) Co / Ca = 4.497 μF I Co / Ca = 767 nF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 14-16 Co / Ca = - IIC (A, B)
Co / Ca = - IIB (C) Co / Ca = - IIA (D) Co / Ca = - I Co / Ca = - IIIC (E, F, G)
Ch1 15-16
Ch1 13-14
Lo / La = 4.34 mH IIC (A, B) Lo / La = 17.36 mH IIB (C) Lo / La = 34.72 mH IIA (D) Lo / La = 56.96 mH I Lo / La = 17.36 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 14-16 Lo / La = - IIC (A, B)
Lo / La = - IIB (C) Lo / La = - IIA (D) Lo / La = - I Lo / La = - IIIC (E, F, G)
Ch1 15-16
Ch1 13-14
Lo/Ro = 0 μH/Ω IIC (A, B) Lo/Ro = 242.2 μH/Ω IIB (C) Lo/Ro = 484.4 μH/Ω IIA (D) Lo/Ro = 794.7 μH/Ω I Lo/Ro = 242.2 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
Ch1 14-16 Lo/Ro = - IIC (A, B)
Lo/Ro = - IIB (C) Lo/Ro = - IIA (D) Lo/Ro = - I Lo/Ro = - IIIC (E, F, G)
Ch1 15-16
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5254 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1 14-16
Ui / Vmax = 30 V Uo / Voc
Ch1 15-16 Ch1 14-16 Ii / Imax = 128 mA Io / Isc Ch1 14-16
Ci = 2.1 μF, Li = 0 mH
Ch1 15-16
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5254 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating
Page 53
ISM0156-9 Page 53
temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5254 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5254 is a repeater power supply / analog signal converter and trip amplifiers housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5254S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect alarm relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5254 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5254S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0293, datasheet and certifications please refer to our website www.gmintsrl.com.
D5263
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 7.2 V, Io/Isc = 177 mA, Po/Po = 471 mW at terminals 13-14-15-16-17-18. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: TUV 15 ATEX 170897 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx TUN 16.0005X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
Page 54
ISM0156-9 Page 54
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5263 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13-14-15-16-17-18 Uo / Voc = 7.2 V Ui / Vmax Ch1 13-14-15-16-17-18 Io / Isc = 177 mA Ii / Imax Ch1 13-14-15-16-17-18 Po / Po = 471 mW Pi / Pi
Ch1 13-14-15-16-17-18
Co / Ca = 300 nF IIC (A, B) Co / Ca = 1.5 μF IIB (C) Co / Ca = 2.2 μF IIA (D) Co / Ca = 2.8 μF I Co / Ca = 1.5 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 13-14-15-16-17-18
Lo / La = 500 μH IIC (A, B) Lo / La = 6.5 mH IIB (C) Lo / La = 9.5 mH IIA (D) Lo / La = 13 mH I Lo / La = 6.5 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 13-14-15-16-17-18
Lo/Ro = - IIC (A, B) Lo/Ro = - IIB (C) Lo/Ro = - IIA (D) Lo/Ro = - I Lo/Ro = - IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5263 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5263 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5263 is a load cell/strain gauge bridge isolating repeater housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5263S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant
Page 55
ISM0156-9 Page 55
national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5263 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5263S unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0227, datasheet and certifications please refer to our website www.gmintsrl.com.
D5264
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 7.2 V, Io/Isc = 177 mA, Po/Po = 471 mW at terminals 13-14-15-16-17-18. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: TUV 15 ATEX 170897 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx TUN 16.0005X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5264 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13-14-15-16-17-18 Uo / Voc = 7.2 V Ui / Vmax Ch1 13-14-15-16-17-18 Io / Isc = 177 mA Ii / Imax Ch1 13-14-15-16-17-18 Po / Po = 471 mW Pi / Pi
Ch1 13-14-15-16-17-18
Co / Ca = 300 nF IIC (A, B) Co / Ca = 1.5 μF IIB (C) Co / Ca = 2.2 μF IIA (D) Co / Ca = 2.8 μF I Co / Ca = 1.5 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 13-14-15-16-17-18
Lo / La = 500 μH IIC (A, B) Lo / La = 6.5 mH IIB (C) Lo / La = 9.5 mH IIA (D) Lo / La = 13 mH I Lo / La = 6.5 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 13-14-15-16-17-18
Lo/Ro = - IIC (A, B) Lo/Ro = - IIB (C) Lo/Ro = - IIA (D) Lo/Ro = - I Lo/Ro = - IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable)
Page 56
ISM0156-9 Page 56
shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5264 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5264 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5264 is a load cell/strain gauge bridge isolating converter housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5264S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect alarm transistors checking the load rating to be within the maximum rating (100 mA at 60 V ( 1.0 V voltage drop)).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5264 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5264S unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0228, datasheet and certifications please refer to our website www.gmintsrl.com.
D5273
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA nC [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical
equipment. Uo/Voc = 7.2 V, Io/Isc = 23 mA, Po/Po = 40 mW at terminals 13-14-15-16.
Ui/Vmax = 12.8 V, Ii/Imax = 28.7 mA, Ci/Ci = 0 nF, Li/Li = 0 mH, at terminals 13-14-15-16. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 12 ATEX E 053 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 12.0050X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26.
Page 57
ISM0156-9 Page 57
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5273 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13-14-15-16 Uo / Voc = 7.2 V Ui / Vmax Ch1 13-14-15-16 Io / Isc = 23 mA Ii / Imax Ch1 13-14-15-16 Po / Po = 40 mW Pi / Pi
Ch1 13-14-15-16
Co / Ca = 13.5 μF IIC (A, B) Co / Ca = 240 μF IIB (C) Co / Ca = 1000 μF IIA (D) Co / Ca = 1000 μF I Co / Ca = 240 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 13-14-15-16
Lo / La = 67.2 mH IIC (A, B) Lo / La = 268 mH IIB (C) Lo / La = 537 mH IIA (D) Lo / La = 882 mH I Lo / La = 268 mH IIIC (E, F, G)
Li / Li device
+ L cable
Ch1 13-14-15-16
Lo/Ro = 875 μH/Ω IIC (A, B) Lo/Ro = 3500 μH/Ω IIB (C) Lo/Ro = 7000 μH/Ω IIA (D) Lo/Ro = 11480 μH/Ω I Lo/Ro = 3500 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5273 series Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
Ch1 13-14-15-16 Ui / Vmax = 12.8 V Uo / Voc Ch1 13-14-15-16 Ii / Imax = 28.7 mA Io / Isc Ch1 13-14-15-16 Ci = 0 μF, Li = 0 mH
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB and 600 nF for Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
D5273 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5273 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Page 58
ISM0156-9 Page 58
INSTALLATION
D5273 is a temperature signal converter housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus. D5273S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect alarm relay contacts checking the load rating to be within the contact maximum rating (4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5273 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5273S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
For the complete instruction manual ISM0209, datasheet and certifications please refer to our website www.gmintsrl.com.
D5290
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5290 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5290 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5290 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board.
Page 59
ISM0156-9 Page 59
D5290S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (10 A 250 Vac 2500 VA, 10 A 250 Vdc 300 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5290 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0111, datasheet and certifications please refer to our website www.gmintsrl.com.
D5290-078
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5290-078 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5290-078 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5290-078 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5290S-078 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks
Page 60
ISM0156-9 Page 60
which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 175 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5290-078 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0152, datasheet and certifications please refer to our website www.gmintsrl.com.
D5291
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5291 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5291 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5291 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022 or on customized Termination Board. D5291S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
Page 61
ISM0156-9 Page 61
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (10 A 250 Vac 2500 VA, 10 A 250 Vdc 300 W resistive load).
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5291 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0151, datasheet and certifications please refer to our website www.gmintsrl.com.
D5293
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5293 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5293 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5293 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5293S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas
Page 62
ISM0156-9 Page 62
(other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).Connect fault relay contacts checking the load rating to be within the contact maximum rating (500 mA 30 Vac 15 VA, 500 mA 50 Vdc 25 W resistive load - 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W resistive load).
To prevent relays contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5293 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5293S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0122, datasheet and certifications please refer to our website www.gmintsrl.com.
D5294
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5294 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5294 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5294 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5294S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas
Page 63
ISM0156-9 Page 63
(other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).Connect fault relay contacts checking the load rating to be within the contact maximum rating (500 mA 30 Vac 15 VA, 500 mA 50 Vdc 25 W resistive load - 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W resistive load).
To prevent relays contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5294 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5294S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0123, datasheet and certifications please refer to our website www.gmintsrl.com.
D5295
SAFETY DESCRIPTION
ATEX: II 3G Ex nA nC IIC T4 Gc IECEx: Ex nA nC IIC T4 Gc, non-sparking electrical equipment. Approvals:
BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15.
WARNING
D5295 is electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +60 °C.
D5295 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
D5295 is a relay output module housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. D5295S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas
Page 64
ISM0156-9 Page 64
(other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).Connect fault relay contacts checking the load rating to be within the contact maximum rating (500 mA 30 Vac 15 VA, 500 mA 50 Vdc 25 W resistive load - 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W resistive load).
To prevent relays contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5295 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5295S unit must be connected to SELV or SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
For the complete instruction manual ISM0222, datasheet and certifications please refer to our website www.gmintsrl.com.
PSD5201
SAFETY DESCRIPTION
ATEX: II 3(1)G Ex nA [ia Ga] IIB T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I IECEx: Ex nA [ia Ga] IIB T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, associated apparatus and non-sparking electrical equipment.
Uo/Voc = 21.5 V, Io/Isc = 604 mA, Po/Po = 3243 mW at terminals 13/15-14/16. Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals: BVS 14 ATEX E 023 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 14.0019X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
PARAMETERS TABLE
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the PSD5201 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters indicated in the table below:
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13/15-14/16 Uo / Voc = 21.5 V Ui / Vmax Ch1 13/15-14/16 Io / Isc = 604 mA Ii / Imax Ch1 13/15-14/16 Po / Po = 3243 mW Pi / Pi
Ch1 13/15-14/16
Co / Ca = 1.2 μF IIB (C) Co / Ca = 4.5 μF IIA (D) Co / Ca = 6.5 μF I Co / Ca = 1.2 μF IIIC (E, F, G)
Ci / Ci device
+ C cable
Ch1 13/15-14/16
Lo / La = 390 μH IIB (C) Lo / La = 780 μH IIA (D) Lo / La = 1.28 mH I Lo / La = 390 μH IIIC (E, F, G)
Li / Li device
+ L cable
Page 65
ISM0156-9 Page 65
Terminals Associated Apparatus Parameters
must
be
Haz. Area/Haz. Locations
Device Parameters
Ch1 13/15-14/16
Lo/Ro = 43.8 μH/Ω IIB (C) Lo/Ro = 87.7 μH/Ω IIA (D) Lo/Ro = 143.9 μH/Ω I Lo/Ro = 43.8 μH/Ω IIIC (E, F, G)
Li/Ri device
and L cable/R cable
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C
cable 50% of Co and Li device + L cable 50% of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 µF for Groups I, IIA, IIB. If the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per foot), Inductance 1μH per meter (0.20μH per foot).
WARNING
PSD5201 is isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIB, Temperature T4 Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
PSD5201 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
INSTALLATION
PSD5201 is a power supply for hazardous area equipment housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022. PSD5201 unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable. Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres ­Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of PSD5201 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, PSD5201 unit must be connected to SELV or SELV-E supplies.
For the complete instruction manual ISM0186, datasheet and certifications please refer to our website www.gmintsrl.com.
Page 66
ISM0156-9 Page 66
Page 67
ISM0156-9 Page 67
Page 68
ISM0156-9 Page 68
Page 69
ISM0156-9 Page 69
Page 70
ISM0156-9 Page 70
Page 71
ISM0156-9 Page 71
Page 72
ISM0156-9 Page 72
Page 73
ISM0156-9 Page 73
Page 74
ISM0156-9 Page 74
Page 75
ISM0156-9 Page 75
Page 76
ISM0156-9 Page 76
Page 77
ISM0156-9 Page 77
Page 78
ISM0156-9 Page 78
Page 79
ISM0156-9 Page 79
Page 80
Note: This manual contains only safety instructions. For the complete installation and user manuals, certifications and data sheets, please refer to www.gmintsrl.com.
D5000 Safety Instruction Manual ISM0156-9
www.gmintsrl.com
Via G. Mameli, 53/55
I-20851 Villasanta (MB) - Italy