GMDE 1KVA, 2KVA, 3KVA, 4KVA, 5KVA User Manual

User Manual
1KVA- 5KVA
INVERTER / CHARGER With MPPT Controller
类型: Powervortex 101K24/102K24/103K24/101K48/102K48 /103K48/102K24M/103K24M/102K48M/ 103K48M/105K48/105K48P
User Manual
Table Of Contents
ABOUT THIS MANUAL ..................................................................................................................................... 1
Purpose................................................................................................................... ......................................... 1
Scope ............................................................................................................................................................... 1
SAFETY INSTRUCTIONS.................................................................................................................... .............. 1
INTRODUCTION ............................................................................................................................................... 2
Features ................................................................... ........................................................................................ 2
Basic System Architecture ............................................................................................................................... 2
Product Overview............................................................................................................................................. 3
INSTALLATION ................................................................................................................................................. 4
Unpacking and Inspection................................................................................................................................ 4
Preparation .......................................................................................... ............................................................ 4
Mounting the Unit ............................................................................ ................................................................. 4
Battery Connection .................................................. ........................................................................................ 5
AC Input/Output Connection ............................................................................................................................ 7
PV Connection ................................................................................................... .............................................. 8
Final Assembly ................................................................................................................................................. 9
Communication Connection........................................................................................................................... 10
Dry Contact Signal ............................................................................................................................ ............. 10
OPERATION ..................................................................................................................................................... 11
Power ON/OFF ................................................................................................................................ .............. 11
Operation and Display Panel ......................................................................................................................... 11
LCD Display Icons ......................................................................................................................................... 12
LCD Setting.................................................................................................................................................... 14
Display Setting ................................................................................ ............................................................... 20
Operating Mode Description ................................................................................................ .......................... 23
Fault Reference Code ...................................................................................................................... .............. 24
Warning Indicator ............................................................................................................ ............................... 25
SPECIFICATIONS ........................................................................................................................................... 26
Table 1 Line Mode Specifications ................................................................................................................... 26
Table 2 Inverter Mode Specifications ............................................................................................................. 27
Table 3 Charge Mode Specifications .............................................................................................................. 28
Table 4 General Specifications ....................................................................................................................... 29
TROUBLE SHOOTING ..................................................................................................................................... 30
Appendix: Approximate Back-up Time Table ........................................................................................... 31
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read
this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage.
Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk.
CAUTION – Only qualified personnel can install this device with battery.
NEVER charge a frozen battery.
For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. Its very important to correctly operate this inverter/charger.
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details.
Fuses (3 pieces of 40A, 32VDC for 1KVA, 4 pieces of 40A, 32VDC for 2KVA and 6 pieces for 3KVA, 1
piece of 200A, 58VDC for 4KVA and 5KVA) are provided as over-current protection for the battery
supply.
GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center
for maintenance.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
1
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger and battery
charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers
user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger
priority, and acceptable input voltage based on different applications.
Features
Pure sine wave inverter Built-in MPPT solar charge controller
Configurable input voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting
Compatible to mains voltage or generator power
Auto restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance
Cold start function
Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to
have a complete running system:
Generator or Utility. PV modules (option)
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.
Figure 1 Hybrid Power System
2
Product Overview
4KVA/5KVA single model
4KVA/5KVA parallel model
LCD display Status indicator
Charging indicator
Fault indicator
Function buttons
Power on/off switch
AC input AC output
PV input
1-3KVA model
1.
2.
3.
4.
5.
6.
7.
8.
9.
NOTE: For parallel model installation and operation,
please check separate parallel installation guide for
the details.
10. Battery input
11. Circuit breaker
12. RS232 communication port
13. Parallel communication cable (only for parallel model)
14. Current sharing cable (only for parallel model)
15. Dry contact
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
The unit x 1 User manual x 1
Communication cable x 1
Software CD x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction
materials.
Mount on a solid surface Install this inverter at eye level in order to allow the LCD display to be read at all times.
The ambient temperature should be between 0°C and 55°C
to ensure optimal operation.
The recommended installation position is to be adhered to
the wall vertically.
Be sure to keep other objects and surfaces as shown in the
right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
 
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
4
Install the unit by screwing three screws.
1-3KVA 24V, 1KVA/3KVA 48V model
2-3KVA 24V/48V Plus, 4-5KVA 48V model
Battery Connection
CAUTION: For safety operation and regulation compliance, its requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, its still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
Ring terminal:
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
5
Model Typical
Amperage
Battery
Capacity
Wire Size Ring Terminal Torque
Value
Cable mm
2
Dimensions
D (mm) L (mm)
1KVA 48V 20A 100AH 1*14AWG 2 6.4 21.8 2~ 3 Nm
1KVA 24V, 2KVA 48V 33A 100AH 1*10AWG 5 6.4 22.5 2~ 3 Nm
3KVA 48V 50A 100AH 1*8AWG 8 6.4 23.8 2~ 3 Nm
2KVA 24V
66A
100AH 1*6AWG 14 6.4 29.2
2~ 3 Nm
200AH 2*10AWG 8 6.4 23.8
3KVA 24V
100A
100AH 1*4AWG 22 6.4 33.2
2~ 3 Nm
200AH 2*8AWG 14 6.4 29.2
4KVA
66A
200AH
1*4AWG 22 6.4 33.2
2~ 3 Nm
2*8AWG 14 6.4 29.2
5KVA
87A
200AH
1*4AWG 22 6.4 33.2
2~ 3 Nm
2*8AWG 14 6.4 29.2
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Connect all battery packs as units requires. Its suggested to connect at least 100Ah capacity battery for
1-3KVA model and at least 200Ah capacity battery for 4KVA/5KVA model.
NOTE: Please only use sealed lead acid battery or sealed GEL/AGM lead-acid battery.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are
tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.
6
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are
connected tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 10A
for 1KVA, 20A for 2KVA, 32A for 3KVA, 40A for 4KVA and 50A for 5KVA. CAUTION!! There are two terminal blocks with IN and OUT markings. Please do NOT mis-connect input
and output connectors.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the proper recommended cable size as below. Suggested cable requirement for AC wires
Please follow below steps to implement AC input/output connection:
1.
2.
3.
Before making AC input/output connection, be sure to open DC protector or disconnector first. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor (
Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
) first.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor (
Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
) first.
7
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
Model Gauge Torque Value
1KVA 16 AWG 0.5~ 0.6 Nm
2KVA 230VAC 14 AWG 0.8~ 1.0 Nm
2KVA 120VAC
3KVA
12 AWG
1.2~ 1.6 Nm
4KVA 10 AWG 1.4~ 1.6Nm
5KVA 8 AWG 1.4~ 1.6Nm
5. Make sure the wires are securely connected.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV
module connection. To reduce risk of injury, please use the proper recommended cable size as below.
8
Model Typical Amperage Cable Size Torque
1KVA 24V / 2KVA 24V/
3KVA 24V
25A
12 AWG
1.2~1.6 Nm
1KVA 48V / 3KVA 48V 18A 14 AWG 1.2~1.6 Nm
2KVA 24V Plus
3KVA 24V Plus
2KVA 48V Plus
3KVA 48V Plus
4KVA / 5KVA
60A
8 AWG
1.4~1.6 Nm
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because its required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check
manufacturer of air conditioner if its equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes
internal damage to the air conditioner.
PV Module Selection: When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Please follow below steps to implement PV module connection:
1.
2.
Remove insulation sleeve 10 mm for positive and negative conductors. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
1KVA/2KVA/3KVA 2KVA Plus/3KVA Plus/4KVA/5KVA
9
Solar Charging Mode
INVERTER MODEL
1KVA 24V
2KVA 24V
3KVA 24V
1KVA 48V
3KVA 48V
2KVA 24V
Plus/ 3KVA
24V Plus
2KVA 48V
Plus/3KVA 48V
Plus/ 4KVA/5KVA
Max. PV Array Open Circuit Voltage 75Vdc max 102Vdc max 145Vdc
PV Array MPPT Voltage Range 30~66Vdc 60~88Vdc 30~115Vdc 60~115Vdc
Min. battery voltage for PV charge 17Vdc 34Vdc 17Vdc 34Vdc