Glowworm Lighting 200 I, 300 I, 250 I User Manual

Installation and Servicing
Flurocyl
Solar Hot Water Cylinder
14161
200 l
250 l
300 l
www.glow-worm.co.uk
1
Guarantee Registration
Thank you for installing a new Glow-worm solar system.
customers a Comprehensive Guarantee.
This product is guaranteed for 24 months from the date of installation or 30 months from the date
of manufacture, whichever is the shorter, for parts and labour.
The second year of the guarantee, from the beginning of the 13th month onwards after installation
or manufacture, is conditional upon the product having been serviced by a competent person (i.e.
clear skies registered engineer),
in accordance with the manufacturer’s recommendations. We strongly recommend regular
servicing of your product, but where the condition is not met, any chargeable spare parts or
components issued within the applicable guarantee period still benet from a 12 month warranty
from the date of issue by the manufacturer.
The “Benchmark” Installation, Commissioning and Service Record must be completed on
installation and kept up to date.
We recommend you complete and return as soon as possible your guarantee registration card.
If your guarantee registration card is missing you can obtain a copy or record your registration by
telephoning the Glow-worm Customer Service number 01773 596510.
Customer Service:
01773 596510
Technical Helpline:
01773 828300
General and Sales enquiries:
Tel. 01773 824639
Fax: 01773 820569
To register your Glow-worm product call:
0800 0732142
2
These instructions consist of, Installation, Servicing, Fault Finding and Replacement
of Parts. The instructions are an integral part of the product and must, be handed to
the user on completion of the installation.
CONTENTS DESCRIPTION SECTION PAGE
Warnings 4 Important Information 4
INTRODUCTION
Statutory Requirements 5 Safety Instructions 6
INSTALLATION
MAINTENANCE
Product Specications 1 6
Installation 2 11 Commissioning 3 18
Inspection and Maintenance 4 19 Fault Finding 5 20
3
WARNINGS
SAFETY
The urocyl must be installed by a competent person, who is responsible for adhering to
the existing standards and regulations.
ALTERATIONS
Under no circumstances should you ever attempt to make alterations to these
components or any other part of the system
SEALED COMPONENTS
Under no circumstances must the user interfere with or adjust sealed parts.
Important Information
Installation and Use Regulations
In your own interests and that of safety, it is the LAW that this product is installed by a competent person in accordance with the current issue of these regulations.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this product are cured and give no known hazard in this state.
Manual Handling
With regards to the “Manual Handling Operations, 1992 Regulations”, the appliance exceeds the recommended weight for a one man lift.
Electrical Supply
The product MUST be earthed.
All system components shall be of an approved type and all wiring to current I.E.E. wiring regulations.
External wiring must be correctly earthed, polarised and in accordance with the relevant standards.
In GB, this is BS 7671.
In IE, this is the current edition of ETCI rules.
The product MUST be connected to a permanent 230V ac, 50Hz supply.
Connection of the whole electrical system of the product, including any heating controls, to the electrical supply MUST be through one common isolator and must be fused 3 Amp maximum.
Isolation should be by a double pole switched fused spur box, with a minimum gap of 3mm for both poles. The fused spur box should be readily accessible and preferably adjacent to
the product. It should be identied as to its use.
Alternatively connection can be made through an unswitched shuttered socket and 3A fused 3-pin plug both to the current issue of BS 1363, provided they are not used in a room containing a bath or shower.
Wiring to the product must be PVC 85°C insulated cable, not less than 0.75mm2 (24/0.20mm).
Testing and Certification
This product is tested and certicated for safety and
performance. It is, therefore, important that no alteration is made to the product, without permission, in writing, by Glow­worm.
Any alteration not approved by Glow-worm, could invalidate
the certication, warranty and may also infringe the current
issue of the statutory requirements.
CE Mark
The CE mark on the Fluropro solar control indicates that it complies with the basic requirements of the applicable directives as stated on the data badge.
“Benchmark scheme”
Glow-worm support the Benchmark initiative. It is very important that the service record is completed by the installation engineer and handed over to the user.
4
Statutory Requirements
IMPORTANT:
Where no British Standards exists, materials and equipment
should be t for their purpose and of suitable quality and
workmanship.
The installation of this product must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
Statutory Requirements
In GB, the installation of the product must be carried out by a competent person as described in the following regulations:
The manufacturer’s instructions supplied.
The Gas Safety (Installation and Use) Regulations.
The appropriate Buildings Regulations either The Building Regulations, The Building Regulations (Scotland),The Building Regulations (Northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
Where no specic instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition
of I.S.813 “Domestic Gas Installations”, the current Building Regulations and reference should be made to the current ETCI rules for Electrical Installation.
GB: the following Codes of Practice apply:
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671.
IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
NOTE: For further information, see the current issue of the
Building Regulations, approved document L1 ( in the UK) and the following current issues of:
1) Central heating system specication (CheSS)
and
2) Controls for domestic central heating system and hot water. BRECSU.
Domestic Hot Water
All domestic hot water circuits, connections, ttings must be
in accordance with the relevant standards and water supply regulations.
GB: Guidance G17 to G24 and recommendation R17 to R24 of the Water Regulations Guide.
IE: The current edition of I.S.813 “Domestic Gas Installations”.
Heating System
In GB, it is necessary to comply with the Water Supply (Water
Fittings) Regulations 1999 (for Scotland, the Water Byelaws 2000, Scotland).
To comply with the Water regulations your attention is drawn to: The Water Regulations guide published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements.
In IE, the requirements given in the current edition of I.S.813 “Domestic Gas Installations” and the current Building
Regulations must be followed.
Solar cylinder and cylinder installation
Pressure equipment directive 97/23/EC Directive of the
European Parliament and Council from 29th May, 1997 for the approximation of the laws on pressure equipment of the Member States
EN 12977-3 Thermal solar systems and components; Custom built systems, Part 3: Performance characterisation of stores for solar heating systems
EN 12897 Water supply - specication for indirectly heated
unvented (closed) storage water heaters
EN 806-1 Specications for installations inside buildings
conveying water for human consumption - Part 1: General
EN 1717 Protection against pollution of potable water installations and general requirements of devices to prevent
pollution by backow
EN 60335-2-21 Safety of household and similar electrical appliances; Part 2: Particular requirements for storage water heaters (hot water cylinders and hot water boilers) (IEC 335-
2-21: 1989 and supplements 1; 1990 and 2; 1990, modied)
Regulations in Great Britain
Building Regulation, dating from 1991 (England and Wales)
Requirement G3, L1 and Regulation 7
BS 7671 Requirements for electrical installations (IEE Wiring Regulations, 16th edition)
BS 6759-1 Directive for the usage of the safety assembly for hot water cylinders
5
Safety Instructions
Safety instructions
NOTE: In the event of leaks in the water pipework close the
main cold water stop valve. This is often located under a kitchen sink.
IMPORTANT: A thermostatic mixing valve must be tted to
the outlet of the cylinder and can be adjusted to the desired domestic hot water temperature by an installation or service engineer. Otherwise there is a risk of scalding as the cylinder outlet temperature at the taps could be up to 85°C.
IMPORTANT: Risk of damage! Do not remove or modify any components of the solar cylinder.
In the unlikely event of a malfunction occurring of the Flurocyl,
such as hot water owing out of the temperature and pressure
relief valve, switch off the boiler and the immersion heater and contact Glow-worm or your installer.
Frost protection of the twin coil solar cylinder
You must drain the solar cylinder completely if it is to be shut down in a room prone to frost. It is drained at the cold water inlet with a T-piece with tap to be provided by the installer.
Also drain all heat exchangers which are not lled with solar uid.
1 Product Specications
Unit Flurocyl 200 l Flurocyl 250 l Flurocyl 300 l
Cylinder:
Size l 200 250 300
Maximum water supply pressure bar 10
Operating pressure bar 3.5
Pressure limiting valve bar 3.5
Expansion relief valve bar 6.0
Hot water expansion vessel admission pressure bar 4.0
Temperature and pressure relief valve °C/bar 95 / 7.0
Net weight kg 39 44 49
Weight (full) kg 245 310 340
Height mm 1499 1789 2109
Cylinder connections:
Cold water supply 22 mm pressure pipe
Hot water connection 22 mm pressure pipe
Pressure-controlled cold water outlet 22 mm pressure pipe
Secondary return Inches G 3/4
Flow (boiler/solar circuit) 22 mm pressure pipe
Return (boiler/solar circuit) 22 mm pressure pipe
Electrical connections:
3 kW immersion heater (according to ENBS 60335) 230/240 V, 50 Hz
Length of the immersion heater mm 430
Motorised 2 port valve 230/240 V, 50 Hz
Cylinder thermostat 230/240 V, 50 Hz
Thermal cut out for solar pump 230/240 V, 50 Hz
Heating coil:
Heat loss kW/24 h 1.9 2.1 2.4
Heat up time (boiler part) mins 21 26 30
Recovery (boiler part) mins 13 16 21
Table 1.1 Technical data
6
1 Product Specications
Approximate cylinder heat up time 15 C to 45 C (minutes)
Reheat time for 70 % of cylinder contents (minutes)
10
15
20
25
30
20
25
30
35
40
45
12
Heat input to cylinder (kW)
15 20 25 30 3835
200 l
250 l
300 l
40
40
8 bar 4 bar
3 bar 2 bar
1 bar
30
30
20
20
Flow available (litres/min) at entry to system
Flow out (litres/min) of the system
10
10
0
8 bar 4 bar 3 bar 2 bar
1 bar
Flow available (litres/min) at entry to system
Flow out (litres/min) of the system
40
40
30
30
20
20
10
10
0
Mixed water of 40 °C, mixed from 60 % hot water of 60 °C and 40 % cold water of 10 °C
14177
Flurocyl cylinder heat-up times (boiler part)
14178
Flurocyl DHW flow rates at 60°C Flurocyl mixed water flow rates
NOTE: The heat-up time is based on a primary ow rate of 9
l/min at 80 °C. Temperature rise from 15 °C to 65 °C
Static operating pressure of the cold water supply
The displayed ow rates apply to installations in which the
cold water supply is of appropriate dynamic pressure.
Please contact Glow-worm if the static water pressure is below 1 bar.
Diagram 1.2
7
Diagram 1.1
14179
Diagram 1.3
1 Product Specications
CARRYING HANDLE
1.1 Intended use
The Glow-worm Flurocyl 200 l, Flurocyl 250 l and Flurocyl 300 l are unvented, indirectly heated hot water cylinders for use with solar systems and boilers for the provision of domestic hot water.
IMPORTANT: Risk of damage! The appliances may only be used to heat up potable water. Damage to the appliance due to corrosion cannot be excluded if the water does not
correspond to the specications of the water ordinance.
Any other use or extended use is considered to be improper. The manufacturer/supplier is not liable for any resulting damage.
Intended use includes the observance of the instructions and the adherence to the servicing requirements.
1.2 Data badge
The data badge has been applied to the top of the solar cylinder by the manufacturer.
1.3 Safety devices
The Flurocyl solar cylinder has been provided with all safety and control devices suitable for operation as part of an unvented domestic hot water supply system.
Temperature and pressure relief valve (95°C, 7 bar)
Pressure limiting valve (3.5 bar) with line strainer
Expansion relief valve (one port valve, 6.0 bar)
Thermal cut out set to 90°C, connected to the solar pump in order to isolate this heat source in the event of failure of the solar control.
Thermal cut out of the immersion heater
Thermal cut out set to 90°C, connected to the motorised 2 port valve, in order to isolate the primary heat source in the event of failure of the domestic water thermostat.
1.4 Safety regulations
This product has been checked for adherence to the building regulations for unvented hot water cylinder systems. It may
not be changed or modied in any way whatsoever.
It should be installed by a qualied specialist, who should
observe the applicable regulations of the local authorities, the building regulations, the building regulations for Scotland, the building regulations for Northern Ireland and the directives of the local water supply companies. Only original spare parts may be used for the replacement of parts.
1.7 Solar Cylinder Charicteristics
Flurocyl solar cylinders are available in three sizes: 200, 250 and 300 litres. The containers are made of stainless steel and insulated with EPS.The cylinders are equipped with all necessary cold and hot water control devices and a motorised 2 port valve.
The Flurocyl cylinders are operated at the pressure of the water supply pipe and do not need a cold water tank for their supply. They have hot and cold water connections of 22 mm diameter. A cold water supply of appropriate pressure and
ow rate is required to operate the solar cylinder ideally, refer
to section 2.6.
Temperature control
The solar water heating control thermostat is part of the solar control with sensor attached to the Flurocyl solar cylinder.
The cylinder includes the boiler and imersion heater control
thermostats that are factory tted and set.
A themostatic mixing valve must be tted to the outlet of the
cylinder and must be adjusted to the desired domestic hot water temperature.
The cylinder also includes the solar, boiler and immersion
heater thermal cut outs that are factory tted and set.
The solar pump must be connected to the solar control via the solar thermal cut out (TCO), It ensures the solar pump is switched off if the hot water temperature in the cylinder rises above 90°C.
Immersion heater
The Flurocyl solar cylinders are equipped with an additional immersion heater of 3 kW, including the control thermostat and thermal cut out. The immersion heater is situated behind the front plate.
NOTE: In the event of a replacement, only the right immersion heater equipped with a thermal cut out fur overheating protection may be used.
1.5 Contents
Check the contents of the pack, see diagram 2.1.
Make sure the cylinder is stored in an upright position in a dry environment prior to its installation.
1.6 Transport
A cylinder carrying handle is supplied to make the transport to the installation site easier.
Fasten the carrying handle to the hot water outlet connection of the solar cylinder.
Carrier handle
8
14180
Diagram 1.4
F
D
E
G
C
A
B
554
598
45°
H
ot water connection
Temperature and pressure relief valve
Solar circuit Flow Cold water supply Solar circuit Return
H
I
Immersion
heater
Boiler Flow
Boiler Return
1 Product Specications
14181
Dimensions
Flurocyl 200 l
Flurocyl 250 l
Flurocyl 300 l
Diagram 1.5
A B C D E F G H I
1468 1499 454 384 314 589 1118 813 953
1758 1789 454 384 314 589 1408 924 1064
2078 2109 454 384 314 589 1648 1101 1241
Table 1.2 Dimensions
9
Boiler
Flow Return
Flurocyl
Flurosorb
Solar Pump Unit
Flow
Return
Immersion Heater
Drinking Water Expansion Vessel
2 Port Valve
2 Port Valve
Automatic Air
Separator System
M
DHW
M
Protection Vessel (optional)
Solar Expansion Vessel
1 Product Specications
14162
Diagram 1.6
10
2 Installation
A B
7 8 9 10
2 3 4 5 6
1
14173
Flurocyl pack contents
Item Description Qty. Qty. Qty.
1 Flurocyl solar cylinder
Part no.
2 Cold water control pack with tundish 1 1 1
3 Motorised 2 port valve 1 1 1
4 DHW expansion vessel 18 l 1
5 DHW expansion vessel 25 l 1 1
6 DHW Expansion vessel mounting bracket 1 1 1
7 Carrying handle 1 1 1
8 Compression Fittings 1 1 1
9 Drain valve 1 1 1
Thermostatic Mixing Valve 1 1 1
10
200 l 250 l
307 206 307 207 307 208
Table 2.1 Flurocyl pack contents
Diagram 2.1
300 l
11
2 Installation
Legionella loop return connection
Cylinder thermostat
Cylinder thermostat thermal cut out
Immersion heater thermostat
Immersion heater thermal cut out
Immersion heater
Domestic hot water outlet connection
Temperature and Pressure relief valve
Expansion vessel connection
Pressure controlled cold water outlet
Cold water supply
Return
(solar circuit)
Adjustable feet
Flow (solar circuit)
Return
(boiler)
Flow (boiler)
Solar pump thermal cut out
Immersion heater switch
Pressure limiting valve
Expansion relief valve
Tundish
Cylinder drain valve
Temperature sensor immersion sleeve
Expansion vessel
REAR VIEW
30°
4
0
°
5
0
°
65°
30°
4
0
°
5
0
°
65°
LN
1 2 3
14174
2.1 Locating the cylinder
Locate the solar cylinder at an appropriate place in the building, while observing the following:
The discharge pipe from the tundish must be installed at a minimum slope of 1:200 and end at a safe and visible point, refer to section 2.9.
The installation surface must be level and able to bear the weight of the full cylinder, refer to table 1.1.
The installation site may not be prone to frost. A frost protection thermostat must be installed if necessary.
There must be sufcient space to install, check and
repressurise the expansion vessel.
Floor unevenness should not be greater than the compensation offered by the adjustable feet of the solar cylinder.
2.2 Boiler heating circuit piping
Copper pipes with a minimum diameter of 22mm should be used for the pipes in the reheating circuit between the boiler and the solar cylinder.
Larger pipe diameters may be necessary for relatively large distances between the boiler and the cylinder.
2.3 Motorised 2 port valve
To prevent the Flurocyl cylinder from overheating the 2 port
motorised valve supplied must be tted to the primary ow to
the indirect coil.
2.4 Domestic hot water pipework
Connect the hot water outlet to the 22mm hot water connection of the solar cylinder.
Lay a further 22mm pipe to the rst T-piece.
A pipe of 15mm diameter should then be sufcient.
If the pipe is very long or several outlets are supplied, continue with another 22mm pipe.
2.5 Thermostatic mixing valve
A hot water thermostatic mixing valve ensures the hot water from the cylinder is mixed with cold water to a desired maximum temperature between 30°C and 60°C.
Set the thermostatic mixing valve to the desired maximum temperature during the solar system commissioning.
IMPORTANT: Risk of scalding, Set the thermostat mixer to 60°C or below and check the temperature at a hot water tap to ensure effective protection against scalding.
Diagram 2.2
12
2 Installation
TUNDISH
THERMOSTAT MIXER
EXPANSION VESSEL
HOT WATER CONNECTION
TEMPERATURE AND PRESSURE RELIEF VALVE (95 °C, 7 BAR)
LEGIONNELLA LOOP (optional)
FLOW
PUMP
BOILER
PRESSURE LIMITING VALVE (3.5 BAR) WITH LINE STRAINER
EXPANSION RELIEF VALVE (6.0 BAR)
COLD WATER SUPPLY
FLUROCYL DRAIN VALVE
MOTORISED 2 PORT VAVE
MOTORISED 2 PORT VAVE
RETURN
14244
2.6 Mains water supply
The performance of unvented cylinders depends on the available mains water pressure and the pipe size.
In order for the performance of the Flurocyl solar cylinder to be ideal, an appropriate cold water supply must be available. The measured static pressure must be at least 2.0 bar. A
corresponding ow rate of at least 20 - 25 l/min should be
available.
NOTE: The mains water pressure is reduced during periods of high water consumption.Make sure you take measurements during these periods.
Diagram 2.3
Example: The available ow rate of mixed water at 40°C is 25
l/min (15 l/min hot water of 60°C from the solar cylinder mixed with 10 l/min cold water of 10°C) if the measured static cold mains water pressure is 2 bar.
The solar cylinder operates satisfactorily at a mains water
pressure of below 2 bar, but at a reduced ow rate.The
unvented solar cylinder should not be installed if the mains water pressure is below 1 bar.You can obtain information on alternative hot water supply systems from Glow-worm.
To keep the friction losses at a minimum, a minimum diameter of 22mm is recommended for the cold water supply in the building, satisfactory performances can also be achieved with 15mm pipes however.
13
2.7 Cold water inlet controls and pipework
COLD WATER SUPPLY
PRESSURE LIMITING VALVE WITH LINER STRAINER
BALANCED PRESSURE COLD WATER CONNECTION
HOT WATER EXPANSION VESSEL CONNECTION
EXPANSION RELIEF VALVE
FLUROCYL CONNECTION
LEGIONELLA LOOP CONNECTION
Connect both parts of the water control pack.
When installing the valves, make sure they are aligned in such a way that the 15mm connection of the expansion relief valve can be connected to the tundish.
Install the assembled water control pack in the cold water supply at an appropriate place next to the solar cylinder.
Make sure there is sufcient space for maintenance and the
connection of the discharge pipe from the expansion relief valve.
Install the drain valve in the cold water supply at the lowest point between the solar cylinder and the water control pack.
We recommend applying a hose, which reaches about 1m under the base of the cylinder, to the outlet of the drain valve.
IMPORTANT: Risk of bursts for the solar cylinder! No stop valve may be installed between the cold water control pack and the cylinder.
Install the water pack so that a discharge pipe of the
expansion relief valve can be tted with constant outward
slope which can end at a safe, visible point where there is no risk of freezing.
IMPORTANT: Risk of the solar cylinder bursting due to overpressure! The outlet of the expansion relief valve must not be covered or closed.
Test the expansion relief valve regularly to avoid calcication.
To ensure an optimum performance of the solar cylinder, in particularly buildings in which a pressure controlled cold water is used, copper pipes with a diameter of at least 22mm should be used for the pipe from the main stop valve of the building to the solar cylinder.
If the discharge pipes are all together, the expansion relief valve may not be installed more than 500 mm away from the temperature and pressure relief valve.
The Flurocyl solar cylinder is supplied with an external hot water expansion vessel (DW EV).
Connect this expansion vessel to the installed water control pack as follows:
Screw the expansion vessel directly onto the water control pack, via the connection intended for this purpose or
Connect the expansion vessel to the water control pack with a copper pipe or an appropriate hose. Make sure the expansion
vessel is supported sufciently.
Use the supplied mounting bracket if the expansion vessel is to be mounted on the wall.
Connect thermostatic mixing valve cold supply to the pressure controlled cold water connection of the water control pack (if convenient).
NOTE: In areas with high water pressure (4 bar or more), a bath or shower mixer valve could also be connected to the pressure-controlled cold water connection of the water control pack. This is to ensure the pressure of the hot and cold water supply to the mixer valve is about the same. Any second cold water supply connection should be installed between the water control pack and the solar cylinder by means of a T-piece.
2 Installation
14187
Diagram 2.4
2.8 Discharge pipework
The outlet connections of both the temperature / pressure relief valve and expansion relief valve should be connected in 15mm copper pipe to the tundish supplied. The tundish should be installed vertically, as close to the Flurocyl as possible and within 500mm of the temperature and pressure relief outlet. It must be positioned away from any electrical components and installed in the same space as the Flurocyl cylinder, so that it is visible to the user. The D1 discharge pipe from the T&P Valve/Expansion valve can be teed together upstream of the tundish.
The discharge pipework must be installed using minimum 22mm copper pipework from the 22mm connection on the tundish to a safe and visible discharge point.
There must be a vertical section of pipe at least 300mm long, below the tundish before any bends or elbows in the pipework. Increase the diameter of the pipework if the total resistance of the discharge pipework exceeds the
gures shown in table 2.2. The installation of the discharge
pipework must be in accordance with G3 refer to Statutory Requirements.
14
METAL DISCHARGE PIPE FROM TEMPERATURE RELIEF VALVE TO TUNDISH
METAL DISCHARGE PIPE FROM TUNDISH WITH CONTINUOUS FALL
TUNDISH
DISCHARGE BELOW FIXED GRATING
FIXED GRATING
TRAPPED GULLY
SAFETY DEVICE (E.G. TEMPERATURE RELIEF VALVE VENTIL)
500 MM
MINIMUM
300 MM
MINIMUM
TUNDISH
300 MM MINIMUM
DISCHARGE PIPE
METAL HOPPER HEAD
2 Installation
Minimum diameter of the discharge pipe from the tundish
22mm
28mm Up to 18m 1.0m
35mm Up to 27m 1.4m
Examples:
22mm discharge pipe with 4 elbows and of 7m length from the tundish to the discharge point:
Resistance for 4 elbows per 0.8m = 3.2m Resistance for discharge pipe = 7.0m Total resistance = 10.2m
The total resistance of the discharge pipe is higher than the maximum permissible value for 22mm pipes (9m). Base your calculations therefore on the next largest pipe diameter.
28mm discharge pipe with 4 elbows and of 7m length from the tundish to the discharge point:
Resistance for 4 elbows per 1.0m = 4.0m Resistance for discharge pipe = 7.0m Total resistance = 11.0m
The total resistance of the discharge pipe is lower than the maximum permissible value for 28mm pipes (18m),which means this pipe diameter can be used.
Water which is almost boiling may escape from the discharge pipe in the event of an error.
IMPORTANT: Risk of being scalded by escaping hot water! Make sure the discharge pipe ends at a safe point inside or outside the building (safe and visible), where there is no risk of anyone coming in contact with hot water.
A suitable point is, for example, under a xed grating above
the trap of a trapped gully. Low discharge pipes, for example up to 100mm above external surfaces, such as parking spaces, grasslands etc., can be used, provided they are secured by a wire fence or something similar to prevent children from coming in contact with the waste water, and the system is visible. No valves or taps may be installed in the discharge pipe.
Make sure the discharge pipe is at a constant slope of at least 1:200 from the tundish to the discharge point.
The discharge pipe from the pressure relief valve of the boiler (if applicable) can be connected to the horizontal discharge pipe of the solar cylinder behind the tundish with a T-piece.
2.9 High level discharge termination
Providing that the point of termination is such that persons in or around the building will not be endangered should discharge take place, this method of termination is satisfactory. Points to consider when deciding whether a location for the high level of discharge is suitable are:
Maximum permissible total resistance, expressed as straight pipe length (without elbows or bends)
Up to 9m 0.8m
Resistance due to each elbow or bend (straight length equivalent)
Table 2.2 Resistance
14188
Diagram 2.5
14189
Diagram 2.6
The possibility, taking into account wind effect, that someone may be in the path of the water being discharged and if so, whether the temperature of the discharge water will have
been sufciently reduced to not be dangerous. Thermal
conductivity of the structure's surface, climatic conditions and location and orientation of the discharge pipe may or may not have an effect on reducing the temperature of the discharge water.
The location of windows and similar openings.
The likelihood of a pram being left beneath the point of discharge.
The ability of structures surface to withstand near boiling water.
The possibility of ice formation if water is discharged onto pedestrian walkways.
15
2 Installation
IMMERSION HEATER THERMAL CUT OUT WITH RESET BUTTON
REHEAT THERMAL CUT OUT WITH RESET BUTTON
REHEAT THERMOSTAT (FACTORY SET)
IMMERSION HEATER THERMOSTAT (FACTORY SET)
IMMERSION HEATER CONNECTION 230V AC 3 kW
TEMPERATURE SENSORS IN IMMERSION SLEEVES
230V AC 3 kW
30°
4
0
°
5
0
°
65°
30°
4
0
°
5
0
°
65°
LN
1 2 3
UPPER TEMPERATURE SENSOR
LOWER TEMPERATURE SENSOR
TEMPERATURE SENSOR GAIN
3
0
°
40
°
50°
65°
3
0
°
40°
50°
65°
LN
1 2
3
DOMESTIC HOT WATER DEMAND WIRING
REHEAT CONTROL THERMOSTAT (FACTORY SET)
SOLAR THERMA
L CUT-OUT WITH RESET BUTTON
2.10 Electrical installation
Remove the front fascia panel.
Wiring should be performed by a competent person in accordance with the building regulations, Part P of the current IEE regulations and further applicable regulations and directives.
The discharge pipes of the tundish, drain valves, motorised valves etc. should be laid at a safe distance to electrical components.
IMPORTANT: Danger of death from electric shock! You must earth the solar cylinder for potential equalisation.
2.11 Immersion heater
The Flurocyl solar cylinders incorporate an immersion heater.
IMPORTANT: Danger of death from electric shock! You must earth the immersion heater for potential equalisation.
Install a separate electrical power supply line for the immersion heater in accordance with current IEE regulations (BS 7671).
You must lay a heat-resistant line (3 x 2.5 mm pole isolating switch for the immersion heater. The circuit must be protected by a 13 A fuse.
The connection of the immersion heater is illustrated in detail in diagram 2.7.
IMPORTANT: Risk of damage! The immersion heater is equipped with a thermal cut out and may under no circumstance be replaced by a standard immersion heater.
Only correct original Glow-worm spare parts are permitted.
2
) from a double
14190
Diagram 2.7
14192
2.12 Thermostat setting
The entire inner wiring has been pre-assembled at the factory.
IMPORTANT: Risk of damage! Switch off the power supply before resetting the thermal cut out or making any other changes to the temperature setting of the cylinder thermostat.
The cylinder thermostats for the regulation of the hot water temperature are factory set at 65°C as the Domestic Hot Water temperature is controlled by the adjustable thermostatic mixing valve.Ensure both control thermostats are adjusted fully clockwise.
Actuate the reset buttons, to reset the thermal cut outs if necessary, see diagram 2.7.
IMPORTANT: Risk of damage! If the immersion heater is not connected, you must connect the earth wire to terminal E
on the terminal strip of the immersion heater. You can nd a
wiring sheme on the inside of the cylinder cover.
2.13 Thermostat and sensor wiring
Connect the domestic hot water demand wiring to the reheat control thermostat as shown in diagram 2.8 and 2.10.
Connect the solar pump live via the solar thermal cut out and ensure this thermal cut out is earthed, as shown in diagram
2.8. and 2.10.
Install the two temperature sensors in the solar cylinder, see diagram 2.9, and connect to the solar control, see diagram
2.10.
Attach the solar gain sensor to the solar circuit return, see diagram 2.9.
Replace the front fascia panel.
Diagram 2.8
14194
Diagram 2.9
16
FLUROCYL
COMMON 230V MAINS TERMINAL BLOCK
E
TERMINAL BLOCK
230V~50Hz MAINS SUPPLY
L
N
E
Double
pole
isolator
RETURN PIPE
AT 3A
FUSED AT 3A
ENL E N 21L
br
blg/y
N L 3 4 5 6 7 8 9
LINKE N L
10
ADDITIONAL TERMINAL BLOCK
FLUROPRO CONTROLLER
230v~ PCSA
NTCA
TAC1
TAC2
GAINR
L
BROWN br BLUE b BLACK bl ORANGE or WHITE w PURPLE p GREEN gn GREY g GREEN /YELLOW g/y
KEY
bl
2 Installation
14238
Wiring diagram
17
Diagram 2.10
3 Commissioning
‘A’ PORT‘B’ PORT
BA
LEVER
3.1 Filling the secondary circuit
IMPORTANT: Risk of damage! Do not manually open the
temperature/pressure relief valve or the expansion vessel for venting purposes. Any foreign matter in the pipework may cause damage to the valve seats.
Make sure the cylinder drain valve is closed.
Open all cold and hot water taps and the corresponding outlets.
Open the mains water supply to the Flurocyl and ll it with water until it ows freely out of the outlets. Make sure all air
bubbles have been removed.
Close the outlets and check the system for leaks. Check in particular the immersion heater connection for leaks.
The system must now be ushed thoroughly.
Open the hot water taps at the opposite ends of the systems
and let the water ow out for at least 5 minutes.
Close the hot water taps.
3.2 Setting the thermostatic mixing valve
The hot water from the solar cylinder can be set to a desired maximum temperature between 30 °C and 70 °C by mixing hot and cold water.
Set the hot water thermostatic mixing valve with the adjusting knob to maintain the householders desired temperature at the hot water taps.
IMPORTANT: Risk of being scalded by hot water! Set the thermostat mixer to 60 °C or below and check the temperature at a hot water tap to ensure effective protection against scalding.
3.3 Reheat circuit (boiler circuit)
NOTE: Do not use the pressure relief valve of the boiler (if
applicable) for bleeding.
Flush the entire primary central heating system with cold and hot water. Fill and bleed the central heating system according to the installation manual of the boiler.
Set the lever on the motorised 2 port valve to MANUAL and lock it in this position, see diagram 3.1.
Fill and bleed the central heating system after draining it completely.
Unlock the lever on the motorised 2 port valve by setting it back to AUTO.
Start up the boiler, refer to section 3.4, until the solar cylinder is at operating temperature and all radiators in the system are warm. Then drain the entire central heating system again to remove any residue from the pipes. Fill and bleed it again afterwards as described above.
3.4 Starting up the boiler
Switch on the main switch of the boiler.
Make sure the control device and the thermostats are set in such a way that heating is necessary.
Check whether the boiler starts up and the water in the solar cylinder and radiators is heated up according to the hot water and room thermostat settings.
Perform the commissioning and testing procedures in accordance with the installation manual for the boiler.
Motorised 2 port valve
GB: It is a requirement that the “Benchmark” Installation,
Commissioning and Service Record is completed and left with the user.
IE: it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S.813. An example of this is given in the current edition of I.S.813.
Diagram 3.1
3.5 Handing over to the householder
l Hand over all manuals to the householder. l Advise the householder to keep the manuals near to the
system. l Draw special attention to the safety instructions which the householder must follow. l Review the user instructions with the householder and answer any questions. l Show the householder how to operate the solar control, CH control and any separate DHW control. l Inform the householder that the cylinder temperature is factory set at 65°C and that the DHW temperature can be adjusted using the TMV by the installer. l Inform the householder that the immersion heater is intended as a standby device and should not be used simultaneously with the boiler to heat the cylinder. l Inform the householder that they are not permitted to change the settings made on the solar system. l Inform the householder that to ensure the continued efficient and safe operation of the solar system it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the installation conditions and usage, but in general, once a year should be enough. lInform the householder that the boiler and solar cylinder
should be serviced by a qualied engineer annually.
Leave these instructions and the “Benchmark” Installation, Commissioning and Service record document with the user.
14184
18
4 Inspection and Maintenance
4.1 Checking the temperature / pressure relief valve and expansion relief valve
Actuate each valve manually by turning the valve cap and
check whether the water ows unhindered to the discharge point via the tundish. Make sure both valves t properly in idle
position.
4.2 Checking the charge pressure of the expansion vessel
Block the water supply and open the nearest hot water tap to reduce the pressure from the secondary water system.
Check the pressure of the expansion vessel at the measurement point with a pressure gauge. If the pressure is below 3.0 bar, increase it with an appropriate air pressure pump.
NOTE: Only use original spare parts from Glow-worm for the replacement of parts.
4.3 Maintenance Checklist
Reheating
Check the circulation pump annually.
Check the timer/time programme settings annually.
Reheating: does it deliver the desired deactivation temperature? annually.
Solar cylinder
Bleed the heat exchanger if necessary annually.
Check the connections for leaks annually.
Check the temperature and pressure relief valve annually.
Checking the expansion relief valve annually.
19
5 Fault Finding
The following tables provide information on possible malfunctions during the operation of the solar cylinder as well as their cause and remedy.
NOTE: Only use original spare parts from Glow-worm. for the replacement of parts. We recommend making a maintenance agreement.
Malfunction Cause Remedy
Solar cylinder
The cylinder cools down at night. The
ow and return temperatures vary after
switching off the pump. The collector temperature is higher than the air temperature at night.
Reheating is not working. The boiler runs for a short time, goes off and then back on again. This is repeated until the cylinder is at its target temperature.
Only cold or lukewarm water comes out of the taps.
1. The gravity brake is blocked. 1. Check the position of the blue handle.
2. Check the gravity brake for tightness (jammed cuttings, particles of dirt in the sealing face).
3. Do not connect the solar heat exchanger directly, rather pull the supply pipes downwards and then upwards to the collector (syphon supports the gravity brake) or install a 2-port valve, which is switched on at the same time as the pump.
2. One-pipe circulation in the event of short pipe networks with low pressure loss.
1. Air in the reheating heat exchanger. Bleed the reheating heat exchanger.
2. Heat exchanger surface area too small.
1. Cold and hot water connections on the cylinder have been mixed up.
2. Hot water thermostat mixer set too low.
3. Solar heating insufcient; boiler does
not reheat. External control device faulty.
Air in the reheating heat exchanger
Cylinder temperature sensor defective.
Install a gravity brake (as close as possible to the cylinder).
Compare the specications of the boiler
manufacturer with those of the cylinder manufacturer. The problem may be able to be solved by a higher setting of the
ow temperature at the boiler.
Turn off the cold water supply, then
let water ow out via the hot water
connection. Only a few litres of water
ow out if the connection is laid correctly.
The inlet of the hot water draw-off pipe then rests in the air space; no further emptying is possible. If the entire solar cylinder runs empty via the hot water connection, the connections have been laid incorrectly. Change the connections!
Increase the setting.
Check whether the boiler is working.
Check whether the external control device is working. Check whether the two port valve is in the hot water position. Replace the two port valve.
Bleed the reheating heat exchanger.
Check the thermal cut out and reset it. Replace the cylinder thermostat.
Table 5.1 Fault Finding
20
5 Fault Finding
Malfunction Cause Remedy
Water ows out of the expansion relief
valve (only when heating up).
Water comes out of the temperature and pressure relief valve (only when heating up).
Dirt on the valve seat of the expansion
relief valve.
Pressure limiting valve defective. Switch off the boiler and immersion
Expansion vessel defective. Check the pressure in the expansion
Expansion relief valve defective. If the pressure is normal, replace the
Dirt on the valve seat of the temperature
and pressure relief valve.
Temperature control of the boiler
defective.
Cylinder temperature sensor defective. Check the cylinder temperature sensor
Two port valve defective. Check whether the two port valve is
Temperature and pressure relief valve
defective.
Immersion heater defective. Check the temperature sensor of the
Check the expansion relief valve and reset it manually.
heater and check whether the pressure behind the pressure limiting valve is lower
than 3.0 bar if water ows out only when
heating up. If so, replace the pressure limiting valve.
vessel. If the pressure is insufcient,
re-establish the pressure and check whether the equalisation tank maintains the pressure.
expansion relief valve.
Check the seat of the temperature and pressure relief valve and reset it manually.
Check the temperature control of the boiler if water only comes out when reheating with the boiler. Check whether the two port valve switches to the heating position after reaching the cylinder temperature.
and the corresponding thermal cut outs and replace the temperature sensor and reset the thermal cut outs if necessary.
working and replace it if necessary.
Replace the temperature and pressure relief valve if water only comes out when heating up with the immersion heater.
immersion heater and the corresponding thermal cut out and replace the immersion heater if necessary.
Table 5.1 Fault Finding (continued)
21
222324
Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT
0020055006
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
0020055006-02 07.07
Loading...