This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler,
without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the
current issue of the Statutory Requirements. The requirements are: The installation of this boiler must be carried out by a
competent person in accordance with the current rules in force in the countries of destination at the time of installation.
Manufacture's instructions supplied. Manufacture's instructions must not be taken as overriding statutory requirements.
Note: The boiler serial number is marked on the label attached to the inside of the drop down door. Refer to the
'Introduction' section for a description of the basic functions of the boiler. The 'Users' section describes how to safely operate the
boiler.
Mandatory warning for CEE countries
Warning: This appliance is designed, approved and inspected to meet the requirements of the market. The identification plate
located on the inside of the appliance certifies the origin where the product was manufactured and the country for which it is
intended.
If you see any exception to this rule, please contact your nearest Glow-worm dealer.
Thank you in advance for your assistance.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is
deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body ****.
Product/production certified by: Notified body ****.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning
gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment
designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic
compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is
broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or
going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
The insulation is composed of non-combustible material.
Spare Parts
REMEMBER, When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and
performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Hepworth
Heating Ltd.
2000221595
2
Page 3
Contents
CONTENTSDESCRIPTIONSECTIONPAGE No.
Introduction4
INSTRUCTION
FOR USE
INSTALLATION
INSTRUCTIONS
Controls and Lighting5
Clock-timer instructions for use6
Draining6
Safety Devices6
Servicing and Maintenance7
Technical Data18
Dimensions29
Heating System Design39
Domestic Hot Water System Design410
Boiler Schematic510
Boiler Location, Flue and Ventilation611
Fixing Jig Pack712
Piping System Installation812
Boiler Installation914
Flue Installation1014
Electrical Connection1117
Commissioning1218
Safety Devices1322
Changing Gas Type1422
Settings1523
SERVICING
INSTRUCTIONS
Routine Cleaning and Inspection1724
Fault Finding1827
Wiring Diagram1929
Replacement of Parts2030
Spare Parts2140
3
2000221595
Page 4
Introduction
The
XTRAFAST 96 and 120
combination boiler with electronic ignition providing central
heating and instantaneous hot water. The boiler is equipped
with a 4 litre domestic hot water storage vessel that ensures
maximum hot water temperature stability during domestic
demand.
The boiler is of the II
as distributed in the United Kingdom.
The boiler has a fan assisted balanced flue which both discharges
the products of combustion to and draws the combustion air
from the outside of the room.
The boiler is suitable for top outlet flue connection only.
Both the central heating and domestic hot water temperature
are user adjustable from the boiler control panel.
Domestic hot water demand always has priority over heating
demand.
The boiler is designed for use as part of a sealed water central
heating system with fully pumped circulation. The pump,
expansion vessel and associated safety devices are all fitted
within the boiler.
The boiler can be installed against either an external wall or on
an adjacent inside wall, that is, the flue system will pass directly
to the rear or to either side to the terminal fitted on the outside
wall face.
The installation must be carried out by a competent person in
accordance with the relevant requirements of The Building
Regulations, The Water Byelaws, The Building Standards
(Scotland) Regulations and any applicable local regulations.
These instructions should be carefully followed for the safe and
economical use of your boiler.
2H3+
Electrical Supply
WARNING: This boiler must be earthed.
All system components shall be of an approved type and shall
be connected in accordance with the current issue of BS7671
and any applicable local regulations.
All external wiring between the appliance and the electrical
supply and earthing requirements shall comply with the current
IEE Regulations.
Connection of the boiler and system controls to the mains
supply must be through a common isolator and must be fused
3A, maximum. This method of connection must be by a fused
double pole isolating switch, with a minimum contact separation
boiler is a wall mounted modulating
category for use with Natural Gas (G20)
of 3mm on both poles. The switch should be readily accessible
and preferably adjacent to the appliance. It should supply the
appliance only and be easily identifiable as so doing.
Alternatively, an unswitched shuttered socket outlet and 3A
fused 3 pin plug, both to the current issue of BS1363 may be
used provided that they are not used in a room containing a bath
or shower.
Wiring to the boiler must be PVC 85
than 0.75mm
2
(24/0.20mm).
o
C insulated cable, not less
Gas safety (Installation and use) Regulations
In your interests and that of gas safety, it is the law that ALL gas
appliances are installed and serviced by a qualified registered
person in accordance with the above regulations.
Gas leak or fault
If a gas leak or fault exists or is suspected, turn the boiler off and
consult the local gas supply company or your installation/
service company.
Air in the heating system
Persistent air in the heating system may indicate leaks in the
system or corrosion taking place. Call your Installation/Servicing
company.
Overheating safety
In the event of a problem, the overheating safety devices cause
safety shutdown of the boiler. If this happens, call your
Installation/Servicing company.
Boiler controls
The control panel, located at the lower front of the boiler casing,
see diagram 1, allows the boiler to be started, shut down,
controlled and monitored during use.
Flue
Do not obstruct the outside terminal of the boiler.
Ancillary equipment
A range of flue accessories are available including vertical
flues, twin-pipe flues, bends etc.
For further information contact your supplier.
1 - On/Off button
2 - Summer/Winter mode selector
3 - Hot water temperature adjuster
4 - Hot water set point display
5 - Graphic display
6 - Heating temperature adjuster
7 - Heating set point display
8 - Display backlight
9 - Clock-timer
(refer to clock-timer
instructions for use).
Diagram 1
2000221595
1
9900
1.5
4
Page 5
Controls and Lighting
e
Lighting the boiler :
Make sure that:
• The boiler is connected to the electrical supply.
• The gas service cock is open.
Then follow the instructions below :
Press the On/Off button (1)
A
The pressure must be between 1 and 2 bar. If not, the system must be filled by a competent person.
1.5
bar
To stop the boiler : Press button (1)
mode
IO
1
1
2
4
2
23
3
22
4
21
5
20
6
1
9
7
8
1
8
17
9
1
6
10
15
1
1
14
2
1
13
0
1
Hab 264
Setting to the SUMMER position
(Hot water only)
Appuyer sur mode pour sélectionner la position été
Press the mode button to select the summer symbol
mode
1.5
bar
The flame symbol appears
Apparaît lorsque le brûleur
when the boiler is running
est en fonctionnement
Adjusting the hot water temperature
Press + or - to adjust the maximum temperature
Appuyer sur + ou - pour ajuster la température
of the hot water (38°C to 60°C)
maximale de l'eau chaude sanitaire (38°C à 60°C)
Visual indication of set temperature
Visualisation de la température demandée
Setting to the WINTER position
B
Press the mode button to select the winter symbol
Appuyer sur mode pour sélectionner la position hiver
The actual temperature
Température actuelle
of the heating system
dans le circuit chauffage
Adjusting the heating temperature
C
Press + or - to adjust the maximum temperature
Appuyer sur + ou - pour ajuster la température
of the heating (38°C to 87°C)
maximale souhaitée du circuit chauffage
(Heating + hot water)
°C
10
Visual indication of set temperature
Visualisation de la température demandé
1.5
bar
Illuminates when
Apparaît lorsque le
the boiler lights
brûleur fonctionne
mode
mode
50
°C
mode
60
°C
To obtain domestic hot water, open a hot water tap. Hot water always has priority over central heating.
5
2000221595
Hab 261
Page 6
Clock-timer instructions for use
The boiler must be conected to the electrical supply and
switched on.
Setting the time
Rotate the clock actuater mechanism clockwise, by hand, until
the current time is indicated by the arrow, see diagram 2.
Note: The time is set in 24 hour format, for example, 1300 for
1pm.
Reg 049
Diagram 2Diagram 3
Setting the programme "On" and "Off" times
• Select the "On" times by pushing the white tappets to the
outside, see diagram 2.
• Select the 'Off' times by pushing the white tappets to the inside,
see diagram 2.
The clock shown in diagram 2 is set as follows:
ON - 07.00am to 09.00am (7-9)
OFF - 09.00am to 4.00pm(9-16)
ON - 4.00pm to 10.00pm(16-22)
OFF - 10.00pm to 07.00am (22-7)
To override or advance the
clock
The clock has a manual On/
Off switch, see diagram 3,
which operates as follows :
Upper position
Heating On/Off as set by the
tappets.
Middle position
Heating Off continuously
Lower position
Heating On continuously
Reg 050
Draining
Protection against freezing
If the boiler is to be out of use for any long periods during severe
weather conditions, it is recommended that the whole system,
including the boiler, be drained to avoid the risk of freezing.
If in doubt, consult your servicing company.
Safety Devices
Air flow rate safety device
If an obstruction, even partial, of the flue occurs, for any reason,
the built in safety system of the boiler will turn the boiler OFF and
the fan will continue to run. The boiler will be ready to operate
when the fault has been cleared.
Overheat safety
In case of boiler overheating, the overheat thermostat will turn
the boiler off. The thermostat, located on the heat exchanger
flow pipe, will need to be manually reset. To have this done call
a qualified service engineer or Heatcall (Glow-worm’s own
service organisation) using the telephone number behind the
controls cover door or on the front cover of this booklet.
In case of power supply failure
The boiler no longer operates. As soon as power supply is
restored, the boiler will be automatically restarted.
Frost protection
The
XTRAFAST
protects the boiler from freezing. If the boiler is to be left and
there is a risk of frost, ensure that the gas and electrical supplies
has a built in frost protection device that
Draining and filling
Caution: The boiler is installed as part of a sealed system which
must only be drained and filled by a competent person.
are left connected. The frost protection device will light the boiler
when the temperature of the boiler water falls below 6°C. When
the temperature reaches 16°C, the boiler stops.
Note : This device works irrespective of any room thermostat
setting and will protect the complete heating system.
Heating safety valve
CAUTION: A heating safety valve with a discharge pipe is fitted
to this boiler.
The valve MUST NOT BE TOUCHED except by a qualified
registered person. If the valve discharges at any time, switch the
boiler off and isolate it from the electrical supply. Contact your
installation/service company.
Pressure relief valve
CAUTION: A domestic hot water pressure relief valve, with a
discharge pipe is fitted to this boiler.
The valve MUST NOT BE TOUCHED except by a qualified
registered person. If the valve discharges at any time, switch the
boiler off and isolate it from the electrical supply. Contact a
qualified service engineer or Heatcall (Glow-worm’s own service
organisation) using the telephone number behind the controls
cover door or on the front cover of this booklet.
2000221595
6
Page 7
Servicing and Maintenance
To ensure the continued efficient and safe operation of the
appliance it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of the Gas Safety (Installation and Use) Regulations,
Section 35.
Servicing/maintenance should be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
behind the controls cover door.
Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and
have a registration number. Both should be recorded in your
boiler Logbook. You can check your installer is CORGI registered
by calling CORGI direct on: 01256 372300.
1 Technical Data
Cleaning
WARNING: This appliance contains metal parts (components)
and care should be taken when handling and cleaning with
particular regard to edges of sheet metal parts to avoid any
possiblity of personal injury.
The boiler casing can be cleaned using a mild liquid detergent
with a damp cloth, followed by a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you
may damage the paint work.
Boiler casing
CAUTION. Do not remove or adjust the casing in any way, as
incorrect fitting may result in faulty operation. If in doubt, consult
your installation/service company.
Heating
Heating output ajustable from ... (kW)10,411,7
to ... (kW)27,634,6
from ... (BTU/H) 35,485 39,920
to ... (BTU/H) 94,170 118,053
Efficiency(%)****
Maximum heating temperature(°C)8787
Expansion vessel effective capacity (l)712
Expansion vessel charge pressure (bar)0,50,5
Maximum system capacity at 75°C (l)160275
Safety valve,
maximum service pressure (bar)33
Products outlet diameter(mm)6060
Fresh air inlet diameter(mm)100100
Hot water
Hot water output
automatically variable from ... (kW)10,411,7
to ... (kW)27,634,6
from ... (BTU/H) 35,485 39,920
to ... (BTU/H) 94,170 118,053
Maximum hot water temperature (°C)6060
Specific flow rate (for 30°C temp rise)
(l/min.)13,216,5
Threshold flow rate(l/min.)11
Nominal water flow rate(l/min.)11,316,5
Maximum supply pressure(bar)88
Minimum operating pressure(bar)0,70,7
XTRAFAST 96
XTRAFAST 120
Natural Gas (G20)
Ø Burner injector(mm)1,201,20
Inlet pressure(mbar)2020
Burner pressure(mbar)13,814,1
Gas rate maximum(m3/h)3,203,98
Gas rate minimum(m3/h)1,321,48
Electrical supply(V)230230
Maximum absorbed power(W)220220
Level of protectionIP44IP44
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is
**.*%.
The value is used in the UK Government's Standard
Assesssment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been
certified by B.S.I.
7
2000221595
Page 8
60
1 Technical Data
PUMP 96
50
1
2
3
40
30
20
10
Available pressure (kPa) between
heating supply and return lines
0
(10 kPa = 1 m WG)
80
4
5
Pom 010 a
120010008006004002000
Flow rate through heating system (I/h)
PUMP 120
70
60
1
50
3
4
5
2
40
30
20
10
Available pressure (kPa) between
heating supply and return lines
0
120010008006004002000
(10 kPa = 1 m WG)
Bypass fully shut Open 1/4 turn Open 1/2 turn Open 1 turn Open 2 turns
1
2
Flow rate through heating system (I/h)
34
5
Pom 058
2000221595
Diagram 4
8
Page 9
The
XTRAFAST
packages:
- the boiler
- the fixing jig
- the flue system
Lifting Weight:
51,2 kg
2 Dimensions
is delivered in three separate
234
890
7422
65
X = 470 (96)
552 (120)
X
3 Heating System Design
• The
XTRAFAST
• Heating surfaces may consist of radiators, convectors or fan
assisted convectors.
• The
XTRAFAST
heating system without the need for a mixing bottle. The
maximum central heating flow temperature can be set to
53°C.on the boiler printed circuit board during commissioning.
• Pipe sectional areas shall be determined in accordance with
normal practices, using the output/pressure curve (diagram
4). The distribution system shall be calculated in accordance
with the output requirements of the actual system, not the
maximum output of the boiler. However, provision shall be
made to ensure sufficient flow so that the temperature difference
between the flow and return pipes be less than or equal to
20°C. The minimum flow is 400 l/h.
• The piping system shall be routed so as to avoid any air
pockets and facilitate permanent venting of the installation.
Bleed fittings must be provided at every high point of the
system and on all radiators.
is compatible with any type of installation.
can be piped directly to an underfloor
380
Diagram 5
• The total volume of water permitted for the heating system
depends, amongst other things, on the static head in the cold
condition. The expansion vessel on the boiler is pressurised at
0,5 bar (corresponding to a static head of 5 m w.g.) and allows
a maximum system volume of 160 litres for an average
temperature of 75°C and a maximum service pressure of 3 bar.
This pressure setting can be modified at commissioning stage
if the static head differs. An additional expansion vessel can be
fitted to the system if required, see diagram 8.2.
• Provision shall be made for a drain valve at the lowest point of
the system.
• Where thermostatic radiator valves are fitted, not all radiators
must be fitted with this type of valve, and in particular, where the
room thermostat is installed.
• In the case of an existing installation, it is ESSENTIAL that the
system is thoroughly flushed prior to installing the new boiler.
Filling the system
A filling device must be provided to fill the system, see diagram
8.2.
9
2000221595
Page 10
4 Domestic Hot Water System Design
• Copper tubing or plastic hep2o may be used for the domestic
hot water system. Unnecessary pressure losses should be
avoided.
• A flow restrictor limiting the flow through the boiler to a
maximum of 12 l/min is fitted to the boiler.
• The boiler will operate with a minimum supply pressure of 0,7
5 Boiler Schematic
1 - Domestic thermistor
2 - Three way valve
3 - Gas valve
4 - Ignition module
5 - Heating element
6 - Micro accumulation vessel
7 - Burner
8 - Ignition electrode
9 - Combustion chamber
10 - Micro accumulation vessel thermistor
11 - Main heat exchanger
12 - Air pressure switch
13 - Heating safety valve (3 bar)
14 - Electronic control (PCB)
15 - Domestic water flow sensor
16 - Bypass
17 - Domestic heat exchanger
18 - Pump
19 - Expansion vessel
20 - Heating thermistor
21 - Overheat safety thermostat
22 - Flame sense electrode
23 - Fan
24 - Domestic safety valve (10 bar)
25 - Loss of water sensor
A - Heating return
B - Cold water inlet
C - Heating flow
D - Domestic hot water outlet
E - Gas
19
21
bar, but under reduced flow rate. Best operating comfort will be
obtained from a supply pressure of 1 bar.
'Hard Water Areas'
In areas where the water is 'hard', more than 200mg/litre, it is
recommended that a proprietary scale reducer is fitted in the
cold water supply to the boiler.
23
12
11
9
22
7
8
4
18
20
3
2
16
17
1
10026
10
6
5
2000221595
25
AB
10
15
13
14
C
24
D
E
Diagram 5.1
Page 11
6 Boiler Location, Flue and Ventilation
If the appliance has to be stored for any length of time before
installation it should be kept in a safe place where it will not be
a hazard to persons or obstruct any access. Care should be
taken when handling or moving the appliance taking note of the
trucking points on the sides of the carton.
6.1 Clearances
The position of the boiler must be such that there is adequate
space for servicing.
The recommended clearances are:
20 mm either side of the boiler.
600 mm at the front of the boiler.
300 mm below the boiler.
25 mm above the flue elbow.
Note: The boiler must be mounted on a flat wall which is
sufficiently robust to take its weight when full, that is, ** kg. If in
doubt, expert advice should be obtained. In the event of the wall
being found not suitable.
Note: It is permissible to install the boiler with smaller clearances
than those quoted above PROVIDING that adequate
consideration is given for Servicing/Repairs at a later date. If
any doubt exists, contact the Glow-worm Technical Helpline
01773 828100.
The minimum acceptable spacings from the terminal to
obstructions and ventilation openings are shown in diagram
6.1.
The boiler must be installed so that the terminal is exposed to
the external air.
Should any doubt exist as to the permissible position of the
terminal, contact the Glow-worm Technical Helpline 01773
828100.
6.2 Terminal guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be sublject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
to be central over the terminal.
Teminal guard type K3 supplied by:
Tower flue components Ltd.
Morley road
Tonbridge
Kent
TN9 1RA
6.3 Flue options
There are various flue systems to choose from as follows:
Standard horizontal flue pack.
Standard horizontal extended flue pack.
Vertical flue pack.
Twin flue pack.
Extentions, 90° and 45° bends.
Flue options and accessories.
For detailed information refer to flue guide Part No. 223278.
6.4 Cupboard or compartment ventilation
The boiler can be fitted in a cupboard or compartment without
the need for permanent ventilation.
MINIMUM SITING DIMENSIONS FOR THE
POSITIONING OF FLUE TERMINALSMM
A DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR
BRICK, OPENING WINDOWS, AIR VENT, OR
ANY OTHER VENTILATION OPENING300
B BELOW GUTTER, DRAIN/SOIL PIPE75
C BELOW EAVES200
D BELOW A BALCONY OR CAR PORT300
E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES300
F FROM INTERNAL CORNERS AND
EXTERNAL CORNERS300
G ABOVE ADJACENT GROUND OR
BALCONY LEVEL300
H FROM SURFACE FACING THE
TERMINAL600
IFACING TERMINALS1200
J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING1200
K VERTICAL FROM A TERMINAL1500
L HORIZONTALLY FROM A TERMINAL 600
A
A
F
G
UNDER CAR PORT etc.
2816
C
B,C
G
A
E
G
H,I
B,C
K
F
F
G
J
K
K
L
L
K
G
D
F
Diagram 6.1
11
2000221595
Page 12
7 Fixing Jig Pack
The fixing jig is made up, from left to right, as follows:
A - Heating return fitting with isolating valve(v) anddrain knob (u).
B - Cold water inlet fitting with isolating valve (m)and
factory fitted flow regulator and filter (not shown).
C - Heating flow fitting with isolating valve (q), drain
knob (r) and safety valve (s1).
D - Domestic hot water outlet fitting with safety valve
(s2).
E - Gas fitting.
SCREW
(4 OFF)
A
u
ISOLATING
VALVE PLATE
B
v
m
s1
Other components within the fixing jig pack.
F - Hanging bracket
G - wall template
H - copper connections
J - sealing washers
K - sealant (putty)
F
K
9959
C
r
D
E
q
G
J
9880
COPPER
LEFT
HAND
SUPPORT
BRACKET
THE FIXING JIG SHOWN ASSEMBLED
H
CONNECTIONS
AND WASHERS
(7 OFF)
8 Piping System Installation
8.1 Fixing jig
• Remove the contents of the fixing jig pack.
• Secure the left and right hand support brackets to the isolating
valve plate with the securing screws (4 OFF) supplied, see
diagram 7.1.
• Connect the six copper connections and sealing washers to
the isolating valves, see diagram 7.1.
• Remove the wall template, follow the instructions given on the
wall template.
• Note: It is important the hanging bracket and service cock
s2
RIGHT
HAND
SUPPORT
BRACKET
Diagram 7.1
bracket are fitted to a flat and true wall area for correct alignment
with the boiler. If this is cannot be achieved it is acceptable to
pack out the service cock bracket to obtain the correct alignment.
• Position the wall template, see diagram 8.1.
• Mark the position of the holes for the hanging bracket and jig.
• Drill, plug and fix the hanging bracket to the wall using suitable
screws.
• Check that the hanging bracket is level.
• Drill plug and fix the fixing jig to the wall.
• For horizontal flue system, mark the position for the flue hole
as follows:
8.3 Flue to rear of boiler
• Mark correct position of hole from template.
8.4 Flue to side of boiler
• Mark the horizontal centre line for the hole on the rear wall.
Extend the horizontal centre line to the side wall and mark the
vertical centre line of flue hole as shown in diagram 8.1.
2000221595
12
Page 13
8 Piping System Installation
8.5 Cutting the flue hole
• Making allowance for the slope of the flue, cut hole in external
wall, preferably using a core drill. For installations with internal
and external access use a 105 mm diameter core drill.
For installations with internal access only use a 125 mm
diameter core drill.
9684
105
8.6 Important
When cutting the flue hole and when extending the flue centre
line to a side wall, remember that the flue system must have a
fall of about 35 mm per metre of flue DOWNWARD towards the
terminal. There must NEVER be a downward incline towards
the boiler.
8.6 Terminal position
The minimum acceptable spacings from the terminal to
obstructions and ventilation openings are shown in diagram
6.1.
The boiler must be installed so that the terminal is exposed to
the external air.
Should any doubt exist as to the permissible position of the
terminal, contact the Glow-worm Technical Helpline 01773
828100.
8.7 Water connection
Connect the system pipework to the copper connections on the
fixing jig observing the correct flow and return format as shown
in diagram 8.2. Do not subject the isolating valves to heat.
8.8 Heating safety valve and domestic safety
valve discharge, refer to diagram 8.3.
Tee the domestic safety valve outlet pipe to the heating safety
valve outlet pipe and extend horizontally to the outside wall.
WARNING. It must not discharge above an entrance or window
or any type of public access area.
Connect the safety valve discharge pipe to the outlets of both
the heating safety valve and the domestic water safety valve,
the discharge must be extended using not less than 15mm.
pipe, to discharge in a visible position outside the building,
facing downward preferably over a drain.
The pipe must have a continuous fall and be routed to a position
so that any discharge of water, possibly boiling or steam, cannot
create any danger to persons, damage to property or external
electrical components and wiring. Tighten all pipe connection
joints.
65
890
Additional
expansion
vessel
(if required)
470 (96)
552 (120)
Boiler
20
234
Diagram 8.1
Domestic
water
Hot
Cold supply
8.9 Gas connection
• The supply from the governed gas meter must be of adequate
size to provide a constant inlet working pressure of 20 mbar (8
in w.g.).
To avoid low gas pressure problems, it is recommended that the
gas supply is connected using 22 mm pipe.
• On completion, the gas installation must be tested using the
pressure drop method and purged in accordance with the
current issue of BS6891.
8.10 Gas Safety (Installation and use)
Regulations
In your interests and that of gas safety, it is the law that ALL gas
appliances are installed and serviced by a competent person in
accordance with the above regulations.
Return
Heating
circuit
HEATING SAFETY
VALVE 3 bar)
13
Flow
control valve
Bypass
valve
Filling device
Drain point
Sch 173a
Diagram 8.2
DOMESTIC
SAFETY
VALVE
(10bar)
Diagram 8.3
2000221595
Page 14
9 Boiler installation
9.1 Statutory requirements
The installation of this boiler must be carried out by a qualified
registered person in accordance with the relevant requirements
of the current issue of:
The Gas Safety (Installation and Use) Regulations
The Building Regulations
The local water company Byelaws
The Building Standards Regulations (Scotland)
The Health and Safety at Work Act
9.2 Sheet metal parts
WARNING. When installing or servicing this boiler, care should
be taken when handling the edges of sheet metal parts to avoid
the possibility of personal injury.
9.3 Installing the boiler
Prior to starting work, the system must be thoroughly flushed
using a propriety cleanser such as Sentinel X300 to eliminate
any foreign matter and contamination e.g. metal filings, solder
particles, oil, grease etc.
Note. Solvent products could cause damage to the system.
The boiler pack consists of the boiler, base panel, literature,
sealing washers and securing screws.
• Lay boiler on its back.
• Remove all packaging from around the boiler.
• Remove front panel, put in a safe place to avoid damaging it.
• Ensure the plastic plugs are removed from water and gas
pipes. NOTE: There will be some spillage of water.
• Remove transportation timber support bar from bottom rear of
boiler.
• If required the boiler can be stood upright supported by
extending the legs at the front bottom of the boiler.
• Engage boiler upper part onto the hanging bracket.
• Fit the washers between the boiler pipes and the inlet and
outlet fittings on the fixing jig and connect the various couplings
between the boiler and jig.
• Fit the base panel, hook in at the rear secure with the four self
tapping securing screws at the front.
2000221595
14
Page 15
10 Flue Installation
10.1 Top outlet flue - kit 86285
The boiler is only suitable for top outlet flue connection.
10.2 Rear flue systems
(Refer to diagram 10.1). To calculate the length when flueing to
the rear measure wall thickness e plus 160 mm for the outer air
duct and e plus 244 mm for the inner flue duct measurement.
10.3 Flue systems Right or Left
(Refer to diagram 10.1). To calculate the length when flueing to
the side measure wall thickness e plus inside of wall to side of
boiler a add 145(mm) for the outer air duct and wall thickness e
plus inside of wall to side of boiler a add 229(mm) for the inner flue
duct measurement.
• Refer to diagram 10.2 (Table A) for cutting lengths of both flue
duct and air duct pipes for each of the various flue options
available.
Important: All flue cutting lengths must be measured from the
terminal end of the flue pipes, see diagram 10.2 (D).
When the dimension X measured on site is greater than that given
in diagram 10.2 ( Table B ), extensions will be required as
necessary.
Calculation of flue cutting lengths for extended flue
•Using the correct number of extension kits as (Table B), measure
dimensions a and e, see diagram 10.1. Cut both the flue duct and
air duct pipes to the dimensions given in (Table C)
Important: All cutting lengths should be measured from the push
fit joint end of the extension pipe. Do not leave any burrs or sharp
edges on the cut ends of the pipes. Note : maximum horizontal
flue length without bends is 3.5m.
70mm70mm
a
X
9659
a
X
Diagram 10.1
ee
Rear flue
Air Duct pipe : e + 160,Flue duct pipe : e + 244
Note : maximum distance 'x' without extension 756 mm
Side flue (right or left)
Air Duct pipe : e + a + 145, Flue duct pipe : e + a + 229
Note : maximum distance 'x' without extension 990 mm
Table B: Number of extension kits required
Flue optionDimension 'X'No. of
extension kits
Side flue991 to 1991 mm1
(left or right)1991 to 2991 mm2
Note: Maximum flue length for 120 model is 2 metres
Table C: Flue extention cutting lengths (mm)
Rear flue option
Air Duct pipe : e + a - 755,Flue duct pipe : e + a -755
Note : maximum distance 'x' without extension 990 mm
(D)Table A: Flue cutting lengths (mm)
AIR DUCT PIPE
Outer pipe
Ven 089
Cutting length
FLUE DUCT PIPE
Inner pipe
Cutting length
Diagram 10.2
15
2000221595
Page 16
10 Flue Installation
10.4 Installation of flue assembly
• Fit rubber sealing collar (F), see diagram 10.3, into groove
at the outer end of pipe (A).
• Fit air duct pipe (A) into wall with groove to the outside.
• Pull pipe inwards to bring rubber sealing collar hard up
against external wall, see diagram 10.4.
• Fit internal plastic flange (G) onto air duct pipe. Push along the
pipe until engaged against internal wall.
• From inside, insert flue duct pipe (B) into air duct pipe.
• Fit both ‘O’ rings (J) into the flue elbow (C), one at the inlet,
one at the outlet. By necessity, they are a loose fit, apply a small
amount of silicone grease to each ‘O’ ring when fitting.
• Fixing collar (D) over air duct pipe (A) and elbow (C) ensuring
it is the correct way round (Note: the fixing collar can only be
fitted one way due to different diameters of the flue elbow and
air duct).
• Take hold of the flue duct pipe and push gently onto the elbow
outlet taking care not to tear the ‘O’ ring.
• Open fixing collar (D) and locate between elbow and air duct
pipe (A). Close fixing jig.
• Engage the two fixing clips (E) onto the collar (D) and press
down to lock into position. Secure clips with screws provided.
Important: If the flue has been cut, ensure that there are no
burrs that could damage the ‘O’ ring.
• For flue systems less than 1,5 m long, leave the restrictor (a)
fitted in the fan outlet, see diagram 10.5.
• Remove the backing from the self adhesive gasket (H) and
carefully fit gasket to base of flue elbow.
• Fit elbow onto boiler and secure with the four screws (I).
A
B
E
C
D
H
The flue kit 86285 is 1000 mm long and comprises:
- Air duct pipe .......................................................... A
- Flue duct pipe ........................................................ B
- Flue elbow .............................................................. C
- Fixing collar............................................................. D
- Locking clips ............................................................ E
- External rubber sealing collar ............................... F
- Internal flange ....................................................... G
- Gasket ..................................................................... H
- Screws ....................................................................... I
The maximum permissible length (L) for the
concentric flue system is 3.5 m. For flue systems up to 1,5 m length, the restrictor (a) supplied fitted to the boiler,
inside the fan outlet, must be left in place. For longer flue systems, the restrictor must be removed.
For each 90° flue elbow used, (or two 45° elbows) the maximum permissible length (L) must be reduced by 1
metre.
L
Gasket
a
65
234
Hab 249a
2000221595
Diagram 10.5
16
Page 17
11 Electrical Connection
Warning. This boiler must be earthed
The boiler is supplied with a mains lead attached.
Standard colours are Brown - Live, Blue - Neutral, Green and
Yellow - Earth.
All system components must be of an approved type.
Electrical components have been tested to meet the equivalent
requirements of the BEAB.
Connection of the whole electrical system and any heating
system controls to the electrical supply must be through a
common isolator.
Isolation should preferably be by a double pole switched fused
spur box having a minimum contact separation of 3 mm on each
pole. The fused spur box should be readily accessible and
preferably adjacent to the boiler. It should be identified as to its
use.
A fused three pin plug and shuttered socket outlet may be used
instead of a fused spur box provided that:
a) They are not used in a room containing a fixed bath or shower.
b) Both the plug and socket comply with the current issue of
BS1363.
The mains electrical supply must be maintained at all times in
order to provide domestic hot water.
Do not interrupt the mains supply with a time switch or programmer.
WARNING: ON NO ACCOUNT MUST ANY EXTERNAL
VOLTAGE BE APPLIED TO ANY OF THE TERMINALS ON
THE HEATING CONTROLS CONNECTION PLUG.
Warning: This appliance must be wired in accordance with these
instructions. Any fault arising from incorrect wiring cannot be put
right under the terms of the Glow-worm guarantee.
9881
The boiler is supplird with a mains lead
attached. Connect this to the electrical supply.
Diagram 11.1
10036
SIDE CLIPS
Diagram 11.2
Leave link in place for no external controls.
11.1 External controls
The
XTRAFAST
efficiency at all times, but will be most efficient and economical
when connected to a room thermostat.
To gain access to the external control connections, unclip side
clips and hinge up control panel cover, see diagram 11.2.
The boiler will work for heating without a room thermostat being
connected provided that the wire link fitted between the two
terminals of the connector (E) is left in place, see diagram 11.3.
Alternatively, a 230V room thermostat can be used but do not
make any connection to the compensating resistor, see diagram
11.3.
ON NO ACCOUNT must any electrical voltage be applied to any
of the terminals of the external controls plug.
Remote Control
A remote control is available for the Xtrafast. Part no. xxxxxx. If
the remote control is fitted the wire link must be in place on
connector (E), and the Switch SW3 must be adjusted, see
diagram 11.4.
boiler is designed to operate at maximum
11.2 Electrical test
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test earth continuity and short circuit of all cables.
3. Test the polarity of the mains.
Note: For further information, see the building regulations 1991
- Conservation of Fuel and Power - 1995 edition - appendix G,
Table 4b.
E
9878
Set 1 & 2 OFF
for normal
operation
9879
IMPORTANT
VOLTAGE FREE
With
room thermostat
Without room
°C
thermostat
E
E
Diagram 11.3
SW3
ON
12
TOGGLES
ONOFF
1 - Remote Control with without
2 - Parametersopen locked
Diagram 11.4
10023
17
2000221595
Page 18
12 Commissioning
d
Please ensure the “Benchmark” logbook is completed and left
with the user.
The commissioning and first firing of the boiler must only be
done by a qualified registered person.
Gas valve settings. Refer to Section 15 "Settings".
Gas installation
It is recommended that any air is purged from the supply at the
gas inlet test point on the gas valve, see diagram 12.1.
9323
Filling the system 1 to 8
Press the mains 'On/Off' button
1
The warning light will illuminate
➜
v
m
➜
GAS INLET
TEST POINT
The display will indicate 0 bar pressure in the system
2
3
4
5
6
7
8
9
10
1
1
12
0.0
mode
bar
Undo cap on
automatic air
vent on top of
pump and
q
leave undone.
Diagram 12.1
Hab 265
IO
1
24
2
3
2
2
21
2
0
1
9
18
1
7
1
6
15
14
13
0
1
3
2
Open the system filling loop and fill the
4
system until the pressure indicated
on the display is between 1 and 2 bar.
2000221595
Open the boiler isolating valves
(v and q), the slot of the screw
corresponds to flow direction.
Fully open valve m by turning
anti-clockwise.
Reg 008
The pressure must be between 1 and 2 bar
mo
1.5 bar
18
Hab 265
Page 19
12 Commissioning
Bleed each radiator to
5
remove the air, re-tighten
Leave the cap on the
6
pump auto air vent open.
bleed screws.
➜
➜
Reg 008
Ins 061
Make sure the display indicates a system pressure of between 1 and 2 bar. Re-fill
8
system as necessary. (The warning light will extinguish at 1 bar).
The pressure must be between 1 and 2 bar
1
2
4
2
2
3
3
22
4
21
5
20
17
9
1
6
0
1
15
1
1
14
12
13
mode
6
7
8
Open various hot water
7
taps to bleed system.
Ins 062
Hab 265
IO
1
9
18
0
1
1.5
bar
19
2000221595
Page 20
12 Commissioning
e
Lighting the boiler:
Make sure that:
• The boiler is connected to the electrical supply. • The gas service cock is open.
Then follow the instructions below :
A
Press the On/Off button (1)
The pressure must be between 1 and 2 bar. If not, the system must be filled by a competent person.
IO
1
24
2
2
3
3
2
2
4
21
5
20
1
9
8
18
17
9
1
6
10
15
1
1
1
4
2
1
13
0
1
1
1.5
bar
mode
6
7
Hab 264
To stop the boiler: Press button 1.
Setting to the WINTER position
(Heating + hot water)
B
Appuyer sur mode pour sélectionner la position hiver
The actual temperature
Température actuelledans le circuit chauffage
of the heating system
Press the mode button to select
the winter symbol
°C
10
1.5
bar
Illuminates when the
Apparaît lorsque lebrûleur fonctionne
boiler lights
Adjusting the heating temperature
C
Press + or - to adjust the maximum
Appuyer sur + ou - pour ajuster la température
temperature of the heating (38°C to 87°C)
maximale souhaitée du circuit chauffage
Visual indication of set temperature
Visualisation de la température demandé
mode
• Adjust heating temperature to maximum 87°C.
• Check that any external controls, if fitted, are calling for heat
(set room thermostat to maximum).
• Allow the temperature to rise to the maximum value, with all
radiator valves open. The temperature rise will cause release
of the gases contained in the water of the central heating
system.
• Gases driven towards the boiler will be automatically released
through the automatic air vent.
• The gases trapped at the highest point of the system must be
released by bleeding the radiators. Check the burner gas rate
required, ten minutes from lighting. Refer to Data Label on
electrical controls box. Should there be any doubt about the
gas rate it should be checked at the meter.
On reaching maximum temperature, the boiler should be
turned off and the system drained as rapidly as possible whilst
still hot.
• Refill system to a pressure of between 1 and 2 bar and vent
as before.
• Restart boiler and operate until a maximum temperature is
reached. Shut down boiler and vent heating system. If necessary,
top up heating system and make sure that a pressure of at least
1 bar is indicated when system is COLD.
2000221595
60
°C
mode
Hab 261
20
Page 21
13 Safety Devices
The
XTRAFAST
fault conditions, should they occur.
In the event of a fault, the display will indicate, by means of
pictograms and/or letters and numbers, exactly in which area
the fault lies.
Should the boiler fail to operate during Commissioning, the
most likely fault is that the gas supply to the boiler has not been
turned on or purged sufficiently or that there is no pressure in the
heating system. These are indicated as follows :
13.1 No gas supply
• Switch off the boiler at the On/Off
push button.
• Rectify the gas supply problem.
• Restart the boiler by pressing the
On/Off button.
13.2 Insufficient system pressure
13.3 Other faults
These are indicated on the display by a fault code and a
telephone symbol. Further information on the fault codes can
be found in the 'Section 17 Fault Finding'.
incorporates a visual display that indicates
➜
This will be indicated on the
display as a pictogram of a
spark. To rectify this, proceed
as follows:
IO
1
This will be indicated on the
display as a flashing warning
0.3
bar
indicating the system pressure
is low. To rectify this the system
must be re-filled, refer to
'Section 12 Commissioning'.
General safety devices
13.4 Air flow rate safety device
If an obstruction, even partial, of the flue occurs, for any reason
whatsoever, the built in safety system of the boiler will turn the
boiler OFF and the fan will continue to run.
The boiler will be ready to operate when the fault has been
cleared.
13.5 Overheat safety
In case of boiler overheating, the overheat thermostat will turn
the boiler off. The thermostat will need to be manually reset. To
do this remove the front panel and sealed chamber cover,
locate the reset button on the heat exchanger flow pipe, refer
to Sections 16.3, 16.4, 16.5 and diagram 19.15.
13.6 In case of power supply failure
The boiler no longer operates.
As soon as power supply is restored, the boiler will be
automatically restarted.
13.7 Frost protection
The XTRAFAST has a built in frost protection device that
protects the boiler from freezing. If the boiler is to be left and
there is a risk of frost, ensure that the gas and electrical supplies
are left connected. The frost protection device will light the boiler
when the temperature of the boiler water falls below 6°C. When
the temperature reaches 16°C, the boiler stops.
Note : This device works irrespective of any room thermostat
setting and will protect the complete heating system.
21
2000221595
Page 22
14 Changing Gas Type
Should it become necessary to change the gas type, a
modification kit will be required.
This modification must only be carried out by a suitably qualified
engineer.
Conversion natural Gas (G20) to G30/G31 Part No. 86216.
15 Settings
Bypass
The
XTRAFAST
adjusted according to the requirements of the system, refer to
the flow rate pressure curve (diagram 4). The boiler is supplied
with the built-in bypass open a half a turn. It is adjusted by
turning the bypass screw (a), see diagram 15.1. Turn the screw
clockwise to close the bypass. When using thermostatic
radiator valves (TRV’s) on all of the radiators, it is essential that
a separate, adjustable bypass of 15 mm minimum diameter is
fitted between the flow and return of the heating circuit, seediagram 8.2. Any bypass must be fitted before system controls.
boiler has a built-in bypass. This must be
9669
a
Diagram 15.1
2000221595
22
Page 23
16 Routine Cleaning and Inspection
To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced at
regular intervals. The frequency of servicing will depend upon
the particular installation conditions and usage, but in general
once a year should be enough.
It is the law that any servicing is carried out by a competent
person.
All parts are replaced in reverse order to removal.
16.1 Products of combustion check, refer to
diagram 16.1
Note: To obtain a products of combustion reading, unscrew the
left hand sampling point cap on the flue elbow, located on top
of boiler.
Connect the analyser tube onto sampling point.
Switch on the electrical supply and gas supply, then operate
the boiler.
On completion of the test switch off the electrical supply and the
gas supply, remove analyser tube and replace sampling point
cap.
10022
9318
PRODUCTS
SAMPLING
POINT
Diagram 16.1
16.2 Service Check and Preparation.
• Operate boiler and check for any faults that need to be put
right.
• Isolate boiler from the gas and electrical supplies.
• On completion check all gas-carrying parts for soundness with
leak detection fluid.
• Remove boiler casing as follows:
16.3 Front panel
• Unscrew and remove the two front panel retaining brackets
from the top of the boiler.
• Remove panel by lifting up and forward.
16.4 Control panel
• Lift control panel up and lower forwards to gain access to lower
part of boiler.
16.5 Sealed chamber cover
• Unclip the two toggle clips holding the sealed chamber cover,
see diagram. 16.2.
• Lift cover up and off boiler.
Diagram 16.2
9950
Diagram 16.3
16.6 Side panels
• Unscrew and remove the four screws securing lower grille
onto boiler. Unhook grille from rear of boiler and remove.
• Remove three screws from front of each side panel.
• Unclip the toggle clip at the top of each side panel.
• Lift each panel up and then forward to remove.
(For ease of access if required)
16.7 Combustion chamber cover
• Unscrew the two screws securing combustion chamber cover
to combustion chamber then unclip the two toggle clips, seediagram 16.3.
• Remove combustion chamber cover from boiler.
23
2000221595
Page 24
16 Routine Cleaning and Inspection
16.8 Burner, refer to diagram 16.4.
• Undo main gas supply nut from under the sealed chamber.
Note: The washer between main burner and main burner gas
supply must be kept for use on reassembly.
• Pull off ignition leads from gas control valve.
• Slacken but do not remove, two burner support screws at rear
of burner chamber using a long blade screw driver.
• Ease burner from boiler by lifting up from key hole slots,
threading the gas supply and ignition leads through the grommets
and pulling forwards, (taking care not to damage the insulation).
Before you completly remove the burner pull off flame sense
lead from flame sense electrode.
• Clean burner by washing in soapy water. Dry thoroughly
before refitting.
• When refitting burner ensure that the burner locates and seals
correctly through the grommets.
Note: To gain access to injectors for removal, refer to Section,
19.24 in Replacement of Parts.
9661
GROMMETS
16.9 Heat exchanger, refer to diagram 16.5.
• Disconnect electrical leads from fan.
• Unscrew and remove two fan retaining screws from the right
hand side edge of fan mounting plate.
• Remove fan with mounting plate attached by pulling forward
and out of boiler.
• Remove air pressure switch sensing tube from sensing probe
on flue hood.
• Remove screws securing flue hood to rear panel
• Lift flue hood clear of heat exchanger and examine for debris.
• Using a soft brush or vacuum clean as required.
DO NOT USE ANY TOOL LIKELY TO DAMAGE PAINTED
FINISH OF HEAT EXCHANGER.
Note: When re-fitting fan, make sure that the two lugs on the fan
mounting plate engage in the flue hood
FAN RETAINING SLOTS
9670
9664
BURNER
SECURING
SCREWS
MAIN GAS
SUPPLY NUT
9344
IGNITION
LEADS
9665
9662
9663
2000221595
9667
IGNITION
ELECTRODE
ASSEMBLY
FLAME SENSE
ELECTRODE
Diagram 16.4
9660
Diagram 16.5
24
Page 25
16 Routine Cleaning and Inspection
16.10 Spark and Sense Gaps
• Check that the spark and sense gaps as shown in diagram
16.6.
16.11 Flue system
• Check externally to make sure that flue is not blocked
• Inspect flue system to make sure that all fittings are secure.
16.12 Operation of fan
• Switch on electrical supply and turn on gas.
• Light burner by opening a hot water tap.
• Check that fan operates when burner lights and stops when it
goes out.
16.13 Cold water inlet filter
Drain down domestic hot water circuit of boiler only, as follows:
• Close isolating valve/throttle (m) on cold water isolating cock,
see diagram 7.1.
Note: This valve is closed when screwed fully clockwise.
• Undo connecting nut from boiler cold water inlet connection.
• Clean and inspect filter, replace if necessary, see diagram
16.7.
• With both filter and restrictor in place, reconnect connecting
pipe to inlet connection and tighten.
• Fully open isolating valve/throttle on cold water inlet and check
for leaks.
4mm
9877
4mm
SPARK GAP
9876
5mm
SENSE GAP
FLOW
RESTRICTOR
AND COLD
WATER INLET
FILTER
Diagram 16.6
9875
Diagram 16.7
25
2000221595
Page 26
17 Fault Finding
Fault finding must be carried out by a competent person.
WARNING. Always isolate the boiler from the electrical supply
before carrying out any electrical replacement work.
On completion of a fault finding task that has required the
disconnection and making of electrical connections then check
for earth continuity, polarity and resistance to earth must be
carried out.
If any gas-carrying components are disturbed, removed or
replaced it will be necessary on completion to check for gas
soundness with leak detection fluid.
Before trying to operate the boiler make sure that :
• All gas supply cocks are open and that the gas supply has
been purged of air.
Table 2
VoltageMeasured valueMeasuring point
230 Volt230 V ACBetween terminals H8.1 and H8.2
24 Voltmaximum 33V DCBetween terminals B2.4 and B2.7
minimum 20V DC
15 Volt15V + 0.5VBetween terminals B2.4 and B2.2
Display5V + 0.5VBetween terminals B2.4 and B4.2
• There is a permanent mains supply to the boiler.
• The heating system pressure is at least 1 bar.
• The fuse on the PCB is intact.
Preliminary electrical system checks, as outlined in a multimeter
instruction book, are the first checks to be carried out during a
fault finding procedure.
Should there be any doubt about the voltage supply to any of
the components, it is possible to carry out a simple electrical
test to ensure all is operational in that area.
To carry out the electrical test, gain access to the main Printed
Circuit Board (PCB) , and measure the voltages according to
table 2.
The In-board fault diagnostic system. Should a fault
occur on the boiler, the warning LED at the top of the
user displaywill illuminate and the LCD display will
indicate the precise area where the fault has occurred.
Sec 052
09FF
A fault code is displayed on the left hand side of the LCD display, whilst at the same time, the letters appear with a
telephone symbol.
Thermistor values
The following table applies to the central heating,
domestic hot water and storage vessel thermistors:
Temperature (°C)Resistance (Ω)
0 ...................................... 32565
5 ...................................... 25345
10 ..................................... 19875
15 ..................................... 15700
20 ..................................... 12500
25 ..................................... 10000
30 ...................................... 8060
35 ...................................... 6535
40 ...................................... 5330
45 ...................................... 4370
50 ...................................... 3605
55 ...................................... 2989
60 ...................................... 2490
65 ...................................... 2085
70 ...................................... 1755
75 ...................................... 1480
80 ...................................... 1260
85 ...................................... 1070
90....................................... 920
95....................................... 785
100...................................... 680
System pressure sensor
The resistance of the sensor at various pressures is
as follows :
0 bar ...................... between 280 Ω and 320 Ω
1 bar ...................... between 195 Ω and 220 Ω
3 bar ...................... between 93 Ω and 143 Ω
2000221595
26
Page 27
17 Fault Finding
TO AID FAULT FINDING REFER TO DIAGRAMS 5.1 AND 18.1.
CODECHECKDISPLAY SYMBOL
00
02
04
05
06
or
07
or
08
09
12
TYPE OF FAULT
NO FAULT
AIR FLOW SAFETY
NO IGNITION
Note: MAX. IGNITION TIME
= 7 SECONDS
OVERHEATING
HEATING THERMIST OR
ON FLOW PIPE
DOMESTIC THERMISTOR
ON DHW PIPE
TEMPERATURE ON
STORAGE VESSEL
LOSS OF WATER
PRESSURE SENSOR.
USER INTERFACE
NO FAULT
THIS SYMBOL IS NOT INSTANTANEOUS BUT IF IT APPEARS
AFTER 40 SECONDS, CHECK
• THE FLUE SYSTEM FOR A BLOCKAGE, EXCESS LENGTH.
• CHECK THE AIR PRESSURE SWITCH.
• CHECK THE ELECTRICAL CONNECTIONS.
IF THE BURNER LIGHTS WITH A TRAIN OF SPARKS
AND GOES OUT AFTER 7 SECONDS.
• REVERSE LIVE AND NEUTRAL TO THE ELECTRICAL PLUG.
• CHECK THE ELECTRODE AND ITS CORRECT CONNECTION.
• CHECK IGNITION BOX.
• CHECK THERE IS MORE THAN 40V BETWEEN LIVE AND EARTH.
IF THE TRAIN OF SPARKS DOES NOT LIGHT THE BURNER, CHECK .
• THE GAS TAP ON THE INSTALLATION IS OPEN.
• THE GAS CONTROL VALVE.
• CHECK THE IGNITON BOX.
• PUMP BLOCKED OR ITS CONDENSER OUT OF SERVICE.
• ISOLATING COCKS CLOSED ON JIG.
• DEFECTIVE OVERHEAT THERMOSTAT.
• BLEED OUT AIR.
• CHECK THE ELECTRICAL CONNECTIONS.
• CIRCUITS OPEN OR SHORT CIRCUIT.
• CHECK RESISTANCE OF THE THERMISTOR. (12500 ohms AT
20°C. 1750 ohms AT 70°C).
• UNCLIP THE THERMISTOR FROM THE PIPE, IF THE BOILER
RE-LIGHTS WHEN THE THERMISTOR IS OPEN CIRCUIT.
REPLACE THE THERMISTOR.
• IF FAULT PERSISTS. REPLACE MAIN CONTROL BOARD (PCB).
• CHECK HEATING THERMISTOR (MAY BE UNCLIPPED) OR
THREE WA Y V ALVE FAUL TY .
• FAULTY PUMP.
• LOW HEATING FLOW RATE.
THIS FAULT MAY BE OCCASIONAL AND CAUSED BY
• ELECTROMAGNETIC INTERFERENCE. OTHERWISE
• CHECK THE MAIN CONTROL BOARD (PCB).
THERE IS DEMAND BY THE ROOM TEMPERATURE THERMOSTAT.
• CHECK THE CONNECTIONS.
IF FAULT PERSISTS, REPLACE MAIN CONTROL BOARD (PCB).
• CHECK THAT CONTACT 1 IS ON 1. OR MEASURE A RESISTANCE
< 10 ohms BETWEEN B5.1 AND B5.2.
• CHECK ROOM THERMOSTAT CONNECTIONS OR MEASURE A
RESISTANCE < 50 ohms BETWEEN B3.1 AND B3.2.
• CHECK THREE WA Y V AL VE.
• CHECK THREE WA Y V AL VE MOTOR (SWITCHING).
• CHECK THE DIRECTION OF
• CLIP ON THREE WAY VALVE (READABILITY OF SYMBOL ).
• MEASURE THE MICROFAST RESISTANCE = 1000 ohms
BETWEEN H4.1 AND H4.3.
• READ THE VALUE OF FLOW RATE DETECTOR ON CODE 07 OF
INFO MENU. IT WILL READ HOT WATER OUTPUT (L/MIN.)(x10)
VALID RANGE 00,,,199 NOTE: DIVIDE THE VALUE BY 10.
IF = 0 THE DETECTOR IS BLOCKED OR FAILED. IF = 0 THE
DETECOR IS BLOCKED OR THE
MAIN CONTROL BOARD (PCB) HAS FAILED.
• CHECK THAT THE HOT WATER CIRCUIT HAS BEEN BLED
PROPERLY (ANY AIR BUFFER MAY ACTIVATE THE FLOW RATE
DETECTOR WHEN THE T APS ARE TURNED ON).
R
O
K
27
2000221595
Page 28
18 Wiring Diagram
FAN
g
p
w
FAN
SENSOR
AIR PRESSURE
WATER
PRESSURE
SENSOR
g
or
w
OVERHEAT
THERMISTOR
bk
bk
THERMISTOR
w
w
CH
w
g
PLUG
THERMISTOR
DHW
rr
SWITCH
ww
3
1
bk
bk
STORAGE VESSEL
THERMISTOR
IGNITION
ELECTRODES
bg/y br
FLOW SENSOR
wg
p
SENSE
ELECTRODE
GAS
CONTROL
VALVE
THREE-WAY
CLOCK-TIMER
bk
VALVE
IGNITION
MODULE
CHASSIS
EARTH
bk
4
3
2
1
HEATING
ELEMENT
USER INTERFACE
NOTE 'E'
J2
J19
J4
230V~50Hz
PERMANENT
MAINS SUPPLY
FUSED AT 3A
br
g/y
J3
NOTE 'F'
b
J16
CHASSIS
EARTH
g/yg/y g/y
J6
S2
ON/OFF
SWITCH
bk
bk
H2
H8
H5
H4
J5
J9
J8
SW3
S1
H1
H3
H6
FUSE
125mAT
NOTE 'E' VOLTAGE FREE room thermostat connection or link.
NOTE 'F' Optional remote control unit with
programmable room stat connection Part No. 86774
PUMP CH
b
br
bk- BLACK
w- WHITE
or- ORANGE
g/y- GREEN/
bk bk
br
b
bk
br
b
g/y
b
br
br
g/y
b
KEY
YELLOW
br - BROWN
b- BLUE
p- PINK
g- GREY
r- RED
Diagram 18.1
9683
2000221595
28
Page 29
19 Replacement of Parts
IMPORTANT INFORMATION
WARNING: Before commencing the replacement of any
component, isolate appliance from electrical supply and turn off
gas at service cock.
Replacement of parts must be carried out by a competent
person.
When replacing components it may be necessary to renew
sealing washers, gaskets and 'O' rings. If new ones are
supplied with replacement components they must be used.
All parts are replaced in reverse order to removal.
If any gas-carrying components are disturbed, removed or
replaced it will be necessary on completion to check for gas
soundness with leak detection fluid.
19.1 Domestic hot water thermistor, refer to
diagram 19.1
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Locate domestic hot water thermistor on hot water flow pipe on
right hand side of boiler adjacent to gas control valve.
• Unclip thermistor from pipe.
• Disconnect leads from thermistor.
• Fit leads to replacement thermistor and fit thermistor to pipe.
The polarity is not important.
19.2 Central heating thermistor, refer to
diagram 19.2
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Locate central heating thermistor on heating flow pipe on
centre of boiler.
• Unclip thermistor from pipe.
• Disconnect leads from thermistor.
• Fit leads to replacement thermistor and fit thermistor to pipe.
The polarity is not important.
19.3 Fan, refer to diagram 19.3
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Disconnect power supply leads and earth lead from fan.
• Unscrew and remove two fan retaining screws at front edge of
mounting plate.
• Remove fan with mounting plate attached by pulling forwards
out of the boiler.
• Remove fan from mounting plate.
Note: When re-fitting, make sure that the two lugs on the fan
mounting plate engage in the flue hood.
• Reconnect electrical leads.
9672
9671
➜
DOMESTIC
HOT WATER
THERMISTOR
Diagram 19.1
CENTRAL
HEATING
THERMISTOR
➜
Diagram 19.2
➜
➜
➜
➜
FAN
RETAINING
SLOTS
19.4 Fan sensor, refer to diagram 19.3
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the 2 fan sensor retaining screws.
• Remove the fan sensor and disconnect the electrical
connection, avoid straining the cables.
Diagram 19.3
➜
9670
➜
29
2000221595
Page 30
19 Replacement of Parts
19.5 Air pressure switch, refer to diagram 19.4
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Locate air pressure switch situated inside combustion chamber
on top right hand side.
• Remove air pressure switch tube.
• Disconnect air pressure switch electrical connections.
• Undo screws on top of boiler securing air pressure switch to
boiler and remove switch.
19.6 Domestic water flow sensor, refer to
diagram 19.5.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Drain down domestic hot water circuit of boiler only, refer torelevant part of Section 16.13.
• Locate flow sensor on cold water inlet pipe to boiler inside
controls area.
• Carefully pull off electrical connector from flow sensor.
• Pull out slotted metal clip securing cold water inlet pipe to flow
sensor disconnect union nut securing cold water inlet pipe to
isolating valve and remove.
• Pull out slotted metal clip securing flow sensor to pump
mounting, remove sensor.
19.7 Printed circuit board (PCB), refer to
diagram 19.6
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover to gain
access to PCB, see diagram 11.2.
• Carefully pull off electrical connections to PCB.
• Unclip and lift out PCB.
Note: Make sure that PCB connections are fully pushed onto
replacement PCB.
19.8 Central heating pump, refer to diagram
19.7.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Drain down central heating water circuit of the boiler only, as
follows:
• Close isolating valves (q) and (v) on central heating isolating
cocks (A) and (C) ,see diagram 7.1.
10037
9674
➜
➜
➜
➜
➜
➜
➜
➜
➜
➜
AIR PRESSURE
SWITCH
Diagram 19.4
WATER
FLOW
SENSOR
Diagram 19.5
Diagram 19.6
CENTRAL
HEATING
PUMP
➜
Diagram 19.7
9673
9680
2000221595
30
Page 31
19 Replacement of Parts
Note: These valves are closed when slots are at right angles to
direction of flow.
• Drain boiler by opening drain valves (r) and (u), see diagram
7.1.
Note: it is not necessary to drain down the entire heating system
to carry out this work.
• For ease of access if required remove the left hand side panel,
refer to Section 16.6.
• Undo two fixing screws and remove pump retaining bracket
from front of pump.
• Pull out slotted metal clip securing pump outlet hose connection
to pump.
• Remove pump from pump block by lifting up at front and pulling
forward.
• Gain access to the pump electrical connection box and remove
cover.
• Disconnect pump cable from pump (avoid straining cables).
• Transfer automatic air vent to replacement pump.
• Re-connect electrical connection.
• Open isolating valves on flow and return connections, refill,
and pressurise boiler.
• Check for leaks.
PLATE TO PLATE
HEAT EXCHANGER
➜
9677
➜
➜
➜
PIPE
CONNECTION
➜
Diagram 19.8
9682
19.9 Hot water plate to plate heat exchanger,
refer to diagram 19.8.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Drain down central heating and domestic hot water circuits of
boiler only ,refer to relevant parts of Sections 16.13 and 19.8.
• To gain access to the left hand securing screw. Disconnect the
domestic water flow sensor at the plate to plate heat exchanger
and cold water inlet. Remove the domestic hot water flow
sensor, refer to Section 19.6.
• Supporting domestic heat exchanger, unscrew and remove
two screws securing it onto pump mounting and 3-way valve/
bypass housing.
• Remove plate to plate heat exchanger from boiler.
• Fit replacement plate to plate heat exchanger using new seals,
supplied.
Note: Plate to plate heat exchanger mounting screws are offset
to ensure correct fitting of replacement.
THREE WAY
VALVE
9956
➜
➜
➜
Diagram 19.9
➜
➜
THREE WAY
VALVE/BYPASS
HOUSING
9785
THREE WAY VALVE
ACTUATOR
31
9955
Diagram 19.10
2000221595
Page 32
19 Replacement of Parts
19.10 Three-way valve head, refer to diagram
19.9.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Locate 3- way valve in centre of lower controls area.
• Remove electrical plug from valve head.
• Pull out slotted metal clip from valve body and remove valve
head from body.
• Fit replacement valve head.
Note :
1) When refitting clip, ensure that letters OK are as shown.
2) It is not necessary to drain boiler to carry out this work.
19.11 Three-way valve actuator, refer to
diagram 19.10.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Drain down central heating and domestic hot water circuit of
boiler only, refer to relevant parts of Sections 16.13 and 19.8.
Note: It is not necessary to drain down entire heating system to
carry out this work.
• Remove three-way valve head, refer to Section 19.10.
• Pull out slotted metal clips and remove bypass pipe.
• Remove three-way valve actuator from three-way bypass
valve housing.
• Fit replacement three-way valve actuator into three-way
bypass valve housing.
9675
➜
➜
➜
➜
➜
➜
9951
Diagram 19.11
9893
➜
19.12 Bypass, refer to diagram 19.11.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
Drain down central heating water circuit and drain the boiler,
refer to relevant part of Section 19.8.
Note: it is not necessary to drain down the entire heating system
to carry out this work.
Pull out slotted metal clips and remove bypass pipe.
Pull out slotted metal clip securing bypass into bypass housing,
ease up and out bypass valve using a screw driver.
SYSTEM WATER
PRESSURE SENSOR
Diagram 19.12
19.13 System water pressure sensor, refer to
diagram 19.12.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
.Drain down central heating water circuit and drain the boiler,
refer to relevant part of Section 19.8.
• Locate system water pressure sensor at front left hand side of
boiler.
• Pull off slotted metal clip and remove sensor from boiler, take
care not to strain cables.
• Remove electrical connection from sensor.
2000221595
32
Page 33
19 Replacement of Parts
19.14 Gas control valve stepper motor, refer to
diagram 19.13.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Locate gas control valve stepper motor attached to front of gas
valve.
• Disconnect multi-plug from stepper motor.
• Remove screws securing stepper motor onto gas valve body.
• Withdraw stepper motor from gas valve body.
• Fit replacement stepper motor in reverse order to removal
taking care not to damage the ‘O’ ring.
19.15 Gas Control valve assembly, refer to
diagram 19.13.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Disconnect multi-plug from stepper motor.
• Disconnect electrical connections from spark ignition unit
above gas control valve assembly.
• Disconnect electrical connection from R/H side of gas control
valve assembly mounting bracket.
• Undo main gas supply nut from main burner, see diagram
16.4.
Note: The washer must be kept for use on reassembly.
• Undo main gas union nut between gas control valve supply
pipe and gas inlet valve.
Note: The washer must be kept for use on reassembly.
• Unscrew and remove screw securing gas control valve mounting
bracket to boiler frame.
• Withdraw gas control valve assembly, pipes and bracket,
taking care not to strain the electrical connection at the rear of
the gas control valve.
• While supporting the gas control valve assembly disconnect
the electrical connection at the rear of the gas control valve, seediagram 19.13.
• Using old gas control valve as a guide, transfer gas pipes and
bracket from old gas control valve to replacement gas control
valve.
• Refit electrical connector to the rear of the gas control valve
assembly.
• Fit replacement gas control valve assembly into boiler.
• Reconnect gas pipes.
• Refit electrical connections in reverse order to removal.
SPARK IGNITION UNIT
➜
➜
➜
➜
➜
➜
➜
➜
➜
➜
➜
➜
GAS CONTROL
VALVE ASSEMBLY
9325
33
➜
➜
10028
GAS SAFETY VALVE
Diagram 19.13
2000221595
Page 34
19.16 Gas safety valve, refer to diagram 19.13.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove gas control valve assembly, refer to Section 19.15.
• Locate gas safety valve on the rear of the gas valve.
• Unscrew and remove the 2 screws securing the gas safety
valve to the gas control valve.
• Fit replacement gas safety valve in reverse order to removal
taking care not to damage the ‘O’ ring.
• Refit electrical connections, the polarity of the wires to the
modulating coil is not important.
• Refit electrical connector to the gas safety valve.
• Fit replacement gas control valve assembly into boiler.
• Reconnect gas pipes.
• Refit electrical connections in reverse order to removal.
19.17 Spark ignition unit, refer to diagram
19.13.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Disconnect electrical connections from spark ignition unit.
• Remove screw securing spark ignition unit to gas valve
mounting bracket.
• Replace spark ignition unit.
19.18 Heating safety valve (3 bar), refer to
diagram 19.14.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
If safety valve seating is damaged, it will be necessary to
replace safety valve as a complete unit, repair is not possible.
Drain down central heating water circuit and drain the boiler,
refer to relevant part of Section 19.8.
• Remove the base panel, secured with four screws and hooked
in at the rear.
• If lt is not possible to remove the safety valve securing pin
(without straining the pipe work), to remove the safety valve.
Continue following the removal instructions below.
• Remove the heating flow isolating valve by disconnecting the
two union nuts and removing the securing clip.
• Disconnect the heating flow union nut at the safety valve
housing.
• Disconnect safety valve discharge pipe from safety valve.
• Remove the safety valve and housing.
• Remove safety valve securing pin.
• Remove safety valve.
• Fit replacement safety valve.
Note: Apply a small quantity of silicon grease to the safety valve
'O' ring prior to fitting.
• Open isolating valves on flow and return connections, refill,
vent and pressurise boiler.
• Check for leaks.
19.19 Domestic safety valve (10 bar), refer to
diagram 19.14.
Before starting refer to the front of Section 19 Important
information.
If safety valve seating is damaged, it will be necessary to
replace safety valve as a complete unit, repair is not possible.
• Remove the base panel, secured with four screws and hooked
in at the rear, see diagram 19.14.
Drain down the boiler, refer to relevant part of Section 19.8.
• Disconnect safety valve discharge pipe from safety valve.
• Remove wire clip securing safety valve to domestic hot water
outlet fitting and remove safety valve.
• Fit replacement safety valve.
Note: Apply a small quantity of silicon grease to the safety valve
'O' ring prior to fitting.
• Open isolating valves on flow and return connections, refill,
vent and pressurise boiler.
• Check for leaks.
19.20 Main heat exchanger, refer to diagram
16.5 and 19.15.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
Drain down central heating water circuit and drain the boiler,
refer to relevant part of Section 19.8.
• Disconnect power supply leads and earth lead from fan.
• Unscrew and remove two fan retaining screws from the right
hand side edge of fan mounting plate.
• Remove fan with mounting plate attached by pulling forward
and out of boiler.
• Remove air pressure switch sensing tube from sensing probe
on flue hood.
• Remove screws securing flue hood to rear panel
• Lift flue hood clear of heat exchanger.
• Unclip overheat thermostat from heating flow pipe.
• Pull out slotted metal clips securing pipes from heat exchanger.
• Lift heat exchanger up and forwards to remove from boiler
taking care not to damage insulation.
DO NOT DAMAGE PAINTED FINISH OF HEAT EXCHANGER.
• Fit replacement heat exchanger.
Note: When re-fitting fan, make sure that the two lugs on the fan
mounting plate engage in the flue hood.
2000221595
34
Page 35
19 Replacement of Parts
• Open isolating valves on flow and return connections, refill,
vent and pressurise boiler.
• Check for leaks.
19.21 Overheat thermostat, refer to diagram
19.15.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Locate high limit thermostat on heating flow pipe on left hand
side of boiler
• Disconnect electrical connection from thermostat
• Unclip thermostat from heating flow pipe.
• Fit replacement thermostat in reverse order to removal. (Use
heat sink compound supplied).
• Refit connection to thermostat.
19.22 Combustion chamber insulation
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
• Remove main heat exchanger, refer to Section 19.20.
• Remove fan and loosen flue hood, refer to relevant parts ofSections 19.3 and 16.9.
9957
➜
DOMESTIC SAFETY VALVE (10 bar)
➜
➜
➜
➜
➜
➜
HEATING SAFETY VALVE (3 bar)
OVERHEAT
RESET
BUTTON
THERMOSTAT
➜
➜
9958
➜
Diagram 19.14
9687
Front panel insulation
• Lift front insulation panel free from retaining lugs on combustion
chamber cover.
Rear panel insulation
• Pull rear insulation panel free from retaining lug at rear of
combustion chamber by tilting forward.
• Fit replacement insulation panels in reverse order to removal
• Refit combustion chamber cover.
Side Panels
Note: Rear panel must be removed first.
• Pull out side panels free from retaining lugs at side of
combustion chamber by tilting sideways.
• Fit replacement insulation panels in reverse order to removal.
• Refit combustion chamber cover.
➜
➜
➜
➜
Diagram 19.15
35
2000221595
Page 36
19 Replacement of Parts
19.23 Burner
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
• Remove burner, refer to Section 16.8.
Assemble replacement burner, supplied in parts, as follows:
• Fit burner injectors to burner injector bar and tighten.
Note: Make sure that injector size, marked on each injector, is
the same as that given in ‘Section 1 Technical Data’ for the
type of gas being used.
• Fit injector bar into burner, secure with retaining rods.
• Fit replacement burner.
19.24 Burner injectors, refer to diagram 19.16.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
• Remove burner, refer to Section 16.8.
• Remove injector bar retaining nuts and separate the injector
bar from the burner.
• Remove and renew injectors as required from injector bar.
Note: Make sure that injector size, marked on each injector, is
the same as that given in ‘Section 1 Technical Data’ for the
type of gas being used.
• Assemble the burner in reverse order to removal taking care
to engage all parts correctly.
19.25 Ignition electrode assembly, refer to
diagram 16.4
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
• Pull off ignition leads from gas control valve.
• Ease ignition leads through the grommet.
• Undo and remove screws securing electrode assembly onto
burner.
• Fit replacement electrode assembly onto burner in reverse
order to removal.
• When refitting ensure that the grommet locates and seals
correctly.
INJECTOR BAR
9689
RETAINING
NUT (2 OFF)
INJECTOR BAR
9686
INJECTORS
Diagram 19.16
19.26 Flame sense electrode, refer to diagram
16.4
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Remove the sealed chamber cover, refer to Section 16.5.
• Remove the combustion chamber cover, refer to Section
16.7.
• Pull off flame sense lead from flame sense electrode.
• Undo and remove screws securing flame sense electrode onto
burner.
• Fit replacement flame sense electrode onto burner.
9688
2000221595
36
Page 37
19 Replacement of Parts
19.27 User interface board assembly, refer to
diagram 19.17.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Carefully pull off electrical connection from the user interface
board to PCB at (B4).
• Remove the two securing screws to release the control panel
fascia.
• Remove the two user interface board assembly securing
screws to remove the user interface board assembly.
• Fit replacement user interface board.
19.28 Clock-timer, refer to diagrams 19.17 and
19.18.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Carefully pull off electrical connection from the clock-timer to
PCB at (B5).
• Remove the two securing screws to release the control panel
fascia.
• Remove the two clock-timer securing screws to remove clocktimer.
• Fit replacement clock-timer.
9892
➜
B4B5
USER INTERFACE BOARD
➜
MAINS POWER
SWITCH
9891
Diagram 19.17
9890
19.29 Mains power switch, refer to diagram
19.17.
Before starting refer to the front of Section 19 Important
information.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Slide back and up to remove the mains power switch.
• Carefully pull off electrical connections from the mains power
switch.
• Fit replacement mains power switch.
CLOCK-TIMER
Diagram 19.18
37
2000221595
Page 38
19 Replacement of Parts
19.30 Domestic Hot water storage vessel, refer
to diagram 19.19.
For this operation the boiler must be removed from the wall.
Before starting refer to the front of Section 19 Important
information.
• Drain down central heating and domestic hot water circuit of
boiler only, refer to relevant parts of Sections 16.13 and 19.8.
Note: It is not necessary to drain down entire heating system to
carry out this work.
• Disconnect flue system.
• Remove the base panel, secured with four screws and hooked
in at the rear.
• Disconnect boiler pipes onto fixing jig.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Disconnect mains cable and any external controls cables.
• Carefully pull off electrical connection at (H4) from the PCB.
Unclip to release the cable back to the storage vessel.
• Remove the sealed chamber cover, refer to Section 16.4.
Remove the two side panels, refer to Section 16.6. Using the
two lifting handles positioned bottom left of the controls and to
the center right of the combustion chamber lift the boiler off the
hanging bracket and away from the wall.
• From rear of boiler, disconnect domestic pipes from the bottom
of the storage vessel.
• Disconnect electrical connections from vessel.
• Unclip vessel from boiler frame and remove from boiler.
CLIP
POSITIONS
(2 OFF)
➜
➜
➜
9882
➜
DOMESTIC
HOT WATER
STORAGE
VESSEL
9883
➜
➜
2000221595
9884
➜
DOMESTIC HOT WATER
STORAGE VESSEL
Diagram 19.19
38
Page 39
19 Replacement of Parts
19.31 Storage vessel thermistor, refer to
diagram 19.20.
For this operation the boiler must be removed from the wall.
Before starting refer to the front of Section 19 Important
information.
• Drain down central heating and domestic hot water circuit of
boiler only, refer to relevant parts of Sections 16.13 and 19.8.
Note: It is not necessary to drain down entire heating system to
carry out this work.
• Disconnect flue system.
• Remove the base panel, secured with four screws and hooked
in at the rear.
• Disconnect boiler pipes onto fixing jig.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Disconnect mains cable and any external controls cables.
• Remove the sealed chamber cover, refer to Section 16.4.
Remove the two side panels, refer to Section 16.6. Using the
two lifting handles positioned bottom left of the controls and to
the center right of the combustion chamber lift the boiler off the
hanging bracket and away from the wall.
• Remove the insulation from around the storage vessel
• Locate thermistor.
• Disconnect the electrical connection to the thermistor.
• Peel off the self adhesive thermistor.
• Clean the surface prior to fitting the replacement thermistor in
same position as old thermistor.
• Refit vessel.
• Refit boiler onto fixing jig, tighten all connections ensuring that
all sealing washers are fitted before tightening.
• Reconnect flue making sure that all joints are properly
connected.
DOMESTIC HOT
WATER STORAGE
➜
VESSEL
INSULATION
INSULATION
DOMESTIC HOT
WATER STORAGE
VESSEL
9887
Diagram 19.20
9888
➜
Diagram 19.21
19.32 Storage vessel heating element, refer to
diagram 19.21.
For this operation the boiler must be removed from the wall and
the storage vessel removed, refer to Section 19.30.
• Remove the insulation from around the storage vessel
• Locate heating element.
• Peel off the heating element, secured with self adhesive tape.
• Clean the surface prior to fitting the replacement heating
element in same position as old heating element.
• Refit vessel in reverse order to removal.
• Refit boiler onto fixing jig, tighten all connections ensuring that
all sealing washers are fitted before tightening.
• Reconnect flue making sure that all joints are properly
connected.
39
2000221595
Page 40
19 Replacement of Parts
19.33 Expansion vessel, refer to diagram
19.22.
For this operation the boiler must be removed from the wall.
Before starting refer to the front of Section 19 Important
information.
• Drain down central heating and domestic hot water circuit of
boiler only, refer to relevant parts of Sections 16.13 and 19.8.
Note: It is not necessary to drain down entire heating system to
carry out this work.
• Disconnect flue system.
• Remove the base panel, secured with four screws and hooked
in at the rear.
• Disconnect boiler pipes onto fixing jig.
• Remove the front panel, refer to Section 16.3.
• Lower the control panel, refer to Section 16.4.
• Gain access to rear of control panel.
• Unclip side clips and hinge up control panel cover, see
diagram 11.2.
• Disconnect mains cable and any external controls cables.
• Remove the sealed chamber cover, refer to Section 16.4.
Remove the two side panels, refer to Section 16.6. Using the
two lifting handles positioned bottom left of the controls and to
the center right of the combustion chamber lift the boiler off the
hanging bracket and away from the wall.
• Supporting expansion vessel unscrew and remove expansion
vessel retaining nut and screw.
• Remove expansion vessel.
• Fit replacement expansion vessel.
Note: Check that expansion vessel pressure is correct, see
‘Section 1 Technical Data’.
UNION NUT
RETAINING
NUT
➜
EXPANSION
VESSEL
Diagram 19.22
20 Spare Parts
When ordering spare parts, quote the part number and description, stating the appliance model number and serial number
from the data label.
Short parts list
No. ...... Description ......................................... Part No. .......... G. C. No.
1 .......... Domestic hot water thermistor ........ 57213 .............. ******
2 .......... Central heating thermistor ............... 57215 .............. ******