Supplied By www.heating spares.co Tel. 0161 620 6677
220677A.05.95
COSHH
Installation & Servicing Instructions
T o be left with the user
40 GC No. 41 319 20 55 GC No. 41 319 19
Fanned Flue Sealed System Boiler
4746
This is a Cat I 2H appliance
Reference in these instructions to British Standards and Statutory
Regulations/Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used.
Customer Services:
Tel: (01773) 828100
One Contact Total Service
Fax: (01773) 828070
BS 6332
BS 5258
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
*
101
All dimensions in millimetres
KEY:
22mm COMPRESSION
CENTRAL HEATING
Rc1/2(1/2 in. BSPT)
GAS CONNECTION
STD FLUE TERMINAL = 63
*
LONG FLUE TERMINAL = 61
*
174
321
161
783
783
450
SAFETY
VALVE
DISCHARGE
346
3130
108
2.5
66
25
OVERALL DIMENSIONS
The instructions consist of two parts, Installation and
Servicing and Instructions for Use. They are the
property of the user and must be handed to them on
completion of the installation.
1.1 Important Notices
This boiler is for use on natural gas (G20) as distributed
in the United Kingdom and Ireland and cannot be used
on any other gas.
Wherever possible, all materials, appliances and
components to be used shall comply with the
requirements of applicable British Standards.
Where no British Standard exists, materials and
equipment should be fit for their purpose and of suitable
quality and workmanship.
This boiler is not suitable for use out of doors.
THIS BOILER IS FOR USE ONLY IN A SEALED
WATER SYSTEM.
It can be used to provide domestic hot water from a
vented or unvented domestic system.
1.2 Sheet Metal Parts
WARNING. When installing or servicing the boiler care
should be taken when handling sheet metal parts to avoid
any possibility of personal injury.
1.3 Statutory Requirements
The installation of the boiler MUST be carried out by a
Diagram 1.1
competent person in accordance with the relevant
requirements of the current issue of:
Manufacturer’s instructions supplied.
The Gas Safety (Installation and Use) Regulations, The
Building Regulations, The Building Standards (Scotland)
Regulations (applicable in Scotland) Local Water
Company Bye-laws, The Health and Safety at Work Act,
The Electricity at Work Regulations, Control of
Substances Hazardous to Health, The Electricity at Work
Regulations and any applicable local regulations.
Detailed recommendations are contained in the current
issue of the following British Standards and Codes of
Practice,
BS4814, BS5440 Part 1 and 2, BS5449, BS5546,
BS6700, BS6798, BS6891, BS7074 Part 1 and 2,
BS7478, BS7593, BS7671.
Manufacturer’s instructions must not be taken as
overriding statutory requirements.
1.4 BSI Certification
The boiler is certificated to the current issue of BS6332
Part 1, invoking the current issue of BS5258 Part 1 for
performance and safety. It is, therefore, important that
no alteration is made to the boiler, without permission, in
writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating
Ltd., could invalidate the BSI Certification of the boiler,
the warranty and could also infringe the current issue of
the Statutory Requirements.
220677A
2
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
CE Mark
The CE mark on this appliance shows compliance with
Directive 90/396/EEC on the approximation of the Laws
of the Member States relating to appliances burning
gaseous fuels.
The CE mark on this appliance shows compliance with
Directive 73/23/EEC on the harmonization of the Laws
of the Member States relating to equipment designed for
use within certain voltage limits.
1.5 Range Rating
The boiler is range rated and is factory preset to
maximum, but may be adjusted to suit individual system
requirements, refer to Range Rating, Table 2.
1.6 Equipment
The boiler is supplied with an integral expansion vessel,
circulating pump, safety valve, pressure gauge, low
water pressure warning light, automatic bypass valve,
gas cock and valved water connections (with drain
points).
Data Label
The data label is positioned on the inner case cover.
Appliance Data refer to Table 1
MODEL
LIFTING
WEIGHT
TOTAL
WEIGHT
WATER
CONTENT
GAS
CONNECTION
WATER
CONNECTION
ELECTRICITY
RATING
ELECTRICITY
SUPPLY
DATA LABEL
INJECTOR
SIZE
DATA TABLE 1
4055
33.3kg 33.3kg
(73.4lb)(73.4lb)
47.8kg 47.8kg
(105.4lb)(105.4lb)
0.62 litre0.62 litre
(0.136 gal)(0.136 gal)
Rc 1/2 (1/2 in. BSPT)
22mm copper,
return at right, flow at left
135W, internal fuse F1A
240V~50Hz fused 3A
On the inner case front
3.1mm3.6mm
1.7 Gas Supply
The gas installation must be in accordance with the
current issue of BS6891.
The supply from the governed meter must be of adequate
size to provide a steady inlet working pressure of
20mbar (8in wg) at the boiler.
On completion, test the gas installation for soundness
using the pressure drop method and suitable leak
detection fluid. Purge in accordance with the current
issue of BS6891.
1.8 Electrical Supply
WARNING. This boiler must be earthed.
All system components and wiring shall be of the
approved type and comply with and be connected in
accordance with the requirements of current issue of
BS7671 and any applicable local regulations.
Connection of the boiler and system controls to the
mains supply must be through a common isolator and
must be fused 3A maximum. The method of connection
should be, preferably, by a fused double pole isolating
switch, provided it has a minimum contact separation of
3mm on both poles. This switch should be readily
accessible and preferably adjacent to the appliance.
It should supply the appliance only and be easily
identifiable as so doing.
Alternatively an unswitched shuttered socket outlet and
3A fused 3 pin plug both to the current issue of BS1363
may be used provided that they are not used in a room
containing a bath or shower.
Wiring to the boiler must be to the current to the of
BS6500 Table 16.
RANGE RATING
NOMINAL
HEAT
INPUT
NOMINAL
HEAT
OUTPUT
BURNER
SETTING
PRESSURE
APPROX
GAS
RATE
RANGE RATING
NOMINAL
HEAT
INPUT
NOMINAL
HEAT
OUTPUT
BURNER
SETTING
PRESSURE
APPROX
GAS
RATE
3
TABLE 2.
Btu/h
kW
Btu/h
kW
m bar
in.w.g
m3h
ft3h
TABLE 2.
Btu/h
kW
Btu/h
kW
m bar
in.w.g
m3h
ft3h
Complheat 40
minmidmax
38,20044,00049450
11.212.914.5
30,00035,00040,000
8.810.311.7
7.610.313.3
3.14.15.3
1.01.21.4
37.743.449.3
Complheat 55
minmidmax
50,50059,75068,000
14.817.519.9
40,00047,50055,000
11.713.916.1
7.911.414.5
3.24.65.8
1.41.71.9
49.858.967.8
220377B
220677A
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Water System
2.1 General Notes
The installation of the boiler must comply with the
requirements of the current issue of BS6798.
2.2 Safety Valve
The safety valve, preset at 3bar, is an integral part of the
boiler and cannot be adjusted.
2.3 Pressure gauge
A pressure gauge is incorporated into the boiler to
indicate the system pressure.
2.4 Circulating Pump
The circulating pump is integral with the boiler.
The remaining conveying capacity of the pump is shown
in diagram 2.1.
2.5 Expansion Vessel
The boiler has an integral expansion vessel with a
capacity of 8Litres (1.76 gallons), with a charge pressure
of 0.75bar.
WATER FLOW RATE
AT 110C (200F) DIFFERENTIAL
UNIT4055
litre/min.15.321.0
gal/min.3.44.6
Flow rate (gallons/minute)
0
1.1
12
10
8
6
4
2
Available pump head (Ft)
0
5
0
Flow rate (litres/minute)
3.3
2.2
Nominal flow rate
0
C differential
for 11
1015
5.5 6.6
4.4
40
55
202530
3131/B
3.6
3.0
2.4
1.8
1.2
0.6
Available pump head (m)
0
The maximum heating system water content using the
fitted expansion vessel ranges from 119litres with a cold
fill pressure of 0.7bar, to 98litres with a cold fill pressure
of 1.05bar. If, due to a high static head, the cold fill
pressure is higher, then the expansion vessel pre-fill
pressure must be increased, and the maximum system
volume decreased, see the current issue of BS7074
Part 1.
Further information can be obtained from the British Gas
Publication “British Gas Specification for Domestic Wet
Central Heating Systems” and the current issue of
BS4814, BS5449 and BS7074 Part 1 and 2.
2.6 Flow Rate
A valve must be incorporated in the main flow or return
of the system, valve “A” shown in the flow diagram 2.2.
This valve must be lockable and be positioned so that
inadvertent closure or unauthorised interference is not
possible. The design differential is 11oC (20oF) with the
boiler thermostat set at “MAX” which is about 82oC
(180oF). The pump adjuster should always be left at
maximum (3).
REMAINING CONVEYING
CAPACITY OF PUMP
3 LITRES
MAKE-UP
BOTTLE
(if required)
AUTO
AIR
VENT
NON-RETURN
VALVE
ADDITIONAL
EXPANSION
VESSEL
(if required)
RETURN
Diagram 2.1
3131
BOILER
FILLING
POINT
2.7 Bypass
An automatic bypass valve is incorporated in the boiler
pipework it is preset and must not be adjusted.
WATER SYSTEM
DIAGRAMATIC LAYOUT
220677A
4
HEATING
CIRCUIT
'A'
FLOW CONTROL
VALVE
DRAIN
COCK
Diagram 2.2
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Water Systems
2.8 Water Make Up
Provision should be made for replacing water lost from
the system using a make up bottle mounted in a position
higher than the top point of the system, connected
through a non-return valve to the return side of the
heating circuit, see diagram 2.2.
Alternatively, provision for make up can be made using
a filling loop.
2.9 Filling Sealed Water Systems
Provision for filling the system at a low level must be
made.
Three methods of filling are shown in diagram 2.3.
There must be no permanent connection to the mains
water supply, even through a non-return valve.
2.10 Corrosion Inhibitor
Attention is drawn to the current issue of BS5449 and
BS7593 on the use of inhibitors in central heating
systems.
If an inhibitor is to be used in the system, contact a
manufacturer for their recommendations.
2.14 Domestic Hot Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT
SUITABLE AND SHOULD NOT BE USED.
The domestic hot water cylinder must be of the indirect
coil type. It must be suitable for a working at a gauge
pressure of 0.35bar above the safety valve setting.
2.15 Domestic Hot Water System Unvented
Where a storage system will not have a vent to
atmosphere the installation must comply with Building
Regulations and local Water Company bye-laws, see
also the current issue of BS6700.
If fitting into an existing system the local authority must
be informed.
METHOD 1
TEMPORARY
HOSE
COMBINED
CHECK VALVE
AND VACUUM
BREAKER
HEATING
SYSTEM
2819
2.11 Existing Systems
When fitting the boiler into an existing system, special
care should be taken to drain the entire system, including
radiators, then thoroughly cleaning out before fitting the
boiler whether or not adding an inhibitor.
2.12 Draining Tap
A draining tap must be provided at the lowest points of
the system, which will allow the entire system to be
drained. An additional draining tap MUST be fitted
close to the boiler.
Draining taps must be to the current issue of BS2879.
The flow and return isolating valves on the boiler are
fitted with drain points for heat exchanger draining.
2.13 Domestic Hot Water System
General
The domestic hot water service must be in accordance
with the current issue of BS5546, refer also to the
current issue of BS6700.
SUPPLY
PIPE
METHOD 2
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 3
CISTERN
SUPPLY
STOP VALVE
SUPPLY
PIPE
HOSE
UNIONS
SUPPLY STOP
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HOSE
UNIONS
SUPPLY STOP
VALVE
OVERFLOW
SERVICING
VALVE
HOSE
UNIONS
SERVICING
VALVE
SERVICING
VALVE
PRESSURE
REDUCING
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HEATING
SYSTEM
HEATING
SYSTEM
FILLING SEALED
WATER SYSTEMS
5
Diagram 2.3
220677A
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Boiler Location
3.1 General
The boiler may be installed in any room although
particular attention is drawn to the requirements of the
current issue of BS7671 with respect to the installation
of a boiler in a room containing a bath or shower.
Any electrical switch or boiler control using mains
electricity should be so situated that it cannot be touched
by a person using the bath or shower.
The electrical provisions of the Building Standards
(Scotland) Regulations are applicable to such
installations in Scotland.
The boiler must be mounted on a flat wall which is
sufficiently robust to take its complete weight, see
Appliance Data, Table 1.
The boiler may be fitted to a wall made of combustible
material. See diagram 3.1.
3.2 Boiler Clearances
The boiler should be positioned so that at least the
minimum operational and servicing clearances are
provided, see diagram 3.1.
3.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building,
it should be fitted in accordance with the British Gas
Publication “Guide for Gas Installation in Timber
Framed Housing” reference DM2. If in doubt, seek
advice from the local gas undertaking or Hepworth
Heating Ltd.
A compartment used to enclose the boiler must be
designed and constructed specifically for this purpose.
An existing cupboard or compartment modified for the
purpose may be used, refer to the current issue of
BS6798 for guidance.
The doorway opening should be of sufficient size to
allow easy removal of the boiler.
TABLE 3. COMPARTMENT AIR VENTS
VENTILATION
REQUIREMENTS
MODEL
HIGH LEVELLOW LEVEL
VENT AREAVENT AREA
cm
2
2
in
cm
2
in
VENTILATION
1322013220
FROM
ROOM
OR SPACE
VENTILATION
40
55
1812818128
40
66106610
FROM
OUTSIDE
55
91149114
5
3133
186
2
5
3.4 Room Vent
The boiler is room sealed, so when installed in a room or
space, a permanent air vent is not required.
3.5 Cupboard or Compartment Vent
Where the boiler is fitted in a cupboard or compartment,
permanent high and low level ventilation must be
provided.
The vent areas required are given in Table 3.
Where the installation of the boiler will be in an unusual
location, special procedures are necessary, refer to the
current issue of BS6798 for guidance.
Make sure that the cupboard or compartment air vents
are positioned to be clear of obstructions at all times.
5
5*
5
800*
5*
150
❋ WHERE EXTERNAL ACCESS TO
THE FLUE IS NOT PRACTICAL THEN
CLEARANCE MUST BE ADEQUATE TO
PERMIT INSTALLATION OF THE FLUE
MINIMUM CLEARANCES FROM WALLS, CEILING,
FLOOR, CUPBOARD, WORKTOPS AND
INFLAMMABLE MATERIALS
MINIMUM CLEARANCESDiagram 3.1
220677A
6
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Flue
The flue must be installed in accordance with the current
issue of BS5440 Part 1.
The air and flue ducting connect to the top of the boiler
using an elbow which can be positioned to the left or
right hand side or the rear.
The rear and side flue assemblies are designed for
internal installation, but if necessary, due to insufficient
clearances (boiler/flue terminal location) they can be
installed from the outside.
For a wall thickness up to 300mm the flue can be fully
installed from the inside.
For wall thickness of over 300mm the external cut hole
will need to be made good from the outside.
The standard flue will provide the flue length range as
shown in diagram 4.1 and 4.2.
If a longer flue is required, do not extend the ducting. A
1, 2 or 3metre flue system must be used and can be
supplied. This will provide the flue length range as
shown in diagram 4.1 and 4.2.
A "Flue Bend Kit" and "Vertical Flue Kit" can be
supplied.
STANDARD FLUE TERMINAL ILLUSTRATED
'R'
Rear Flue Lengths
R = Wall Thickness
Flue. STD75mm to 598mm
1m75mm to 913mm
2m75mm to 1913mm
3m75mm to 2908mm
REAR FLUE
STANDARD FLUE TERMINAL ILLUSTRATED
Diagram 4.1
3134
3135
'S'
Side Flue Lengths
S='External wall face’to‘boiler mounting frame’
Flue. STD80mm to 547mm
1m80mm to 857mm
2m80mm to 1857mm
3m80mm to 2852mm
SIDE FLUEDiagram 4.2
7
220677A
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
4.1 Terminal Position
The minimum acceptable siting dimensions for the
terminal from obstructions, other terminals and
ventilation openings are shown in diagram 4.3.
The terminal must be exposed to the external air, the
position allowing free passage of air across it at all
times.
Car ports or similar extensions of a roof only, or a roof
and one wall, require special consideration with respect
to any openings, doors, vents or windows under the roof.
Care is required to protect the roof if it is made of plastic
sheeting. If the car port comprises of a roof and two or
more walls, seek advice from the local gas company
before installing the boiler. If the terminal is fitted
within 600mm below plastic guttering and aluminium
shield 1500mm long should be fitted immediately
beneath the guttering or eaves. If the terminal is fitted
within 450mm below painted eaves or a painted gutter,
an aluminium shield 750mm long should be fitted
immediately beneath the guttering or eaves.
4.2 Terminal Guard
4 Flue
A
A
F
G
UNDER CAR PORT etc.
MINIMUM SITING DIMENSIONS
FOR FANNED FLUE
TERMINALS POSITION
E
C
B,C
G
A
G
H,I
B,C
K
F
F
G
J
K
L
L
K
G
2816
D
F
K
A terminal guard is required if persons could come into
contact with the terminal or the terminal could be subject
to damage.
If a terminal guard is required, it must be positioned to
provide a minimum of 50mm clearance from any part of
the terminal and be central over the terminal.
A suitable guard as shown, reference type K3, can be
obtained from:
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING300
BBELOW GUTTER, DRAIN/SOIL PIPE75
CBELOW EAVES200
DBELOW A BALCONY OR CAR PORT200
EFROM VERTICAL DRAIN PIPES AND
SOIL PIPES75
FFROM INTERNAL OR EXTERNAL
CORNERS300
GABOVE ADJACENT GROUND OR
BALCONY LEVEL300
HFROM A SURFACE FACING THE
TERMINAL600
IFACING TERMINALS1200
JFROM OPENING (DOOR/WINDOW) IN
CAR PORT INTO DWELLING1200
KVERTICAL FROM A TERMINAL1500
LHORIZONTALLY FROM A TERMINAL300
Diagram 4.3
0161M
220677A
8
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Preparation
INFORMATION
PLATE
5.1 Unpacking
3137
Remove the top carton from the boiler.
To remove the outer case, slide the information plate up
to access and remove the single securing screw, see
diagram 5.1, unhook the case at the top and lift it off.
Remove the cover of the inner case, secured with four
screws, see diagram 5.2.
Disconnect the gas service cock union and the front
unions of the isolation valves, see diagram 5.3.
Slacken but do not remove the retaining strap screws of
the gas service cock and the isolating valves.
OUTER CASE SECURING SCREW
OUTER CASEDiagram 5.1
GAS SERVICE
COCK UNION
SECURING
31383139
SCREW (4)
INNER CASE
COVER
INNER CASE COVERDiagram 5.2
FLOW
WATER
ISOLATING
VALVE
UNION
RETAINING
STRAP
RETAINING
STRAP
9
RETURN
WATER
ISOLATING
VALVE
UNION
RETAINING
STRAP
Diagram 5.3GAS SERVICE COCK / WATER ISOLATING VALVES
220677A
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Preparation
Remove the two boiler securing screws, see diagram 5.4
then separate the boiler from the mounting frame, by
pulling the location studs/clips apart then unhook it at
the top.
BOILER
SECURING SCREW (2)
3140
6 Installing the Flue
6.1
With due regard to boiler location, clearances and
having determined the flue application, length and
terminal position carry on as follows:
MINIMUM
CLEARANCE
78
149
115 Diameter
FLUE
CENTRE LINE
Top of
Boiler
BOILER
MOUNTING FRAME
LOCATION
STUD(S) and CLIP(S)
BOILER
MOUNTING FRAME
6.2 Marking
The boiler mounting frame is the same width as the
boiler but the flue connection protrudes above. Place the
boiler mounting frame on the wall in the required
position, maintaining minimum clearances,
see diagram 3.1.
3142
CORNER
(RIGHT FLUE)
173
(LEFT FLUE)
173
Diagram 5.4
3143
CORNER
629
FLUE
480
TEMPLATE
BOILER FIXING POINTS
220677A
BOILER
MOUNTING FRAME
FIXING POINTS
300
Diagram 6.1
SIDE FLUE
10
115 Dia.
FLUE
CENTRE
LINES
Diagram 6.2
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installing the Flue
Make sure that the isolation valves are at the bottom
facing forward and that the frame top is horizontal, then
mark the four fixing points through the holes in the two
horizontal straps, do not drill the holes, see diagram 6.4.
Position the flue template on the wall, the arrow points
on the centres of the two upper fixing points previously
marked, see diagram 6.1 which also gives dimensions.
For a rear flue, mark the rear flue position as required,
centre or diameter.
For a side flue, mark the horizontal flue centre line at the
sides of the template. Extend the flue centre line
horizontally left or right to the internal corner where the
flue is required to exit to the outside. Mark the position
of the circular hole, on the flue exit wall, using the
dimensions given in diagram 6.2.
From the flue position marks, check that the flue
terminal will be in a suitable position, see diagram 4.3.
6.3 Flue Hole Cutting
WALL
SLEEVE
WALL SLEEVE
3144
Q
300mm
MAX.
Q
LENGTH
Diagram 6.3
Cut a horizontal hole in the wall, making sure that there
is no downwards slope towards the boiler position,
using, preferably, a core drill, to the diameter shown in
diagram 6.1 and 6.2.
6.4 Wall Sleeve
Take the wall sleeve from the pack. If the wall thickness
“Q” is less than 300mm, cut the wall sleeve to the
required length, see diagram 6.3. If the wall thickness
“Q” is greater than 300mm the sleeve must be fitted
flush with the outside wall face.
Place the sleeve into the hole.
Make good around the wall sleeve at both internal and
external wall faces, through the wall sleeve if internal
access only is available.
For a wall thickness of over 300mm the external wall
face will need to be made good from the outside.
6.5 Boiler Mounting Frame - Fixing
Position the flue template over the flue hole and check
the position of the wall fixing points. Mark the position
of the fixing holes again, if required, see diagram 6.1.
BOILER MOUNTING
FRAME
FIXING
POINTS
3145
Drill the four holes and insert wall plugs to suit
No10x50mm screws.
Secure the boiler mounting frame to the wall using
No10x50mm screws, see diagram 6.4.
Note: Remove the clear plastic protective film from the
sides of the boiler mounting frame.
BOILER
MOUNTING FRAME
11
Diagram 6.4
220677A
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installing the Flue
6.6 Flue Preparation
Rear Flue
Mark and cut the air duct terminal assembly, see diagram
6.5 and the flue duct, see diagram 6.6 to the lengths
required, cutting square and removing any burrs.
Refer to diagram 6.9, mark through the holes in the flue
elbow assembly and drill the flue duct as shown.
Side Flue
Mark and cut the air duct terminal assembly, see diagram
6.7 and the flue duct, see diagram 6.8 to the lengths
required, cutting square and removing any burrs.
Refer to diagram 6.9, mark through the holes in the flue
elbow assembly and drill the flue duct as shown.
6.7 Flue Assembly
Note. At this point if side or front access is restricted,
continue at “External Flue Assembly”.
Internal Flue Assembly
Locate the flue duct into the flue elbow assembly and
secure with the screws provided, see diagram 6.9.
Fully locate the flue elbow and flue duct assembly into
the air duct/terminal assembly as shown, ensuring
correct terminal alignment of the “TOP”,
see diagram 6.10.
STANDARD FLUE TERMINAL ILLUSTRATED
FLUE
DUCT
'R' + 107
'R'
REAR FLUE - FLUE DUCT
1M, 2M, 3M LONG FLUE TERMINAL
STANDARD
FLUE
TERMINAL
'S' + 148
Diagram 6.6
AIR DUCT/
TERMINAL
ASSEMBLY
3147
3148
1M, 2M, 3M LONG FLUE TERMINAL
STANDARD
FLUE
TERMINAL
'R' + 92
'R'
REAR FLUE - AIR DUCT /
TERMINAL ASSEMBLY
AIR DUCT/
TERMINAL
ASSEMBLY
Diagram 6.5
'S'
SIDE FLUE - AIR DUCT /
TERMINAL ASSEMBLY
STANDARD FLUE TERMINAL ILLUSTRATED
3146
FLUE
DUCT
'S' + 163
'S'
SIDE FLUE - FLUE DUCTDiagram 6.8
Diagram 6.7
3149
220677A
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installing the Flue
Mark the position of the air duct terminal assembly
securing holes and drill two 3mm diameter holes through
the air duct/terminal assembly.
Secure the air duct/terminal assembly to the flue elbow
and flue duct assembly with the two self tapping screws
supplied in the loose items pack and then seal with the
tape provided.
Fix the self adhesive seal to the air duct,
see diagram 6.11.
Place the flue assembly into the flue hole. Make sure
that the flue terminal is correctly positioned and
projecting the correct distance from the outside wall
face, see diagram 6.11.
Note: The foam seal is a tight fit in the wall sleeve, so
either the wall sleeve will need to be rigidly fixed in the
wall, that is, the cement has fully set or it can be held
from the other side whilst inserting the flue assembly.
External Flue Installation
Locate the air duct/terminal assembly into the flue elbow
assembly as shown in diagram 6.10, ensuring correct
terminal alignment of the “TOP”.
From outside, place the air duct/terminal assembly and
flue duct into the flue hole. Make sure that the flue
terminal is correctly positioned and projecting the correct
distance from the outside wall face, see diagram 6.11.
Note: The foam seal is a tight fit in the wall sleeve, so
either the wall sleeve will need to be rigidly fixed in the
wall, that is, the cement has fully set or it can be held
from the other side whilst inserting the flue assembly.
FLUE DUCT
3150
Mark the position of the air duct terminal assembly
securing holes and drill two 3mm diameter holes through
the air duct/terminal.
Fix the self adhesive seal to the air duct,
see diagram 6.11.
SCREW (2)
3mm
DRILL SIZE
FLUE
ELBOW
ASSEMBLY
FLUE ELBOW
ASSEMBLY
FLUE ELBOW /
DUCT ASSEMBLY
SECURING
SCREW (2)
Diagram 6.9
3151
AIR DUCT/TERMINAL
& FLUE DUCT
ASSEMBLY
FLUE ASSEMBLY
13
Diagram 6.10
220677A
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installing the Flue
Locate the flue duct into the flue elbow assembly and
secure with the screws provided.
Secure the air duct terminal to the flue elbow with the
two self tapping screws supplied in the loose items pack,
making sure that the flue duct is correctly located into
the terminal, see diagram 6.11, then seal with the tape
provided.
7 Gas, Water and Electrical Connections
7.1 Gas Connection
The gas supply can be connected from below or through
the wall at the rear of the boiler, see diagram 7.1 for
position.
Refer also to Section 1.7.
Make the gas connection to the gas service cock.
Slacken or remove the securing strap, whilst making the
connection. Do not subject the gas service cock to heat.
STD FLUE TERMINAL = 63
*
LONG FLUE TERMINAL = 61
*
FLUE
TERMINAL
FLUE
DUCT
Outside Wall Face
FLUE TERMINAL
'NOTCH' MARKING POSITION OF
SAFETY VALVE DISCHARGE
27
23
33
346
WALL SLEEVE
SEAL
30
3152
Diagram 6.11
3153
27
66
7.2 Water Connections
Provision is made for the flow and return pipes to be
connected from above, if required, passing down either
side of the boiler, see diagram 7.2 for clearances.
Note: Take care that any pipework connected from
above within the boiler mounting frame will clear the
expansion vessel.
Clean out the heating system before connecting the
boiler.
Make the connections to the heating system by way of
the isolating valves, see diagram 7.1.
Slacken or remove the securing straps whilst making the
connections. Do not subject the valves to heat.
Make sure that the drain points on the valves are
positioned toward the front of the boiler, also that the
drain and operating screw heads are accessible.
7.3 Safety Valve Discharge
WARNING. It must not discharge above an entrance or
window or any type of public access area.
A discharge pipe is supplied loose with the boiler, which
when fitted to the safety valve, will terminate below the
boiler at the notch, see diagram 7.1.
GAS
CONNECTION
SECURING STRAPS
SLOT (CLOSED)
GAS SERIVCE COCK
BOILER CONNECTIONS
This must be extended, using not less than 15mm od
pipe, to discharge, in a visible position, outside the
building, facing downward, preferably over a drain.
The pipe must have a continuous fall and be routed to a
position such that any discharge of water, possibly
boiling water, or steam cannot create a hazard to persons
or damage to property or external electrical components
or wiring.
Note. To make future servicing easier it is advisable to
use a compression type fitting when extending the
discharge pipe.
WATER
CONNECTION
DRAIN
POINT
WATER ISOLATION
VALVES
SLOT
(CLOSED)
Diagram 7.1
220677A
14
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Gas, Water and Electrical Connections
7.4 Electrical Connections
WARNING. The boiler must be earthed.
Take the electrical connector from the loose items pack
and remove the two screws and cover, see diagram 7.3.
Using cable at to the current issue of BS6500 Table 16
of a suitable length connect the mains supply cable to the
appropriate terminals of the connector, see diagram 7.3.
Standard colours are, Brown - Live (L); Blue Neutral (N); Green/Yellow - Earth (E) or ().
The mains cable outer insulation must not be cut back
external to the connector, see diagram 7.3.
Make the earth conductor of a greater length than the
current carrying conductors so that if the cable is strained
the earth conductor would be the last to become
disconnected.
It is essential that the polarity is correct.
After completing the connections secure the cable with
the connector’s cover using the two screws previously
removed, make sure that no basic insulated wire is
accessible outside of the connector, see diagram 7.3.
Clip the electrical connector into position on the boiler
mounting frame and secure the mains cable with the
cable clamp immediately behind the connector.
20
EXPANSION
VESSEL
POSITION
3154
46
320
If necessary also secure the cables to the wall using
suitable cable clips.
Keep cables away from hot surfaces.
Carry out preliminary electrical system checks, using a
suitable Multimeter, that is, earth continuity, polarity,
short circuit and resistance to earth.
7.5 Heating System Controls
It is recommended that the system is controlled by a time
switch and room thermostat, proprietary control system
or by thermostatic radiator valve, refer to diagram 12.5.
Refer to the current issue of BS7478 for guidance on the
use of thermostatic radiator valves.
52
GAS CONNECTION
WATER CONNECTION
Note: Keep any pipework
clear of shaded area.
UPWARD ROUTING
OF PIPEWORK
L
E
N
Diagram 7.2
COVER
CABLE
CLAMP
3156
CONNECTOR
ELECTRICAL PLUGDiagram 7.3
15
MAINS
CABLE
220677A
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Boiler and Flue Fixing
8.1 Mounting the Boiler
After installing the boiler mounting frame, gas and
water, making the electrical connections and preparing
the flue components continue as below:
Lift the boiler into position, hooking it onto the boiler
mounting frame at the top, see diagram 8.1 then loosely
fit the two, previously removed, boiler securing screws
at the top, see diagram 5.4.
3157
Locate the water pipes into the isolation valves and the
gas service cock union halves, see diagram 5.3.
After positioning the location studs into the clips, see
diagram 8.1, fully push the boiler back to the mounting
frame.
Make the compression joint on the isolating valves and
join the gas service cock union. Secure the valves and
gas service cock with the securing straps.
Secure the boiler by tightening the two fixing screws at
the top.
To fit the discharge pipe to the safety valve, release the
single securing screw and pivot forward the fascia and
control board assembly (PCB), see diagram 8.2. Secure
the discharge tube with the nut and olive supplied in
loose items pack, see diagram 8.2.
Refit fascia control board assembly (PCB).
Connect the plug and socket of the electrical connector
together, see diagram 8.3.
LOCATION
CLIPS
and
STUDS(S)
UNION
CONNECTORS
BOILER MOUNTINGDiagram 8.1
CONTROL THERMOSTAT
CONTROL KNOB
3158
FASCIA/
CONTROL
BOARD
SECURING
SCREW
DISCHARGE
TUBE
UNION
NUT
OLIVE
FASCIA / SAFETY VALVEDiagram 8.2
220677A
16
FASCIA
SECURING
SCREW (2)
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Boiler and Flue Fixing
8.2 Flue Assembly to Boiler - Connection
NOTE. The fan could be fitted with transit clips, see
diagram 8.6 which will need removing.
Slacken but do not remove the fan securing screws and
flue hood wing nuts, see diagram 8.4.
Secure the flue assembly to the spigot on top of the
boiler, see diagram 8.5.
Tighten the fan securing screws and flue hood wing nuts
previously slackened, see diagram 8.4.
3159
FLUE
SPIGOT
FLUE DUCT ASSEMBLY
and FLUE ELBOW
3161
ELECTRICAL
CONNECTOR
ELECTRICAL
CONNECTOR
FAN
SECURING
SCREW (2)
FLUEHOOD
SECURING
ANGLE WING NUT
CABLE
CLAMP
MAINS
CABLE
Diagram 8.3
3160
SECURING
SCREW (2)
FLUE ASSEMBLY
CONNECTION
FRONT
Diagram 8.5
4856
REAR
FLUEHOOD / FANDiagram 8.4
TRANSIT CLIPS
17
Diagram 8.6
220677A
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Completion and Commissioning
9.1 System Commissioning
Commissioning must only be carried out by a competent
person in accordance with the current issue of BS6798.
Check that the boiler is isolated from the electrical
supply at the external isolator.
Open the two water isolating valves, slots in line with
the length of the valves, see diagram 9.1.
Note: In addition to the automatic air vent, to speed the
filling of the system, at any time, the air vent on the heat
exchanger should be opened, see diagram 9.1.
Once the system is filled this vent should be closed,
making sure that a watertight seal is made.
Flush out the whole system.
Refill the system, check the operation of the safety
valve, by allowing the water pressure to rise until the
valve operates. The valve should open within +/-0.3bar
(+/-4.3lbf/in2) of the 3bar, preset, pressure. Where this is
not possible carry out a manual check and test.
Clear any air locks and check for water soundness.
IMPORTANT
THE CAP ON THIS
AIR VENT SHOULD
NOT BE REMOVED
OR REPLACED
3162
BLEED
SCREW
Release cold water to initial system design pressure.
Gas Soundness Test - Pilot
Temporarily disconnect the black cable from the main
burner multifunctional control solenoid and insulate the
connector with insulation tape to prevent the main burner
from lighting.
Turn the gas service cock “On”, the slot in line with the
length of the cock, see diagram 9.3.
WARNING: The multifunctional control and fan
operate on mains voltage, the terminals will become
“Live”.
With the control thermostat control knob in the “O”
“Off” position switch on the electrical supply to the
system.
Turn the control thermostat control knob fully clockwise
to “MAX”, the fan will start, sparks will be generated
and the pilot burner will light.
Check around pilot connections for gas soundness with a
suitable leak detection fluid.
Turn the control thermostat control knob fully anticlockwise to “O” and isolate the boiler from the
electrical supply.
DRAIN
POINT
FILLING / VENTING
WATER
ISOLATING
VALVE
SLOT
OPEN
Diagram 9.1
Remove the insulation tape and refit the black cable to
the pilot solenoid valve.
220677A
18
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Completion and Commissioning
9.2 Initial Lighting and Testing and
Adjustment
The set pointer on the pressure gauge should be set to
coincide with the cold fill pressure.
Refit the inner case, securing it with the four screws
previously removed.
Make sure that the case is correctly fitted and sealed.
Identify the controls by reference to diagram 9.2.
3163
Check that the boiler is isolated from the electrical
supply.
Make sure that the control thermostat control knob is
turned to “O” the “off” position.
The pilot gas rate is preset and cannot be adjusted..
For future reference stick the self adhesive arrow
indicator, from the loose items pack, to the data label
against the rating that the boiler is going to be set to.
Remove the main burner pressure test point screw
located on the underside of the gas manifold and fit a
suitable pressure gauge, see diagram 9.2.
Make sure that any remote controls are calling for heat.
WARNING. The multifunctional control and fan
operate on MAINS voltage, terminals will become
“LIVE”.
Switch on or connect the electrical supply to the boiler
and heating system, neon 1 will light.
PRESSURE
GAUGE
CONTROL
NEON
WARNING
LIGHT
PRESSURE
TEST
POINT
BOILER CONTROLS
THERMOSTAT
CONTROL
GAS
PRESSURE
ADJUSTMENT
SCREW
COVER
Diagram 9.2
3164
GAS SERVICE COCKDiagram 9.3
19
'SLOT' shown on
GAS SERVICE COCK
220677A
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Commissioning and Completion
9.3 Testing - Electrical
Checks to ensure electrical safety should be carried out
by a competent person.
In the event of an electrical fault after installation of the
system. preliminary electrical system checks as below
should be carried out.
1.Test insulation resistance to earth of mains cable.
2.Test the earth continuity and short circuit of all
cables.
3.Switch on the electrical supply to the boiler, neon 1
will light.
Test the polarity of the mains supply.
Turn the control thermostat control knob fully clockwise
to the maximum setting, neon 2 will light.
Note: The burner will not light between “O” and “MIN”.
The lighting sequence is automatic, as follows:
The fan operates.
The spark ignition operates.
The pilot solenoid opens.
The pilot burner lights.
The ignition spark stops.
The main solenoid opens
and after a short period of time the main burner will
light, check this by looking through the viewing window.
neon 3 will light
}
neon 4 will light
}
9.4 Testing - Gas
Test for gas soundness around the boiler gas
components, using a suitable leak detection fluid.
Check the main burner gas pressure at least 10 minutes
after the burner has lit, refer to Data label or Appliance
Data, Table 2.
If The gas pressure requires adjustment, remove the
screw cover, see diagram 9.2 for access to the main
burner pressure adjustment screw. Adjust the gas
pressure to obtain the required setting (turn anticlockwise to decrease).
Should any doubt exist about the gas rate, check it using
the gas meter test dial and a stop watch, at least 10
minutes after the burner has lit, make sure that all other
gas burning appliances and pilot lights are off.
The rates are as shown in Table 4.
Turn the control thermostat knob to “O” “Off”. Remove
the pressure gauge from the test point and refit the screw,
making sure that a gas tight seal is made.
When the control thermostat is turned to “O” “Off”
position, by hand, wait at least 30 seconds before turning
“On” again.
There may be an initial smell given off from the boiler
when new, this is quite normal and will disappear after a
short period of time.
OUTER CASE
3165
The main burner will remain alight until switched off,
either by the boiler thermostat or a remote system
control.
To make sure that the flame supervision device is
working correctly the following should be done.
1.With the main burner alight, turn the gas service
cock “Off”, see diagram 7.1.
After a short period the main burner and pilot will
go out.
2.The correct working of the flame supervision device
is shown by neon 4 going out within 10 seconds and
the ignition spark starting up.
Neons 1, 2 and 3 should stay alight.
3.If the above does not happen refer to fault finding,
Section 12.
4.To carry on turn the gas service cock “On”, see
diagram 9.3.
When the boiler switches “Off”, both the pilot and main
burner go out and the fan stops. The automatic lighting
sequence will operate again when heat is required.
The neon indicator lights on the control board (PCB) are
an aid to fault finding, for details, refer to Section 12.
OUTER
CASE
SECURING
SCREW
CASE SECURINGDiagram 9.4
220377B
220677A
20
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Commissioning and Completion
9.5 Heating System
Check that all remote controls are calling for heat.
Allow the system to reach maximum working
temperature and examine for water leaks. The boiler
should then be turned off and the system drained as
rapidly as possible whilst still hot.
Refill the system, vent and again check for water
soundness.
Adjust the system to initial design pressure. The set
pointer on the pressure gauge should be set to coincide
with the indicating pointer.
9.6 Operational Checks
Adjust the control thermostat and any system controls to
their required settings.
Do not attempt to adjust the thermostat calibration
screw.
Operate the boiler again on full service and check that
the balancing of the heating circuits and radiators is
satisfactory, make adjustments as necessary.
TABLE 4
APPROX.GAS RATEminmedmax
MODEL 40
MODEL 55
m3/h
ft3/h
m3/h
ft3/h
1.01.21.4
37.743.448.8
1.41.71.9
49.858.967.1
3211/A
Refit the outer case, see diagram 9.4, slide the
information plate forward and secure the case with the
screw previously removed.
10 Instructions to the User
Hand the Instructions for Use to the user for their
retention.
Instruct and demonstrate the efficient and safe operation
of the boiler, heating system and if fitted, the domestic
hot water system.
Show the user the position of “Lighting Instructions” by
reference to diagram 9.5.
Advise the user of the precautions necessary to prevent
damage to the system and building in the event of the
heating system being out of use during frost and freezing
conditions.
INFORMATION
PLATE
INFORMATION PLATE
Advise the user, that to ensure the continued efficient
and safe operation of the boiler it is recommended that it
is checked and serviced at regular intervals.
The frequency of servicing will depend upon the
particular installation conditions and usage, but in
general once a year should be enough.
Draw attention, if applicable, to the current issue of the
Gas Safety (Installation and Use) Regulations, Section
35, which imposes a duty of care on all person who let
out any property containing a gas appliance.
It is the Law that servicing is carried out by a competent
person.
Diagram 9.5
Reminder, leave these instructions with the user.
21
220677A
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Servicing
11.1 Notes
To ensure the continued efficient and safe operation of
the boiler it is recommended that it is checked and
serviced at regular intervals. The frequency of servicing
will depend upon the particular installation conditions
and usage, but in general once a year should be enough.
It is the Law that any servicing must be carried out by a
competent person.
Unless stated otherwise, parts removed for servicing
should be replaced in the reverse order to removal.
After completing any servicing of gas carrying
components, ALWAYS test for gas soundness and carry
out functional check of controls.
Slide the information plate forwards and remove the
outer case securing screw, see diagram 9.4 and lift the
case off.
Before starting any servicing, isolate the boiler from the
electrical supply at the external isolator and close the gas
service cock, see diagram 9.3.
As an aid to Servicing the air pressure switch tube
connection can be used to obtain a products of
combustion reading.
12 to 14 FLAME LENGTH
SPARK GAP 3 to 4.5
PILOT FLAME AND
SPARK GAP DIMENSION
FAN SECURING
SCREW (2)
3167
Diagram 11.1
3203
FAN ELECTRICAL
CONNECTORS
Remove the RED tube from the connection on the air
pressure switch and insert the analyser probe into the
tube.
WARNING: The electrical components work on mains
voltage and they will become live.
Switch on the electrical supply to operate the fan and
turn on the gas supply.
On a satisfactory completion of the test, switch off the
electrical supply and reconnect the red tube to the air
pressure switch.
Routine Servicing
11.2 Inner Case
Remove the cover of the inner case, secured with four
screws.
11.3 Pilot Check
Check that the pilot flame is burning correctly and of the
correct size, see diagram 11.1. If the pilot flame is not
correct, the pilot injector will require removing, see
Section 11.7.
FAN
ASSEMBLY
FLEXIBLE
SECURING
SCREW (4)
BURNER
SECURING
WING NUT
COMBUSTION CHAMBERDiagram 11.2
COMBUSTION
CHAMBER
FRONT PANEL
TUBES
220677A
22
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Servicing
11.4 Main Burner
Slacken the flue hood securing angle wing nuts, see
diagram 11.2.
Remove the combustion chamber front panel, secured
with four screws and a wing nut, see diagram 11.2.
Disconnect the pilot pipe union connector and ignition
lead, see diagram 11.3.
Separate the pilot assembly from the main burner,
secured with two screws, remove by lifting upward, see
diagram 11.3.
Remove the main burner from the main injector at the
rear. Raise the burner up and forward, easing the pilot
pipe down, to clear, take care not to damage the
combustion chamber insulation or the pilot burner
assembly.
Use a vacuum cleaner or suitable stiff brush to clean the
burner thoroughly, making sure that all the burner ports
are clear and unobstructed.
Do not use a brush with metallic bristles.
Note: On refitting and after cleaning the heat exchanger
make sure the main burner is fitted correctly, that is,
located on the main injector and horizontal,
see diagram 11.4.
3169
PILOT BURNER
ASSEMBLY
SECURING
SCREW (2)
PILOT
TUBING NUT
SEALING
ANGLE
PILOT BURNER
ELECTRODE ASSEMBLY
BURNER
INJECTOR
ELECTRODE
SECURING
SCREW
ELECTRODE
PILOT
INJECTOR
IGNITION
LEAD
Diagram 11.3
3170
11.5 Main Injector
With the main burner removed the main injector can be
inspected and cleaned as necessary.
If removing for cleaning do not use a wire or sharp
instrument on the hole.
Use new seal when refitting to ensure a gas tight seal is
made.
BURNER REMOVALDiagram 11.4
FLUEHOOD
FAN RETAINING
BRACKET
3171
FLUEHOODDiagram 11.5
23
220677A
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Servicing
11.6 Cleaning Heat Exchanger.
Disconnect the two electrical connections at the fan, see
diagram 11.2. It is not necessary to disconnect the green
and yellow earth cable.
Disconnect the two flexible tubes from the fan, see
diagram 11.2.
Remove the fan by releasing the securing screws, see
diagram 11.2.
Remove the flue hood securing bracket, secured with
two wing nuts and hook bolts, see diagram 11.2.
Remove the flue hood, see diagram 11.5.
Remove the burner as Section 11.4.
Cover the pilot assembly and main injector and place a
sheet of paper in the combustion chamber to catch any
debris.
Brush the heat exchanger with a suitable brush.
Do not use a brush with metallic bristles.
Remove the paper and cover from the pilot assembly and
main injector together with any debris.
11.7 Pilot Injector
If the pilot flame is not burning correctly, it may be
necessary to remove the pilot injector.
Unscrew the pilot injector from the pilot assembly.
Inspect the injector and if necessary clean only by
blowing clear.
Do not use wire or sharp instrument.
When relighting check that the flame length is as shown
in diagram 11.1.
11.8 Operational Checks
Check the safety valve manually by turning the knob in
the direction of the arrow.
Light the boiler, carry out operational checks and any
necessary adjustments as described in the
Commissioning Section 9 of these instructions.
When replacing, please note:
(a) Locate the fan mounting plate assembly behind the
retaining bracket at the same time easing the fan outlet
into the flue elbow, see diagram 11.5.
(b) Make sure the coloured flexible tube connects to the
upper connection on the fan.
(c) The polarity of the two fan electrical connections is
not important.
12 Fault Finding
12.1 Electrical
Important. On completion of the Service/Fault Finding
task which has required the breaking and remaking of the
electrical connections the earth continuity, polarity, short
circuit and resistance to earth checks must be repeated
using a suitable multimeter.
Refer to: Neon Indicators - Aid to Fault Finding,
diagram 12.1, Fault Finding, diagram 12.2 Wiring,
diagram 12.5 and Functional Flow diagram 12.3.
12.2 Electrical Supply Failure
Failure of the electrical supply will cause the burner to
go out. Operation will normally resume on restoration of
the electrical supply. If the boiler does not relight after
an electrical supply failure the overheat cutoff device
may need resetting.
To reset, pull the information panel forwards on the
underside of the boiler and press the reset button, see
diagram 12.4.
If the cutoff operates at any other time press the reset
button and the burner should relight. If the fault persists
refer to Fault Finding, diagram 12.2.
220677A
24
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
Neon Indicators - An Aid to Fault Finding
THE NEON INDICATORS ARE AN AID TO FAULT FINDING ONLY.
FAILURE OF ANY OF THE NEON INDICATORS DOES NOT WARRANT THE
REPLACEMENT OF AN OTHERWISE SATISFACTORY PRINTED CIRCUIT BOARD (PCB).
IF RED NEON ON FASCIA IS ILLUMINATED FILL CENTRAL HEATING SYSTEM,
PRESSURE 0.7bar MIN.
Is neon 1 lit?
YES
Is neon 2 lit?
YES
Is neon 3 lit?
YES
Is neon 4 lit?
YES
Is main burner
operating?
YES
System
satisfactory
NO
NO
NO
NO
NO
Fault with mains supply, PCB fuse or
low water pressure switch.
Overheat cut off device tripped.
Thermostat, Overheat cut off device,
Water differential pressure switch,
or faulty Pump. - see detailed fault
finding chart.
Air flow proving fault - that is fan or air
pressure switch - see detailed fault
finding chart.
Ignition, pilot or flame proving fault see detailed fault finding chart.
Multi-functional control/harness problem see detailed working? Fault finding chart.
NEON INDICATORS
NEON INDICATORS
25
3172
Diagram 12.1
220677A
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
Before detailed checking of electrical components ensure that remote controls are calling for heat. Check that the gas
supply is free of obstructions and purged of air. Isolate the elctrical supply, check all cables, connections and the
printed circuit board (PCB) fuse. Check the air tubes to the air pressure switch for kinks and splits. Switch on the
electrical supply and check for correct polarity. If red neon on the fascia is illuminated isolate the elctrical supply and
pressurise the sytem to 0.7bar minimum with the sytem cold. Switch on the electrical supply. Turn the control
thermostat to its maximum setting.
Is neon 1 lit ?
YES
Is neon 2 lit ?
YES
NO
NO
Is there 240V~between
3 and 2 ?
YES
Is there 240V~between
5 and 2 ?
Fill Central heating system
to 0.7bar min.
Does the red neon go off?
YES
NO
Is there 240V~between N/o
on Low water pressure
switch and 2 ?
YES
Is there 240V~between
yellow connection on
overheat device and 2 ?
NO
NO
Faulty Neon
NO
NO
Correct power supply
problem
Is Red neon on fascia
YES
illuminated ?
Is there 240V~between N/c
YES
on Low water pressure
switch and 2 ?
Is there 240V~between C
on Low water pressure
switch and 2 ?
YES
Isolate electrical supply.
Check continuity of
purple cable.
4761/A
NO
NO
NO
AB
Is there 240V~ between
YES
white connection on water
differential pressure switch
and 2 ?
Does the pump run?
YES
Is the tube to Water
differential pressure switch
kinked or damaged.
NO
Faulty Water differential
pressure switch. Replace.
MAIN TERMINAL STRIP
NO
YES
NO
Faulty Low water pressure
switch. Replace.
Check overheat reset.
If satisfactory replace
overheat device.
Is there 240V~ between
L and N at pump?
YES
NO
Isolate electrical supply.
Check continuity of pump
cable.
Faulty pump. Replace.
Rectify tube or replace.
Diagram 12.2
220677A
26
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
4761/B
A
Is neon 3 lit ?
YES
NO
B
Is there 240V ~ between
yellow connection on
thermostat and 2 ?
Is there 240V~between N/c
on air pressure
switch and 2 ?
YES
Is there 240V~between C
on air pressure
switch and 2 ?
YES
NO
NO
NO
MAIN TERMINAL STRIP
Replace thermostat
Check yellow cable between
printed circuit board and air
pressure switch.
If satuisfactory replace
printed circuit board (PCB)
Replace air pressure switch
C
YES
Does fan run ?
Replace fan.
Does fan hunt ?
D
NO
NO
YES
Is there 240V ~ between
motor connections on fan ?
YES
NO
Isolate electrical supply, test
fan harness continuity.
If satisfactory replace
printed circuit board (PCB)
Replace printed circuit
NO
board (PCB)
27
Diagram 12.2
continued
220677A
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
4761
C
YES
Is neon 4 lit ?
YES
NO
D
Is there 240V ~ between
(N/o) on air pressure
switch and 2 ?
YES
Is there 240V~between
pilot multi-functional control
soleniod blue and brown
connections ?
YES
Does discharge tube flash
on printed circuit board
during ignition attempt ?
YES
Is there a spark at the
pilot burner ?
YES
NO
NO
NO
MAIN TERMINAL STRIP
Inspect air tubes for leaks
kink and correct fitting.
If satisfactory replace faulty
air pressure switch.
Isolate supply, test harness
continuity. If satisfactory
replace printed circuit board
(PCB)
Replace printed circuit
board (PCB)
Check lead continuity and
inspect electrode and lead
for damage.
Does main burner
light ?
YES
System satisfactory
NO
Does pilot light ?
YES
With pilot lit does spark stop ?
YES
Is there 240V ~ between
main multi-functional control
solenoid black and blue
cable.
YES
Replace multi-functional control
NO
NO
NO
Check for pilot jet blockage,
incorrect electrode
adjustment. If satisfactory
replace multi-functional
control.
Inspect electrode lead/
connection for poor contact.
Check electrical supply
polarity. If satisfactory
replace printed circuit board
(PCB)
Isolate supply, test harness
NO
continuity. If satisfactory
replace PCB
220677A
28
Diagram 12.2
continued
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
MAIN TERMINAL STRIP CONNECTIONS
CONTROL THERMOSTAT CONNECTIONS
CONTROL BOARD CONNECTIONS
N/O
C
R
P
L
3 POLE
CONNECTOR
FUSE
TYPE
F1A
BR
SPARK
ELECTRODE
N/C
3
BR
BR
BR
W
OVERHEAT
CUT-OFF
CONTROL
THERMOSTAT
R
BL
BLK
5
WATER
DIFFERENTIAL
PRESSURE
SWITCH
BL
4
FAN
Y
Y
BLK
NEON
INDICATOR
LOW WATER
PRESSURE
SWITCH
PUMP
BL
BL
BL
W
3173
PLATE
3174
RESET BUTTON
2
INFORMATION
RESET BUTTON
BL
(N)
2
BL
(N)
2
Diagram 12.4
R
AIR PRESSURE
SWITCH
BLK
Y
BR
PILOT
SOLENOID
BLK
NOTE: LOW WATER PRESSURE SWITCH
SHOWN IN UNPRESSURISED STATE
KEY
BLK BLACK
BR BROWN
BL BLUE
W WHITE
R RED
Y YELLOW
N/O
C
N/C
BL
MAIN SOLENOID
BL
BL
(N)
2
BL
2
(N)
FUNCTIONAL FLOW
Diagram 12.3
29
220677A
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Fault Finding
RED
PURPLE
WATER
PRESSURE
WARNING
NEON
BLACK
BROWN
Nc
CHASSIS
EARTH
G/Y
BLACK
BLUE
BLACK
FAN ASSEMBLY
BROWN
BLUE
FUSE
TYPE F1A
1 AMP
BLUE
BROWN
5
BLUE
BLUE
RED
GREEN/
YELLOW
SPARK
ELCTRODE
PRINTED
CIRCUIT BOARD
1
2
34
CIRCULATION
PUMP
N
L
E
BLUE
BROWN
BLUE
G/Y
G/Y
CHASSIS
EARTH
AIR PRESSURE
SWITCH
NC
NCC
3175
G/Y
No
C
LOW WATER
PRESSURE
SWITCH
CONTROL
THERMOSTAT
WATER
DIFFERENTIAL
PRESSURE
SWITCH
YELLOW
WHITE
WHITE
OVERHEAT
CUTOFF
THERMOSTAT
YELLOW
BLUE
G/Y
BROWN
RED
YELLOW
BLACK
G/Y
BROWN
BLUE
BLUE
BLACK
MULTI-FUNCTIONAL
CONTROL
N E L
240V~50Hz
SWITCHED MAINS
SUPPLY FUSED
AT 3 AMP
220677A
30
Diagram 12.5PICTORIAL WIRING
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13 Replacement of Parts
13.1 Replacement of parts must only be carried out by a
competent person.
Before replacing any part isolate the gas and electrical
supplies.
Unless stated otherwise all parts are replaced in the
reverse order to removal.
13.2 Access
Slide forward the information plate, remove the securing
screw and remove the case, see diagram 9.4.
Unless stated otherwise gain access as Sections 11.2
and 11.4.
13.3 Boiler Pressure and Draining
All parts containing water within the boiler are under
system pressure. Before any parts are disconnected,
close the isolating valves and reduce the boiler pressure
at the integral drains on the isolating valves,
see diagram 9.1.
After replacing any water containing part of the central
heating circuit, make up the water loss, vent all air and
pressurise the system. Refer to Commissioning.
13.9 Pilot Injector
Gain access as the relevant part of Section 11.4 and
proceed as Section 11.7.
When relighting check that the flame length is as shown
in diagram 11.1.
Note. For Sections 13.10, 13.11, 13.13, 13.14, 13.15,
13.17, 13.18, 13.25, 13.26, 13.27 and 13.28 release
fascia and control board (PCB) assembly by removing
the screw and pivot forward, see diagram 8.2.
3176
GLAND PLATE
After replacing any gas carrying parts always test for gas
soundness and if necessary carry out functional check of
controls.
13.4 Fan
Remove as the relevant part of Section 11.6
13.5 Main Burner
Remove as Section 11.4
13.6 Main Injector
Remove as Section 11.5.
Unscrew the main injector.
When fitting the main injector, fit the sealing washer,
supplied, to ensure gas soundness.
13.7 Pilot Burner
Remove as the relevant part of Section 11.4.
13.8 Electrode
Gain access as the relevant part of Section 11.4.
GLAND PLATE
SECURING SCREW
PHIAL
RETAINING
CLIP
ELECTRICAL
CONNECTORS
THERMOSTAT
SECURING NUT
Disconnect the ignition lead from the electrode, see
diagram 11.3.
Remove the electrode, secured with a single screw.
Check the spark gap upon assembly, see diagram 11.1.
CONTROL
THERMOSTAT
CONTROL THERMOSTATDiagram 13.1
31
220677A
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.10 Control Thermostat
Gain access as Section 13.2
Remove the control knob and fascia by removing the
screws, see diagram 8.2.
Remove the thermostat securing nut, see diagram 13.1.
3177
Remove the electrical connections from the thermostat
body.
Slacken but do not remove the gland plate.
Now remove the phial retaining clip and then the
thermostat phial from the pocket, see diagram 13.1.
When refitting, make sure that the thermostat capillary is
correctly routed and the phial covered with heat sink
compound, before it is secured in the pocket, by the phial
retaining clip.
Reconnect the electrical connections, see diagram 12.5.
13.11 Overheat Cutoff: diagram 13.2
Remove the electrical connections from the cutoff body.
Remove the capillary securing clamp.
Remove the locknut securing the overheat cutoff to the
bracket and withdraw the assembly.
13.12 Ignition Lead: diagram 11.3
Slacken but do not remove the sealing angle securing
screw.
Disconnect the ignition lead at both ends and withdraw.
When refitting push the lead through the seal from the
top and make sure that the clear end is fitted to the spark
electrode and that the lead follows the same route, being
secured in the same manner, as the original.
PLASTIC
RETAINING
CLIP
CAPILLARY
SECURING
CLAMP
SCREW
ELECTRICAL
CONNECTIONS
VIEWED FROM REAR
OVERHEAT CUT-OFF
UNION NUT
3178
CONNECTION
OVERHEAT
CUT-OFF
LOCKNUT
Diagram 13.2
SAFETY
VALVE
FIBRE
WASHER
Take care not to damage the seal of the sealing angle.
13.13 Pressure Gauge: diagram 13.3
Release the water pressure and drain the boiler, refer to
Section 13.3.
Disconnect the pressure gauge connection from the
safety valve, discard the washer.
Remove the pressure gauge secured with the retaining
spring tabs from the bracket.
Fit the supplied washer under the pressure gauge
connection when refitting to the safety valve.
220677A
SECURING
SPRING TAB (2)
SAFETY VALVE /
PRESSURE GAUGE
32
PRESSURE
GUAGE
CONNECTION
PRESSURE
GUAGE
Diagram 13.3
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.14 Safety Valve: diagram 13.3
Release the water pressure and drain the boiler, refer to
Section 13.3.
Remove the pressure gauge connection as Section 13.3.
Disconnect the union nut to release the discharge pipe.
Place a spanner on the hexagon on the volume vessel and
break the union nut connection to release and then
unscrew the safety valve.
When refitting use a proprietary sealant to seal the joint.
When fitting use a new washer for the pressure gauge
connection.
13.15 Water Differential Pressure Switch:
diagram 13.4
Release water pressure as Section 13.3.
Remove the two electrical connections and release the
union connections, and remove the pressure switch,
complete with the flexible tubing.
Fit the flexible tubing to the new pressure switch.
LOW C.H.
WATRE PRESSURE
SWITCH
3180
ELECTRICAL
CONNECTORS
Refer to diagram 12.5 when remaking the electrical
connections.
13.16 Low Water Pressure Switch: diagram
13.5
Release the water pressure and drain the boiler, refer to
Section 13.3.
Disconnect the electrical connectors at the micro-switch.
Remove the pressure switch.
Use a proprietary sealant to seal the connection.
Make sure that the switch is positioned as shown.
Refer to wiring diagram 12.5 when making the electrical
connections.
3179
UNION
CONNECTOR
WATER DIFFERENTIAL
PRESSURE SWITCH
LOW C.H. WATER
PRESSURE SWITCH
SUPPORT
CONTROL BOARD P.C.B.
POST (4)
PLASTIC
RETAINING
CABLE
TIE
CLIP
MULTI PIN
CONNECTORS
TERMINAL
CONNECTIONS
Diagram 13.5
3181
TERMINAL
BLOCK
SECURING
SCREW (2)
UNION
HOSE
ASSEMBLY
ELECTRICAL
CONNECTORS
UNION
CHASSIS EARTH
CONNECTION
CABLE
WATER DIFFERENTIAL
PRESSURE SWITCHCONTROL BOARD (P.C.B)
Diagram 13.4Diagram 13.6
CONNECTION
33
220677A
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.17 Control Board (PCB): diagram 13.6
Disconnect all multi-pin connectors.
Remove the blue and brown cables from terminals 4 and
5 also disconnect the yellow cable from the control
thermostat and the white cable from the overheat cutoff
and the chassis earth cable.
Remove the terminal block and cables complete.
Remove the ignition lead.
Remove the printed circuit board from the support posts,
noting their correct positions. Great care must be taken
when handling the board.
To connect the multi-pin connectors, cables and terminal
block correctly, refer to diagram 12.5
SOLENOID
13.18 Multifunctional Control and Pilot
Solenoid: diagram 13.7
Disconnect all electrical connections at the
multifunctional control.
Remove the four securing screws from the left hand side
of the multifunctional control and pilot pipe, take care as
there is a restrictor in this pipe.
Support the multifunctional control, disconnect the union
nut of the gas service cock and remove the
multifunctional control complete with inlet pipe.
Separate the multifunctional control from the pipe, four
screws, noting the fitted position.
Discard the “O” rings and fit the new ones supplied.
To reconnect the connections refer to diagram 12.5
Light and adjust the boiler as necessary, refer to
Section 9.
Pilot Solenoid
3182
Disconnect the electrical connections at the solenoid,
remove the retaining clip and solenoid.
ELECTRICAL
CONNECTORS
ELECTRICAL
CONNECTORS
SECURING
SCREWS (8)
SOLENOID
RETAINING
CLIP
GAS SUPPLY
PIPE UNION
When reconnecting refer to diagram 12.5.
END
SCREW
UNION
CONNECTOR
3183
PILOT
PIPE
CONNECTOR
MULTI-FUNCTIONAL CONTROL
220677A
Diagram 13.7
PUMP
34
UNION
CONNECTOR
IN-LINE
ELECTRICAL
CONNECTORS
Diagram 13.8
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.19 Pump: diagram 13.8
Release the water pressure and drain, refer to
Section 13.3.
Disconnect the “in-line” connections at the pump.
Disconnect the pump at the union connections.
Discard the sealing washers and fit the new ones
supplied.
When fitting the replacement make sure that the flow
direction arrow is pointing upward.
Set the flow adjuster to position 3, see Section 2.6.
Note: Should the pump fail to operate, and all is in order
but the pump still does not operate, remove the end
screw, turn the pump spindle to release any temporary
seizure. DO NOT HIT THE SPINDLE.
13.20 Automatic Air Vent: diagram 13.9
Release the water pressure as Section 13.3.
Remove the automatic air vent.
Discard the sealing washer and use the new one supplied.
HEAT
EXCHANGER
LOCATION
SLOT
AUTOMATIC
AIR VENT
3184
Slacken the vent cap on the air vent of the new item.
This cap must not be re-tightened.
13.21 Heat Exchanger: diagram 13.9
Isolate the boiler from the gas and electrical supplies.
Remove all the necessary internal parts.
Fit the automatic air vent to the new heat exchanger,
using the new washer provided.
Disconnect the union nuts at the heat exchanger.
When fitting new heat exchanger use the new sealing
washers provided.
Locate the raised location tabs on the combustion
chamber sides into the slots on the heat exchanger when
fitting it.
UNION CONNECTORS
HEAT EXCHANGER
Diagram 13.9
35
220677A
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.22 Combustion Chamber Insulation:
diagram 13.10
Remove the securing clip and insulation panel.
Take care when sliding the replacement insulation into
position securing it with the original clip.
The rear insulation cannot be removed until the heater
exchanger is removed, see Section 13.21, then slide the
insulation from behind the heat exchanger.
13.23 Expansion Vessel: diagram 13.11
Renewal of the expansion vessel requires the removal of
the boiler from the wall. As an alternative, in certain
circumstances, a separate expansion vessel of the same
specification may be connected as close as possible to
the boiler, leaving the original in position.
Isolate the boiler from the gas and electrical supplies.
Release the water pressure and drain, as Section 13.3.
Remove the fan from the flue hood, see Section 11.6.
Disconnect the flue elbow, by reversing the instruction
in Section 8.2.
INSULATION
PANEL
INSULATION
RETAINING
CLIP
COMBUSTION
CHAMBER FRONT
PANEL
COMBUSTION CHAMBER FRONT PANEL
3197
Disconnect the boiler water connections union nuts,
see diagram 5.3.
Disconnect the gas service cock, see diagram 5.3.
Disconnect the electrical plug, see diagram 8.3.
Remove the boiler from the mounting frame secured
with two screws at the top, see diagram 5.4. Pull the
boiler from the isolating valves and clips at the bottom.
Unhook the boiler at the top and withdraw it forward.
Carefully lay the boiler down on its side to gain access to
the expansion vessel.
Disconnect the union nut connection.
Remove the expansion vessel, secured with three
clamps.
Discard the sealing washers and use the new ones
supplied.
Connect the union nut, when fitting the expansion vessel,
before clamping it.
13.24 Pilot Viewing Window: diagram 13.12
Remove the two screws and then the window.
SIDE INSULATION
PANEL(S)
REAR INSULATION
PANEL(S)
When replacing take care not to damage the gasket.
13.25 Inner Case Seal: diagram 13.12
Gain access as Section 13.2.
When removing seal make sure that all the old adhesive
is removed.
When fitting the new seal make sure that it fits correctly
and has not buckled.
220677A
COMBUSTION
CHAMBER INSULATION
36
Diagram 13.10
Page 37
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Replacement of Parts
13.26 Air Pressure Switch: diagram 13.13
Remove the pressure tubes and electrical connections.
Release the air pressure switch from its bracket by
unfastening the two screws.
UNION NUT
CONNECTION AND
SEALING WASHER
CLAMPING
SCREW (3)
When refitting make sure that the coloured tube is fitted
as shown and that the electrical connections are made as
shown in diagram 12.5.
The polarity of the electrical connections is important.
13.27 Bypass Valve: Diagram 13.14
Release the pressure and drain as Section 13.3.
Break the union connections
3187
Note: The replacement valve will be supplied preset and
must not be adjusted.
13.28 Warning Light
Disconnect the electrical connections, see diagram 12.5,
squeeze the securing tabs and remove from the fascia.
3189
EXPANSION
VESSEL
EXPANSION VESSEL
PILOT
VIEWING
WINDOW
INNER
CASE
INNER
CASE
SEAL
Diagram 13.11
ELECTRICAL
CONNECTORS
3210
SECURING
SCREW (2)
(WHITE)
PRESSURE
TUBES(S)
(RED)
CONNECTION(S)
AIR PRESSURE SWITCH
BYPASS VALVE
Diagram 13.13
3190
FRAME
SECURING
SCREW (2)GLASS
GASKET
PILOT VIEWING
WINDOW / INNER CASE
Diagram 13.12
BYPASS VALVEDiagram 13.14
37
UNION
CONNECTIONS
220677A
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Spare Parts
14.1 Part Identification
The key number in diagram 14.1 and the first column of
the list will help to identify the spare part.
14.2 Ordering
When ordering any spare part, please quote the part
number and the description from the list together with
the model name and serial number information from the
data label. The data label is positioned at the top right of
the inner case.
If ordering from the local gas company also quote the
GC number of the appliance from the data label and the
GC number of the spare part, from the list.
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Spare Parts
18
1
16
18
17
2
11
9
3
4
14
3198/A
19
10
19
21
20
5
13
15
8
21
12
12
6
7
39
Diagram 14.1
220677A
Page 40
Supplied By www.heating spares.co Tel. 0161 620 6677
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide
information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this
state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels
are usual only if the material is broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your
hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
THERMOSTATS
These contain very small amounts of dichlorotrifluoroethane in the sealed phial and capillary.
If broken, under normal circumstances the fluid does not cause a problem.
If there is irritation to the eyes or skin then seek medical attention.
CUT-OFF DEVICES
These contain a very small amount of ethylene glycol and methanol in the capillary.
If broken, under normal circumstances the fluid does not cause a problem, but in cases of skin
or eye contact, wash with cold water.
If swallowed drink plenty of water and seek medical attention.
Because of our constant endeavour for improvement details may vary slightly from those given in these instructions.
220677A
40
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.