Supplied By www.heating spares.co Tel. 0161 620 6677
Important Information
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler,
without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the
current issue of the Statutory Requirements, see Section 1.4.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed
to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous
fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0087.
Product/production certified by: Notified body 0087.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning
gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment
designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic
compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is
broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or
going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
CONTENTS DESCRIPTIONSECTION PAGE No.
INSTRUCTIONS
FOR USE
INSTALLATION
INSTRUCTIONS
Introduction3
Clock Settings4
Lighting the Boiler5
General Data17
Boiler Position29
Flue and Ventilation310
Heating System412
Domestic Hot Water System514
Installation Preparation615
Flue Preparation716
Gas and Water Connections818
Electrical Connections919
Boiler Fixing1021
Commissioning1122
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Introduction
Please read these instructions and follow them carefully for the
safe and economical use of your Combination boiler.
This boiler must have been installed by a competent person in
accordance with the rules in force in the countries of destination.
Once the pilot has been lit and the controls set, the boiler is
automatic in operation.
The Swift-flow combination boiler is able to provide room
heating as part of a central heating system and domestic hot
water direct from the cold water supply, without the need for
secondary storage.
The boiler can be fitted with one of two makes of clock, which
look like this:-
Clock / Timer
Digital
timer
Electro /
mechanical
clock / timer
IMPORTANT NOTICE:
This boiler is for use only on G20 gas.
Gas Leak or Fault
If a gas leak or fault exists or is suspected, turn the boiler off and
consult your local gas company or your local installation/
servicing company.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than
in the summer.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off tap.
As the markings on your plug may not correspond with these
colours continue as follows:-
The wire coloured blue must be connected to the terminal
marked “N” or “Black”.
The wire coloured brown must be connected to the terminal
marked “L” or “Red”.
The wire coloured green and yellow must be connected to
the terminal marked “E” or “Green” or the earth symbol
PVC flexible cable having a conductor size of 0.75mm
0.20mm) must be used within the boiler casing to connect
to the boiler.
Electrical Supply Failure
6509
The boiler will not work without an electrical supply.
Normal operation of the boiler should resume when the
electrical supply is restored.
Note. The boiler safety cutoff may have operated, please
refer to the following section to reset.
Reset any external controls, to resume normal operation of
the central heating.
The digital timer, has a lithium battery back up and will not
need resetting.
Boiler Safety Cutoff Reset Button
The boiler is fitted with a safety cutoff device to prevent
damage through overheating.
Should the main burner go out during a demand the red
neon on the Reset Button will light.
In certain circumstances the red neon light may not come
on, due to no system demand. It is suggested that a hot
water draw off tap be opened to create a demand, the neon
should then come on.
Allow the boiler and system to cool down waiting at least a
minimum of four minutes before pressing the Reset button.
If the problem persists, turn the boiler off and consult the
local gas company or your installation/servicing company.
2
(24/
.
Boilers Installed in Compartments
If the boiler has been fitted into a compartment or cupboard, do
not obstruct the compartment air supply vents.
Do not use the compartment for storage.
Electrical Supply
WARNING. The boiler must be earthed.
The boiler must be connected to a 230V~50Hz permanent
supply.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should preferably be by a double pole switched fused
spur box. The fused spur box should be readily accessible and
preferably adjacent to the appliance. It should be identified as
to its use.
Alternatively a fused 3A 3 pin plug and shuttered unswitched
socket may be used.
The colours of three core flexible cable are, blue - neutral, brown
- live, green and yellow - earth.
3
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Setting Instructions for Electro/mechanical
Clock - if fitted
This clock has a twenty four hour dial, that is, 1pm is 13.
To set the time, turn the whole face clockwise until the pointer
is against the time of day.
To set any “Off” time, push the tappets outwards.
To set any “On” time, push the tappets inwards.
Time can be set either “On” or “Off” in fifteen minute segments.
Note. The clock supplied could be fitted with an override device,
see diagram 1, which switches the clock programme “On” or
“Off” permanently.
The switch will need to be repositioned to resume programmed
working.
CLOCK FACE
0
OVERRIDE
SWITCH
12
11
13
14
15
16
17
18
19
20
21
22
23
24
CONSTANT OFF
0
PROGRAMMED
CONSTANT ON
I
10
9
3
2
1
I
8
7
6
5
4
POINTER
TAPPETS
Diagram 1
Setting Instructions for the 7 Day Digital
Clock/Timer
This is a 24 hour clock/timer, that is 1pm is 13:00, and has 8
“ON” and 8 “OFF” daily switching actions.
It is fitted with a lithium battery back up which protects the
programme in the event of an electrical failure. The battery
should have a life of several years.
P
AUTO
I
MT
WTh
RUN
FS
Su
Setting the Clock
1. With both AUTO and RUN switches set to the central
position, press R reset button, the display will flash.
2. Set RUN switch to .
3. Set day of week by pressing button DAY.
4. Set time of day by pressing buttons HR and MIN.
5. Set RUN switch to the central position, colon will flash, this
indicates the clock is set.
With the clock set, the factory preset programme shown below
will operate.
4956
MON/FRI
ON -06:30
OFF -08:30
ON -16:30
OFF -22:30
SAT/SUN
ON -07:00
OFF -09:00
ON -16:00
OFF -23:00
Setting Timed Programmes
With the clock set to the correct time, see SETTING THE
CLOCK paragraphs 1-4, and then continue as follows:
1.Set RUN switch to P , the display will indicate
the 1st (ON) preset programme and the symbol .
2.Set day of week to be programmed by pressing the
DAY button.
Note. The days can be selected individually or
as groups:
Mon-Fri., Mon-Sat., Mon-Sun., Sat/Sun.
An arrow will be displayed under the day or
days selected.
3.Set time of day by pressing the buttons HR and MIN.
4.Press button P to confirm programmes, the
display will indicate the 2nd (OFF) preset programme
and subsequently, 3rd, 4th, 5th, 6th, 7th, 8th.
5.Repeat procedures 2, 3 and 4 until desired
programmes are set.
Note. It is not a requirement to use the 8 on/off
programmes.
6.Set the RUN switch the central position, your
appliance will now operate at the programmed times.
General Notes.
5673
With the AUTO switch in the I position the central
heating will operated constantly ON.
With the AUTO switch in the O position the central
heating will not operate.
Soft Override button indicated by the
symbol
, this function will override the
current central heating programme for the
next available.
ON time programmes are indicated by the symbol .
P
DAYHRMIN
R
Diagram 2
221473B
4
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
User Indicator Lights
Identify the lights be reference to diagram 3.
The Orange - Mains light - shows that the electrical supply to
the boiler is on.
The Green - Running light - shows that the boiler is working
normally, in either the central heating or hot water modes.
If the Red - Low Central Heating water pressure light
flashes continually it is warning of a loss of pressure in the
central heating system.
During this time the red light will continue to flash and the
boiler will not work.
If this happens you MUST call your installation or
servicing company.
To Operate the Boiler
1. Check that all five isolating valves are open, the slots in
line with the length of the valve, see diagram 4.
2. Open the door, by pushing at the side opposite to the hinge.
3. CAUTION. A sealed pressurised system must be filled
and pressurised by a competent person.
Only operate the boiler when you are sure that the system has
been filled and pressurised. Check this by looking at the pressure
gauge “A”, diagram 3, it should read 0.7bar minimum.
4. Check reset button neon, refer to previous instructions
on page 4.
5. Open a hot water tap, check that water flows, then close it.
6. If you are in any doubt about the boiler being filled with
water contact your installation/servicing company or the local
gas company.
7. Check that the electrical supply to the boiler is ON at
the external isolator.
8. Set switch “C”, clock/timer (if fitted) and any remote controls
as required.
Close the door.
In certain circumstances, a surge in water pressure may cause
the appliance to operate momentarily, this will be indicated by the
pump starting and the fan speed increasing. This is quite normal.
Central Heating Selector Switch
For central heating set switch “C” to “On” as shown in diagram 3.
The main burner will light to provide central heating.
Note, when the central heating is also controlled by a
room thermostat, clock/timer or other remote control these
controls must be calling for heat for the boiler to operate.
The user central heating temperature control enables
you to control the temperature of the central heating water.
The knob can be set between Minimum, about 55oC and
Maximum, about 80oC.
If a hot water tap is opened while the boiler is on for heating,
the burner flame will increase in size and priority will be given
to hot water. When the hot water tap is closed, the main
burner flames will decrease in size but will remain alight until
the boiler controls or any heating controls switch it off.
For domestic hot water only, set switch “C” to “Off”, as shown
in diagram 3.
The main burner will then light when any domestic hot water
tap is opened and go out when the tap is closed.
Which ever position switch “C” is in domestic hot water will
be available.
To Turn the Central Heating Off
To turn the heating off for short periods, set switch “C” to “Off”
as shown in diagram 3 and make sure all the domestic hot water
draw off taps are closed.
Set switch “C” to “On” as shown in diagram 3 to turn the central
heating on again..
To Turn the Boiler Off
To turn the boiler off, isolate the boiler from the electrical supply.
To turn on again following the operating instructions.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than
in the summer.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the
appliance it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.
Servicing/maintenance should be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
behind the controls access door, see diagram 1.
To ensure the continued efficient and safe operation of the
appliance it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of the Gas Safety (Installation and Use) Regulations,
Section 35.
Servicing/maintenance should be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
behind the controls access door, see diagram 4.
Clearances
The boiler requires a clearance in front, below and at the sides
of the casing for safety, servicing and maintenance access, see
diagram 5.
5
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
5
5
1505
5
150
5
*
*
*
*
Increase to 25mm clearance from
combustible material.
Dimensions in millimetres
800
Instructions for Use
Protection Against Freezing
If the boiler is to be out of use for any long periods during severe
weather, it is recommended that the whole system, including
the combination boiler, should be drained to avoid the risk of
freezing.
If in doubt, contact you installation/servicing company for advice.
Draining and Filling
CAUTION. This boiler works in a pressurised system which
must only be drained, refilled and pressurised by a competent
person.
Note: If the pressure gauge indicates a loss of system pressure,
that is, less than 0.7bar, YOU MUST CONTACT YOUR
INSTALLER.
Pressure Relief Safety Valve
CAUTION. A pressure relief safety valve and discharge pipe is
fitted to the boiler. This valve must not be touched. Should there
be any discharge from the pipe, turn the boiler off, isolate from
the electrical supply and contact your installation/servicing
company.
Cleaning
WARNING. This appliance contains metal parts (components)
and care should be taken when handling and cleaning with
particular regard to edges.
The boiler casing can be cleaned using a mild liquid detergent
with a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may
damage the paint work
Boiler Casing
CAUTION. Do not remove or adjust the casing in any way, as
incorrect fitting may result in incorrect operation or failure to
operate at all. If in doubt seek advice from the local gas
company or your installation/ servicing company.
COLD WATER
SUPPLY IN
HEATING
FLOW
SAFETY
VALVE
DISCHARGE
SLOT(OPEN)
HEATING
RETURN
GAS
SERVICE
COCK
WATER VALVES
DRAIN
POINT
HOT
WATER
OUT
SLOT(OPEN)
Diagram 4
2793
2811
Replacement Parts
If replacement parts are required apply to your local supplier or
British Gas.
Please quote the name of the appliance.
SWITCH
'OFF'
5044
CENTRAL HEATING
SELECTOR SWITCH
'C'
SWITCH
'ON'
PRESSURE GAUGE
‘A’
Orange Light 'MAINS'
Green Light 'RUNNING'
Red Light 'LOW C.H. WATER
PRESSURE'
CONTROL
RESET
BUTTON
Diagram 3
6622
Diagram 5
221473B
6
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
63
168
101
KEY:
22mm COMPRESSION
CENTRAL HEATING
15mm COMPRESSION
DOMESTIC WATER
1
1
Rc
/
/
(
in. BSPT)
2
GAS CONNECTION
2
ALL DIMENSIONS in MILLIMETRES
331
133
783
450
SAFETY
VALVE
DISCHARGE
66
107
107
66
2804
63
25
2.5
Diagram 1.1
1.1 Installation
Materials and equipment should be fit for their purpose and of
suitable quality and workmanship.
1.2 Important Notice
This boiler is for use only on natural gas, G20.
1.3 Sheet metal Parts
WARNING. When installing the appliance, care should be
taken to avoid any possibility of personal injury when handling
sheet metal parts.
1.4 Requirements
The installation of this boiler must be carried out by a competent
person in accordance the rules in force in the countries of
destination.
Manufacturer’s instructions, supplied.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
WATER
THROTTLE
MINI
EXPANSION
VESSEL
EXPANSION
VESSEL
FANNED
FLUE
HEAT EXCHANGER
MAIN BURNER
FLOW
SWITCH
SAFETY
VALVE
GAS VALVE
5275
AUTOMATIC
AIR VENT
SPARK
ELECTRODE
PUMP
PRESSURE
SWITCH
7
D.H.W.
COLD
INLET
C.H.
FLOW
GAS
SUPPLY
SAFETY
VALVE DISCHARGE
C.H.
RETURN
Diagram 1.2
D.H.W.
HOT
OUTLET
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.5 Data Label
The data label is on the inner case cover.
1.6 Data
See Tables 1 and 2.
1.7 Gas Supply
The gas installation must be in accordance with the rules in force
in the countries of destination.
The supply from the governed gas meter must be of adequate
size to provide a steady inlet working pressure of 20mbar (8in
wg) at the boiler.
WARNING: The boiler must be earthed.
The electrical installation must be in accordance with the rules
in force in the countries of destination.
All system components shall be of an approved type.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should be by a double pole switched fused spur box,
with a minimum separation of 3mm in both poles. The fused
spur box should be readily accessible and preferably adjacent
to the appliance. It should be identified as to its use.
Alternatively connection can be made through an unswitched
shuttered socket and 3A fused 3 pin plug.
The mains supply cable and other cables connected to the
boiler must be the PVC flexible type of at least 0.75mm
0.20mm).
2
, (24/
BURNERmbar6.215.51.8
PRESSURE in.wg2.66.20.7
APPROX.m3/h2.13.41.2
GAS RATEft3/h75.8121.843.4
TABLE 2
Lift Weight37.0kg (81.4lb)
Total Weight50.4kg (111lb)
● Ball valves are fitted in water and gas connections, plus a drain point on all water connections.
❋ Boiler starts at an inlet pressure of 0.5bar but requires 0.8bar for maximum output.
■ For larger systems use an additional expansion vessel, see Section 4.
221473B
8
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Boiler Position
2.1 Location
The boiler must be installed in accordance with the rules in
force in the countries of destination.
The boiler is not suitable for fitting out of doors.
Any electrical switch or boiler control using mains electricity
must be positioned so that it cannot be touched by a person
using the bath or shower.
The boiler must be mounted on a flat wall which is sufficiently
robust to take its weight, refer to Section 1 ‘Data’.
If the location of the boiler or any part of the system is subject
to severe cold weather conditions, it is recommended that a
frost thermostat is fitted. Any part of the system that may be
vulnerable to freezing must be protected.
If the boiler is to be fitted into a cupboard, compartment or
unusual location, special procedures are necessary.
Make sure that the cupboard or compartment air vents are
positioned to be clear of obstructions at all times, refer to
Section 3.
2.2 Clearances
The boiler should be positioned so that at least the minimum
operational and servicing clearances are provided, see diagram
5 Instructions for Use.
Additional clearances may be required around the boiler for
installation.
For flue installations where external access is not practicable,
the clearances around the boiler may need to be increased as
follows.
For rear flue installations the dimension between the boiler
mounting wall and a permanent facing wall must be a minimum
of “X”, see diagram 3.1 and 3.3, plus 272mm.
For side flue installation the dimension between any adjacent
permanent walls must be a minimum of “Y”, see diagram 3.2
and 3.4, plus 332mm.
9
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.1 Flue
Ventilation must be provided in accordance with the rules in
force in the countries of destination.
The following information refers specifically to his boiler:
3.2 Flue Position and Length
The air and flue ducting connect to the top of the boiler using the
air box and can be positioned in one of three directions:
Rearward, left or right.
The standard flue is able to provide the duct length range shown
in diagram 3.1 for a rear flue or diagram 3.2 for a side flue.
If a longer flue duct is required, do not extend the ductings.
A 1 or 2metre flue system and elbow / terminal kit must be used
and can be supplied.
This is able to provide the duct length range shown in diagram
3.3 for a rear flue, diagram 3.4 for a side flue.
A Vertical Flue Kit can be supplied with instructions.
To make a neat finish to the flue outlet a flue collar kit, part No.
443286, with instructions, is available.
The use of this collar will mean that the flue lengths will need to
be altered, full instructions are given in the kit.
3.3 Terminal Position
The minimum acceptable siting dimensions for the terminal
from obstructions, other terminals and ventilation openings are
shown in diagram 3.5.
The terminal must be exposed to the external air, the position
allowing free passage of air across it at all times.
Car ports or similar extensions of a roof only, or a roof and one
wall, require special consideration with respect to any openings,
doors, vents or windows under the roof. Care is required to
protect the roof if made of plastic sheeting. If the car port
comprises of a roof and two or more walls, seek advice from the
local gas undertaking before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering, an
aluminium shield 1500mm long should be fitted immediately
beneath the guttering or eaves. If the terminal is fitted within
450mm below painted eaves or a painted gutter, an aluminium
shield 750mm long should be fitted immediately beneath the
guttering or eaves.
WALL THICKNESS 'X': 75 TO 408mm
"X"
REAR FLUE - STANDARD
DISTANCE 'Y': 80 TO 353mm
Diagram 3.1
2812
2813
1m DISTANCE 'X' = 75 TO 898mm
2m DISTANCE 'X' = 75 TO 1898mm
"X"
REAR FLUE - 1 and 2 metre
1m DISTANCE 'Y' = 80 TO 843mm
2m DISTANCE 'Y' = 80 TO 1843mm
"Y"
4738
Diagram 3.3
4739
"Y"
SIDE FLUE - STANDARD
Left or Right
221473B
Diagram 3.2
SIDE FLUE - 1 and 2 metre
Left or Right
10
Diagram 3.4
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
A
A
F
G
E
A
G
G
G
B,C
B,C
F
F
K
K
K
C
G
L
L
UNDER CAR PORT etc.
H,I
J
D
F
K
3.4 Terminal Guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
be central over the terminal.
The guard should be similar to that shown in diagram 3.5 and
can be bought from:
Tower Flue Components Ltd.
Morley Road
Tonbridge
Kent
TN9 1RA
their type K3
3.5 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.
2816
3.6 Room Ventilation
The boiler is room sealed, so when it is installed in a room or
space, a permanent air vent is not required.
3.7 Cupboard or Compartment Ventilation
If the boiler is to be fitted in a cupboard or compartment,
permanent high and low level air vents must be provided in
accordance with the rules in force in the countries of destination.
The vents must have at least the effective areas as given in
Table 3.
MINIMUM SITING DIMENSIONS FOR
FANNED FLUE TERMINALS
POSITION
MINIMUM
SPACING
mm
A DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING300
B BELOW GUTTER, DRAIN/SOIL PIPE75
C BELOW EAVES200
D BELOW A BALCONY OR CAR PORT200
E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES75
F FROM INTERNAL OR EXTERNAL
CORNERS300
G ABOVE ADJACENT GROUND OR
BALCONY LEVEL300
H FROM SURFACE FACING THE
TERMINAL600
IFACING TERMINALS1200
J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING1200
K VERTICAL FROM A TERMINAL1500
L HORIZONTALLY FROM A TERMINAL 300
TABLE 3
PositionAir fromAir Direct
ofRoom orfrom
Air VentInternal spaceOutside
High Vent326cm
Low Vent326cm
2
(50in2)163cm2 (25in2)
2
(50in2)163cm2 (25in2)
11
Diagram 3.5
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
Btu/h x
1000kW
60
16
50
14
40
12
10
30
SYSTEM HEATING LOAD
FEET
M
5
15
4
10
3
2
5
AVAILABLE PUMP HEAD
1
0
0
GRUNDFOS
REMAINING CONVEYING CAPACITY OF PUMP
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
VARIOUS SYSTEM HEATING LOADS.
P
U
M
P
C
U
R
V
E
-
S
E
T
T
I
N
G
3
P
U
M
P
C
U
R
V
E
-
S
E
T
T
I
N
G
2
18
11
2.55.0
13
1715
FLOW RATE
1920
4.03.53.0
21
4.5
22
23
0
C
0
F
40
20
35
17
30.6
15
25
11
19.8
10
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL
RANGE
LITRES/Min
GALLONS/Min
Diagram 4.1
4462
*
SYSTEM DIFFERENTIAL TEMPERATURE
Btu/h x
1000kW
60
16
50
14
40
12
10
30
SYSTEM HEATING LOAD
FEET
M
5
15
4
10
3
2
5
AVAILABLE PUMP HEAD
1
0
0
11
WILO
REMAINING CONVEYING CAPACITY OF PUMP
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
VARIOUS SYSTEM HEATING LOADS.
- Setting 2- Setting 1
P
U
M
P
C
U
R
V
E
-
P
U
M
P
C
U
R
V
E
-
S
E
13
2.55.0
S
E
T
T
I
N
G
2
/
W
I
L
T
T
I
N
G
1
/
W
I
L
O
1715
FLOW RATE
O
S
E
T
T
I
N
S
E
T
T
I
N
G
18
4.03.53.0
G
1920
4.5
21
22
23
0
C
0
F
40
20
35
17
30.6
15
25
11
19.8
10
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL
RANGE
LITRES/Min
GALLONS/Min
Diagram 4.1A
4463
*
SYSTEM DIFFERENTIAL TEMPERATURE
221473B
12
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.1 General Notes
The boiler is for use in sealed water systems only.
4.2 Safety Valve
The safety valve is an integral part of the boiler and it cannot be
adjusted.
4.3 Pressure Gauge
A pressure gauge is incorporated into the boiler to indicate the
system pressure.
4.4 Pump
The circulation pump is integral with the boiler.
The remaining circulating pressure head available from the
boiler is shown in diagram 4.1, Grundfos or 4.1A Glow-worm
Wilo.
4.5 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of
8Litres (1.76gallons), with a charge pressure of 0.75bar.
The maximum heating system water content using the fitted
expansion vessel ranges from 119Litres with a cold fill pressure
of 0.7bar, to 98Litres with a cold fill pressure of 1.05bar. If, due
to a high static head, the cold fill pressure is higher, then the
expansion vessel pre-fill pressure must be increased, and the
maximum system volume decreased.
4.6 Flow Rate
A valve must be incorporated in the main flow or return of the
system, valve “A” shown in the flow in diagram 4.2. This valve
must be lockable and positioned so that inadvertent closure or
unauthorised interference is not possible. The design differential
can be between 11°C (20°F) and 17°C (30°F), dependent on
the system resistance and the available pump head.
Grundfos Pump
The pump adjuster should normally be left at maximum (3) but
in some cases it is permissible to adjust the pump to a lower
setting (2). See diagram 4.1.
To use diagram 4.1 start with the required heating system load.
In the example shown the maximum boiler output has been
chosen, 17.6kW (60,000Btu/h).
Draw a horizontal line from the required system differential
temperature axis to intersect the curve. In the example 11°C
(19.8°F) has been chosen, shown . At the point
of intersection draw a vertical line to cross the pump curve.
From this point draw a further horizontal line to determine the
available pump head. In the example 1.9m (6ft3in) is available.
A greater pump head can be achieved by choosing a higher
system differential temperature, up to a maximum of 4.0m (13ft)
at a system differential of 17°C (30.6°F). The system must be
designed such that the available pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h)
then it is permissible to adjust the pump setting to (2),
shown . This results in an available pump
head of 2.1m (7ft). This is the maximum that can be achieved
with the pump at this setting.
Glow-worm Wilo Pump
The pump adjuster should normally be left at maximum (2) but
in some cases it is permissible to adjust to a lower setting (1),
see diagram 4.1A.
To use diagram 4.1A start with the required heating system
load.
In the example shown the maximum boiler output has been
chosen, 17.6kW (60,000Btu/h).
Draw a horizontal line from the required system differential
temperature axis to intersect the curve. In the example 11°C
(19.8°F) has been chosen, shown . At the point
of intersection draw a vertical line to cross the pump curve.
From this point draw a further horizontal line to determine the
available head. In the example 1.9m (6ft3in) is available. A
greater pump head can be achieved by choosing a higher
system differential temperature, up to a maximum of 4.0m (13ft)
at a system differential of 17°C (30.6°F). The system must be
designed such that the available pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h)
then it is permissible to adjust the pump setting to (1),
shown . This results in an available pump
head of 4.2m (13ft9in). This is the maximum that can be
achieved with the pump at this setting.
4.7 Bypass
It is ESSENTIAL that a bypass of 22mm od minimum is fitted to
all installations. The bypass must have a lockable valve, “B” in
diagram 4.2, incorporated in a position so that inadvertent
closure is not possible.
The bypass MUST be fitted before any system control. A
radiator bypass is NOT recommended.
4.8 Make Up
Provision should be made for replacing water lost from the
system using a make up bottle mounted in a position higher than
the top point of the system, connected through a non-return
valve to the return side of the heating circuit, see diagram 4.2.
Alternatively, provision for make up can be made by prepressurisation of the circuit.
4.9 Filling Sealed Systems
Provision for filling the system at a low level must be made.
Three methods of filling are shown in diagram 4.3. There must
be no permanent connection to the mains water supply, even
through a non return valve.
NOTE: It is important that fittings used for connection to potable
water comply with the water undertakers requirements.
4.10 Corrosion Inhibitor
If an inhibitor is to be used in the system, contact a manufacturer
so that they can recommend their most suitable product.
When fitting the boiler into an existing system, special care
should be taken to drain the entire system, including radiators,
then thoroughly cleaning out before fitting the boiler whether or
not adding an inhibitor.
4.11 Draining Tap
A draining tap must be provided at the lowest points of the
system, which will allow the entire system to be drained. An
additional draining tap MUST be fitted close to the boiler.
The flow and return isolation valves are provided with drain
points for boiler heat exchanger drainage.
13
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
3-LITRE
MAKE-UP
BOTTLE
(if required)
NON-RETURN
VALVE
AUTO AIR
VENT
ADDITIONAL
EXPANSION
VESSEL
(if required)
HEATING
CIRCUIT
BOILER
MIN. 22mm
DIA. BY-PASS
RETURN
'A'
FLOW CONTROL
VALVE
'B'
BY-PASS
VALVE
DOMESTIC
WATER
HOT
FILLING
POINT
DRAIN
POINT
Diagram 4.2
2818
COLD SUPPLY
METHOD 1
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 2
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 3
CISTERN
HOSE
UNIONS
SUPPLY STOP
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HOSE
UNIONS
SUPPLY STOP
VALVE
OVERFLOW
SERVICING
VALVE
COMBINED
CHECK VALVE
AND VACUUM
BREAKER
SERVICING
VALVE
SERVICING
VALVE
PRESSURE
REDUCING
VALVE
HEATING
SYSTEM
HEATING
SYSTEM
HEATING
SYSTEM
3132
5 Domestic Hot Water System
5.1 General
The domestic hot water service must be in accordance with the
rules in force in the countries of destination.
5.2 Water Pressure
For the minimum and maximum working pressures of the
domestic hot water circuit of the boiler, refer to Section 1.6
‘Data’.
If the cold water supply pressure exceeds the maximum, a
pressure reducing valve must be fitted in the supply to the boiler
to reduce the pressure to within the limits given.
SUPPLY
STOP VALVE
SUPPLY
PIPE
HOSE
UNIONS
DOUBLE CHECK
VALVE ASSEMBLY
Diagram 4.3
5.3 “Hard” Water Areas
In areas where the water is “hard”, that is, more than 200mg/
litre, it is recommended that a proprietary scale reducer is fitted
in the cold supply to the boiler. Check the total water “hardness”
using the kit supplied, in the door, following the instructions
given. Consult the local water undertaking for additional advice.
A double check valve assembly must be fitted upstream of the
scale reducer. For the relative position of the scale reducer and
pressure reducing valve, if required, refer to the manufacturer’s
instructions.
221473B
14
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installation Preparation
6.1 Unpacking
Remove the top carton and cut out the flue template from the
inner flap.
Open the control door, see diagram 6.1.
Remove the two screws securing the outer case and then lift
it at the top and pull it forwards and off, see diagram 6.1.
Remove the cover of the inner case, secured with four
screws, see diagram 6.2
Disconnect the gas cock union and the front unions of the
isolation valves, see diagram 6.3.
Slightly loosen the clips of the gas service cock and the
isolating valves.
Remove the two boiler securing screws then remove the
boiler from the mounting frame, by pulling the studs from the
clips and unhooking it at the top.
6.2 Marking
The boiler mounting frame is the same width as the boiler
but the flue connection sticks out above it.
Place the boiler mounting frame on the wall in the required
position, see diagram 2.1 to maintain minimum clearances.
Make sure that the isolation valves are at the bottom facing
forwards and that the frame top is horizontal, then mark the
four wall fixing points through the holes in the two horizontal
straps.
Position the flue template on the wall, the arrow points on the
centres of the two upper fixing points previously marked,
see diagram 6.4 which also shows dimensions.
For rear flue, mark the rear flue position as required, centre
and/or diameter.
For a side flue, mark the horizontal flue centre line at the
sides of the template. Extend the flue centre line horizontally
left or right to the internal corner where the flue is required
to exit to outside. Mark the position of the circular hole, on
the flue exit wall, using the dimensions given in diagram 6.5.
From the flue position marks, check that the flue terminal will
be in a suitable position, see diagram 3.6.
6.3 Flue Hole Cutting
Cut the hole horizontally in the wall, to the diameter shown
in diagram 6.4, using, preferably, a core drill.
INNER
CASE
COVER
SECURING
SCREW (4)
PILOT
WINDOW
SCREW (2)
DATA LABEL
5040
Diagram 6.2
6957
SECURING SCREW (2)
RESET SWITCH AND NEON
INDICATOR
CLOCK TIMER
IF FITTED
6622
CENTRAL
HEATING
SELECTOR
SWITCH
LOCATION
CLIPS
DOOR
CLIP (5)
OUTER CASE SECURING
SCREW (2)
OUTER CASE
Diagram 6.1
15
UNIONS (5)
Diagram 6.3
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installation Preparation
6.4 Wall Sleeve
Note: If required, an optional Wall Liner Kit, Part No.900862, is
available, complete with fixing instructions.
C
L
MIN.
CLEARANCE
584
87
104
480
FLUE
TEMPLATE
(Cut from
carton top
inner flap)
115Dia.
FLUE
CENTRELINE
TOP OF
BOILER
BOILER
MOUNTING FRAME
FIXINGS POINTS
300
Diagram 6.4
6.5 Boiler Mounting Frame Fixing
Position the flue template over the flue hole and check the
position of the wall fixing points. Mark the position of the fixing
holes again, if required.
Drill the four fixing holes and insert wall plugs to suit
No.10x50mm long screws.
Secure the boiler mounting frame to the wall using
No.10x50mm long screws.
CORNER
(Left Flue)
FLUE
CENTRE
LINE
2882
CORNER
(Right Flue)
115Dia.
168168
C
L
2304
Diagram 6.5
7 Flue Preparation
7.1 Flue Length
For a rear flue, measure the distance from the outside wall face
to the boiler mounting wall. Check that the flue length will be
suitable, see diagram 3.1 for a standard flue system or diagram
3.3 for a long flue system.
For a side flue, measure the distance from the outside wall face
to the side of the boiler mounting frame. Check that the flue
length will be suitable, see diagram 3.2 for a standard flue
system or diagram 3.4 for a long flue system.
All long flue systems are installed in a similar manner to the
standard flue.
7.2 Rear Flue
Mark the air duct assembly and the flue duct at the lengths
shown in diagram 7.2 then cut to length, cutting square and
removing any burrs.
Mark a line 34mm from the end of the flue duct, see diagram 7.4.
7.3 Side Flue
Mark the air duct assembly and the flue duct at the lengths
shown in diagram 7.3 then cut to length, cutting square and
removing any burrs.
Mark a line 34mm from the end of the flue duct, see diagram 7.4.
FLUE
TERMINAL
FLUE DUCT
63
OUTSIDE
WALL FACE
X + 165
( AIR DUCT ASSEMBLY)
2884
Diagram 7.1FLUE TERMINAL
2823
X
OUTSIDE
WALL FACE
REAR DUCT
221473B
16
BOILER
MOUNTING
WALL
X + 115
( FLUE DUCT )
Diagram 7.2
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
7.4 Flue Assembly
Fit and secure the flue elbow, see diagram 7.4.
Insert the flue and spacer into the air duct.
Fit the air box spigot plate in the correct position on the air box
according to left, right or rear flue.
Fit the air and flue duct assembly to the boiler, see diagram 7.5.
Note: Fully insert the air duct into the air box spigot. Make sure
the flue terminal is in the correct orientation, marked TOP and
the flue duct is engaged in the flue terminal.
Drill a hole, diameter as shown in diagram 7.6, in each side of
the air duct, through the holes in the air box. Secure the air duct
to the air box using the two screws provided in the loose items
pack.
Note: If side or front access is restricted then it may be
necessary to carry out the above operation after passing the
flue through the wall.
Seal around the joint between the air duct and the air box using
the tape provided in the loose items pack.
Place the flue assembly into the flue hole, to make sure that the
flue terminal is correctly positioned and sticking out the correct
distance from the outside wall face, see diagram 7.1 and the
appropriate diagram 7.2 or 7.3.
Remove flue assembly.
FLUE DUCT
MARK LINE
34mm
CLIP
STANDARD FLUE
SECURING
NUT (4)
AIR DUCT
FLUE ELBOW - Excercise
caution when handling this
component (push onto, flue
duct up to the line)
WASHER (4)
AIR DUCT
2825
FLUE
DUCT
SPACER
Diagram 7.4
2826
7.5 Internal Access Flue
If access to the outside wall surface is not practical, the flue
system can be installed from inside. Use of the optional wall
liner kit is required, see diagram 7.7.
Y + 172
(FLUE DUCT)
Y
Y + 209
(AIR DUCT
ASSEMBLY)
OUTSIDE
WALL
FACE
SIDE DUCT -STANDARD FLUE
SIDE
OF
BOILER
MOUNTING
FRAME
Diagram 7.3
2824
AIR BOX
SPIGOT
PLATE
AIR BOX / FLUE
ASSEMBLY
FLUE DUCT
FLUE
TERMINAL
TAPE
AIR DUCT
SCREW (2)
AIR BOX
Diagram 7.5
3.3 DIA
HOLE IN EACH SIDE
OF THE AIR DUCT
AIR BOX
STANDARD FLUE ILLUSTRATEDDiagram 7.6
OUTSIDE WALL FACE
AIR
DUCT
FLUE
TERMINAL
SEAL
STANDARD FLUE ILLUSTRATED
WALL
LINER
Diagram 7.7
2827
2302
17
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Gas and Water Connections
8.1 Gas Connection
The gas supply can be connected from below or through the
wall at the rear of the boiler, see diagram 8.1 for position.
Refer also to section 1.7
Make the gas supply connection to the gas
Service cock. Slacken or remove the clip, as desired, whilst
making the connection. Do not subject the gas service cock to
heat.
8.2 Water Connections
Provision is made for the water connections to be made from
below or through an internal wall at the rear of the boiler, see
diagram 8.1 for position.
Provision is made for the domestic hot water outlet and heating
flow and return pipes to be connected from above, if desired,
passing down either side of the boiler, see diagram 8.2 for
clearances. Take care that any pipework connected from
above, within the boiler mounting frame will clear the expansion
vessels.
Flush out the domestic hot water and the heating systems
before connecting to the boiler.
Make the connections to the domestic hot water outlet by
straight connector and heating systems by way of the isolating
valves, see diagram 8.1.
Slacken or remove the clips, as desired, while making the
connections. Do not subject any of the isolating valves to heat.
Make sure that the drain points on the isolating valves are
positioned towards the front of the boiler, also that the drain and
operating screw heads are accessible.
'NOTCH' MARKING POSITION OF
SAFETY VALVE DISCHARGE
63
DOMESTIC
COLD
WATER
SUPPLY IN
SLOT (CLOSED)
CENTRAL
HEATING
FLOW
DRAIN POINT
GAS
SERVICE
COCK
BOILER
MOUNTING
FRAME
CENTRAL
HEATING
RETURN
2297
DOMESTIC
HOT
WATER
OUT
SLOT
(CLOSED)
Diagram 8.1
2828
8.3 Safety Valve Discharge
WARNING. It must not discharge above an entrance or window
or any type of public access area.
A short discharge pipe is supplied loose with the boiler, which
when fitted to the safety valve, will end below the boiler at the
mark between the cold water inlet and the heating flow, for
position and dimension see diagram 8.1.
This must be extended, using not less than 15mm od pipe, to
discharge, in a visible position, outside the building, facing
downwards, preferably over a drain
The pipe must have a continuous fall and be routed to a position
so that any discharge of water, possibly boiling, or steam cannot
create any danger to persons, damage to property or external
electrical components and wiring.
Note. To ease future servicing it is advisable to use a
compression type fitting to extend the discharge pipe.
20mm
EXPANSION
VESSEL
POSITION
120mm
115mm
MINI
EXPANSION
VESSEL
46mm
320mm
221473B
18
DOMESTIC
WATER
NOTE:
KEEP ANY PIPEWORK
CLEAR OF SHADED AREA
CENTRAL
HEATING
Diagram 8.2
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
9.1 Supply Cable Connection
CAUTION. To prevent an induced current from switching the
central heating on, when not required, it is important that the
heating system control cables are separated from the other
mains supply cables.
The boiler requires a permanent mains supply through an
isolator which must also isolate any heating system controls,
see diagram 9.2.
Any heating system controls must not interrupt the permanent
mains supply to the boiler.
Remove the electrical connector from the loose items pack.
Remove the two screws and cover from the connector, see
diagram 9.1.
Using PVC cable of suitable length and rating as stated in
Section 1.8, connect the mains supply cable to the appropriate
terminals of the connector, see diagram 9.2.
Standard colours are, Brown - Live; Blue - Neutral; Green and
Yellow - Earth.
The mains cable outer insulation must not be cut back external
to the plug, see diagram 9.1.
Make the earth cable of a greater length so that if the cable is
strained the earth would be the last to become disconnected.
CAUTION. It is essential that the polarity is correct.
E
N
L
3
COVER
SCREW (2)
2643
RED LINK
Remove when
connecting any
heating system
1
2
CABLE
CLAMP
controls.
MAINS
CABLE
Diagram 9.1
9.2 Heating System Controls
CAUTION: To prevent an induced current from switching the
central heating on, when not required, it is important that the
heating system control cables are separated from the other
mains supply cables.
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the
room thermostat.
Note: For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.
If electrical controls are not to be used to regulate the heating
system, do not disturb the red link cable.
When any form of electrical control is being used to regulate the
heating system, remove the red link cable and connect heating
system controls in series.
The mains cable outer insulation must not be cut back external
to the plug.
9.3 Clock/Timer Kit
An internal clock/timer kit can be supplied, refer to the literature
supplied with it.
9.4 Frost Thermostat
If the installation requires protection by a “frost thermostat”,
connect a single pole type, to the appropriate terminals of the
connector.
9.5 Cable and Connector Securing
After completing all the connections to the boiler, secure the
cable(s) with the cover, using the two screws previously
removed, see diagram 9.1.
19
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
EXTERNAL CLOCK
RED LINK.
REMOVE WHEN
CONNECTING ANY
HEATING SYSTEM
CONTROLS
TIME
CONTROL
JUNCTION
BOX
3 AMP
FUSE
DOUBLE
POLE
ISOLATOR
230V~50Hz
PERMANENT
MAINS SUPPLY
(3) (L) (N) (E)(2)
CLOCK
LNE
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
SWITCH
CONTACTS
ROOM
THERMOSTAT
FROST
THERMOSTAT
ELECTRICITY SUPPLY CONNECTIONS
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
MAINS POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz ROOM STAT. NO FROST STAT.
INTEGRAL CLOCK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(1)
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
POTENTIAL
FROST STAT.
230V~50Hz
FROST STAT. NO ROOM STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
230V~50Hz
FROST STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
MAINS
POTENTIAL
FROST STAT.
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT. USED AS LINK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
230V~50Hz
POTENTIAL
FROST STAT.
RED
LINK
MAINS
MAINS
POTENTIAL
ROOM STAT.
5217
(3) (L)(N)(2)(1)
3 AMP
FUSE
230V~50Hz
PERMANENT MAINS
DOUBLE
LN
POLE
ISOLATOR
SUPPLY
POTENTIAL
FREE ROOM STAT. NO FROST STAT.
221473B
(E)
E
POTENTIAL FREE
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT.
20
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
E
230V~50Hz
PERMANENT MAINS
SUPPLY
230V~50Hz
FROST STAT.
JUNCTION
BOX
230V~50Hz
POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
Diagram 9.2
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.1 Mounting the Boiler
After installing the boiler mounting frame, gas, domestic and
heating systems, making the electrical connections and
preparing the flue components, continue as below:
Lift the boiler into position, hooking it onto the boiler mounting
frame at the top, then loosely fit the two boiler securing screws
at the top, see diagram 6.3.
10.2 Gas and Water Connections
Locate the boiler water pipes into the isolation valves and the
gas service cock union halves.
Fully push the boiler back to the mounting frame, locating the
studs into the clips.
Make the compression joint on the isolating valves and join the
gas service cock union. Secure all of the valves and gas service
cock with the clips.
10.3 Boiler Securing
Secure the boiler by tightening the two boiler securing screws
at the top.
10.4 Discharge Pipe
Remove the two control housing securing screws, see diagram
10.1.
Remove the control housing, and support the control housing
on a surface or by screwing it to the front edge of the base, using
one of its securing screws,see diagram 10.1.
If required, to improve access, the air pressure switch can be
removed , refer to the service instruction, section 4.31
Fit the short discharge pipe to the safety valve using the nut and
olive supplied loose, see diagram 10.2.
Extend the discharge, refer to Section 8.3
Refit the pressure gauge.
TEMPERATURE
FASCIA
CONTROL HOUSING
SECURING SCREW (2)
CONTROL
HOUSING
COVER
CONTROL KNOB
CONTROL HOUSING
COVER SECURING
SCREW
SECURING SCREW
(To support the control
housing if necessary)
UNION
CONNECTION
3911
FASCIA
SECURING
SCREWS (3)
Diagram 10.1
2795
DISCHARGE
PIPE
10.5 Clock/timer Kit (if applicable)
Fit the clock/timer kit following the appropriate sections of the
instructions supplied with it.
10.6 Electrical Connector
Connect the two halves of the electrical connector together.
Clip the connector into position on the boiler mounting frame
and secure the cables with cable clamp immediately behind the
connector.
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of cables.
3. Test the polarity of the mains.
FLUE
ELBOW
CLIP
FAN
ELBOW
'NOTCH'
Diagram 10.2
ELECTRICAL
CONNECTORS
FAN
SECURING
SCREW (2)
Diagram 10.3
2832
21
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.7 Flue Fixing
Remove the air box access plate from the front of the air box,
see diagram 10.4.
Pass the prepared air box and flue assembly into and through
the wall.
Place the air box gasket supplied in the loose items pack,
between the boiler top and airbox.
Loosely fit the air box to the boiler.
Using the air box access hole, fit the flue elbow onto the fan
outlet and secure with the flue elbow clip, see diagram 10.3.
MAKE SURE THAT THE FLUE DUCT REMAINS ENGAGED
IN THE TERMINAL.
Tighten the screws securing the air box to the top of the boiler
taking care not to damage the air box gasket.
Refit the air box access plate and gasket
Make sure that the ductings do not slope down towards the
boiler.
Make the wall good internally and externally around the air duct.
AIR BOX
ACCESS PLATE
AND GASKET
SECURING
SCREW
Diagram 10.4
2833
11 Commissioning
11.1 Filling Domestic Water Circuit
Check that the boiler is isolated from the electrical supply, at the
external isolator.
Fully open the domestic water supply stop cock or valve in the
supply to the boiler.
Open the two domestic water isolation valves, slots in line with
the length of the valve, see diagram 8.1.
Open all hot water draw-off taps and close them when the water
flows. Check for water soundness of the complete domestic
water system.
11.2 Filling the Heating Circuit
REMINDER: It is essential that a bypass is fitted in all
installations, refer to Section 4.7.
Open the two central heating isolating valves, slots in line with
the length of the valve, see diagram 8.1.
Flush, fill and vent the system refer to Section 4.9.
WARNING. Several components operate on mains voltage
and witH THE OUTER CASE REMOVED THEY BECOME
EXPOSED.
To assist in filling and venting, the pump may be used. Turn on
the electrical supply, if red lockout neon is lit press reset switch,
wait 15 seconds between attempts, set switch “C” to “ON” (see
diagram 11.1) any remote heating system controls, time switch
and room thermostat, for duty, see diagram 11.1.
Note. If the clock/timer kit is to be fitted, refer to the setting
instructions in the Instructions for Use.
Make sure that the automatic air vent is operating correctly, see
diagram 1.2.
Alternate the position of switch “C” between “ON” and “OFF” to
make sure that water flows through all parts of the boiler and air
is not trapped in the boiler internal bypass.
Pressurise the system until the pressure is 1.5bar (21.5lbf/in
pressure gauge “A”, see diagram 11.1.
Check the heating system and boiler for mwater soundness.
2
11.3 Preparation for Lighting
Isolate the boiler from the mains electrical supply at the external
isolator.
Test for soundness and purge air from the gas supply in
accordance with the rules in force in the countries of destination.
Turn on the gas service cock, slot in line with the length of the
cock.
Loosen the burner pressure test point screw and connect a
suitable pressure gauge, see diagram 11.2.
11.4 Burner Pressure - Hot Water
The burner pressure is factory preset and no adjustment should
be required.
Connect the electrical supply, the pump will operate for about 30
seconds, then the pump stops.
Fully open the largest hot water draw off tap whereby the main
burner will light, the flames gradually increasing to maximum.
Check the soundness of the boiler gas joints, with the main
burner on, using leak detection fluid. Take care not to splash
any of the electrical components.
Fully open the hot water throttle, (clockwise), see diagram 11.4.
Check that the water flow rate is not less than 14Litre/min
(3.1gall/min) to prevent any modulation of the gas pressure.
This is equivalent to 4.3 seconds to fill a 1Litre container (2.4
seconds for 1pint).
To achieve this flow rate a water pressure of at least 0.8bar is
required during commissioning, although subsequently the
appliance will work at a minimum pressure of 0.5bar.
),
221473B
22
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
This flow rate should prevent any modulation of the gas pressure.
Check the burner pressure is within +/-0.35bar (+/-0.14in wg)
of 15.5mbar (6.2in wg), the hot water burner pressure. If this is
incorrect, the burner pressure may be adjusted to the correct
setting by turning the hot water gas pressure adjuster
(potentiometer), using an insulated screwdriver, see diagram
11.3. Gain access to the adjusters on the control board by
removing the control housing cover, see diagram 11.3. Turn the
adjuster slowly, always making adjustment by reducing below
the required pressure then increasing up to the required setting
(turn clockwise to increase).
Close the hot water draw off.
If the maximum pressure cannot be obtained, check that the gas
supply is of adequate size, refer to Section 1.7.
11.5 Gas Rate Modulation
The minimum gas rate is factory preset and no adjustment
should be required.
ALWAYS CHECK HOT WATER BURNER PRESSURE FIRST
- REFER TO SECTION 11.4.
To check the minimum gas rate, first make sure that the boiler
is isolated from the electrical supply at the external isolator.
Disconnect one of the electrical connectors (grey), from the
modulator, see diagram 11.3. Insulate the connector to make
sure that it does not contact any metallic part of the boiler.
Switch on the electrical supply.
Fully open a hot water draw off tap and the main burner will light
at minimum gas rate.
Check that the burner pressure is 1.8mbar +/-0.2mbar (0.7in wg
+/-0.1in wg). If this is incorrect, it may be adjusted by removing
the cap and turn the larger adjusting nut of the modulator,
(anticlockwise to decrease pressure).
If the above adjustment was necessary, it will be essential to
check that the maximum pressure can still be obtained. Push
the spindle gently in to the stop and hold it in. The maximum
pressure should not be less than 16.0mbar (6.4in wg). If this
pressure cannot be achieved, obtain it by turning the small
adjusting nut (clockwise to increase the pressure). Always
adjust the minimum pressure first.
If the maximum pressure is unobtainable, check that the gas
supply is of adequate size, refer to Section 1.7. Put right as
necessary.
Isolate the boiler from the electrical supply then reconnect the
modulator cable and refit the cap.
11.6 Domestic Water Flow Rate
Adjust the water throttle to obtain a flow rate of 12Litre a minute
(2.6gall/min), clockwise to increase, see diagram 11.4. This is
equal to 5.0 seconds to fill a 1Litre container, 2.8 seconds to fill
a 1pint container.
Close the tap when adjustment is satisfactory.
The minimum water flow rate for operation of the boiler is
3.6Litre a minute, (0.8gall/min), equal to 16.5 seconds to fill a
1Litre container, 9.5 seconds for 1pint. If this flow rate cannot
be achieved, check that there is no blockage and that the supply
pressure is adequate.
Refer to Table 2.
Close the hot water draw off tap.
SWITCH 'ON'
CENTRAL HEATING
SELECTOR SWITCH 'C'
PRESSURE
GAUGE 'A'
LARGE
ADJUSTING
NUT (MIN.
PRESSURE)
SMALL
ADJUSTMENT
NUT (MAX.
PRESSURE)
CAP
SWITCH 'OFF'
5044
NEON
RESET
BUTTON
SPINDLE
SCREW
Diagram 11.1
TEST
POINT
ELECTRICAL
CONNECTOR
(GREY)
Diagram 11.2
5048
5052
23
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.7 Burner Pressure - Heating
The burner pressure is factory preset and no adjustment should
be required.
Check that all remote heating system controls, room thermostats,
time switches and the like are switched on/programmed and
calling for heat.
Set switch “C” to “ON”, white flash showing, see diagram 11.1.
The pump will circulate water through the boiler and the main
burner will light.
Check that the burner pressure, with the heating system cold
and temperature control knob at maximum, to prevent any
modulation of the gas pressure, is within +/- 0.2mbar (+/-0.08in
wg), of 6.2mbar (2.6in wg). If the burner pressure is incorrect,
it may be adjusted to the correct setting by turning the central
heating gas pressure adjuster (potentiometer) using an insulated
screwdriver, see diagram 11.3. Turn the adjuster slowly,
always making adjustment by reducing below the required
pressure then increasing up to the required setting, turn clockwise
to increase.
Isolate the boiler from the electrical supply.
Remove the pressure gauge and tighten the test point screw.
Test for gas soundness around the burner pressure test point
with the main burner alight, using a suitable leak detection fluid.
Refit the cover of the control housing and refit the housing to the
boiler.
11.8 Temperature Settings
The domestic hot water outlet and central heating flow
temperatures are factory preset and sealed.
The nominal temperature setting for the Domestic Hot Water
outlet is 55oC (131oF) at a flow rate of 3.6Litre a minute (0.8gal/
min).
The nominal flow temperature setting for central heating is 82
o
F), with the user central heating temperature control set to
(180
maximum.
o
11.9 Heating System Commissioning
Check that all remote system controls and integral clock are
calling for heat.
Fully open radiator valves, flow control valve “A” and bypass
valve “B”, see diagram 4.2.
Set the heating system in operation and balance the radiators.
Adjust the flow control valve “A” to achieve the required system
differential temperature between the boiler flow and return.
Turn off all radiators, then adjust bypass valve “B” to achieve the
same temperature difference between the boiler flow and
return.
Refer to Section 4.6 and diagram 4.1.
Allow the system to reach maximum temperature then switch
off, isolate the boiler from the electrical supply and drain the
system rapidly whilst hot, using the external drain tap at the
lowest point of the system.
Fill and vent the system as described previously in Section 11.2.
Add the inhibitor, if required, refer to Section 4.10.
Lower the pressure to the initial cold fill design pressure, using
the draining tap, close to the boiler, refer to Table 2 and 4
Section 4.11.
Set pointer on the pressure gauge to this pressure.
Lock or remove the handles from the spindles of flow control
valve “A” and bypass valve “B” to prevent unauthorised
adjustment.
C
CENTRAL
HEATING
GAS PRESSURE
ADJUSTER
DO NOT
ADJUST
CONTROL
BOARD
HOT WATER
GAS
PRESSURE
ADJUSTER
Diagram 11.3
5085
DOMESTIC
HOT WATER
THROTTLE
2801
Diagram 11.4
221473B
24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.10 Completion
The user control door is designed for left or right hand hinging.
If required the hinge can be moved to the other side to that
supplied, as follows:
Remove the hinge pin bracket securing screw then remove the
hinge pin retaining bracket and, holding the door, remove the
hinge pin. Prise out the hinge pin bushes and fit on to the
opposite side of the door, see diagram 11.5.
Remove the screw and nut and fit to the opposite side of the
case. After removing the other hinge pin retaining bracket refit
the door and hinge pin. Refit the hinge pin retaining bracket and
fit the securing screw.
Fit the catch assembly, supplied on the loose items pack, see
diagram 11.5.
If required, fit the plastic covers to hide the bracket securing
screw.
Change the position of the “Push” label to suit new door opening.
Clock/timer, if fitted, remove the screws, nuts and washers to
release the cover plate, see diagram 11.5.
Stick the casing label to the right hand side of the clock/timer.
Fit the outer case, secure with the four screws, see diagram
11.5.
Note: Secure with the two outer screws only if there is no clock/
timer fitted.
Set the boiler and any remote heating control to the desired
settings, then close the door.
11.11 Instruct the User
Instruct and demonstrate the lighting procedure and advise the
user on the safe and efficient operation of the boiler.
Instruct on and demonstrate the operation of any heating
system controls.
Advise the user on the use and maintenance of any scale
reducer and pass on any relevant instructional documents.
Advise that to ensure the continued efficient and safe operation
of the boiler it is recommended that it is checked and serviced
at regular intervals. The frequency of servicing will depend upon
the installation conditions and usage, but in general, once a year
should be enough.
Draw attention, if applicable, to the current issue of the Gas
Safety (Installation and Use) Regulations, Section 35, which
imposes a duty of care on all persons who let out any property
containing a gas appliance.
It is the Law that any servicing is carried out by a competent
person.
Advise the user of the precautions necessary to prevent damage
to the system, boiler and the building, in the event of the heating
system being out of use during frost or freezing conditions.
Reminder - Leave these instructions with the user.
Because of our constant endeavour for improvement details
may vary slightly from those given in these instructions.
HINGE PIN
RETAINING
BRACKET
BRACKET
SECURING
SCREW
HINGE PIN
SCREW (2)
NUT &
WASHER(2)
PLASTIC COVERS
COVER
PLATE
HINGE PIN
PLASTIC BUSH (2)
CATCH
ASSEMBLY
SECURING NUT
6524
OUTER CASE
SECURING
SCREWS (4)
Diagram 11.5
25
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals.
The frequency of servicing will depend upon the particular
installation conditions and usage, but in general once a year
should be enough.
The servicing of this boiler must be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
NOTE: To obtain a products of combustion reading, remove the
outer case see diagram 1.2.
Disconnect the clear upper tube from the air pressure switch,
see diagram 1.3 and 4.26, insert the analyser probe into the
tube.
Typical values for this boiler at maximum domestic hot water
demand are:-
CO
7.0% to 8.0% and CO 0.005% to 0.020%
2
These figures are based on a 300mm length rear flue.
Make sure the appliance does not modulate whilst checking
combustion and allow the appliance to warm up for 5 minutes.
before taking reading.
Unless stated otherwise, parts removed or renewed during
servicing should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying
components, ALWAYS test for gas soundness and carry out
functional checks of controls.
Throw away all used sealing washers, gaskets and “O” rings
when renewing components.
Use the new ones supplied with the replacement.
1.3 Isolation of Boiler
Before starting any servicing or the replacement of parts, isolate
the boiler from the electrical supply at the external isolator and
close the gas service cock, see diagram 1.1.
BEFORE DRAINING THE BOILER, REFER TO SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door catch is
spring loaded, to open, push the side opposite to the hinge then
pull.
Remove the two screws securing the outer case then unhook
the case at the top and pull it forwards and off, see diagram 1.2.
Note: Remove the four securing screws if there is a clock/timer
fitted.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four screws,
see diagram 1.3.
CONTROL
RESET BUTTON
SELECTOR
SWITCH
CLOCK TIMER
6622
1.2 Data Label
The data label is positioned on the front of the inner case cover,
see diagram 1.3.
COLD WATER
SUPPLY IN
HEATING
FLOW
SAFETY
VALVE
DISCHARGE
SLOT
(CLOSED)
GAS
SERVICE COCK
HEATING
RETURN
DRAIN
POINT
HOT
WATER
OUT
SLOT
(CLOSED)
Diagram 1.1
2793
DOOR
OUTER CASE SECURING SCREW (2)
(IF CLOCK TIMER FITTED (4))
INNER CASE
COVER
SECURING
SCREW (4)
DATA LABEL
PILOT WINDOW
SCREW (2)
AIR
PRESSURE
SWITCH
Diagram 1.2
5040
Diagram 1.3
221473B
26
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.6 System Pressures and Draining
All parts containing water of the central heating circuit within the
boiler, are under the system pressure. Before any parts of this
circuit are disconnected, reduce the system pressure at the
external draining tap, turn the central heating isolating valves
off, and drain at the drain points on the appropriate valves, see
diagram 1.1.
All water containing parts of the domestic hot water circuit of the
boiler will be under the supply water pressure. Before any parts
2 Servicing
2.1 Isolation and Access
Before commencing, refer to Section 1.1.
Isolate the boiler from the electrical supply and close the gas
service cock, refer to Section 1.3.
Remove the outer case and the cover of the inner case, refer to
Sections 1.4 and 1.5.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the flue collector secured by two screws, see diagram
4.1.
Remove the main burner, refer to Section 4.2.
2.2 Cleaning Heat Exchanger
Place a sheet of paper or similar in the combustion chamber, to
act as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove paper
together with any debris
2.3 Cleaning Main Burner
Use a vacuum cleaner or suitable brush to clean the burner
thoroughly, making sure that all burner ports are clear and
unobstructed.
Do not use a brush with metallic bristles.
of this circuit are disconnected, turn the domestic cold water
isolating valve off, open the hot water taps to reduce the water
pressure in the boiler, and drain the boiler at the valves, see
diagram 1.1.
After replacing any water containing part of the central heating
circuit, make up the water loss, vent all air and pressurise the
system. Refer to “Commissioning” in the Installation Instructions.
Check for water soundness and that the safety valve seats
without leaking.
When fitting the flexible tubes to the air pressure switch make
sure the lower (red) tube from the fan connects to the lower
connection of the switch.
Connect the electrical cables to the fan, the polarity of the two
connectors is not important, see diagram 4.1.
Secure the flue collector and combustion chamber front panel
by tightening the wing nut and screws, evenly, see diagrams 4.1
and 4.2.
2.6 Operational Checks
Light the boiler, carry out operational checks and any necessary
adjustments as described in “Commissioning” in the Installation
Instructions.
2.7 Completion
Hook the outer case on at the top and secure with the screws
previously removed, see diagram 1.2.
Close the door.
SENSING
ELECTRODE
5017
2.4 Service Checks
Inspect the spark and sensing electrodes, Clean or renew if
necessary, refer to Sections 4.4, 4.5, 4.6 and 4.7.
Check the main injector, cleaning or renewing as necessary,
refer to Section 4.3.
Before replacing any of the parts removed during servicing,
inspect the condition of all seals and joints, renewing them as
necessary.
Check the condition of the combustion chamber insulation. If
renewing, refer to Section 4.30.
Check that the spark and sensing gaps are as shown in diagram
2.1.
2.5 Initial Assembly
Make sure that the main burner is located on the main injector
and is horizontal, the tips of the rearmost blade under the two
burner guides.
The combustion chamber front panel should be fitted loosely,
then the flue collector also fitted loosely, making sure that it is
seated correctly on the heat exchanger and over the top edge
of the front panel.
To fit the fan, locate it into the rear bracket and ease the flue
elbow onto the fan outlet and secure with the two screws, see
diagram 4.1.
SPARK
ELECTRODE
+0.5
5
-0.5
EARTH
ELECTRODE
SPARK AND SENSING GAP
3
+0.5
-0.5
+0.5
5
-0.5
Diagram 2.1
5059
27
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
3.1 Initial Checks
CONTROL BOARD
TERMINALS,
BLOCK 3
CONTROL BOARD
TERMINALS,
BLOCK 2
3
2
2B
2B
2A
2A
2A
TRANSFORMER
CONTROL BOARD
PERMANENT
LIVE 230V~50Hz
T2A
FUSE
LOW
VOLT
24V~
CVI IGNITION UNIT
230V~
br
b
br
br
4b
5b
6b3a
br
b
or
p
y
bl
w
br
b
br
LN
br
N/CN/O
br
(L)
OPTIONAL
SWITCHED LIVE
FROM ROOM
STAT. 230V~50Hz
COMMON
CLOCK/TIMER
b
(N)
b
p
y
(L)
(N)
ON
PUMP
APS
FAN
RESET /
NVLO
INDICATOR
C
3
36
M
(N)
BOILER
OVERHEAT CUT OFF
br
If the boiler fails to operate, first check the following:
1) That the electrical supply is available at the boiler and the
fuses are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED
BY INCORRECT TESTING WITH THE POWER ON.
2) Make sure that the system pressure gauge registers 0.7bar,
minimum, and that the automatic air vent works. Refer to
Installation Instructions, Section 11.2.
3) That the gas supply is available at the boiler and purged of
air.
4) That the boiler is set for the required service.
5) With the boiler central heating selector switched “Off”, see
diagram 1.2 check that the domestic water supply is available
and water flows freely from the hot taps. Close the taps.
6) With the boiler central heating selector switched “ON”, see
diagram 1.2, check that all heating system controls, if fitted, are
working correctly and calling for heat. If not isolate the boiler
from the electrical supply. Disconnect the rear multipole
connector at the base of the boiler and release the cable from
the clamp.
Remove the connector cover and dependent on the type of
control fitted test for continuity, mains or at terminals 1 and 2,
see diagram 3.1.
7) Check reset button - if red neon is lit press button. In certain
circumstances the red neon light may not come on, due to no
system demand. Turn on a domestic hot water draw off tap to
create a demand, the light should come on, if reset is required.
Allow the boiler and system to cool down waiting at least a
minimum of four minutes before pressing the reset button.
If this is satisfactory proceed with the detailed fault finding as
Section 3.3.
3 Fault Finding
KEY
5034
brBROWN
bBLUE
rRED
pPURPLE
vVIOLET
y
3.2 Clock/Timer
If the clock has failed it can be bypassed by disconnecting the
plug at the wall frame.
Gain access to the control box refer to Section 4.12, disconnect
the clock wiring harness from the 4 way terminal block. Fit a
yellow link between the terminals Y1 and Y2.
This is a temporary measure and the clock should be repaired
or replaced as soon as possible.
L
CABLE
CLAMP/COVER
SCREW (2)
N
3
E
CABLE TO
2883
REMOTE
1
2
HEATING
CONTROLS
MAINS
CABLE
CABLE
CLAMP
Diagram 3.1
Diagram 3.2
221473B
28
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
3.3 Electrical
Preliminary electrical system checks, as outlined in a Multimeter
Instruction book, are the first checks to be carried out during a
fault finding procedure.
Isolate the boiler from the electrical supply, refer to Section 1.3.
Gain access to the boiler controls by removing the outer case,
refer to Section 1.4. Check that all cables and connectors are
secure.
Gain access to the control board, refer to Section 4.12. Check
all cables at the multipin connectors on the board.
Test the two fuses on the main control board and renew as
necessary. Fuse 1 type (2AT), Fuse 2 type T (630 mA). If a fuse
fails repeatedly or the initial fault-finding checks described in
Section 3.1 indicate a boiler fault, check the boiler electrical
circuits and follow the fault finding procedures, see diagram 3.2,
3.3, 3.4, 3.5 and for clock/timer fault finding, diagram 3.6 and
3.7.
GREY
GREY
1 2 3 4 5 6 7 8 9 10 11 12
CVI IGNITION UNIT
GAS VALVE
MODUREG
TRANSFORMER
TERMINAL No's
DHW
HIGH
LIMIT
GREY
GREY
TRANSFORMER
8
GREY
24V
7
2
1
On completion of a fault finding task that has required the
disconnection and making of electrical connections then checks,
for earth continuity, polarity and resistance to earth must be
carried out.
Before replacing any part please read points below:
Replacement of parts must only be carried out by a competent
person.
1. Refer to Section 1.1.
2. Always isolate the boiler from the electrical supply and as
required the gas supply as Section 1.3.
3. Remove outer case described in Section 1.4.
4. On completion, make good any water loss and pressurise the
system to initial design pressure, refer to “Commissioning” in
the Installation Instructions.
If the red light “flashes”, momentarily interrupt the electrical
supply.
5035
CVI IGNITION UNIT
1
TERMINAL No's
CONTROL BOARD
BLACK
YELLOW
WHITE
RED
GREY
GREY
WATER
PRESSURE
SWITCH
1
1
Fuse rating
1
630 mA Fuse
1
1
1
D.H.W.
FLOW
SWITCH
CH SELECTOR
SWITCH
CH THERMISTOR
D.H.W.
THERMISTOR
BLOCK 1
1
BLOCK 4
4
5
BLOCK 5
RED
RED
ORANGE
ORANGE
PURPLE
PURPLE
WHITE
GREY
PURPLE
YELLOW
ORANGE
USER CONTROL
BOARD
29
RED
RED
BROWN
BROWN
ORANGE
ORANGE
PURPLE
PURPLE
4
4
4
4
4
4
4
4
5
5
5
5
Diagram 3.3
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
Carry out initial Fault Finding checks described in Section 3.1 and 3.4. Check that gas, water and electricity
Carry out initial Fault Finding checks described in Section 3.1 and 3.4. Check that gas, water and electricity
are available at the boiler.
are available at the boiler.
Before starting the test, isolate the boiler from the electrical supply, ensure that the remote
Before starting the test, isolate the boiler from the electrical supply, make sure that the remote
controls are not calling for duty. Refer to the functional flow diagrams in conjuction with the
controls are not calling for duty. Refer to the functional flow diagrams in conjunction with the
following fault finding.
following fault finding.
START
Remove outer case control housing, control housing cover, user control knob and the cover.
Check all connections on the controls boards. Rectify or renew as necessary.
5084
Restore power to the appliance.
Is the Orange 'Mains' light illuminated?
NO
YES
Does Pump run?
NO
YES
Turn on hot water tap.
Is the Green 'Running' light illuminated?
YES
With central heating demand on.
Can the temperature be varied by rotating the
control knob?
YES
Turn off C.H. and D.H.W demand.
Simulate a leak on Central Heating Circuit by
draining the appliance. As pressure approaches
'ZERO' does the Red 'Low Pressure' light flash?
NO
NO
NO
Faulty 'User Control' Replace
Refer to Electrical Control Fault Finding
Faulty 'User Control' Replace
Faulty 'User Control Replace
See Electrical Controls fault finding for
'Water Pressure Switch', if in order
replace faulty user control
YES
User Control board in order
To stop Red 'Low Pressure' light flashing.
Refill C.H circuit to 0.7 bar then switch the
electrical supply to the appliance off and then on.
Proceed to Electrical Controls fault finding
if fault persists.
221473B
30
Diagram 3.4
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
Carry out the initial fault finding checks described in Section 3.1.
Check that gas, water and electricity are available at the boiler.
Before starting tests isolate the boiler, make sure that the remote controls are not
calling for duty and there is no domestic hot water demand.
Remove the outer case, control housing and it's cover.
Check all connections on the control board and the boiler components, rectify or renew
as necessary. Two dummy two way connectors are provided for ease of testing
continuity. Remove fuses and test for continuity, if faulty, check cables and connections
for shorting to E or N, rectify if necessary and replace fuse, with spare provided.
Check central heating water pressure, repressurize if necessary.
Make sure boiler is cold. Check all pipes and connections between the Air Pressure
Switch (APS) fan and combustion sample point. Make sure sample point cap is fitted
correctly. The boiler will go to lockout if the boiler overheat cut off goes open circuit,
or the boiler fails to detect flame.
Isolate supply, disconnect cables, is there
continuity, across boiler overheat cut off, brown and
black on APS, DHW cut out, and yellow and grey
on W.P.S. Is there 8kΩ-10KΩ across CH and DHW
thermistor ?
NO
5063
Replace faulty
device.
YES
Disconnect red cables to
flow switch, turn on hot
water tap. Is there
continuity between red
cables ?
YES
Turn off hot water tap
is there open circuit,
between red flow switch
cables ?
YES
Connect all cables
restore supply, does pump
run for ≈ 30 seconds.
YES
NO
NO
NO
Replace faulty
flow switch.
Replace faulty
flow switch.
Is there
230V ac at
pump ?
YES
NO
Replace faulty
main PCB .
NO
Turn on hot water tap,
is red lockout neon lit.
YES
AB
31
faulty pump
rectify.
Diagram 3.5
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
NO
NO
B
Is burner
pressure
at full DHW.
YES
NO
YES
A
Press reset switch
wait 15 seconds between
attempts. Are there sparks
at electrode ?
YES
Does burner light ?
YES
Does boiler go to lockout
after ≈ 10 seconds ?
YES
Isolate supply, Check
dimensions of sense
electrode and condition of
lead. If ok replace CVI
ignition unit ?
NO
NO
5064
Check
dimensions of
spark electrode,
if ok replace
CVI gas valve
unit.
Reduce DHW
water flow,
does burner
modulate.
YES
Turn off hot tap,
does burner
extinguish.
YES
Turn on CH
demand, does
pump operate.
YES
As heating
system
becomes
satisfied does
burner pressure
reduce ?
NO
NO
NO
NO
Does the DC voltage
across the modureg
reduce.
YES
Faulty modureg, replace.
Faulty main PCB, replace.
Is there 230V ac on pump ?
YES
Faulty pump, replace.
Faulty main PCB, replace.
NO
NO
Faulty main
PCB, replace.
Faulty main
PCB, replace.
YES
Normal
D
221473B
operation.
32
C
Diagram 3.5
Supplied By www.heating spares.co Tel. 0161 620 6677
NO
3 Fault Finding
5065
NO
D
Faulty main
PCB.
Faulty CVl
ignition unit.
NO
NO
C
Is there between
15 - 30 V DC on the two
greys on CN1 main PCB ?
YES
Is there between
15 - 30 V DC on the
Modureg coil ?
YES
Faulty coil.
Faulty
transformer,
replace.
Faulty CVI
ignition
unit, replace.
Is there 24V ac on white
NO
and red CNI on main PCB ?
Faulty main
PCB, replace.
NO
Is there 230ac on brown
and blue, on fan ?
Faulty fan,
replace.
YES
YES
Is there 230ac between
NO
NO
Is there 230ac between
yellow on CH Overheat
Thermostat and Neutral.
YES
Faulty CVI
ignition unit.
brown pin 10 and blue
pin 11 an CVI ignition
connector ?
YES
Is fan turning.
YES
NO
Faulty APS,
replace.
33
Diagram 3.5
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
If mains potential room thermostat is connected, make sure that the switch live is connected
If mains potential room thermostat is connected, ensure that the switch live is connected to
to Pin 1 in the 5 pole connector.
Pin 1 in the 5 pole connector.
Check continuity of clock/timer harness, make sure an electrical supply is available,
Check continuity of clock/timer harness, ensure an electrical supply is available,
make sure that remote controls are calling for heat.
ensure that remote controls are calling for heat.
Isolate the boiler from electrical supply,
remove outer case.
3 Fault Finding
5665
Switch on electrical supply, is there a
display on clock/timer?
YES
Disconnect and insulate the yellow cables from
heating common and heating on
Advance clock/timer until a demand is indicated
Is there now continuity between heating
common and heating on?
YES
Clock/timer in order if no central heating,
refer to main fault finding.
NO
NO
Faulty clock/timer. Replace.
Faulty clock/timer. Replace.
DIGITAL CLOCK/TIMER
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1 in
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remote
controls are calling for heat.
Does clock keep time
Yes
Isolate electrical supply set clock to on period
Is there continuity across
common and heating on
Yes
Set clock to off period. Is there continuity
across common and heating on
No
No
Clock in order if no
central heating refer to
main fault finding
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.1 Fan
Disconnect the two electrical connectors at the fan, see diagram
4.1. It is not necessary to disconnect the green and yellow earth
cable.
Remove the two flexible tubes from the fan.
Remove the air box access plate, refer to Section 10.2 in the
Installation Instructions.
When replacing the tubes from the air pressure switch ensure
the lower (red) tube from the fan connects to the lower connection
of the switch.
Slacken the clamp securing the flue elbow to the fan.
Remove the fan, secured with two screws at the front and gently
ease the fan from the flue elbow and rear bracket.
To fit the fan, locate it into the rear bracket and ease the flue
elbow onto the fan outlet and secure with the two screws, see
diagram 4.1.
The polarity of the two electrical connectors is not important.
4.2 Main Burner
Remove the inner case as Section 1.5.
Slacken the two screws securing the flue collector, see diagram
4.2.
Remove the combustion chamber front panel, secured with four
screws, see diagram 4.3.
Remove the burner support bracket wing nut and securing
screw, see diagram 4.2
Remove the spark electrode assembly from the burner, secured
by 2 screws, see diagram 4.3 and carefully lay it down in the
combustion chamber.
NOTE: The sensing lead is connected to the burner. Disconnect
the lead when the burner is being removed.
Remove the main burner from the main injector at the rear.
Raise the burner up and forwards. Take care not to damage the
combustion chamber insulation.
Remove the sensing electrode and fit to new burner.
Make sure the sensing lead is reconnected and the main burner
is fitted correctly on assembly, located on the main injector and
horizontal, the tips of the rearmost blade under the two burner
guides, see diagram 4.2A.
Locate the combustion chamber front panel under the front
edge of the flue hood on assembly, then secure all screws and
wing nut.
4.3 Main Injector
Remove the main burner, refer to Section 4.2.
Unscrew the main injector.
When fitting the main injector, fit the new sealing washer,
supplied, to ensure gas soundness.
FLUE ELBOW
(Exercise caution when
handling this component)
FLUE
COLLECTOR
SECURING
SCREWS (2)
REAR BRACKET
FLUE
COLLECTOR
SECURING
SCREWS (2)
WINGNUT
SCREW (4)
ELECTRICAL
CONNECTORS
SECURING
SCREW (2)
Diagram 4.1
6959
6958
4.4 Spark Electrode
Remove the inner case as Section 1.5.
Slacken the two screws securing the flue collector, see diagram
4.2.
Remove the combustion chamber front panel, secured with four
screws.
Remove the spark and earth electrode assembly leads and
silicone tubes, securing nuts and washers
35
COMBUSTION
CHAMBER
FRONT PANEL
BURNER SUPPORT BRACKET
SECURING SCREW
Diagram 4.2
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
Disconnect the leads and silicone tubes.
NOTE: the ignition lead is black and the earth lead is white
4.5 Sensing Electrode
Remove the main burner refer to Section 4.2
4.6 Ignition Lead
Remove inner case as Section 1.5.
Disconnect spark electrode assembly, and lead as described in
Section 4.4.
Disconnect lead at the ignition unit on gas valve. Remove
silicone tube, slacken sealing angle and withdraw lead.
4.7 Sensing Lead
Remove main burner as described in Section 4.2. Disconnect
the lead from sensing electrode.
Disconnect lead at the ignition unit on gas valve.
Slacken sealing angle and withdraw lead.
4.7a Earthing Lead
Refer to section 4.6
4.8 Boiler Overheat Cutoff
Remove user control switch bracket by slackening securing
screws, disconnect electrical connectors, see diagram 4.6.
Disconnect the boiler overheat cutoff electrical connectors, see
diagram 4.5.
Remove the overheat cutoff, secured with two screws, see
diagram 4.5.
Use the heat sink compound supplied, between the mounting
plate and the cutoff, when fitting it.
SPARK
ELECTRODE
SECURING
SCREW (2)
SILICONE
TUBES
SEALING ANGLE
SECURING
SCREW (2)
EARTH
ELECTRODE
Diagram 4.3
5018
6627
SENSING
ELECTRODE
Diagram 4.2A
5017
SECURING SCREW (2)
USER
CONTROL
SWITCH
BRACKET
ELECTRICAL
CONNECTORS
SELECTOR SWITCH
ELECTRICAL
CONNECTORS (2)
Diagram 4.5
CONTROL RESET
BUTTON
Diagram 4.6
5029
221473B
36
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.9 Water Pressure Switch
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the control housing as Section 4.11.
Disconnect the electrical connectors at the pressure microswitch,
see diagram 4.7.
Remove pressure switch, see diagram 4.7.
Replace the “O” ring seal with the new seal provided.
Make sure that the switch terminals are facing diagonally
forwards to give access, as shown in diagram 4.7.
Reconnect the electrical connections, refer to diagram 4.12.
4.10 Domestic Hot Water High Limit Control
Remove the pump, see Section 4.24.
Disconnect the electrical connectors at the domestic hot water
high limit control, see diagram 4.8.
Remove the high limit control from the flow pipe, secured with
two screws.
Use the heat sink compound supplied, between the mounting
plate and the control.
When refitting the electrical connections to the high limit control
the polarity is not important, see diagram 4.12.
DHW HIGH LIMIT CONTROL
WATER
PRESSURE
SWITCH
Diagram 4.7
4814
6626
4.11 Pressure Gauge
Remove the control housing assembly, secured with two screws.
Support the control housing on a surface or by screwing it to the
front edge of the base, using one of the screws previously
removed, see diagram 4.10.
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge bracket.
Disconnect the pressure gauge connection from the safety
valve, discard the washer, see diagram 4.9.
Remove the pressure gauge secured with the retaining spring
tabs.
Locate the supplied washer under the pressure gauge
connection when refitted to the safety valve.
4.12 Control Boards
If applicable, remove the clock/timer mounting bracket securing
screws, see diagram 4.27.
Remove control housing cover, temperature control knob and
the fascia, see diagram 4.10.
Remove the control housing assembly, see Section 4.11.
Disconnect all multi-pin connectors, see diagram 4.11.
Remove the control boards from the support posts, noting their
correct positions. Great care must be taken when handling any
control board.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI
STATIC HOLDER UNTIL IMMEDIATE REQUIREMENT.
To connect the multi-pin connectors correctly, see diagram
4.11.
When replacing the main control board check and if necessary
adjust the main burner gas pressure in both the hot water and
central heating modes. Refer to “Commissioning” in the
Installation Instructions.
ELECTRICAL
CONNECTORS
SAFETY
VALVE
SEALING
WASHER
PRESSURE
GAUGE
CONNECTION
SECURING
SCREW (2)
PRESSURE
GAUGE
SECURING
SCREW (2)
D.H.W.
HIGH
LIMIT
CONTROL
Diagram 4.8
2831
PRESSURE
GAUGE
BRACKET
Diagram 4.9
37
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.13 Transformer
Before starting, refer to section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.3
Remove the outer case, refer to section 1.4
Remove the control housing cover, refer to Section 4.11.
Support the control housing, see diagram 4.10
Remove the transformer cables correctly, see,diagram 4.12.
TEMPERATURE
FASCIA
CONTROL KNOB
CONTROL
HOUSING
COVER
SECURING
SCREW
3904
TRANSFORMER
5015
ELECTRICAL
CONNECTORS (6)
CONTROL HOUSING
SECURING SCREW (2)
CONTROL
HOUSING
COVER
WIRING AS
DIAGRAM 4.12
B
Y
Y
FASCIA
SECURING
SCREW (3)
SECURING SCREW
(To support the control
housing if necessary)
TIMER/CLOCK
(IF FITTED)
Diagram 4.10
Note:
Remove
*
'Yellow Link'
before fitting
BR
Clock/Timer
4 WAY
TERMINAL
BLOCK
MULTI-PIN
CONNECTOR
(6)
USER CONTROL
BOARD
CONTROL
BOARD
SUPPORT
POST (3)
Diagram 4.11
5229
221473B
*
Y1
Y2
Y
L
N
B
Y
BR
4 WAY
TERMINAL
BLOCK
38
Y
Y
B
N
COMMON
HEATING ON
BR
CLOCK / TIMER
L
Diagram 4.12A
Supplied By www.heating spares.co Tel. 0161 620 6677
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.14 Gas Valve
Remove control box housing, see Section 4.11.
Remove the user control switch bracket, see diagram 4.6.
Remove the ignition unit securing screw and two electrical
connectors. see diagram 4.13.
Remove ignition unit.
Remove the four extended hexagon screws at the right hand
side of the gas valve,
Support the gas valve, disconnect the union nut at the gas
service cock and remove the valve complete with the inlet pipe.
Separate the valve from the pipe, noting the fitted position.
Discard the “O” rings and fit the new ones supplied.
Fit gas valve cables. The polarity is not important.
Check and adjust the main burner gas pressure in the hot water
and central heating modes, refer to “Commissioning” in the
Installation Instructions.
4.14a Ignition unit
Remove control box housing, see Section 4.11.
Remove the user control switch bracket, see diagram 4.6.
Remove the ignition unit securing screws. see diagram 4.13a.
Disconnect the electrical connector and the three electrode
leads.
Remove ignition unit.
Note: when re-fitting make sure the electrode leads are fitted to
the correct terminals, see diagram 4.13a.
SECURING
SCREW
(4+4)
IGNITION UNIT
SECURING
SCREW
SECURING
SCREW
SECURING
SCREW (2)
ELECTRICAL
CONNECTORS (2)
IGNITION UNIT
Diagram 4.13
IGNITION UNIT
5049
5288
4.15 Central Heating Selector Switch
and Control Reset Switch
Slacken the user control switch bracket securing screws and
remove the bracket from the keyhole slots, see diagram 4.6.
Pull the leads from the switch, see diagram 4.14.
To remove the switch press in the tabs on each side of it.
THE POLARITY OF THE ELECTRICAL
CONNECTORS IS IMPORTANT, see diagram 4.12.
4.16 Modulator
Isolate the boiler from the electrical supply and closethe gas
service cock, refer to Section 1.3
Remove the outer case, refer to Section 1.4.
Disconnect the two electrical connectors at the modulator,
see diagram 4.15.
Remove the modulator, secured with two screws.
Discard the gasket and fit the new one supplied, when
fitting the modulator.
Light, check and adjust the boiler if necessary, refer to
"Commissioning" in the Installation Instructions.
EARTH
ELECTRODE
LEAD
SPARK
ELECTRODE
LEAD
SENSING
ELECTRODE
LEAD
Diagram 4.13a
4.17 Domestic Hot Water Flow Switch
Before commencing refer to Section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.3.
Remove the outer case, refer to Section 1.4.
Isolate the domestic hot water inlet, release the domestic water
pressure and drain, refer to Section 1.3 and 1.6.
Remove the control housing, refer to Section 4.11.
Remove the user control switch bracket, see diagram 4.14.
Remove the pressure gauge bracket, see diagram 4.9.
Disconnect the flow switch cables at the inline connectors.
Remove the flow switch by disconnecting the union nuts, see
diagram 4.16, noting the fitted position.
Slacken or remove the clip securing the isolating valve, to ease
removal.
Discard the sealing washers and use the new ones supplied.
It is recommended that the water inlet filter is cleaned or
renewed at this stage.
Make sure that the switch is positioned correctly, with the flow
arrow pointing upwards.
221473B
40
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.18 Thermistor - Heating
Release the water pressure and drain the heating circuit of the
boiler, refer to Sections 1.3 and 1.6.
Gain access, by removing the user control switch bracket, see
diagram 4.6.
Disconnect the cables from the thermistor, see diagram 4.17.
Remove the thermistor, complete with its “O” ring.
The polarity of the electrical connections is not important.
4.19 Thermistor - Domestic Hot Water
On minimum clearance installations, remove the pump, see
Section 4.24.
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Disconnect the cables from the thermistor, see diagram 4.17.
Remove the thermistor complete with its “O” ring.
The polarity of the electrical connections is not important.
4.20 Safety Valve
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.11.
Remove air pressure switch.
Disconnect the union nuts to release the safety valve, see
diagram 4.18.
4.21 Water Inlet Filter
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3, 1.6 and diagram 4.16.
ELECTRICAL
CONNECTORS
GAS
VALVE
GASKET
MODULATOR
5027
CONTROL RESET
BUTTON
SELECTOR SWITCH
Diagram 4.14
5043
SPACER
ELECTRICAL
CONNECTOR (2)
4.22 Domestic Hot Water Throttle
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe assembly, refer to
Section 4.17.
Remove the cap nut and carefully remove the throttle adjuster,
by unscrewing and pushing it out, see diagram 4.19.
Clean if necessary, taking care not to damage the throttle body.
Reset the domestic hot water flow rate refer to Section 11.7 in
Installation Instructions.
4.23 Mini Expansion Vessel
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe complete with the
mini-expansion vessel from the boiler, refer to Section 4.17.
When refitting use the new sealing washer supplied.
TORX
SCREW (2)
Diagram 4.15
41
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
FLOW
SWITCH
FILTER
UNION
NUT
WATER
FILTER
UNION NUT
VIEW ON ARROW 'A'
4 Replacement of Parts
5267
FLOW SWITCH
LOCKNUT
'A'
FLOW SWITCH
ELECTRICAL
CABLES
SAFETY
VALVE
2794
DISCHARGE
PIPE
UNION
NUT
UNION
NUT
Diagram 4.18
WATER
INLET
PIPE
ASSEMBLY
ISOLATING VALVE
CENTRAL
HEATING
THERMISTOR
'O' RING
UNION
NUT
THROTTLE
Diagram 4.16
6628
CAP
NUT
THROTTLE
ADJUSTER
'O' RING
Diagram 4.19
MINI
EXPANSION
VESSEL
4600
5271
'O' RING
D.H.W.
THERMISTOR
CONNECTORS
Diagram 4.17
221473B
42
SEALING WASHER
Diagram 4.20
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.24 Pump
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove control housing, refer to Section 4.11.
Disconnect the electrical connectors at the water pressure
microswitch. Remove the water pressure switch, refer to
Section 4.9.
Remove the terminal cover from the pump and disconnect the
cable, see diagram 4.21.
Disconnect the pump at the unions.
Discard the sealing washers.
Make sure that the flow direction arrow is pointing upward when
fitting and use the new sealing washers.
Refit water pressure switch, refer to Section 4.9.
The flow adjuster on the new pump should be set to that of the
original, refer also to Section 4.6 in the Installation Instructions.
The flow rate should be controlled by means of a valve in the
heating flow, refer to Section 11.10 in the Installation Instructions.
Note: Should the pump fail to operate, refer to Fault Finding
diagram 3.5. If all is in order, but the pump still does not operate,
remove the end screw, or cap, see diagram 4.21, then turn the
pump spindle to release any temporary seizure.
DO NOT HIT THE SPINDLE.
PUMP
SPINDLE
END
SCREW
PUMP
ADJUSTER
TERMINAL
COVER SCREW
FLOW
DIRECTION
ARROW
UPPER
PUMP
UNION
4593
LOWER
PUMP
UNION
4.25 Automatic Air Vent
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the automatic air vent, see diagram 4.22
SLACKEN THE SMALL CAP ON THE AIR VENT. THIS MUST
NOT BE RE-TIGHTENED.
When refitting use the new sealing washer provided.
4.26 Heat Exchanger
Release the water pressure and drain the central heating and
domestic hot water circuits refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the flue collector, secured with two screws, see diagram
4.1.
Remove the main burner, refer to Section 4.2.
Remove the automatic air vent, refer to Section 4.28. If
renewing the heat exchanger, transfer the air vent, using the
new sealing washers provided.
Disconnect the union nuts of the heat exchanger to remove it,
see diagram 4.22.
Locate the raised location tabs on the combustion chamber
sides into the slots on the heat exchanger, see diagram 4.22.
Make sure that the main burner is located on the main injector
and is horizontal, the tips of the rearmost blade under the two
burner guides, see diagram 4.2A.
The combustion chamber front panel should be fitted loosely,
then the flue collector also fitted loosely, ensuring that it is
seated correctly on the heat exchanger and over the top edge
of the front panel.
LOCATION
SLOT
CAP
Diagram 4.21
2284
AUTOMATIC
AIR VENT
SEALING
WASHER
43
UNION (4)
Diagram 4.22
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.27 Combustion Chamber Insulation
Remove the fan, refer to Section 4.1.
Remove the flue collector, secured with two screws, see diagram
4.1.
Remove the combustion chamber front panel, secured with four
screws, see diagram 4.2.
Remove the front insulation piece secured with a clip, see
diagram 4.23.
Slide out both side insulation pieces
Pull the lower rear insulation forwards, then slide the upper rear
insulation down from behind the heat exchanger.
COMBUSTION CHAMBER
FRONT PANEL
CLIP
FRONT
INSULATION
5269
SIDE INSULATION PIECES
LOWER REAR INSULATION
221473B
44
UPPER
REAR
INSULATION
Diagram 4.23
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.28 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be
removed from the wall. As an alternative, a separate expansion
vessel of the same specification may be connected as close as
possible to the boiler, leaving the original in position, refer to
Section 4 in the Installation Instructions.
Release the water pressure and drain the central heating and
domestic water circuits, refer to Section 1.3 and 1.6.
Remove the air box access plate, refer to Installation Instructions.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the air box, secured to the boiler with four screws and
to the air duct with two screws, see diagram 4.24.
Disconnect the boiler water connection union nuts at the front of
the isolating valves, see diagram 1.1.
Disconnect the gas service cock union.
Disconnect the safety valve discharge pipe from the boiler, see
diagram 4.18.
Separate the two parts of the boiler multi-pole electrical connector.
Slacken the clips of the gas service cock and the water isolating
valves.
Remove the boiler from the mounting frame, secured with two
screws at the top, see diagram 4.24. Pull the boiler from the
isolating valve. Unhook the boiler at the top and lift off.
Carefully lay the boiler down on its side for access to the
expansion vessel.
Disconnect the union nut connection, see diagram 4.25 and
discard the sealing washer.
Remove the expansion vessel, secured with three clamping
screws.
Connect the union nut, when fitting the expansion vessel, before
clamping it.
SECURING
SCREW (4)
AIR BOX
BOILER
MOUNTING
FRAME SCREW (2)
UNION NUT
CONNECTION AND
SEALING WASHER
AIR DUCT
SECURING
SCREW (2)
Diagram 4.24
2860
2861
CLAMPING SCREW (3)
Diagram 4.25
AIR PRESSURE
SWITCH TUBES
CLEAR
RED
ELECTRICAL
CONNECTORS
AIR PRESSURE
SWITCH
Diagram 4.26
5276
45
221473B
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.29 Viewing Window
Remove the viewing window, secured with two screws. When
fitting a new window use the gasket provided, see diagram 1.3.
4.30 Casing Seal
Remove the old seal, clean out the old adhesive.
Glue the new seal into place, making sure that there are no
breaks in it.
CLOCK/
TIMER
4.31 Air Pressure Switch
Disconnect the two electrical connectors at the air pressure
switch, see diagram 4.26.
Remove the flexible tubes from the switch.
Remove the air pressure switch, secured with two screws.
When replacing the tubes to the air pressure switch make sure
that the lower (red ) tube from the fan connects to the lower
connection of the switch.
THE POLARITY OF THE ELECTRICAL CONNECTIONS IS
IMPORTANT, see diagram 4.12.
4.32 Clock/Timer - if fitted
ELECTRO/MECHANICAL and DIGITAL clock/timer - Release
the mounting bracket securing screws, see diagram 4.27
Disconnect electrical cables, release securing clip to remove
the clock/timer spacer, see diagram 4.28.
6507
ELECTRICAL
CONNECTIONS
y
y
br b
SECURING
SCREWS (2)
KEY
brBROWN
bBLUE
yYELLOW
MAINS
NEUTRAL (N)
SECURING CLIP (2)
MOUNTING
BRACKET
SPACER
PLATE
6515
COMMON
MAINS
LIVE (L)
HEATING ON
DIGITAL CLOCK/TIMER
221473B
Diagram 4.27
46
TIMER/CLOCK
ELECTRO/MECHANICAL and
DIGITAL CLOCK/TIMER
Diagram 4.28
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Spare Parts
5.1 Part Identification
The key number in diagram 5.1 and the first column of the list
will help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part number
and the description from the list together with the model name
and serial number information from the data label.
The data label is positioned on the inner case cover, see
diagram 1.3.
Key NoPart NoDescriptionGC No
1452402Fan assembly278 411
2205732Main injector assembly278 412
3202631Spark electrode278 420
4202632Sensing electrode278 421
5800745Boiler over heat cut off assy278 413
6432868DHW high limit control assy313 024
7800134Pressure gauge assembly313 294
8202253Control board313 775
9800322Transformer313 761
10202250Central heating selector switch382 813
10A202251Control reset switch375 735
11A800504Thermistor assembly-Domestic278 135
11800504Thermistor assembly-Heating278 135
12800136DHW switch assembly313 277
13202240Fuse 2 type T (630 mA) - not illustrated