Glow-worm 20040796 Installation And Instructions For Use

To b e l e f t w i t h t h e u s e r
Installation and Instructions for Use
Outdoor
Sensor
www.glow-worm.co.uk
www.glow-worm.co.uk
2
Customer Service: 01773 828100 Technical Helpline: 01773 828300
Please read these instructions and follow them carefully for the safe and economical use of
your boiler. On completion of installation leave the instructions with the user.
General
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference. Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot water Industry Council who manage and promote the Scheme. Visit www.central heating.co.uk for more information.
www.glow-worm.co.uk
3
Contents
Contents Page
General information 3 Kit contents 5
Section (A)
Installer important information 6 Outdoor sensor location 7 Installation 9
Section (B)
Conguring the outdoor sensor 13
Section (C)
Conguring the outdoor sensor 22
with external Glow-worm Climapro or Climastat controls
General
The outdoor sensor enables weather compensation by providing an advanced level of modulation, achieving an additional
level of efciency. This control compensates
for the outside temperature by modulating the lower radiator temperatures in warmer weather and higher radiator temperatures in colder weather.
The outdoor temperature compensation is
easily congured using either the boilers
interface controls or the interface of an external Glow-worm Climastat or Climapro
room control (if tted). Optimum comfort and efciency is achieved when used in
conjunction with a Climastat or Climapro
(in modulating mode). The outdoor sensor
can also be used with a conventional on/off thermostat.
General Information
www.glow-worm.co.uk
4
The installation and the commissioning of the Outdoor sensor has to be carried out by a competent person in accordance with the current regulations.
The maintenance and the repairing of the Outdoor sensor will also require the use of a competent person.
Documents
Please keep these instructions as well as any documents enclosed, for future reference.
We accept no liability in case of damage due to the non-compliance of these instructions.
General Information
Application
The outdoor sensor controls the heating demand for the appliance, which is dependant on the outdoor temperature.
Any other use is considered as inappropriate and is forbidden.
The user will be responsible for any damage caused by any other use.
Servicing
Clean the case of the outdoor sensor with damp soapy cloth, make sure that no water goes inside the outdoor sensor.
Do not use any abrasive cleaning product as they could damage the housing or plastic case.
www.glow-worm.co.uk
5
General Information
(A) Installer important information
Diagram 1
Recycling
The Outdoor Sensor comprises of many recyclable parts and should be disposed of according to the current WEEE regulations.
The packaging should also disposed of according to the current regulations.
Kit contents Refer to diagram 1.
Kit part number 0020040796.
Safety instructions and regulations
This outdoor sensor is tested and certicated
for safety and performance. It is, therefore, important that no alteration is made to the outdoor sensor, without permission, in writing, from Glow-worm.
Any alteration not approved by Glow-worm,
could invalidate the certication, appliance
warranty and may also infringe the current issue of the statutory requirements.
Safety instructions
WARNING:
Incorrect installation can cause electric shock and damage to the outdoor sensor.
13663
w
w
w .
gl
o w
­w
o r
m
. c
o .
u k
Outdoor sensor
INSTALLATION AND
INSTRUCTIONS FOR USE LITERATURE.
LABEL
OUTDOOR
SENSOR
EDGE CONNECTOR
www.glow-worm.co.uk
6
Regulations
When installing and commissioning the outdoor sensor, the regulations below shall be observed in their current version.
Where no specic instructions are given,
reference should be made to the relevant British Standard Code of Practice.
Where no British Standard exists, materials
and equipment should be t for their purpose
and of suitable quality and workmanship.
The installation of this outdoor sensor must be carried out by a competent person in accordance the rules in force in the countries of destination. Manufacturer’s instructions must not be taken as overriding statutory requirements.
Mandatory WARNING for EEC countries
The CE mark on this appliance shows compliance with:
Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Directive 73/23/EEC on the harmonisation of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
(A) Installer important information
www.glow-worm.co.uk
7
Technical data
Power supply 5V
Power consumption <10mW
Cable 2 core insulated for outdoor use
Electrical protection IP 44
Electrical category Protection class II
Dimensions:
Height 32mm Width 46mm
Depth 86mm (including gland)
Outdoor sensor location
Refer to diagram 2.
The outdoor sensor should be placed on an external North/North-West facing wall of the house.
For optimal reading of the outdoor temperature, the device should be placed about
2
/3 up the wall for buildings of 3 oors
or less.
For higher buildings, the recommended
position is between the 2nd and 3rd oors. It
should not be installed sheltered from wind or draughts, nor directly exposed to the sun.
The sensor should be placed at least 1 metre from openings and away from permanent or
occasional emissions of hot air.
(A) Installer important information (A) Outdoor sensor location
www.glow-worm.co.uk
8
(A) Outdoor sensor location
E
W
S
N
1m
2/3
1/3
1m
1m
1m
1
2
3
4
1
2
3
1/3
OUTDOOR SENSOR POSITION (For buildings higher than three floors)
OUTDOOR SENSOR POSITION
(For buildings three floors or less)
OUTDOOR SENSOR POSITION (For buildings three floors or less)
2/3
Diagram 2
13662
www.glow-worm.co.uk
9
COVER
SEAL
ELECTRICAL SEALING
GLAND
BACK BOX
(A) Installation
Diagram 3 Diagram 4
BACK BOX
Refer to diagram 3. Remove the front cover, seal and electrical sealing gland.
Choose the location of the outdoor sensor, refer to page 6. Fit the back box to the wall,
see diagram 4.
13666
13667
www.glow-worm.co.uk
10
ELECTRICAL CONNECTION
ELECTRICAL SEALING GLAND
(A) Installation
WARNING: Isolate the boiler from the
electrical supply. A competant person should make the electrical connections.
Use a cable that complies with the
specications given in Technical data, page
7. Route the cable from the outdoor sensor to the boiler electrical cartridge at the boiler, refer to the literature supplied with your boiler for location and access.
Refer to diagram 5, thread the cable through the electrical sealing gland. Connect the cable to the electrical connection, polarity is not important. Fit the sealing gland, this secures the cable and gives a water tight seal. Connect the cable to OTC1 and OTC2 connection in the electrical cartridge at the boiler, polarity is not important, refer to
diagram 6.
Note:Ultracom hxi & Flexicom hx open vent system models only. The edge connector will
need to be tted, see diagram 7.
Diagram 5
13668
www.glow-worm.co.uk
11
OTC 1 and OTC 2
(A) Installation
Diagram 6
13683
www.glow-worm.co.uk
12
COVER
SEAL
(A) Installation
Diagram 8
13669
Refer to diagram 8, t and secure the seal
and cover.
Diagram 7
14819
Connection at
X41 on main PCB
EDGE
CONNECTOR
www.glow-worm.co.uk
13
(B) Conguring the Outdoor Sensor
NOTE: If a Glow-worm Climapro or Glow-
worm Climastat is tted, please refer to section C to congure the outdoor sensor.
Glow-worm Climapro
Glow-worm Climastat
Conguration of the outdoor sensor is
achieved through the Appliance interface controls on the boiler, see diagram below.
Appliance interface controls
www.glow-worm.co.uk
14
Choosing and Setting Sensor Heating Curve.
A gradient must be chosen from the range shown on page 17, labelled 0-9.
The decision as to which heating curve should be used is based on two factors:
1. The average minimum outside
temperature of the region.
2. The maximum temperature which the
heating appliance can provide.
NOTE: Consider the level of heat loss in
comparison to typical UK heat loss e.g. (double glazing, loft insulation and cavity wall
insulation).
Method with example.
The following example describes the process. The temperatures quoted should
be substituted with real values to nd the
required heating curve.
1. Select the average minimum outdoor temperature expected in your region where the sensor will be installed. For example at the peak of winter the temperature may drop
to -5°C. This would be the value selected from the Outdoor temperature °C axis.
2. Select the maximum output temperature of the heating appliance from the Heating
ow temperature (°C) axis. For example this
could be 82°C.
(B) Conguring the Outdoor Sensor
www.glow-worm.co.uk
15
Using the domestic hot water +/- button, scroll through to ‘35’. Press mode button.
(B) Conguring the Outdoor Sensor
Running screen is displayed
Press and hold the mode button. When the screen is lit orange and displays ‘0’, release the mode button.
Plot these two points onto the chart.They intersect the gradient curve labelled 6. The value 6 would be entered into the boiler via the diagnostic menu d.45.
Refer to the following diagrams and text to do this.
www.glow-worm.co.uk
16
On screen are two blocks of information, ‘d0’ in the lower part of the screen in small text. In the top centre of the screen, where the pressure or temperature is normally shown, is displayed the heating part load for the appliance (it will be different
for various kW output boilers).
For example this could be ‘18’, ‘38’.
Using the domestic hot water +/- button, scroll through until ‘d45’ is shown in small text. Press mode button once. The large
number on the screen then starts ashing.
Using the domestic hot water +/- button change the value to ‘6’. Press mode button once.
(B) Conguring the Outdoor Sensor
www.glow-worm.co.uk
17
(B) Conguring the Outdoor Sensor
50
60
70
80
90
30
40
9
0
1
3
7
4
2
5
6
8
20
Default
curve
Heating flow
temperature (ºC)
Minimum outdoor temperature (ºC)
Factory default room temperature setpoint, for weather compensation
13664
www.glow-worm.co.uk
18
(B) Conguring the Outdoor Sensor
Adjusting room temperature set point.
By default the outdoor sensor aims to provide a room ambient temperature of 20°C. In some situations it may be necessary to have a lower or higher ambient room temperature the adjustment is made in terms of an offset value, which is entered into the appliance via diagnostic menu ‘d.46’. Refer to the following diagrams and text to do this.
Method with example.
Running screen is displayed
Press and hold the mode button. When the screen is lit orange and displays ‘0’, release the mode button.
www.glow-worm.co.uk
19
Using the domestic hot water +/- button, scroll through to ‘35’. Press mode button.
On screen are two blocks of information, ‘d0’ in the lower part of the screen in small text. In the top centre of the screen, where the pressure or temperature is normally shown, is displayed the heating part load for the appliance (it will be different
for various kW output boilers).
For example this could be ‘18’, ‘38’.
(B) Conguring the Outdoor Sensor
www.glow-worm.co.uk
20
If extra heating comfort is required, the room temperature setpoint can be increased via diagnostic menu d.46. D.46 provides a means to offset from the default 20°C room set point. For example to increase the target room temperature to 22°C set d.46 to the value 2.
Range of value d.46: -10 to 10.
(B) Conguring the Outdoor Sensor
For example:
10°C = offset -10
20°C = offset 0
30°C = offset 10
www.glow-worm.co.uk
21
(C) Conguring the Outdoor Sensor with external
Glow-worm Climapro or Climastat controls
Choosing and Setting Sensor Heating Curve.
A gradient must be chosen from the range shown on page 17, labelled 0.2-4.
The decision as to which heating curve should be used is based on two factors:
1. The average minimum outside
temperature of the region.
2. The maximum temperature which the
heating appliance can provide.
NOTE: Consider the level of heat loss in
comparison to typical UK heat loss e.g. (double glazing, loft insulation and cavity wall
insulation).
Method with example.
The following example describes the process. The temperatures quoted should
be substituted with real values to nd the
required heating curve.
1. Select the average minimum outdoor temperature expected in your region where the sensor will be installed. For example at the peak of winter the temperature may drop to -5°C. This would be the value selected from the Outdoor temperature °C axis.
2. Select the maximum output temperature of the heating appliance from the Heating
ow temperature (°C) axis. For example this
could be 82°C.
3. Plot these two points onto the chart.They
intersect the heating curve labelled 2.5. The value 6 would be entered into the boiler via the diagnostic menu d.45.
www.glow-worm.co.uk
22
Making Adjustment on Climastat
Refer to your Climastat instructions, section 6 Commissioning. The heating curve is adjusted via Menu 2. Acess to this menu is achieved by following the steps stated in Adjustments.
Making Adjustment on Climapro/ Climapro RF
Refer to your Climapro/Climapro RF Commissioning Instructions. The heating curve is adjusted via menu COMP which is accessible by procedure stated in the table in the Commissioning section.
(C) Conguring the Outdoor Sensor with external
Glow-worm Climapro or Climastat controls
Adjusting Room Ambient
With the heating curve correctly setup for
your specic region, the room temperature
can be adjusted. This is achieved by increasing or decreasing the setpoint temperature of your Climastat or Climapro/ Climapro RF roomstat.
For systems with a Glow-worm Climapro. To adjust the room ambient set point temperature, refer to sections, Setting the “Comfort” temperature or Central heating temporary override - central heating of the Climapro instructions for use, installation and servicing literature.
For systems with a Glow-worm Climastat. To adjust the room ambient set point temperature, refer to section 2 instructions for use of the Climapro instructions for use,
installation and servicing literature.
www.glow-worm.co.uk
23
13682
(C) Conguring the Outdoor Sensor with external
Glow-worm Climapro or Climastat controls
50
60
70
80
90
30
40
4
0.2
0.6
1.2
3
1.5
1
2
2.5
3.5
20
Outdoor temperature (ºC)
Heating flow
temperature (ºC)
Default curve
Factory default room temperature setpoint, for weather compensation
Recommended
for UK
Because of our constant endeavour for improvement, details may vary slightly
from those shown in these instructions.
Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT
0020040798-04 08.09