STANDARD RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
DESCRIPTION AND OPERATION
The Globe Series GL-SR/DRY Upright Sprinkler is designed for
use in special applications such as freezing environments. As an
example, they may be effi ciently used when connected to a wet
type sprinkler system and extended into an unheated attic space.
The Globe Series GL-SR/DRY Upright Sprinkler utilizes a
frangible glass ampule sprinkler. At the ampule's rated temperature,
the sprinkler opens releasing the bulb seat, causing the inner tube
assembly to move, allowing the spring assembly to pivot alongside
the inner tube. At this time, water fl ows through the sprinkler and
is distributed by the defl ector, in the approved discharge pattern.
The heart of Globe's Series GL-SR sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fl uid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At
the prescribed temperature the internal pressure within the ampule
exceeds the strength of the glass causing the glass to shatter. This
results in water discharge which is distributed in an approved pattern.
UPRIGHT
SERIES GL-SR/DRY
UPRIGHT
TECHNICAL DATA
• See reverse side for Approvals and Specifi cations.
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Defl ector - brass • Screw - brass
• Bulb Seat - brass • Spring - nickel alloy • Seal - tefl on
• Retainer - brass • Pin - stainless steel
• Torsion Spring - stainless steel • Orifi ce Insert - brass
• Bulb - glass with glycerin solution, 5mm size
• 3/4”NPT or 1”NPT • Outer Tube - galvanized steel pipe • Inner Tube - stainless steel
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION
ORDINARY
INTERMEDIATE
HIGH
AVAILABLE SPRINKLER
TEMPERATURES
135°F/155°F
175°F/200°F
286°F
57°C/68°C
79°C/93°C
141°C
BULB COLOR
ORANGE/RED
YELLOW/GREEN
BLUE
N.F.P.A. MAXIMUM CEILING
TEMPERATURE
100°F
150°F
225°F
38°C
66°C
107°C
DEC 2017 GFS-530b (Formerly A-95)
STANDARD RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE UPRIGHT
SPECIFICATIONS
SIN
GL5683 5.6 (80 metric) 1”NPT
GL5684 5.6 (80 metric) 3/4”NPT
GL8183 8.0 (115 metric) 1”NPT
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1
FINISHES AVAILABLE ON SPECIAL ORDER.
2
cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN HAZARD
GL5683 ALL X X X X X X X X
Upright
GL8183 ALL X X X X X --- X X
1
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
*FM APPROVED 155°F (68°C), 200°F (93°C), AND 286°F (141°C)
ALL: ALL HAZARDS
NOMINAL
“K” FACTOR
135°F
1
(57°C)
155°F
(68°C)
THREAD
SIZE
APPROVALS
175°F
(79°C)
200°F
(93°C)
LENGTH FINISHES
cULus Variable to 48”
FM Variable to 36”
286°F
(141°C)
*FM cULus
101-92-E
Factory Bronze
White Polyester
Black Polyester
NYC
DOB
MEA
Chrome
DISTANCE
BETWEEN
SPRINKLERS
Feet (Meters)
2
1,2
MIN.
6 (1.8) 12 (0.8)GL5684 ALL X X X X X --- X X
MIN.
OPERATING
PRESSURE
psi (Bars)
CROSS SECTION
TOP OF
DEFLECTOR
"B"
4 3/4" MIN. 3/4"NPT
4 1/2" MIN. 1"NPT
3" DIA. 3/8"
FACE OF
TEE
FITTING
TEE FITTING
ANSI B16.3 CLASS 15 OR
ANSI 16.4 CLASS 125
GLOBE
Globe agrees to repair or replace any of its own manufactured
®
PRODUCT WARRANTY
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specifi c details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
1 1/2" MIN. DIA.
HOLE IN CEILING
IMPORTANT INSTALLATION DATA
Globe GL Series Dry Pendent Sprinklers should be
installed in accordance with the requirements set
forth in NFPA 13. These sprinklers are to be installed
using a pipe wrench applied to the outer tube. When
this is not possible, the proper sprinkler head wrench
may be used with extreme care for lengths up to
approximately 18”. Excessive force may distort the
frame thus destroying the unit.
The GL Series Dry Sprinkler must not be installed in a
short radius 90° elbow. When installing in other than an
iron tee, the clearances between the end of the sprinkler and fi tting should be checked.
When installed in a wet system extending into a
freezing area see chart on Dry Caution Sheet for
minimum exposed barrel length to prevent ice
plugs. Please refer to our Dry Caution Sheet for further
important installation data.
ORDERING INFORMATION
SPECIFY
• Quantity • SIN • Style • Orifi ce • Temperature
• Finishes desired • Quantity - Wrenches -
“B” Dimension - Distance from face of fi tting to the top of the
defl ector.
P/N 333010
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583
1-800-248-0278
DEC 2017 GFS-530b (Formerly A-95)