globe fire sprinkler corporation GL5679, GL5680, GL8179 User Manual

STANDARD RESPONSE
AUTOMATIC SPRINKLERS
DESCRIPTION AND OPERATION
The Globe Series GL-SR/DRY Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. The Globe Series GL-SR/DRY Pendent Sprinkler utilizes a fran­gible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water fl ows through the sprinkler and is distributed by the defl ector, in an approved discharge pattern. The heart of Globe's Series GL-SR sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fl uid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
GL SERIES
DRY TYPE PENDENT
SERIES GL-SR/DRY
SURFACE
MOUNT
SLEEVE & SKIRT
TECHNICAL DATA
See reverse side for Approvals and Specifi cations.
Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C) 200°F (93°C), 286°F (141°C)
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze Defl ector - brass Screw - brass
Bulb Seat - brass Spring - nickel alloy Seal - tefl on
Retainer - brass Pin - stainless steel
Torsion Spring - stainless steel Orifi ce Insert - brass
Bulb - glass with glycerin solution, 5mm size
3/4”NPT or 1”NPT Outer Tube - galvanized steel pipe Inner Tube - stainless steel
CLASSIFICATION
ORDINARY
INTERMEDIATE
HIGH
AVAILABLE SPRINKLER
TEMPERATURES
135°F/155°F 175°F/200°F
286°F
57°C/68°C 79°C/93°C
141°C
BULB COLOR
ORANGE/RED
YELLOW/GREEN
BLUE
EXTENDED
N.F.P.A. MAXIMUM CEILING
TEMPERATURE
100°F 150°F 225°F
RECESSED
38°C 66°C
107°C
DEC 2017 GFS-505b (formerly A-90)
STANDARD RESPONSE AUTOMATIC SPRINKLERS GL SERIES DRY TYPE PENDENT
SPECIFICATIONS
SIN
NOMINAL
“K” FACTOR
GL5679 5.6 (80 metric) 1”NPT GL5680 5.6 (80 metric) 3/4”NPT GL8179 8.0 (115 metric) 1”NPT
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1
FINISHES AVAILABLE ON SPECIAL ORDER.
2
cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
135°F
STYLE SIN HAZARD
Pendent
GL5679 ALL X X X X X X X X
1
(57°C)
Recessed
Pendent
1
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS. *PENDENT STYLE - FM APPROVED 155°F (68°C), 200°F (93°C), AND 286°F (141°C) *RECESSED PENDENT STYLE - FM APPROVED 155°F (68°C) AND 200°F (93°C) ALL: ALL HAZARDS
GL8179 ALL X X X X X --- X X
THREAD
SIZE
cULus Variable to 48”
FM Variable to 36”
APPROVALS
155°F
(68°C)
175°F
(79°C)
200°F
(93°C)
LENGTH FINISHES
286°F
(141°C)
*FM cULus
Factory Bronze
Chrome
White Polyester
Black Polyester
NYC-DOB
MEA
101-92-E
2
1,2
MIN. DISTANCE BETWEEN
SPRINKLERS
Feet (Meters)
6 (1.8)GL5680 ALL X X X X X --- X X
2 1/2" MIN. DIA.
HOLE IN CEILING
3 3/4" MIN. 4 3/4" MAX.
CROSS SECTIONS
TEE FITTING ANSI B16.3 CLASS 15 OR ANSI B16.4 CLASS 125
FACE OF
TEE
FITTING
"A" 1" MIN. 3/4"NPT 3/4" MIN. 1"NPT
TWO PIECE ESCUTCHEON
FACE OF CEILING
3 1/2" DIA.
TEE FITTING ANSI B16.3 CLASS 15 OR ANSI B16.4 CLASS 125
FACE OF FITTING
2 1/2" MIN. 3/4"NPT
1 1/2" MIN. DIA. HOLE IN CEILING
1/4"
TEE
"A"
2 1/4" MIN. 1"NPT
FACE OF CEILING
IMPORTANT INSTALLATION DATA
Globe GL Series Dry Pendent Sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18”. Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry
Caution Sheet for further important installation data.
EXTENDED
TEE FITTING ANSI B16.3 CLASS 15 OR ANSI B16.4 CLASS 125
FACE OF
TEE
FITTING
3 1/4" MIN. 3/4"NPT
2 3/4" MIN. 1"NPT
2" MIN. DIA. HOLE IN CEILING
2 15/16" DIA.
1 1/4" MIN.
2" MAX.
1/8"
CUP
RETAINER
RECESSED
DEC 2017 GFS-505b (formerly A-90)
SURFACE MOUNT
"A"
TWO PIECE
ESCUTCHEON
FACE OF CEILING
TEE FITTING ANSI B16.3 CLASS 15 OR ANSI B16.4 CLASS 125
1 3/4" MIN. DIA.
HOLE IN CEILING
3 7/32" DIA.
2 1/2" MIN.
4" MAX.
SLEEVE & SKIRT
FACE OF
TEE
FITTING
"A"
1 3/4" MIN. 3/4"NPT
1 1/2" MIN. 1"NPT
FACE OF CEILING
ORDERING INFORMATION
SPECIFY
Quantity SIN Style Orifi ce Temperature Finishes
Quantity - Wrenches -
Quantity Recessed Wrenches -
Escutcheons Desired
Quantity - Protective Caps - P/N
“A” Dimension - Distance from face of tting to the nished ceiling line
regardless of escutcheon used.
GLOBE
Globe agrees to repair or replace any of its own manufactured
®
PRODUCT WARRANTY
products found to be defective in material or workmanship for a period of one year from date of shipment. For specifi c details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).
PRINTED U.S.A.
P/N 333010
P/N 337014
327109-cap (Friction Fit Recessed)
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583
1-800-248-0278
FAX 989-846-9231
www.globesprinkler.com