Global Industrial 708384 User Manual

Emergency Drench Shower, Horizontally Mounted Model no. 708384
The Global Industrial Eye Wash Station is essential for industrial spaces where accidents can occur with chemicals or hazardous substances. These units provide immediate, reliable and effective treatment as needed. High quality and durable components ensure these stations comply and meet ANSI Standard Z358.1.
PRODUCT INFO
Pipe & Fittings safety yellow polyethylene covers for corrosion resistance
and easy visibility.
Shower Head – ABS plastic, 10” Dia.
Supply & Waste – Inlet and Outlet Tee allow inflow for
water supply and separate outflow for waste disposal.
Quality Assurance – Valves and Spray heads are tested at factory to assure efficiency.
Please read this manual completely and save these instructions for reference. Upon receiving, inspect the unit for any damage. If damage is evident, notify the
carrier immediately to file a claim. These products must
be handled with caution.
- Schedule 40 galvanized steel includes
Table of Contents Page
General Information 2
Parts List 3 Product Dimensions 4 Assembly instructions 5 Warranty Info 6
1
GENERAL INFORMATION & GUIDELINES
Emergency eye wash stations are designed to deliver water to rinse chemical substances from a person’s eyes, face or body.
WARNING: Eye wash stations are NOT to be used as substitutes for primary protective
equipment (such as gloves, masks, eye protection, and protective clothing) when handling
dangerous substances. Simply installing these stations is not sufcient to assure worker
safety. Staff must be trained in the use, maintenance, and knowledge of the eye wash station. A response plan and action should be in place in the event that an accident does occur and employees have guidelines to follow for injured personnel.
Below are guidelines that should be followed in accordance with the eye wash station when applicable. Note OSHA regulations, accessibility & surroundings, and water connections before assembling and installing the eye wash combo station. There are certain circumstances where these guidelines may not be adequate.
LOCATION OF EMERGENCY EQUIPMENT
Per ANSI Specications, emergency equipment must be installed on the same level as the possible incident (e.g. stairs/ramps must not be required to use the unit).
It is advised that emergency equipment be installed within 10 seconds (approx. 55 feet) of walking time/distance from the location of the possible incident.
WATER TEMPERATURE
Water temperature should be between 60°F(15.5°C) – 100°F(37.8°C). This can vary depend­ing on the chemical substance and should be consulted with a safety counselor.
SHUT OFF VALVES
These stationary eye wash units are designed to be connected to a clean and viable water supply line.
A shut off valve on the water line is advised to easily maintain/repair the station.
If a shut off valve is installed, make sure necessary procedures are established to prevent misuse of the valve. Only authorized personal should be installing/maintaining the shut off valve.
CORROSION & RUST RESISTANCE
All parts of the system must be constructed of materials that will not corrode.
FREEZING CONDITIONS
Emergency equipment that must be installed in potential freezing conditions should be installed with the proper equipment to protect against freezing per ANSI Z358.1 Section 4.5.5, 5.4.5.
Freeze resistant equipment includes but is not limited to:
1. Temperature actuated bleed valve that permits water to ow through the unit when the
temperature drops below freezing.
2. Remote-activated valves or electrically heated units/heated
enclosures.
2
DISPOSAL OF WATER
Waste water must be treated with care to avoid creating any hazards. It is highly recommended that emergency shower stations should be connected to drain piping or
ood drains. Depending on the chemical substances, drainage into an acid waste
disposal system may be recommended.
MODEL NO. 708381 PARTS LIST
WARNING:Use Caution when tightening connections with a pipe wrench to avoid damaging/scratching protective coating.
PARTS LIST
Item Description QTY
A 1" IPS Shut-off Valve 1
B 1" IPS x 11" Lg. Pipe 1
C 90° Elbow Reducer 1
D NPT Pipe Reducer Bushing 1
E Shower Head 1
F Pull Handle 1
D
E
C
A
B
F
3