GLI International PRO-E3 Operating Manual

OPERATING MANUAL
PRO-series Model E3
Electrodeless Conductivity
Transmitter
(for conductivity, % concentration, and TDS measurement)
Worldwide Headquarters and Sales:
9020 West Dean Road Milwaukee, Wisconsin 53224 U.S.A.
In the interest of improving and updating its equipment, GLI reserves the right to alter specifications to equipment at any time.
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
Phone: Fax: E-mail: Web:
Represented By:
[414] 355-3601 [414] 355-8346 info@gliint.com www.gliint.com
Viridor Instrumentation
A company
1
This operating manual and other GLI operating manuals are available on GLI’s web site at gliint.com. when viewed using Adobe’s free Acrobat reader. To get this reader, link to Adobe through GLI’s web site or visit Adobe’s web site at adobe.com.
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
2
IMPORTANT SAFETY INFORMATION
This transmitter is compliant with safety standards as outlined in:
FMRC Class Numbers 3600, 3611, and 3810 (U.S.A.)
CSA C22.2 No. 142 and C22.2 No. 213 (Canada)
EN 61010-1 (European Community)
Please read and observe the following:
The transmitter (not intrinsically safe) must always be located in a safe (non-hazardous) area.
Since the transmitter is powered by only low DC voltage, it is completely safe to handle.
Wiring or repairs should only be performed by qualified personnel, and only when transmitter is unpowered.
Whenever it appears that transmitter safety is questionable, disable the transmitter to ensure against
any unintended operation. For example, an unsafe condition is likely when:
1) The transmitter appears visibly damaged.
2) The transmitter fails to operate properly or provide the intended measurements.
3) The transmitter has been stored for long periods at temperatures above 158°F (70°C).
Install this transmitter in accordance with relevant local codes and instructions contained in this oper-
ating manual. Also, note and comply with the transmitters technical specifications and ratings.
HELPFUL IDENTIFIERS
In addition to information on installation and operation, this instruction manual may contain WARNINGS pertaining to user safety, CAUTIONS regarding possible instrument malfunction, and NOTES on important, useful operating guidelines.
WARNING:
A WARNING LOOKS LIKE THIS. IT WARNS YOU OF THE POTENTIAL FOR PERSONAL INJURY.
CAUTION:
A CAUTION LOOKS LIKE THIS. IT ALERTS YOU TO POSSIBLE INSTRUMENT MALFUNCTION OR DAMAGE.
NOTE: A note looks like this. It alerts you to important operating
information.
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
3
WARRANTY
GLI International, Inc. warrants the PRO-series Model E3 to be free from defects in material or workmanship for a period of 2 years (24 months) from the date of shipment of this product from our facility. A warranty claim will not be honored if defects are not reported within the warranty period, or if GLI International deter­mines that defects or damages are due to normal wear, misapplication, lack of maintenance, abuse, improper installation, alteration, or abnormal conditions. GLI Internationals obligation under this warranty shall be limited to, at its option, replacement or repair of this product. The product must be returned to GLI Inter­national, freight prepaid, for examination. The product must be thoroughly cleaned and any process chemicals removed before it will be accepted for re­placement or repair. GLI Internationals liability shall not exceed the cost of the product. Under no circumstances will GLI International be liable for any inciden­tal or consequential damages, whether to person or property. GLI International will not be liable for any other loss, damage or expense of any kind, including loss of profits, resulting from the installation, use, or inability to use this product.
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
4
CONDENSED OPERATING INSTRUCTIONS
This manual contains details for all operating aspects of the instrument. The following condensed in­structions are provided to assist you in getting the instrument started up and operating as quickly as possible.
tion.
These condensed instructions only pertain to basic conductivity measurement
To measure % concentration or TDS, or to use specific features of the instrument, refer to the
appropriate sections in this manual for instructions.
A. CONNECTING SENSOR/CONFIGURING TEMPERATURE ELEMENT TYPE
1. After properly mounting the transmitter (PART TWO, Section 2), connect the GLI electrodeless conductivity sensor, matching wire colors to terminals as indicated:
Sensor Wire Colors Connect To TB2
White Terminal 1
Blue Terminal 2
Inner and Outer Shield Wires Terminal 3
Red Terminal 4
Yellow Terminal 5
No connection (not used) Terminal 6
Green Terminal 7
2. The transmitter is supplied factory-set for automatic temperature compensation using the Pt 1000 ohm temperature element built into GLI electrodeless conductivity sensors. For fixed MANUAL temperature compensation, you must change the temperature element type (see PART THREE, Section 3.2, subheading Select TEMP ELEMENT Type”).
opera-
B. CONNECTING DC POWER
Refer to PART TWO, Section 3.2, 3.3, 3.4 or 3.5 to connect DC power to the transmitter.
C. CALIBRATING THE TRANSMITTER
The transmitter must be calibrated so that measured values will correspond to actual process values. Preferably, use the COND CAL calibration method to enter the known value of a properly prepared conductivity reference solution. (When using a sample of the process to calibrate, use the “SAMPLE CAL method to enter its known value determined by laboratory analysis or a comparison reading.)
Calibration Tip!
Each electrodeless conductivity sensor has a unique zero point and span. Conse­quently, when calibrating a sensor for the first time, always zero it according to step 1. Zeroing provides the best possible measuring accuracy.
NOTE: An in-progress calibration can always be aborted by pressing the ESC key. After the
ABORT: YES? screen appears, do one of the following:
Press ENTER key to abort. After the CONFIRM ACTIVE?” screen appears, press ENTER key
again to return the analog output to its active state (MEASURE screen appears).
Use
×
or
Ø
key to choose ABORT: NO? screen, and press ENTER key to continue calibration.
×
Ø
1. Zero the sensor if it is being calibrated for the first time. If not, disregard this step and perform steps 2 through 13.
Zeroing Tip!
press
ENTER key
If at any time during zeroing, the ZERO: CONFIRM FAILURE? screen appears,
×
to confirm. Then, use the
×
or
Ø
to select between CAL: EXIT or
key
Ø
CAL: REPEAT and do one of the following:
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
(continued on next page)
5
CONDENSED OPERATING INSTRUCTIONS
C. CALIBRATING THE TRANSMITTER -- (continued)
With the “ZERO? (CAL: EXIT)” screen selected, press
CONFIRM ACTIVE? screen appears, press its active state (MEASURE screen appears).
With the “ZERO? (CAL: REPEAT)” screen selected, press
A. Make sure that the sensor is dry before zeroing.
B. Press
C. Press
D. Press
E. Press
F. Press
G. With the dry sensor
H. After the ZERO: CONFIRM ZERO OK screen appears, press
MENU key
showing, use
ENTER key
ENTER key
Ø
key
Ø
ENTER key
zeroing, the analog output is automatically held at the last measured value.)
to display a “MAIN MENU” screen. If the screen is not
×
Ø
or
×
twice to display
key
Ø
to display it.
to display
again to display
to display the ZERO: IN DRY AIR? screen.
held in air, press
ENTER key
.
.
ENTER key
again to start automatic zeroing. (During
ENTER key
again to return the analog output to
ENTER key
.
ENTER key
. After the “ZERO:
to repeat zeroing.
to end zeroing.
I. After the ZERO: CONFIRM ACTIVE? screen appears, press
analog output to its active state (MEASURE screen appears).
2. Prepare a reference solution that has a conductivity value within the measuring range that you set for the transmitter. For best accuracy, the conductivity reference solution value should be near the typical measured process value. In PART THREE, Section 4.3, subsection COND CAL Method, refer to step 1 and Table E for solution preparation details.
3. Thoroughly rinse the clean sensor in de-ionized water. Then immerse the sensor in the prepared reference solution. pending on their temperature differences, this may take up to 30 minutes.
Important: Allow the sensor and solution temperatures to equalize.
ENTER key
to return the
De-
NOTE: Suspend the sensor to prevent it from touching the container. Simply laying it into the
container will produce calibration error.
Calibration Tip!
screen appears, press CAL: EXIT or CAL: REPEAT and do one of the following:
With the “COND? (CAL: EXIT)” screen selected, press
CAL: CONFIRM ACTIVE? screen appears, press to its active state (MEASURE screen appears).
With the “COND? (CAL: REPEAT)” screen selected, press
of the point.
If at any time during calibration, the COND CAL: CONFIRM FAILURE?
×
ENTER key
(continued on next page)
to confirm. Then, use the
ENTER key
ENTER key
ENTER key
Ø
or
×
key
Ø
to select between
. Then, after the “COND
to return the analog output
to repeat calibration
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
6
CONDENSED OPERATING INSTRUCTIONS
C. CALIBRATING THE TRANSMITTER -- (continued)
4. Press
5. Press
6. Press
7. Press
MENU key
ENTER key
ENTER key
ENTER key
temperature to match the desired reference temperature, if other than 25°C, and press
key
to enter the value.
to display
to display
again to display
again to display
.
.
.
arrow keys
. Use
to adjust the displayed
NOTE: During calibration, the analog output is automatically “held at the last measured value.
8. After the screen appears, use value to match the known slope of the reference solution, and press
arrow keys
to adjust the displayed % per °C
ENTER key
to enter value.
NOTE: Measured values are normally compensated using the configured temperature compen-
sation method. While using the COND CAL method to calibrate, the measured reference solution is linearly compensated by these entered reference temperature and slope values.
9. With the sensor in solution and the screen displayed, press
confirm. This active tion value.
screen appears showing the measured reference solu-
ENTER key
ENTER
to
10. Wait for the reading to stabilize which may take up to 30 minutes. Then press PLEASE WAIT screen may appear if the reading is still too unstable. After the reading has sta-
bilized, this static
11. Use the ence solution, and press CAL OK? screen appears).
12. Re-install the sensor into the process.
13. Press put status screen. When the reading corresponds to the actual typical process value, press
ENTER key
This completes COND CAL calibration. The transmitter is now ready to measure conductivity.
arrow keys
ENTER key
again to return the analog output to its active state (MEASURE screen appears).
to adjust the displayed value to exactly match the known value of the refer-
ENTER key
to display the active measurement reading on the CONFIRM ACTIVE? out-
screen appears showing the last-measured value.
to enter the value and complete calibration (“CONFIRM
ENTER key
NOTE: To change MEASURE screen display format, for example from 0-2000 µS/cm to 0-2.000
mS/cm, refer to PART THREE, Section 3.2, subheading Select DISPLAY FORMAT.
D. COMPLETING TRANSMITTER CONFIGURATION
To further configure the transmitter to your application requirements, use the appropriate CONFIGURE screens to make selections and “key in” values. Refer to PART THREE, Section 3 for complete configuration details.
. The
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
7
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
8
TABLE OF CONTENTS
PART ONE - INTRODUCTION
SECTION 1 GENERAL INFORMATION
1.1 Capability Highlights ........................................................................13-14
1.2 Transmitter Safety .................................................................................14
1.3 Retained Configuration Values .............................................................14
1.4 Transmitter Serial Number ....................................................................14
1.5 EMI/RFI Conformance...........................................................................14
SECTION 2 SPECIFICATIONS
....................................................................................15-16
PART TWO - INSTALLATION
SECTION 1 UNPACKING
SECTION 2 MECHANICAL REQUIREMENTS
2.1 Location................................................................................................. 17
2.2 Wall and Pipe Mounting ........................................................................18
2.3 Panel Mounting .....................................................................................19
2.4 Integral Sensor Mounting ...................................................................... 20
SECTION 3 ELECTRICAL CONNECTIONS
3.1 GLI Electrodeless Conductivity Sensor ............................................21-22
3.2 Two-wire Hookup ..................................................................................23
3.3 Three-wire Hookups (load sinking or load sourcing
with or without RS-485 serial communication) .............................23-25
3.4 Four-wire Hookups (with or without RS-485
serial communication) ..................................................................25-26
3.5 Monitor Mode Hookups (without current loop and
with or without RS-485 serial communication) ..................................27
.................................................................................................17
PART THREE - OPERATION
SECTION 1 USER INTERFACE
1.1 Display .................................................................................................. 28
1.2 Keypad .............................................................................................28-29
1.3 MEASURE Screen (normal display mode) ............................................30
SECTION 2 MENU STRUCTURE
2.1 Displaying Main Branch Selection Screens ..........................................31
2.2 Displaying Top-level Menu Screens...................................................... 32
2.3 Displaying Submenu Screens ...............................................................33
2.4 Adjusting Edit/Selection Screen Values ................................................33
2.5 Entering (Storing) Edit/Selection Screen Values/Choices..................... 33
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
9
TABLE OF CONTENTS (continued)
SECTION 3 TRANSMITTER CONFIGURATION
3.1 Selecting LANGUAGE to Operate Transmitter......................................34
3.2 Configuring Sensor Characteristics:
SELECT MEASURE (conductivity, concentration or TDS) .........34-35
Select DISPLAY FORMAT..........................................................35-36
Select Temperature COMPENSATION.......................................36-37
CONFIG CONC or CONFIG TDS Measurement
(not needed for conductivity) .................................................37-41
CONFIG LINEAR or CONFIG T-TABLE Temp. Comp. (con-
figuration not needed for other compensation methods) .......42-45
SET FILTER Time............................................................................ 45
ENTER NOTE (top line of MEASURE screen) ..............................45-46
Select TEMP ELEMENT Type ....................................................46-47
SET T FACTOR (sensors GLI-certified “T” factor) .....................47-48
3.3 SET °C OR °F (temperature display format) ......................................... 48
3.4 Configuring Analog Output:
SET PARAMETER (representation) ................................................ 49
SET 4 mA and 20 mA VALUES (range expand) .........................49-50
SET FILTER Time............................................................................ 50
SET FAIL LEVEL Mode (off, 4 mA or 20 mA) ..................................50
3.5 SET PASSCODE (feature enabled or disabled) ................................... 51
3.6 Configuration Setting Summary (ranges/choices and defaults) .......52-53
SECTION 4 TRANSMITTER CALIBRATION
4.1 Important Information .......................................................................54-55
4.2 ZERO Procedure (first-time sensor calibration only)........................55-56
4.3 Conductivity Calibration:
COND CAL Method.....................................................................56-58
SAMPLE CAL Method.................................................................59-60
4.4 % Concentration Calibration:
CONC CAL Method.....................................................................60-62
COND CAL Method..........................................................................62
4.5 TDS Calibration................................................................................62-64
4.6 Analog Output Calibration ................................................................64-65
SECTION 5 TEST/MAINTENANCE
5.1 STATUS Checking (transmitter and sensor) ....................................66-67
5.2 HOLD OUTPUT.....................................................................................67
5.3 OUTPUT Test Signal........................................................................67-68
5.4 Firmware (EPROM VERSION) Checking ..............................................68
5.5 SELECT SIM Measurement .............................................................68-69
5.6 SIM SENSOR Setting............................................................................69
5.7 RESET CONFIGURE Values to Factory Defaults............................69-70
5.8 RESET CALIBRATE Values to Factory Defaults ..................................70
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
10
TABLE OF CONTENTS (continued)
PART FOUR - SERVICE AND MAINTENANCE
SECTION 1 GENERAL INFORMATION
...........................................................................71
SECTION 2 PRESERVING MEASUREMENT ACCURACY
2.1 Keeping Sensor Clean ..........................................................................71
2.2 Keeping Transmitter Calibrated ............................................................71
2.3 Avoiding Electrical Interference............................................................. 71
SECTION 3 TROUBLESHOOTING
3.1 Checking Electrical Connections........................................................... 72
3.2 Verifying Sensor Operation ...................................................................72
3.3 Verifying Transmitter Operation ............................................................72
3.4 Verifying Sensor Interconnect Cable Integrity....................................... 72
SECTION 4 TRANSMITTER REPAIR/RETURN
4.1 Customer Assistance.............................................................................73
4.2 Repair/Return Policy .............................................................................73
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
11
TABLE OF CONTENTS (continued)
ILLUSTRATIONS
Figure 1-1
Figure 2-1
Figure 2-2
Figure 2-3
Figure 2-4
Figure 2-5
Figure 2-6
Figure 2-7
Figure 2-8
Figure 2-9
Figure 2-10
Figure 2-11
Figure 2-12
Figure 2-13
Figure 2-14
EMI/RFI Immunity Diagram ............................................................................................. 14
Wall and Pipe Mounting Details....................................................................................... 18
Panel Mounting Details.................................................................................................... 19
Integral Sensor Mounting Details ..................................................................................... 20
Transmitter Terminal Designations .................................................................................. 21
Connecting GLI Electrodeless Conductivity Sensor ......................................................... 22
Two-wire Hookup............................................................................................................. 23
Three-wire Hookup -- Load Sinking.................................................................................. 24
Three-wire Hookup -- Load Sinking with RS-485 Serial Communication .......................... 24
Three-wire Hookup -- Load Sourcing ............................................................................... 25
Three-wire Hookup -- Load Sourcing with RS-485 Serial Communication ........................ 25
Four-wire Hookup without RS-485 Serial Communication ................................................ 26
Four-wire Hookup with RS-485 Serial Communication..................................................... 26
Monitor Mode Hookup (without Current Loop) -- without RS-485 Serial Communication .. 27
Monitor Mode Hookup (without Current Loop) -- with RS-485 Serial Communication ....... 27
Figure 3-1
Table A
Table B
Table C
Table D
Table E
Transmitter Keypad ......................................................................................................... 29
TABLES
BUILT-IN Chemical Concentration Tables ....................................................................... 38
Values for USER-DEFINED Concentration Table ............................................................ 39
Values for TEMP TABLE ................................................................................................. 44
Transmitter Configuration Settings (Ranges/Choices and Defaults) ............................ 52-53
Conductivity Reference Solutions.................................................................................... 57
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
12
PART ONE - INTRODUCTION SECTION 1 - GENERAL INFORMATION
PART ONE - INTRODUCTION
ECTION
1.1 Capability Highlights
Sensor Input
S
GENERAL INFORMATION
The transmitter can be used with any GLI Model 3700E-series electrodeless conductivity sensor. These sensors have a built­in Pt 1000 RTD temperature compensator element.
1
MEASURE Screen
Passcode-protected
Access
Calibration Methods
The MEASURE screen (normal display mode) can provide different readouts of measured data. With the MEASURE
ÕÕ or
screen displayed, press
Measured conductivity, % concentration or TDS
Measured temperature (°C or °F)
Measured conductivity, % concentration or TDS and temperature
Measured analog output value (mA)
Measured uncompensated conductivity v alue corresponding to
concentration readout (only available when transmitter is set up to measure concentration)
ÖÖ key to show:
For security, you can enable a passcode feature to restrict ac­cess to configuration and calibration settings to authorized personnel only. See PART THREE, Section 3.5 for details.
Each sensor has a unique zero point and span. Therefore, always ZERO the sensor in air if it is being calibrated for the first time (PART THREE, Section 4.2). Specific methods to calibrate for sensor span are available and dependent on the transmitters configured measurement (conductivity, % concentration or TDS). For calibration details, refer to Sec­tion 4.3, 4.4 or 4.5 respectively. The analog output loop can also be calibrated (Section 4.6).
Analog Output
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
The transmitters isolated 4-20 mA analog output can be assigned to represent one of these measurements:
Measured conductivity, % concentration or TDS
Measured temperature
Parameter values can be entered to define the endpoints at which the 4 mA and 20 mA analog output values are de­sired (range expand). For output setup details, see PART
13
PART ONE - INTRODUCTION SECTION 1 - GENERAL INFORMATION
THREE, Section 3.4.
1.2 Transmitter Safety
1.3 Retained Configuration Values
1.4 Transmitter Serial Number
NOTE: During calibration, the analog output is automati-
cally held at the last measured value and, upon completion, returned to its active state.
The transmitter is completely safe to handle. Only low DC voltage is present.
WARNING:
ALWAYS LOCATE THE TRANSMITTER IN A SAFE AREA. IT IS NOT DESIGNED INTRINSICALLY SAFE.
All user-entered configuration values are retained indefi­nitely, even if power is lost or turned off. The non-volatile transmitter memory does not require battery backup.
A label with the transmitter model number, serial number, and build date is located on its enclosure.
1.5 EMI/RFI Conformance
The transmitter is designed to provide protection from most normally encountered electromagnetic interference. This protection exceeds U.S. standards and meets European IEC 801-series testing for electromagnetic and radio fre­quency emissions and susceptibility. Refer to Figure 1-1 and the specifications in Section 2.1 for more information.
EMISSIONS
SUSCEPTIBILITY
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
FIGURE 1-1 EMI/RFI Immunity Diagram
14
PART ONE - INTRODUCTION SECTION 2 - SPECIFICATIONS
ECTION
S
2
SPECIFICATIONS
2.1 Operational
Display....................................... Two-line by 16 character LCD
NOTE:
Measurement Ranges
Conductivity ..........................µS/cm: 0-200.0 or 0-2000
% Concentration ................... 0-99.99% or 0-200.0%
TDS ...................................... 0-9999 ppm
Temperature .........................-20.0 to +200.0°C or -4.0 to 392.0°F
Analog Output....................... 4.00-20.00 mA
Ambient Conditions:
Operation.............................. -4 to +140°F (-20 to +60°C); 0-95% relative
Storage................................. -22 to +158°F (-30 to +70°C); 0-95% relative
Temperature Compensation ....... Automatic from 14.0 to 392.0°F (-10.0 to
NOTE:
The measured value (conductivity, % concentration or TDS) and tem­perature can be displayed separately or shown together on a single screen. The corresponding 4-20 mA analog output value can also be shown. When the transmitter is set for concentration measurement, a useful readout of uncompensated conductivity is provided.
mS/cm: 0-2.000, 0-20.00, 0-200.0 or 0-2000 S/cm: 0-2.000
humidity, non-condensing
humidity, non-condensing
+200.0°C) with selection for Pt 1000 ohm RTD temperature element, or manually fixed at a user-entered temperature
The selected measurement (conductivity, % concentration or TDS) determines which of the following temperature compensation methods are available:
Linear % per °C slope, built-in natural water temperature proper­ties table, user-entered temperature table, or no compensation
Sensor-to-Transmitter Distance .. Maximum cable length is a function of the
measuring range and allowable non-linearity. The following schedule is recommended:
Full-scale Range Max. Length
200 to 2000 µS/cm................ 200 ft. (61 m)
2000 to 2,000,000 µS/cm ...... 300 ft. (91 m)
NOTE:
Power Requirements:
Two-wire Hookup .................. 16-30 VDC
Three-wire Hookup ................ 14-30 VDC (16 VDC min. with RS-485 comm.)
Four-wire Hookup.................. 12-30 VDC (16 VDC min. with RS-485 comm.)
Calibration Methods:
Sensor ZERO........................ With the dry sensor in air, press keys to
(all measurements) initiate automatic system zeroing
Conductivity Measurement:
When measuring % concentration, convert the transmitter full-scale value to conductivity to determine the maximum distance.
COND CAL ...................... Enter compensation reference temperature,
linear % per °C slope, and one known reference solution value
SAMPLE CAL .................. Enter one sample value (determined by
laboratory analysis or a comparison reading)
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
15
PART ONE - INTRODUCTION SECTION 2 - SPECIFICATIONS
Concentration Measurement:
CONC CAL ...................... Enter one sample value (determined by labo-
ratory analysis or a comparison reading)
COND CAL ...................... Enter compensation reference temperature,
linear % per °C slope, and one known refer­ence solution value
TDS Measurement:
TDS CAL ......................... Enter one sample value (determined by labo-
ratory analysis or a comparison reading)
Analog Output ............................ Isolated 4-20 mA output with 0.004 mA
(12-bit) resolution
2.2 Transmitter Performance
(Electrical, Analog Outputs)
NOTE:
The output can be assigned to represent the selected measurement (conductivity, % concentration or TDS) or temperature. Parameter values can be entered to define the endpoints at which the 4 mA and 20 mA output values are desired (range expand). During calibration, the output is automatically held at the last measured value and, upon completion, returned to its active state.
Maximum Loop Load.................. Dependent on power supply voltage,
transmitter hookup arrangement, and wire resistance (see load resistance charts for respective hookup diagrams in PART TWO, Section 3.2, 3.3 or 3.4)
Memory (non-volatile)................. All user settings are retained indefinitely with-
out battery backup
EMI/RFI Conformance................ Exceeds US and meets European standards
for conducted and radiated emissions and immunity; certified CE compliant for applica­tions as specified by EN 50081-2 for emissions and EN 50082-2 for immunity
Electrical Certifications:
General Purpose (pending) ..... UL, C-UL, FM, and CENELEC
Class 1, Div. 2 (pending)......... UL, C-UL, and FM: Groups A, B, C, D, F, and G
Accuracy*................................... ± 0.1% of span
Sensitivity* ................................. ± 0.05% of span
Repeatability*............................. ± 0.05% of span
Temperature Drift*...................... Zero and Span: ± 0.02% of span per °C
Response Time .......................... 1-60 seconds to 90% of value upon step
change (with sensor filter setting of zero)
2.3 Mechanical
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
*These typical performance specifications are:
1. Based on 25°C with conductivity of 500 µS/cm and higher. Consult GLI for applications in which conductivities are less than 500 µS/cm.
2. Derated above 100°C to the maximum displayed temperature of 200°C. Consult GLI for details.
Enclosure................................... Polycarbonate; NEMA 4X general purpose;
choice of included mounting hardware
Mounting Configurations............. Panel, wall, pipe or integral sensor mounting
Dimensions ................................ With Back Cover:
3.75 in. W x 3.75 in. H x 2.32 in. D (95 mm W x 95 mm H x 60 mm D)
Without Back Cover for Panel Mount:
3.75 in. W x 3.75 in. H x 0.75 in. D (95 mm W x 95 mm H x 19 mm D)
Net Weight ................................. 10 oz. (280 g) approximately
16
PART TW O - INSTALLATION SECTION 1 - UNPACKING
PART TWO - INSTALLATION
ECTION
S
UNPACKING
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument must be stored or re-shipped. Inspect the equipment and packing materials for signs of shipping damage. If there is any evi­dence of damage, notify the transit carrier immediately.
ECTION
S
MECHANICAL REQUIREMENTS
1
2
2.1 Location
1. It is recommended to locate the transmitter as close as possible to the installed sensor. The maximum allow­able distance between an installed sensor and the transmitter depends upon the full-scale value you set for the transmitter measuring range:
200-2000 µS/cm
Full-scale Value
200 feet (61 m) max. 300 feet (91 m) max.
NOTE: When measuring % concentration, convert the
transmitter full-scale value to conductivity to determine the maximum distance.
ALWAYS LOCATE THE TRANSMITTER IN A SAFE (NON-HAZARDOUS) AREA. THE TRANSMITTER IS NOT INTRINSICALLY SAFE.
2. Mount the transmitter in a location that is:
Clean and dry where there is little or no vibration.
2000-2,000,000 µS/cm
Full-scale Value
WARNING:
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
Protected from corrosive fluids.
Within ambient temperature limits (-4 to +140°F or
-20 to +60°C).
CAUTION:
EXPOSING THE TRANSMITTER TO DIRECT SUNLIGHT MAY INCREASE THE OPERATING TEMPERATURE ABOVE ITS SPECIFIED LIMIT, AND DECREASE DISPLAY VISIBILITY.
17
PART TW O - INSTALLATION SECTION 2 - MECHANICAL REQUIREMENTS
2.2 Wall and Pipe Mounting
Figure 2-1 illustrates how to wall or pipe mount the trans­mitter using the supplied GLI hardware kit. Determine the mounting method, and attach the hardware as shown.
1. Fasten the wall/pipe adapter to the wall or pipe.
2. Using a blunt tool, open both cable entry knockout holes in the back cover.
3. Insert-and-twist the back cover onto the installed wall/pipe adapter, and tighten its screw to lock back cover onto adapter.
4. Attach transmitter to back cover using its four captive screws.
FIGURE 2-1 Wall and Pipe Mounting Details
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
18
PART TW O - INSTALLATION SECTION 2 - MECHANICAL REQUIREMENTS
2.3 Panel Mounting
Figure 2-2 illustrates how to panel mount the transmitter using the supplied GLI panel mount hardware kit.
1. Cut a 3.30-inch (84 mm) square cutout hole in panel.
2. Position panel-mount gasket over cutout in front of panel, and place retainer plate behind panel with its four threaded inserts facing away from back of panel.
3. Attach transmitter to retainer plate using its four captive screws.
NOTE: If panel is too thick, remove captive screws
from transmitter, and use longer screws pro­vided in hardware kit.
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
FIGURE 2-2 Panel Mounting Details
19
PART TW O - INSTALLATION SECTION 2 - MECHANICAL REQUIREMENTS
2.4 Integral Sensor Mounting
Figure 2-3 illustrates how to integrally mount the transmitter onto a sensor using the supplied GLI mounting hardware kit.
1. Using a blunt tool, open knockout hole in bottom of swivel ball for routing the sensor cable.
2. Attach swivel-mount assembly onto back end of sensor using coupling provided with GLI sensor (only sensors with PRO1 suffix in their part number) or an appropri­ate-sized coupling that you provide.
3. Insert-and-twist back cover onto installed swivel-mount assembly, and tighten its screw to lock back cover onto swivel-mount assembly.
NOTE: To change mounting angle, loosen swivel-mount
assembly by lifting tab on bottom of swivel nut. Posi­tion to desired angle and re-tighten swivel nut.
4. Attach transmitter to back cover using its four captive screws.
FIGURE 2-3 Integral Sensor Mounting Details
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
20
PART TW O - INSTALLATION SECTION 3 - ELECTRICAL CONNECTIONS
y
(
)
(
)
(Sig
)
(
)
(-)
(+)
(
(
)
ECTION
S
3
ELECTRICAL CONNECTIONS
Figure 2-4 shows the terminal block arrangement and terminal designations for the transmitter.
NOTE: All terminals are suitable for single wires up to 14
AWG (2.5 mm2).
Wiring Tip!
To comply with European Community (CE) electromagnetic
compatibility requirements, follow these general wiring guidelines:
1. Locate transmitter as far as possible from motors and other non­CE certified devices with excessive electromagnetic emissions.
2. Use GLI-specified ferrites and cables. Failure to do so may elimi­nate compliance. Locate all ferrites as close as possible to the transmitter.
3. Loop these cables through the specified ferrite using the required number of loops:
DC Power Supply Cable (GLI 1W0980 two-conductor plus shield): Connect cable shield to earth ground at the supply end. Loop cable 4 times through ferrite (Fair-Rite Corp. #2643102002 or equivalent).
Sensor Cable: Keep cable shield as short as possible and connect it to the SHIELD terminal. Loop cable 3-1/2 times through ferrite (Fair-Rite Corp. #2643804502 or equivalent).
Analog mA Output Cable (four-wire hookup only -- GLI 1W0980 two-conductor plus shield): Connect cable shield to earth ground at the supply end. Loop cable 4 times through ferrite (Fair-Rite Corp. #2643102002 or equivalent).
Rev. 0-201 PRO-series Model E3 Electrodeless Conductivity Transmitter
TB1 TB2
PRO-E-ESP: 0E Conductivit
Serial #: 47474747479
1 2 3
2-Wire Connection
4 5 6 7
14-30 VDC
(See manual for 3, 4 Wire Connections)
White Drive
Blue
Drive0
Shield
Ground
Red
Temp
Yellow
Ground
NC
Green
nal
1 2 3 4 5 6 7
FIGURE 2-4 Transmitter Terminal Designations
21
PART TW O - INSTALLATION SECTION 3 - ELECTRICAL CONNECTIONS
)
)
(
)
)
(Sig
)
3.1 GLI Electrodeless Conductivity Sensor
Refer to Figure 2-5 and connect the sensor (or intercon­nect) cable wires to Terminals 1 through 5 and to Terminal 7 on TB2, matching colors as indicated. (Terminal 6 is un­used.)
Wiring Tip!
Route the sensor cable in 1/2-inch, grounded metal conduit to protect it from moisture, electrical noise, and mechanical damage.
For installations where the distance between sensor and transmitter exceeds the sensor cable length, indirectly connect the sensor to the transmitter using a junction box and interconnect cable.
NOTE: Do not route the sensor cable in any conduit con-
taining AC or DC power wiring (electrical noise may interfere with the sensor signal). Also, always re-calibrate the system when the cable length be­tween sensor and transmitter changes.
SENSOR
Depending on how transmitter is mounted, route the sensor (or interconnect) cable into the transmitter as follows:
Wall/Pipe-mounted Transmitter: Route cable through left
side cable entry knockout hole in the back cover.
Panel-mounted Transmitter: Route cable behind panel to
the exposed TB2 terminal strip.
Integral Sensor-mounted Transmitter: Route cable
through swivel ball knockout hole and center hole in the back cover. (Do not open left side cable entry knockout hole in the back cover.)
White
Blue
Inner and
Outer Shields
Red
Yellow
Green
1 White (Drive-
2 Blue (Drive+
3 Shield
4 Red
5 Yellow (Ground
6
7 Green
Temp
nal
FIGURE 2-5 Connecting GLI Electrodeless Conductivity Sensor
PRO-series Model E3 Electrodeless Conductivity Transmitter Rev. 0-201
22
Loading...
+ 51 hidden pages