gledhill STAINLESSLITE PLUS Instruction Manual

WWW.GLEDHILL.NET
ONE NAME. EVERY SOLUTION.
STAINLESSLITE PLUS
BUFFER STORE
HOT WATER STORAGE FOR USE WITH HEAT PUMPS AND BOILERS
INSTRUCTION MANUAL
Page 2
These instructions should be read in conjunction with the installation/ servicing instructions issued by the manufacturer of the heat source being used.
Any installation must be in accordance with the relevant requirements of the Gas Safety Regulations, Building Regulations, I.E.E. Wiring Regulations and the Water Fitting Regulations (England and Wales) or Water Byelaws (Scotland). It should be read in accordance with the relevant recommendations of the following: BS 6798; BS EN 12828, BS EN 12831, BS EN 14336; BS 5546; BS 5440:1; BS 5440:2; CP 331:3 BS EN 806-1 to 5, BS EN 8558:2011: BS EN 1458-1:2011 and BS 7593:2006
It must be installed by a competent person as defined by the relevant regulations. Manufacturers notes must NOT be taken as over-riding statutory obligations.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised at all times to ensure they do not play with the appliance.
This information is provided to assist generally in the selection of equipment.
Responsibility for selection and specification of our equipment must however remain that of our customer and any experts or consultants concerned with the installation(s).
PLEASE NOTE: THAT WE DO NOT THEREFORE ACCEPT ANY RESPONSIBILITY FOR MATTERS OF DESIGN SELECTION OR SPECIFICATION, FOR THE EFFECTIVENESS OF AN INSTALLATION OR SYSTEM CONTAINING ONE OF OUR PRODUCTS UNLESS SPECIFICALLY REQUESTED TO DO SO IN WRITING.
All goods are sold subject to our Conditions of Sale which are set out at the rear of this specification. In the interest of continuously improving the StainlessLite Plus range, Gledhill Building Products Limited reserve the right to modify the product without notice, and in these circumstances this booklet, which is accurate at the time of printing, should be disregarded. An updated set of Instructions will be produced and supplied with new appliances and will be made available for other appliances on request.
StainlessLite Plus Buffer Store is produced under an iso 9001:2008 quality management system approved by bsi.
ISSUE 2: SEPTEMBER 2017
Section Page
DESIGN
Description 3 Technical Data 4
INSTALLATION
Installation 8 Commissioning 10
APPENDIX
Appendix A 11 Appendix B 12
Notes 13
Benchmark Checklist 16 Benchmark Service Record 17
Terms & Conditions 18
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturers instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
For further information on the HWA Charter Statement, please refer to the HWA website hotwater.org.uk.
Page 3
Buffer vessels are simply a duplex stainless steel tank that contains a volume of water. Buffer vessels are used in heating systems to decouple the heat sources from the heat demands, in the same way a hot water cylinder decouples the hot water demands from the boiler.
Buffer stores are recommended by heat pump manufacturers to ensure trouble free operation of their appliances. They achieve this by presenting the heat pump with a larger volume of water to heat which reduces the amount of cycling. This in turn extends the life of the heat pump’s compressor and by reducing cycling reduce running costs.
These buffer stores can be connected to air, water or ground source heat pumps.
Buffer stores can be connected to either open vented or sealed systems as they are designed to work at up to 3.5 bar. The systems that are connected to the buffer store dictate the selection of system and components required for safe operation, and this is the responsibility of the system designer.
Buffer stores are not suitable for potable water and should not be used to feed any hot water outlets.
Direct & Indirect buffer stores
Direct buffer stores are heated directly by the main heat source only, eg. heat pump, and do not incorporate electric heaters and therefore the heating circuit flow temperature connected to the buffer vessel depends upon the flow temperature of the heat source. This type of store is ideal for the combination of a heat pump with under floor heating. Underfloor heating operating at 30°C - 40°C.
Indirect stores enable connections to be made to the heat pump, heating system and an additional heat source. This could be an oil or gas boiler but not a solid fuel heat source because the heat exchanger is not of the correct type. The additional heat is supplied via a heat exchanger and therefore is hydraulically separate from the water in the buffer store.
An additional heat source is useful for extreme conditions when the heat pump may not be able to supply the heat required and when it can top up the store.
Flexible buffer stores
This type of buffer store has been designed with flexibility in mind. It enables multiple heat pumps and/or separate domestic hot water and central heating zones to be connected. For this reason the installation diagrams in the following pages do not relate to this model. The installer can choose how to install this product and blank off any unused connections.
Weather compensation
Some heat pumps can use the external temperature to control the temperature of the water supplied to the cylinder and therefore the temperature supplied to the under floor heating. This can produce further savings by eliminating the need for the thermostatic component of the under floor heating manifold. Also it enables the heating system to run at its optimum temperature, rather than running too hot for the conditions at that time.
DESIGN
DESCRIPTION
Please Note:­i) Any heat source, heat pump, boiler or other source used in a sealed
system must incorporate a certified overheat protection device and the heat source should be certified for use in a sealed heating system. All heat sources must have two independent temperature control devices, for example, a control and an overheat thermostat.
ii) Any sealed heating system must have a means for accommodating
the expansion of the whole system volume including the buffer vessel’s volume.
iii) Any heat source in a sealed heating system must be fitted with a
pressure relief valve (PRV), and there should be no isolating valve between the PRV and the heat source.
iv) Any sealed heating system should incorporate an approved filling
method.
v) Should it be deemed necessary by the designer or installer to
incorporate a third level of protection against overheat, a manual reset overheat thermostat can be fitted in the top thermostat pocket. This coupled with the energy cut off valves for every heat source will stop the buffer store overheating if all other devices fail.
The Environment
This product has been manufactured using many recyclable materials, including the approved HCFC/CFC free polyurethane foam insulation. At the end of its useful life, it should be disposed of at a Local Authority Recycling Centre, to maximise the products full environmental benefits.
Page 4
The Buffer store is insulated to a very high standard using high density HCFC free foam cased in a steel shell and has an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of 2.
The specification of the models are shown in the following tables.
DESIGN
TECHNICAL DATA
Heating Flow
Heat Pump Return
Heating Return
Heat Pump Flow
Sensor Pocket
Sensor Pocket
StainlessLite Plus Direct Buffer Store Technical Specification
Description 90D 120D 210D 300D 400D
Product stock code PLUDR090B PLUDR120B PLUDR210B PLUDR300B PLUDR400B
Energy efficiency class A B B C C
Heat loss
watts 32 39 62 86 87
kWh/24h 0.77 0.94 1.49 2.06 2.09
Capacity litres 91 119 208 287 393
Height mm 764 931 1494 1990 2030
Diameter mm 550 550 550 550 630
Weight (empty) kg 17 20 30 39 51
Weight (full) kg 108 139 238 326 451
Maximum working pressure - cylinder bar 3.5 3.5 3.5 3.5 3.5
Maximum working pressure - space heating bar 3.5 3.5 3.5 3.5 3.5
Central heating flow connection mm 28 28 28 28 28
Central heating return connection mm 28 28 28 28 28
Heat pump flow connection mm 28 28 28 28 28
Heat pump return connection mm 28 28 28 28 28
Central heating flow tapping height mm 798 966 1530 2025 2030
Central heating return tapping height mm 225 225 225 225 214
Heat pump flow tapping height mm 504 672 1235 1731 1805
Heat pump return tapping height mm 325 325 325 325 314
Thermostatic pocket size - Bottom mm 22 22 22 22 22
Thermostatic pocket size - Top mm 22 22 22 22 22
Thermostatic pocket height - Bottom mm 275 275 447 586 621
Thermostatic pocket height - Top mm 458 567 933 1255 1201
Page 5
DESIGN
TECHNICAL DATA
StainlessLite Plus Indirect Buffer Store Technical Specification
Description 120IND 210IND 300IND 400IND
Product stock code PLUIN120B PLUIN210B PLUIN300B PLUIN400B
Energy efficiency class B B C C
Heat loss
watts 39 62 86 87
kWh/24h 0.94 1.49 2.06 2.09
Capacity litres 119 208 287 393
Height mm 931 1494 1990 2030
Diameter mm 550 550 550 630
Weight (empty) kg 22 32 43 55
Weight (full) kg 141 240 328 455
Maximum working pressure - cylinder bar 3.5 3.5 3.5 3.5
Maximum working pressure - space heating bar 3.5 3.5 3.5 3.5
Maximum working pressure - heat exchanger bar 3 3 3 3
Central heating flow connection mm 28 28 28 28
Central heating return connection mm 28 28 28 28
Heat pump flow connection mm 28 28 28 28
Heat pump return connection mm 28 28 28 28
Coil flow connection mm 22 22 22 22
Coil return connection mm 22 22 22 22
Central heating flow tapping height mm 966 1530 2025 2030
Central heating return tapping height mm 225 225 225 214
Heat pump flow tapping height mm 672 1234 1731 1805
Heat pump return tapping height mm 325 325 325 314
Coil flow tapping height mm 574 799 1003 1014
Coil return tapping height mm 354 539 703 714
Thermostatic pocket size - Bottom mm 22 22 22 22
Thermostatic pocket size - Top mm 22 22 22 22
Thermostatic pocket height - Bottom mm 275 447 586 621
Thermostatic pocket height - Top mm 567 959 1255 1201
Coil - loops 6 7 8 8
Coil - surface area m
2
0.59 0.68 0.78 0.78
Heating Flow
Coil Flow
Sensor Pocket
Heating Return
Heat Pump Flow
Sensor Pocket
Heat Pump Return
Coil Return
Page 6
DESIGN
TECHNICAL DATA
StainlessLite Plus Flexible Buffer Store Technical Specification
Description 90FLX 120FLX 210FLX 250FLX 300FLX 400FLX
Product stock code
PLU090MB PLU120MB PLU210MB PLU250MB PLU300MB PLU400MB
Energy efficiency class A B B C C C
Heat loss
watts 32 39 62 74 86 87
kWh/24h 0.77 0.94 1.49 1.78 2.06 2.09
Capacity litres 91 119 208 248 287 393
Height mm 764 931 1494 1744 1990 2030
Diameter mm 550 550 550 550 550 630
Weight (empty) kg 18 21 30 34 39 51
Weight (full) kg 109 140 238 282 326 451
Maximum working pressure - cylinder bar 3.5 3.5 3.5 3.5 3.5 3.5
Maximum working pressure - space heating bar 3.5 3.5 3.5 3.5 3.5 3.5
Tappings mm 28 28 28 28 28 28
Upper tapping height mm 505 672 1235 1485 1731 1776
Lower tapping height mm 325 325 325 325 325 310
Vent/relief boss (22mm compression) mm Top/Mid Top/Mid Top/Mid Top/Mid Top/Mid Top/Mid
Drain (1/2” BSP) height mm 235 235 235 235 235 235
Inspection hatch (1 3/4” BSP) height mm 400 400 400 400 400 385
Thermostatic pocket size mm 22 22 22 22 22 22
High level stat height mm 505 672 1235 1485 1731 1776
Low level stat height mm 325 325 325 325 325 310
Upper Plain Pipe Connections
Lower Plain Pipe Connections
High Level Stat
Low Level Stat
Inspection hatch
22mm Compression
½ " BSP Fitting for Drain Valve
The 22mm compression connection at the top of the cylinder can be used as a vent or possible pressure relief position.
Loading...
+ 14 hidden pages