gledhill StainlessLite D300, StainlessLite D90, StainlessLite D180, StainlessLite D400, StainlessLite D210 Design, Installation & Servicing Instructions

...
Design, Installation & Servicing Instructions
Models covered in this manual
Stainless Lite Direct 90-400 litres
Stainless Lite Indirect 90-400 litres
Stainless Lite Solar Direct 180-400 litres Stainless Lite Solar Indirect 180-400 litres Stainless Lite Slimline Direct 60-210 litres
StainlessLite
Unvented mains pressure water storage in Duplex stainless steel
Page 2
Section Page
DESIGN
Description 3 Technical Information 6 System Design 10
INSTALLATION
Installation 12 Commissioning 22
USER INSTRUCTIONS 23
SERVICING AND MAINTENANCE
Servicing and Maintenance 24 Fault Finding 25 Short Parts List 28
APPENDIX
Appendix A 29 Appendix B 30
Notes 31
Terms & Conditions 32
Benchmark Checklist 34 Benchmark Service Record 35
ISSUE 23: MARCH 2016
These instructions should be read in conjunction with the installation/servicing instructions issued by the manufacturer of the heat source being used.
Any installation must be in accordance with the relevant requirements of the Gas Safety Regulations, Building Regulations, I.E.E. Wiring Regulations and the Water Fitting Regulations (England and Wales) or Water Byelaws (Scotland). It should be read in accordance with the relevant recommendations of the following: BS 6798; BS EN 12828, BS EN 12831, BS EN 14336; BS 5546; BS 5440:1; BS 5440:2; CP 331:3 BS EN 806-1 to 5, BS EN 8558:2011: BS EN 1458-1:2011 and BS 7593:2006
Stainless Lite is covered by Section G3 of the Building Regulations (England and Wales) Technical Standard P3 (Scotland) and Building Regulation P5 (Northern Ireland). Compliance can be achieved via a Competent Person Self Certication Scheme or noticaton of installation to the Local Authority Building Control Department.
It must be installed by a competent person as dened by the relevant regulations. Manufacturers notes must NOT be taken as over-riding statutory obligations.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised at all times to ensure they do not play with the appliance.
This information is provided to assist generally in the selection of equipment. Responsibility for selection and specication of our equipment must however remain that of our customer and any experts or consultants concerned with the installation(s).
Please note: that we do not therefore accept any responsibility for matters of design selection or specication, for the eectiveness of an installation or system containing one of our products unless specically requested to do so in writing.
All goods are sold subject to our Conditions of Sale which are set out at the rear of this specication. In the interest of continuously improving the Stainless Lite range, Gledhill Building Products Limited reserve the right to modify the product without notice, and in these circumstances this booklet, which is accurate at the time of printing, should be disregarded. An updated set of Instructions will be produced and supplied with new appliances and will be made available for other appliances on request.
Stainless Lite is produced under an ISO 9001:2008 Quality Management System approved by BSI.
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturers instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
For further information on the HWA Charter Statement, please refer to the HWA website hotwater.org.uk.
Page 3
Maintenance
Modifications should not be made to this product. Replacement parts, including immersion heaters, should be purchased from Gledhill Building Products Limited, or agents approved by them. Unvented hot water storage vessels need regular routine checks, and these are detailed below. It is for this reason that this manual must always be left with the Stainless Lite.
It is essential that these checks be carried out at the time of boiler maintenance by a qualied installer:
1. Manually open the relief valves in turn, and check that water is discharged from the valves and runs freely through the tundish and out at the discharge point. Ensure that the valves re-seat satisfactorily. (Note - the water may be very hot).
2. It is important to check that the discharge pipework is carrying the water away adequately. Check for blockages etc. if it is not.
3. Turn the mains water o and remove and clean the strainer element in the Pressure Reducing Valve.
4. Check the charge pressure in the expansion vessel and repressurise if required
5. Re-ll the system and ensure that all relief valves have re-seated.
6. The Benchmark Service Record should be updated at each service.
7. Check the water pressure downstream of the combination valve is 3 bar in static condition.
8. Check and if necessary, descale the heat exchanger in hard water areas ie. above 200ppm (mg/l).
Note:
The cylinder is factory fitted with a lift up temperature & pressure relief valve that must not be used for any other purpose or removed.
The cylinder is factory tted with immersion heaters with thermal cut outs. Immersions without thermal cut outs must not be tted.
Manufacturer: Gledhill Building Products Ltd
Maximum inlet pressure to Pressure reducing valve 12 bar Operating pressure (PRV setting) 3 bar Expansion vessel charge pressure 3 bar Expansion relief valve setting 4.5 bar Opening pressure of P & T Relief Valve 6 bar Opening temperature of P & T Relief Valve 92-95°C Energy cut-out thermostat setting 85°C Max. working pressure - Primary heat exchanger (Indirect models) 6 bar Max. working pressure - Solar heat exchanger (Solar models) 10 bar Immersion heater rating 3kW, 240V AC
All cylinders are manufactured in accordance with the requirements of BS EN 12897 The tundish must be positioned so that it is visible to the occupant and is away from electrical devices.
Components supplied with Stainless Lite:
• Cold water inlet PRV combination valve/expansion relief
• Lift up pressure and temperature relief valve
• Control thermostat
• Energy cut-out thermostat
• Energy cut-out motorised valve (indirects only)
• Tundish
• 3kW Immersion heater including control and cut out thermostats
• Expansion vessel/mounting bracket/exible hose
• Technical/user product literature
(Note: Please refer to tables 1 and 2 on pages 6-9 to conrm the quantity of immersion heaters supplied with the unit)
In any situation where the volume of heated pipework (eg. secondary circulation pipes or manifold pipework for multiple units) exceeds 10 litres, then an additional expansion vessel must be tted to accommodate the extra expansion volume.
Handling Before Installation
Stainless Lite must be handled with care and stored the correct way up in a dry place. Any manual handling/lifting operations will need to comply with the requirements of the Manual Handling Operations Regulations issued by the H.S.E. The appliance can be moved using a sack truck on the rear face although care should be taken and the route should be even. In apartment buildings containing a number of storeys we would recommend that the appliances are moved vertically in a mechanical lift. If it is proposed to use a crane, expert advice should be obtained regarding the need for slings, lifting beams etc.
A specic manual handling assessment is shown in Appendix B at the rear of this manual.
The Environment
This product has been manufactured using many recyclable materials, including the approved HCFC/CFC free polyurethane foam insulation. At the end of its useful life, it should be disposed of at a Local Authority Recycling Centre, to maximise the products full environmental benets.
DESIGN
DESCRIPTION
Page 4
Stainless Lite is a range of unvented hot water storage cylinders, manufactured in the latest high quality duplex stainless steel. They are designed to provide mains pressure hot water and are supplied as a package which complies with Section G3 of the Building Regulations. The appliance is extremely well insulated using high density HCFC free foam insulation with an ozone depleting potential (ODP) of zero and a global warming potential (GWP) of 1. It is tted with all necessary safety devices and supplied with all the necessary control devices to make installation on site as easy as possible.
Stainless Lite is available in four basic variants:
1. Stainless Lite Direct - For providing hot water heated by electricity (Figure 1).
2. Stainless Lite Indirect - For use with gas or oil boilers (Figure 2). Unvented cylinders must not be used with solid fuel boilers or steam as the energy source.
3. Stainless Lite Direct Solar - For providing hot water by solar gains and electricity. (Figure 3).
4. Stainless Lite Indirect Solar - For providing hot water by solar gains and gas or oil boilers (Figure 4). Unvented cylinders must not be used with solid fuel boilers or steam as the energy source.
Stainless Lite Direct
Stainless Lite direct is an electrically heated, unvented hot water storage cylinder designed primarily for use with off peak electrical supplies.
It is supplied tted with two 3kW immersion heaters which are BEAB approved for safety as recommended by the Electricity Council.
Stainless Lite direct models are listed in Table 1 on Page 6 & 7.
Stainless Lite Indirect
Stainless Lite indirect is an unvented hot water storage cylinder and is provided with a high eciency internal primary coil which is designed for use with a gas or oil boiler and is suitable for both open vented and sealed pumped primary systems.
When used with a sealed heating system the boiler must incorporate its own energy cut-out overheat thermostat.
Stainless Lite indirect models are listed in
Table 2 on Page 8 & 9.
Stainless Lite
DIRECT
Stainless Lite
INDIRECT
Figure 1 Figure 2
Pipework is not supplied by manufacturer,
but to be supplied and tted by installer.
DESIGN
DESCRIPTION
Page 5
Stainless Lite
DIRECT SOLAR
Stainless Lite
INDIRECT SOLAR
Figure 3 Figure 4
Pipework is not supplied by manufacturer,
but to be supplied and tted by installer.
Stainless Lite Direct Solar
Stainless Lite direct is an electrically heated, unvented hot water storage cylinder designed primarily for use with off peak electrical supplies.
It is supplied tted with two 3kW immersion heaters which are BEAB approved for safety as recommended by the Electricity Council.
A high eciency coil is positioned in the lower part of the Stainless Lite vessel to ensure maximum benet of solar gain energy.
Stainless Lite direct models are listed in Table 1 on Page 6 & 7.
Stainless Lite Indirect Solar
Stainless Lite indirect is an unvented hot water storage cylinder and is provided with a high eciency internal primary coil which is designed for use with a gas or oil boiler and is suitable for both open vented and sealed pumped primary systems.
When used with a sealed heating system the boiler must incorporate its own energy cut-out overheat thermostat.
A high eciency second solar coil is positioned below the primary coil to ensure maximum benet of solar gain energy.
Stainless Lite indirect models are listed in
Table 2 on Page 8 & 9.
Note: The cold supply elbow c/w drain tapping must be tted as shown in gs 1, 2, 3 and
4. A exible hose can then be connected to the drain tapping and, providing the hose runs below the lowest level of the cylinder, then all the water contents can be drained out by syphonic action. (The cold feed pipe dips internally to the base of the cylinder.)
DESIGN
DESCRIPTION
Page 6
Table 1 - Direct Models
Model
Stock Code
Load Prole
Energy Eciency Class
Heat Loss
Energy Eciency %
Annual Consumption
Other Load Prole
Thermostat
Temperature Setting
Sound Power Level
O-Peak Available
Capacity (Total Volume)
Weight - Empty
Weight - Full
Pressure Regulator 3 bar inlet group c/w balance
cold supply, expansion vessel connection and
expansion valve set at 4.5 bar
Expansion Vessel size.
Pre-charged to 3 bar
Overall Height
Watts % kWh °C db Litres kg kg bar
Litres A=mm mm B=mm C=mm D=mm E=mm F=mm Litres K=mm L=mm M=mm N=mm P=mm R=mm m
Direct
D90
ASL0001 M D 35 36 2320 - 62 15 Y 90 13 103 3
12 745 550 490 n/a n/a 367 223 n/a n/a n/a n/a n/a n/a n/a n/a n/a 90 n/a
D120
ASL0005 M D 44 35 2366 - 62 15 Y 120 18 138 3
12 930 550 678 n/a 487 367 223 55 n/a n/a n/a n/a n/a n/a n/a n/a 119 n/a
D150
ASL0010 L D 51 37 4522 M 62 15 Y 150 22 172 3
18 1120 550 865 n/a 587 442 223 70 n/a n/a n/a n/a n/a n/a n/a n/a 150 n/a
D180
ASL0015 L D 54 36 4537 M 62 15 Y 180 24 204 3
18 1305 550 1053 n/a 686 442 223 85 n/a n/a n/a n/a n/a n/a n/a n/a 179 n/a
D210
ASL0020 XL D 65 37 6939 L/M 62 15 Y 210 28 238 3
24 1495 550 1241 1127 786 442 223 90 n/a n/a n/a n/a n/a n/a n/a n/a 209 n/a
D250
ASL0025 XL D 75 37 6990 L/M 62 15 Y 250 32 282 3
24 1745 550 1491 1377 927 522 223 125 n/a n/a n/a n/a n/a n/a n/a n/a 249 n/a
D300
ASL0030 XL D 85 36 7042 L/M 62 15 Y 300 37 337 3
35 1992 550 1720 1577 1077 522 223 155 n/a n/a n/a n/a n/a n/a n/a n/a 299 n/a
D400
ASL0031 XL D 118 36 7213 L/M 62 15 Y 400 48 448 3
2 x 24 2030 630 1784 1592 1181 457 238 180 n/a n/a n/a n/a n/a 338 n/a n/a
Direct Slimline
D60-SL
ASL475D60 M D 40 35 2341 - 62 15 Y 60 13 73 3
12 705 475 462 n/a n/a 348 197 n/a n/a n/a n/a n/a n/a n/a n/a n/a 60 n/a
D90-SL
ASL475D90 M D 52 34 2407 - 62 15 Y 90 16 106 3
12 978 475 734 n/a n/a 348 197 n/a n/a n/a n/a n/a n/a n/a n/a n/a 90 n/a
D120-SL
ASL475D120 L D 59 36 4561 M 62 15 Y 120 22 142 3
12 1250 475 1006 n/a 650 348 197 55 n/a n/a n/a n/a n/a n/a n/a n/a 119 n/a
D150-SL
ASL475D150 L D 68 36 4609 M 62 15 Y 150 30 180 3
18 1520 475 1278 n/a 785 423 197 70 n/a n/a n/a n/a n/a n/a n/a n/a 150 n/a
D180-SL
ASL475D180 L D 76 37 4522 M 62 15 Y 180 31 211 3
18 1790 475 1548 n/a 921 423 197 85 n/a n/a n/a n/a n/a n/a n/a n/a 179 n/a
D210-SL
ASL475D210 XL D 84 36 7036 L/M 62 15 Y 210 32 242 3
24 1970 475 1706 1540 1147 503 197 90 n/a n/a n/a n/a n/a n/a n/a n/a 209 n/a
Solar Direct
SOL180d
ASL0070 n/a B 54 n/a n/a n/a n/a n/a n/a 180 26 206 3
18 1305 550 1053 n/a 746 437 482 75 223 352 419 882 203 n/a 0.680 0.191 n/a 60
SOL210d
ASL0075 n/a C 65 n/a n/a n/a n/a n/a n/a 210 30 240 3
24 1495 550 1241 1127 908 437 544 80 223 352 419 1000 203 n/a 0.680 0.191 n/a 70
SOL250d
ASL0080 n/a C 75 n/a n/a n/a n/a n/a n/a 250 34 284 3
24 1745 550 1491 1377 1092 522 629 100 223 472 539 1180 262 n/a 0.970 0.241 n/a 84
SOL300d
ASL0085 n/a C 85 n/a n/a n/a n/a n/a n/a 300 39 339 3
35 1992 550 1720 1577 1287 522 724 115 223 472 539 1367 262 n/a 0.970 0.241 n/a 100
SOL400d
ASL0086 n/a D 118 n/a n/a n/a n/a n/a n/a 400 49 449 3
2 x 24 2030 630 1784 1592 1296 557 691 140 238 548 651 1383 334 n/a 1.270 0.310 n/a 150
Solar Direct Slimline
SOL 180d-SL
ASL475D180SOL n/a C 51 n/a n/a n/a n/a n/a n/a 180 32 212 3
18 1790 475 1548 n/a 1090 423 640 75 179 329 678 1263 243 n/a 0.680 0.191 n/a 60
SOL 210d-SL
ASL475D210SOL n/a C 84 n/a n/a n/a n/a n/a n/a 210 36 246 3
24 1970 475 1706 1540 1190 503 730 80 179 409 778 1363 273 n/a 0.680 0.191 n/a 70
A
C
Direct
D
F
E
B
R
A
Solar Direct
C
N
M
L
P
E
K
B
D
F
DESIGN
TECHNICAL INFORMATION
Page 7
Expansion Vessel size.
Pre-charged to 3 bar
Overall Height
Overall Diameter
Pressure & Temperature
Relief Valve 6bar 95°C
22mm Secondary
Return Tapping
On Peak Immersion
Heater - High Level
Cold Feed 22mm
Compression Connection
O Peak Immersion
Heater - Low Level
Volume of On Peak Water
Heated
22mm Solar Return
Compression Connection
22mm Solar Flow
Compression Connection
Dual Control & Overheat Stat
Solar Pocket
Solar Pocket
Second O Peak Immersion
Heater - Low Level
Surface Area of
Solar Heater Coil
Pressure Loss Across Solar Heater
Coil
Heat Up Time from 15°C to 60°C
(applies to Primary Heat Source only)
Dedicated Solar Volume
Litres A=mm mm B=mm C=mm D=mm E=mm F=mm Litres K=mm L=mm M=mm N=mm P=mm R=mm m2bar min Litres
12 745 550 490 n/a n/a 367 223 n/a n/a n/a n/a n/a n/a n/a n/a n/a 90 n/a 12 930 550 678 n/a 487 367 223 55 n/a n/a n/a n/a n/a n/a n/a n/a 119 n/a 18 1120 550 865 n/a 587 442 223 70 n/a n/a n/a n/a n/a n/a n/a n/a 150 n/a 18 1305 550 1053 n/a 686 442 223 85 n/a n/a n/a n/a n/a n/a n/a n/a 179 n/a 24 1495 550 1241 1127 786 442 223 90 n/a n/a n/a n/a n/a n/a n/a n/a 209 n/a 24 1745 550 1491 1377 927 522 223 125 n/a n/a n/a n/a n/a n/a n/a n/a 249 n/a 35 1992 550 1720 1577 1077 522 223 155 n/a n/a n/a n/a n/a n/a n/a n/a 299 n/a
2 x 24 2030 630 1784 1592 1181 457 238 180 n/a n/a n/a n/a n/a 338 n/a n/a
398/198
n/a
12 705 475 462 n/a n/a 348 197 n/a n/a n/a n/a n/a n/a n/a n/a n/a 60 n/a 12 978 475 734 n/a n/a 348 197 n/a n/a n/a n/a n/a n/a n/a n/a n/a 90 n/a 12 1250 475 1006 n/a 650 348 197 55 n/a n/a n/a n/a n/a n/a n/a n/a 119 n/a 18 1520 475 1278 n/a 785 423 197 70 n/a n/a n/a n/a n/a n/a n/a n/a 150 n/a 18 1790 475 1548 n/a 921 423 197 85 n/a n/a n/a n/a n/a n/a n/a n/a 179 n/a 24 1970 475 1706 1540 1147 503 197 90 n/a n/a n/a n/a n/a n/a n/a n/a 209 n/a
18 1305 550 1053 n/a 746 437 482 75 223 352 419 882 203 n/a 0.680 0.191 n/a 60 24 1495 550 1241 1127 908 437 544 80 223 352 419 1000 203 n/a 0.680 0.191 n/a 70 24 1745 550 1491 1377 1092 522 629 100 223 472 539 1180 262 n/a 0.970 0.241 n/a 84 35 1992 550 1720 1577 1287 522 724 115 223 472 539 1367 262 n/a 0.970 0.241 n/a 100
2 x 24 2030 630 1784 1592 1296 557 691 140 238 548 651 1383 334 n/a 1.270 0.310 n/a 150
18 1790 475 1548 n/a 1090 423 640 75 179 329 678 1263 243 n/a 0.680 0.191 n/a 60 24 1970 475 1706 1540 1190 503 730 80 179 409 778 1363 273 n/a 0.680 0.191 n/a 70
4
0
,0
0
º
4
5
,
00º
3
5
,00º
2
5,
0
0
º
1
5
,
0
0
º
NOTES
1. Not all models - see table 1.
2. Recovery times based on Primary Coil/I.H. duty (ie. assumes the boiler output is adequate).
3. All connections are supplied with compression fittings for direct connection to copper pipework.
4. The heat up times shown for the D400 model indicate the times when 1 or 2 immersions are connected.
5. The diagrams shown are generic. For exact product specification refer to the table eg. the number of immersion heaters varies depending on model.
6. Heat up and recovery times based on 0.25 l/s primary ow rate and at 82°C ow temperature.
DESIGN
TECHNICAL INFORMATION
Page 8
Table 2 - Indirect Models
Model
Stock Code
Energy Eciency Class
Heat Loss
Capacity (Total Volume)
Weight - Empty
Weight - Full
Pressure Regulator 3 bar inlet group c/w balance
cold supply, expansion vessel connection and
expansion valve set at 4.5 bar
Expansion Vessel size.
Pre-charged to 3 bar
Overall Height
Overall Diameter
Pressure & Temperature
Relief Valve 6bar 95°C
22mm Secondary
Return Tapping
On Peak Immersion
Heater - High Level
Cold Feed 22mm
Compression Connection
O Peak Immersion
Heater - Low Level
Watts Litres kg kg bar Litres A=mm mm B=mm C=mm D=mm
E=mm F=mm Litres G=mm H=mm I=mm J=mm K=mm L=mm M=mm N=mm P=mm R=mm kW m
Indirect
IND90
ASL0035 B 35 90 19 109 3 12 745 550 490 n/a 352
367 n/a 40 367 367 223 312 n/a n/a n/a n/a n/a n/a 16.5 0.59 0.165 n/a n/a 17 n/a
IND120
ASL0040 B 44 120 22 142 3 12 930 550 678 n/a 352
367 n/a 67 367 367 223 312 n/a n/a n/a n/a n/a n/a 18 0.59 0.165 n/a n/a 21 n/a
IND150
ASL0045 B 51 150 26 176 3 18 1120 550 865 n/a 392
442 n/a 92 407 407 223 392 n/a n/a n/a n/a n/a n/a 18.5 0.68 0.191 n/a n/a 25 n/a
IND180
ASL0050 B 54 180 28 208 3 18 1305 550 1053 n/a 432
442 n/a 116 447 447 223 392 n/a n/a n/a n/a n/a n/a 19 0.78 0.216 n/a n/a 30 n/a
IND210
ASL0055 C 65 210 33 243 3 24 1495 550 1241 1127 432
442 n/a 145 482 482 223 392 n/a n/a n/a n/a n/a n/a 20.5 0.78 0.216 n/a n/a 32 n/a
IND250
ASL0060 C 75 250 38 288 3 24 1745 550 1491 1377 927
522 512 109 577 577 223 472 n/a n/a n/a n/a n/a n/a 21.5 0.97 0.241 n/a n/a 36 n/a
IND300
ASL0065 C 85 300 44 344 3 35 1992 550 1720 1577 1077
522 512 130 677 677 223 522 n/a n/a n/a n/a n/a n/a 25 0.97 0.241 n/a n/a 38 n/a
IND400
ASL0066 D 118 400 55 455 3 2 x 24 2030 630 1784 1577 1151
542 586 180 668 668 223 533 n/a n/a n/a n/a n/a n/a 30.5 1.27 0.310 n/a n/a 41 n/a
Indirect Slimline
IND60-SL
ASL475IND60 B 40 60 14 74 3 12 705 475 462 n/a 352
348 n/a 28 242 242 179 329 n/a n/a n/a n/a n/a n/a 15 0.59 0.165 n/a n/a 13 n/a
IND90-SL
ASL475IND90 C 52 90 19 109 3 12 978 475 734 n/a 392
348 n/a 54 359 359 179 329 n/a n/a n/a n/a n/a n/a 16.5 0.59 0.165 n/a n/a 17 n/a
IND120-SL
ASL475IND120 C 59 120 23 143 3 12 1250 475 1006 n/a 432
348 n/a 75 423 423 179 329 n/a n/a n/a n/a n/a n/a 18 0.59 0.165 n/a n/a 21 n/a
IND150-SL
ASL475IND150 C 68 150 28 178 3 18 1520 475 1278 n/a 462
423 n/a 102 514 514 179 409 n/a n/a n/a n/a n/a n/a 18.5 0.68 0.191 n/a n/a 25 n/a
IND180-SL
ASL475IND180 C 76 180 31 211 3 18 1790 475 1548 n/a 512
503 n/a 125 604 604 179 449 n/a n/a n/a n/a n/a n/a 19.0 0.78 0.216 n/a n/a 30 n/a
IND210-SL
ASL475IND210 C 84 210 34 244 3 24 1970 475 1706 1540 512
503 n/a 150 695 695 179 449 n/a n/a n/a n/a n/a n/a 20.5 0.78 0.216 n/a n/a 32 n/a
Solar Indirect
SOL180i
ASL0090 B 54 180 30 210 3 18 1305 550 1053 n/a 680
437 n/a 80 825 n/a 715 935 223 352 419 882 218 n/a 18 0.59 0.165 0.680 0.191 28 96
SOL210i
ASL0095 C 65 210 35 245 3 24 1495 550 1240 1127 723
437 n/a 95 888 n/a 758 1018 223 352 419 1000 233 n/a 18.5 0.68 0.191 0.680 0.191 35 101
SOL250i
ASL0100 C 75 250 40 290 3 24 1745 550 1491 1377 785
522 n/a 115 970 n/a 820 1120 223 472 539 1180 294 n/a 19 0.78 0.216 0.970 0.241 38 107
SOL300i
ASL0105 C 85 300 46 346 3 35 1992 550 1720 1577 910
522 n/a 140 1095 n/a 945 1245 223 472 539 1367 300 n/a 20.5 0.78 0.216 0.970 0.241 41 125
SOL400i
ASL0110 D 118 400 59 459 3 2 x 24 2030 630 1784 1592 872
557 n/a 190 1060 1060 930 1190 238 548 651 1383 357 n/a 22 0.97 0.241 1.270 0.310 45 165
Solar Indirect Slimline
SOL180i-SL
ASL475IND180SOL C 76 180 33 213 3 18 1790 475 1548 n/a 1044
423 n/a 75 897 n/a 619 1004 179 320 583 1232 243 n/a 18 0.59 0.165 0.680 0.191 28 60
SOL210i-SL
ASL475IND210SOL C 84 210 37 247 3 24 1970 475 1706 1540 1130
503 n/a 85 1083 n/a 710 1095 179 409 673 1383 273 n/a 18.5 0.68 0.191 0.680 0.191 35 70
A
C
Indirect
D
H
F
E
I
J
B
G
D
Solar Indirect
N
G
P
I
E
K
J
A
B
M
L
C
DESIGN
TECHNICAL INFORMATION
Page 9
Cold Feed 22mm
Compression Connection
O Peak Immersion
Heater - Low Level
Volume of On Peak Water
Heated
Dual Control & Overheat Stat
Extra Stat Pocket
For Boiler Use If Required
22mm Primary Return Compression
Connection
(28mm tails for 400 litre model)
22mm Primary Flow Compression
Connection
(28mm tails for 400 litre model)
22mm Solar Return
Compression Connection
22mm Solar Flow
Compression Connection
Dual Control & Overheat Stat
Solar Pocket
Solar Pocket
Second O Peak Immersion
Heater - Low Level
kW Rating of Primary Coil
Surface Area of
Primary Heater Coil
Pressure Loss Across
Primary Heater Coil
Surface Area of
Solar Heater Coil
Pressure Loss Across Solar Heater
Coil
Heat Up Time from 15°C to 60°C
(applies to Primary Heat Source only)
Dedicated Solar Volume
E=mm F=mm Litres G=mm H=mm I=mm J=mm K=mm L=mm M=mm N=mm P=mm R=mm kW m2bar m2bar min Litres
367 n/a 40 367 367 223 312 n/a n/a n/a n/a n/a n/a 16.5 0.59 0.165 n/a n/a 17 n/a 367 n/a 67 367 367 223 312 n/a n/a n/a n/a n/a n/a 18 0.59 0.165 n/a n/a 21 n/a 442 n/a 92 407 407 223 392 n/a n/a n/a n/a n/a n/a 18.5 0.68 0.191 n/a n/a 25 n/a 442 n/a 116 447 447 223 392 n/a n/a n/a n/a n/a n/a 19 0.78 0.216 n/a n/a 30 n/a 442 n/a 145 482 482 223 392 n/a n/a n/a n/a n/a n/a 20.5 0.78 0.216 n/a n/a 32 n/a 522 512 109 577 577 223 472 n/a n/a n/a n/a n/a n/a 21.5 0.97 0.241 n/a n/a 36 n/a 522 512 130 677 677 223 522 n/a n/a n/a n/a n/a n/a 25 0.97 0.241 n/a n/a 38 n/a 542 586 180 668 668 223 533 n/a n/a n/a n/a n/a n/a 30.5 1.27 0.310 n/a n/a 41 n/a
348 n/a 28 242 242 179 329 n/a n/a n/a n/a n/a n/a 15 0.59 0.165 n/a n/a 13 n/a 348 n/a 54 359 359 179 329 n/a n/a n/a n/a n/a n/a 16.5 0.59 0.165 n/a n/a 17 n/a 348 n/a 75 423 423 179 329 n/a n/a n/a n/a n/a n/a 18 0.59 0.165 n/a n/a 21 n/a 423 n/a 102 514 514 179 409 n/a n/a n/a n/a n/a n/a 18.5 0.68 0.191 n/a n/a 25 n/a 503 n/a 125 604 604 179 449 n/a n/a n/a n/a n/a n/a 19.0 0.78 0.216 n/a n/a 30 n/a 503 n/a 150 695 695 179 449 n/a n/a n/a n/a n/a n/a 20.5 0.78 0.216 n/a n/a 32 n/a
437 n/a 80 825 n/a 715 935 223 352 419 882 218 n/a 18 0.59 0.165 0.680 0.191 28 96 437 n/a 95 888 n/a 758 1018 223 352 419 1000 233 n/a 18.5 0.68 0.191 0.680 0.191 35 101 522 n/a 115 970 n/a 820 1120 223 472 539 1180 294 n/a 19 0.78 0.216 0.970 0.241 38 107 522 n/a 140 1095 n/a 945 1245 223 472 539 1367 300 n/a 20.5 0.78 0.216 0.970 0.241 41 125 557 n/a 190 1060 1060 930 1190 238 548 651 1383 357 n/a 22 0.97 0.241 1.270 0.310 45 165
423 n/a 75 897 n/a 619 1004 179 320 583 1232 243 n/a 18 0.59 0.165 0.680 0.191 28 60 503 n/a 85 1083 n/a 710 1095 179 409 673 1383 273 n/a 18.5 0.68 0.191 0.680 0.191 35 70
4
0
,0
0
º
4
5
,
00º
3
5
,00º
2
5,
0
0
º
1
5
,
0
0
º
NOTES
1. Not all models - see table 2.
2. Recovery times based on Primary Coil/I.H. duty (ie. assumes the boiler output is adequate).
3. All connections are supplied with compression fittings for direct connection to copper pipework.
4. The diagrams shown are generic. For exact product specification refer to the table eg. the number of immersion heaters varies depending on model.
5. Heat up and recovery times based on 0.25 l/s primary ow rate and at 82°C ow temperature.
DESIGN
TECHNICAL INFORMATION
Page 10
Stainless Lite Direct
Basic Appliance
1. Hot water draw o (22mm) compression
2. Lift up temperature & pressure relief valve 92-95°/6 bar
3. Hot water secondary return 22mm
(not tted to smaller sizes, see table 1)
4. Immersion heater 1¾” BSP 3kW
(normally on-peak)
5. 22mm cold supply compression
6. Immersion heater 1¾” BSP 3kW
(normally o-peak)
7. Immersion heater 1¾” BSP 3kW
(normally o-peak - 400 litre model only)
Part G3 loose components supplied in a separate box
A. Combination inlet group incorporating
pressure reducing valve, strainer, check valve, balance cold take o point, expansion relief valve and expansion vessel connection points.
B. Portable expansion vessels c/w exible hose
and wall bracket
C. Tundish
Stainless Lite Indirect
Basic Appliance
1. Hot water draw o (22mm) compression
2. Lift up temperature & pressure relief valve 92-95°/6 bar
3. Hot water secondary return 22mm
(not tted to smaller sizes, see table 2)
4. Immersion heater 1¾” BSP 3kW
5. 22mm cold supply compression
6. Immersion heater 1¾” BSP 3kW
7. Dual control/overheat stat pocket (22mm)
8. Boiler control sensor pocket (spare)
9. Primary return (22mm)
- (28mm tails for 400 litre models)
10. Primary ow (22mm)
- (28mm tails for 400 litre models)
Part G3 loose components supplied in a separate box
A. Combination inlet group incorporating
pressure reducing valve, strainer, check valve, balance cold take o point, expansion relief valve and expansion vessel connection points.
B. Potable expansion vessels c/w exible hose
and wall bracket
C. Tundish D. Dual control thermostat and combined
overheat thermostat
E. Two port (22mm) zone valve for primary circuit F. Wiring junction box for primary system
1
2
5
3
4
6
7
1
2
3
4
7
5
6
9
8
10
Typical arrangement of component kit shown tted to the appliance for clarity
Pipework to be supplied and tted by installer.
DESIGN
SYSTEM DESIGN
Page 11
7
9
3
11
6
12
12
1
2
8
4
5
10
Stainless Lite Direct Solar
Basic Appliance
1. Hot water draw o (22mm) compression
2. Lift up temperature & pressure relief valve
92-95°/6 bar
3. Hot water secondary return 22mm (not tted to smaller sizes, see table 1)
4. Immersion heater 1¾” BSP 3kW (normally on-peak)
5. 22mm cold supply
6. Immersion heater 1¾” BSP 3kW (normally o-peak)
7. Dual control/Overheat stat pocket (solar)
8. Solar coil return to panel collector (22mm)
compression
9.
Solar coil ow from panel (22mm) compression
10. Solar thermostat pocket
Part G3 loose components supplied in a separate box
A.
Combination inlet group incorporating pressure reducing valve, strainer, check valve, balance cold take o point, expansion relief valve and expansion vessel connection points.
B. Portable expansion vessels c/w exible hose
and wall bracket C. Tundish D. Dual control thermostat and combined
overheat thermostat
Stainless Lite Indirect Solar
Basic Appliance
1. Hot water draw o (22mm) compression
2. Lift up temperature & pressure relief valve
92-95°/6 bar
3. Hot water secondary return 22mm (not tted to smaller sizes, see table 2)
4. Immersion heater 1¾” BSP 3kW
5. 22mm cold supply
6. Dual control/Overheat stat pocket (solar)
7. Primary return (22mm)
- (28mm tails for 400 litre models)
8. Primary ow (22mm)
- (28mm tails for 400 litre models)
9. Dual control/Overheat stat pocket (boiler)
10. Solar coil return to panel collector (22mm)
compression
11.
Solar coil ow from panel (22mm) compression
12. Solar thermostat pocket
Part G3 loose components supplied in a separate box
A.
Combination inlet group incorporating
pressure reducing valve, strainer, check valve,
balance cold take o point, expansion relief
valve and expansion vessel connection points. B. Potable expansion vessels c/w exible hose
and wall bracket C. Tundish D. Dual control thermostat and combined
overheat thermostat (x2) E. Two port (22mm) zone valve for primary circuit F. Wiring junction box for primary system
1
2
5
8
7
6
4
3
9
10
10
Typical arrangement of component kit shown tted to the appliance for clarity
Pipework to be supplied and tted by installer.
DESIGN
SYSTEM DESIGN
Page 12
General Design Considerations
The cupboard footprint needs to be at least 650mm square for standard units up to 300 litres, 730mm for 400 litre and 575mm for slimline units. The base chosen for the cylinder should be level and capable of supporting the weight of the unit when full of water as shown in General Data. The discharge pipework for the safety valves must have a minimum fall of 1 : 200 from the unit to a safe discharge point. All exposed pipework and ttings on the cylinder should be insulated, and the unit should NOT be xed in a location where the contents could freeze.
In new systems, pipes should be insulated to comply with building regs, the maximum permissible heat loss is indicated in the table opposite, and labelled accordingly as follows: i. Primary circulation pipes for domestic hot water circuits should be insulated
through their length, subject only to practical constraints imposed by the need to penetrate joists and other structural elements.
ii. All pipes connected to hot water storage vessels, including the vent pipe, should
be insulated for at least 1 metre from their points of connection to the cylinder (or they should be insulated up to the point where they become concealed).
In replacement systems, whenever a boiler or hot water storage vessel is replaced in an existing system, any pipes that are exposed as part of the work or are otherwise accessible should be insulated as recommended for new systems, or to some lesser standard where practical constraints dictate.
The pipe connecting the boiler ow to the appliance must not be less than 22mm copper or equivalent.
Standard and Slimline Model Selection Guide
Max hot water demand
Max number
of bed spaces
(Bedrooms)
Indirect
litres
Direct
litres
1 shower room Bedsit (0) 90 120
1 bathroom 2 (2) 120 150
1 bathroom 4 (3) 120 180
1 bathroom + separate shower room 6 (4) 150 210
1 bathroom + 2 separate shower rooms
or 2 bathrooms
7 (5) 180 210
2 bathrooms + separate shower room 7 (5) 210 250
2 bathrooms + 2 separate shower rooms 7 (5) 250 300
3 bathrooms + 2 separate showers rooms 9 (6) 300 400
3 bathrooms + 3 separate showers rooms 9 (6) 400 -
Solar Model Selection Guide
Max hot water demand Bedrooms
Indirect
litres
Direct
litres
1 shower room Bedsit - 180
1 bathroom 1-3 180 -
1 bathroom 1-3 210
1 bathroom + 1 shower room 1-3 210 -
1 bathroom + 1 shower room 1-3 - 250
1 bathroom + 2 shower rooms 2-4 250 -
1 bathroom + 2 shower rooms 2-4 - 300
2 bathrooms + 1 shower room 3-4 300 -
2 bathrooms + 1 shower room 4-5 - 400
2 bathrooms + 2 shower rooms 4-5 400 -
INSTALLATION
INSTALLATION
Further guidance on converting heat loss limits to insulation thickness for specific thermal conductivities is available in TIMSA “HVAC guidance for achieving compliance with Part L of the Building Regulations”.
Mains Water Supply
Existing properties with a 15mm supply will be satisfactory provided the local mains pressure is good, but should be conned to single bathroom properties. For new properties where simultaneous demand is required to more than one bathroom or a bathroom and one or more en-suites, the communication and service pipe into the dwelling should be a minimum of 22mm (usually in the form of a 25mm MDPE supply). The optimum performance is achieved if the inlet pressure is 3 bar dynamic. However, the Stainless Lite will function with lower inlet pressures, but this will reduce the performance. For optimum performance, 30L per minute incoming mains ow should be present, however the Stainless Lite will work at lower ow rates, although performance will be affected. Normally Stainless Lite provides well in excess of 40 litres/min in most conditions. Flow rates for ALL mains pressure systems are subject to district pressures and system dynamic loss. Particularly on larger properties with more than one bathroom, the pipe sizes should be calculated in accordance with BS EN 806-3:2006 and BS 8558:2011.
Model Selection
The suggested Direct model sizes, shown opposite, are based on a typical days hot water use assuming an Economy 7 tari is provided. A reduction of one model size can normally be made with an Economy 10 tariff. When using the Direct models for high specication developments an increase of one model size should be considered.
The suggested model sizes are based on typical hot water usage. For high specication dwellings an increase of one model size should be considered.
Insulation of pipework
Pipe outside
diameter
Maximum
heat loss
15mm 7.89W/m
22mm 9.12W/m
28mm 10.07W/m
35mm 11.08W/m
Page 13
INCOMING COLD SUPPLY
M
DC
DC
DC
TO EXTERNAL TAP
SINK
WATER SOFTENER (IF NECESSARY)
WM or DWM
WHB
W.C.
DC
DC
SH
DHW
WHB
WC BATH
SCV
SCV
P&T
ERV/NRV
PRV
DCV
Note: Cold supplies to single taps must be
taken from the mains cold water system.
Cold supplies to mixer taps must be taken from the balanced cold water connection on the combination valve.
General Restrictions
a. The highest hot or cold water draw o point should not exceed 10 metres above
the Pressure Reducing Valve.
b. An ascending spray type bidet or any other appliance with a Class 1 back-syphonage
risk requiring a type A air gap should not be used.
c. Stainless Lite should not be used where steam is the primary heating medium, or
in a situation where maintenance is likely to be neglected. d. Unvented cylinders are not suitable for use with solid fuel boilers. e. If the supply to the mixer ttings (other than a dual outlet type) is not taken from
the balanced supply the system will become over pressurized and cause the
pressure relief valve to discharge. Over time this could also cause the premature
failure of the appliance itself which will not be covered by the warranty.
f. In larger properties with a number of bathrooms/en-suites and long pipe runs
we would recommend that the balance cold supply is provided with its own
pressure reducing valve and is not taken from the balanced cold connection on
the combination valve. In this case it will also be necessary to t a small expansion
vessel on the balanced cold water system to accommodate the pressure rise caused
by the increase in temperature of the balanced cold water. g. Check the performance requirements of the terminal ttings with regard to ow/
pressure are suitable. h. In relation to potable water systems, expansion vessels shall be installed in a vertical
orientation and located so that the length of the connecting pipe work is kept to
a minimum.
Shower Fittings
Aerated taps are recommended to prevent splashing. Any type of shower mixing valve can be used as long as both the hot and cold supplies are mains fed. However, all mains pressure systems are subject to dynamic changes particularly when other hot and cold taps/showers are opened and closed, which will cause changes in the water temperature at mixed water outlets such as showers. For this reason and because these are now no more expensive than a manual shower we strongly recommend the use of thermostatic showers with this appliance. These must be used in 3 storey properties where the impact on pressure/temperature of opening another tap in the system is greater than normal. The shower head provided must also be suitable for mains pressure supplies.
Pipe Layout
In all mains pressure installations it is important to remember that the incoming cold supply must be shared between all terminal ttings. It is important that a 22mm supply is brought to the appliance and a 22mm take-o is continued at least to the bath. If there are two baths, 28mm pipework should be considered. One metre of smaller diameter pipework, or ow restrictors, should be provided on the nal connection to all outlets so as to balance the water available. In any event the distribution pipework should generally be in accordance with BS EN806-1 to 5.
Plastic Pipework
This appliance is suitable for use with plastic pipework as long as the material is recommended for the purpose by the manufacturer and is installed fully in accordance with their recommendations.
Secondary Hot Water Circulation
Some models are fitted with a secondary return tapping as standard (see tables 1 and 2 for details). If tted, an extra expansion vessel may be necessary. A non-return valve MUST be FITTED near the return connection. No valve or terminal tting should be installed between the non return valve and the cylinder. (See schematic arrangement on page 15.) All pipes kept hot by the secondary circulation should be insulated.
INSTALLATION
INSTALLATION
Page 14
15 mm discharge pipe
Expansion relief valve
Typical Discharge Pipe Arrangement
Dotted line showing alternative route with single tundish being used
600 mm max.
P & T
Relief
Valve
300 mm
min.
22 mm metal pipe with continuous fall up to 9m equivalent length (D2).
NOTES:
The discharge will consist of scalding waterand steam. Asphalt, roong felt and non-metallic rainwater goods may be damaged by such discharges.
It is not acceptable to discharge straight into a soil pipe.
Discharge below xed grating
Fixed Grating
Trapped gully
Pressure & Temperature/expansion Relief Valve Pipework
The relief valve should be installed to discharge in accordance with G3 of the Approved Document of the Building Regulations and should be piped to where it is visible, but will not cause danger to persons or damage to materials.
The following information is taken from Approved Document G3 of the Building Regulations and is provided to assist with the design and installation of the discharge pipework. However, the information is not exhaustive and reference should always be made to Approved Document G3 of the Building Regulations. The nal decision regarding any arrangements rests with Building Control and it is recommended that their advice is sought if you have any concerns regarding this aspect of the installation.
The two safety valves will only discharge water under fault conditions. When operating normally water will not be discharged.
The tundish should be vertical, located in the same space as the unvented hot water storage system and be tted as close as possible and within 600mm of the safety device e.g. the temperature relief valve.
The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge, be of metal and:
a) Be at least one pipe size larger than the
nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger, and so on. Bends must be taken into account in calculating the ow resistance. Refer to the table and the worked example.
An alternative approach for sizing discharge
pipes would be to follow BS EN 806-2:2005 Specication for design installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages.
b) Have a vertical section of pipe at least
300mm long, below the tundish before any elbows or bends in the pipe work.
c) Be installed with a continuous fall.
Worked Example
The example below is for G1/2 temperature relief valve with a discharge pipe (D2) having 4 elbows and length of 7m from the tundish to the point of discharge.
From the table below:
Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is: 9m subtract the resistance for 4 x 22mm elbows at 0.8m each = 3.2m.
Therefore the maximum permitted length equates to: 5.8m.
5.8m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valve equates to: 14m.
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
Sizing of copper discharge pipe ‘D2’ for a temperature relief valve
with a G1/2 outlet size (as supplied)
Size of discharge
pipework
Maximum length of
straight pipe
(no bends or elbows)
Deduct the gure
below from the
maximum length for
each bend or elbow in
the discharge pipe
22mm Up to 9m 0.8m
28mm Up to 18m 1m
35mm Up to 27m 1.4m
INSTALLATION
INSTALLATION
Page 15
d) It is preferable for the discharge to be visible at both the tundish and the nal point
of discharge but where this is not possible or practically dicult there should be clear visibility at one or other of these locations. Examples of acceptable discharge arrangements are:
1. Ideally below the xed grating and above the water seal in a trapped gulley.
2. Downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc are acceptable providing that where children play or otherwise come into contact with discharges, a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility.
3. Discharges at a high level; e.g. into metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering systems that would collect such discharges.
4. Where a single pipe serves a number of discharges, such as in blocks of ats, the number served should be limited to not more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected. If unvented hot water storage systems are installed where discharges form safety devices may not be apparent i.e. in dwellings occupied by blind, inrm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
P&T Relief Valve
Tundish
Hot Outlet
To Drain
PRV
NRV
Stop Tap
Kitchen
Cold
Tap
Combination
Valve
Balanced
Cold
Outlets
Immersion Heater
Expansion Vessel(s)
Boiler
Return
Boiler
Flow
2 Port Valve
Secondary
Return Circuit
Schematic Diagram
Non Return
Valve
Pump
ERV
Combination Inlet Group
Combines elements 1, 2 and 3 below.
1. Pressure Reducing Valve - This must be xed near the cylinder. The cold water supply to any mixer taps/showers must be taken from the cold water tapping of this valve to ensure balanced hot and cold pressures. This valve is factory set to ensure the correct operating pressure for the Stainless Lite.
2. Non Return Valve - This is integral with the pressure reducing valve to prevent backow of hot water towards cold water draw o points.
3. Cold Water Expansion Relief Valve - This safety device is preset at the factory and will relieve excess cold water pressure resulting from a fault condition.
2 expansion cylinders on 400 litre Models
All 400 litre models are supplied with two 24 litre expansion cylinders. These can be coupled together and tted to the expansion cylinder tapping on the combination inlet valve, or by some other means on the cold/hot water inlet pipework. There must be no valve on the pipe work between the expansion cylinders and the unvented cylinder which could prevent the expansion of the water contained in the unvented cylinder reaching the expansion cylinders.
INSTALLATION
INSTALLATION
Safety
The safety devices supplied or fitted on an Stainless Lite are selected for their suitability for the temperatures and pressures involved. They must not be changed, removed or by-passed and it is essential that only genuine replacement parts supplied or approved by Gledhill Building Products Limited are used. All parts are available to approved installers from Gledhill Building Products Limited, Sycamore Estate, Squires Gate, Blackpool (Telephone 01253 474402).
Line Strainer
This is integral within the combination inlet group to reduce the likelihood of contaminants fouling the valve seat. Following installation this line strainer must be cleaned and replaced. This needs to be carried out on a regular basis. as part of the annual maintenance/service check.
Tundish
This is to allow the discharge from any Relief Valve to be seen. It must be tted away from any electrical devices. See page 14 for discharge pipework details.
Page 16
Lift Up Pressure & Temperature Relief Valve
This safety device is also pre-set at the factory and relieves before the temperature reaches 100°C. It is also a Pressure Relief Valve, and is pre-set to 6 bar.
Immersion Heaters
The immersion heaters tted to our units are 3kW 240V ~AC. Check that the mains supply conforms to this, and all external wiring conforms to the most recent revision of the IEE wiring regulations. An Incoloy element is used on this product for standard domestic use and water conditions, use our Titanium elements in all other circumstances, part number SH002.
The immersion heater is tted into the hot water cylinder using an O-ring. After the unit is lled with water check for leaks to determine if the O-ring has sealed and tighten carefully using the appropriate tool. To prevent damage to the O ring do not use excessive force to tighten the immersion heater.
The immersion heater is supplied with a thermostat which has been tested for operation in the cylinder and complies with the European directives for Electromagnetic compatibility and radio interference. It is Rated at 16 Amp 250V ~AC.
Immersion Heater Wiring
E
L
N
INSTALLATION
INSTALLATION
The immersion thermostat has two terminals A and B. The Live (brown) wire should be connected to terminal A and the Neutral (blue) wire should be connected to terminal B. It has been our experience that Crimp terminals make better connections. The immersion heater must be fully earthed (earth post) and connected via a double pole isolator switch having a contact separation at least 3mm, see diagram opposite.
Danger of electrocution: before making any adjustments to the thermostat isolate the immersion heater from the mains electricity supply at the fuse spur unit.
The immersion heater thermostats incorporate a manual reset safety/overheat cut out thermostat. Should this operate, investigate the cause for the operation cut out before pressing the red reset button labelled safety. If there is no apparent fault adjust the control setting down slightly to prevent nuisance tripping.
If another heat source is used to heat the cylinder and this is allowed to raise the water temperature excessively then the overheat thermostat will trip. This is likely on solar thermal products when the solar thermostats are set at high temperatures.
The Direct cylinder is intended to be heated from an off peak supply using the lowest immersion heater(s) and boosted via the upper immersion heater from an on peak supply. Suitable controllers are available to control this operation eectively.
Solar Thermistors / sensors
Care must be taken to ensure that the solar probes are fully inserted into the pockets provided.
Important
Failure to follow the drain down procedure will invalidate the warranty. (see page 22)
NEVER drain the cylinder of hot water and
then close all cylinder inlets and outlets.
REASON as the air remaining in the cylinder
cools the pressure inside the cylinder will fall below atmospheric and cause damage to the cylinder.
NEVER close the cold main and drain the
cylinder via any tap connected to it.
REASON as the water drains, the pressure
inside the cylinder may decrease below atmospheric and this may cause damage to the cylinder.
In line with good plumbing practice, use of excessive ux should be avoided.
I.V.
Combination Valve
I.V.
If two Stainless Lites are coupled together the secondary inlet and outlet pipes must be balanced. The units must be tted on the same level.
Note: No valves must be tted between the expansion vessel and the storage cylinder(s).
Thermostat Type TSR tted in the Direct cylinders; is supplied set at 62°C ± 3°C. Position 4 is 55°C ± 3°C and position 5 is 68°C ± 3°C.
Thermostat Type TSE tted in the indirect cylinders - is supplied set in position 5 at 60°C ± 4°C.
When ordering a replacement part the TSR thermostat type will be supplied with the immersion heater.
Page 17
Heating/primary Systems
The boiler and primary/heating systems should be sized and installed in accordance with BS EN 12828:2003, BS EN 12831:2003 & BS EN 14336:2004.
Safety
Stainless Lite is fitted with a Combined Lift Up Temperature/Pressure Relief Valve to cope with any increase in system temperature and pressure above the design limitations, when used with boilers up to 45kW output, which is the maximum allowed by section G3 of the Building Regulations. The primary water temperatures should be controlled as outlined below.
Primary Circuit
It is essential that the circuit between the boiler and the Stainless Lite is pumped. The motorised zone valve supplied should be tted adjacent to the unit and controlled by the cylinder thermostat supplied. The thermostat and motorised valve must be wired so that they both switch o should an overheat situation develop. It is important to follow the wiring diagram in the Wiring Section of these instructions.
Sealed Primary Circuit
Any boiler used must be tted with an over temperature cut-out. Unvented primary circuits may be filled or replenished by means of a temporary connection between the circuit and a supply pipe provided a ‘Listed’ double check valve or some other no less eective backow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use.
Alternatively, a CA device can be used, which will allow the system to be permanently connected to the cold mains supply. The primary system can then be topped up, when required, in the same way as an open vented system tted with an F&E Cistern.
Gate Valve
All our cylinders are tested to BS EN 12897 at 15 l/mim at which they exceed the minimum requirements for heat up performance and reheat in less time than the maximum reheat times.
In extreme situations where excessive flow rates, above 25 l/min are present, then a gate valve on the return from the cylinder to the boiler, before it joins the central heating return, may be required to reduce excessive ow rates and therefore any potential noise problems.
Schematic Open Vented Primary System
Boiler
Pump
150mm max.
Warming/Overflow
Pipe
F & E Cistern
Minimum
distance as
required by
boiler
manufacturers
instructions
Motorised Valve
(Not supplied)
Motorised Valve
(Energy cut-out)
Gate Valve
(Not supplied)
Schematic Sealed Primary System
Boiler
Motorised Valve (Energy cut-out)
Expansion
Vessel
Gauge
Safety Valve
Pump
Motorised Valve
(Not supplied)
Gate Valve
(Not supplied)
INSTALLATION
INSTALLATION
Page 18
Schematic Solar Direct System
Solar Pumping Station
Solar Panel
Expansion
Vessel
Solar
Controller
Motorised Valve
Energy cut-out
(Not supplied)
All components in a solar primary system must be marked or identiable in such a way that their design pressure and temperature can be readily determined.
A pressure and temperature relief valve to control the risk of over-pressure in system components should be tted. A termination from a pressure and temperature relief valve should minimise the risk of damage to persons or materials. Suitable locations are into a high temperature receptacle, an internal gully or externally at ground level. High level termination from walls or on roofs could cause injury to people or animals below if the valve were to release scalding water and steam.
The pipe leading to the safety device and the collector should be of rigid and non-deformable construction, without any possibility of restriction or disclosure by any other fitted component.
A more detailed diagram of our recommended arrangement for a typical solar system is shown on page 20.
This provides all the necessary controls and safety devices necessary for the solar system i.e. the two port zone valve is wired as an energy cut out and the pump/valve will only allow heat transfer as required under control of the solar controller.
The solar pocket provided accommodates an 8mm diameter sensor which, with the sensor located in the solar collector (or in the ow pipe immediately adjacent to the collector), will provide the information required by the solar controller.
Note: If the motorised valve is not used then any factory built hydraulic station for solar use MUST be tted with suitable non-return valves in both flow and return pipes to prevent gravity circulation when the pump is not running.
If there is a possibility of the solar controller that you install causing the cylinder temperature to exceed 80°C, under normal working conditions, then a Solar tempering valve must be tted to the domestic hot water outlet of the cylinder. This must limit the hot water temperature to a maximum of 60°C.(ref building regulations part G3 3.63). This product can be supplied from Gledhill part number XC007 which has a inlet temperature limit of 100°C. Suitable plumbing configurations for installing this valve are shown on page 19 of this manual. NB. Any tted Overheat thermostats may require resetting in the winter months to enable backup heat sources to heat the cylinder.
Schematic Solar Indirect System
Solar Pumping Station
Solar Panel
Expansion
Vessel
Solar
Controller
Motorised Valve
Energy cut-out
(Not supplied)
Motorised Valve
Energy cut-out
(Not supplied)
INSTALLATION
INSTALLATION
Page 19
Mixed HW out
Mains CW in
Figure 1: Cold port of the blending valve connected to mains supply
NOT ALLOWED
Mixed HW out
Mains CW in
Figure 3: Cold port of the blending valve connected to mains supply
to the vessel after the inlet control group
Mixed HW out
Mains CW in
Non-Return Valve (must be fitted)
Figure 2: Cold port of the blending valve connected to balanced cold
supply - NON-RETURN VALVE MUST BE FITTED
Fitting Blending Valves To The Unvented Stainless Lite Appliances
When tting a blending valve to the unvented appliances, it is important that the installation does not contravene the G3, WRC and Health and Safety directives or the manufacturers recommendations. If this is the case, then the warranty should be null & void. The key requirements to comply with these regulations are: -
1. Any fitting or material in contact with potable water (e.g. a blending valve) must be approved by WRC or an equivalent body.
2. Connections or wiring arrangements must not bypass any safety devices.
3. Any expansion due to heating must not be allowed to expand back into the cold mains.
4. The settings of any safety devices must not be tampered with or adjusted.
The diagrams opposite shows how the blending valve can be piped onsite.
Figure 1 shows the cold water port of the blending valve connected to the mains cold water supply before the inlet control group. This arrangement is completely unacceptable and illegal because: -
• the water is allowed to expand in to mains cold water supply.
• the vessel will be charged to the incoming mains supply which may be considerably higher than the working pressure of the vessel.
If this arrangement is used then the Gledhill warrant will not be valid.
Figure 2 shows the cold water port of the blending valve connected to the balanced cold water outlet. This arrangement will only be acceptable if a WRAS approved non-return valve is tted, otherwise: -
• during the heating cycle, the water will expand back into the mains supply, as the regulating valve must not be relied upon to act as a check valve under all operating conditions.
• depending upon the characteristics of the blending valve, hot water may also ow from the balanced cold water taps.
Figure 3 shows the cold port of the blending valve connected to the cold water supply to the vessel after the inlet control group. This should be the preferred method. It is recommended that the installer should ensure that there is no gravity circulation in the pipework connected to the cold port. If necessary, this can be achieved by tting a non-return valve or using a thermal trap.
INSTALLATION
INSTALLATION
Page 20
1 98765432 10
1 2 3 4 5 6 7 8
S1 S2 S3
201918171615141312
LNR1R2 NN
T
S1
S1
1 bar
Solar Pumping Station
Solar Coil
TWO PORT ZONE VALVE
A
B
C
1 2C1
+ C
o
+ C
o
L N
230 VAC 5 amp Mains Supply
Dual Thermostat
Gledhill Stainless Lite Unvented Cylinder
T
Anti Gravity Check Valve
Pressure Relief Valve
Anti Gravity Check Valve
Standard 10 way wiring junction box (Not supplied)
This valve must be tted on
the return to the solar panels
and be suitable for higher
temperatures operation
(Not supplied)
No isolation valve should be installed between the solar circuit and the safety valve (pressure relief valve)
Solar Controller
Schematic Showing Solar Wiring Requirements
INSTALLATION
INSTALLATION
Page 21
1 98765432 10
11
12
N L 1 2 3 4
OFF ON OFF ON
HW CH
1 2 3 4
Room ThermostatCentral Heating Control
C
1
C
1
2
Dual Aqau Stat
Overheat Stat Control Stat
L
N
E
Mains Supply Fed Via Double Pole Isolator 230 VAC ~ 5 Amps
Danfoss WB12 Wiring Centre
HTG VALVE
HW VALVE
Typical schematic wiring diagram for an unvented installation
The electrical installation must
comply with IEE requirements.
For electrical installation
refer to BS7671
Note: Do not attempt
the electrical work unless
you are competent to carry
out to the above standard
BlueBl
BrownBr
Green
Grey
Green / Yellow
G
Gr
G/Y
WIRE COLOUR LEGEND
Black
Orange
Yellow
White
Red
B
Or
Y
Wh
R
Br Bl G/Y Br Br Bl G/Y
Or
Gr
5 Amps
Br Bl
G/Y
Br Br B
*Br
Bl
G/Y
Br
B
Bl Br Br Br
Br Bl B
G/Y
G/Y Br *Br
* Blue core used from standard 3 core flex please ensure you use brown sleeving at both terminating ends to identify core potential.
3 core flex
4 core cable
L N
L
L_P
SL_B
ENN_P
E_P
Br Bl G/Y B Br Bl G/Y
Boiler Pump
ISSUE No : 5
APPROVED
DRN.
DATE
07-12-10
N. Fursman
V4043A TWO PORT ZONE VALVE
A
B
HTG
Br Bl G/Y
OrGr
V4043A TWO PORT ZONE VALVE
A
B
DHW
Br Bl G/Y Or Gr
GAS BOILER
Boiler Permanent Live
Boiler Neutral
Boiler Earth
Boiler Switch Live Demand
Boiler Controlled Pump
Provide extra core from terminal 12 to L-P connection on the boiler (shown dotted) and remove the boiler pump link if the boiler has an independant pump output.
L
N
E
(S-PLAN) WIRING DIAGRAM WITH TWO 2 PORT VALVES AND BOILER CONTROLLED PUMP OVERRUN OPTION
Br Bl G/Y
B
Br
Or
ELECTRONICS
1 98765432 10
11
12
N L 1 2 3 4
OFF ON OFF ON
HW CH
1 2 3 4
Room ThermostatCentral Heating Control
1
C
2
2
C
1
Dual Cylinder Stat
Overheat Stat
Spade
connectors
required for earth
connections
Control Stat
L
N
E
Mains Supply Fed Via Double Pole Isolator 230 VAC ~ 5 Amps
HTG VALVE
HW VALVE
Typical schematic wiring diagram for an unvented installation
The electrical installation must comply with IEE requirements.
For electrical installation
refer to BS7671
Note: Do not attempt
the electrical work unless
you are competent to carry
out to the above standard
BlueBl
BrownBr
Green
Grey
Green / Yellow
G
Gr
G/Y
WIRE COLOUR LEGEND
Black
Orange
Yellow
White
Red
B
Or
Y
Wh
R
Br Bl G/Y Wh Br BrBl G/Y
Or B
Gr Gr
5 Amps
Br Bl
G/Y
Br Br B
*Br
Bl
G/Y
Bl Br Br Br
Br Bl B
G/Y
G/Y Br
R (Supplied with stat)
*BrB
* Blue core used from standard 3 core flex please ensure you use brown sleeving at both terminating ends to identify core potential.
4 core cable
4 core cable
L N
L
L_P
SL_B
ENN_P
E_P
Br Bl G/Y B Br Bl G/Y
Boiler Pump
ISSUE No : 4
APPROVED
DRN.
DATE
07-12-10
N. Fursman
A
B
HTG
Wh Bl G/Y
OrGr
A
B
DHW
Br Bl G/Y Or Gr
GAS BOILER
Boiler Permanent Live
Boiler Neutral
Boiler Earth
Boiler Switch Live Demand
Boiler Controlled Pump
Provide extra core from terminal 12 to L-P connection on the boiler (shown dotted) and remove the boiler pump link if the boiler has an independant pump output.
L
N
E
(Y-PLAN) WIRING DIAGRAM WITH 3 PORT VALVE/2 PORT SAFETY VALVE AND BOILER CONTROLLED PUMP OVERRUN OPTION
Br Bl G/Y
B
B
Br
Or
ELECTRONICS
13
V4073A
MID POSITION
ZONE VALVE
V4043A
TWO PORT
ZONE VALVE
INSTALLATION
INSTALLATION
Page 22
Connections can come loose in transit, and all should be checked before installation.
The 90 degree elbow tted on the hot draw o needs to be positioned and tightened by installer.
The control thermostat of the immersion heaters for direct heating of our cylinders are set at 60°C. The control thermostat for indirect heat exchanger heat up of our cylinders are usually set at between 60°C - 65°C. During commissioning the actual temperature that the cylinder reaches when the thermostat(s) operate should be tested and adjusted so that it achieves a minimum of 60°C. This temperature needs to be achieved on a regular basis.
Check the pressure on the air side of the expansion vessel = 3 bar. This must be done when the water in the cylinder is free to expand in atmospheric pressure or the cylinder and relevant pipe work is empty.
Check that the drain cock is closed, and open all the cold and hot water taps and other terminal ttings. Allow the system to ll with water, and to run until there is no air left in the system. Close the taps and inspect the system closely for leaks.
Manually open the Relief Valves one by one and check that water is discharged and run freely through the tundish and out at the discharge point. The pipework should accept full bore discharge without overowing at the tundish, and the valve should seat satisfactorily.
In line with good plumbing practice, use with excessive ux should be avoided. When soldering above the cylinder, ensure ux/solder does not contaminate the cylinder below, since this can cause corrosion. Flushing should be done performed as per BS EN 806:4 2010 section 6.2.
Allow the cylinder to heat to normal working temperature, then thoroughly ush the domestic hot and cold water pipework through each tap.
NOTE: If this appliance is to be installed in other than a single domestic dwelling ie. in an apartment block or student ats etc., the hot and cold water system will need to be disinfected in accordance with BS EB 806:4 2010 section 6.3 and the Water Regulations.
Because the Stainless Lite appliance is stainless steel, the use of chlorine as the disinfection agent can cause damage unless the appliance is adequately ushed and relled with the mains water immediately on completion of the disinfection procedure.
Damage caused through a failure to do this adequately will not be covered by the warranty.
For the reasons mentioned, we recommend the use of a non chlorine based disinfectant such as Fernox LP Sterox as manufactured by Cookson Electronics when carrying out disinfection of systems incorporating these appliances.
Remove the lter from the combination inlet group clean and replace. Rell the system and open all hot taps until there is no air in the pipe work. ENSURE CYLINDER IS DRAINED PRIOR
TO CHECKING OR REMOVING FILTER FROM THE COMBINATION INLET GROUP.
Allow the cylinder to heat to normal working temperature with whatever heat source is to be used, and check again for leaks. The pressure relief valve or the P&T valve should not operate during the heating cycle. If the P&T valve operates before the pressure relief valve due to high pressure, check that the inlet control group is tted correctly.
The boiler/heating systems should be lled and commissioned in accordance with good practice following the guidance in BS 7593:2006/the boiler manufacturers instructions. This includes adequately ushing the system to remove any debris that may have been introduced during installation/maintenance.
NOTE
At the time of commissioning, complete all relevant sections of the Benchmark Checklist located on the inside back pages of this document.
This must be completed during commissioning and left with the product to meet the Warranty conditions oered by Gledhill.
IMPORTANT - DRAIN DOWN PROCEDURE
1 Switch o both the boiler and the immersion heater
2 Open the nearest hot tap and run all hot water until cold, then close it
3 Close the incoming cold main at the stop tap
4 Hold open the pressure and temperature relief valve until water stops
discharging into the tundish and leave it open
5 Open the cold taps starting from the highest point and working down to
the lowest tap, leaving them open
6 When the cold taps have stopped draining, open the hot taps starting from
the highest and working down to the lowest tap
7 Open the drain cock and ensure the pressure and temperature relief valve
is held open until the cylinder is empty
INSTALLATION
COMMISSIONING
Page 23
Your Stainless Lite unvented cylinder is automatic in normal use, but requires routine maintenance which is normally carried out at least annually along with the boiler service. The maintenance must be carried out by a suitably competent tradesperson who is qualied to work on unvented cylinders. The checks/work needed are listed in the maintenance part of these Instructions.
The control thermostat of the immersion heaters for direct heating of our cylinders are set at 60°C. The control thermostat for indirect heat exchanger heat up of our cylinders are usually set at between 60°C - 65°C. During commissioning the actual temperature that the cylinder reaches when the thermostat(s) operate should be tested and adjusted so that it achieves a minimum of 60°C, in order to comply with the Legionella pasteurisation requirements.
When initially opening the taps, a small surge in ow may be experienced, which disappears as the pressure in the system stabilises. This is quite normal with these types of systems and does not indicate a fault.
In some areas the water will initially appear cloudy, but will quickly clear when left to stand. This is nothing to be concerned about and is due to aeration of the water.
WARNING - If water is seen owing through the tundish, this indicates a fault condition which needs action.
If the discharge is hot and continuous, turn the boiler and/or the immersion heaters o, but do not turn o the cold water to the appliance until the discharge is cold. Note: The discharge may stop by itself as the discharge cools.
If the discharge is cold and intermittent, no immediate action is needed but this indicates a problem with the expansion vessel.
However, in both cases you must call the registered installer / a suitably qualied, competent tradesperson, advise them that you have an unvented cylinder and request a maintenance visit.
DO NOT, at any time, tamper in any way with the safety valves or overheat thermostats/
wiring.
INSTALLATION
USER INSTRUCTIONS
Page 24
The Registered Installer is responsible for the safe installation and operation of the system. The installer must also make his customer aware that periodic maintenance of the equipment is essential for safety.
Maintenance periods will vary for many reasons. Gledhill Building Products Ltd recommend a maximum of 12 months to coincide with boiler maintenance. Experience of local water conditions may indicate that more frequent maintenance is desirable, eg, when water is particularly hard, scale-forming or where the water supply contains a high proportion of solids, eg, sand. Maintenance must include the following:
1. Check and clean lter
2. Manually check the operation of the temperature relief valve.
3. Manually check the operation of the expansion relief valve.
4. Check discharge pipes from temperature and expansion relief valves are free from obstruction and blockage and are not passing any water.
5. Check the condition and if necessary descale the heat exchangers in hard water areas.
6. Check that water pressure downstream of pressure reducing valve is within the manufacturers limits.
7. Check operation of motorised valve.
8. Check the pressure on the air side of the expansion vessel. This must be done when the volume in the cylinders is cold.
9. Check and advise the householder not to place any clothing or other combustible materials against or on top of this appliance.
10. On completion of the work, ll in the Benchmark Service Record towards the back of this manual.
After servicing, complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
IMPORTANT NOTE
When draining down the appliance for any reason, the instructions provided in the Commissioning Section (Page 22) MUST be followed to prevent potential damage to the cylinder.
SERVICING AND MAINTENANCE
SERVICING AND MAINTENANCE
Page 25
Scale
In hard water areas it is recommended that an in-line scale inhibitor is tted. Reducing the temperature of the stored water will reduce the rate at which scale forms. If the recovery rate is badly aected, this is an indication that scaling may have occurred. In this event, follow the procedures as recommended by a reputable Water Treatment Company.
General
No water at the tap. Check that the mains water supply is turned ON. Check the line strainer is not blocked. Check that the combination valve has been tted so that water is owing in the correct direction. If the water at the tap is cold, ensure that the boiler has been switched ON and is working correctly. Check that there are no air locks in the primary system. ISOLATE THE UNIT AT THE MAINS ELECTRIC SUPPLY AND THEN CHECK THE FOLLOWING: i. The cylinder thermostat ii. The thermal cut-out, which can be re-set by pushing the red button iii. The motorised valve iv. The boiler thermostat v. The boiler thermostat cut-out (if tted)
ANY ENERGY CUT-OUT MUST NEVER BE BY-PASSED UNDER ANY CIRCUMSTANCES.
If the units are not getting hot and the heat source is electrical, ensure that the immersion heaters are isolated from the mains before re-setting the energy cut-out. If the immersion heater(s) need replacing this should be done with the units supplied from Gledhill Building Products Limited. Same day despatch to approved installers can be arranged by telephoning 01253 474402.
Discharge From Relief Valves
If cold water is discharging from the expansion relief valve into the tundish check the pressure on the expansion vessel when cold and recharge if necessary.
If the fault continues and the problem cannot be stopped by operating the easing control a few times then either the Pressure Reducing Valve or the Relief Valve may be at fault. If the cold water pressure is too high, this would suggest that the Pressure Reducing Valve is at fault and the Gledhill approved replacement should be tted. If the pressure is correct then the Relief Valve will require replacing with a Gledhill approved component.
See Commissioning for drain down procedure.
If there is an overheat fault and very hot water is being discharged, turn o the heat source, but not the water supply.
When the supply is cool, check thermostats and energy cut-outs in the boiler and immersion heaters and replace the faulty component with a unit supplied by Gledhill and check that it works correctly before returning the system to full operation.
SERVICING AND MAINTENANCE
FAULT FINDING
Page 26
FAULT - No Hot Water (Direct)
FAULT - No Hot Water (Indirect)
Switch on
Re-set
Replace element
START
Is power on to elements?
Is control temperature
set at 60ºC - 65ºC?
Has high limit tripped?
Check wiring links
continuity and Re-set
END
YES
YES
YES
NO
NO
NO
Switch on
Set programmer
Re-set, check wiring &
plumbing is correct
Re-set
Is all wiring to the
controls ok?
Replace thermostat
Re-wire
START
Is boiler on?
Is hot water programmer
in ‘on’ position?
Is zone valve in
correct position?
Is control temperature
set at 60ºC - 65ºC?
Has high limit cut out?
Re-set
END
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO NO
NO
SERVICING AND MAINTENANCE
FAULT FINDING
Page 27
FAULT - Poor Water Flow at Hot Taps
FAULT - Water Discharge Into Tundish
Water service check by
supply company required
Clean or replace strainer
as appropriate
Service /replace PRV
as appropriate
START
END
Is incoming mains supply flow/pressure adequate?
Is in-line strainer
(in combination valve)
clean?
YES
YES
YES
YES
NO
NO
NO
Clear obstructions
Is system free from
restrictions/blockages?
YES
NO
Is pressure reducing valve
(in combination valve)
working?
Clean or replace
as required
Is expansion vessel
charge pressure correct?
Replace ERV/TPRV
Replace PRV END
START
Is pressure downstream
of pressure reducing valve
correct?
Is valve seal and seat clean & undamaged?
Is heater operating at
less than 60ºC?
Re-set temperature
NO
YES
YES
NO
NO
YES
YES
Is ERV/TPRV
discharging?
YES
Recommission
expansion
vessel pressure
NO
NO
SERVICING AND MAINTENANCE
FAULT FINDING
Page 28
SPARE PARTS LIST
Description Quantity Stock Code No.
1 3kW immersion element 1 SH010
2 22mm 90° compression elbow c/w/drain 1 SF003
3 Lift up pressure and temperature relief valve 6 bar 92-95°C 1 SG023
4 Inlet group set at 3 bar c/w expansion relief valve set at 4.5 bar 1 SG022
5 ¾” exible hose 1 SG024
7 12 litre expansion vessel 1 XG190
8 18 litre expansion vessel 1 XG191
9 24 litre expansion vessel 1 XG192
10 35 litre expansion vessel 1 XG193
11 Wall mounting bracket for 35 litre expansion vessel 1 XG058
12 22mm 2 port valve (indirects only) 1 XG083
13 Junction wiring box (12 way) 1 XG129
14 Control and overheat limit thermostat 1 XG212
15 15mm x 22mm tundish 1 XG207
16 28mm 2 port valve 1 XC012
SERVICING AND MAINTENANCE
SHORT PARTS LIST
Page 29
Vast quantities of water are needlessly run o to waste due to Taps, Mixers and Showers discharging ow rates far in excess of the rates required for them to perform their duties.
The contrasting ow rates shown on this leaet clearly illustrate the savings that can be made whilst still providing a good performance.
British made Aquaow Regulators provide constant ow rates by automatically compensating for supply pressure changes between 1 bar & 10 bars.
To facilitate installation into the wide range of plumbing equipment which is
encountered in the U.K, Four Fixing Options are available:-
Options For Showers
1. MXF “DW” Range - For tting behind Fixed Shower Heads or onto Flexible Hoses for Handshowers (preferably onto the inlet end when lightweight hoses are used).
2. Compression Fitting Range. “In Line” regulators as in Option 4 for Taps & Mixers.
Information by courtesy of
AQUAFLOW REGULATORS LTD
Haywood House, 40 New Road, Stourbridge, West Midlands DY8 1PA
TELEPHONE 01384 442611 FAX: 01384 442612
Water Savings
Water Related Costs Can Be Reduced By Good Plumbing Practice
TAPS & MIXERS
SHOWERS
Unregulated
25 - 30 l/m
Regulated
10 - 12 l/m
Over
20 l/m
5, 6 or
8 l/m
2 tap
half open
Fitted with regulator
Unregulated
4 Fixing Options For Taps & Mixers
1. MK Range - Combined Regulators & Aerator for screwing onto Taps & Mixers with internal or external threads on their noses. Anti Vandal models also available.
2. MR05-T Range - Internal Regulators. Push­fit into Tap or Mixer seats. Produced in three sizes - 12.5mm (BS1010), 12mm & 10mm, Flangeless models also available for Taps with Low Lift washers.
3. MXF Standard Range - Screw on tail
models for Taps & Mixers. Fix onto the tails
before tting the tap connectors. Available in 3/8", 1/2", 3/4" and 1" BSP.
4. Compression Fitting Range - “In Line” regulators housed in 15mm & 22mm CXC Couplers & Isolating Valves. “ ”UK WFBS listed by the Water Research Centre. Isolation valves available for slotted screwdriver operation or with coloured plastic handles. Now available also in plastic bodied push-t couplers & valves.
2
1
1
2
1
2
3
3
1
4
APPENDIX
APPENDIX A
Page 30
Description
Manual handling means any transporting or supporting of a load (including lifting, putting down, pushing, pulling, carrying or moving) by hand or bodily force.
Scope
This assessment will cover the largest unit within each product range.
For specic weights and dimensions please refer to technical data section.
Main Hazards
Vision may not be clear due to the size of the products. Adopting an incorrect method of lifting may cause injury, attempting to lift these products will require help from others. (Team lifts)
Control Measures
Manual lifting procedure
The lift, key factors in safe lifting are:
a. Balance b. Position of back c. Positioning of the arms and body d. The hold e. Taking the lead for team lifts
a. Balance - Since balance depends essentially upon the position of the feet,
they should be apart about hip breadth with one foot advanced giving full balance sideways and forward without tension. In taking up this position, lifting is done by bending at the knees instead of the hips and the muscles that are brought into use are those of the thigh and not the back.
b. Position of back - Straight - not necessary vertical. The spine must be
kept rigid, this coupled with a bent knee position, allows the centre line of gravity of the body to be over the weight so reducing strain.
c. Positioning of arms and body - The further arms are away from the side,
the greater the strain on the shoulders, chest and back. Keep elbows close to the body arms should be straight.
d. The hold - Before lifting ensure you have a good hold.
e. Taking the lead for team lifts- As
more than one person is required for these products ensure that one person is taking the lead. This may be you so ensure that each person that is helping is made aware of the weight and of the items listed within this assessment. Make sure you and any others helping know the route you intend to take that it is clear of any obstructions. Never jerk the load as this will add a little extra force and can cause severe strain to the arms, back and shoulders. If there are steps involved decide on where you will stop and take a rest period. Move smoothly and in unison taking care to look and listen to others helping with the lift. Where possible use a sack truck to move the product over long at distances, only lift the products when necessary. If in doubt stop and get more help.
Individual capability
Individual capability plays an important part in handling these products. Persons above average build and strength will nd it easier and should be in good health. Persons below average build and strength may require more rest periods during the handling process.
Pregnant women should not carry out this operation.
Persons who are not in good health should seek medical advice prior to commencing any lifting or manual handling operation.
Residual risk
Following the guidelines given above will reduce any risk to injury.
All persons carrying out this operation must be fully trained and copies of the specic risk assessment made available for inspection and use in their training process.
Further guidance on Manual Handling can be obtained from the Health and Safety Executive. Manual Handling Operations Regulations 1992.
MANUAL HANDLING OF APPLIANCE PRODUCTS
APPENDIX
APPENDIX B
Page 31
WARRANTY INFORMATION
WARRANTY INFORMATION
Gledhill Building Products guarantees the StainlessLite cylinder and components against material defect or manufacturing fault for a period of two years from the date of purchase. The two year warranty on the stainless steel inner cylinder will be extended to twenty ve years in domestic properties on the registration of the cylinder (see documentation enclosed with the unit).
The above product guarantees are valid provided:
• It has been installed by a competent installer in accordance with the instructions detailed in our installation manual and all relevant Codes of Practice and Regulations in force at the time of installation.
• No factory tted parts have been removed for unauthorised repair or replacement and the product has not been modied - other than by Gledhill.
• Any replacement parts used should be authorised, approved Gledhill spare parts.
• The cylinder has only been used for the storage of potable water supplied form the public mains (-max 200mg/litre chloride).
• It has not been subject to wrong or improper use, left uncared for, or subjected to scale or frost damage.
• The unit has been serviced annually by a competent, licenced engineer in accordance with the requirement set out in the manual.
• The Benchmark TM Commissioning Checklist Service Record included in our manual has been completed and updated after each annual service.
• Any disinfection has been carried out strictly in accordance with BS6700.
• For heavy use installation where constant usage / reheat is required titanium immersion heaters should be tted.
The registration document enclosed with the unit is completed and returned within 60 days of purchase by the owner. Evidence of purchase and date of supply must be submitted upon making a claim.
Guidance in the event of a problem
If you have a problem in the rst year, please contact the plumber who tted the unit. After the rst year, you should contact the plumber who carries out the annual servicing for you.
Action in the event of component failure within warranty period
Failed components should be returned via the local authorised supplier. A nominal charge of £30 will be made which is refunded in full by Gledhill on receipt of the original part and proof of purchase.
Action in the event of inner vessel cylinder failure within warranty period
Since the full diagnosis of cause of failure is usually only possible with a laboratory test environment where a product can be fully assessed and tested, we will require the return of a cylinder which develops a leak for inspection. Providing our expert examination conrms a manufacturing fault or defect, credit will then be raised against the cost of the original cylinder.
Please note that a copy of the completed annual service record and commissioning checklist should be submitted with any claim.
As a HWA Charter Member we endeavour to provide consumers quality assurance, product satisfaction, and condence in Gledhill, that we will deliver a service beyond just supplying the product.
Page 32
TERMS AND CONDITIONS
Gledhill (Building Products) Ltd
AMD.DECEMBER 2013
CONDITIONS OF SALE & GUARANTEE TERMS
1. Gledhill (Building Products) Ltd (“We” or “Gledhills”) only do business upon the Conditions which appear below and no other. Unless we so agree in writing these Conditions shall apply in full to any supply of goods by us to the exclusion of any Conditions or terms sought to be imposed by any purchaser. These Conditions of Sale and Warranty Terms override those which are contained on the Invoice Forms and all Sales are now subject to these Conditions of Sale and Warranty terms only.
2. PRICE Once an order or call off has been accepted the price will be held for three months but if delivery is extended beyond that period at the customer’s request, then we reserve the right to amend the price when necessary.
The company reviews its pricing annually to adjust for changes in our cost base. We reserve the right to alter prices at any time for severe movements in raw materials (mainly copper and steel). If there is to be a change we will give customers at least four weeks notice but anything delivered after that date will be at the revised price. An order may not be cancelled or varied after acceptance without the written consent of the company. Such cancellation or variation shall be subject to such reasonable charges as may be appropriate.
3. SPECIFICATION
The goods are supplied in accordance with the Specifications (if any) submitted to the Purchaser and any additions and alterations shall be the subject of an extra charge. Any goods not so specified shall be in accordance with our printed literature or the literature of any of our component suppliers (subject to any modifications made since publication). If we adopt any changes in construction or design of the goods, or in the specification printed in our literature, the Purchaser shall accept the goods so changed in fulfilment of the order.
4. PAYMENT
The buyer shall make payment in full within thirty days from the end of the month in which the invoice is dated. If we receive payment in full on or before the due date we will allow an appropriate settlement discount except where we have quoted a special net price. If payment is not received in full on or before the due date we shall be entitled in addition to the invoice price to: (i) payment of a sum equal to any increase in the copper price supplement applicable to the particular goods sold
between the date of receipt of order and the date of receipt of payment in full; and
(ii) interest on any part of the invoice price unpaid after the due date at the rate of 3% per annum over the base
rate for the time being of HSBC Bank plc.
5. TIME
We give estimates of delivery dates in good faith and time of delivery is not nor shall be made of the essence of any contract nor shall we be liable for any loss or damage occasioned by delay in delivery.
6. DELIVERY
We deliver free normally by our own vehicles within 25 miles of any of our manufacturing depots. Delivery to any place more than 25 miles from one of our manufacturing depots may be subject to our quoted delivery charges. We reserve the right to make delivery of goods contained in one order by more than one consignment and at different times. Where a period is agreed for delivery and such period is not extended by our Agreement, the Purchaser shall take delivery within that period. If the Purchaser fails to take delivery, we shall be entitled at the Purchaser’s risk and expense to store the goods at the Purchaser’s premises or elsewhere and to demand payment as if they had been despatched. Off loading at point of delivery shall be the responsibility of and be undertaken by the Purchaser.
7. SHORTAGES OR DAMAGE
Goods must be inspected before signature of delivery note and any damage, shortage or discrepancy noted on the delivery note and the goods returned on the same vehicle. The buyer must also give us immediate written notice of the damage, shortage or discrepancy so that we may prompt investigation.
8. RETURN OF GOODS
Goods may not be returned to the Company except by prior written permission of an authorised officer of the Company and such return shall be subject to payment by the Purchaser of handling and re-stocking charges, transport and all other costs incurred by the Company.
9. COMPANY LIABILITY AND GUARANTEE
9.1. Subject to the terms of these Conditions of Sale and Guarantee Terms Gledhills provide Guarantees in respect of specific products as set out in this clause.
9.2. Each Guarantee is strictly conditional upon the following:-
9.2.1. Complaints must be given to us immediately, before any action is taken, as responsibility cannot be accepted if repairs or renewals are attempted on site without our written approval.
9.2.2. The unit has been installed in accordance with our installation and service instructions and all relevant codes of practice and regulations in force at the time of installation.
9.2.3. All necessary inlet controls and safety valves have been fitted correctly.
9.2.4. The unit has only been used for the storage of potable water supplied from the public mains. The water quality shall be in accordance with European Council Directive 98/83 EC, or revised version at the date of installation, and is not fed with water from a private supply. Particular:
Chloride content: Max. 200 mg/l Sulphate content: Max. 200 mg/l Combination chloride/sulphate: Max. 300 mg/l (in total)
9.2.5 Where appropriate the unit has been regularly maintained as detailed in the installation and service instructions
9.2.6. Defects caused by corrosion or scale deposits are not covered by any Guarantee.
9.2.7. Where we agree to rectify any defect we reserve the right to undertake the work on our own premises.
9.2.8. We will not accept any labour charges associated with replacing the unit or parts for any of the following products listed.
9.2.9. If the newly fitted water heater is not in regular use then it must be flushed through with fresh water for at least 15 minutes. Open at least one hot water tap once per week, during a period of at least 4 weeks.
9.3. Guarantees are provided in respect of specified goods supplied by Gledhills as follows:-
(a) Domestic and Commercial Open Vented Cylinders and Tanks.
The storage vessel is guaranteed for ten years and if it proves to be defective either in materials or workmanship,
we will either repair or supply replacement at our option with the closest substitute in the case of any obsolete product to any address in Great Britain.
(i) free of all charge during the first year after delivery by us. (ii) thereafter at a charge of one-tenth of the then current list price and any copper price supplement and
delivery charge during the second year after delivery by us and increasing by a further one-tenth on the second and subsequent anniversary of delivery by us.
(b) Domestic Mains Fed Products [Primary Stores]
The storage vessel is guaranteed for five years and if it or any integral pipework as part of the storage vessel
assembly proves to be defective either in materials or workmanship, we reserve the right to either repair or supply replacements or the closest possible substitute in the case of any obsolete product and will collect and deliver to any address in England, Wales and Scotland (excluding all Scottish Islands).
(i) free of all charge during the first year after delivery
by us.
(ii) thereafter at a charge of one-fifth of the then current
list price or any copper price supplement and delivery charge during the second year after delivery by us increasing by a further one-fifth on the second and subsequent anniversary of delivery by us.
(c) StainlessLite Unvented Cylinders
Gledhill guarantee the components including controls,
valves and electrical parts for two years from the date of purchase. IT SHOULD BE NOTED THAT THE FACTORY FITTED TEMPERATURE AND PRESSURE RELIEF VALVE MUST NOT BE REMOVED OR ALTERED IN ANY WAY OR THE GUARANTEE WILL NOT BE VALID. GLEDHILL WILL NOT BE RESPONSIBLE FOR ANY CONSEQUENTIAL LOSS OR DAMAGE HOWEVER IT IS CAUSED.
The guarantee for the stainless steel vessel is
for twenty five years against material defect or manufacturing faults if the original unit is returned to
us AND PROVIDED THAT: (i) It has not been modified, other than by Gledhill. (ii) It has not been subjected to wrong or improper
use or left uncared for.
(iii) It has only been used for the storage of potable
water supplied from the public mains, max
200mg/litre chloride. (iv) It has not been subjected to frost damage. (v) The benchmark service record is completed after
each annual service. (vi) The unit has been serviced annually. (vii) Any disinfection has been carried out strictly in
accordance with BS6700.
If the stainless steel vessel proves to be defective
either in materials or workmanship we reserve the right to either repair or supply replacements or the closest possible substitute in the case of any obsolete product and will collect and deliver to any address in England, Scotland and Wales (excluding all islands):
(i) free of charge during the first year after delivery by
us. (ii) thereafter at a charge of one twenty fifth of the
then current list price during the second year
after delivery by us and increasing by a further
one twenty fifth on the second and subsequent
anniversary of delivery by us.
ACTION IN THE EVENT OF FAILURE We will require the return of a cylinder which develops
a leak for inspection. If our examination confirms a failure then an appropriate level of credit against the cost of the original cylinder will be issued in line with the terms of our warranty.
Please note:
- Installation must have been carried out by a
licensed specialized company (heating contractor
or plumber) following the version of installation
instructions in force.
- Gledhill or its representative was given the
opportunity to check complaints on site
immediately after any defect occurred.
- Confirmation exists that the system was
commissioned properly and that the system
was checked and maintenance was performed
annually by a specialised company licensed for
this purpose.
(d) Components of our products other than Storage Vessels and Integral Pipework.
We will either extend to the purchaser the same terms
of warranty as we are given by the manufacturer of the component or if the manufacturer does not give any warranty, replace free of charge any component which becomes defective within two years after the date of the delivery by us and is returned to us at the purchaser’s expense but we shall not meet the cost of removal or shipping or return of the component or any other cost charges or damages incurred by the purchaser.
9.4.
9.4.1. In respect of goods supplied by us and in respect of any installation work carried out by or on our behalf, our entire liability and the purchaser’s sole remedies (subject to the Guarantees) shall be as follows:-
(a) We accept liability for death or personal injury to
the extent that it results from our negligence or that of our employees
Page 33
TERMS AND CONDITIONS
(b) Subject to the other provisions of this clause 9 we accept liability for direct physical damage to tangible
property to the extent that such damage is caused by our negligence or that of our employees, agents or subcontractors.
(c) Our total liability to the purchaser over and above any liability to replace under the Guarantees (whether
in contract or in tort including negligence) in respect of any one cause of loss or damage claimed to result from any breach of our obligations hereunder, shall be limited to actual money damages which shall not exceed £20,000 provided that such monetary limit shall not apply to any liability on the part of ourselves referred to in paragraph (a) above
(d) Except as provided in paragraph (a) above but otherwise not withstanding any provision herein contained
in no event shall we be liable for the following loss or damage howsoever caused and even if foreseeable
by us or in our contemplation:­ (i) economic loss which shall include loss of profits, business revenue, goodwill or anticipated savings (ii) damages in respect of special indirect or consequential loss or damage (other than death, personal
injury and damage to tangible property)
(iii) any claim made against the purchaser by any other party (save as expressly provided in paragraph (b)
above)
(e) Except in respect of our liability referred to in paragraph (a) above no claim may be made or action brought
(whether in contract or in tort including negligence) by the purchaser in respect of any goods supplied by
us more than one year after the date of the invoice for the relevant goods. (f) Without prejudice to any other term we shall not be liable for any water damage caused directly or
indirectly as a result of any leak or other defect in the goods. We cannot control the conditions of use of
the goods or the time or manner or location in which they will be installed and the purchaser agrees to be
fully responsible for testing and checking all works which include the goods at all relevant times (up to,
including and after commissioning) and for taking all necessary steps to identify any leaks and prevent any
damage being caused thereby. (g) Nothing in these Conditions shall confer on the purchaser any rights or remedies to which the purchaser
would not otherwise be legally entitled
10. LOSS OR INJURY
Notwithstanding any other provision contained herein the purchaser’s hereby agree to fully indemnify us against any damages losses costs claims or expenses incurred by us in respect of any claim brought against us by any third party for:­(a) any loss injury or damage wholly or partly caused by any goods supplied by us or their use. (b) any loss injury or damage wholly or partly caused by the defective installation or substandard workmanship or
materials used in the installation of any goods supplied by us. (c) any loss injury or damage in any way connected with the performance of this contract. (d) any loss resulting from any failure by the purchaser to comply with its obligations under these terms as to
install and/or check works correctly. PROVIDED that this paragraph will not require the purchaser to indemnify us against any liability for our own acts of negligence or those of our employees agents or sub-contractors FURTHER in the case of goods supplied by us which are re-sold and installed by a third party by the purchaser it will be the sole responsibility of the purchaser to test the goods immediately after their installation to ensure that inter alia they are correctly installed and in proper working order free from leaks and are not likely to cause any loss injury or damage to any person or property.
11. VARIATION OF WARRANTY AND EXCLUSION
Should our warranty and exclusion be unacceptable we are prepared to negotiate for variation in their terms but only on the basis of an increase in the price to allow for any additional liability or risk which may result from the variation. Purchasers are advised to insure against any risk or liability which they may incur and which is not covered by our warranty.
12. ADVICE
Any advice or assistance given by the Company is provided without charge and is in good faith without undertaking, representation or warranty, and we will not accept any liability, whether consequential or compensatory, for advice or assistance given.
13. RISK AND RETENTION OF TITLE
(a) goods supplied by us shall be at the Purchaser’s risk immediately upon delivery to the Purchaser or into
custody on the Purchaser’s behalf or to the Purchaser’s Order. The Purchaser shall effect adequate insurance
of the goods against all risks to the full invoice value of the goods, such insurance to be effective from the time
of delivery until property in the goods shall pass to the Purchaser as hereinafter provided. (b) property in the goods supplied hereunder will pass to the Purchaser when full payment has been made by the
Purchaser to us for :-
(i) the goods of the subject of this contract. (ii) all other goods the subject to of any other contract between the Purchaser and us which, at the time of
payment of the full price of the goods sold under this contract, have been delivered to the Purchaser but not paid for in full.
(c) until property in the goods supplied hereunder passes to the Purchaser in accordance with paragraph (2)
above.
(i) the Purchaser shall hold the goods in a fiduciary capacity for us and shall store the same separately from
any other goods in the Purchaser’s possession and in a manner which enables them to be identified as our goods.
(ii) the Purchaser shall immediately return the goods to us should our authorised representative so request.
All the necessary incidents associated with a fiduciary relationship shall apply.
(d) the Purchaser’s right to possess the goods shall cease forthwith upon the happening of any of the following
events, namely :-
(i) if the Purchaser fails to make payment in full for the goods within the time stipulated in clause 4 hereof. (ii) if the Purchaser, not being a company, commits any act of bankruptcy, makes a proposal to his or her
creditors for a compromise or does anything which would entitle a petition for a Bankruptcy Order to be presented.
(iii) if the Purchaser, being a company, does anything or fails to do anything which would entitle an
administrator or an administrative receiver or a receiver to take possession of any assets or which would entitle any person to present a petition for winding up or to apply for an administration order.
(e) the Purchaser hereby grants to us an irrevocable licence to enter at any time any vehicle or premises owned
or occupied by the Purchaser or in the possession of the Purchaser for the purposes of repossessing and
recovering any such goods the property in which has remained in us under paragraph (2) above. We shall
not be responsible for and the Purchaser will indemnify us against liability in respect of damage caused to
any vehicle or premises in such repossession and removal being damaged which it was not reasonably practicable to avoid.
(f) notwithstanding paragraph (3) hereof and subject to
paragraph (7) hereof, the Purchaser shall be permitted to sell the goods to third parties in the normal course of business. In this respect the Purchaser shall act in the capacity of our commission agent and the proceeds of such sale :-
(i) shall be held in trust for us in a manner which
enables such proceeds to be identified as such, and:
(ii) shall not be mixed with other monies nor paid into
an overdrawn bank account.
We, as principal, shall remunerate the Purchaser as
commission agent a commission depending upon the surplus which the Purchaser can obtain over and above the sum, stipulated in this contract of supply which will satisfy us.
(g) in the event that the Purchaser shall sell any of the
goods pursuant to clause (6) hereof, the Purchaser shall forthwith inform us in writing of such sale and of the identity and address of the third party to whom the goods have been sold.
(h) if, before property in the goods passes to the
Purchaser under paragraph (2) above the goods are or become affixed to any land or building owned by the Purchaser it is hereby agreed and declared that such affixation shall not have the effect of passing property in the goods to the Purchaser. Furthermore if, before property in the goods shall pass to the Purchaser under paragraph (2) hereof, the goods are or become affixed to any land or building (whether or not owned by the Purchaser), the Purchaser shall:-
(i) ensure that the goods are capable of being removed
without material injury to such land or building.
(ii) take all necessary steps to prevent title to the
goods from passing to the landlord of such land or building.
(iii) forthwith inform us in writing of such affixation and
of the address of the land or building concerned.
The Purchaser warrants to repair and make good
any damage caused by the affixation of the goods to or their removal from any land or building and to indemnify us against all loss damage or liability we may incur or sustain as a result of affixation or removal.
(i) in the event that, before property in the goods
has passed to the Purchaser under paragraph (2) hereof, the goods or any of them are lost, stolen, damaged or destroyed :-
(ii) the Purchaser shall forthwith inform us in writing
of the fact and circumstances of such loss, theft, damage or destruction.
(iii) the Purchaser shall assign to us the benefit of any
insurance claim in respect of the goods so lost, stolen, damaged or destroyed.
14. NON-PAYMENT
If the Purchaser shall fail to make full payment for the goods supplied hereunder within the time stipulated in clause 4 hereof or be in default of payment for any other reason then, without prejudice to any of our other rights hereunder, we shall be entitled to stop all deliveries of goods and materials to the Purchaser, including deliveries or further deliveries of goods under this contract. In addition we shall be entitled to terminate all outstanding orders.
15. VALUE ADDED TAX
All prices quoted are exclusive of Value Added Tax which will be charged at the rate ruling at the date of despatch of invoice.
16. TRADE SALES ONLY
We are only prepared to deal with those who are not consumers within the terms of the Unfair Contract Terms Act 1977, the Sale of Goods Act 1979 and the Supply of Goods and Services Act 1982. Accordingly any person who purchases from us shall be deemed to have represented that he is not a consumer by so purchasing.
17. JURISDICTION
The agreement is subject to English law for products delivered in England and Scottish law for products delivered in Scotland and any dispute hereunder shall be settled in accordance therewith dependent upon the location.
18. PRODUCT DEVELOPMENT
Gledhill have a policy of continuous product development and may introduce product modifications from time to time.
Page 34
BENCHMARK
This Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST
Customer name: Telephone number:
Address:
Cylinder Make and Model
Cylinder Serial Number
Commissioned by (PRINT NAME): Registered Operative ID Number
Company name: Telephone number:
Company address:
Commissioning date:
To be completed by the customer on receipt of a Building Regulations Compliance Certicate*:
Building Regulations Notication Number (if applicable)
ALL SYSTEMS PRIMARY SETTINGS (indirect heating only)
Is the primary circuit a sealed or open vented system? Sealed Open
What is the maximum primary ow temperature? °C
ALL SYSTEMS
What is the incoming static cold water pressure at the inlet to the system? bar
Has a strainer been cleaned of installation debris (if tted)? Yes No
Is the installation in a hard water area (above 200ppm)? Yes No
If yes, has a water scale reducer been tted? Yes No
What type of scale reducer has been tted?
What is the hot water thermostat set temperature? °C
What is the maximum hot water ow rate at set thermostat temperature (measured at high ow outlet)? I/min
Time and temperature controls have been tted in compliance with Part L of the Building Regulations? Yes
Type of control system (if applicable) Y Plan S Plan Other
Is the cylinder solar (or other renewable) compatible? Yes No
What is the hot water temperature at the nearest outlet? °C
All appropriate pipes have been insulated up to 1 metre or the point where they become concealed Yes
UNVENTED SYSTEMS ONLY
Where is the pressure reducing valve situated (if tted)?
What is the pressure reducing valve setting? bar
Has a combined temperature and pressure relief valve and expansion valve been tted and discharge tested? Yes No
The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes
Are all energy sources tted with a cut out device? Yes No
Has the expansion vessel or internal air space been checked? Yes No
THERMAL STORES ONLY
What store temperature is achievable? °C
What is the maximum hot water temperature? °C
ALL INSTALLATIONS
The hot water system complies with the appropriate Building Regulations Yes
The system has been installed and commissioned in accordance with the manufacturer’s instructions Yes
The system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineer’s Signature
Customer’s Signature
(To conrm satisfactory demonstration and receipt of manufacturer’s literature)
This Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturers instructions may invalidate the warranty but does not affect statutory rights.
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST
Customer name: Telephone number:
Address:
Cylinder Make and Model
Cylinder Serial Number
Commissioned by (PRINT NAME): Registered Operative ID Number
Company name: Telephone number:
Company address:
Commissioning date:
To be completed by the customer on receipt of a Building Regulations Compliance Certicate*:
Building Regulations Notication Number (if applicable)
ALL SYSTEMS PRIMARY SETTINGS (indirect heating only)
Is the primary circuit a sealed or open vented system? Sealed Open
What is the maximum primary ow temperature? °C
ALL SYSTEMS
What is the incoming static cold water pressure at the inlet to the system? bar
Has a strainer been cleaned of installation debris (if tted)? Yes No
Is the installation in a hard water area (above 200ppm)? Yes No
If yes, has a water scale reducer been tted? Yes No
What type of scale reducer has been tted?
What is the hot water thermostat set temperature? °C
What is the maximum hot water ow rate at set thermostat temperature (measured at high ow outlet)? I/min
Time and temperature controls have been tted in compliance with Part L of the Building Regulations? Yes
Type of control system (if applicable) Y Plan S Plan Other
Is the cylinder solar (or other renewable) compatible? Yes No
What is the hot water temperature at the nearest outlet? °C
All appropriate pipes have been insulated up to 1 metre or the point where they become concealed Yes
UNVENTED SYSTEMS ONLY
Where is the pressure reducing valve situated (if tted)?
What is the pressure reducing valve setting? bar
Has a combined temperature and pressure relief valve and expansion valve been tted and discharge tested? Yes No
The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes
Are all energy sources tted with a cut out device? Yes No
Has the expansion vessel or internal air space been checked? Yes No
THERMAL STORES ONLY
What store temperature is achievable? °C
What is the maximum hot water temperature? °C
ALL INSTALLATIONS
The hot water system complies with the appropriate Building Regulations Yes
The system has been installed and commissioned in accordance with the manufacturers instructions Yes
The system controls have been demonstrated to and understood by the customer Yes
The manufacturers literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineers Signature
Customers Signature
(To conrm satisfactory demonstration and receipt of manufacturers literature)
* All installations in England and Wales must be notied to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance Certicate will then be issued to the customer.
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
While this Checklist can be used for any installation covered by its description, only appliances manufactured by Scheme Members will be covered by the rules and requirements of the Benchmark Scheme.
Page 35
BENCHMARK
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE RECORD
SERVICE 01
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 03
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 05
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 07
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 09
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 02
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 04
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 06
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 08
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
SERVICE 10
Date:
Engineer name:
Company name:
Telephone No:
Comments:
Signature
Protect your Gledhill product after your initial warranty period
For any spare part requirements on
this product simply scan the
QR code using your smart phone app
or go to www.gledhill-spares.net
On expiry of your initial warranty period, Gledhill Response Limited would be
pleased to provide further customer support with a range of services including:
Low cost annual repair and maintenance contracts direct from Gledhill
Annual servicing and safety checks
Expert response to ‘out of warranty’ breakdowns at fixed charges
Please call 08445 679898 or visit www.gledhill.net for further details
Due to a programme of continuous improvement Gledhill Building Products reserve the right to modify products without prior notice.
It is advisable to check the product technical detail by using the latest design and installation manuals available from our technical support team or on our website.
It is an offence to copy or adapt this document without consent of the owner.
Gledhill Building Products Limited
Sycamore Estate, Squires Gate, Blackpool FY4 3RL Tel: 01253 474550 Fax: 01253 474551 sales@gledhill.net
After Sales Technical Support Tel: 01253 474584
Gledhill Building Products produce cylinders for use with a wide range of heat sources including;
Gas and oil boilers Electricity Air source heat pumps
Ground source heat pumps Solar energy Wood burning stoves
Further information on Gledhill products can be found at www.gledhill.net
“Only the best
is acceptable”
FM 02057
Loading...