gledhill PulsaCoil PCS 120, PulsaCoil PCS 180, PulsaCoil PCS 150, PulsaCoil PCS 220 Design, Installation & Servicing Instructions

Design, Installation & Servicing Instructions
Models covered in this manual
PulsaCoil PCS 120 PulsaCoil PCS 150 PulsaCoil PCS 180 PulsaCoil PCS 220
PulsaCoil Stainless
Hot water cylinder utilising off-peak electric
Page 2
DESIGN
Introduction 3
Technical Data 5
System Details 9
INSTALLATION
Site Requirements 13
Installation 14
Commissioning 18
SERVICING
Annual Service 19
Changing Components 19
Short Parts List 20
Fault Finding 21
ADDENDIX
Addendix A 24
Addendix B 25
Addendix C 26
Notes 27
Terms & Conditions 28
BENCHMARK
Commissioning Checklist 30
Service Record 31
ISSUE 2: JANUARY 2014
The Gledh ill Pul saCoi l range is a WBS li ste d pro duc t an d co mpl ies with the HWA Spec ifi cation for hot w ate r only thermal storage products. The principle was developed in conjunction with British Gas. This product is manufactured under an ISO 9001:2008 Quality System audited by BSI.
Gledhill’s rst priority is to give a high quality service to our customers.
Quality is built into every Gledhill product and we hope you get satisfactory service from Gledhill.
If not please let us know.
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturers instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water Industry Council who manage and promote the Scheme. Visit www. centralheating.co.uk for more information.
Page 3
DESIGN
INTRODUCTION
Any wate r distrib ution system/installation must comp ly with the relevant recommendations of the current version of the Regulations and British Standards listed below:-
Building Regulations Requirements for Electrical Installations Water Regulations Manual Handling Operations Regulations
British Standards
BS EN 806:1-5: BS EN 8558:2011
The Building Regulations (England & Wales) require that the installation of a heating appliance be notied to the relevant Local Authority Building Control Department. From 1st April 2005 this can be achieved via a Competent Person Self Certication Scheme as an option to notifying the Local Authority directly. Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1st January 06.
A suitably competent trades person must install the PulsaCoil and carry out any subsequent maintenance/repairs. In fact the appliance front cover is secured by 2 screws and this should only be removed by a competent trades person. The manufacturer’s notes must not be taken as overriding statutory obligations.
The PulsaCoil Stainless is not covered by section G3 of the current Building Regulations and is therefore only notiable to Building Control as part of the domestic water installations.
The PulsaCoil Stainless is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience or knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
The information in this manual is provided to assist generally in the selection of equipment. The responsibility for the selection and specication of the equipment must however remain that of the customer and any Designers or Consultants concerned with the design and installation.
Please Note: We do not therefore accept any responsibility for matters of design, selection or specication or for the eectiveness of an installation containing one of our products unless we have been specically requested to do so.
All goods are sold subject to our Conditions of Sale, which are set out at the rear of this manual.
In the interest of continuously improving the PulsaCoil range, Gledhill Building Products Ltd reserve the right to modify the product without notice, and in these circumstances this document, which is accurate at the time of printing, should be disregarded. It will however be updated as soon as possible after the change has occurred.
Page 4
The PulsaCoil Stainless shown schematically above is designed to provide an improved method of supplying mains pressure hot water when used with a suitable o peak electric supply/tari.
An important feature of the concept is that hot water can be supplied directly from the mains at conventional ow rates without the need for temperature and pressure relief safety valves or expansion vessels. This is achieved by passing the mains water through a plate heat exchanger. The outlet temperature of the domestic hot water is maintained by a printed circuit control board, which controls the speed of the pump circulating the primary water from the store through the plate heat exchanger.
The Building Regulations L1A: New dwellings/L1B: Existing dwellings and the requirements set out in the Domestic Heating Compliance Guide specify that “where the mains water hardness exceeds 200ppm provision should be made to treat the feed water to water heaters and the hot water circuit of combination boilers to reduce the rate of accumulation of lime scale”.
To comply with this requirement the hardness of the mains water should be checked by the installer and if necessary the optional factory tted in-line scale inhibitor should be specied at the time of order for hardness levels between 200 and 300 ppm (mg/l).
Where the water is very hard ie 300ppm (mg/l) and above the optional polyphosphate type, inhibitor should be specied at the time of order. However, this will need to be tted by the installer at a suitable point in the cold water supply to the appliance.
The printed circuit board incorporates the facility to automatically run the D.H.W. Primary pump for about 3 seconds every 30 hours to help prevent it sticking. For this reason we would recommend that once the appliance is installed it should be commissioned and the electricity left on to the appliance.
Because this product does not require a safety discharge from a temperature and pressure relief valve, any installations will be easy to incorporate into the building and will not suer from the problems associated with using PVCu soil stacks to take the discharge from unvented cylinders.
The heat losses from thermal stores should not be directly compared with heat losses from unvented or vented cylinders because they are treated dierently in SAP. This is because the unvented and vented cylinders are tested at 65°C and the thermal store at 75°C.
Figure 1.1
1. Bottom (Off-Peak) immersion heater (1H_1)
2. Top (On-Peak) immersion heater (IH_2)
3. PHE pump
4. Cold Feed
5. CW inlet
6. HW outlet
7. Drain
8. Return from PHE to store
9. Flow from store to PHE
10. Feed and expansion tank
1
7
2
3
9
5
8
6
4
10
DESIGN
INTRODUCTION
Page 5
Technical Specication PulsaCoil Stainless
Model PCS 120 PCS 150 PCS 180 PCS 220
Height (mm) 1075 1145 1275 1575
Width (mm) 530 560 560 560
Depth (mm) 595 630 630 630
Min cupboard height (mm) 1825 1895 2025 2325
Min cupboard width (mm) 570 600 600 600
Min cupboard depth (mm) 610 645 645 645
Weight (empty) (kg) 40 45 48 55
Weight (full) (kg) 154 192 213 265
Volume of water heated by on-peak heater (litres) 66 80 85 111
Model Selection Guide PulsaCoil Stainless
Dwelling Type
Bedroom 1-2 2-3 2-3 2-4
Bathroom 1 or 1 1 2
En-suite shower rooms 1 1 2 1
Standard Economy-7 tari PCS120 PCS150 PCS180 PCS220
Economy-10 tari PCS120 PCS120 PCS150 PCS180
Notes:-
1. Plastic top up cistern will be supplied separately.
2. The ow rates are based on a 35°C temperature rise and assume that recommended pressures and adequate ow are available at the appliance. The actual ow rate from the appliance is automatically regulated to a maximum of 15 litres/min.
3. Unit is supplied on a 100mm high installation base.
4. The domestic hot water outlet temperature is automatically regulated to approximately 52°C, and the temperature is not user adjustable.
Table 1.2
Table 1.1
DESIGN
TECHNICAL DATA
Page 6
Standard Equipment
The standard configuration of the PulsaCoil Stainless is sh own oppo sit e. The Printed Circuit Control Board (A.C.B.), mounted inside the appliance, controls the production of the domestic hot water. This is pre-wired to a terminal strip where all electrical connections terminate. The installer must t components to control the operation of the immersion heaters. It is supplied with the following factory tted equipment:-
1. 3kW O-Peak immersion heater
2. 3kW On-Peak boost immersion heater
3. Printed Circuit Board
4. Plate heat exchanger
5. Domestic hot water primary (plate heat exchanger) pump
6. DHW temperature sensor
7. Incoming cold water sensor
8. Strainer and ow regulator
9. Screwed connection for a drain tap
10. Top up cistern complete with cold feed/ open vent pipework assembly is supplied separately
11. Store sensor
Note
Both immersion heaters are low watts density type with incaloy 825 sheaths and are specially manufactured to suit thermal stores. It is recommended that any replacements should be obtained from Gledhill Spares.
The immersion heaters are tted with control th erm ost ats and over hea t th erm ost ats . Immersion heaters without these components must not be tted to the unit.
Optional Extra Equipment
In line scale inhibitor for mains water services with hardness levels between 200 and 300ppm (mg/l) tted but ready for wiring by the installer to the suitable 230V ac supply.
• Polyphosphate scale inhibitor for tting on site by the installer.
• Ballvalve/overow connector fortop up
cistern.
Figure 1.2
7
8
4
6
5
11
3
10
2
1
9
DESIGN
TECHNICAL DATA
Page 7
Note: The Appliance dimensions above do not allow for the100mm high installation base.
The following table of minimum cupboard dimensions only allow the minimum space required for the appliance (including the F & E cistern). Any extra space required for shelving etc in the case of airing cupboards etc must be added.
Note: The above dimensions are based on the Appliance and the Top up cistern (tted with a ballvalve) being in the same cupboard. If the
manual ll method is chosen the heights can be reduced by 125mm.
If pipework needs to rise vertically adjacent to the appliance the width/depth will need increasing to accommodate this.
Appliance Dimensions
Model
HeightAWidthBDepth
C
PCS120 1075 530 595
PCS150 1145 560 630
PCS180 1275 560 630
PCS220 1575 560 630
Minimum Cupboard Dimensions
Model
HeightDWidthEDepth
F
PCS120 1825 570 610
PCS150 1895 600 645
PCS180 2025 600 645
PCS220 2325 600 645
B
E
C
PulsaCoil Stainless
Top up cistern
Top up cistern
300 *350A100
D
F
Maintenance
access
Figure 1.3
280
420
*Min maintenance access to comply with the Water Regulations (ballvalve model only)
The minimum
clear opening in
front of the
appliance to be
at least the
same depth as
the appliance.
The cupboard door opening will need to take into account the various sizes of appliances.
DESIGN
TECHNICAL DATA
Page 8
Connection Details/Dimensions For Top Of Unit
Figure 1.4
95
148
156
103
Open Vent (22mm)
Cold Feed (22mm)
Connection Details/Dimensions For Bottom Of Unit
Mains Cold Water Inlet (15mm/22mm)
Hot Water Outlet (18mm/22mm)
70
35
546
558
Plan Of Appliance Connections
The PulsaCoil Stainless units are supplied on an installation base to allow the pipe runs to connect to the appliance from any direction. It is easier if all pipes protrude vertically in the cut out area shown. Compression or push t connections can be used. All pipe positions are approximate and subject to a tolerance of +/- 10mm in any direction. Space will also be required for a 15mm cold water supply and a 22mm warning / overow pipe (if the optional extra ball valve and overow connector have been specified. If a warning/overflow pipe is NOT provided the F&E Cistern should be fill ed from a temp orary hose co nnecti on incorporating a double check valve. This can be from a temporary hose connection supplied from a cold water tap or a permanent cold branch provided adjacent to the Top up Cistern. The temporary connection must be removed once the appliance is lled.
Note: All dimensions are shown in mm and are to the centre line of the pipework.
DESIGN
TECHNICAL DATA
Page 9
Hot and Cold Water System
General
A schematic layout of the hot and cold water services in a typical small dwelling is shown below. PulsaCoil Stainless will operate at mains pressures as low as 1 bar and as high as 5 bar although the recommended range is 2-3 bar dynamic at the appliance. It is also important to check that all other equipment and components in the hot and cold water system are capable of accepting the mains pressure available to the property. If the mains pressure can rise above 5 bar or the maximum working pressure of any item of equipment or component to be tted in the system, a pressure limiting (reducing) valve set to 3 bar will be required.
If you encounter a situation where the water pressure is adequate but ow rates are poor please contact our technical helpline for details of an eective solution.
Note : Each Pulsacoil Stainless is tted with a strainer and ow regulator on the cold mains supply connection. If the supply pressure is less than 2 bar or if all taps are provided with ow regulators the ow regulator on the cold inlet should be removed.
No check valve or similar device should be tted on the cold water supply branch to the PulsaCoil Stainless.
The Building Regulations L1A: New dwellings/L1B: Existing dwellings and the requirements set out in the Domestic Heating Compliance Guide specify that “where the mains water hardness exceeds 200ppm provision should be made to treat the feed water to water heaters and the hot water circuit of combination boilers to reduce the rate of accumulation of lime scale”.
To comply with this requirement the hardness of the mains water should be checked by the installer and if necessary the optional factory tted in-line scale inhibitor should be specied at the time of order for hardness levels between 200 and 300 ppm (mg/l).
Warning/ overflow
pipe
MCWS
Safety/open vent
Shower
Expansion/ cold feed
Second
dwelling
Pressure limiting valve
NOT REQUIRED at
pressures below 5 bar
unless any components
have a lower
maximum working
pressure
Double check valve
NOT REQUIRED unless
pipe supplies more
than one dwelling
‘a’ - flow regulator recommended for better balance of hot and cold water supplies
MCWS supply
pipe
Sink
H C
a a
SV
a a a a
Bath
H C
Hand basin
H C
WC - fitted
with BS1212
ballvalve
C
Figure 1.5
Typical hot and cold water distribution
PULSACOIL
STAINLESS
Check valve
NOT REQUIRED unless
chemical water
treatment unit is fitted
a
Top up cistern
DESIGN
TECHNICAL DATA
Where the water is very hard ie 300ppm (mg/l) and above the optional polyphosphate type, inhibitor should be specified at the time of order. However, this will need to be tted by the installer at a suitable point in the cold water supply to the appliance.
The hot water flow rate from the PulsaCoil Stainless is directly related to the adequacy of the cold water supply to the dwelling. This must be capable of providing for those services, which could be required to be supplied simultaneously, and this maximum demand should be calculated using procedures dened in BS EN 806:1-5: BS EN 8558:2011.
If a water meter is tted in the service pipe, it should have a nominal rating to match the maximum hot and cold water peak demands calculated in accordance with BS EN 806:1-5: BS EN 8558:2011. This could be up to 60ltr/min in some properties.
Note: The diagram below shows the top up cistern with ballvalve and warning/overow pipe which can be supplied as an optional extra if required. However, the standard preferred arrangement is for the cistern to be manually lled from a temporary hose connection tted with a double check valve.
The cistern must not be tted more than 10 metres above the PulsaCoil Stainless appliance itself.
Page 10
Hot and Cold Water System
Pipe Sizing / Materials
To achieve even distribution of the available supply of hot and cold water, it is important in any mains pressure system, that the piping in a dwelling should be sized in accordance with BS EN 806:1-5: BS EN 8558:2011. This is particularly important in a large property with more than one bathroom.
However, the following rule of thumb guide lines should be adequate for most smaller property types as long as water pressures are within the recommended range.
1. A 15mm copper or equivalent external service may be sucient for a small 1 bathroom dwelling (depending upon the ow rate available), but the minimum recommended size for new dwellings is 22mm (25mm MDPE).
2. The internal cold feed from the main incoming stop tap to the PulsaCoil Stainless should be run in 22mm pipe. The cold main and hot draw-o should also be run in 22mm as far as the branch to the bath tap.
3. The nal branches to the hand basins and sinks should be in 10mm and to the baths and showers in 15mm (1 metre minimum).
4. We would recommend that best results for a balanced system are achieved
by tting appropriate ow regulators to each hot and cold outlet. This is particularly relevant where the water pressures are above the recommended water pressure range. Details of suitable ow regulators are provided in Appendix A.
All the recommendations with regard to pipework systems in this manual are generally based on the use of BS/EN Standard copper pipework and ttings.
However, we are happy that plastic pipework systems can be used in place of copper internally as long as the chosen system is recommended for use on domestic hot and cold water systems by the manufacturer and is installed fully in accordance with their recommendations.
This is particularly important in relation to use of push t connections when using the optional exible hose kits - see installation section of this manual.
It is also essential that if an alternative pipework material/system is chosen the manufacturer conrms that the design criteria of the new system is at least equivalent to the use of BS/EN Standard copper pipework and ttings.
Taps/Shower Fittings
Aerated taps are recommended to prevent splashing.
Any type of shower mixing valve can be used as long as both the hot and cold supplies are mains fed. However all mains pressure systems are subject to dynamic changes particularly when other hot and cold taps/showers are opened and closed, which will cause changes in the water temperature at mixed water outlets such as showers. For this reason and because these are now no more expensive than a manual shower we strongly recommend the use of thermostatic showers with this appliance.
The shower head provided must also be suitable for mains pressure supplies.
However, if it is proposed to use a ‘whole body’ or similar shower with a number of high ow/pressure outlets please discuss with the Gledhill technical department.
The hot water supply to a shower-mixing valve should be fed wherever practical directly from the PulsaCoil
Stainless
or be the rst draw-o point on the hot circuit. The cold supply to a shower-mixing valve should wherever practical be fed directly from the rising mains via an independent branch. The shower must incorporate or be
tted with the necessary check valves to provide back-syphonage protection in accordance with the Water Regulations.
The supply of hot and cold mains water directly to a bidet is permitted provided that it is of the over-rim ushing type and that a type ‘A’ air gap is incorporated.
Hot and Cold Water System
If the length of the hot water draw o pipework is excessive and the delivery time will be more than 60 seconds before hot water is available at the tap, you may wish to consider using trace heating to the hot water pipework such as the Raychem HWAT system. Please consult Gledhill Technical Department for further details.
Note: A conventional pumped secondary circulation system is NOT suitable for use with this appliance.
It is important that the cold water pipework is adequately separated/protected from any heating/hot water pipework to ensure that the water remains cold and of drinking water quality.
DESIGN
TECHNICAL DATA
Loading...
+ 22 hidden pages