Glastender Dixell Operation Manual

Page 1
A Family Company Manufacturing
In The USA Since 1969
Dixell
Digital Controller operation
This manual is specic to the operation and diagnostic guides of the Dixell digital controller used in Glastender self-contained back bar coolers.
Dixell
To view the manual specic to the Full Gauge digital controller used in Glastender self-contained back bar coolers visit: http://www.glastender.com/PDF/Full_Gauge_digital_controller_operation.pdf
Full Gauge
Glastender, Inc. · 5400 North Michigan Road · Saginaw, MI · 48604-9780
800.748.0423 · 989.752.4275 · Fax 989.752.4444 · www.glastender.com
© 2017 Glastender, Inc. 11-02-17
Page 2
Dixell Digital Controller operation & DiagnostiC guiDe
The operating temperature range is preset at the factory according to the table below and can be
adjusted up or down within the limits shown.
To see the set point - push and immediately release
the SET button. The set point will be displayed.
To return to normal visualization - Push and
immediately release the SET button or wait ve seconds.
To change the set point - push and hold the SET button for more than two seconds. When the º F display begins ashing, push the up arrow or down
arrow buttons to adjust the set point to the desired
value.
To save the new set point and return to the tem­perature display mode - push and release the SET
button or wait ten seconds.
Factory Settings Range of Adjustment
Standard Cooler Setting
Set Point Operating
Range†
34º F 34º F to 39º F 33º F 65º F
Minimum Set
Point
Maximum Set
Point
Two Zone Cooler Settings*
B = Beer
W = White Wine
R = Red Wine
34º F 34º F to 39º F 33º F 65º F 50º F 50º F to 55º F 33º F 65º F 60º F 60º F to 65º F 33º F 65º F
Adjusting the factory set point will also adjust the operating range by the same amount * To determine a Two Zone Cooler refrigeration conguration, refer to the 2 digits immediately preceding the
rst hyphen of the model number found on the cooler data tag. These 2 digits will always be BW (Beer/ White Wine), BR (Beer/Red Wine), or WR (White Wine/Red Wine). Example: MODEL: BB60BR-L1-
XS(LR).
The refrigerator is programmed to automatically
defrost four times daily for approximately twenty minutes. During defrost, the fan inside the cooler
will remain on and the refrigeration system will
turn off. To initiate defrost manually, push and hold the DEFROST button for more than two seconds.
The thermostat controller does not have an “OFF”
function. To turn refrigerator off, the unit must be
unplugged or power to the electrical branch circuit
has to be turned off via a circuit breaker or switch.
Models BB, ND, LP, FV, MFV, UCR Self Contained Coolers using Dixell digital thermostat controller
The thermostat control probe wire connector may become disconnected when the compressor
compartment cover and/or grill are removed. This will result in thermostat P1 code. While the P1 code is ashing the compressor will cycle 5 minutes on and 5 minutes off and may cause icing of the evaporator coil.
Service calls to reconnect the probe wiring are not
covered by factory warranty.
Probe wire connector
Glastender, Inc. • 5400 North Michigan Road • Saginaw, MI • 48604-9780
800.748.0423 • 989.752.4275 • Fax 989.752.4444 • www.glastender.com
Rev. 11-11-14
Page 3
Warning: Performance and reliability issues that result from the controller parameters being changed from
Table 1
Temp Deg F Temp Deg F Temp Deg F Temp Deg F Temp Deg F
-4 67770 22 34852 42 21596 64 13246 86 8313
-2 64579 23 33900 44 20687 66 12668 88 8008 0 61388 24 33164 46 19778 68 12090 90 7703 2 58197 26 31693 48 18869 70 11626 92 7398 5 53410 28 30222 50 17960 72 11161 94 7093 8 49763 30 28751 52 17233 74 10697 95 6940
10 47332 32 (Ice Water) 27280 54 16507 76 10232 96 6816 12 44901 34 26118 56 15780 77 10000 98 6569 14 42470 36 24956 58 15053 78 9813 100 6322 16 40566 38 23793 59 14690 80 9438 102 6074 18 38661 40 22631 60 14401 82 9063 104 5827
Ohms
Resistance
Ohms
Resistance
Ohms
Resistance
Ohms
Resistance
Ohms
Resistance
the factory default settings are not covered under warranty.
Controller error codes:
P1- Room Probe Failure
Check to make sure the probe is connected to the controller
Check the probe resistance (see “Checking the probe resistance” below)
P2- Evaporator Probe Failure
This error should only occur on MFV units. Verify that the unit is an MFV model.
Check to make sure the probe is connected to the controller
Check the probe resistance (see “Checking the probe resistance” below)
dF- Indicates that the unit is in defrost
Normal Scheduled defrosts can last up to 20 minutes at the factory default values
If abnormal defrosts are suspected see “Resetting the program to factory default settings” below
HA- Maximum Temperature Alarm
The box temperature has exceeded the 75° maximum for more than 30 minutes
See diagnostic flow charts below
LA- Minimum Temperature Alarm
The box temperature has deceeded the 25° minimum (-15° for MFV) for more than 30 minutes
See diagnostic flow charts below
Checking the controller set point:
Press the set button once to display the controller set point. Press again to return to the temp display.
Changing the controller set point:
Hold the SET key for 3 seconds, release, and use the arrow keys to change the set point. The set point can be
changed from 33° to 65° on coolers and 0° to 28° on MFV's
Factory Default set points are as follows: MFV 10°, Beer 34°, White Wine 50°, Red Wine 60°
There is a 5° (8° for MFV) differential between cut in and cut out temps. If the controller set point is 35°
the range will be 35° to 40°. (MFV controller set point 10°, range will be 10° to 18°)
Checking the probe resistance:
Verify the probe resistance is accurate at the box temperature
Use a calibrated thermometer to check the cooler's temperature at the evap inlet where the probe is located
Disconnect the probe from the controller
Use a calibrated Ohm meter to measure the resistance of the probe at the box temperature
The resistance of the probe should match the associated box temperature of the following table
Fill a cup full of ice water (use a lot of ice), put the probe into the ice bath, stir for 1 minute, then measure the
resistance with a calibrated Ohm meter. Make sure to keep the probe in the center of the cup.
The probe should have 27,280 Ohms of resistance in the ice bath. Replace the probe if it is not within 2
degrees Ohms range from Table 1 above.
F-755-028 Rev. E 9/16/16
Page 4
Checking the controller display temperature accuracy:
Label Description
MFV Beer Wht Wi ne Red Wine
Label Description
MFV Beer Wht Wine Red Wine
0-35 34-40 50-55 60- 65 0-35 34-40 50-55 60-65
Regulation Defrost
Hy Differential 8 5 5 5 td Defrost type in
LS Min Set Point 0 33 33 33 dE D efrost Termination Temp 75 50 50 50
US Max Set Point 35 65 65 65 id Inter val Between Defr ost Cycles 4 6 6 6
ot Fi rst Probe Calibration 0 0 0 0 Md Max Length For Defrost 20 20 20 20
P2 Second Probe Presence y n n n dd Start Defrost Delay 0
oE Second Probe Calibration 0 0 0 0 dF Display During Defrost dE dE dE dE
od Delay At Startup 0 0 0 0 dt Drip Time 2
AC Anti-short Cycle Delay 1 1 1 1 dP Defrost at Power On n
Cy Comp On Time Faul ty Probe 5 5 5 5 Alarms
Cn Comp Off Time Faul ty Probe 8 5 5 5 AU Max Temp Alarm 75 75 75 75
Display AL Min Temp Alarm -15 25 25 25
CF Units of Measur e Ad Temp Alarm Delay 30 30 30 30
rE in in in in dA Exclusion Of Temp Alarm At Startup 99 99 99 99
Ld Default Display P1 P1 P1 P1 Other
dy Display Delay 0 0 0 0 tb tb y y y
d1 Thermostat Probe Display
d2 Evap Probe Display nP nP nP
Pt Parameter Code Table 1 5 5 5
rL Firmware Release 1.5 1.5 1.5 1.5
°F °F °F °F
Resolution (For °C Only)
Reads
input
Reads
input
After verifying the probe resistance to the box temperature, plug the probe into the controller and check the
temperature displayed
The controller should display the associated temperature of Table 1 above when compared to the
resistance measured
Note: the probe cannot be plugged into the controller when measuring resistance
Fill a cup full of ice water (use a lot of ice), put the Ohm verified probe into the ice bath, stir for 1 minute.
Make sure to keep the probe in the center of the cup.
The controller should display 32°
Checking the controller compressor relay:
Does the controller relay open and close at the operating range specified on the data tag?
If the controller is calling for cooling, the compressor relay (terminals 8 & 9) will have continuity
Note: there is a 1 minute anti-short cycle delay programmed into the controller. The snowflake will flash on the display indicating this delay. When the snowflake is solid, the controller is calling for cooling and the relay will be closed.
Resetting the program to factory default settings:
Hold the SET and DOWN ARROW for 3-4 seconds until the display changes and release; the display will
either read “rE” or “d2” and the °F symbol will be flashing. Immediately hold the SET and DOWN ARROW for another 7-8 seconds until the display changes to L2, release the buttons and Hy will be displayed; this is the controllers hidden menu where you can set the parameters of the chart below.
Note: The SET and DOWN ARROW must be pressed at the same time. If one is accidentally released, the process will need to be restarted. Note: If no keys are pressed, the hidden menu access will time out after 15 seconds and revert to normal operation.
Use the arrow keys to scroll to the desired set point
Press set to access the value
Use the arrow keys to change the value
Press set again to lock in the value
The chart below represents the factory default settings of MFV, Beer, White and Red Wine controllers Set the values to the associated product for the proper control of the unit
F-755-028 Rev. E 9/16/16
Page 5
Diagnostic flow charts:
Is the box temp cycling at the
HA
LA
Replace the
set point plus the differential? See Checking the controller
See Warm Box
Diagnostic Flow Chart
Is the refrigeration
system running?
Does the probe resistance
match the associated
temperature of Table 1
No Yes
Probe
Set point
No
No
Replace the
Controller
Is the “AU” Set point
programmed for factory default?
YES
See Resetting the program to
factory default settings
See Resetting the program to
factory default settings
Is the box temp cycling at the
YES
set point plus the differential? See Checking the controller
Set point
No
Is the controller relay
stuck closed?
See Checking the
Controller compressor
relay
No
Reprogram
See Resetting the program to
factory default settings
No
Reprogram
Yes
Replace the
YES
Replace the
Controller
Probe
Does the probe resistance
YES
programmed for factory default?
See Resetting the program to
factory default settings
Yes
match the associated
temperature of Table 1?
Replace the
Probe
Is the “AL” Set point
See Resetting the program to
factory default settings
No
Reprogram
Does the probe resistance
match the associated
No
temperature of Table 1?
Replace the
Controller
YesNo
Yes
Warm
Box
Replace the
Is the controller calling for
cooling? A snowflake will
appear on the display
Does the probe resistance
match the associated
temperature of Table 1?
Probe
No
YesNo
Replace the
Controller
Are the
YES
compressor
and all
fans running?
No
Is there continuity
across the controller
compressor relay? See Checking the
No
controller compressor
relay
Check for bad
compressor,
fans, or wiring
YES
Yes
Is the controller set
at the desired set point?
See Checking the
Controller set point
No
Reprogram
See Changing the
controller set point
Is the probe
YES
refrigeration issues
touching the
evaporator?
No
Check for
or air infiltration
Yes
Reposition the
probe
F-755-028 Rev. E 9/16/16
Loading...