This manual is specic to the operation and diagnostic
guides of the Dixell digital controller used in Glastender
self-contained back bar coolers.
Dixell
To view the manual specic to the Full Gauge digital controller used in Glastender
self-contained back bar coolers visit:
http://www.glastender.com/PDF/Full_Gauge_digital_controller_operation.pdf
Full Gauge
Glastender, Inc. · 5400 North Michigan Road · Saginaw, MI · 48604-9780
Dixell Digital Controller operation & DiagnostiC guiDe
The operating temperature range is preset at the
factory according to the table below and can be
adjusted up or down within the limits shown.
To see the set point - push and immediately release
the SET button. The set point will be displayed.
To return to normal visualization - Push and
immediately release the SET button or wait ve
seconds.
To change the set point - push and hold the SET
button for more than two seconds. When the º F
display begins ashing, push the up arrow or down
arrow buttons to adjust the set point to the desired
value.
To save the new set point and return to the temperature display mode - push and release the SET
button or wait ten seconds.
Factory SettingsRange of Adjustment
Standard Cooler Setting
Set PointOperating
Range†
34º F34º F to 39º F33º F65º F
Minimum Set
Point
Maximum Set
Point
Two Zone Cooler Settings*
B = Beer
W = White Wine
R = Red Wine
34º F34º F to 39º F33º F65º F
50º F50º F to 55º F33º F65º F
60º F60º F to 65º F33º F65º F
† Adjusting the factory set point will also adjust the operating range by the same amount
* To determine a Two Zone Cooler refrigeration conguration, refer to the 2 digits immediately preceding the
rst hyphen of the model number found on the cooler data tag. These 2 digits will always be BW (Beer/
White Wine), BR (Beer/Red Wine), or WR (White Wine/Red Wine). Example: MODEL: BB60BR-L1-
XS(LR).
The refrigerator is programmed to automatically
defrost four times daily for approximately twenty
minutes. During defrost, the fan inside the cooler
will remain on and the refrigeration system will
turn off. To initiate defrost manually, push and hold
the DEFROST button for more than two seconds.
The thermostat controller does not have an “OFF”
function. To turn refrigerator off, the unit must be
unplugged or power to the electrical branch circuit
has to be turned off via a circuit breaker or switch.
Models BB, ND, LP, FV, MFV, UCR Self Contained
Coolers using Dixell digital thermostat controller
The thermostat control probe wire connector
may become disconnected when the compressor
compartment cover and/or grill are removed. This
will result in thermostat P1 code. While the P1 code is
ashing the compressor will cycle 5 minutes on and 5
minutes off and may cause icing of the evaporator coil.
Service calls to reconnect the probe wiring are not
covered by factory warranty.
Probe wire
connector
Glastender, Inc. • 5400 North Michigan Road • Saginaw, MI • 48604-9780
the factory default settings are not covered under warranty.
Controller error codes:
➢ P1- Room Probe Failure
•Check to make sure the probe is connected to the controller
•Check the probe resistance (see “Checking the probe resistance” below)
➢ P2- Evaporator Probe Failure
•This error should only occur on MFV units. Verify that the unit is an MFV model.
•Check to make sure the probe is connected to the controller
•Check the probe resistance (see “Checking the probe resistance” below)
➢ dF- Indicates that the unit is in defrost
•Normal Scheduled defrosts can last up to 20 minutes at the factory default values
•If abnormal defrosts are suspected see “Resetting the program to factory default settings” below
➢ HA- Maximum Temperature Alarm
•The box temperature has exceeded the 75° maximum for more than 30 minutes
•See diagnostic flow charts below
➢ LA- Minimum Temperature Alarm
•The box temperature has deceeded the 25° minimum (-15° for MFV) for more than 30 minutes
•See diagnostic flow charts below
Checking the controller set point:
➢Press the set button once to display the controller set point. Press again to return to the temp display.
Changing the controller set point:
➢Hold the SET key for 3 seconds, release, and use the arrow keys to change the set point. The set point can be
changed from 33° to 65° on coolers and 0° to 28° on MFV's
•Factory Default set points are as follows: MFV 10°, Beer 34°, White Wine 50°, Red Wine 60°
•There is a 5° (8° for MFV) differential between cut in and cut out temps. If the controller set point is 35°
the range will be 35° to 40°. (MFV controller set point 10°, range will be 10° to 18°)
Checking the probe resistance:
➢ Verify the probe resistance is accurate at the box temperature
•Use a calibrated thermometer to check the cooler's temperature at the evap inlet where the probe is located
•Disconnect the probe from the controller
•Use a calibrated Ohm meter to measure the resistance of the probe at the box temperature
•The resistance of the probe should match the associated box temperature of the following table
➢ Fill a cup full of ice water (use a lot of ice), put the probe into the ice bath, stir for 1 minute, then measure the
resistance with a calibrated Ohm meter. Make sure to keep the probe in the center of the cup.
•The probe should have 27,280 Ohms of resistance in the ice bath. Replace the probe if it is not within 2
degrees Ohms range from Table 1 above.
F-755-028Rev. E9/16/16
Page 4
Checking the controller display temperature accuracy:
LabelDescription
MFVBeer Wht Wi ne Red Wine
LabelDescription
MFV Beer Wht Wine Red Wine
0-35 34-4050-5560- 650-35 34-4050-5560-65
RegulationDefrost
HyDifferential8555tdDefrost typein
LSMin Set Point0333333dED efrost Termination Temp75505050
USMax Set Point35656565idInter val Between Defr ost Cycles4666
otFi rst Probe Calibration0000MdMax Length For Defrost20202020
P2Second Probe PresenceynnnddStart Defrost Delay0
oESecond Probe Calibration0000dFDisplay During DefrostdEdEdEdE
odDelay At Startup0000dtDrip Time2
ACAnti-short Cycle Delay1111dPDefrost at Power Onn
Cy Comp On Time Faul ty Probe5555Alarms
Cn Comp Off Time Faul ty Probe8555AUMax Temp Alarm75757575
DisplayALMin Temp Alarm-15252525
CFUnits of Measur eAdTemp Alarm Delay30303030
rEinininindA Exclusion Of Temp Alarm At Startup99999999
LdDefault DisplayP1P1P1P1Other
dyDisplay Delay0000tbtbyyy
d1Thermostat Probe Display
d2Evap Probe DisplaynPnPnP
PtParameter Code Table1555
rLFirmware Release1.51.51.51.5
°F°F°F°F
Resolution (For °C Only)
Reads
input
Reads
input
➢After verifying the probe resistance to the box temperature, plug the probe into the controller and check the
temperature displayed
•The controller should display the associated temperature of Table 1 above when compared to the
resistance measured
Note: the probe cannot be plugged into the controller when measuring resistance
➢Fill a cup full of ice water (use a lot of ice), put the Ohm verified probe into the ice bath, stir for 1 minute.
Make sure to keep the probe in the center of the cup.
•The controller should display 32°
Checking the controller compressor relay:
Does the controller relay open and close at the operating range specified on the data tag?
•If the controller is calling for cooling, the compressor relay (terminals 8 & 9) will have continuity
Note: there is a 1 minute anti-short cycle delay programmed into the controller. The snowflake will
flash on the display indicating this delay. When the snowflake is solid, the controller is calling for
cooling and the relay will be closed.
Resetting the program to factory default settings:
➢ Hold the SET and DOWN ARROW for 3-4 seconds until the display changes and release; the display will
either read “rE” or “d2” and the °F symbol will be flashing. Immediately hold the SET and DOWN ARROW
for another 7-8 seconds until the display changes to L2, release the buttons and Hy will be displayed; this is
the controllers hidden menu where you can set the parameters of the chart below.
Note: The SET and DOWN ARROW must be pressed at the same time. If one is accidentally
released, the process will need to be restarted.
Note: If no keys are pressed, the hidden menu access will time out after 15 seconds and revert to
normal operation.
•Use the arrow keys to scroll to the desired set point
•Press set to access the value
•Use the arrow keys to change the value
•Press set again to lock in the value
The chart below represents the factory default settings of MFV, Beer, White and Red Wine controllers
Set the values to the associated product for the proper control of the unit
F-755-028Rev. E9/16/16
Page 5
Diagnostic flow charts:
Is the box temp cycling at the
HA
LA
Replace the
set point plus the differential?
See Checking the controller
See Warm Box
Diagnostic Flow Chart
Is the refrigeration
system running?
Does the probe resistance
match the associated
temperature of Table 1
NoYes
Probe
Set point
No
No
Replace the
Controller
Is the “AU” Set point
programmed for factory default?
YES
See Resetting the program to
factory default settings
See Resetting the program to
factory default settings
Is the box temp cycling at the
YES
set point plus the differential?
See Checking the controller
Set point
No
Is the controller relay
stuck closed?
See Checking the
Controller compressor
relay
No
Reprogram
See Resetting the program to
factory default settings
No
Reprogram
Yes
Replace the
YES
Replace the
Controller
Probe
Does the probe resistance
YES
programmed for factory default?
See Resetting the program to
factory default settings
Yes
match the associated
temperature of Table 1?
Replace the
Probe
Is the “AL” Set point
See Resetting the program to
factory default settings
No
Reprogram
Does the probe resistance
match the associated
No
temperature of Table 1?
Replace the
Controller
YesNo
Yes
Warm
Box
Replace the
Is the controller calling for
cooling? A snowflake will
appear on the display
Does the probe resistance
match the associated
temperature of Table 1?
Probe
No
YesNo
Replace the
Controller
Are the
YES
compressor
and all
fans running?
No
Is there continuity
across the controller
compressor relay?
See Checking the
No
controller compressor
relay
Check for bad
compressor,
fans, or wiring
YES
Yes
Is the controller set
at the desired set point?
See Checking the
Controller set point
No
Reprogram
See Changing the
controller set point
Is the probe
YES
refrigeration issues
touching the
evaporator?
No
Check for
or air infiltration
Yes
Reposition the
probe
F-755-028Rev. E9/16/16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.