GJD D-TECT 50 IP, GJD250 User Manual

PACKAGE CONTENTS
• 1 x D-TECT 50 IP
1 x Drilling template for xing holes
3 x 31.75mm wall plugs
3 x 31.75mm screws
• 2 x Tamper feet
1 x Tamper cup
INTRODUCTION
The D-TECT 50 IP is a highly sophisticated, but user friendly, IP-based motion detection device and alarm trigger that harnesses the power of IP with PoE (Power over Ethernet) connectivity, advanced signal processing, quad pyro scanning and unique optical systems to provide state­of-the-art alarm capture.
MOUNTING THE UNIT WARNING
• NYLON WASHERS PROVIDED MUST BE USED WITH SCREWS
• ENSURE CABLE ENTRY AND SCREW HOLES ARE SEALED WITH WATER BASED SEALANT
• DO NOT USE SILICONE BASED SEALANT
During installation, protect the electronics against water, as trapped moisture can affect or damage the unit.
1. Drill the wall to accept the xing screws, the cable entry, and the tamper cup (if used). See Figures 1 and 2. A hole-drilling template is provided. Note: GJD recommend using the tamper cup on uneven wall surfaces.
2. Remove the cover assembly by loosening the locking screw. The cover hinges from the top and lifts out of the location slot. See Figure 3.
3. Feed standard CAT5 cable into the cable entry. See Figures 2, 4 & 5.
4. Screw the unit to the wall ensuring that the rear tamper pin is correctly located and that the tamper micro switch is closed. See Figure 6. To aid installation, two spare tamper feet are provided. One is 1mm longer and the other is 2mm longer than the tamper foot originally tted. The tamper foot is a push t and can be removed by carefully pulling it from the pin. See Figure 2.
5. When the detector is aligned, connected, and programmed to suit the installation, replace the front cover and lock as shown. See Figure 7.
CONNECTING THE UNIT
Fit the RJ45 plug to the cable and plug into the socket on the top PCB. This must be done before the cable is connected to the PoE switch.
There are 2 volt free relay contacts on the top PCB for connecting auxiliary equipment. These are programmable in the web browser set-up page.
BEAM ALIGNMENT
The PIR circuitry detects changes in heat and movement in the beam pattern; therefore items such as trees, shrubs, ponds, boiler ues, and animals should be considered when positioning the detector.
The detector is tted with a mirror on the pyro sensor to provide a detection zone directly underneath the detector.
Note: The maximum mounting height is 3 metres when utilising the creep detection zone.
When using the pet immune conguration the mirror should be removed.
Note: The PIR sensor is more sensitive to movement across the beams, and less sensitive to movement directly towards or away from the beams.
When coverage exceeds the desired detection area, adjust the module as required to avoid unwanted detection.
Figures 14 and 8 illustrates alignment recommendations for when the detector is mounted close to a wall.
The alignment shown in Figure 14 is not recommended. If the detector module is orientated at an angle of 90° to the perimeter, the mounting wall may cut off short and medium range beams. The long range beam will still detect an intruder, however the wall can cause false alarms when heated by sunlight.
Figure 8 shows the recommended alignment. The detector module is orientated at a 55° angle to the perimeter. As a result, short and medium range beams are parallel to the perimeter, but the detection range along the perimeter is reduced to 25 metres.
PROGRAMMING
There are 2 different ways of programming the detection range, pulse count and LED setting.
1. Using the programming button, programming LED and programming chart below.
2. Via the web based interface. The user can individually program a number of congurable settings, as illustrated in the programming chart.
D-TECT 50 IP
GJD250 IP Motion Detector
Using programming button
Programming Chart
SETTING
1 2 3 4 5
O P T
I O N S
1 RANGE (m) 25 30 40 45 50
2 Pulse Count 1 2
3 LED Off On
To change any of the D-TECT 50 IP settings:
1. Press the program button, as shown in gure 4, for the number of the Option to be changed, i.e. once for range, twice for pulse count, three times for LED.
2. Wait until the blue LED indicator goes off (typically four seconds).
3. The indicator will then ash out the existing settings.
4. To change the settings for that option, press the program button the number of times for the required new setting.
5. The indicator blinks twice and the changes are stored in the D-TECT 50 IP’s non volatile memory.
Example: To change the LED setting from OFF to ON:
1. Press the program button three times.
2. Wait until the blue LED indicator goes off (typically four
seconds).
3. The indicator will then ash once, indicating the current LED setting is OFF.
4. Press the program button twice to change the setting to ON.
5. The indicator blinks twice and the changes are stored in the D-TECT 50 IP ’s non-volatile memory.
PROGRAMMING OPTIONS DEFINITIONS Pulse Count
This is the number of times the unit has to detect on both of its sensors before signalling an output.
LED
LED Off – LED disabled. LED On – LED signals a detection
Relay outputs
Output 1 and output 2 These are magnetically immune volt free relay contacts used to trigger alarm inputs on connected equipment. The contacts are rated at a maximum of 24V AC/DC @ 50mA.
The contact operating timer can be adjusted in the web based user interface.
WALK TEST
In walk test mode, the detection LED option is set to ON, and the pulse count option is set to 1.
1. The detection LED lights each time the D-TECT 50 IP detects your presence
2. To enter the walk test mode, press the programming button once. The detection LED is enabled and pulse count 1 is automatically selected. Alternatively, the walk test mode can be entered via the web based user interface. The unit can then be aligned.
3. The test mode ends automatically ve minutes after the last activation. Alternatively, press the program button three times, to cancel the walk test mode.
Note: When you conduct a walk test, make sure that the front cover is in place. Do not conduct walk tests with the cover removed.
The range of the detector increases without the protective front cover. Therefore the front cover must be tted to establish the correct beam pattern. Use programming chart to adjust the range as necessary. Pan and tilt the lens module over the eld of view to obtain the correct coverage
area.
1 2
3
4 5 6
7
8
9
RJ45
Program
Reset
3m
50m
0m
2.5m
5m
2.5m
5m
77º
29º
21.5º 14º
6.5º
10m
Loading...
+ 7 hidden pages