Gira Powernet Switchactuator 2fold, Powernet Switchactuator 4fold Installation Instructions Manual

GIRA Info
Powernet Switchactuator 2fold/4fold
Installation Instructions
230 V AC~
L
N
50 Hz
23
1
µ
56
4
c
NN L L
A1
A2

System Information

This device is a product of the GIRA-Powernet EIB system and complies with EIBA directives. Detailed technical knowledge obtained in instabus or
GIRA-Powernet
®
EIB training courses is a pre­requisite to proper understanding. The functionality of this device depends upon the software. Detailed information on loadable software and attainable functionality may be taken from the manufacturer’s ETS2 product database as well as from the GIRA-Powernet
®
EIB controller database.
Planning, installation and commissioning of the unit is done by means of the ETS2 software, Ver. 1.1 or later, as well as by the GIRA-Powernet
®
troller.
®
EIB con-
230 V AC~
L
N
50 Hz
23
1
µ
56
4
A2
A1
d

Function

The Switchactuator allows two (or, respectively,
e
four) groups of loads to be switched independent of each other.

Connection

Establish electrical connection as shown in the opposite illustration.
c
NN L L
89
7
A3
µ
11 12
10
A4
d
e
Where: c GIRA-Powernet
®
EIB connection.
d Programming key. e Programming LED
The connection of different external leads to the channels is admissible.

Indications of danger

Caution! The installation and assembly of electrical equipment may be carried out only by a skilled person. Do not connect any loads/types of load other than specified.
Subject to change without notice.
Powernet Switchactuator 2fold/4fold 03/99 Page: 1 of 3
GIRA Info
Powernet Switchactuator 2fold/4fold
Installation Instructions

Technical Data

Supply Mains voltage: 230 V AC (sine wave) Mains frequency: 50 Hz
Power consumption at no-load: ca. 2 VA
Connection Powernet: screw terminals 0,5 - 4 mm², unifilar 0,5 - 2,5 mm² finewire 0,5 - 2,5 mm² finewire with core end bush Load circuit: Plug terminals 0,5 - 2,5 mm², unifilar 0,5 - 2,5 mm² finewire with pin cable socket 0,5 - 1,5 mm² finewire with core end bush
max. Switching power incandescent lamps: 1000 W HV halogen: 1000 W NV halogen (depending on ballast): 200 to 500 VA Fluorescent lamps non-compensated: 500 W dual circuit: 1000 W parallel compensated (C 14µF): 2 x 58 W / 3 x 36 W / 6 x 18 W
Terminal current: 10 A Ambient temperature: -5 °C to +45 °C Type of protection: IP 20
Switchactuator 2fold
Build-in width: 45 mm (2,5 PU) Weight: 185 g
Switchactuator 4fold
Build-in width: 63 mm (3,5 PU) Weight: 250 g
Powernet Switchactuator 2fold/4fold 03/99 Page: 2 of 3