Installation instructions
GB
Gira G1 temperature sensor module
2091 00
Device description
The Gira G1 temperature sensor module is an
additional device for the Gira G1. It serves to
measure the room temperature. The Gira G1
temperature sensor module is only suitable
for use indoors.
Inserting temperature sensor module
Gira
Giersiepen GmbH & Co. KG
Electrical installation
Systems
P.O. Box 1220
42461 Radevormwald
Tel +49 (0) 21 95 - 602 - 0
Fax +49 (0) 21 95 - 602 - 191
www.gira.de
info@gira.de
Security instructions
Fig. 1: Structure of Gira G1 temperature sen-
sor module
(1) Holding frame of Gira G1
(2) 6-pole spring contact
(3) Measuring element
Mounting the module
Selecting installation site
43/17 10 86 19 80
At an incorrectly selected installation site, the
Gira G1 temperature sensor module will
measure the room temperature incorrectly.
- Avoid an installation site that has a draught
(e. g. between a window and a door).
- Avoid direct proximity with heaters and
windows.
- Never cover the Gira G1 temperature sensor module (e.g. curtain).
Unlocking and opening the Gira G1
Fig. 4: Inserting temperature sensor module
4 Remove blind plug to the left under the
holding frame.
5 Attach temperature sensor module with
the 6-pole spring contact at the former
position of the blind plug in the holding
frame. The 6-pole spring contact must be
visible in the process.
Swivelling in the Display module
Electrical devices may only be
installed by a qualified electrician.
Temperature detection via the
temperature sensor module is
only supported in the Gira G1
from index status I09.
Fig. 2: Unlocking Display module
1 Guide unlocking tool or thin screwdriver
into the unlocking opening (4) using slight
pressure.
The Display module is unlocked.
Fig.3: Removing Display module
2 Pull Display module forward on the top
side using force (5).
3 Remove Gira G1 (6).
Fig. 5: Swivelling in the Display module
6 Insert Display module in the guide element
of the holding frame (7).
7 Swivel Display module above (8).
The Display module engages with the
snap-in points and the holding frame.
The Gira G1 has not correctly
engaged until the latch in the
unlocking opening has fallen
back into its end position.

Calibrate sensor
Preparation
- The "Internal sensor" setting must be activated in the ETS for the parameter "Sensor
selection".
- The Gira G1 temperature sensor module
must rest for at least 60 minutes after the
voltage has been activated before the calibration can be carried out.
- The room in which the Gira G1 temperature
sensor modulel is installed must have no
draught or temperature fluctuations during
this time.
- Now measure the room temperature with a
precise thermometer at a distance of at
least 20 cm from the wall.
Execution
Fig. 8: [Calibrate sensor] view
4 Enter the measured room temperature
(10).
5Touch [ok] (11).
The [System] view is opened.
The Gira G1 then progressively adjusts the
measured value.
This process may take up to 20 minutes. No
specific message is displayed when the
calibration is complete. Please do not carry
out any further calibrations during the 20minute waiting time as this can cause
problems.
Fig. 6: Opening view [system menu]
1Touch the [System menu] button (9) in
the Gira G1.
The [System menu] view is opened.
2Touch [System].
The [System] view is opened.
Technical data
Protection class: IP 20
Dimensions
(WxHxD): 44x11x6mm
Measuring accuracy: ± 0.5 K
Ambient
temperature: 0 °C to +45 °C
Storage and transport temperature: –20 °C to +70 °C
Relative humidity: max. 95 % R. H.,
no condensation
Warranty
The warranty is provided in accordance with
statutory requirements via the retailer.
Please submit or send faulty devices postage
paid and with an error description to your
sales representative (retailer / installation
company / electrical contractor).
They will forward the devices to the Gira Service Centre.
Fig. 7: View [System]
3Touch [Calibrate sensor].
The [Calibrate sensor] view is opened.