Wireless diagnostic unit
Wireless diagnostic unit
Order No. : 5304 00
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Keep button cells out of reach of children! If button cells are swallowed, get medical help
immediately.
Risk of explosion! Do not throw batteries into fire.
Risk of explosion! Do not recharge batteries.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1: Front view
(1) LED display
(2) Button field
3 Function
Intended use
- Indication of the radio signal quality in eNet installations
- Indication of third-party radio in the area of an eNet installation
- Switch-on, switch-off of the repeater function of suitable eNet devices
i Only with eNet Server Software up to version 1.4
i This device is unsuitable for testing the radio signal quality of the eNet server, as it cannot
detect all the telegrams of the eNet server.
i In systems with an eNet servers, we recommend checking the radio signal quality of the
eNet installations with the eNet server.
32587112 29.03.2017
10865125
1/5

Wireless diagnostic unit
Product characteristics
- Indication of the signal quality of a selected eNet device using LEDs
- Display of the signal quality of status messages using LEDs
- Indication of radio signals of non-eNet radio transmitters in the 868.3 MHz frequency band
using LEDs
- Switch-on, switch-off of the repeater functions of network-operated actuators, transmitters
and energy sensors
- Battery-powered device
- Devices switches off after 5 minutes without actuation.
4 Information for electrically skilled persons
4.1 Operation
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before working on energised devices, cover up live parts in the working
environment.
Indication of the signal quality of a selected eNet radio transmitter, actuator or sensor
In this operating mode, only the eNet telegrams of a selected device are evaluated. In the case
of multichannel devices, the telegrams of all the channels are evaluated.
i During the selection of a device or the diagnostics, switch off any available eNet servers.
o Press the On button of Channel 1.
LED (1) turns red if no telegrams of a previously selected eNet device are received. The
operating mode eNet Send is switched on.
o Press the On button of Channel 1 for longer than 4 seconds.
LED (1) flashes red, selection mode is switched on.
o On the radio transmitter/sensor, trigger a telegram,
or
o press the Prog button on the actuator/energy sensor.
During radio reception, LED (1) turns green.
LED (1) turns red. The eNet device is selected.
i Only one eNet device can ever be selected. The selection remains intact when the
diagnostics device is switched off. A newly selected device replaces the previous device.
o Trigger additional telegrams on the selected eNet device.
LED (1) of the diagnostics device displays the signal quality of the received telegrams for
approx. 3 seconds. Then the LED (1) turns red again.
i The display of the LEDs is updated on each newly-received telegram. A varying signal
quality can cause the LEDs to flicker.
LED turns green Signal quality is sufficient for a secure
connection.
LED turns alternately green and red Signal quality is borderline for a secure
connection.
LED turns red Signal quality is not sufficient for a secure
connection or there is no reception.
Indication of the signal quality of eNet radio transmitters, actuators or sensors
In this operating mode, all the eNet telegrams are evaluated except for those of the device
selected under eNet Send.
i During the diagnostics, switch off any available eNet servers.
32587112 10865125 29.03.2017